WebRelay-10 Users Manual

image

Contents

1. Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0004 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Read Coils 0x01 Data 2 3 bytes Byte Count 0x01 0x02 0x02 Coil status lower byte 0x00 to 0x03FF ee Coil status upper byte RX String 00 01 00 00 00 04 FF 01 02 55 01 Errors The following are possible error responses for function code 0x01 Coil Read Error Function Code 1 byte 0x81 0x01 Function code not supported Exception Codes 1 byte 0x02 Incorrect combination of start address and quantity of relays Error Response Frame Example Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization between messages of 0x0001 server and client Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0003 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Function code 0x81 Data 1 byte Exception code 0x01 0x02 0x02 Rx String 00 01 00 00 00 03 FF 81 02 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 4 5 Read Discrete Inputs Modbus Function Code 02 0x02 WebRelay 10 Plus only Th
2. Example Let a 1 Let edl 04 10 2010 sets th vent date to April 10 2010 Let etl 02 30 00 sets th vent time to 2 30 Do While a lt gt 0 If edl gt date Then Tests event date versus current date If etl gt time Then Tests event time versus current time Let etl etl 3600 Increments th vent time by one hour in seconds page 102 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix G BASIC Scripts Print Event Event to occur End If End If Loop End External Variables There are five external variables extvar0 through extvar4 External variables are similar to general purpose variables and can be used in the same manner The difference between general purpose variables and external variables is that external variables can be accessed by the user through a web browser and modified while the script is running Scripts can use external variables as a method of retrieving user input The following example demonstrates this by creating a script that will turn Relay 1 ON if extvar1 equals 1 and turn Relay 1 OFF if extvar1 equals 0 Example Do If extvarl 1 Then Let relayl 1 Else Let relayl 0 End If Loop End Extvar1 can be set and cleared by entering the following requests into a web browser or by configuring on and off buttons to appear on the Control Page for extvar0 http 192 168 1 2 state xml extvarl 1 http 192 168 1 2 state xml ext
3. Data types may be implemented at the discretion of the manufacturer Address ranges may also over lap Discrete is a binary or boolean value 1 or 0 Function codes memory types and addresses can be converted to the PLC addressing equivalent using the table below To use the table look up the row corresponding to the Modbus function code Then take the desired WebRelay 10 feature address and add to it the address offset in the PLC address mode column input address PLC address range PLC address For example to read discrete Input 2 the Modbus function code 02 is used Adding the address of Input 2 1 to the address range 1001 gives a PLC address of 1002 Programming the PLC to read from 1002 will return the value of Input 2 Code Name Modbus WebRelay Addresses Data Type PLC Address PLC Address Function Mode 485 Mode 584 984 Read Coils 01 0 9 Relays 1 10 Discrete Addr 1 Addr 1 Read Discrete 02 0 1 Inputs 1 2 Discrete Addr 1001 Addr 10001 Inputs Read Holding 03 272 286 Sensors 1 8 32 bit Addr 4001 Addr 40001 Registers Write Coils 05 0 9 Relays 1 10 Discrete Addr 1 Addr 1 Write Multiple Coils 15 0 9 Relays 1 10 Discrete Addr 1 Addr 1 Write Multiple 16 0 9 Relays 1 10 32 bit Addr 1 Addr 1 Registers WebRelay 10 Plus only For 32 bit numbers two registers must be read starting at the desired address examples of each are given
4. Data Blue Data Data end Blue White Gnd 5V Out 5V Gnd Orange 5V Out Input 2 Input 1 Figure 2 2h Recommended connection using Cat 5 cable A linear daisy chain rather than a star direct connection topology will minimize signal reflections Appropriate strain relief should be used at the WebRelay 10 and other connections that may be subjected to vibration movement or repeated handling Avoid sensor runs adjacent to industrial equipment power cables These cables can have high current spikes that may induce noise on the sensor signals Similarly avoid running sensor cables near any radio transmission antennas or coaxial feedlines Protect any electrical connections with appropriate weather shielding Due to the broad range of applications and environments were the WebRelay 10 may be employed installation success on long sensor runs may vary significantly Xytronix Research amp Design Inc page 17 Installation and Setup WebRelay 10 Users Manual 2 3 Establishing Communications for Setup 2 3 1 In order to configure WebRelay 10 with the web browser interface WebRelay 10 must be connected to an Ethernet computer network This can be done by one of two methods Method 1 Assign a temporary IP address of WebRelay 10 to work on an existing network Or Method 2 Temporarily change the IP address of a connected computer to the match the default IP address used by WebRelay 10
5. set relay opposite of input 1 When the input is tied to ground the relay turns OFF When the input is open the relay turns ON latch relay when input 1 on reset via web When the input is tied to ground the relay turns ON Once the relay is on it will stay ON unaffected by input change until it is turned page 42 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup OFF manually via the web or command by a user or WebRelay 10 Plus is powered off This option is useful for alarming functions latch relay when input 1 off reset via web When the input is open the relay turns ON Once the relay is ON it will stay ON unaffected by input change until it is turned OFF through a computer command Control Page or WebRelay 10 Plus is powered off This option is useful for alarming functions latch relay when input 1 changes reset via web Each time the input is tied to ground or when the input is open the relay turns ON Once the relay is on it will stay ON unaffected by input change until it is turned OFF via the web or command by a user or WebRelay 10 Plus is powered off This option is useful for alarming functions toggle relay when input 1 on When the input is tied to ground the relay will change states When the input is open the relay will remain in its current state toggle relay when input 1 off When the input is open the relay will change states Whe
6. Note If multiple ControlIByWeb products are used on the same network install one at a time and set the IP address of each unit before connecting the next unit to the network This avoids having multiple devices being installed on the network with the same factory default IP address at the same time If this approach is used be sure to clear the arp cache after disconnecting each unit arp d Method 1 Assign a Temporary IP address to WebRelay 10 This option is used to TEMPORARILY assign an IP address to WebRelay 10 without the need to change the IP address of the configuration computer WebRelay 10 will use this IP address as long as power is maintained Once power is lost WebRelay 10 will use the IP address assigned in the setup page and not the temporary address assigned here Make sure that WebRelay 10 and the configuration computer are connected to the same network This will not work through routers or gateways Microsoft Windows Instructions 1 Open a Command Prompt select START then RUN then type cma Note For Vista the Command Prompt should be run as administrator select Start then type cmd and right click on cmd and select Run as administrator 2 Type arp s new IP address serial number of WebRelay 10 Note IP address format is xxx xxx xxx xxx The serial number can be found on a label on the module board The format is SS SS SS SS SS SS For example to set W
7. Contact Arrangement Form C SPDT Contact Rating N O 40A 240VAC resistive 30A 277VAC General Purpose 2hp 250VAC N C 30A 240VAC resistive 30VDC 20A 277VAC General Purpose 1 hp 250VAC Contact Resistance lt 30 milliohms initial Contact Material AgSnO Max Switching Power 9600VA 1120W Max Switching Voltage 277VAC 110VDC Max Switching Current 40A Electrical Life Y Rated Load 100K cycles typ Mechanical Life 10M cycles typ Connectors Ya inch Tab Connectors page 104 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix H Specifications Accessory Connector WebRelay 10 Plus only 5 position removable terminal strip 3 81 mm terminal spacing Replacement part number Phoenix Contact 1803604 Inputs WebRelay 10 Plus only Number of Inputs 2 Input Type Discrete Inputs connect to dry contacts Maximum Input Voltage 5 VDC Minimum Hold Time high or low 20ms Counters WebRelay 10 Plus only Number of counters 2 Counter Triggers Input transitions low to high high to low or both Maximum Count 4000000000 Maximum Count Frequency 25Hz Temperature Sensors WebRelay 10 Plus only 1 Wire Digital Thermometer Dallas Semiconductor part DS18B20 Temperature Range 20 C to 40 C 4 F to 104 F Accuracy 0 5 from 10 C to 85 C Maximum number of sensors 8 Maximum Dista
8. ooonnncncuuuuoncncncnncononnonnnnnanananananos 16 e A e 46 47 P A E A E E AE EE TEE 13 17 PASSWOLKC 0ccccccccccccccecceceecececcececcecececcececeece 26 31 32 Desdband cintia aaa il 46 Defadlt 23 31 57 64 82 83 84 97 Sensor Tab ci ds 45 97 Password Ta da 31 SENSO TSR ET sinri ai e ae a s e Tei 38 Period 4 35 38 48 49 50 51 62 64 105 Serial mimbre ii 18 A 18 19 Setup Password succes tess yes ctecestysetanrie tiesto 31 PECA TE pa EEA e A AE E 60 NM e sn da 30 93 ele A E O EE E E AEA 28 Enable iaa 29 Port Forero idad 88 SNMP RequestS ocoomonin ronsomisisosomerrrermers 95 PO WE bic SPOCHICAONS or saetssnnpeysanaacesgennntesninendntantnncinnys 104 Backup GR cate aD sata ee go ae ent a Mac a 9 105 State A A 59 C rr nt raina eaii dine ieii 13 Subnet Mask ineco eri E n 25 ICAO A is ida 11 T NTP es 105 TIPO 9 14 16 105 BOWER EU TOTS Fst o nee a LOS Terminal Connector oooonoccnooccnonnnonnncnonncnonoconnncnnnonnnos 14 a 13 RETA P lse Col ica asen 79 Dalia i 33 Pole Duration ssescs Weve dae S a Wesoees loses 42 Daylight Vi ccoo 36 R Edrmatrani a ad AE 34 Read Col aida 69 Manual Time ConfiguratiOM ocoioninnincnninninninnoos 33 Read Discrete Imputs oooonioiononononononononorororonarononos 71 NTP Time Configuration 34 Read SensoOTS ooocononnnnonononnonecnononnononannonornononaonenacnono 73 A Oa 33 Refresh iaa eis 55 U Relay E RA ias E A a A Seu ete 26 Connection ssssssessesse
9. 4 Refer to Section 2 3 Establishing Communications for Setup to begin reconfiguration of the device Reset Button Figure Appendix A 1 Restore Factory Defaults Xytronix Research amp Design Inc page 83 Appendix B Installing New Firmware WebRelay 10 Users Manual Appendix B Installing New Firmware From time to time updates are made to WebRelay 10 firmware WebRelay 10 firmware can be updated in the field The procedure for updating the firmware is outlined below Please note that it is important that this procedure is followed precisely Requirements The firmware update software requires Windows XP Vista with the Net framework installed The Net framework is generally installed automatically through Windows update To install it manually go to the following address http www microsoft com downloads details aspx Familyld 333325FD AE52 4E35 B531 508D977D32A68displaylang en Select the Download button Once you ve downloaded the installation file double click on the installation file to install the framework Setup 1 Download the bootloader exe and the new firmware image from the ControlByWeb website under the WebRelay 10 downloads section Only a WebRelay 10 image can be installed on WebRelay 10 so make sure the correct image is being downloaded 2 bootloader exe will connect to the the WebRelay 10 using default IP address 192 168 1 2 not the address currently assigned to t
