S2000-4 ver 2.03 User`s Manual
Contents
1. ccceceeceeeeeeeeeeeeeeeees 37 1 10 Reader connection A isssiels wiwiecteated ieee nv etindaivccantiaave 39 1 11 Light and sound signaling siiwacvctiutisnecatsvy Aiden Avamantvavivei 42 1 12 Configuration parameters cccccsseeceeeesesseeeeecseessseeeeeeeeeeseesneses 48 TAS IdentitierS ernan a E a aa TE EE ENE N O 49 1 13 1 Identifier parameters cccccccecceeeeeeeeeeeeeeeeeeseeeeeeeeeseeeeeeeeerererress 49 1 13 2 Identifier programming nennen 51 2 Application i L t hea a ea headin eaea aia E ERTAINE 55 SECURITY SYSTEMS S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL 2 1 Preparation for use xgscccecczccacws vavocsseacvsasevceceusuitdscaldun seepcaneeseseamsocessaues 55 2 1 1 Protective measures cond thet xed tennnandinscraanieaanaadiaint eabwankend mddmnnbinne aie 55 2 1 2 TNE panel Mounting seese aeir ea a EE aa a Eee 55 2 1 3 RS 485 interface wiring cccccccccccccccccceeeecceeeeeeeeeeeeeeeeeeeeeeeeeeeeeseeeeess 55 2 1 4 Changing the panel default settings ccccceceeeeeeeeeeeeeeeeeeeeeeess 56 2 2 Iypi alapplicati n sssri E EEEa 56 2 2 1 Fire alarm system without access control at the small object 56 2 2 2 Fire alarm system without access control at the large object 59 2 2 3 Burglary and fire alarm without access Control cceeeeeeeeeeeees 61 2 2 4 Burglary and fire alarm along with access Control cccceeeeeeees 64 3 MAINTGN ANG e isscc
2. 40 to 50 C 1 2 Specifications The panel is supplied by external direct power voltage 12V 10 2 to 14 2 V DC or 24V 20 4 to 28 4 V DC It is recommended to use RIP 12 or RIP 24 uninterruptible power supplies manufactured by NVP BOLID Company Consumed power is less 3 W The table 1 is demonstrated the maximal consumed current in standby and Alarm or Fire modes The maximum number of alarm loops that can be connected to is 4 SECURITY SYSTEMS Detectors Relays Mode S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Table 1 Consumed current in different modes Power voltage 12 V 24V There are no detectors being power supplied by loops all detectors are contacting Turned off Norm 100 mA 50 mA Alarm Fire 140 mA 70 mA Turned on Norm 150 mA 75 mA Alarm Fire 200 mA 100 mA All detectors are power supplied by loops with consumed current being equal 3 mA in each loop Turned off Norm 130 mA 70 mA Alarm Fire 170 mA 85 mA Turned on Norm 180 mA 90 mA Alarm Fire 220 mA 110 mA The loop input voltage in stand by mode varies from 19 to 24 V de pending on loop consumed current and supports its value even in case of short circuit failure in one of the alarm loops The panel restricts the electric current through the actuating detector by value no more than 20 mA voltage applie
3. 1 Turn on turned off The relay is not used AccessControl Of Reader Interface Type Proximity reader with Touch 1 Touch M celts LA Memory interface is used for example S2000 Proxy LED Control Polarity Direct active 1 Reader LED Standby Mode 2 that is if any given loop is armed then Reader LED is on if at least one LED is red lit other burglary loop is armed wise Is off Loop Arming Reader Light Indication 62 The reader LED indicates only the burglary loop arming The status of loop 4 is not indicated INSTALLER S AND USER S MANUAL APPLICATION Parameter Parameter value Comment 100p1 100p2 10073 loop On Loop Alarm 2 On Any loop breaking is indicated Reader Light 3 On by LED Indication 3 4 On To arm disarm two sets of Proximity cards are used with first set cards controlling the loop 2 arming and disarming and second set cards controlling the loop 3 arming disarming The loop 1 is armed and disarmed automatically as Common zone when Loop 2 or 3 arming Loop 4 fire is controlled from the S2000 S2000 4 console or PC when necessary Separate rooms arming disarming is executed be presenting the cor responding card to the reader If controlled by the card loop was armed it is disarmed with reader light indicator being turned off If controlled by the card loop was disarmed it is armed with reader light indicator being tur
4. 1 4 1 2 Arming Delay The parameter Arming Delay means the exiting duration or the number of seconds you want the panel to wait before arming the alarm loop after having received the corresponding command Nonzero Arming Delay is normally used for entering alarm loop in case of after entering arming command it is possible for some time to break this loop without go ing off an alarm If before loop arming it is necessary to turn relay on the executive program 17 Turn on for a given time before arming then the Arming delay loop parameter has to be set to a nonzero value Otherwise the relay will not turn on because of the turning time for this program must not exceed the Arming delay loop parameter 1 4 1 3 Intrusion Fire Delay For entering alarm loop type 7 the Intrusion Fire Delay parameter means the transition delay from Entry Alarm to Intrusion Alarm status and is considered as entering duration Intrusion Fire Delay is given to make it possible to disarm alarm loop after entering loop breaking For entering alarm loop types 1 2 3 the Intrusion Fire Delay pa rameter means the period of loop transition from Fire prealarm to Fire alarm status Alarm loops with double actuation recognition types 1 and 3 can transit to the Fire alarm status when second fire detector in this loop has actuated If Intrusion Fire Delay is set to 255 s it means unlim it
5. Fire Alarm mode from Fire Prealarm if the second detector has activated at this loop or Intru sion Fire delay has been expired If Intrusion Fire delay was given as 0 then the transition from Fire prealarm to Fire alarm mode would happen instantly If Intrusion Fire delay was given as maximum value 255 then the transition from Fire prealarm to Fire alarm would be able only if the sec ond detector in this loop has actuated 13 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL The type 3 alarm loop resolving time is 300 ms The compatibility of loop resistance and the corresponding status can be shown at the Table 5 The diagram of connection the heat normally closed detectors to the type 3 alarm loop is contained into the Appendix C The type 4 is the burglary alarm loop The alarm loop includes burglary detectors of all types including nor mally closed normally opened powerless supplied via alarm loop or sepa rately The alarm loop statuses can be Armed the alarm loop is monitored and the resistance is in normal range Disarmed the alarm loop is not monitored Arming delay the arming delay has not yet been elapsed Intrusion alarm the detector breaking has been fixed Arm Failed the alarm loop was broken when arming The intrusion alarm loop is considered as broken if its resistance has been out of 2 6 KOhm range when armi
6. after having entered Entry Alarm status the In trusion Fire Delay period has expired Arm Failed the alarm loop was broken when arming The performance and parameters of entering alarm loop are identical to those of type 4 burglary alarm loop except that breaking of armed loop transits it at first to the Entry Alarm and only if during the Intrusion Fire Delay period arming or disarming of the alarm loop had not occurred it would enter to the Intrusion Alarm status While the alarm loop is in the Entry Alarm status the relay switching by means of executive programs 1 8 and 12 does not perform This type alarm loop resolving time is 70 ms The compatibility of loop resistance and the corresponding status can be shown at the Table 5 The diagram of connection burglary detectors to the type 7 alarm loop is contained into the Appendix C The type 11 is the alarming loop The alarm loop includes normally opened and normally closed alarm devices call points footboards and so on The alarm loop statuses can be Armed the alarm loop is monitored and the resistance is in normal range Disarmed the alarm loop is not monitored Arming Delay the arming delay has not yet been elapsed Silent Alarm attack the alarm loop breaking has been detected Arm Failed the alarm loop was broken when arming The alarming loop is considered as bro
7. If all related loops have been armed then this loop enters the armed status It is not possible to change the common zone status by arming disarming via RS 485 interface or with the help of identifi ers If alarm loop from common zone has the Intrusion Alarm status the arming disarming command leads to the arming of this loop ALARM RESET status 20 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Table 5 Loop parameters depending on the status Loop type Alarm loop statuses Loop trbl Fire alarm Fire Loop trbl rst Loop trbl short Actuation of prealarm Loophas open alarm loop two or more Actuation of been re alarm 1 short cir smoke de one smoke stored after loop Fire Smoke cuit tectors detector any failure open cir with dou cuit ble actua less then from 150 from 1 1 to from 2 4 to tion recog 100 Ohm Ohmto1 56 2 0 kOhm 5 4 kOhm 6 6 kOhm nition KORM Depending on detector stand by mode consumed current Loop trbl Fire alarm Loop trbl rst Fire Loop trbl short Actuation of Loop has prealarm open 2 alarm loop smoke de been re Actuation of alarm Fire Com short cir tector stored after heat detec loop bined cuit any failure tor open cir smoke cuit and heat less then from 150 from2 2to from 6 6 to 100 Ohm Ohm to 1 8 5 4 kKOhm 30 KOhM KOhm Loop trbl Loop trbl rst Fire Fire alarm Loop trbl short Loop has Prealarm Actuatio
8. MASTER key is designed for programming or adding of the new keys The keys programmed with the help of MASTER key have Basic type Opening key is designed for access opening access free mode and normal access mode recovering see 1 6 2 Closing key is designed for access closing and normal access mode recovering see 1 6 2 The Blocking parameter setting on defines any type key prohibition It is used for temporary key blocking for example in case of key loss the recovery possibility being retained The Without Extra Code parameter simplifies several key identifica tion in case of double identification using see 1 7 If double identification is not realized this key parameter is ignored If the parameter User Code is set the key is used for loop arming and disarming The parameters Loop1 Arming Loop4 Arming and Loop1 Disarming Loop4 Disarming gives the lists for arming and dis arming accordingly The Arming Disarming Time Window is the number of time win dow defining the time periods when loop arming and disarming are en abled If it is equal to zero then arming and disarming are enabled at any time If the Access parameter is set the key is used for access control Access Time Window is the number of time window defining inter vals for access gaining If this parameter is set to zero the access is free at any time If the parameter Validity Restriction is
9. loops and entering type 11 alarm loops are able to be armed or disarmed as follows With the help of Proximity card or Touch Memory key assigned by user code controlling this loop arming disarming local control By the arming disarming command from net controller via RS 485 interface centralized control Scheduled arming disarming auto control Common zone arming disarming in case of arming disarming of re lated loops auto control Auto rearming when disarmed auto control Auto rearming when fire alarm auto control 22 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION If the loop Non disarming parameter is set on then this loop can not be disarmed When arming disarming command for non disarming loop has been received through RS interface If been armed this loop retains it status and sends the message Armed to the net controller If been in Alarm Fire Alarm or Arm Failed statuses this loop is armed and enters the Armed status in case of normal resistance value or in Arm Failed statuses otherwise For arming disarming with the help of Proximity card or Touch Mem ory key it is necessary to program this key or card with the User Code at tribute and the list of arming disarming available loops see 1 13 1 When the identifier is presented to the reader all loops controlled by this identifier are armed if they all have Disarme
10. Alarm and Access Control Panel The replacement component set including Resistances 4 Screw nails 3 3 Dowels Installers and User s Manual 1 4 Alarm loops The panel monitors four alarm loops and generates the following sig naling depending on their status displays the alarm loop statuses by means of internal two color panel indicators 1 4 see Table 14 turns the panel internal sounder on when loops have been troubled see Table 15 displays the loop status with the highest priority by means of reader two color indicator see Table 13 controls the two panel relays The alarm loop status is defined by its type its resistance and by the logical state armed or disarmed The status having been changed the panel generates and sends corresponding messages to the net controller either ARM Orion or S2000 S2000M console BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL 1 4 1 The loop configuration parameters The alarm loop control algorithm can be changed by varying the loop configuration parameters that can be viewed in Table 4 Table 4 Loop configuration parameters Parameter oe Description name Determines the control algo rithm available types of detec tors to be connected and po tential statuses The time interval between hav ing received arming command and loop transition to the armed status The delay for transitions from ENTRY ALA
11. Each identi fier has the parameter set attributes demonstrated by Table 17 49 BOLID AE S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Table 17 Identifier attributes Basic MASTER Opening Closing Blocking The key is disabled doesn t effects On Off To identify this key the extra code is Without Extra not obligatory double identification for Code other keys being required for other keys see section 1 7 Loop arming disarming designated key On Off Loop 1 Arming On Off Loop 2 Arming The list of alarm loops which are avail On Off Loop 3 Arming able for arming by this key On Off Loop 4 Arming On Off Key type Defines the key destination On Off SS On Off Disarming Loop 2 On Off The list of alarm loops which are avail Loop 3 able for arming by this key Oops On Off Disarming Arming Disarming Time Window The key is designed for access On Off Access Time The time window when Window access is permissible Validity Defines is there restrictions of key va Loge ee On Off Restriction lidity period or not Key Validity The start and finish 01 01 2000 Period dates of the key validity 31 12 2255 The Key Type parameter defines the main designation of the given The time window when arming and dis arming are permissible Z O key 50 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Basic key is designed for access or loop arming disarming
12. alarm or Fire alarm then OFF else ON output If Intrusion alarm or Fire alarm then ON for a given time else OFF 3 On for a time 26 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Program description 4 Off for a time If Intrusion alarm or Fire alarm then OFF for a given time else ON 5 Blinking Normal If Intrusion alarm or Fire alarm then blink state OFF 0 5 s ON and 0 5 s OFF else OFF 6 Blinking Normal If Intrusion alarm or Fire alarm then blink state ON 0 5 s ON and 0 5 s OFF else ON 7 Blinking for a time If Intrusion alarm or Fire alarm then blink Normal state OFF 0 5 s ON and 0 5 s OFF during given time else OFF 8 _ Blinking for a time If Intrusion alarm or Fire alarm then blink Normal state ON 0 5 s ON and 0 5 s OFF during given time else ON 9 LAMP If Fire alarm then blink 0 25 s ON and 0 5 s OFF If Fire prealarm then blink 0 25 s ON and 0 75 s OFF If Intrusion alarm Entry alarm or Arm failed then blink 0 5 s ON and 0 5 s OFF If Fire trouble then blink 0 25 s ON and 1 75 s OFF If there is at least one armed loop then ON If all loops are disarmed then OFF 10 Alarm output 1 If all relay assigned loops are armed then ON close output else OFF open output 11 ASPT If at least two relay assigned l
