Home

TAC 200 OTP User`s manual

image

Contents

1. tace TAC 200 OTP Heating controller with outdoor reset OFL 3563 000 User s Manual Mounting Controller TAC 200 OTP TAC 200 OTP is encased in a plastic enclosure with a transparent cover The controller can be mounted in three ways either directly on the wall on a DIN rail or in a panel There are cable inlet holes on three sides The controller is attached to the base and should be removed as in figure 1 Mount the base plate in an easily accessible position where the display is clearly legible Connect the wires according to the wiring diagram Screw the controller back onto the base plate There are holes in the base plate for mounting the controller directly onto the wall if preferred To mount the controller on a DIN rail see figure 2 place the controller on the upper edge of the rail and press it inwards to snap it into place To remove it again place a screw driver in the red piece of plastic on the lower part of the controller pull downwards and then pull the controller upwards from the rail To mount the controller in a panel the space needs to be 138x92 mm Place the controller in the panel and turn the small plastic hooks in the controller s screw holes to secure it Outdoor sensor EGU Mount the sensor on an external wall facing north or north west The sensor should be placed about 3 m above ground level and the cable inlet should face downwards Supply sensor EGWS EGA The immersion sensor
2. EGWS is mounted in the riser pipe some 0 5 1 m downstream of the mixing valve If an EGA strap on sensor is used it should be mounted on an un insulated part of the pipe Clean the pipe thoroughly so that the copper contact plate of the sensor makes good contact with the pipe Room sensor EGRL To achieve the best performance the following should be taken into consideration when mounting the room sensor e The sensor should be installed in a room which is typical of the building e The sensor should be placed on an inner wall of light building material The wall must not beheated by for example uninsulated heating pipes behind it e The room should be of sufficient size for the temperature not to be adversely affected by people or machinery e The radiators in the room should not have thermostat valves If they have they should be turned to the largest value possible e The room sensor should be placed so that the air can flow freely around it e The room sensor should be placed within 10 m from the nearest radiator but not right above it Actuator M44 M5 M15 M42 Mounting instructions are supplied with the actuator mounting kit OFL 3563 000 2000 01 Base plate TAC 2000TP Cover es AT p D de a Aa D Figure 1 Figure 2 Wiring Connect the cables to the controller according to the wiring diagram see figure 3 on
3. ced night operation the controller provides night temperature all the time In the same way the controller provides day temperature all the time during forced day operation During automatic operation the controller provides day and night temperature according to the programmed settings To change the operating mode 1 Press P or P until P 00 Operating mode is displayed if it is not already shown 2 Press D or El until the desired symbol is activated If forced day or night operation has been activated from outside the controller Extended day night operation see the handbook the corresponding symbol flashes Externally forced operation X1 X2 has a higher priority than any locally forced operation To access other functions Normally it is sufficient to use P 00 P 15 and for this reason the display scrolls through P 15 P 00 or vice versa To access functions P 16 and higher 1 Simultaneously press P and P to get to P 16 2 Press P or P to step up or down within the new interval To return to P 00 P 15 either press P and P simultaneously or wait for approximately two minutes for the controller to return to P 00 automatically Depending on the specific configuration certain non relevant functions may be missing Power failure The controller maintains the settings for at least twelve hours during a power failure The clock keeps running and when the power returns the controll
4. e 1 Press P or P until P 09 Time program 1 7 days is displayed 2 Press D or El until the first day to be removed flashes 3 Press oa The marked day disappears Remove all the days for which the change should not apply in the same way Make sure that the days to which the changes apply are visible on the display 5 The flashing weekday indication will automatically skip to the segments of 30 minutes when passing either Sunday or Monday in reverse direction 6 When day setpoint is required mark the segments in the same way as above 7 Press P or P to save the changes 8 To set other times for other days return to P 09 and repeat steps 2 7 for these days Note Take care as this operation changes several days at the same time To change operating mode The temperature of the building can be lowered for a longer period of time e g if it is empty during a holiday or if the day temperature is required for a couple of hours extra one night without changing the TAC 200 OTP program The controller can also provide day or night temperature all the time or be turned off without losing the settings It is possible to toggle between the following operating modes on the operator s panel C Forced off Forced night operation i97 Automatic operation control by the time program X Forced day operation During forced off the controller is turned off without loosing the settings During for
5. er continues to control the system as if nothing had happened Should the power failure last longer than twelve hours the time date and year will require re setting Restart If the controller has stopped working it may need to be restarted To do this switch DIP switch 8 behind the brief instruction on the front of the controller to on and then back to off All the settings remain in the controller To restart the controller and regain the factory settings 1 Press P and P to reach P 16 2 Press P or P until P 54 is shown on the display 3 Press Accessories TAC 200 OTP Handbook part number 0 004 1400 TAC AB Jagershillgatan 18 SE 213 75 MALMO SWEDEN 46 40 38 68 50 vx 4 4 English OFL 3563 000 2000 01