10. Capply Cancel Figure Appendix C 3 Port Range Forwarding Accessing Setup Pages After changing ports the setup pages are accessed on a local network as described below http Local IP Address Port Number setup html For example to access WebRelay 10 at the setup page above the following command would be used http 192 168 1 25 8000 setup html To access the ControIByWeb units from the Internet enter the public IP address of the router plus the port number of the desired device in the following format http Public IP Address of Router Port Number of Device setup html Using the example above the following line would be used to access the setup page of WebRelay 10 http 266 70 164 97 8000 setup html Xytronix Research amp Design Inc page 89 Appendix D Log Files WebRelay 10 Plus only WebRelay 10 Users Manual Appendix D Log Files WebRelay 10 Plus only Data WebRelay 10 Plus logs information to two different log files log txt and syslog txt Both log files are text files and are stored in nonvolatile memory this data will not be lost due to power failure and is also not cleared when restoring factory defaults The log files are stored in circular buffers which write from the beginning of the allocated memory space to the end and then repeat from the beginning over writing the original data The nonvolatile memory is divided into 4K byte sectors Each time data get
11. Ethernet Connection ejeg jo lt ot Z indu punoi NO AS et Figure 2 2c Connector Pinout Input Connection WebRelay 10 Plus only Two discrete inputs can be connected to dry contact sensors or switches Third party sensors can be used for monitoring alarm conditions such as door access switches or transducer thresholds Inputs can also be used for operator switches and the unit can be configured such that they control the relays 5V Input To Processor Figure 2 2d Input Schematic Connect one terminal of sensor or switch to the input terminal Input 1 or Input 2 Connect the other terminal to the ground terminal on WebRelay 10 Plus When contacts are closed the input is connected to ground and the input is considered to be ON Switch current is less than 2 mA Xytronix Research amp Design Inc page 15 Installation and Setup WebRelay 10 Users Manual Dry Contacts Input 1 GND L indu Zndu punol5 INO AS exeg Figure 2 2e Input Connector Temperature Humidity Sensor Connection WebRelay 10 Plus only Temperature and or humidity sensors can be used for monitoring environmental conditions The digital sensors use a one wire data bus which allows up to eight sensors to share the same terminals 5V Ground Data Every sensor on the one wire bus is assigned a unique serial number when it is manufactured That number is used to address the device during communication
12. South America http www pool ntp org zone south america 0 south america pool ntp org 1 south america pool ntp org 2 south america pool ntp org 3 south america pool ntp org Africa http www pool ntp org zone africa 1 africa pool ntp org 1 pool ntp org 3 pool ntp org Sync With Server This option allows the user to specify how often WebRelay 10 Plus time will be synchronized with the time server When the submit button on this page is pressed WebRelay 10 Plus will immediately synchronize with the time server If Daily Weekly or Monthly options are selected WebRelay 10 Plus will thereafter re synchronize with the time server at the period interval specified starting at 12 00 AM 00 00 The exact time the NTP Request occurs is 12 00 AM 00 00 plus the minute equivalent of the last two digits in the models serial number For example if the last two digits in the model s serial number were 09 the NTP Request will occur 9 minutes after 12 00 AM The default value of this setting is Once the unit will immediately sync with the NTP server but will not automatically sync again Sync on Power Up When this option is set to Yes WebRelay 10 Plus will be synchronized with the time server each time it is powered Note If WebRelay 10 Plus will lose power on a frequent basis it may be beneficial to set this option to No some servers are configured to dis allow access from client devices that excessively request
13. you can monitor temperature and or humidity control multiple relays using an input schedule reoccurring events log relay state changes and much more page 8 Xytronix Research amp Design Inc WebRelay 10 Users Manual Introduction 1 3 WebRelay 10 Models Available WebRelay 10 is currently available in two models The main differences between each model are listed below X WR 10R12 1 Standard WebRelay 10 with built in web server and ten individually controlled relays X WR 10R12 IP WebRelay 10 Plus includes all features of standard model plus WebRelay 10 Plus temperature humidity monitoring humidity monitoring requires optional humidity sensor discrete inputs real time clock event scheduling capacitor power backup and logging 1 3 1 Optional Accessories WebRelay 10 Plus Accessory Description Part Number Temperature Sensor Digital temperature sensor with 12 inch wire leads X DTS U Note Leads may be extended Temperature Sensor Digital temperature sensor housed in vented plastic X DTS WM Wall Mount enclosure Temperature Humidity Digital temperature and humidity sensor housed in X DTHS WM Sensor Wall Mount vented plastic enclosure Xytronix Research amp Design Inc page 9 WebRelay 10 Users Manual Introduction 1 4 Connectors amp Indicators Version H Newest version Gnd and Vin pin position moved from ver
14. 192 168 1 29 R 11 15 2010 11 20 54 1 0 0 0 0 1 1 0 1 0 1 1 077 7 076 4 083 4 XmlReq 192 168 1 29 W The file can then be saved using the Save As option under the File menu of the web browser If the TCP port has been changed not port 80 the port will be required to read the file For example using the default IP address and port 8000 the log file would be read as follows http 192 168 1 2 8000 log txt The log txt file may be erased with the following command http 192 168 1 2 log txt erase 1 After erasing the file it might be necessary to refresh the page Note If the Control Password is enabled in the setup pages the password will be required to access the log file page 90 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix D Log Files WebRelay 10 Plus only System Log Fi le syslog txt The systole file records various system events which can be used for diagnostics and troubleshooting purposes File Format MM DD YYYY HH MM SS Sample File 01 02 2010 04 08 13 DEVICE category to which messag applies message Power Up 01 01 2010 00 41 05 DEVICE Reset factory defaults Listed below is a description of messages that a user may see Category Message Description Power Up Device has been properly powered DEVICE Initialize Device is ready Reset Factory Def
15. GET ai Ghee 30 59 64 94 H Hal Duplex iia io 26 HTTP Portatil tarta pines 25 Humidity cts 9 14 16 105 I Inputs ccc eren in r a A AA Counter OptiOMS ocoocononccnocncoonanonononncnnonccnonacinnoos 40 Input ComnectiOM ooconccnncnncnnncnnncanoninnncnononnnonnnnnncnnnos 15 Input eiie 15 Imputs Tabie e a a ai a E 39 Installation dl 12 druida eas Accessing WebRelay 10 oooooonooccccnioooccccononnnnos 86 TP ad dress ideada 23 92 IP AddressES oooocononocccoonnccnonnccoonnncconnanononnncconnnnnonnno 86 L LAN A e eed eae 87 A 19 Local Area Network ooooconncoccnooonccoonnncnoonncononnnnonos 86 Log Pilesis ststes cscs ice tlre cd haa nedagneeiadety 90 Logging Tabla 37 M MAC addressen esenario rnia a 18 19 23 MacOS A A A ST 19 Mail Seva alt 26 Mail Server POlrt ooconoccccnnonocinoccccoooncccnonnncononanocnnanoss 26 Man Taba coca ios 23 Manual Time ConfiguratiOM ooconoonnnonncnonncnnnnconnnnnnos 33 A este vates Seatac Gost sa eSoosa a e Ea a i Enabled 28 O A TN 28 Modbus OperatiOM coooooconncionnnoncnconccconccnnnocannncnnnnnos 66 Modbus TER a a 28 Models iii sa 9 N Network Tab iii od 24 NTP aen dio 25 page 108 Xytronix Research amp Design Inc WebRelay 10 Users Manual Alphabetical Index NTP Time ConfiguratiOW cccooooccnnnnnnnnnnnnnnnnnnnnnnnnos 34 O E A 98 Sec an e a laced 6 29 30 31 93 94 o e SEO a a ca 9 One wire A IO SEE 16 A NA O AN 46 47 One wire data DUS
16. NTP Time Configuration Server Name IP Address This field is used to specify the name or IP address of the NTP server If a name is specified a working DNS server address must be entered into the Network settings If the IP address is specified it should be entered in the following format aaa bbb ccc ddd where each of the letters represents a number between 0 and 255 This field can be up to 40 characters There is no default value for this field Many NTP Internet servers are available In addition many desktop computers will function as an NTP server both Mac and PC If a desktop computer is used firewall settings may need to be adjusted to allow for NTP communications on port 123 Public NTP servers can be found at www pool ntp org Some of these are listed below US Servers http www pool ntp org zone us 0 us pool ntp org 1 us pool ntp org 2 us pool ntp org 3 us pool ntp org North America http www pool ntp org zone north america 0 north america pool ntp org 1 north america pool ntp org 2 north america pool ntp org page 34 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 3 north america pool ntp org Europe http www pool ntp org zone europe 0 europe pool ntp org 1 europe pool ntp org 2 europe pool ntp org 3 europe pool ntp org Australia http www pool ntp org zone au 0 au pool ntp org 1 au pool ntp org 2 au pool ntp org 3 au pool ntp org
17. Code 1 byte Error code 0x8F Data 1 byte Exception code 0x01 0x02 0x02 Rx String 00 01 00 00 00 03 FF 8F 03 page 78 Xytronix Research 8 Design Inc WebRelay 10 Users Manual Operation 3 4 9 Pulse Coils Modbus Function Code 16 0x10 The Modbus Write Multiple Registers function is used to pulse the relay s for a specified time When WebRelay 10 receives this command it immediately turns the appropriate relay coil s ON if not already on and starts the pulse timer The relay s are selected by writing the pulse time to the register s associated with the appropriate relay s The pulse time is specified in the register value field and can range from 0 1 seconds to 86400 seconds 1 day When the pulse time expires the relay coil will be turned OFF If a pulse time command is sent with a value greater than 86400 the pulse timer will be set to 86400 If a pulse time command is sent with a value less than 0 1 the pulse timer will be set to 0 1 If any commands are sent to WebRelay 10 Modbus xml or html before the pulse timer has expired the pulse timer will be canceled immediately and the new command will be executed The pulse time is provided in IEEE 754 floating point format The four data bytes are treated as two individual big endian 16 bit words but the least significant word is sent first In other words the 32 byte floating point number represented as 1234 ABCD is sent ABCD 1234 In the example s