13. days The red letter day list allows to redefine the weekday for a year or to declare any day as red letter If the day is not redefined in the red letter day list black letter day than this weekday corresponds to the calendar day If the day is redefined the calendar is ignored and the panel consider this day in accordance with the red letter day list Redefined weekday can take the following values 1 Monday 2 Tuesday 7 Sunday 8 Eighth Timetable Day 14 Fourteenth Timetable Day Red letter Day The last value Red letter Day is designed to simplify the comprehension of the list and is not distinct from the other values It can be called as the Fifteenth Timetable Day So the red letter day list allows to Declare any day as red letter day that is the day with time intervals unlike intervals given for other weekdays are active 36 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Set weekdays aside e g Saturday can be redefined as Monday Program complex sliding access timetables with the period less or more than 7 days Program complex access timetables without return period One can mention two typical ways of creating the red letter list The first way If the employer access timetable or working timetable is assigned with the calendar week for example the days from Monday to Friday are black letter and the Saturday and Sunday are red letter days then the most og days are not re
14. from 0 to 255 sec Control De a particular loop lay Scheduled Alarm loop auto arming at the Scheduled Alarm loop auto disarming at Time Win dow for Scheduled Arming Disarming Loop The pause before alarm loop from 0 to 255 sec Analysis analysis after power dump Delay after when FIRE SIGNAL or Reset ARMED Common The alarm loop is common No No No If the alarm loop is common No No No zone for other loops this pa Yes No No IN N rameter shows that ones No No No No No No The number of time window defining the period of time with the disarming at the beginning and arming at the end from 0 to 15 1 4 1 1 Loop Type The fundamental configuration parameter identifying the loop control method and detector types to be included is represented by Loop Type The panel supports nine alarm loop types The type 1 is the fire smoke loop with double actuation recogni tion The fire smoke normally opened detectors are included into the alarm loop The alarm loop statuses can be 11 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Armed the alarm loop is monitored and the resistance is in normal range Disarmed the alarm loop is not monitored Arming delay the arming delay has not yet been elapsed Fire prealarm the single detector actuation has been fixed Fire alarm actuating more than one detector
15. green MASTER key programming flashes alternately The messages signaled by internal panel light indicators are de scribed in Table 14 Table 14 Panel indicator lights 7 4 Loop status Light operating mode Lighting Disarmed On Green Armed On Red Loop is normal On Green Arming Dela inki i g y Loop is broken seat with the 2 Hz Ceen requency Arm Failed Bu with the 2 Hz Green requency Blinks in Short stopping Fire Alarm mode Red with 1 Hz frequency Fire Prealarm Blinks in Flashing mode Red with 1 Hz frequency Intrusion Alarm Entry Alarm Si Blinking with the 2 Hz Red lent Alarm Aux Zone Alarm frequency Blinks in Short Flashing Yellow Trouble mode with 0 5 Hz fre reen Loop Trbl Open or Loop Trbl Short quency g red T Al APRESSAR e Blinking with the 4 Hz ni detector tamper opening frequency in type 5 loop 45 BOLID BOLD S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Loop status Light operating mode Lighting The key doesn t Off n control the loop The key has only Blinks in Flashing mode arming authority with 1 Hz frequency Key pro ee nt gramming The key has only Blinks in Flashing mode disarming authority with 1 Hz frequency The key has arming and disarm ing authority both Red and green flashes alternately The messages signaled by reader and panel sounders are identical and are described in Table 15 Table 15 Panel an
16. has been fixed or af ter first detector actuation the Intrusion Fire delay has expired Loop trbl short the alarm loop resistance is less than 100 Ohm Loop trbl open the alarm loop resistance is more than 6 KOhm Arm Failed the alarm loop was broken when arming When detector has actuated the panel generates the Fire Signal message and de energizes the alarm loop for a short time If within 55 sec onds after de energizing the detector connected to this loop repeats actua tion the panel enters the Fire Prealarm mode at given loop If the second actuating has not occurred within 55 seconds the alarm loop returns to the Armed state From the Fire Prealarm mode the panel can transit to the Fire alarm mode if the second detector has been actuated or Intru sion Fire delay has expired at this loop If Intrusion Fire delay was given as 0 then the transition from Fire prealarm to Fire alarm mode would hap pen instantly If Intrusion Fire delay was given as maximum value 255 then the transition from Fire prealarm to Fire alarm would be able only after actuating of the second detector at one loop The type 1 alarm loop resolving time is 300 ms The compatibility of loop resistance and the corresponding status can be shown at the Table 5 The diagram of connection the fire smoke normally opened detec tors to the type 1 alarm loop is contained into the Appendix C The
17. identification the panel is to store two codes for each user main and extra then the maximum S2000 4 panel storage capacity is only up to 1024 codes Main and extra codes are presented to the same reader so the com bining of different code types for example Proximity card PIN code is possible only in case of using of integrated devices providing different type identifier reading and transmitting to the panel using unified format Touch Memory Wiegand or ABA TRACK II 1 8 Time windows The panel time windows are used to limit the access into the protected premises depending on date weekday and time of day limit the assigned arming disarming authority depending on date weekday and time of day arm and disarm alarm loops automatically at the given time To add the access time restrictions each key is assigned with the number of access time window To restrict arming disarming authorities the key is assigned with the number of arming disarming time window The assigning with 0 number time window means the absence of date time or weekday limitations Time window parameters with the num bers from 1 to 16 are programmed by the panel The time window descriptor consists from the list of 10 time intervals and the list of red letter days for one year The time interval description comprises the beginning hours and min utes the finishing hours and minutes and activity attribute for all weekdays and red letter
18. loop 4 59 BOLID ye S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL 100p1 loop2 1o0p3 100p4 255 255 255 O The Fire Alarm signal forming is re alized only after two smoke or heat detector actuations at the same alarm loop or manual call point acti vation All loops are armed The arming Non di R On On On On command is used only for rearming isarming of the actuated loop If during rearming the alarm loop has Auto Rearm not been restored Arm Failed has ing when Dis On On On On joccurred then it will be automatically armed armed after loop having been recov ered Auto Rearm The recovering of the Armed mode ing when Off Off Off Off after Fire Alarm status is possible Fire Alarm only by means of operator command Relay 1 On On Onl On All loops control the smoke elimina Control tion system damper The sound notification control from Relay 2 of of off ot the net controller by the Fire Alarm Control signal generated by the any device installed on premises Relay 1 The damper control delay after Fire Control Delay Alarm signal is 30 s Turn on the local dumper is opened from the Fire Alarm mo ment to the actuated loop rearming Defines the initial status of the relay Relay 2 Con turned off The relay 2 control tac trol Program tics Siren is given by the net con troller Access ee a ee ee The two smoke detectors at the loop 1 or two smok
19. privi leges by successively switching between arming and disarming only arming and does not control this loop values 52 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION One short tamper pressing changes loop 1 arming disarming privi leges twice short tamper pressing changes loop 2 arming disarming privi leges and so on The pauses between pressings in one series must not exceed 0 5 s The programming key status is indicated by the panel and reader LED in accordance with the Table 18 Table 18 Programming key parameters displaying 1 4 LED display 1 4 Programming Reader LED loop arming privileges key status of the programming key Single red and Access key green alternately flashes Two green Turned off if the key Loop Arming flashes and two Twice doesn t control given Disarming key red flushes flashes loop alternately Blinks by red when the key has only arming privileges Blinks by green and red alternately when the key has given loop arming and disarming privileges Single flashes Access and Three green Loop Arming flashes and three Trial Disarming key red flushes flushes combined alternately MAIN MASTER key can be added with the help of the computer To do this the first key in the list must be attributed with the MASTER type The panel can record any number of MASTER keys but programming key attributes can be changed with the help of tamper only if programmin
20. sent by net controller via RS 485 interface Turning relays on off for a given time while accessing process 1 5 1 Relay local control To control the relay depending on connected alarm loop status it is necessary to assign the relays with the corresponding loops by means of Relay 1 Control and Relay 2 Control loop parameters give the Relay 1 Control Delay and Relay 2 Control Delay loop parameters assign the Relay Control Program and Relay Control Time relay pa rameters for relay 1 and relay 2 The Relay Control Program parameter defines the relay behavior de pending on the related loop statuses All available executive programs are represented in Table 7 The Relay Control Time parameter gives the period of time required by executive programs with the limited duration Except the programs NeNe 9 10 13 14 15 16 see Table 7 all other programs support the delayed relay turning on off for time interval given by Relay Control Delay parameter for the corresponding loop So different panel alarm loops associated with the same relay can be given by different starting delays For executive programs from 1 to 8 11 12 33 34 35 the relay as signed auxiliary loop type 6 breaking blocks up the relay turning on If when auxiliary loop recovering the turning on condition depending on the other loops are retained then for the programs 1 2 5 6 12 and 33 the re lay sw
21. switches the relay ON for a given time else OFF Turn off for a given time when auxiliary alarm If at least one loop is in the state Auxiliary alarm switches the relay OFF for a given time else ON 28 Turn on when dis armed Turn off when dis armed Turn the relay ON if at least one assigned alarm loop is disarmed else OFF Turn the relay OFF if at least one assigned alarm loop is disarmed else ON Turn on when Turn the relay ON if at least one assigned 29 armed alarm loop is armed else OFF Turn off when Turn the relay OFF if at least one assigned 30 jarmed alarm loop is armed else ON 34 Turn on when aux In case of Auxiliary alarm turns the relay ON iliary alarm else OFF Turn off when aux In case of Auxiliary alarm turns the relay 32 iliary alarm OFF else ON ASPT 1 If the alarm loop has entered the Fire alarm 33 status and there are no broken auxiliary loops then switches the relay ON for a given time If an auxiliary loop has broken during the relay 29 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Number Program description control delay then when recovering the output will be turned ON for a given time the auxil iary loop breaking holds the turning on delay counting ASPT A If at least two assigned alarm loops have en tered the Fire alarm status and there are no broken au
22. the alarm loop will automatically enter the Armed state when it resistance will be in normal range during The Alarm Loop Recovery Time period 1 4 1 7 To Control When Disarmed The parameter To Control When Disarmed makes the panel to control alarm loops in all statuses including Disarmed If the alarm loop resistance is in normal range the message Ready to Arm is sent for net controller if not the panel sends the Not Ready to Arm message for the net controller The resolving time for Not Ready to Arm is 300 ms and for Ready to Arm is equal to the The Alarm Loop Recovery Time 1 4 1 8 The Alarm Loop Recovery Time The Alarm Loop Recovery Time is used when making the deci sion about loop having been recovered in case of Auto Rearming when Fire Alarm or transition to Aux Zone Restore status or transition of dis armed auxiliary loop to the Aux Zone Restore status 1 4 1 9 Relay 1 and Relay 2 Control The parameters Relay 1 Control and Relay 2 Control are asso ciated the alarm loop with the panel relays If relay 1 or and relay 2 state must be influenced by the alarm loop then the corresponding parameter must be set otherwise it must be turned off If relay 1 or relay 2 must be controlled depending on the loop partitions status in accordance with the assigned program given by S2000 S2000M or ARM Orion in case of centralized control then
23. type 2 is the fire combined alarm loop The fire smoke normally opened and heat normally closed detec tors are included into the alarm loop The alarm loop statuses can be Armed the alarm loop is monitored and the resistance is in normal range Disarmed the alarm loop is not monitored Arming delay the arming delay has not yet been elapsed Fire prealarm the heat detector actuation or second smoke detec tor actuation has been fixed Fire alarm after detector actuation the Intrusion Fire delay has ex pired Loop trbl short the alarm loop resistance is less than 100 Ohm Loop trbl open the alarm loop resistance is more than 50 KOhm 12 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Arm Failed the alarm loop was broken when arming When heat detector has actuated the panel enters the Fire Prealarm mode When smoke detector has actuated the panel generates Fire Signal message and de energizes the alarm loop for a short time If within 55 seconds after de energizing the detector connected to this loop repeats actuating the panel enter the Fire Prealarm mode at given loop If the second actuation of smoke detector has not occurred within 55 sec onds the alarm loop returns to the Armed state From the Fire Prealarm mode the panel can transit to the Fire alarm mode if Intrusion Fire delay has expired If Intrusion Fire de
24. 1 ioop2 100p3i00p4 2 that is if any given Reader LED loop is armed then Reader LED is on if at least one Standby Mode LED is red lit other burglary loop is armed wise is off Reader LED Loop Arming Indication Any burglary loop arming is in dicated by the reader LED but loop 4 arming is not indicated Reader LED Loop Alarm Indication Any loop breaking is indicated by the reader LED The signal polarity can be direct or reverse but has to agree with the defined reader polarity The reader sounder makes the Access short double sound in case of any access gaining or one long Reader sound Error if the access is Sound Alarms prohibited a The reader sounder goes off in ion Program interrupted mode in case of ming Alarm Fire Alarm Door Forced or Door Left Open Sounder Control Polarity To arm disarm burglary loops and for access gaining the same Prox imity cards are used so called combined cards If the premises are armed then card presenting leads to burglary loops disarming accompanied with the access gaining To arm the premises it is necessary to present and hold the card near the reader during 3 seconds If apart from the combined cards access cards are in use then the access gaining is possible only when the object is disarmed that is loops from 1 to 3 are disarmed The relay 1 control time gives the Time for passing when access gaining During this t
