1. p ee MSI Elektronik Drager Instruction Manual Dual BCl SIEMENS MSI Elektronik GmbH A company of the Drager Group RohrstraBe 32 58093 Hagen Phone Germany 2331 9584 0 Fax Germany 2331 9584 29 e mail info msi elektronik de D 896 Date 2004 12 15 Instruction Manual Dual BCl Contents 1 Hints 2 Data Transfer from Digital Burner Controllers of Satronic 2 1 Satronic Oil Burner Controllers 2 1 1 Start function 2 1 2 Status information 2 1 3 Data Transfer Error 2 2 Satronic Gas Burner Controllers 2 2 1 Start function 2 2 2 Status information 2 2 3 Data Transfer Error 3 Data Transfer from Digital Burner Controllers of Siemens 3 1 Siemens Oil Burner Controllers 1 Start function 3 1 3 1 2 Status information 3 1 3 Data Transfer Error 3 2 Siemens Gas Burner Controllers 3 2 1 Data Transfer 3 2 2 Data Transfer Error 4 Printing 5 Store Data D896 1 of 15 Page 2 Page 2 Page 2 Page 4 Page 5 Page 6 Page 7 Page 8 Page 9 Page 10 Page 11 Page 12 Page 13 Page 14 Edition 2004 12 15 Instruction Manual Dual BCl 1 Hints Any use of a MSI 150 which contents the Option Data Transfer from Digital Burner Controllers requires a full understanding and strict adherence to the in structions of this manual and the manuals of the Burner Controller and the used MSI 150 All MSI 150 which content the Option Data Transfer from Digital Burner Control lers are able to
2. Connect the plug of the BC Interface with the RS 232 interface of the MSI 150 and put the sensor head over the lighted switch of the burner controller Switch on the MSI 150 choose the fuel type selection and then by pushing the menu Functions With A set the mark gt to Burner controller and start the function with F The display now reads Burner Controller searching cancel With cancel you may stop the searching and the menu Functions is shown again Are all data transferred the display reads Burner control ler Satlronic DATA OK and after a few seconds DEG 372 Mod 63 236 Went E Ianit H i E Mu E Flame E Cont The rectangles mean that the function is active The data will be continuously re freshed The displayed functions are Vent Ventilation on Ignit Ignition on MV1 magnetic valve 1 on MV2 magnetic valve 2 on Flame Flame on Edition 2004 12 15 6 of 15 D896 Instruction Manual Dual BCl 2 2 2 Status Information After the start function is finished the display reads DEG 972 Mod 03 23a Went H Ianit H i E HJ gt E Flame E Cont After pushing F Cont the display shows Ionization 1 2 uA Woltase 276 WM Rest TS 2x7 5S Status oFerate Cont Hold If an error occurs you see instead of the measured values bars and the status changes from operate to Failure Pushing Hold locks all measured values or unlocks them again Lo
3. diagnostic 9 old software and General error 3 2 2 Data Transfer Error If the connection between burner controller and MSI 150 is disturbed the display will read Data transfer LMG Data transfer error Cancel By pushing the button Cancel you may call the menu Functions again After the connection is repaired new mounting of the sensor head for example the data Transfer see 3 2 1 starts again automatically 4 Printing If the menu Printing has been called the display reads Print HO VES by pushing YES the print out may be started and the display will read Printing Cancel After pushing F NO and after the print out is finished or cancelled the menu Store Data see 5 is called D896 13 of 15 Edition 2004 12 15 Instruction Manual Dual BCl 5 Store Data If the menu Store Data has been called the display reads Store NO YES With pushing the button F NO you may call the menu Functions With pushing YES you may start the data transfer If the plug of the BC Interface is still connected with the instruments RS 232 interface then the display will read Please first disconnect BC Interface Cont Cancel Pushing Cancel leads back to the menu Functions After pushing the button F Cont the selection of the customer can be done See Instruction Manual of your MSI 150 the display reads example New3 gt Miller Michael 12340
4. read out the digital burner controllers of Siemens Landis amp Staefa and Satronic The data which are given by the digital burner controllers differ depending of the manufacturer and of the fuel type Therefore the description of the data transfer in this manual is separated for each type of burner controller The MSI 150 Pro2 and MSI 150 Euro recognize the type of digital burner control ler All needed adjustments will be done automatically All shown displayed data are only examples 2 Data Transfer from Digital Burner Controllers of Satronic The digital burner controllers of Satronic are always sending data which can be received by the MSI 150 It does not matter if the burner is working normal if he is starting or if he has stopped because an error occurred 2 1 Satronic Oil Burner Controllers 2 1 1 Start function Connect the plug of the BC Interface with the RS 232 interface of the MSI 150 and put the sensor head over the lighted switch of the burner controller Switch on the MSI 150 choose the fuel type selection and then by pushing the menu Functions With A set the mark gt to Burner controller and start the function with F Edition 2004 12 15 2 of 15 D896 Instruction Manual Dual BCl The display reads Burner Controller searchina cancel And if the burner controller is recognized Burner controller Satronic Please wait Cancel With cancel you may stop the sea