18. Oxff if not used OxFF Function Code 1 byte Read Coils 0x01 Data 4 bytes Start Address 0x0000 0x0009 0x0001 Quantity of coils to read 0x0001 0x000A 0x0009 Tx String 00 01 00 00 00 06 FF 01 00 01 00 09 Response The WebRelay 10 will respond to the request with a data field of one or two bytes each bit representing the coil status A 1 indicates the relay is ON A 0 indicates that the relay is OFF A single byte is returned if no more than 8 coils are requested Two bytes are returned if the status of nine or 10 coils are requested Consequently the message length will be 0x0004 bytes or 0x0005 bytes depending on the number of coils Bit zero of the return value will be the state of the coil corresponding to the start address For example if a start address of 0x0006 is used bit zero will be the status of coil 7 The tables below show two examples Coil status for relays 7 9 start address of 0x0006 and quantity of 3 Single Byte Bit7 6 5 4 3 2 1 Bit 0 x x X X X Relay Relay Relay 9 8 7 Full 10 bit return value Xytronix Research amp Design Inc page 69 Operation WebRelay 10 Users Manual Upper Byte Lower Byte Bit15 14 13 12 11 10 9 8 7 6 5 4 3 1 Bit 0 X X X X X Relay 9 8 7 6 5 4 2 Relay 10 WebRelay 10 Response Frame Example Status of Coils 2 through 10
19. Research amp Design Inc WebRelay 10 Users Manual Trademark and Copyright Information Trademark and Copyright Information This document is Copyright 2005 2015 by Xytronix Research amp Design Inc All rights reserved WebRelay 10 WebRelay ControlByWeb and Xytronix Research amp Design are trademarks of Xytronix Research amp Design Inc 2005 2015 All other trademarks are the property of their respective owners All parts of this product and design including but not limited to firmware hardware design schematics PCB layout concept graphics users manual etc are property of Xytronix Research amp Design Inc 2005 2015 WebRelay 10 may not be opened disassembled copied or reverse engineered No part of this manual may be reproduced or transmitted in any form or by any means electronic or mechanical including photocopying or scanning for any purpose other than the personal use by the purchaser of this product Xytronix Research amp Design Inc assumes no responsibility for any errors that may appear in this document Whereas reasonable effort has been made to make the information in this document as useful and accurate as possible Xytronix Research amp Design Inc assumes no responsibility for the application usefulness or completeness of the information contained herein Under no circumstance will Xytronix Research amp Design Inc be responsible or liable for any damages or los
20. Slave Address Oxff if not used OxFF Function Code 1 byte Error code 0x83 Data 1 byte Exception code 0x01 0x02 0x02 RX String 00 01 00 00 00 03 FF 83 02 page 74 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 4 7 Write Single Coil Modbus Function Code 05 0x05 This function allows you to control relays one at a time Relay Address 2 bytes 0x0000 Relay 1 0x00009 Relay 10 Relay Value 1 byte 0x00 ON OxFF OFF Padding 1 byte 0x00 Request Modbus TCP Request Frame Example Write Coil 3 ON Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0006 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Write Coil 0x05 Data 4 bytes Relay address 0x0000 0x0009 0x0002 Relay value 0x00 OxFF OxFF Padding 0x00 0x00 Tx String 00 01 00 00 00 06 FF 05 00 02 FF 00 Response WebRelay 10 Response Frame Example Write Coil 3 ON Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0006 Unit Identifier 1 byte Slave Address Oxff i
21. The NEXT statement always follows the section of code to be looped The format is FOR variable expression TO expression code to be looped NEXT variable DO WHILE LOOP The DO WHILE statement loops a section of code while a condition is found true The LOOP statement always follows the section of code to be looped Note that if the condition is omitted the code will be looped without end The format is DO WHILE variable lt gt lt gt lt gt expression code to be looped LOOP LOG The LOG statement causes the device to log data according to the settings specified under the Logging setup tab Note In order to log logging must be enabled in the Logging setup tab The format is LOG Xytronix Research amp Design Inc page 99 Appendix G BASIC Scripts WebRelay 10 Users Manual EMAIL The EMAIL statement causes the device to send an email of the same format as that generated by other status change and alarm conditions The event that triggered the email is given followed by the input and relay states The format is EMAIL feature state relayX inputX tempX X represents the feature number such as relay9 Examples EMAIL Status email sent to addresses listed under Network tab OM EMAIL relay2 Sends state change message to emails setup in Relays tab Ol ii EMAIL inputl Input state change message to emails setup in Input tab OM EMAIL temp2 Te
22. The sensors have three wires the wire color is show in the table below Sensor Wire Color Connection Red Vout Black Gnd Blue or White Data Figure 2 2f Temperature Sensor Multiple sensors can be connected in two ways directly connected to the unit star topology or daisy chained linear topology as shown in Figure 2 2g page 16 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup Figure 2 2g Direct Connection Star and Daisy Chain Connection Linear Many factors will determine the maximum length of cable used to connect sensors to WebRelay 10 Plus Some of these factors include but are not limited to the type of cable used the number of sensors ambient electromagnetic noise and sensor network topology Combined cable lengths to all sensors of 600 ft using Cat 5e cable have been successful However due to the uniqueness of installation environments results may vary Please test in the desired environment before permanent installation The following are general recommendations that will maximize sensor runs and minimize problems Cat 5 and Cat 5e network cable has proven to be an effective and low cost solution for long runs Other cable types can be used but cable capacitance may limit the length Figure 2 2h shows the recommended connection using Cat 5 network cable Temperature Sensor Cat 5 Network Cable Terminal Connector
23. Xytronix Research amp Design Inc page 45 Installation and Setup WebRelay 10 Users Manual sensor comes from the factory with a unique non changeable address When the sensors tab is selected or the Refresh List button is pressed WebRelay 10 Plus scans the bus for sensors The addresses of the sensors that are found on the bus are listed in the drop down list For each sensor number Sensor 1 Sensor 8 select the address of the appropriate sensor from the drop down list Selecting sensors is simplest when the sensors are connected to the bus one at a time The procedure is to start with one sensor and associate it with the appropriate sensor number by selecting the sensor address within the appropriate drop down list Submit the page connect a second sensor and press the Refresh List button Associate the second sensor to the appropriate sensor number Continue this procedure until all sensors are set up Alarm 1 This setting is used to set the trigger point for an alarm condition The number field specifies the temperature humidity at which the alarm is triggered The High and Low radio buttons indicate whether the alarm is triggered as a high or low alarm A high alarm is triggered when the sensor reading exceeds the alarm value and a low alarm is occurs when the sensor reading falls below the alarm value Alarm 2 This is a second alarm trigger that works similar to Alarm 1 Deadband This option sets the
24. bar of the browser It displays model and serial number information and allows the user to select the desired temperature units 600 WebRelay 10 6 http 192 168 1 2 setup html Qy ControlByWeb WwW Setup sensors evens sip Contra rege sotun contr rose _ WN Fahrenheit CelsiusO AA X WR 10R12 1P Firmware Revision 1 01 Tele 00 0C C8 02 4D 66 For product support go to www ControlByWeb com Xytronix Research amp Design Inc Figure 2 4a Main Tab Units WebRelay 10 Plus only This allows the user to select between the temperature units of Fahrenheit and Celsius All settings entered and displayed on subsequent pages will be in the units selected Part Number This is the full model number of WebRelay 10 Firmware Revision This is the current product revision of the unit s firmware Serial Number This is the serial number of this unit The serial number is also the MAC address of the unit Xytronix Research amp Design Inc page 23 Installation and Setup WebRelay 10 Users Manual 2 4 2 Network Tab The network parameters are set on this page Note WebRelay 10 must be power cycled power disconnected then reconnected before network settings take effect Only the settings on the Network tab require power cycling before taking effect O pe 00 WebRelay 10 x GC http 192 168 1 2 setup html ZA Ww Setup sensors Events script contro Page setup contro
25. brief description of what triggered the email message Remote Reboot To cause the device to reboot the following command can be entered into the address bar of the browser http 192 168 1 2 networkSetup srv rbt 1 The username and password will be requested before the reboot will occur so that only administrators of the device can cause the reboot MTU Setting To change the MTU manually enter the advSetup html case sensitive page into the address bar http 192 168 1 2 advSetup html This new setup page will have a text box that will allow the MTU to be changed The valid range is 256 to 1476 bytes MTU is a network parameter that stands for Maximum Transmission Unit This defines the max size in bytes of the TCP packets sent out from the device This normally can be left alone but there are some circumstances where it might be page 26 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup beneficial to change it One of these circumstances is when the device is to be used over a VPN virtual private network VPN s add extra information to TCP packets if the new packets are too big to physically travel across the network greater than about 1500 bytes then the packets will be split up This causes problems for some firewalls and those firewalls will just discard the packets To fix this the MTU can be adjusted until the TCP packets do not get split up Xytronix Research