25. 1 Control Time but no less then 10 s Until the door having been opened or until the Relay 1 Control Time expired the new identifier presentation is not considered by the panel in case of door having been opened the panel can generate the Passed event the door can be controlled against burglary and blocking see Door Burglary Control and Door blocking control parameters the relay 1 control the lock can turn off before the Relay 1 Control Time having expired see Turn Relay 1 Off When Door Is Opening and Turn Relay 1 Off When Door Is Closing parameters The parameter Door Opening Detector being turned off the men tioned functions are enabled the passing is not waited and reader LED in dicates the fact of access gaining during Relay 1 control Time but no less than 2 s If the parameter Passed Event is set on then during door opening after access gaining the panel generate the message about the passing This report can be needed for Net Anti Passback function or Time and Attendance recording when using under Orion system If the parameter Door burglary control is set on then in case of door opening without access gaining the alarm message Door Forced is generated and light and sound signaling goes off If the parameter Door blocking control is set on then in case of door being opening within period exceeding the Door Blocking Time Out the alarm message
26. 30 minutes Comments The wire connection or disconnection when testing is realized under power off conditions Take into account that technical readiness time of the panel can take up to 3s Following are the testing steps a Check the package consistency and unpack the device b Check up the delivery set in accordance with this manual see sec tion 1 3 c Make sure that the panel case is not mechanically damaged 67 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL d Shake up the panel to make sure that foreign objects are absent inside the panel e Check up the terminal block attachments f Check up the conformity of the panel number and the release date with those specified by user s manual 3 1 1 Overall functional testing a Energize the panel b The internal sounder shall make Turning on sound c The panel useful current shall not exceed 200 MA d The S2000 S2000M console shall display the events occurred such as panel detection panel reset and panel tamper 3 1 2 Testing in diagnostic mode Before diagnosing disconnect all relay load circuits To run the diagnostic mode open the panel cover and press tamper three times for short time 0 1 0 5 s and once hold for a time at least 1 5 s The pauses between pressings shall be no more than 0 5 s The panel being useful the Ready indicator and the reader light in dicator enter the interrupted quick flashing light mode with the re
27. 9 1 4 1 7 To Control When Disarmed iiscaccscededaenageisecatetay wadevavwateasmndaants 19 1 4 1 8 The Alarm Loop Recovery Time ccccccecececeeeeeeeeeeeeeeeseeaanneeees 19 1 4 7 9 Relay 1 and Relay 2 Control ccccscscsnscssscsnscsnsncnscsesrenersssranerses 19 1 4 1 10 Relay 1 and Relay 2 Control Delays cccscssssesessessneneetsetesstseeeees 19 1 4 1 11 Scheduled Arming and Disarming cccccccecsseeeeeeeeeeeeeeseennnneeees 20 1 4 1 12 Loop Analysis Delay after R S t cccccccccceseceeeeeeeeeeeeeeeeeeseeeenseeees 20 14 1013 COMMON ZoNe incu aici ne are a ei 20 1 4 2 Loop arming and disarming ccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaeaeees 22 1 5 Relays acesvarea hess cruriiteenacbcsteadanianctueeh recess a a mete a 24 LST Relay local controlin tannins 24 1 5 2 Relay centralized COntroll ccccccssssssssceeeeeeeeseeeeessseeeeeeeeeesseseaeeess 25 1 5 3 Turning relay on off during access Controlling c000ceeeeeeeeeees 25 1 5 4 The relay configuration parameters ccccceeeeeeeeeeeeeeeeeeeeeeeeeeeees 26 150 Access Controls naene aeae e ea AE E a AE 30 1 6 1 Access control configuration parameters 31 1 6 2 Access Modes erieihin e E A E a e i 34 1 7 Double identification srren eaa ea i a K 35 1 8 TIME WINDOWS Ssciccu vist easdedenesustiuosons E aeeai aaaea eE Ee FERE EEE AEA NAAA REE 36 1 9 Centralized access and partition Control
28. A03 PR A05 or PR P09 reader connection Variant 1 Touch Memory interface Variant 2 Wiegand interface PR A03 PR A05 White Whi Led G Orange BEEP GND Black Red Red 12V 0V 12V OV to the power supply to the power supply 1 Led V S2000 4 configuration parameters Reader interface type pega aa Reader interface type 2 Wiegand LED control polarit ee LED control polarit ee direct reverse Sounder control polarity active 1 Sounder control polarity active 0 76 APPENDIX E READER CONNECTION DIAGRAMS E4 PR H03 PR H05 or PR MO9 reader connection PR H03 PR H05 PR M03 12V OV to the power supply S2000 4 configuration parameters Variant 1 Touch Memory interface Variant 2 Wiegand interface S2000 4 configuration pa Reader jumpers S2000 4 configuration pa Reader jumpers rameters rameters Reader inter 1 Touch red Reader inter 2 Wiegand facetype Memory face type delete LED control direct gange kaelet LED control reverse polarity active 1 polarity active 0 Sounder con direct Sounder con reverse nam green delete trol A ee trol polarity active 1 polarit active 0 TT SECURITY SYSTEMS S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL E5 Touch Memory reader connection Touch Memory reader connection in case of having two LED Touch Memory reader LED iTouch Memory reader To
29. Appendix D S2000 4 testing connection diagram PV1 PR1 and PA1 are correspondently voltage resistance and current measurement modes of combined tester 73 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Appendix E Reader connection diagrams E1 S2000 Proxy and S2000 Proxy N reader connection S2000 Proxy and S2000 Proxy N S2000 Proxy and S2000 Proxy N connection diagram connection diagram reader is used for access controlling reader is used for arming disarming S2000 Proxy S2000 Proxy S2000 Proxy N S2000 Proxy N Ea Indicator LEDR 3 Exit D0 Exit D0 Common GND Common GND Power U Power U S2000 4 configuration parameters Reader interface type 1 Touch Memory LED control polarity direct active 1 74 APPENDIX E READER CONNECTION DIAGRAMS E2 Proxy 2A and Proxy 3A reader connection Proxy 2A Proxy 3A 12V OV to the power supply Variant 1 Touch Memory interface Variant 2 Wiegand interface Reader DIP switch settings Proxy 2A Proxy 3A Proxy 2A Proxy 3A EET Fanann S2000 4 configuration parameters Reader interface type Touch ane Reader interface type TE aad direct reverse LED control polarity active 1 LED control polarity active 0 direct reverse Sounder control polarity active 1 Sounder control polarity active 0 15 SECURITY SYSTEMS S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL E3 PR
30. Door Left Open is generated and light and sound sig naling goes off The parameter Turn Relay 1 Off When Door Is Opening being set on the turning relay 1 on off when access gaining interrupts just after the door having been opened before the Relay 1 Control Time elapsing The parameter Turn Relay 1 Off When Door Is Closing being set on the turning relay 1 on off interrupts just after incomer has closed the door This parameter used to be set in case of electromagnetic lock being controlled with the help of executive relay 1 program BpikniouuTb Ha Bpe MA If one of Turn Relay 1 Off When Door Is Opening and Turn Relay 1 Off When Door Is Closing is set on then the Relay 1 Control Time de fines the maximum time period for passing The actually time of turning on off shall be less or equal to Relay 1 Control Time 33 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Access Zone number is important in case of the system Orion operation mode BaxeH when using Anti Passback or Time and Attendance functions It is the number of access zone in the system the panel to gain access when identifier reading This number is displayed by the panel in connection with the passing event and access gaining denying If the panel is used as a part of the system but Anti Passback or Time and Attendance functions are not in use it should retain the default value of this parameter being equa
31. ED Device power supply is out of range POWER RESTORE Device power supply is restored after failure PROGRAMMING The panel has entered the user s key pro gramming mode If the panel was disconnected from net controller during message generation the event report would be stored in the panel non volatile mem ory When the connection would recover the event report will be transmit ted to the net controller with the date and time of its origin being noted The buffer storage in the panel non volatile memory is sized to 1023 events INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION The panel executes several commands having been received via RS 485 interface which are configuration writing net address assigning loop arming disarming relay control access control access identifier reading access identifier adding or changing time synchronization or reading the non dimensional loop resistance value given by digital to analog converter The panel uptime after power on does not exceed 3 seconds The panel mean life is 20 000 hours The panel average operating life is 8 years The mass of the panel is about 0 3 kg with overall dimensions being equal to 150 x105x35 mm The panel construction design provides the ingress protection rating in accordance with IP20 1 3 The delivery set The S2000 4 panel delivery set is demonstrated in Table 3 Table 3 The S2000 4 panel delivery set S2000 4 Intrusion amp Fire
32. Free Mode ping mode with 1 Hz frequency Access Granted the passing is waiting The extra code is waiting after main code having been presented in case of double identification Arm Failed Green Blinking with the 5 Hz frequency Three flashes blinking with the 3 Hz frequency Switches from red to green with 5 Hz frequency Access Denied The unknown key is presented the net controller verdict is waiting Partition centralized control partition being armed Partition centralized control partition being disarmed Partition centralized control Blinking with the 2 Hz partition alarm frequency Partition centralized control Flashes with partition trouble 1 Tu frequency Red and green al ternately Red and green al ternately Access Red and green flashes keys programming alternately Arming Disarming Two red and two green Keys Programming flashes alternately 44 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Panel status Light operating mode Lighting Three red and three Red and Arming disarming and access com A green flashes alter green al bined keys programming nately ternately Red and green al ternately Note loop alarming Fire Alarm Fire Prealarm Intrusion Alarm En try Alarm Loop Trbl Short Loop Trbl Open Tamper Alarm Aux Zone Alarm Arm Failed is indicated only if Loop Alarm Reader Light Indication is enabled for this loop Two red and two
33. If during the alarm loop arming it resistance is less than normal value for example if the smoke fire detector has actuated at the alarm loop then the panel automatically resets this loop that is de energizes all loops for 3 sec In addition the panel resets the loop after the first normally opened smoke detectors actuation at the alarm loop of type 1 or type 2 1 4 1 12 Loop Analysis Delay after Reset The Loop Analysis Delay after Reset parameter enables to in clude the detectors with long warm up time or long reading time in the alarm loop If the loop power supplied detectors enters to the operational mode and requires higher current consumption during long time after loop resetting than it is necessary to set the Loop analysis delay after reset parameter to the value just over maximum warm up time of loop included detectors 1 4 1 13 Common Zone The Common Zone parameter enables auto disarming of loop when any other associated alarm loop has been disarmed Moreover it en ables auto arming of loop when all associated alarm loops has been armed Except the Common Zone parameter the parameter The List of Associated Alarm Loops is defined for the alarm loop If the Common Zone parameter is set for the alarm loop then this loop arming and disarming depend on the arming and disarming of the re lated loops If at least one of the related loops has been disarmed then the present loop is disarmed too
34. PLICATION 2 APPLICATION 2 1 Preparation for use 2 1 1 Protective measures There are no dangerous voltage circuits within the panel The mounting and maintaining of the panel shall be executed under power off conditions 2 1 2 The panel mounting The panel can be mounted to the wall or above the suspended ceil ing or to other places on premises being protected from atmospheric fall outs mechanical damages and unauthorized access The installation procedure is as follows a attach the panel to the wall in any convenient place b install the reader in front of the door to the protected premises or inside the premises if access control is not in use c if the access control is in use place the EXIT button inside the premises d attach the connecting wires in accordance with the S2000 4 connecting diagram presented in Appendix B 2 1 3 RS 485 interface wiring To connect the panel with the net controller via RS 485 highway in terface refer to the connecting diagram in appendix B and execute the fol lowing steps a Connect the A and B lines of RS 485 highway interface to the A and B terminals of S2000 4 panel b Connect the panel circuit OV to the similar circuits of preceding and following RS 485 connected devices it is not obligatory if the devices are connected to the same power supply c Delete XT3 jumper connecting the terminal 620 Ohm resistance to the interface circuit except for th
35. PLICATION Parameter Parameter value Comment oop1 loop2 1oop3 loop4 Relay 1 Control Program To open the door it is necessary to supply latch voltage The maximum turning on time 5s for electromechanical latch in case of access gaining Defines the initial relay status turned off The relay 2 control tactics Siren is given at the net controller The door opening detector is connected To control the door from the un 3 Turn for a time Relay 1 Control Time Relay 2 Control Program Detector Detector Control 1 Turn on authorized opening To generate the Door Left To Turn Relay 1 Off when Door Is Opening To Deny the Access if Any Pointed Loop Is Armed To remove supply voltage when the door has just been opened If burglary loops are armed the access is denied The fire loop arming is enable Open event if the door is open Door Blocking 30s ing more than 30 s Time Out On On On Off The Proximity reader with Touch Memory interface is in use for example Proxy 2A Reader Interface 1 Touch Memory Type Arming Disarming Combined Key Holding Time To arm it is necessary to hold the combined card near the reader for 3 s The signal polarity can be direct direct active 1 or reverse but has to agree with the defined reader polarity LED Control Polarity 65 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL 100p
36. RM to Default value for 1 4 loops Range from 0 to 255 sec from 0 to 254 sec 255 means Off INTRUSION ALARM state or one detector hav Intrusion from FIRE PREALARM to Fire FIRE ALARM one Delay ing been acti vated it must not transit Fire Alarm or Intru sion Alarm Non The loop cannot be disarmed On Off Off Off Off Off disarming by any way Auto Re Auto transition from ARM arming FAILED to ARMED when When Dis loop having recovered armed Auto Re Auto transition from FIRE arming INTRUSION ALARM or When SILENT ALARM to ARMED Fire Alarm when loop having recovered To Control To monitor and transmit the When Dis resistance changes is its nor mal or not via RS 485 The Alarm The time of making the decisi on that loop has recovered in case of Auto Rearming when Fire Alarm or transition to Aux Zone Restore status or disarmed loop control 10 from 0 to 255 sec INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Parameter Default value Description Range for 1 4 loops name a1 2 3 4 Relay 1 Assign relay 1 to the particular On Off Onl Onl On On Control loop Relay 2 Assign relay 2 to the particular On Off On On On On Control loop Relay 1 Relay 1 turning on off delay for from 0 to 255 sec Control De a particular loop lay Relay 2 Relay 2 turning on off delay for