5. tics will be shown Edition 2004 12 15 4 of 15 D896 Instruction Manual Dual BCl The display reads for instance Errors total 43 Failure liaht Starts Reset 178 Starts Disturb J Following errors may be displayed No Flame no flame signal after ignition Straylight flame signal before ignition LW stay open air guard open after ventilator start LW open air guard open before ventilator start LW closed air guard close after fan stop FI signal flame signal after operation stop Loss Flame no flame signal during operation Manual Stop manual Reset of the burner controller System Error electronic error unknown unknown error Pushing the button locks all measured values or unlocks them again Locked values are marked by a rectangle and may be printed and or stored By pushing the button F you may call the menu Printing see 4 if values are locked in other case the menu Functions is called again 2 1 3 Data Transfer Error If the connection between burner controller and MSI 150 is disturbed the display will read Burner controller Satronic Error Cancel By pushing the button Cancel you may call the menu Function again After the connection is repaired new mounting of the sensor head for example the start function see 2 1 1 is done again automatically D896 5 of 15 Edition 2004 12 15 Instruction Manual Dual BCl 2 2 Satronic Gas Burner Controllers 2 2 1 Start Function
6. 07 new record Cont AA For marked customers a data record is already stored With A aa or vw you may place the mark to the wanted cus tomer If you are using a scanner you may read now the barcode label by pushing the scanners key A beep and the lighting of the LED quit the scanners correct func tion The assigned customer name if stored will be displayed marked by gt Edition 2004 12 15 14 of 15 D896 Instruction Manual Dual BCl With pushing F Cont the marked customer is accepted Now the display reads 002 Miller Michael Boiler Nr 1 BCD Back Cancel Store The first line shows the customer number the second the customer name The third line contents the number of the boiler If for this customer a data record is already stored this is shown by and the type of data record A and or B C D If A follows a data record regarding the Data Transfer from Digital Burner Controllers is already stored Pushing F back leads back to the selection of customer With A cancel the data storing is cancelled and the menu Functions is shown With pushing Store the data record is stored and the menu Functions is shown Is the type of data record already stored then the display reads Data record filled overwrite NO With F NO the customer selection is called again without data storing With pushing YES the existing data record is over
7. cked val ues are marked by a rectangle and may be printed and or stored With F Cont you change to the error statistics Starts total 345 Error statistics Last error gt Ho Flame Prior error Failure light Pushing locks all measured values or unlocks them again Locked values are marked by a rectangle and can be printed and or stored With A you may scroll the displayed values and new elements of the error statis tics will be shown D896 7 of 15 Edition 2004 12 15 Instruction Manual Dual BCl The display reads for instance Errors total Failure lisht Starts Reset Starts Disturb Following errors may be displayed No Flame no flame signal after ignition Straylight flame signal before ignition LW stay open air guard open after ventilator start LW open air guard open before ventilator start LW closed air guard close after fan stop Fl signal flame signal after operation stop Loss Flame no flame signal during operation Manual Stop manual Reset of the burner controller System Error electronic error unknown unknown error Pushing the button locks all measured values or unlocks them again Locked values are marked by a rectangle and can be printed and or stored By pushing the button F you may call the menu Printing see 4 if values are locked in other case the menu Functions is called again 2 2 3 Data Transfer Error If the connection between burner controlle
8. er in the interface diagnosis mode connect the plug of the BC Interface with the RS 232 interface of the MSI 150 and put the sensor head over the lighted switch of the burner controller Switch on the MSI 150 choose the fuel type selection and then by pushing the menu Functions With A set the mark gt to Burner controller and start the function with F now the display reads Burner Controller searching cancel With cancel you may stop the searching and the menu Functions is shown again If the burner controller is recognized the display reads Burner Controler LMG Please wait Cancel With cancel you may stop the searching and the menu Functions is shown again In other case a short time later the display will read Burner Controler LMG Series LMG 21 236 O Start count 174 D 3 Loss flame H Cont Hold In the 4 line the actual error is displayed Pushing the button Hold locks all measured values or unlocks them again Locked values are marked by a rectangle and can be printed and or stored By pushing the button F Cont you call the menu Printing see 4 if values are locked in other case the menu Functions is called again Edition 2004 12 15 12 of 15 D896 Instruction Manual Dual BCl Following errors may be displayed 1 Straylight 2 No flame 3 Loss flame 4 4 No flame 5 LP not closed air guard 6 LP opened 7 Starting inhibit 8 No