26. can be made up of two or more computers or other devices connected to an Ethernet switch Each device on the network is assigned a unique private IP address For example consider a simple network that consists of a computer a WebRelay 10 and a WebRelay In this example the computer is assigned an IP address of 192 168 1 10 WebRelay 10 has the IP address of 192 168 1 25 and a WebRelay has and IP address of 192 168 1 26 A person using the computer can access WebRelay 10 by entering its IP address in the URL line in the browser http 192 168 1 25 Similarly WebRelay can be accessed by entering its unique private IP address in the URL line in the browser http 192 168 1 26 page 86 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix C Accessing WebRelay 10TM Over the Internet WebRelay 10 y WebRelay Ethernet Switch Computer Figure Appendix C 1 Local Area Network A Simple LAN connected to the Internet The LAN in the example above can be connected to the Internet by adding a router and an Internet connection The router has two network connections It has an Ethernet network connection to the LAN and another connection to the Internet Often the Internet connection is called a Wide Area Network WAN connection Each network connection on the router has an IP address In our example the IP address on the LAN side of the router has an address of 192 168 1 1 The IP address
27. deadband used when evaluating alarm conditions Deadband prevents alarms from triggering excessively when the sensor measurement vacillates quickly around the set point due to normal fluctuations Deadband on high alarms requires the measurement to fall below the high alarm point minus the deadband before the high alarm can be triggered again Likewise the deadband on the lower alarm requires the measurement to rise above the low alarm point plus the deadband before the low alarm can be triggered again For example if the deadband is set to 1 degree and a high alarm is to occur at 95 degrees the dead band ensures that once the high alarm is triggered it won t go off until the temperature returns below 94 degrees 95 1 This reduces problems with small fluctuations in sensor readings triggering multiple alarms High Alarm High Alarm sd Set T e m p Low Alarm 45F Set Low Alarm Time Figure 2 4k Alarm Deadband Email Option Simple email messages can be sent in response to alarm conditions This parameter is used to specify what alarm conditions if any will cause email messages to be sent Note that email notification will work only if email is correctly setup in the Network setup page page 46 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup No Email Messages No email messages will be sent due to alarm conditions Send Email on Alarm 1 Email notification
28. for the applicable functions Xytronix Research amp Design Inc page 67 Operation WebRelay 10 Users Manual 3 4 3 WebRelay 10 Full Address Table The table below gives commonly used function code memory types data sizes and equivalent PLC addresses for accessing the WebRelay 10 The data size will be the same regardless of the addressing mode Function Address Data Size PLC Address PLC Address Section Code Mode 485 Mode 584 984 Read Relay 1 01 0 Discrete 1 1 Read Relay 2 01 1 Discrete 2 2 Read Relay 3 01 2 Discrete 3 3 Read Relay 4 01 3 Discrete 4 4 Read Relay 5 01 4 Discrete 5 5 Read Relay 6 01 5 Discrete 6 6 Read Relay 7 01 6 Discrete 7 7 Read Relay 8 01 7 Discrete 8 8 Read Relay 9 01 8 Discrete 9 9 Read Relay 10 01 9 Discrete 10 10 Write Relay 1 05 0 Discrete 1 1 Write Relay 2 05 1 Discrete 2 2 Write Relay 3 05 2 Discrete 3 3 Write Relay 4 05 3 Discrete 4 4 Write Relay 5 05 4 Discrete 5 5 Write Relay 6 05 5 Discrete 6 6 Write Relay 7 05 6 Discrete 7 7 Write Relay 8 05 7 Discrete 8 8 Write Relay 9 05 8 Discrete 9 9 Write Relay 10 05 9 Discrete 10 10 Read Input 1 State 02 0 Discrete 1001 10001 Read Input 2 State 02 1 Discrete 1002 10002 Read Sensor 1 03 272 32 bit Float 4273 40273 Read Sensor 2 03 274 32 bit Float 4275 40275 Read Sensor 3 03 276 32 bit Float 4277 40277 Read Sensor 4 03
29. schedules if any will be affected by the event Pulse lf a relay pulse event is programmed the Pulse Duration will be displayed Next Occurrence The date and time of the event s next occurrence will be displayed If the event has already occurred the event will be listed as Inactive here The events are color coded to indicate their status Gray Event has not been set up GABBA Events are active and will occur sometime in the future RG Events have been temporarily disabled by the disable event action page 48 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup Yellow Events have already occurred and are not scheduled to happen in the future Configuration of events is accomplished by clicking on the appropriate event which causes the following setup screen to be displayed WebRelay 10 http 192 168 1 2 setup html Current Date Time Schedule Description Start Date Start Time HH MM SS Period Days Count Action Affected Relays Pulse Duration Qr ControlByWeb Event 6 11 15 2010 10 42 51 E Event Description November 2010 u We Th 3 10 PFA 24 Enter 0 to disable event Sun Mon MTue MWed MTh Fri Sat 0 Enter O for continuous occurrence oi 02 03 Es LS secs BS 06 07 o8 o9 glo Select a period of one day in order to spe
30. setup is complete it may be necessary to clear the arp cache to configure additional WebRelays This is necessary because each unit has the same default IP address but a different unit serial number MAC address Clearing the arp table can be done by typing sudo arp d a in the command prompt window Mac OS X Instructions 1 4 Open a terminal Note The terminal is in the Utilities directory which is in the Applications directory Type sudo arp s new IP address serial number of WebRelay 10 Administrator password may be required Note IP address format is xxx xxx xxx xxx The serial number can be found on the label on the module board The format is SS SS SS SS SS SS For example to set a WebRelay 10 with serial number 00 0C C8 01 00 01 to 10 10 10 40 the following command would be used sudo arp s 10 10 10 40 00 0c c8 01 00 01 Next type ping s 102 new IP address For example if the new IP address is 10 10 10 40 the following command would be used ping s 102 10 10 10 40 Proceed with WebRelay 10 setup in section 2 4 Once setup is complete it may be necessary to clear the arp cache to configure additional WebRelays This is necessary because each unit has the same default IP address but a different unit serial number MAC address Clearing the arp table can be done by typing sudo arp da a inthe command prompt window Xytronix Research amp Design Inc page 19 In
31. single pulse initiated by that command In other words you must issue the pulseTime command for each pulse command that differs from the preset value page 60 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation For example suppose the WebRelay 10 is configured for a Pulse Duration of 1 5 seconds To issue one 1 5 second pulse three 5 second pulses and another 1 5 second pulse to Relay 1 you would issue the following commands Command Description state xml relay1State 2 Pulse Relay 1 for the preset time 1 5 seconds state xml relay1State 2 amp pulseTime1 5 Pulse Relay 1 for 5 seconds state xml relay1State 2 amp pulseTime1 5 Pulse Relay 1 for 5 seconds state xml relay1State 2 amp pulseTime1 5 Pulse Relay 1 for 5 seconds state xml relay1State 2 Pulse Relay 1 for the preset time 1 5 seconds Message Acknowledgment By default when commands are sent to WebRelay 10 the state xml page is returned The xml reply can be disabled by adding the noRep1y field as follows Command Description state xml relaylState 1 amp noReply 1 Turn Relay 1 ON without returning state state xml relaylState 0 amp noReply 1 Turn Relay 1 OFF without returning state Password If the Control Password is enabled on WebRelay 10 and the state xml page is requested through a browser the user will be prompted for a password If the XML request is sen
32. specifies the location and the port specifies the specific recipient Port numbers can be set to any number between 1 and 65235 However many port numbers are reserved for specific applications and should be avoided As a general rule numbers above 8000 are safe to use All of the ControlByWeb products come from the factory with the HTTP port set to 80 which is the standard port for HTTP In this example WebRelay 10 HTTP port will be changed to port 8000 and WebRelay port will be changed to 8001 Once the ports are changed in the two ControlIByWeb devices the router must be set up for port forwarding Port forwarding associates the IP address of each local device with an assigned port In this example the address 192 168 1 25 for WebRelay 10 would be associated with port 8000 The address 192 168 1 26 for WebRelay would be associated with port 8001 WebRelay 10 would be accessed from the Internet by entering the public IP address of the router plus the port number assigned to WebRelay 10 in the URL window of the browser http 266 70 164 97 8000 All Internet requests to the router for port 8000 would be forwarded to WebRelay 10 Similarly all request for port 8001 would be forwarded to WebRelay Note When an HTTP request comes in to the router without the specific port specified http 266 70 164 97 the router will handle this as a port 80 request default HTTP port In other words http 266 70 164 97 is exactly
33. 0 Users Manual Tx String 00 01 00 00 00 OF FF 10 00 16 00 04 08 00 00 3F 00 00 00 40 A0 Response WebRelay 10 Response Frame Example Write Coils 7 9 ON Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0004 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Write Multiple Coils Ox0F Data Start address 0x0000 0x0009 0x0006 Relay count 0x0001 0x000A 0x0003 Rx String 00 01 00 00 00 06 FF 10 00 16 00 04 Errors Pulse Function code Error 1 Byte Exception codes 1 Byte 0x90 0x01 Feature not supported 0x02 Address quantity not an even number Incorrect combination of start address and relay count Error Response Frame Example Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization between messages of 0x0001 server and client Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0003 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Error code 0x90 Data 1 byte Exception code 0x01 0x02 0x02 Rx String 00 01 00 00 00 03 FF 90 02 page 80 Xytronix Research amp Design In
34. 1 until it is explicitly set to 0 as described below lt devicePowerUpFlag gt Loss of power to the device is indicated by 1 A value of 1 means WebRelay 10 has lost power at least one time since the flag was set to 0 By default the flag value is 1 It is not automatically set and will read 1 until it is explicitly set to 0 as described below lt powerLossCounter gt This field is a count of how many times WebRelay 10 has lost main power It may be reset to 0 The above flags may be cleared by requesting the diagnostics xml file along with request parameters To clear the real time clock power loss flag http 192 168 1 2 diagnostics xml memoryPowerUpFlag 0 To clear the device power loss flag http 192 168 1 2 diagnostics xml devicePowerUpFlag 0 To clear the powerLossCounter flag http 192 168 1 2 diagnostics xml powerLossCounter 0 Resetting of multiple flags may be done at one time by placing between each request http 192 168 1 2 diagnostics xml memoryPowerUpFlag 0 devicePowerUpFlag 0 Note Requests for the diagnostics xml file do not require a password Xytronix Research amp Design Inc page 63 Operation WebRelay 10 Users Manual 3 3 Configuring Events Through GET Requests WebRelay 10 Plus only Events can be configured using a GET request For example to configure event 5 to start on November 19 2010 at 12 00 00 and continue every day tur