37. Reader interface Double Two identifiers are pre Identification sented for recognition On Off Direct The active logic level ts sea Direct FED Gon trol choice for reader LED aciiva 1 active Polarity e reverse 4 lighting active 0 40 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION value 1 Off 2 if any given loop is armed then LED is Describe the reader red lit other Reader LED aes aoe wise is off LED lighting in standb Standby Mode g i z 3 if all given loops are armed then LED is red lit otherwise is off 4 red lighting The list of alarm loops Loop Arming which arming results in Reader Light red reader LED turning Indication on for 2 and 3 Reader LED Standby Mode 1 Loop Alarm The list of alarm loops On Off aa Reader Light i ing is indi A which breaking is indi Indication 3 cated by reader LED On Off O Ono On Direct active 1 reverse e F active 0 The active logic level choice for reader sounders going off Reader Access Reader sound signaling On Off Sound of access gain Indi arms ing denying alarms and aaa Program entering into the pro a ming gramming mode The Reader Interface Type Touch Memory Wiegand or ABA TRACK II parameter has to agree with the interface of the readers being in use Direct active A F Sound Control Polarity The Touch Memory interfaced reader being used the Arm in
38. SCRIPTION To control the partition by means of this key it is necessary previously to switch the panel mode to the Arming Disarming Readiness mode identi cally to the loop arming disarming local control combined keys using see section 1 4 2 The communication between the panel and the net controller being absent the centralized access and partition control are impossible When centralizes access and partition control are in use the double identification is not supported 1 10 Reader connection To read off the identifier codes it is necessary to connect the reader with Touch Memory Wiegand or ABA TRACK II magnetic card interfaces to the panel One can use any identifier such as Touch Memory keys Prox imity labels cards or tags magnetic cards PIN codes and so on designed for readers transmitting the identifier code to the panel in one of the men tioned above interface formats The panel terminals designation can be shown in the Table 10 Table 10 S2000 4 terminals designation for reader connection Touch Memory mode Wiegand mode Input Reader DO data ABA TRACK II mode Input Output Reader data Reader DATA data Touch Memory mode Wiegand mode Reader D1 data a TRAGR Reader CLOCK tick mode LEDG Output Reader green LED controller LEDR Output Reader red LED controller BEEP Output Reader sounder controller The reader is connected by coupling the terminals listed above with the reader cont
39. SECURITY SYSTEMS 2000 4 INTRUSION amp FIRE ALARM AND ACCESS CONTROL PANEL READY 2000 4 10 E005 Installer s and User s manual BOLID AEE S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL ATTENTION To modify configuration parameters use the program uprog exe of version 4 0 0 810 or above You must not use for this procedure earlier versions of uprog exe or to modify parameters by means of S2000 or S2000M fire and alarm console INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Table of contents 1 Product description ccdecconsardennsesticssspendonsdecectesennnsteta cence idineeesasccxnosesennenns 5 1 1 Product designation vescccecncaustunnlconeuanvndvvvecewedeatesedacunsiulidaarieyrenepedeeen 5 12 SS PCCM CANONS nen eer eeta g Ne EE eaS E E E Rida REO 5 1 3 The delivery Set m rrsrercrip iesire aorta Eaa EERE EAE EKES 9 14 Alarmi OOPS hs a S G T 9 1 4 1 The loop configuration parameters 0ccccceceeeeeeeeeeeeeeeeeeeeeeeeeeees 10 TATI Loop TYPE enoe ee ae a e e E 11 1 4 1 2 Arming Delay sects ra veya espct see vases caucasian on gaan ao aumenua uaa 18 PASTS Intrusion Fire Delay onesie cri erste a a dclneneteuacivion ts 18 LATA Non disarming 3 Si seeGiilie a GTiae AES Ts GA Aas a 18 1 4 1 5 Auto Rearming When Disarmed 2 cccccccccsssssssesssseeeeeeenseaeeeeees 18 1 4 1 6 Auto Rearming when Fire Alarm ccccccccccessseeeeeeeeeeeeeeesanneeeees 1
40. ability principles and maintenance of version 2 03 of S2000 4 Intru sion amp Fire Alarm and Access Control Panel 1 PRODUCT DESCRIPTION 1 1 Product designation Intrusion amp Fire Alarm and Access Control Panel S2000 4 hereinafter referred to as panel is designated for usage in integrated safety systems to protect shops pay offices banks establishments plants and other ob jects from fire or intrusion threats and to meet access control needs The panel is intended to v monitor four alarm loops with burglary and fire detectors included v control internal and external sounders or light alarms v transmit alarm signals to S2000 S2000M console or PC via RS 485 interface and to the centralized surveillance station through two relay outputs Y control the access with the help of Touch Memory keys and Proximity Cards that is to read identifiers to check assigned authority and to switch the contacts of relay controlling electromechanic lock The panel is designated for usage either in integrated Orion system based on PC supplied by at least 7 issue ARM Orion 1 0 KD software or on S2000 version at least 1 20 or S2000M fire and alarm console or stand alone use The panel is to be mounted inside the premises and is destined for clock round duration The panel must not be used in aggressive medium or dust condition or in dangerous space The panel is intended to be used under temperatures from 233 to 323 K from
41. acts of the same name The readers having the useful cur rent above 100 MA or being located far from the panel 50 m or farther then to supply them one must use the separate wire pair connected to the power supply directly Is not in use 39 BOLID BOLD S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL If the reader is supplied separately the GND terminal minus of reader power must be connected to the GND contact of S2000 4 The reader having sole unicolored LED it control circuit is connected to the LEDG contact of the panel in case of reader being used only for access control If the reader is used for loop arming disarming only and ac cess control is not in use then the unicolored LED control circuit has to be connected to the LEDR contact of the panel S2000 4 The reader having not sounder control input or sounder is not re quired then the BEEP contact of the S2000 4 retains nonworking Some reader connection examples can be referred to at the Appen dix E The reader configuration parameters are presented in Table 11 Table 11 Reader configuration parameters vane The way of transmitting 1 Touch Memory tone of the read identifier 2 Wiegand yP code to the panel 3 ABA TRACK II The time of holding the Arming combined key card Disarming near the reader for loop 0 32 5 Combined Key arming disarming only on Holding Time for Touch Memory inter faced readers
42. ader light indicator switching red lighting to green and the internal sounder making two beeps Then the panel LED indicators 1 4 shall light one by one for short time with 0 5 s red and 0 5 s green light The relay 1 contacts close in the moment of LED 1 and 2 lighting but the relay 2 contacts close in the moment of LED 3 and 4 lighting 3 1 3 Testing of the reader connection circuits a Present the key or card unregistered by the panel to the reader b The reader light indicator shall light three times by red c The internal panel sounder and the reader sounder if presented and controlled by the panel shall make long Error sound If the panel doesn t respond to the presented key or card it can mean the inconsistency between the data format and the Reader interface Type of reader Touch Memory or 1 by default The absence of sound can mean that the Access typed signals are disabled for panel and reader sounders enabled by default 3 1 4 Alarm loop checking a The alarm loop being disconnected terminal resistor being dis connected measure the first alarm loop voltage It shall be within the range from 26 5 to 27 5 V 68 INSTALLER S AND USER S MANUAL STORAGE b Connect the terminal resistor 4 7 kKOhm to the LUC1 and read the ADC value by means of S2000 S2000M as follows Select the menu commands Request INFO and Zone ADC gradually Enter the panel address the default
43. aining Arming disarming by means of combined identifier is possible without Arming Disarming Readiness mode transit For this purpose one should give non zero value for the Combined Identifier Holding Time reader pa rameter If the combined identifier is presented to the reader and is held for some time then the corresponding alarm loops are armed or disarmed Short time presenting of combined identifier leads to access gaining with relay turning on and access gaining message generation being realized with some delay after identifier disappearing This arming disarming method can be used only for Touch Memory interface reader 23 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL If Combined Identifier Holding Time is set to zero then the method mentioned above is disabled and the panel gains the access instantly after combined identifier presenting The arming disarming can be realized by the corresponding com mands sending via RS 485 interface from PC S2000 S2000M console or one of the safety system Orion devices using the partition arm ing disarming mechanism Moreover to control fire and burglary alarm sys tem one can use S2000 4 panel see section 1 9 1 5 Relays The panel relays can be controlled by one of the following ways Local control in accordance with the assigned executive program depending on the connected alarm loop status Centralized control by means of commands
44. ation parameters If access control is in use then relay 1 assignment with the panel loops and relay control commands through the RS 485 interface are ig 1 5 4 The relay configuration parameters Table 6 Relay configuration parameters Default values Parameter Description Available when delivered name range Relay1 Relay 2 Defines the relay control Relay method depending on the 3 10 related loop statuses the i P Control pte 1 37 On for a Alarm out Prodrar initial relay status and the iine ut 1 g relay 1 control method p during the access control Rela The switching on or off from 1 to y period for the executive 8192 s in Control 100 0 Time programs with restricted increments operating time of 1 8 s The Relay Control Program parameter defines the relay control method realized via loops local control or relay 1 control method during the ac cess control or initial relay status from power supply turning on to the first receiv ing of the control command via RS 485 interface centralized control All avail able executive programs are shown in the Table 7 The Relay Control Time parameter gives the switching on or switching off period for the executive programs requiring the limited operat ing time Table 7 Relay executive programs Number Program description 1 On If Intrusion alarm or Fire alarm then ON else OFF 2 Off If Intrusion
45. cesc scare cccccdussecucccasseanavssvassiccrcuccdessqeestoavennnssssenaseccusadedsr ucts 67 3 L PANGSINCS TING isre EEA EE EE 67 3 1 1 Overall functional testing sesnvsscsncernscn teen ccc acess 68 3 1 2 Testing in diagnostic mode 2 00 ceeececceceeeeeeeeeeeeeeeeeeeeeeeeeeeeeesneeeeeees 68 3 1 3 Testing of the reader Connection circuits c cee ccccccceeeeeseeeeeeeeeeeees 68 3 1 4 Alarm loop CHECKING riren rai a a erent 68 A Storage sise erea PE aaa a Teraa EE RE Sadara aed CaF E EEEE iR 69 Appendix A S2000 4 overall and mounting dimensions c00 70 Appendix B S2000 4 connecting diagram cccceeeseeeeeeeeeeaeeeeeeeeeeeees 71 Appendix C Connection the detectors to the IOODS ccceeeeeeeeeeeee tees 72 Appendix D S2000 4 testing connection diagram ccccecceeeeeeeeeeeeees 73 Appendix E Reader Connection diagrams ccccceceeeseeeeeeeeaeeeeeeeeeeeeees 74 E1 S2000 Proxy and S2000 Proxy N reader connection 74 E2 Proxy 2A and Proxy 3A reader connection 0 ceeee 15 E3 PR A03 PR A05 or PR PO9 reader connection 76 E4 PR H03 PR H05 or PR MO9 reader connection TT E5 Touch Memory reader connection 0 cceeeeeeeeeeeeeeeeeeeees 78 Warranty eee e REEE e EEEO E EE 79 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION This Installers and User s manual is intended to help for studying op er
46. d status or are all dis armed otherwise The combined using for arming disarming and for access control identifiers in standard mode are used for access control To arm or disarm with the help of this identifier one has to switch the reader to the Arm ing Disarming Readiness mode To do this press the Arming Request button the button closes the DO circuit to the GND circuit and hold more than 1 s until the reader LED flashes Instead of Arming Request pressing one can close two Touch Memory reader terminals for the same time and after that during 30 s reader light pulsing the combined identifier will be considered as arming disarming one The Arming Disarming Readiness mode operates only for one reading and switches off after pre senting the identifier or after 20 s or in case of repeated Arming Request button pressing reader terminals closing If there are access blocking armed alarm loops the access control parameter Armed loop access blocking is on then when presenting of the combined identifier without Arming Disarming Readiness mode switching on the loop will be disarmed and the access will be gained simultaneously if identifier authority level are enabled to disarm access blocking alarm loops So it is necessary to switch the Arming Disarming Readiness on only when arming by means of combined identifier with disarming being realized after first combined card access g
47. d reader sounds Standbymode Tumedoff Long signal Error The main code is pre sented in case of dou Access One short signal ble identification Aeee anen The sequence from short two bys N ki g Access short and another two short sig y Sp y nals Access Opened Long signal followed by four short by special key signals Access Closed The sequence from two short an other two short and one more short signals Access Free Mode The panel sounder operates in al ternating tone mode siren The reader sounder operates in continuous mode with short pauses The recovering of ac cess normal mode Access by special key 46 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Status or event_ Category The panel sounder operates in the paused alternating tone mode paused siren The reader sounder operates in interrupted mode with 2 seconds period Sounder operates in interrupted Intrusion Alarm Alarm mode with 1 seconds period Sounder operates in interrupted En yaar mode with 0 25 seconds period Trouble fire loop short Short sounds with Alarm or open failures 2 seconds period Tamper Alarm t preki Sounder operates in interrupted tamper breaking in mode with 0 125 seconds period c 5 type loop Sounder operates in interrupted Door Forced Alarm mode with 0 25 seconds period until the door having been closed Door Left Open The door has been opening Four short signals bei
48. d to actuated detector being above 6 8 V The ripple voltage effective value does not exceed 20 mV If burglary detectors are included into the alarm loop the panel pro vides in standby mode the value of loop resistance being equal no more than 1 kOhm with out regard to external element the value of leakage resistance between wires or between any wire and ground being equal no less than 20 kOhm If fire detectors are included into the alarm loop the panel provides in standby mode the value of the loop resistance being equal to value no more than 100 Ohm without regard to external element the value of leakage resistance between wires or between any wire and ground being equal no less than 50 kOhm The panel supplies loop voltage for Okno Foton 8 and Volna 5 burglary detectors and for DIP fire detector The maximum number of one alarm loop connected detectors is demonstrated by Table 2 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Table 2 Maximum number of detectors connected to one loop Maximum number of detectors for different loop types Fire smoke loop Fire combined loop Burglary Detector type with recognition without two detectors alarm loop type 1 activated in one loop oad recognition type 2 pet Okno 4 Okno 5 Folon 8 Volna 5 Shorokh 1 Stecklo 2 DIP 3M DIP 3SU DIP U Note The value in the parentheses cor