9. head over the lighted switch of the Burner Controller Switch on the MSI 150 choose the fuel type selection and then by pushing the menu Functions With A set the mark gt to Burner controller and start the function with F now the display reads Burner Controller searching With cancel you may stop the searching and the menu functions is shown again Are all data transferred the display reads Data transfer LMO Load table Please wait Cancel D896 9 of 15 Edition 2004 12 15 Instruction Manual Dual BCl And a short time later Ther moll Went E Ianit Bl 1 E Flame E Bl 2 Cont The displayed functions are Vent ventilation on Ignit ignition on BV1 fuel valve 1 on BV2 fuel valve 2 on Flame flame on The rectangles mean that the function is active All data will be continuously re freshed By pushing F Cont you call further status information 3 1 2 Status Information After choosing further status information the display reads example Fotocurr 44 uA O Woltlagse z225 M D Flamestab 1 2 s I The displayed measuring value Fotocurr means current of the photo sensor Pushing the button locks all measured values or unlocks them again Locked values are marked by a rectangle and may be printed and or stored With pushing the button F you choose the displaying of the error statistics The display reads example Current error Ho flame Start coun
10. r and MSI 150 is disturbed the display will read Burner controller satroanic Error Cancel By pushing the button Cancel you may call the menu Functions again After the connection is repaired new mounting of the sensor head for example the start function see 2 2 1 is done automatically Edition 2004 12 15 8 of 15 D896 Instruction Manual Dual BCl 3 Data Transfer from Digital Burner Controllers of Siemens 3 1 Siemens Oil Burner Controller Before data can be transferred the burner controller has to be set to interface di agnosis mode see user manual burner burner controller If the burner is shut off the light in the burner controller switch is off you may set the burner controller to interface diagnosis mode by pressing the burner controller button for more than 3 seconds The red light in the switch is now flickering Shows the burner controller an error the light in the burner controller is red you may set the burner controller to visual diagnosis mode by pressing the burner con troller button for more than 3 seconds The red light in the switch is now blinking red Now press the button for more than 3 seconds again This will set the burner controller into interface diagnosis mode the red light in the switch is now flickering 3 1 1 Start Function Is the burner controller in the interface diagnosis mode connect the plug of the BC Interface with the RS 232 interface of the MSI 150 and put the sensor
11. rching and the menu Functions is shown again Are all data transferred the display reads Burner controller Satronic DATA OK Cancel and after a few seconds DEO 976 Mod 85 23a Went E Ianit H i E HU 2 E Flame E Cont The rectangles mean that the function is active The data will be continuously re freshed The displayed functions are Vent Ventilation on Ignit Ignition on MV1 magnetic valve 1 on MV2 magnetic valve 2 on Flame Flame on D896 3 of 15 Edition 2004 12 15 Instruction Manual Dual BCl 2 1 2 Status Information After the start function is finished the display reads DEO 976 Mod 65 23a Went E Ianit hd H HU 2 E Flame E Cont After pushing F Cont the display shows Ionization 1 2 uA Woltase 276 I Rest TS 227 5S Status oFerate Cont Hold If an error occurs you see instead of the measured values bars and the status changes from operate to Failure Pushing Hold locks all measured values or unlocks them again Locked val ues are marked by a rectangle and can be printed and or stored With F Cont you change to the error statistics Starts total 345 Error statistics Last error Ho Flame Prior error Failure light Pushing locks all measured values or unlocks them again Locked values are marked by a rectangle and may be printed and or stored With A you may scroll the displayed values and new elements of the error statis
12. t 224 Error history Ho flame With A you may scroll the displayed values and new elements of the error statis tics will be shown Edition 2004 12 15 10 of 15 D896 Instruction Manual Dual BCl Following errors may be displayed No Flame no flame signal after ignition Straylight flame signal before ignition Loss Flame no flame signal during operation Timeout heater oil heater error unknown unknown error By pushing the button F you may call the menu Printing see 4 if values are locked in other case the menu Functions is called again 3 1 3 Data Transfer Error If the connection between burner controller and MSI 150 is disturbed the display will read Data transfer LAO Data tranfer error Cancel By pushing the button Cancel you may call the menu Functions again After the connection is repaired new mounting of the sensor head for example the start function see 3 1 1 is done automatically 3 2 Siemens Gas Burner Controller Before data can be transferred the burner controller has to be set to interface di agnosis mode see user manual burner burner controller Shows the burner controller an error the light in the burner controller is red you may set the burner controller to visual diagnosis mode by pressing the burner con troller button for more than 3 seconds D896 11 of 15 Edition 2004 12 15 Instruction Manual Dual BCl 3 2 1 Data Transfer Is the burner controll
13. written and the menu Functions is shown D896 15 of 15 Edition 2004 12 15