35. 10 9 8 7 6 5 4 3 2 1 Bit 0 X X X X X X Relay 9 8 7 6 5 4 3 2 Relay 10 1 Start Address 2 bytes 0x0000 relay 1 0x0009 relay 10 Relay Quantity 2 bytes 0x0001 Ox000A Byte Count 1 2 bytes 0x01 0x02 Output Value 1 2 bytes 0x0000 0x03FF Request Relay states are controlled by specifying the start address of the first relay to be controlled the count of the relays to be affected and the relay state byte s Only the lower byte needs to be specified when relays 1 8 are changed Both bytes must be specified if relays 9 or 10 are affected Modbus TCP Request Frame Example Write Coils 7 ON 8 OFF and 9 ON Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0009 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Write Multiple Coils Ox0F Data 8 9 bytes Start address 0x0000 0x0009 0x0006 Relay quantity 0x0001 0x000A 0x0003 Byte count 0x01 0x02 0x01 Lower byte value 0x00 OxFF 0x05 Upper byte value 0x00 0x03 TX String 00 01 00 00 00 08 FF OF 00 06 00 03 01 05 Only coils that are in the address and count range will be affected by the output value Consequently an output value of OxFFFF w
36. 278 32 bit Float 4279 40279 Read Sensor 5 03 280 32 bit Float 4281 40281 Read Sensor 6 03 282 32 bit Float 4283 40283 Read Sensor 7 03 284 32 bit Float 4285 40285 Read Sensor 8 03 286 32 bit Float 4287 40287 Write Multiple Relays 15 0 8 or 16 bit 1 1 Pulse Relays 16 0 32 bit Float 1 1 page 68 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 4 4 Read Coils Modbus Function Code 01 0x01 This function returns the state of the relay coils 0 denotes that the coil is not energized 1 denotes that the coil is energized Request Valid starting address can fall in the range of 0x0000 and 0x0009 Relay 1 is at address 0x0000 Relay 2 is at address 0x0001 Relay 3 is at address 0x0002 and so forth Multiple relays may be read at the same time by specifying the correct starting address and quantity of coils to be read Start Address 0x0000 coil 1 to 0x0009 coil 10 Coil Quantity 0x0001 1 coil to OxO00A 10 coils The sum of the start address and coil count cannot exceed the maximum coil count or an error response will be returned Modbus TCP Request Frame Example Read Coils 2 through 10 Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0006 Unit Identifier 1 byte Slave Address
37. Plus model allows you to control the relays using inputs or events Using an input or event to control the relays was described throughout previous sections of the manual and will not be described here 3 1 Browser Operation Once WebRelay 10 is set up users can access the Control Page using a web browser by typing the IP address of WebRelay 10 into the web browser address bar For example using the default IP address the user would enter http 192 168 1 2 If the IP address is changed from the default the user must use the new IP address Note that if any port is used other than the default port 80 the port must also be included in the request For example accessing the unit at port 8000 would be as follows http 192 168 1 2 8000 The following screen appears when the Control Page is Selected 800 WebRelay 10 WebRelay 10 Input 1 Count 0 Input 2 OFF Count 0 Relay 1 Con J orr J PULSE Relay 2 EN ON OFF J PULSE Relay 3 Pon Yor TS Relay 4 OFF on J orr PULSE J Relay 5 Relay 6 Con J orr J PULSE Relay 7 OFF ON J OFF J PULSE Relay 8 DF on J OFF PULSE Relay 9 OFF ON J orF J PULSE J Relay 10 Con J OFF J PULSE Sensor 1 Sensor 2 Sensor 3 extVar0 Con orr s5 set Current Time Fri 10 Dec 2010 10 48 00 Figure 3 1a Control Page Xytronix Research amp Design Inc page 57 Operation WebRelay 10 Users Manual Header Displays the text entered i
38. RES SHOULD BE PROPERLY ATTACHED CRIMPED TO THE CONNECTORS AND CONNECTORS SHOULD BE PROPERLY ATTACHED TO THE CIRUCIT BOARD OR RELAYS 2 2 1 Power Supply Connection WebRelay 10 requires power for its internal logic circuits Connect a 10 36VDC power supply to the Vin and Gnd terminals Note that a regulated power supply is recommended such as a wall mount AC DC adapter Verify that the adapter is rated for the operating current of WebRelay 10 See Appendix H Specifications for current requirements Multiple WebRelay 10 units may be connected to a single power supply by connecting the power supply input terminals in parallel The power supply must have a high enough current rating to power all units connected See Appendix H Specifications for current requirements 2 2 2 Relay Connection Direct connection to relay contacts is provided through tab connectors located on the top of the relays Do not exceed the specified load ratings for relay contacts see Appendix H Specifications for load ratings 2 2 3 Network Connection Connect the Ethernet port to a 10 Base T or 10 100 Base T Ethernet connection This typically connects to an Ethernet hub switch or router For configuration WebRelay 10 may be connected directly to the Ethernet port on a computer using a crossover cable Otherwise for connection through a hub or router a standard straight through cable should be used Xytronix Research amp Des
39. Rae A A be eR ee E 57 32 XML Operatoria eai agdas apio sa aa epedtepasvenecsussaevd capeetbnsedabinesdstesesbeeustles cavedatnteontuyactenraty ra er i ti ba eani dite 59 3 3 Configuring Events Through GET Requests WebRelay 10 Plus ONlY ooooocccnncccononccononccononcnonancnnnrnconnon co nnrnnarnn nn 64 3 4 Modbus Operati Ms e nnne n A a eee a hee ae eve ees 66 9 Email Notifica OT es a A a a e a led e e bonds 81 Appendix A Restoring Factory Default SettingS ssssssuussnunrenurrnnnrnnnrnnnnrnnnrenunnnnnnnnnnnnnnrnnnnnnnnnennnnnnnnnnnnnnnnnennnnnnnnnnnnn nanne 83 Appendix B Installing New FirMWare oooommncccconnnnnccccnncncccrnnnnccrrr nena 84 Appendix C Accessing WebRelay 10TM Over the InterNet oooococcccinnnnnccccnnnnoccccnnnnoncnccnnnnnnnnncnnnnnnnr nr nnnnnn renacer rentas 86 Appendix D Log Files WebRelay 10 Plus only ss ssssusssunsuusrennrnnnnnnnnnnunnnnnnnnnnnnnnnnnnnnnnunnnnnnnnnnnnunnnnnnnnnnnnnnnnnnnnnnnnnnnnn ennnen 90 Appendix E External Server and Remote ServiceS oocoocnnnccccinnnoncccccnncnccccnonnnnnnnc cnn rre 93 Appendix F SNMP Requests Objects and Community StringS s ssssessersssnnnrennrnnnnrnnnrnnnnnnnnnnnnnnnnnrnnnnnnnnrennnnnnnnnnnnnnnnn nnn 95 Appendix 6 BASIC Scripts vivi a ai p aa naaa 98 Appendix Hi Specifications da 104 Appendix I Mechanical Informati0N ooocoonnonnccconnnnnicnnnnnnnccnnnnnn nc 107 Alphabetical Indeksin a ena eh id eel ain ia ns 108 page 2 Xytronix
40. Refresh Rate setting When set to NO the web page will need to be manually refreshed to show the current status of the unit in the control page Refresh Rate When the Auto Refresh Page option is set to Yes this field specifies the time interval in seconds that the page will be refreshed It can be set from 1 to 32 seconds Display Configuration This field sets the options that are displayed on the Control Page Display State For Inputs 1 and 2 Relays 1 10 and Sensors 1 3 this controls whether the current states of the Relay Input and Sensor are displayed Display Counter When checked the counter is displayed for the selected input Xytronix Research amp Design Inc page 55 Installation and Setup WebRelay 10 Users Manual Display Counter Reset Button When checked a Reset button is displayed to reset the counter on the selected input Display On Off Buttons When checked an ON and OFF button is displayed for direct user control Display Pulse Button When checked a button allowing a user to manually pulse a specified relay is displayed Note Inputs Counters and Sensors are available on WebRelay 10 Plus only page 56 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation Section 3 Operation WebRelay 10 can be operated using a web browser by sending text commands to an XML status control page and or by sending Modbus TCP requests In addition WebRelay 10
41. Response Frame Example Inputs 1 and 2 ON Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0006 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Read Inputs 0x02 Data 2 bytes Byte count 0x01 0x01 Input State 0x00 0x03 0x03 RX String 00 01 00 00 00 04 FF 02 01 03 Errors Input Read Error Function Code 1 Byte 0x82 Exception codes 1 Byte 0x01 Function not supported 0x02 Incorrect combination of start address and input quantity Error Response Frame Example Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization between messages of 0x0001 server and client Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0003 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Error code 0x82 Data 1 byte Exception code 0x01 0x02 0x02 Rx String 00 01 00 00 00 03 FF 82 02 page 72 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 4 6 Read Sensors Modbus Function Code 03 0x03 WebRelay 10 Plus only The Read Holding Registers function is used for the temperature or humidity sensors 32 bit sensor values a
42. Revision 2 6 WebRelay lO Users Manual Covers X WR 10R12 1 X WR 10R12 IP CO www ControlByWeb com a division of Xytronix Research amp Design Inc Nibley Utah USA 2011 2015 Xytronix Research and Design Inc WebRelay 10 Users Manual Table of Contents Trademark and Copyright Information ccccseneseneeeeeeeeneeeeseenenseeesnseeeeaseeeenseeeseseeeeaseeeenseeeeaseeesaseeeeaseeeeaseeesaseenenseneeaseeeeasees 3 Wa AY A ee i RE ee et eet 4 EGG Statement mas Asics ete cates A eh elects A A A oui ATA Ad AA 5 Installation Guidelines Read Before Installidg ooooonnnncconnonococcnnnnncccncnnnnncnnncnnnnnnn rr nn 6 Section IMEFOCUCTION odiando T T N EA E A 7 1 1 Features nn A ee ey ee AAA EA A A A eae 8 1 2 Application dee 8 1 3 WebRelay 10 Models Available cece eecceceeeeeesnreeeeneeeeneeeeeaeeeseaeeecaeeesaeeeeaeeseeeesesaeeseaeeseneeeseneeesenieeseneeeenneeeseaas 9 14 Connectors amp NICO ii A tone 10 1 5 ACCESSING WERE y TOM rana id atada des 11 Section 2 Installation AMA Setup a ts 12 DAA MOUSE 12 22 CONNECtIOM anisan a eae e e aa te eelbe s tend e Sarees nos 13 2 3 Establishing Communications for SCtup ccceccceesseeeeneeeeeeneeeeeeeeenaeeeseneeeeeeeeeaeeseeaeeseeeeesaeeeeaeeseneeeseneeeeeneeeseeees 18 2 4 WebRelay 10 Setup Pages imac iia 23 Section 3 Operator oia TA A A T AE 57 3 1 Browser Operation e
43. There is no default setting for this field Note If the server name is entered and not the IP address the address of a DNS server will be required Mail Server Port This field is used to specify the SMTP Mail Server Port The default setting is 25 which is the standard SMTP port User Name If Required If the SMTP mail server requires authentication the user name must be entered here There is no default setting for this field Password If Required If the SMTP mail server requires authentication the password must be entered here There is no default setting for this field Return Email WebRelay 10 will not receive email messages but when WebRelay 10 sends email messages it must include a return email address This field is used to specify the return email address Note that although WebRelay 10 will send email messages with any email address specified in this field some email filters spam filters will not allow messages through that include an invalid email address There is no default setting for this field Email 1 to Email 5 Enter the email addresses of up to five recipients for alarm messages in these fields There are no default settings for these fields Email Length Choose either full or short email lengths When full is selected all visible fields in the control page will be included in the email message to be sent out however if short is selected the email content will only be a
44. Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 2 XML Operation Custom XML computer applications may be created to monitor and control WebRelay 10 This method does not use a web browser Diagnostics xml is available for troubleshooting and system monitoring 3 2 1 state xml Monitoring The state of the relays inputs and sensors can be monitored by sending a request to port 80 or port specified in setup This can be demonstrated by entering the following URL into the address bar of a web browser substituting the IP address as necessary http 192 168 1 2 state xml The following state xml page is returned lt datavalues gt lt inputlstate gt lt input2state gt lt hightimel gt 0 lt hightime2 gt 0 0 lt inputlstate gt 0O lt input2state gt 000 lt hightimel gt 000 lt hightime2 gt lt count1 gt 0 lt count1 gt lt count2 gt 0 lt count2 gt lt relayls lt relay2s lt relay3s lt relay4s lt relay5s lt relay6s lt relay7s lt relay8s lt relay9s tate gt 0 lt relaylstate gt tate gt 0 lt relay2state gt tate gt 0 lt relay3state gt tate gt 0 lt relay4state gt tate gt 0 lt relay5state gt tate gt 0 lt relay6state gt tate gt 0 lt relay7state gt tate gt 0 lt relay8state gt tate gt 0 lt relay9state gt lt relayl0state gt 0 lt relayl0state gt lt units gt F lt units gt lt sensorl lt sensor2 lt sensor3 lt sensor4
45. al web server can integrate multiple ControlByWeb products into a single control page In other words the user may not be aware that he she is using multiple ControlIByWeb devices but rather the user sees an integrated control page for the entire system In addition the use of an external web server allows programmers to create custom user interfaces that take advantage of the additional resources typically available on larger web servers including more memory and various web programming languages There are two approaches that an external server can use to communicate with WebRelay 10 and other ControlByWeb devices Direct Server Control and Remote Services Direct Server Control The first approach is for the external server to create a TCP connection whenever it needs to access WebRelay 10 In this case the external server opens the connection sends commands and or reads the device and closes the connection This method is ideal when the the web server and all of WebRelay 10 devices are on the same network without routers between them In this case the server can communicate with WebRelay 10 devices directly and securely since data never has to leave the local network When the server and WebRelay 10 are on different networks routers must be configured to allow appropriate access If a public network is used such as the Internet security precautions should be considered Remote Services The second approach i
46. alue to screen PRINT message relay message to screen User Defined Variables Two types of variables are available for use in the ControlByWeb BASIC interpreter user defined variables and predefined variables Up to 10 user defined variables are allowed to be used in scripts Variables are represented by single lower case characters ranging from the letter a to the letter j They are always global and stored internally as floating point numbers Variables are defined using the LET statement Examples Let b 5 variable b will be set to 5 Let d b 2 variable d will be set to 7 Predefined Variables The following are useful predefined variables for the ControlByWeb BASIC interpreter These are useful for accessing internal values and features states Note Some models may not contain digital inputs analog inputs and or relays and thus would not have digital input analog input and or relay variables Timer Variables Six timers are available for use in BASIC scripts They are designated as t0 through t5 Timers can be set to any positive integer or 0 by using the LET statement As soon as a value is assigned to a timer it will begin to count down immediately by decrementing one count every 100ms until it reaches zero Examples Let t3 1500 set timer 3 to 150 seconds Let tl 0 disable time 1 Relay Variables The relays can be turned ON turned OFF pulsed toggled or read in BASIC scripts The LET st
47. amp Design Inc page 27 Installation and Setup WebRelay 10 Users Manual 2 4 3 Advanced Network Tab Note These settings are not used for most installations 000 WebRelay 10 http 192 168 1 2 setup html Q ControlByWeb x Wi Setup sensors event seo convolregescup contro paa PCr ltr ir t te YesO No Modbus Port 502 AE ASE EA Yeso No Server Name IP Address MM Aa s000 AER SA 00 0C C8 02 4D 66 ControlByWeb X 10 AA N 1 Minutes SEL CT YesO No QUAN 192 168 1 TA 161 SNMP Trap Port N un T IP Filter Range 1 N un mn z o un uw alo un un oln o un un o o ST E IP Filter Range 2 T o o lo z Figure 2 4c Advanced Network Tab Modbus Enabled WebRelay 10 can support Modbus TCP Modbus is a messaging structure protocol used in industrial manufacturing control and automation It is an open protocol and offers interoperability with software and devices from other manufacturers This is enabled by selecting Yes in this field The default setting for this field is No See 3 4 Modbus Operation for more information on using WebRelay 10 on a Modbus network Note Modbus communications are disabled whenever the Control Password is enabled Modbus Port This specifies the port used for Modbus TCP communications with WebRelay 10 By default this is set to port 502 which is the standard Modbu
48. aracters may be entered in this field The default text is ON Off Button Label The text entered in this field appears in the OFF button for the corresponding relay on the Control Page Up to 10 characters may be entered in this field The default text is OFF Pulse Button Label The text entered in this field appears in the Pulse button for the corresponding relay on the Control Page Up to 10 characters may be entered in this field The default text is PULSE On Status Text The text in this field specifies the text that will be displayed in the status field in the Control Page and in email messages when the corresponding relay is on Up to 10 characters may be entered in this field The default text is ON Off Status Text The text in this field specifies the text that will be displayed in the status field in the Control Page and in email messages when the corresponding relay switches OFF Up to 10 characters may be entered in this field The default text is OFF Pulse Duration When WebRelay 10 receives a pulse command for the relay the relay will switch ON for the time specified in this field The time is specified in seconds and can range from 0 1 seconds to 86400 seconds in 0 1 second increments The default time is 1 5 seconds Note When a pulse command is sent through the command interface the command can include a pulse time which will over ride this value for that pulse only Relay State at Powerup This drop down men
49. atement is used to set the relay state The state options available are O turn relay off 1 turn relay on 2 pulse relay 5 toggle relay The pulse time is specified in the Relays setup tab Relays are designated as relay1 relay2 etc which correspond to Relay 1 Relay 2 etc Examples Let relayl 1 turn on relay 1 Let relay2 0 turn off relay 2 Let relayl 2 pulse relay 1 Let relay2 5 toggle relay 2 Let a relay2 read the state of relay 2 state will be 0 or 1 Input Variables WebRelay 10 Plus only The input states can be read in BASIC scripts The inputs are designated as input1 and input2 Xytronix Research amp Design Inc page 101 Appendix G BASIC Scripts WebRelay 10 Users Manual Example Let a inputl sets a equal to value of input 1 Temperature Humidity Sensor Variables WebRelay 10 Plus only Each temperature sensor or humidity sensor can be read in BASIC scripts The sensors are designated as temp1 temp temp8 Example If temp2 gt 80 Then If temperature sensor reads greater than 80 degrees then Let relay2 1 Turn on relay 2 End If Date and Time Variables WebRelay 10 Plus only The variables time and date are predefined read only variables that store the current date and time They can be used to schedule events and activities such as sending emails reading temperature or setting relays The date uses the mm dd yyyy for
50. aults Device has been reset to factory defaults Failed DNS Lookup Unable to lookup mail server due to an incorrect DNS setting Bad Username Email was not sent due to an incorrect user name EMAIL Bad Password Email was not sent due to an incorrect password Authentication Required A user name and password are required by the mail server No Response No response from SMTP server CLOCK RTC Reset Real Time Clock has been reset Request Attempt Device attempting to connect to NTP Server NTP Failed DNS Lookup Unable to lookup NTP server name due to an incorrect DNS SERVER setting Success Device successfully connected to NTP Server Failed DNS Lookup Unable to lookup Remote Server due to an incorrect DNS setting beavis Connection Attempt Connection port with Remote Server has ben opened Started Connection Closed Connection port with the Remote Server has been closed DHCP Address Acquired IP address request successful and IP address assigned Lease Renewal IP address assigned to device was renewed MAIN_MCU New Firmware Loaded New firmware has been loaded to the device Xytronix Research amp Design Inc page 91 Appendix D Log Files WebRelay 10 Plus only WebRelay 10 Users Manual This file is read by requesting the syslog txt file For example using the default IP address the following command would be used http 192 168 1 2 syslog txt Note The setup user name and password are required to access this
51. ays 1 Days 1 Days 1 Days 1 Days 1 Days Days M F M F All M F M F All Count 0 0 0 0 0 0 Action pulse relay pulse relay change pulse relay pulse relay change schedules schedules Affected 2 2 2 2 2 1 Pulse Duration 3 3 n a 3 3 n a In the above example the Affected row applies to relays when a relay action is selected or schedules when a change schedule action is selected The security system example could also be changed to schedules 1 and 2 allowing for different hours of operation for summer and winter schedules Additional lunch or break bells could also be added to schedules 1 and 2 or added in schedules 3 and 4 Events 5 and 8 would also enable and disable schedules 1 2 3 and 4 Additional equipment could be controlled by event schedules such as lighting compressors and magnetic door locks Xytronix Research 8 Design Inc page 51 Installation and Setup WebRelay 10 Users Manual 2 4 11 Script Tab WebRelay 10 can be used to run simple custom programs written in a language similar to BASIC This page is used to load and execute these programs Before it can be loaded to WebRelay 10 a script must first be written as a txt file The file must then be uploaded to WebRelay 10 The maximum size of script that can be uploaded to the device is 2K bytes Information on writing a basic program for WebRelay 10 can be found in Appendix G Basic Scripts Note An ASCII standard text file forma