49. de having been received the panel prompts to enter or to present extra code with reader LED beginning to blink by green with 5 HZ frequency T After that within 30 s it is necessary to present key or code to be written as extra for main one having been presented before To exit programming mode after adding and programming of the all the necessary keys one must present the same MASTER key that has switched the programming mode on Moreover the key programming mode finishes automatically in case of no key presenting and no tamper pressing having occurred within 30 s After programming mode exiting the panel and reader sounders make three short and one long sounds Programming Completed Ready LED lights in continuous mode and reader LED enters the standby indication mode Programming the keys without using of the computer has the follow ing restrictions It is impossible to program Opening Closing and subordinate MASTER keys It is impossible to assign the key validity period to the program ming key When double identification is in use it is impossible to program the key with without extra code attribute In case of key programming with the help of uprog exe program such restrictions are absent Moreover any key can be removed or blocked In addition the possibility of key text comments entering and stor ing in the memory remarkably simplifies the key list editing process 54 INSTALLER S AND USER S MANUAL AP
50. defined Some days are marked as Red letter Day or redefined in case of setting aside or redefined to values more than 7 if the special access time intervals are to be in use in such a days The second way One can create the complex and sliding access timetables or working timetables not attached to the calendar week In such a case all days in the list are given by weekday directly are redi rected To restrict the access or to arm disarm depending on the date and the time or key validity period the internal panel clocks have to be synchro nized It is supplied automatically when the panel operates as a part of safety system Orion based on PC or S2000M S2000 ver 1 20 or above In stand alone panel operation mode the access and arming disarming time restrictions or scheduled arming disarming are out of use If the parameters Scheduled Arming and Scheduled Disarming are set for any alarm loop then in the moment when the Arming Disarming Time Window time interval see Table 17 has been active the loop is disarming But in the moment when this time interval has been over the loop is attempted to arm Scheduled arming and disarming doesn t dis able other ways of alarm loop arming and disarming 1 9 Centralized access and partition control If the panel operates as a part of security system Orion it can work with identifiers registered by net controller with the proper privileges but not
51. dicates the certain alarm loops being armed the LED is lit or disarmed the LED is not lit It is defined by Reader LED Standby Mode parameter and the list of alarm loops which Loop Arming Reader Light Indication parameter is on The Loop Alarming Reader Light Indication parameter defines the list of loops which breaking are indicated by reader LED The Sound Control Polarity parameter defines the active logic level for reader sounder control similarly to the LED control polarity The reader sound indication parameters allow sounder going off for each signal categories see section 1 11 1 11 Light and sound signaling The panel uses the internal light indicators LED and internal sounder along with light and sound reader indicators to communicate sys tem information to you The messages signaled by panel READY light indicator are de scribed in Table 12 Table 12 Panel READY indicator lights Event or status Message description Operating mode Light indicator is on POWE SUPPIY IroubI amp Supply Indicator blinks with the 2 Hz frequency voltage is out of range MASTER key programming Indicator blinks in Time spaced short 42 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Event or status Message description O ooo tiie ashe s mode r Indicator blinks in Time spaced short Access keys programming iashes med Loop arming disarming keys Indicator blinks in Time spaced short
52. e detectors at the loop 2 or two heat detectors at the loop 3 being actuated or manual call point at the loop 4 being activated the panel enters the Fire Alarm mode with Intrusion Fire Delay Relay 1 Con trol Program 60 INSTALLER S AND USER S MANUAL APPLICATION the panel LED corresponding to this loop being blinking in short stopping mode with 1Hz frequency the panel sounder switching on the siren mode alternating tone the smoke elimination damper control delay relay 1 control delay beginning to count the Fire Alarm event message being transmitted to the net control ler Having received this message the net controller S2000 S2000M console gives commands to switch on the sound alarming in all the build ing including the turning on the panel relay 2 the delayed turning on the common smoke elimination system and commands to the relays controlling another common systems The light and audible alarming of S2000 S2000M console is turning on too After the ignition or smoking cause elimination the actuated loop re arming command is given from the S2000 S2000M console and the S2000 4 panel enters the standby mode 2 2 3 Burglary and fire alarm without access control The purpose is the part of burglary and fire alarm system for the pro tection of two separate rooms and one common room hall or waiting room Detectors in use are burglary fire smoke and fire h
53. e in cluded into alarm loop along with additional or shunt resistances Moreover one can control short or open failures of this loop Audible and light alarming and the influence of this loop to the relay are defined by the statuses this alarm can have Status changing of the programmable auxiliary alarm loop depends only on the alarm loop resistance changing and is not defined by any loop parameters or arming disarming commands The resolving time in case of status changing is equal to 300 ms If alarm loop is entering Armed Disarmed Aux Zone Restore or one of recovering statuses then the transition is considered as completed in The Alarm Loop Recovery Time seconds The programmable auxiliary alarm loop is impossible to disarm it is monitored permanently Received the programmable auxiliary loop arm ing disarming command the panel generates the current loop status mes sage Programmable auxiliary alarm loop status having been changed the corresponding messages are sent to the net controller S2000 S2000 M console or ARM Orion These messages are not storied in non volatile panel memory So if during net controller disconnection several status changes had occurred then when connection is recovered either only one message would be sent to the net controller or no messages would be sent if the current status is equal the last sent one 17 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL
54. e latest device This jumper is located near the A and the B terminals of the S2000 4 panel When wiring the RS 485 interface it should connect the devices to the chain If it is necessary to make long RS 485 interface branch longer than 50 m for example to reduce the cable length it is recommended to use the interface repeater S2000 PI One can use no more than 10 re peaters no more than 10 interface branches in one RS 485 interface 55 BOLID a S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL segment The number of in series S2000 PI repeaters the number of segments is not restricted 2 1 4 Changing the panel default settings In networking operation mode the panel has to be assigned with the unique net address in the range from 1 to 127 To assign the address connect the panel to the S2000 S2000M console or to the computer with other devices being disconnected from the RS 485 interface Being used the computer has to be connected with the panel through the RS 232 RS 485 interface converter such as S2000 PI or PI GR or S2000 USB or S2000 S2000M console Then change the default address of S2000 4 panel by means of S2000 S2000M console or uprog exe program running from the com puter To adjust the panel for the particular application and to gain full ca pability it is probably to change some configuration parameters with the help of uprog
55. e loops are disarmed and access is gained simultaneously For other keys either for access only or combined without blocking loops disarming privileges the access is prohibited Access closing because of loops is removed by means of blocking loops disarming 34 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION If the access has closed by Closing key or RS 485 interfaced com mand then Normal mode recovering is realized either by repeated pre senting of Closing key or by Opening key presenting or by net controller command via RS 485 interface The Access Opened mode entering is realized by Opening key pre senting or by net controller command via RS 485 interface It is accompa nied by reader LED green interrupted lighting with the 1 Hz frequency and short pauses In this mode the access is free and any identifier presenting is not required In Access Opened mode the corresponding relay is given by the panel opening action permanently so that the relay is continuously turned on off Therefore this mode must not be used for several type devices that cannot be powered all time The Normal access mode recovering is realized either by repeated presenting of Opening key or Closing key presenting or by net controller command via RS 485 interface 1 7 Double identification The panel reader can realize the specific operational mode when to identify the person it is necessary to present two identifiers instead of
56. eat detectors Device under control is siren Panel control algorithm is burglary loops arming disarming by means of Proximity cards with the Proximity reader being installed outside the protected premises in front of the entrance Loop 1 is used for the common placement burglary alarming Loop 2 and loop 3 are used for the separate room burglary alarming Loop 4 is used for all premises fire alarming The configuration parameters have to be set in accordance with the Table 21 Table 21 Configuration parameters Parameter Parameter value Comment 100p1 loop loop3 loop4 Loops from 1 to 3 are burglary arm Loop Type lt 4 j 4 2 Loop 4 is fire combined The reader is located outside Arming Delay 0 0 0 O the protected premises Arming delay is not required 61 S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL SECURITY SYSTEMS Parameter Parameter value Comment o0p1 loop2 loop loop4 Auto Rearming when Disarmed Relay 1 Control Centralized sounder alarm con trol follows the Fire signal formed be any building device Relay 2 Control The relay 2 is not used Common Zone List of ASso ciated Alarm Loops Control Program Loop 1 is the common zone for loop 2 and loop 3 Defines the initial relay status turned off The relay 1 control LAREN Os tactics Siren is given at the net controller Relay 2 Control Program Defines the initial relay status
57. ed by panel itself without PC To do this it is necessary to open the panel cover and gradually realize one long more than 1 5 s one short less then 0 5 s and one more long tam per pressing The pauses between pressings must not exceed 0 5 s In such a case the panel and reader sounders make the MASTER programming melody The Ready LED of the panel and reader LED syn chronously blinks by twice flashes with reader LED flushing twice by red and twice by green After that it is necessary within 30 s to present the identifier to be programmed The panel and reader sounders will make the end of the MASTER programming melody with the Ready LED and reader LED en ter the continual mode Attention The MASTER key programming with the help of tam per removes all keys having been recorded by the panel before The MASTER key programming by means of uprog exe program does not affect upon the keys programmed earlier If the programming key mode is entered with the help of MAIN MASTER key then the programmed key status can be changed by means of tamper Long more than 1 5 s tamper pressing switches the Access and User Code attributes of the programming keys successively between the only access only arming disarming and Access and arm ing disarming combined values When the User Code attribute is set for the programmed key then tamper short pressing series changes the key loop arming disarming
58. ed delay when the panel does not enter to the Fire Prealarm status due to the time conditions In this case type 1 or 3 alarm loop can enter the Fire Alarm status only along with second loop detector actuation but type 2 alarm loop can not enter the Fire Alarm status under any conditions 1 4 1 4 Non disarming The parameter Non disarming prohibits loop disarming This pa rameter is used to prevent fire or alarming loop incident disarming If alarm loop is entering Intrusion Alarm Silent Alarm Fire Prealarm Fire Alarm or Arm Failed statuses then arming and disarming of the alarm loop will lead to attempt to arm this loop ALARM RESET As a result the alarm loop will enter the Armed status the loop resistance is within the normal range or the Arm Failed status the alarm loop is broken 1 4 1 5 Auto Rearming When Disarmed When the alarm loop has entered the Arm Failed status the loop was broken when arming and if the parameter Auto Rearming When Disarmed is set for this alarm loop then the alarm loop will automatically enter the Armed state when it resistance will be in normal range 18 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION 1 4 1 6 Auto Rearming when Fire Alarm When the alarm loop has entered the Intrusion Alarm Silent Alarm or Fire Alarm statuses and the parameter Auto Rearming When Fire Alarm is set then
59. ee categories such as Access Alarm and Programming see Table 15 The internal panel sounder going off is defined by the corresponding parameters status To change the configuration parameters use the uprog exe pro gram versions 4 0 0 810 or above ATTENTION Don t use the earlier versions of uprog exe program or S2000 S2000M console for changing of the configuration parameters The program uprog exe runs under Windows 98 or above operational systems To connect the panel to the COM port use the interface converter such as PI GR S2000 PI S2000 console version 1 20 or above or S2000M console The latest version of device configuring program uprog exe along with the related information is available at the www bolid ru 1 13 Identifiers Identifiers such as Touch Memory keys Proximity cards or PIN codes can be used along with the S2000 4 panel with the aim of access gaining alarm loop arming disarming partition arming disarming access opening and closing other identifiers programming recording into the panel memory The identifiers have to be recorded into the S2000 4 panel memory except for identifiers used for partition control or centralized access which are recorded only into the net controller database 1 13 1 Identifier parameters Up to 2048 identifiers can be entered to the panel database They can be Touch Memory keys or Proximity cards or PIN codes
60. el mem ory can be access limited by the following factors date and time if the time window for this key access is not active see 1 7 section key validity period if it has elapsed or has not yet begun in Access Closed mode when access blocking alarm loops are armed or access is closed by RS 485 interfaced command or by special Closing key see section 1 6 2 If the electromagnetic lock or latch being in use is connected to the same power supply as the device then it should be supplied by separate wire It is recommended to supply the electromagnetic locks by separate power source If the electromagnetic lock design is not provided with the scheme of sup pression of high voltage pulse appearing during the commutation it is necessary to connect the lock terminals in parallel with the reverse directed diode with di rect diode current available being no more than 1 A 1 6 1 Access control configuration parameters The configuration parameters dealing with the access control process are shown in Table 8 31 BOLID T S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Table 8 Access control configuration parameters value Access Control On Off Door Opening Door opening detector is On Off Detector connected Passed Event To form the Passed event On Off Door Burglary To control the unauthorized On Off Control door openings Door Blocking To control the time the door On Off control having be