6. nt time e g 09 45 Keeping the button depressed increases the stepping speed 3 Press P so that P 14 Day Month is displayed 4 Press D or El until the controller shows current date e g 29 11 5 Press P so that P 15 Year is displayed 6 Press D or until the controller shows current year e g 1994 7 Press P so that P 00 Time is displayed The time value is now stored If P or P is not pressed as the last step any changes will not be stored applies to all entries In this case the display will automatically revert to P 00 in about two minutes Note TAC 200 OTP automatically switches to and from daylight saving time even in leap years The dates for change over can be set manually if desired Current tem peratures 1 Press P or P to display P 01 P 02 P 03 or P 04 Function displays current P 01 room temperature if a room sensor is installed P 02 outdoor temperature P 03 supply water temperature P 04 supply water temperature setpoint 2 The current value is continually updated but after about two minutes the display reverts to P 00 Time Operating mode Setting temperature setpoint 1 Press p or P to display P 05 P 06 or P 07 Function displays P 05 room temperature setpoint C with room sensor P 06 night setback C with room sensor P 07 parallel shift of reset curve C without room sensor 2 Press D or El until the display shows de
7. sired value Keeping the button depressed increases the stepping speed 3 Store changes by pressing P or P at least once OFL 3563 000 2000 01 Setting time program The digital clock has a time program which is used for switching between day and night temperature All times can be set individually for every day of the week with a resolution of 30 minutes The segments each is 30 minutes long on the 0 24 scale show when day and night temperature are used starting with Monday MO displayed A black segment denotes day temperature setpoint and a white one night 1 Press P or P until P 08 Time program day by day is displayed 2 Press D or d until you reach the segment you want to change The segment flashes 3 Press oa The colour of the segment changes and the flashing skips to the next segment 4 If you press and you are at the last segment the display changes to the following day If you are in the first segment and press El the display changes to the previous day 5 Mark all the segments of all day and night periods as desired 6 Use the same procedure to mark the segments for each day of the week 7 Store the changes by pressing P or P at least once If the same pattern for day night setpoint is required for several days either repeat the above or for speed use P 09 Time program 1 7 days The days of the week and the 0 24 segments can then be changed in the same procedur
8. talled room sensor 4 7 no function 8 hardware reset when switched 0 1 0 Switches 4 8 should be in the off position 3 Switch on power 4 Set current time and date see the next page 5 Put the brief instruction back in its place TAC 200 OTP will now control using the factory settings To set values other than those set at the factory refer to the TAC 200 OTP Handbook part number 0 004 1400 Brief instruction Display TAC 200 Z DIP switches Buttons Figure 4 Factory setting 1 8 1000 000 Figure 5 Operator s panel P nn in the display indicates the current function used see figure 6 P 00 for example means time of day and operating mode P P Use these buttons to move up and down the list Bic Use these buttons to increase or decrease the value shown on the display Keep either of them depressed to increase the stepping speed Use this button to change between day and night in segments of 30 minutes To save alterations press P or P again Failure to carry out this step will result in the changes not being saved and the controller reverting to the old value in approximately two minutes 7 8 9 10 11 12 13 14 15 16 17 MO TU WE TH FR SA SU P 00 12 34 i IHI VA Figure 6 OFL 3563 000 2000 01 Setting time and date 1 Press P or P until P 13 Set time is displayed 2 Press either D or d until the controller shows curre
9. the next page The wires from the controller are connected between inputs 1 and 2 on the room sensor Length of cables To terminals B1 B3 and X1 X3 Max 200 m area 0 5 mm To other terminals Max 100 m area 1 5 mm oe 7 1L ANg 230 V N E Supply temp sensor E O r Room sensor Forced day op Forced night op 230 V L 230 V N Terminal board connections 1 230 V L Mains phase live 2 230 V N Mains neutral 3 PE Protective earth 4 KC1 Power supply relays K1 and K2 5 K1 Relay K1 increase stage 1 6 K2 Relay K2 decrease stage 2 7 KC2 Power supply relays K3 and K4 8 K3 Relay K3 circulating pump 9 K4 Relay K4 boiler 10 M Measurement neutral 11 B1 Supply sensor EGWS EGA 12 B2 Outdoor sensor EGU 13 B3 Room sensor EGRL 14 M Measurement neutral 15 X1 Input forced day operation 16 X2 Input forced night operation 17 X3 Not in use 18 M Measurement neutral Figure 3 Commissioning After the controller has been mounted and the electrical wiring is completed the following checks should be carried out and the settings entered before operation of the installation 1 Check that sensors and actuators are correctly wired 2 Set the switches on the DIP switches on the circuit board located under the brief instruction as required see figure 4 and 5 Switch Position off 0 Position on l 1 on off control mixing valve 2 radiator system floor heating 3 no room sensor ins

Download Pdf Manuals

image

Related Search

Related Contents

Register and win! - MHD  Philips TT2030 Bodygroom+ Total body grooming system  LVP-XD280 LVP    Evaluación de la producción de carne de ganado criollo patagónico  Ewent EW7004 floppy drive  

Copyright © All rights reserved.
Failed to retrieve file