52. c WebRelay 10 Users Manual Operation 3 5 Email Notification 3 5 1 Email Notification Description WebRelay 10 can be configured to send messages to five email addresses when certain events occur Events that can trigger email messages include input state changes relay state changes temperature humidity changes and commands sent from a BASIC script When an email message is sent it looks similar to this WebRelay 10 Trigger Relay 1 ON Input 1 ON Input 2 OFF Relay 1 ON Relay 2 OFF Relay 3 OFF Relay 4 OFF Relay 5 OFF Relay 6 OFF Relay 7 OFF Relay 8 OFF Relay 9 OFF Relay 10 OFF Sensor 1 73 5 Sensor 2 XX X Sensor 3 xx x Sensor 4 XX X Sensor 5 XX X Sensor 6 XX X Sensor 7 XX X Sensor 8 XX X Note Input relay and sensor names as well as ON and OFF status text may be customized by the user installer in the setup pages The same field names are used in the Control Page Note Inputs and Sensors are only available on WebRelay 10 Plus Subject Line The top line that reads WebRelay 10 appears in the subject line of the email message This is the same text that appears as the header on the Control Page It is set in the Main Header Text field under the Control Page Setup tab Trigger The first line displayed in the body of the message shows the event that triggered the message The text Trigger will always appear and cannot be changed The remaining text includes the trig
53. cify days on which the event will occur Cancel update Figure 2 4m Event Setup Current Date Time This field displays the current date and time as specified in the Date Time tab Schedule WebRelay 10 Plus can be setup to use multiple schedules The master event schedule is schedule 0 See Schedules at the end of this section for more information Description Text entered here is used to name and describe each event The default text is Event Description Start Date This field is used to enter the start date of the event The date is entered by first selecting the correct month and year by using the left and right arrows at the top of the calender The single arrows lt and gt change the month and the double arrows lt lt and gt gt change the year Once the current month and year are displayed the date should be entered by selecting the day Start Time HH MM SS The start time of the event is entered in the drop down menus as HH MM SS HH represents hours in 24 hour format 00 23 MM represents minutes 00 59 SS represents seconds 00 59 Default setting is 00 00 00 Period When events are configured to occur more than one time any entry other than 1 in the Count below the period field specifies the time between the beginning of events This time can be Xytronix Research amp Design Inc page 49 Installation and Setup WebRelay 10 Users Manual specified in Seconds Mi
54. d to turn the relays ON and OFF at specific times Up to 100 events can be created Each event can occur one time or multiple times e00 WebRelay 10 a gt Ls Le ge 4 nttp 192 168 1 2 setup htm Wi Setup Main Network Advanced Network Password Date Time Logging Inputs Relays AQ ControlByWeb Sensors Events Script Control Page Setup Control Page ler OnO OffO e 11 15 2010 10 41 5 Event y Schd Start Date Time Period Count Act s Next Occurance Figure 2 4l Events Tab A list of all scheduled events and information about each event is displayed in a table Events can be sorted according to each column in ascending or descending order The following columns are displayed Events Scheduler On Off Turns scheduled events ON or OFF ON is selected by default Current Date Time Displays the current date and time Event The number and name of events that are listed Schd The schedule where the event is located 0 is the default schedule Start Date Time The start date and time 24 hour of the event Period The time between the start of successive events Count The number of times the event will occur Action What action the relays or schedule will take Act s Which of the relays or
55. e Link LED will stop flashing and remain lit WebRelay 10 will be set to factory defaults with an IP address of 192 168 1 2 6 Refer to section 2 3 Establishing Communication for Setup to reconfigure the WebRelay 10 Verify the new version of firmware has been installed by viewing the default setup page with a web browser htto 192 168 1 2 setup html ES ControlByWeb Programmer V1 5 File Check Firmware compatibility Firmware compatible with device You can now release the reset button Erase old firmware Done Upload firmware R etting device Done Upload Firmware Figure Appendix B 2 Firmware Update Complete Xytronix Research amp Design Inc page 85 Appendix C Accessing WebRelay 10TM Over the Internet WebRelay 10 Users Manual Appendix C Accessing WebRelay 10 Over the Internet WebRelay 10 can be monitored and or controlled from a remote location over the Internet Once WebRelay 10 can be accessed on the local network almost all of the settings required to provide remote access are in the router and not in WebRelay 10 This guide is not meant to be a tutorial in router setup but rather to provide a basic overview of remote access For specific details the user should refer to the instruction manual for the router on the local network Users not familiar with basic IP networking should study one or more basic IP networking tutorials before proceeding many tutorials are available on the I
56. e network DHCP Dynamic Host Control Protocol is a mechanism that automatically assigns an IP address to a computer or other devices when it is connected to a network This eliminates the need to manually enter the IP address When a computer is connected to the network another device on the network called a DHCP server detects the presence of the computer and dynamically assigns the IP address to that computer On many small networks the DHCP server is built into the router DHCP works well for client devices such as computers but is not ideal for servers This is because servers usually don t initiate communications with other devices but rather they wait for a request from clients To make this request the client must know the IP address of the server If a server gets its IP address dynamically the IP address may not always be the same so client devices may not be able to find the server For this reason servers usually use an IP address that is fixed and does not change The WebRelay 10 Plus is a server and manual IP address assignment is usually recommended IP Address Enter the IP address for WebRelay 10 in this field The IP address is specific to the network where WebRelay 10 will be installed and must be obtained from the network administrator For more information on IP addresses and remotely accessing WebRelay 10 over the Internet see Appendix C Accessing WebRelay 10 Remotely Over the Internet The default set
57. e relays The buttons can be removed when needed in the Control Page Setup tab and the text within the buttons can be customized in the Relays tab Sensor 1 8 WebRelay 10 Plus only These rows display the current temperature or humidity measured by the associated sensors Each row can be displayed as shown or not displayed by checking or unchecking the appropriate boxes under the Control Page Setup tab in the setup pages The text in the left column by default reads Sensor 1 through Sensor 8 is specified in the Sensor Description field under the Sensors tab in the setup pages External Variables These rows display the current state of the five external variables These rows can be displayed as shown or not displayed by checking or unchecking the appropriate boxes in the extvar setup page The text in the left column is specified in the Description field on the extvar setup page The state of the extvar is shown to the right of the description text By default the status text will read ON or OFF To the right of the extvar status buttons and an input box are provided to control the state value of the external variable Current Time WebRelay 10 Plus only Displays the current time that is set using the Date Time tab in the setup pages Note If the sensors are not configured sensor addresses selected for each sensor or are unreadable the display will read x x rather than displaying a false numerical value page 58
58. each bit represents one day of the week Bit 0 is Saturday and Bit 6 is Sunday See the table below for some common values Action This number represents which relay will be affected by the event This value is the base ten version of a binary number where each bit represents the ON OFF state of one relay Bit O corresponds to relay schedule 1 and Bit 9 corresponds with Relay 10 page 64 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 3 1 Common Base Ten Values for Event Days Sun Mon Tues Wed Thurs Fri Sat Base 10 Value Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 1 1 1 1 1 1 1 127 0 1 1 1 1 1 0 62 0 1 0 1 0 1 0 42 0 0 1 0 1 0 0 20 0 0 0 0 0 0 1 1 Xytronix Research amp Design Inc page 65 Operation WebRelay 10 Users Manual 3 4 Modbus Operation 3 4 1 3 4 2 WebRelay 10 can be controlled and monitored using Modbus TCP protocol This provides a standard means of using WebRelay 10 with devices and software from other manufacturers This section is not a tutorial on Modbus and it is assumed that the reader is already familiar with Modbus Detailed Modbus information can be found at http www modbus org Note Modbus communications are disabled whenever the Control Password is enabled This is because Modbus TCP does not provide a mechanism for password protection Make sure the Control Pass
59. ebRelay 10 with serial number 00 0C C8 01 00 01 to 10 10 10 40 the following command would be used arp s 10 10 10 40 00 0c c8 01 00 01 3 Next type ping 1 102 new IP address For example if the new IP address is 10 10 10 40 the following command would be used ping 1 102 10 10 10 40 4 Proceed with WebRelay 10 setup in section 2 4 Once setup is complete it may be necessary to clear the arp cache to configure additional WebRelays This is necessary because each unit has the same default IP address but a different unit serial number MAC address Clearing the arp table can be done by typing arp d in the command prompt window page 18 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup Linux Unix Instructions 1 2 Open a terminal and change to root user su then enter root password Type arp s new IP address serial number of WebRelay 10 Note IP address format is xxx xxx xxx xxx The serial number can be found on a label on the module board The format is SS SS SS SS SS SS For example to set WebRelay 10 with serial number 00 0C C8 01 00 01 to 10 10 10 40 the following command would be used arp s 10 10 10 40 00 0c c8 01 00 01 Next type ping s 102 new IP address For example if the new IP address is 10 10 10 40 the following command would be used ping s 102 10 10 10 40 Proceed with WebRelay 10 setup in section 2 4 Once