61. en opened Door Blocking Available duration of the 1 255s Time Out door having been opened Bi 30 Turn Relay 1 Off B EE ean When Door when incomer have opened Is Opening the door Pre schedule interrupt of rur ae 1 Off relay 1 opening program When Sor when incomer have closed Is Closing the door The number of the access 0 65535 zone with entering con 65535 ee trolled by the panel being means 65535 used as a part of the sys zone tem undefined To Deny Ac cess if Any Pointed Loop Is Armed oe om The list of access denying alarm loops any being On Off armed Or denying cess if All joop2 The list of access denying Pointed alarm loops all being armed On Off Loops Are And denying Armed O O O O O O O O O O O O ff ff n S n ff n n n ff ff ff ff ff The parameter Access Control activates the access control func tions of the panel If this parameter is off the access control is not realized with the first loop being of any type and the first relay being controlled by loops with the help of any programs local or centralized 32 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Further lets suppose the Access Control parameter to be set on The Door Opening Detector parameter setting on indicates the usage of the door opening detector In such a case After access gaining the panel is waiting for the door opening pass ing within Relay
62. es sense to switch relay on immediately after power turning on In such a case it is necessary to give the relay any executive program assuming the initial turned on status for example the program 2 Turn off 1 5 3 Turning relay on off during access controlling When the access control is in use it is necessary to give the Relay Controlling Program and the Relay Control Time for the relay 1 The Relay 1 Controlling loop parameter defines if the relay 1 turns on or not during access controlling Only the executive programs 3 On for a time and 4 Off for a time are available The executive programs 3 On for a time is used for electrome chanical locks or latches controlling Initially the relay is off but in case of access gaining the relay is turning on closing for a given time The executive programs 4 Off for a time is used for electromag netic locks or latches controlling Initially the relay is on but in case of ac cess gaining the relay is turning off opening for a given time The Relay 1 Control Time parameter defines the maximum turning on off time when access gaining The actual relay 1 control time when ac cess gaining can be less or equal to the pointed time see Turn Relay 1 25 SECURITY SYSTEMS nored S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Off When Door Is Opening and Turn Relay 1 Off When Door Is Closing access control configur
63. exe program versions 4 0 0 810 or above see 1 12 section In case of usage the panel along with the access identifiers it is nec essary to record corresponding Touch Memory keys Proximity cards PIN codes or other identifiers to the panel memory For local access control arming and disarming the identifiers have to be recorded to the panel memory in accordance with the 1 13 2 section of this manual but for cen tralized access control arming and disarming the identifiers have to be re corded into the net controller memory 2 2 Typical application 2 2 1 Fire alarm system without access control at the small object The purpose is light and sound alarming of fire at the small object Detectors in use are fire smoke detectors fire heat detectors and fire manual call points Devices under control are light and sound annunciators Panel control algorithm is actuated loop rearming by means of Touch Memory key The configuration parameters have to be set in accordance with the Table 19 56 INSTALLER S AND USER S MANUAL APPLICATION Table 19 Configuration parameters Parameter value vane Parameter loop loop2 loop3 loop4 Comment The smoke detectors without additional resistors are included into the loops 1 Alarm loop 2 and 2 Heat detectors are included into type the loop 3 and manual call points both normally closed or opened are included to the alarm loop 4 oja enter the Fire Alarm mode in case Int
64. f loop resistance and the corresponding status can be shown at the Table 5 The diagram of connection burglary detector with tamper check to the type 5 alarm loop is contained into the Appendix C The type 6 is the auxiliary alarm loop The auxiliary alarm loop is intended to control the door status in gas fire extinguishing systems to control the status actuations and operability of extinguishing equipment and to control the detectors or other equipment independent from burglary or fire alarming The detectors or devices with dry contact output normally opened or closed or with open collector output are included in alarm loop of this type The alarm loop statuses can be Aux Zone Alarm Aux Zone Restore If the alarm loop resistance has come out of 2 6 kOhm range for more than 300 ms the loop has entered the Aux Zone Alarm status The loop resistance having been within 2 6 kOhm range for more than The Alarm Loop Recovery Time sec the loop has entered the Aux Zone Re store status The auxiliary alarm loop is impossible to disarm it is moni tored permanently Having received the arming disarming command the panel generates the current loop status message Alarm loop status having been changed the corresponding mes sages are sent to the net controller S2000 S2000 M console or ARM Orion These messages are not storied in non volatile panel memory So if during net control
65. g mode entering is realized by MAIN MASTER key Otherwise the program ming keys succeed MASTER key attributes apart from key type and with out editing feature If several MASTER keys assume to be used it is necessary to pro gram them with the help of uprog exe program To enter the programming mode of keys designed for arm ing disarming or access it is necessary to present the MASTER key to the panel connected reader The panel and reader sounders would make three double short sounds with reader LED lighting alternately by red and green once twice or trial see the Table 18 In such mode the identifier pre sented are recorded to the panel memory with the MASTER key parame 53 BOLID BOLD S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL ters If the MAIN MASTER key was used then the programming key pa rameters can be changed with the help of tamper If the MAIN MASTER key was used the programming key parameters can be edited by means of tamper Twice short sound and 2 second longed reader LED green lighting when the identifier is presented mean that the new code has been entered to the panel or current key parameters have been changed Single short sound and 1 second longed reader LED green lighting mean that such key with given parameters has already exist The long sound and trial red blinking of reader LED mean the key entering fail ure the memory is full If the panel uses double identification then after main co
66. g Disarming Combined Key Holding Time parameter allows to control loop arming and disarming with the help of combined key without previ ously panel switching to the Arming Disarming Readiness mode To arm disarm the loop one shall hold the key near the reader for this time To 41 BOLID BOLD S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL gain the access one shall present the combined key to the reader for short time actual relay being switched on in the moment of removing the key from the reader By default when the S2000 4 panel has just been delivered the Arming Disarming Combined Key Holding Time parameter is set to zero so that such a way of loop arming disarming is off with combined card ac cess being gained instantly when the key is presented not when removed The Double Identification parameter setting means that to recognize the same person it is necessary to present two identifiers instead of one see the section 1 7 The LED Control Polarity parameter defines the active logic level for reader red and green LED control If the direct polarity is given then the LED switching on is realized by logical 1 level issue to the LEDG and LEDR contacts of the panel If the reverse control polarity is given then the LED switching on is realized by logical O level issue In standby mode the reader LED can be either always turned off or turned on with the red lighting or in
67. ime after access gaining the door is enabled to be opened When door is opening the electromechanical voltage is removed 66 INSTALLER S AND USER S MANUAL MAINTENANCE and being returning to the initial status the door has just been closed re gardless of passing duration In the loops 1 3 Intrusion Alarm or loop 4 Fire Alarm the panel transmits the messages analogous those described in section 2 2 3 3 MAINTENANCE To make sure that the panel is in reliable working condition test it on receipt and once a year The testing shall include Visual inspection of the possible mechanical damage of the panel case Inspection of the panel mounting security and contacting wire and contact coupling statuses Functional testing of the panel efficiency identically with the section 3 1 of this manual 3 1 Panel testing The purpose of this testing is the panel receiving inspection The test includes the functional check with the aim of showing up possible defects and their operability status estimation If the panel doesn t meet the re quirements of the checking procedure described below then appeal to the manufacturer The panel shall be tested under the following ambient conditions Temperature 25 10 C Relative humidity 45 80 Atmospheric pressure 630 800 mm Hg The S2000 4 testing connection diagram is presented in the Ap pendix D The operability status testing time is no more than
68. itching on will be resumed but for the programs 3 4 7 8 34 and 35 the switching will not be on Thus the auxiliary loop breaking holds the time 24 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION unlimited programs along with programs 11 and 33 and cancels time re stricted programs along with programs 12 34 and 35 If the panel loops are assigned with the relays then control com mands via RS 485 interface will be ignored and the local relay control will be in use 1 5 2 Relay centralized control To control the relays via RS 485 interface it is necessary to Turn off the Relay 1 Control and Relay 2 Control loop parameters Define the executive program with the corresponding initial relay status turned on or off Assign this relays with the corresponding partition in the net control ler configuration define the executive program give the control de lay and the control time In case of relays being not assigned with the loops the Relay Control Program parameter defines only the initial status of relay that is the status which relay will be set to under the power turning on until the first central ized command will be received Usually the programs with turned off ini tial statuses are used for example the program 1 Turn on After the power turning the centralized control command can be re ceived after some time so if centralized command supposes the turned on initial statuses it mak
69. ken if its resistance is out of 2 6 kOhm range When breaking in armed status the alarming loop enter the Silent alarm status This status is indicated only by inner panel LED 1 4 and influences the relay controlled by means of 10 program Alarm out put 1 or 16 program Alarm output 2 with relay being opened The inner 16 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION audible sounders of panel and reader don t make sounds and reader LED don t change it status This type 11 alarm loop resolving time equal 300 ms The compatibility of loop resistance and the corresponding status can be shown at the Table 5 The diagram of connection call points and other alarm annunciators to the type 11 alarm loop is contained into the Appendix C The type 12 is the programmable auxiliary alarm loop This type alarm loop can be used to control the variety of equipment among them the devices not dealing with burglary or fire alarming The detectors or devices with dry contact output normally opened or closed or with open collector output are included in alarm loop of this type The programmable auxiliary alarm loop can have up to 5 various statuses that are defined by loop resistance One can program both statuses and the corresponding threshold resistance values In so manner the equipment having several statuses and associated output contact groups can be monitored by means of one alarm loop if groups ar
70. l actuated loops arming programmed key shall be presented to the reader The panel will enter the standby mode 2 2 2 Fire alarm system without access control at the large object The purpose is fire alarm and smoke elimination from the part of the object some adjacent premises one floor the part of the building and so on Detectors in use are fire smoke detectors fire heat detectors and fire manual call points Devices under control are sound annunciator and smoke elimination system damper Panel control algorithm is arming and disarming by the command from S2000 S2000M console or computer supplied with ARM Orion software The reader is not connected sound notification control is centralized in case of any placed ignition with S2000 S2000M console or ARM Orion control the second panel relay The common smoke elimination system turning on sending of the Fire signal to the local Fire Department and another common system con trol are centralized with S2000 S2000M console or ARM Orion con trolling the S2000 SP1 unit relays The configuration parameters have to be set in accordance with the Table 20 Table 20 Configuration parameters 100p1 Ioop2 100p3 100p4 1 1 3 2 The smoke detectors are included to the loop 1 and the loop 2 the heat Alarm loop detectors are included to the loop 3 type and manual call points both normally opened and closed are included to the
71. l to 65535 Passing events with such of access zone number are not retranslated to the other devices Local access by means of S2000 4 panel recorded the panel are armed If the access blocking is required in case of arming any from the pointed loops one must include these loops to the list of To Deny Access if Any Pointed Loop Is Armed parameter If the access blocking is required in case of only all pointed loops arming one must include these loops to the list of To Deny Access if All Pointed Loop Are Armed parameter 1 6 2 Access modes The panel can have one access mode from three available ones Normal Access closed Access opened In Normal access mode the access is gained for such identifiers keys which are recorded to the panel database have the Access attrib ute are not blocked have no expired key validity period and have no time zone offences The panel enters the Access closed mode in such a case arming of the loops blocking access special Closing key presenting net controller command via RS 485 interface If the access is closed by Closing key or command then reader LED enters the interrupted red light mode with the 1 Hz frequency and short pauses In such a case the access is closed for all panel recorded keys It the access is closed by reason of blocking access loops being armed then in case of combined key having disarming this loops privileges presenting th
72. lay was given as 0 then the transition from Fire prealarm to Fire alarm mode would happen instantly If Intru sion Fire delay was given as maximum value 255 then the transition from Fire prealarm to Fire alarm would be impossible The type 2 alarm loop resolving time is 300 ms The compatibility of loop resistance and the corresponding status can be shown at the Table 5 The diagram of connection the fire smoke normally opened and heat normally closed detectors to the type 2 alarm loop is contained into the Appendix C The type 3 is the fire heat loop with double actuation recogni tion The fire heat normally closed detectors are included into the alarm loop The alarm loop statuses can be Armed the alarm loop is monitored and the resistance is in normal range Disarmed the alarm loop is not monitored Arming delay the arming delay has not yet been elapsed Fire prealarm the one detector actuation has been fixed Fire alarm actuating more than one detector has been fixed or af ter one detector actuation the Intrusion Fire delay has expired Loop trbl short the alarm loop resistance is less than 2 KOhm Loop trbl open the alarm loop resistance is more than 50 KOhm Arm Failed the alarm loop was broken when arming When the detector in such alarm loop has actuated the panel enters the Fire Prealarm mode The panel enters the
73. ler disconnection several status changes had occurred then when connection recovering either only one message would be sent to the net controller or no messages would be sent if the current status is equal the last sent one Auxiliary alarm loop being associated with a relay it failure blocks up the relay turning on assigning to the 1 8 11 12 33 34 35 programs see 1 5 1 section of this Manual This feature can be used for example for creating the gas fire extinguishing system with launch blocking dealing with opened door to the protected premises The compatibility of loop resistance and the corresponding status can be shown at the Table 5 The connection of normally opened or normally closed detectors and other controlled dry contact circuits to the type 6 alarm loop is identical to the connection of burglary detectors to type 4 loop see Appendix C 15 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL The type 7 is the entering alarm loop All types of burglary detectors including opening or closing power less or power supplied via alarm loop or separately are included into the type 7 alarm loop The alarm loop statuses can be Armed the alarm loop is monitored and the resistance is in normal range Disarmed the alarm loop is not monitored Arming Delay the arming delay has not yet been elapsed Entry Alarm the loop breaking has been fixed Intrusion Alarm
74. n off open alarm loop been re Actuation of two or more alarm 3 short cir stored after one heat heat detec loop cuit any failure detector tors open cir cuit less 1 8 from 2 2 to from 6 6 to from 12 5 to more KOhm 5 4 KOhm 11 KOhm 30 KOhmM than 50 kOhm 4 Loop trbl rst Burglary from 2 2 to 5 4 kKOhm less than 1 8 KOhm or more than 6 6 kOhm or more than 10 hop off Fire Heat 21 BOLID BOLD S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Loop type Alarm loop statuses 5 Loop trbl rst from 2 2 to less than 1 8 KOhm from 6 6 KOhm to 9 0 kKOhm Burglary 5 4 khOm or more than 6 6 or more than 20 kOhm with tam per check ig kOhm in Armed Arm delay or in Armed status Arm failed statuses 6 Aux zone restore Aux zone alarm Auxiliary from 2 2 to 5 4 KOhm less then m sae or more than 6 KOhm Loop trbl rst Entry alarm 7 from 2 2 to 5 4 KOhMm less then 1 8 KOhm or more than Entering 6 6 kOhm or more than 10 hop off 11 Loop trbl rst Silent alarm attack Alarming from 2 2 to 5 4 KOhm less then i See or more than 6 KOhmM 42 Status 1 Status 2 Status 3 Status 4 Status 5 less then from R1 from R2 from R3 more than R1 to R2 to R3 to R4 R4 alarm loop statuses and threshold resistances are pro grammable Auxiliary Program mable 1 4 2 Loop arming and disarming Fire types 1 2 or 3 alarm loops burglary types 4 5 and 7 alarm
75. ned on After latest separate placement arming loops 2 and 3 the common placement loop 1 is armed automatically Any separate placement disarming leads to automatically common placement disarming In case of breaking of armed loop the panel enters the Alarm mode with the panel LED corresponding to breaking loop and reader LED be ginning to blink regularly with 2 Hz frequency the panel sounder turning on in interrupted mode with 2 Hz fre quency the Intrusion Alarm event message being transmitted to the net controller S2000 S2000M Having received this message S2000 S2000M console gives light and audible alarm turning on command with S2000 S2000M light and audible alarm turning on too In case of loop 4 fire detector actuation the panel enters the Fire mode with the corresponding panel LED beginning to blink in short stopping mode with 1 Hz frequency the panel sounder turning on in Siren mode alternating tone the Fire Alarm event message being transmitted to the net control ler 63 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Having received this message S2000 S2000M console gives the command to turn on the light and audible alarming in all building including the panel relay 1 turning on with S2000 S2000M light and audible alarm turning on too After the ignition or smoking cause elimination the loop 4 arming command i
76. ng or having been armed or re sistance jump more than 10 when the loop is armed The breaking of the armed loop leads this one to the Intrusion Alarm status The type 4 alarm loop resolving time is 70 ms The compatibility of loop resistance and the corresponding status can be shown at the Table 5 The diagram of connection burglary detector to the type 4 alarm loop is contained into the Appendix C The type 5 is the burglary alarm loop with tamper check The alarm loop includes burglary detector with normally closed con tacts and tamper detector The alarm loop statuses can be Armed the alarm loop is monitored and the resistance is in normal range Disarmed the alarm loop is not monitored Arming Delay the arming delay has not yet been elapsed Intrusion Alarm the detector breaking has been fixed Arm Failed the alarm loop was broken when arming Tamper Alarm the loop being disarmed the tamper has actuated When alarm loop is armed the detector actuation opening of its bur glary contact or tamper actuation switches the loop to the Intrusion Alarm mode When alarm loop is not armed being in statuses Disarmed Arm 14 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION delay or Arm failed tamper actuation switches the loop to the Tamper Alarm status The type 5 alarm loop resolving time is 70 ms The compatibility o
77. ng repeated a Alarm more than Door with some seconds period Blocking Time Out Entering to the key Program Three pairs of short sounds Pro programming mode ming gramming Exiting from the key Program Three short and long sounds programming mode ming Programming Finishing Entering to the at MASTER key Program The MASTER Programming programming mode mng melody MASTER key has been The end of MASTER programmed ming programming melody Adding of new key or changing parameters of the existing key the panel being in the key programming mode Presenting of the exis tent key in the key pro gramming mode Fire Prealarm Alarm Program Two short signals Key Recording ming Confirmation Program Short sound The key has been ming already recorded 47 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Any signal category can be disabled for both panel and reader sounder 1 12 Configuration parameters Following are the seven configuration parameter groups system configuration parameters loop parameters see Table 4 relay parameters see Table 6 access control parameters see Table 8 reader configuration parameters see Table 11 time window parameters see the section 1 7 identifier configuration parameters see Table 17 System configuration parameters are shown in Table 16 Other con figuration parameters are considered at the correspondi
78. ng sections Table 16 System configuration parameters Parameter Description Derat value RS 485 interface Net address n taddicde 1 127 MASTER The main MASTER key P generation by means of the rogramming Inhibit panel tamper detector i is inhibited The maximum number of PIN code digits for readers PIN code max with Wiegand interface length transmitting the PIN code to the panel one digit after one Access 3BykoBaa cnrHannzayna B npn6ope o npegocTtasBne Alarm Hnn sanpeTe Aoctyna Tpe Borax n BKNIOYEHNN pexKumMa Program 7 3 nporpammuposBauua Kniouen ming Net address parameter is used for RS 485 communications When having been connected to the Orion safety system the panel has to be assigned with net address 48 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION The MASTER Programming Inhibit parameter turning on inhibits the procedure of programming the main MASTER key with the help of the panel tamper In such a case the panel key recording is possible only from the computer or by means of previously generated MASTER keys If the Wiegand interfaced keypad transmitting the PIN code to the panel one digit after one is used as a reader then the code entering is con sidered as completed when the number of digits entered has reached the PIN code max length parameter To complete the less codes entering press button code 0B hex on the keypad All available panel sounds are divided into thr
79. oke loop with double actuation recognition loop loop R 1 5 KOhm 5 for DIP 3SU DIP U actuated detector voltage is from 7 5 V to 8 5 V R 2 2 KOhm 5 for 2100 2151E actuated detector voltage is from 4 V to 5 V R 2 4 KOhm 5 for IP 101A actuated detector voltage is from 3 5 V to 4 V R 3 KOhm 5 for detectors with dry contact type output circuit Connection of normally opened smoke and normally closed heat fire detectors into the type 2 fire combined alarm loop loop R 0 for DIP 3M DIP 3SU DIP U 2100 2151E actuated detector voltage is more than 4V R 510 Ohm for IP 101A IPR513 3 and for detectors with dry contact type output circuit actuated detector voltage is less than 4V Connection of normally closed heat fire detectors into the type 3 fire heat with double actuation recognition alarm loop 72 Connection of normally closed and normally opened burglary detectors to the type 4 burglary 7 entering n 11 alarming alarm loops loop Connection of burglary detectors with tamper contacts into the type 5 Burglary with tamper check alarm loop 13 KOhm loop Connection of EXIT button and door opening detector into the type 4 burglary or type 7 entering alarm loop in case of access controlling door opening detector loop EXIT button 4 7 KOhM 1 KOhM loop APPENDIX D S2000 4 TESTING CONNECTION DIAGRAM
80. one e g Proximity card followed by PIN code Such a mode is called as double identification and to enter it the Double Identification parameter shall be set If the parameter Double Identification is set this mode will be used not only for access and arming disarming keys but for special keys MASTER Opening Closing The double identification procedure begins with the presenting of the first identifier or Main Code If this key is recognized the panel enters to the mode of waiting for the second identifier or Extra Code and the reader light indicator blinks with green color and 5 Hz frequency For half a minute it is necessary to present the extra identifier If the second identifier presented is not coincided with extra code then the message Illegal Code with the Extra Code Error attribute is generated If the extra code presented is correct then the identification procedure is considered as successful and the panel executes such action the pre sented key is assigned to access gaining alarm arming disarming key programming mode entering or access opening or closing If the identification procedure needs to be simplified for some keys when all other keys have to be double identified one can set Without Extra Code for given keys To identify with the help of such keys it is enough to present only main key without extra one 35 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Since in case of double
81. oops have en tered the Fire alarm status and there are no broken auxiliary loops then ON for a given time The breaking of an auxiliary loop blocks switching on If the auxiliary loop has broken during the re lay control delay then when recovering the output will be turned ON for a given time the auxiliary loop breaking holds the turning on delay counting Else OFF 27 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Number Program description 12 SIREN If Fire alarm then blink for a given time 1 5 s ON and 0 5 s OFF if Fire Prealarm then blink for a given time 0 5 s ON and 1 5 s OFF if Intrusion alarm then ON for a given time else OFF 13 Fire output If Fire alarm or Fire prealarm then ON close output else OFF open output Output FAULT If there are loops having the statuses Fire trouble Disarmed or Arm failed then 1a switches output OFF opens else ON closed output Fire LAMP In case of Fire alarm switches in interrupted mode 0 25 s ON and 0 25 s OFF In case of Fire prealarm switches in inter rupted mode 0 25 s ON and 0 75 s OFF In cases of Intrusion alarm Entry alarm or 15 Arm failed switches in interrupted mode 0 5 s ON and 0 5 s OFF In case of Fire trouble switches in interrupted mode 0 25 s ON and 1 75 s OFF If all associated loops are armed switches o
82. or opening detector if used are included into the first panel alarm loop in accordance with the connection diagram 30 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION being contained to the appendix C The parameter Loop Type has to be selected as Burglary type 4 or Entering type 7 The relay 1 in this case is used to control electromagnetic lock To control the electromechanical lock the executive program 3 is used On for a time but for electromagnetic lock control it should select the program 4 Off for a time The parameter Relay 1 Control Time defines the maxi mum period of relay being turned on off when access providing The relay binding with loops and external control commands apart from the access control commands are ignored If the presented identifier Proximity card or Touch Memory keys is registered in the panel memory then the S2000 4 panel resolves if the access will be gained on base of key authority level current access mode and key access violation presence This is the local control process If the presented identifier is not registered in the panel memory then it will be transmitted to the net controller ARM Orion which has to come to a decision about access granting or prohibiting This centralized control is possible if the panel operate as a part of the safety system controlled by PC Access attributed keys being written into the S2000 4 pan
83. pa rameters Relay 1 Control and Relay 2 Control have to be turned off even though this alarm loop is included to the partition affecting upon the panel relay 1 4 1 10 Relay 1 and Relay 2 Control Delays If the alarm loop status changing is to lead to the relay switching in accordance with the executive relay programs then turning relay 1 or 2 on off takes place not at once but after some Relay 1 Control Delay or Relay 2 Control Delay period given for this alarm loop For the executive programs 9 10 13 14 15 and 16 see the Table 7 these parameters are ignored and relays switches straight after the alarm loop status having been changed 19 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL 1 4 1 11 Scheduled Arming and Disarming The parameters Scheduled Arming and Scheduled Disarming turn loop auto arming and disarming on at the given time To give the time of auto arming or auto disarming the parameter Time Window for sched uled arming disarming is used At a moment when the Time Window For Scheduled Arm ing Disarming has been active the loop is disarmed if Scheduled Disarm ing is on When the Time Window For Scheduled Arming Disarming has been finished the loop disarming is tried on Scheduled Arming and Disarming are enabled only in networking op eration mode of the panel as a part of Orion system with the panel date and time being synchronized
84. programming double flashes mode Access keys and arm ing disarming combined keys programming Test operation mode Indicator blinks with the 5 Hz frequency The messages signaled by reader light indicator are described in Table 13 Indicator blinks in Time spaced short triple flashes mode Table 13 Reader indicator lights Panel status Light operating mode Lighting Reader LED standby Off lt Standby mode is 1 off mode that is no alarms Asse et ee On if the loop is armed Red and normal Mode is 2 or 3 loop otherwise is off e access arming indication mode Reader LED standby mode is 4 red light On Blinks in Short stop Fire Alarm ping mode with 1 Hz Red frequency Blinks in Flashing Fire Prealarm mode with 1 Hz fre Red quency Blinking with the 2 Hz frequency Blinks in Short flash Yellow ing mode with o 5 Hz green frequency red Intrusion Alarm or Entry Alarm Red Trouble Loop Trbl Open or Loop Trbl Short Tamper Alarm detector tamper opening in type 5 loop Blinking with the 2 Hz frequency Red 43 BOLID BOLD S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Panel status Light operating mode Lighting Biinking wihtheDHe a o frequency E Aux Zone Alarm Blinking with the 2 Hz frequency Blinks in Short stop Access Closed ping mode with 1 Hz frequency Blinks in Short stop Access
85. recorded to the panel database Such identifiers can be used for cen tralized control only if the system is controlled by ARM Orion And they can be used for partition arming disarming if the system is controlled by ARM Orion or S2000 S2000M console Like local the centralized keys can be combined for access gaining and arming disarming both More over the local access gaining can be in tegrated with the centralized partition control for keys being recorded to the panel database with the Access attribute 37 SECURITY SYSTEMS S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL If unknown identifier is presented to the panel connected reader its code is transmitted to the computer or console The reader light indicator is switching from red to green alternately with the 5 Hz frequency until the computer or console response has been received It can takes from a frac tion up to a few seconds depending on the number of devices being con nected to the RS 485 interface If the net controller decides to gain the access the centralized access is available along with the local one If the key presented is assigned with the partition control privileges then the reader LED displays the current partition status accordingly to the Table 9 The second presenting of this key leads to arming of disarmed partition or to disarming at any other case Each subsequent identifier pre senting causes the action contrary to preceding one that is if the
86. responds to the detector s number in case of both smoke current consumed normally opened and passive heat normally closed detectors being combined in one loop The number of other types detectors is calculated based on maxi mum load current being equal to 3 mA or 1 2 mA in case of type 2 alarm loop with both smoke or heat detectors being used together In case of type 1 alarm loop using the detectors must retain their operability during loop voltage dropping to 12 V Only one Touch Memory key or Proximity Card or PIN code reader can be connected to the panel The reader output interface is to be Touch Memory 1 Wire u LAN Wiegand or ABA TRACK II magnetic card inter face The panel provides the reader s LED control with directly connected LED current being restricted up to 10 mA The panel supplies the reader s sounder control The quit options for LED and sounder control are 5V 10mA The distance between the panel and connected reader must not exceed 100 m The identifier storage capacity of the panel is 2048 The number of control relays for locking arrangement is two with each relay maximum switching current being equal 7 A maximum commu tating voltage being equal 30V and maximum switching power being equal 100 W Following are the messages being transmitted by the panel to the net controller both ARM Orion or S2000 S2000M console via RS 485 in terface USER S CODE ENTR The user has entered arming di
87. rusion ofo one fire detector actuation bypassing Fire Delay the Fire Prealarm mode All loops are always armed The arming Non On On On On command is used only for actuated disarming alarm loop rearming Auto Re If during rearming the alarm loop has arming not been restored Arm Failed has oc when Dis Se da R el curred then it will be automatically ar armed med after loop having been recovered Auto Re The recovering of the Armed mode ARIA after Fire Alarm status is possible only Cras Off Off Off Off by means of operator command pre Fire Alarm senting of the loop arming Touch Mem ory key to the Touch Memory reader SETAN on Light annunciator Lamp control a Sound annunciator Siren control The 60 s delay is given to the user to Relay 2 rearm actuated loop without siren get Control 60s 60s 60s Os ting off in case of false detector actua Delay tion The siren is gone off if the signal was received fron the manual call point Relay 1 Control 15 Program Relay 2 Control The program Siren controls the exter nal sound annunciator Program Relay 2 Con 420 The maximum time of siren going off trol Time 3 during the fire is 2 minutes 57 The program Fire LAMP controls the external light annunciator BOLID ay S 2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Access coe we Reader Interface 1 Touch Memory Type LED Control direct active 1 Polari
88. s given from the S2000 S2000M console and the S2000 4 panel enters the standby mode 2 2 4 Burglary and fire alarm along with access control The purpose is the burglary and fire alarm and protected premises access control as a part of safety system Detectors in use are magnetic contact detector door opening detector in loop1 volumetric alarm detector and glass break detector in loops 2 and 3 fire smoke or heat detectors in loop 4 Devices under control are the electromechanical latch in case of ac cess control and the siren in case of fire Panel control algorithm is burglary loops arming disarming by means of Proximity cards with the Proximity reader being installed outside the protected premises in front of the entrance The configuration parameters have to be set in accordance with the Table 22 Table 22 Configuration parameters loop1 o0p2 toop3 ioop4 Loops from 1 to 3 are burglary Alarm Loop Type Loop 4 is fire combined The reader is located outside the protected premises Arming delay is not required Arming Delay Auto Rearming when Disarmed 4 4 4 0 0 0 Off Off Off The relay 1 is used for electro Off Off Off mechanical latch control and is not loop controlled Relay 1 Control Centralized sounder alarm con Off Off Off trol follows the Fire signal formed be any building device Relay 2 Control 64 INSTALLER S AND USER S MANUAL AP
89. sarming code ACCESS GRANTED Access was granted PASSED A person was passed into the access zone SECURITY SYSTEMS S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL ACCESS DENIED Access is prohibited for this code ILLEGAL CODE Access was denied due to the illegal code ACCESS CLOSED Access is prohibited for all codes ACCESS FREE MODE Access control is deactivated ACCESS NORM MODE Access control is activated DISARMED The detector status is not monitored ARMED Detector status monitoring has been turned on ARM FAILED Arming has failed due to the activated status of detector LOOP TRBL OPEN Open circuit failure in the alarm loop LOOP TRBL SHORT Short circuit in the alarm loop FIRE SIGNAL Fire conditions have been detected FIRE PREALARM Fire signal has been received and fire alarm is probable FIRE ALARM Fire alarm INTRUSION ALARM Intrusion alarm SILENT ALARM Silent zone alarm ENTRY ALARM Entry zone alarm AUX ZONE ALARM Auxiliary loop alarm AUX ZONE RESTORY Auxiliary loop restored DOOR LEFT OPEN Door is opened too long DOOR CLOSED Door is closed after blocking in open state DOOR FORCED haa has been opened without access grant TAMPER ALARM Device or detector case is opened TAMPER RESTORE Device or detector case is closed POWER FAIL
90. second presenting has resulted in partition disarming then the third presenting re sults in partition arming If the key privileges are limited for example only arming is permitted then the repeated and all followed presenting results in only allowed operation arming in this case regardless of the current parti tion status Table 9 Partition status representation Partition status Reader LED mode Light color Disarmes Turnedoff Armed Turned on TEON green red Alarm Fire Alarm Fire Prealarm Arm Failed Blinks with 2 Hz frequency Yellow Fire Trouble Short flashes with 1 s re ne Yellow in fire partition regularity If the identifier presented is not recognized by the net controller or it has not access authority then the panel indicates the access denying that is the panel and reader sounders makes the long audible signal Error but reader LED blinks three times and then is red lit continuously If when presenting the unknown key the panel is not communicated with the computer then the message Illegal Code is generated This mes sage along with the other ones is storied into the panel non volatile mem ory and is to be transmitted to the computer when the communication has been recovered If the combined key for centralized access and partition control or for local access and partition control is presented then the access is gained 38 INSTALLER S AND USER S MANUAL PRODUCT DE
91. set then the beginning and finishing time are given by Key Validity Period parameters Otherwise the key has unrestrictive validity period This parameter can be attributed to any type of key 1 13 2 Identifier programming The panel operating as a part of the Orion safety system based on PC the Touch Memory Proximity card PIN code or other identifier are en tered into the panel non volatile memory by means of ARM Orion Database Administrator software 51 BOD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL If the panel is operated in stand alone mode or as a part of the Orion safety system controlled by S2000 or S2000M console then the identifiers are entered programmed by means of uprog exe program which is designed to add delete keys set or change their attributes stores keys into a file load key list from the file into the panel and so on In addition one can program the keys without PC by means of one or more so called MASTER keys Any identifier given by MASTER type key attribute can be MASTER key The presenting of MASTER key turns on the key programming mode In this mode all other presented keys are re corded to the panel memory with the type Basic and take over all MASTER key parameters such as Access User Code Loop Arm ing Disarming List Access Time Window Arming Disarming Time Win dow and Key Validity Period One MASTER key can be programm
92. ty 3 that is Reader if all given loops are LED g p armed than the indi The reader LED repeats Fire LAMP Standby tactic Mode cator is red other wise is turned off Reader LED loop 1 Loop Arm kaa o LED is lit if all 4 alarm loops are armed ing Indica Any loop breaking is displayed by the Alarming reader LED Indication In case of smoke detector actuation at the loop 1 or the loop 2 or heat detector actuation at the loop 3 or manual call point signal at the alarm loop 4 the panel enters the Fire Alarm mode with the panel LED of the corresponding loop and Touch Memory reader LED beginning to blink in Short stopping mode with 1 Hz frequency the panel sounder turning on with alternating tone mode fire siren sound the external light annunciator connected to the panel relay 1 turning on with the mode 0 75 s turned on and 0 25 s turned off siren turning on delay counting beginning if one of the loop1 loop 3 actuating or instant siren turning on if the manual call point at the loop 4 is activating If during relay 2 control delay the loop arming programmed Touch Memory key is presented to the reader than the rearming of the breaking loop will be occur and the siren will not sound 58 INSTALLER S AND USER S MANUAL APPLICATION If the key is not presented then after control delay expiration the siren will be switched on After fire source e g smoking elimination the al
93. uch Memory reader used for access used for controlling arming disarming I I I S2000 4 configuration parameters Reader interface type 1 Touch Memory LED control polarity direct active 1 78 WARRANTY Warranty Manufacturer warrants it S2000 4 product to be in conformance with specification under normal transportation storage mounting and mainte nance Manufacturer warrants S2000 4 product to be free from defects in ma terials and workmanship for 18 months since putting in to operation but no more then 24 months since production under normal use and service 2000 4 Panel Product designation serial number Produced tested by quality control department in compliance with state standards and specifications and packed by NVP BOLID company Q C STAMP Name Date 79
94. utput ON else OFF Alarm output 2 If all associated loops are armed or disarmed 16 then turns output ON else turns OFF Turn on for a given During arming delay period turns ON for a 17 time before arming given time otherwise OFF Turn off for a given During arming delay period turns OFF for a 18 time before arming given time otherwise ON Turn on for a given If at least one loop is armed switches the re 19 time when arming lay ON for a given time else OFF Turn off for a given If at least one loop is armed switches the re 20 time when arming lay OFF for a given time else ON 28 INSTALLER S AND USER S MANUAL PRODUCT DESCRIPTION Program description Turn on for a given time when disarm ing If at least one loop is disarmed switches the relay ON for a given time else OFF Turn off for a given time when disarm ing If at least one loop is disarmed switches the relay OFF for a given time else ON Turn on for a given time if arming has failed If at least one loop is in the state Arm has failed switches the relay ON for a given time else OFF Turn off for a given time if arming has failed If at least one loop is in the state Arm has failed switches the relay OFF for a given time else ON Turn on for a given time when auxiliary alarm If at least one loop is in the state Auxiliary alarm
95. value is 127 or select the panel descriptor from the list of connected devices with the help of a and 7 keys Enter the alarm loop number 1 The value given out shall be within the range from 46 to 50 c Repeat the steps from b item for loop 2 loop 3 and loop 4 4 STORAGE Acids and alkalis vapors aggressive gases and other noxious agent have to be absent at panel store rooms The panel storage life in package has to be no more then 6 months 69 105 BOLD S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Appendix A S2000 4 overall and mounting dimensions All dimensions are defined in millimeters e o o 70 APPENDIX B S2000 4 CONNECTING DIAGRAM Appendix B S2000 4 connecting diagram Proximity card or Touch Memory reader reader loop 1 LEDG loop 2 ene loop 3 GND loop 4 12V 24V To the reader power OV supply unit 12V 14V To the door lock V ower supply unit X OV p pply Electromagnetic lock NS 12V 24V To the siren power NA supply unit E OV PP Siren or other sounder RS 485 from the previous system device AB le RIP 12 RIP 24 12V 24V SN I I I I TH RS 485 to the next system device 71 SECURITY SYSTEMS S2000 4 INTRUSION amp FIRE AND ACCEESS CONTROL PANEL Appendix C Connection the detectors to the loops Connection of normally opened smoke fire detectors to the type 1 alarm loop fire sm
96. xiliary loops then switches the relay 34 ON for a given time In case of broken auxiliary loop the switching has blocked and the relay has remained OFF even after loop recovering ASPT A1 If there is alarm loop having Fire alarm status and there are no broken auxiliary loops then switches the relay ON for a given time 35 wr In case of broken auxiliary loop the switching has blocked and the relay has remained OFF even after loop recovering Turn on with tem If an alarm loop has entered High tempera perature increas ture status that is the temperature has ex 36 ling ceeded temperature high threshold then switches ON else OFF Turn on with tem If an alarm loop has entered Low tempera perature decreas ture status that is the temperature has ex 37 ling ceeded temperature low threshold then switches the relay ON else OFF Remark Only programmable auxiliary alarm loop type 12 can enter the statuses Temperature High or Temperature Low and only if these statuses were programmed for this loop 1 6 Access control The panel is intended to be used for door access control with the en tering to the access controlled area being identifier protected and exiting being performed by pressing EXIT button The Touch Memory or Proximity card reader is mounted in front of the door into the protected area the EXIT button being placed indoors The EXIT button and do