60. ecture Circular Buffer Log File Size 512K max 17900 logs Unlimited data storage from Web Monitoring Service Password Settings Password protection on setup page Yes Password protection on Control Page Optional Password Encoding Base 64 Max password length 13 character Electromagnetic Compliance IEC CISPR 22 CISPR 24 FCC 47CFR15 EU EN55024 EN55022 Product Safety Compliance IEC 60950 1 EN 60950 1 page 106 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix Mechanical Information Appendix I Mechanical Information Voltage Input 10 36VDC Locations may vary on older modules Gnd Vin Relay 2 Relay 3 Relay 1 Relay Contacts Normally Closed Normally Open Common ly a Pover Power LED gt WebRelay 10 co c eiee Gnd Vin Relay LED gt ow wt y 6 green when coil energized 4 T 3 E E E A Relay 6 Relay 7 Relay 8 Relay 9 Relay 10 Pa e LINK 5 Input LED Terminal Reset ACT Ethemet Connector LED Connector WebRel ay 10 372408 1NT 3 1 2 42 in page 107 Xytronix Research 8 Design Inc Alphabetical Index WebRelay 10 Users Manual Alphabetical Index 1 Wire nat A EEE E EE 105 10 Bas Tita da 13 10 100 Base iii ic 13 A Advanced Network Tab ccccccceeceeeeeeeeeeeeeeees 28 Ap
61. ed at 6 am Monday through Friday The web interface could be used to disable the system for any authorized exceptions page 50 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup Field Name Event 1 Event 2 Application Description Schedule 0 0 Schedule 0 cannot be disabled by other events Description Security ON Security OFF User description of event Start Date Current Day Current Day Set to current or previous day Start Time 20 00 00 06 00 00 Start time in 24 hr format Period 1 Days 1 Days Event occurs daily Days M F M F Security system is disabled during work hours and remains on over weekend Count 0 0 Event is always in effect set to zero Action turn relay on turn relay off Security system is controlled through a Relay 1 Affected 1 1 Pulse Duration n a n a The value is ignored except for a pulse action Schedule 1 and 2 Events Shift alarm sounds at 8 am and 5 pm Monday through Friday during winter months but shifts to 6 am start time during summer Field Name Event 3 Event 4 Event 5 Event 6 Event 7 Event 8 Schedule 1 1 1 2 2 2 Description Summer AM Summer AM End Summer Winter AM Winter AM End Winter Bell Bell Bell Bell Start Date 30 May 30 May 01 Sep 01 Sep 1 Sep 30 May Start Time 08 00 00 17 00 00 00 00 00 06 00 00 03 00 00 00 00 00 Period 1 D
62. elay and input state sensor data and events Both periodic and event based logging are supported The logged data is stored in internal nonvolatile memory and can be retrieved by entering the command http WebRelay 10 IP addressVlog txt For more information on logging see Appendix D Log Files Note Changing the log settings will erase the current log file 000 WebRelay 10 noca O mpin2s8 L2 seunnm KO ConvoByed_ W Setup Sensors l Events l Script l Control Page Setup Control Page l Items logged as result of an event only Not periodically ETT AE NE YesO No SCAN 01 00 Logging Rate 60 Mins HoursO DaysO Event Logging OnlyO Sensor Trigger Delta 2 0 po Log Event Trigger Input 2 Relay 1 Relay2 Relay3 Relay 5 Relay 9 Sensor 3 Events MODBUS Requests SNMP Requests Logging Configuration 7 F F Lo E E E E E E E E E E E E E Y Y F F A Y gt F A F J Y hal hal AE TAE TES None ReadsO WritesO LOSE TAO Disabled Figure 2 4g Logging Tab Logging Enabled When this option is set to Yes WebRelay 10 Plus will record data as configured on this page The default setting for this option is No Note This option controls data logging but not system logging System logging is always enabled Start Time If a logging interval is specified periodic logging rather than event logging logg
63. f not used OxFF Function Code 1 byte Write coil 0x05 Data 4 bytes Relay address 0x0000 0x0009 0x0003 Relay value OxFF 0x00 OxFF Padding 0x00 0x00 Rx String 00 01 00 00 00 06 FF 05 00 02 FF 00 Errors Single Coil Write Error Function Code 1 Byte 0x85 Exception codes 1 Byte 0x01 Function not supported 0x02 Address out of range 0x03 Incorrect relay value or padding value Xytronix Research amp Design Inc page 75 Operation WebRelay 10 Users Manual Error Response Frame Example Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization between messages of 0x0001 server and client Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0003 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Error code 0x85 Data 1 byte Exception code 0x01 0x02 0x02 RX String 00 01 00 00 00 03 FF 85 03 page 76 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 4 8 Write Multiple Coils Modbus Function Code 15 0x0F One to two bytes can be written to set the state of all 10 relays each bit representing one relay The least significant bit of the lower byte represents Relay 1 and the 2nd bit of upper byte representing Relay 10 Upper Byte Lower Byte Bit15 14 13 12 11
64. fective page 44 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 9 Sensor Tab WebRelay 10 Plus only This tab is used to configure temperature humidity sensors and associated alarms WebRelay 10 Plus will automatically detect whether a temperature or humidity sensor is connected WebRelay 10 BQ ControlByWeb Setup Sensora Events script control Page setup control Page Sensor AAA Sensor 1 2873DFA0010000EC Sensor Address Refresh List NET AA 90 0 High LowO PAF Tibet 20 0 HighO Low Deadband 0 5 Email Option No Email Messages Use Email Address ODOO Remote Service SNMP when Submit X Reset Figure 2 4j Sensors Tab Sensor Up to eight sensors can be connected to WebRelay 10 Plus This drop down list selects the sensor to be configured The fields below are the same for each sensor Sensor Description The text in this field appears to the left of the corresponding temperature humidity reading on the Control Page This text also appears in the email status message when email is enabled This field can be up to 24 characters in length The default text in this field is Sensor Sensor Address Each sensor connected to WebRelay 10 Plus should be associated or assigned to a sensor number This identifies the name location and function of the sensor Every temperature humidity
65. file If the TCP port has been changed not port 80 the port will be required to read the file For example using the default IP address and port 8000 the log file would be read as follows http 192 168 1 2 8000 syslog txt To erase the file use http 192 168 1 2 syslog txt erase 1 page 92 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix E External Server and Remote Services Appendix E External Server and Remote Services Note The following methods are supported by WebRelay 10 however Xytronix Research amp Design Inc does not provide or support custom third party applications or external web servers Accessing WebRelay 10 with Custom Software or Third Party Applications Custom applications can send commands to WebRelay 10 for monitoring and control The application interface can be used to provide a custom user interface access to multiple units in a single screen and allow for automation logging and other application specific features Using an External Web Server Rather than accessing WebRelay 10 directly from a computer an external web server can be used The term external web server is used here to mean a separate web server such as Apache or IIS that is not the web server built into WebRelay 10 In this scenario users access custom web pages that reside on the external web server and the external web server communicates with WebRelay 10 An extern
66. g purposes or for any purpose where its failure could cause serious injury or the loss of life This unit must not be used in any way where its function or failure could cause significant loss or property damage Security Notes WebRelay 10 does not employ a general purpose computer operating system and does not have features such as telnet FTP SSH nor uncontrolled open ports This means it is unlikely for someone to break in to WebRelay 10 and access other devices on your local network The simplicity of WebRelay 10 makes it a inherently secure device Nevertheless as with any device installed ona network appropriate security precautions should be observed If WebRelay 10 is installed on the Internet it is recommended that passwords be enabled for the Control Page Passwords should be at least 8 characters in length and use a combination of upper and lower case letters and numbers For additional security a firewall may be used to limit access to selected IP addresses Another option may be to set up a Virtual Private Network VPN between the network where WebRelay 10 resides and the client machine web browser another ControlByWeb TM product etc Final Installation Notes This ControlByWeb product supports connection to 10 Mbps and 100 Mbps networks Although 100Mbps networks are faster the amount of data transferred to and from this device is very minimal and little if any performance increase will be gai
67. ger name the current state of the relay or input or the current temperature humidity of the sensor The text that describes the trigger and its current state are configured in the setup pages as described below Current Status of Relays Inputs and Sensors The remainder of the email message will display the same information shown on the Control Page Fields not displayed in the Control Page will not be included in the email message Displayed fields may be configured in the Control Page Setup page Xytronix Research amp Design Inc page 81 Operation WebRelay 10 Users Manual 3 5 2 Email Notification Setup Email notification requires that the following fields are properly configured See Section 2 4 2 for a description of each field Network Tab IP Address Subnet Mask Gateway Preferred DNS Server this is required if Mail Server is entered by name and not by IP address Mail Server SMTP User Name If Required Password If Required Return Email Email 1 Email 2 Email 3 Email 4 Email 5 Note WebRelay 10 must be power cycled power disconnected then reconnected before network settings take effect Only the settings on the Network tab require power cycling before taking effect Email triggers can be generated within a BASIC script See Appendix G BASIC Scripts or can be explicitly defined for each relay input and sensor under Relays Inputs and Sensors tabs The email options and recipien
68. he WebRelay 10 After the update all settings will be lost and the device will return to its default IP address of 192 168 1 2 Configure the PC to the same subnet as the IP address 192 168 1 2 such as 192 168 1 10 For instructions on doing this see section 2 3 Establishing Communications for Setup ES ControlByWeb Programmer V1 5 DAR Upload Firmware Figure Appendix B 1 Firmware Update Utility 3 Open the bootloader exe utility on the computer by double clicking on the downloaded file Figure Appendix B 1 4 Within the cowProgrammer utility programmer select File then Open Specify the firmware image page 84 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix B Installing New Firmware downloaded from the ControlByWeb web site Device Upgrade Procedure Carefully follow the following steps to put the WebRelay 10 into bootloader mode and perform the upgrade 1 Remove DC power to WebRelay 10 2 Using a small non conductive tool press and hold the reset button 3 While holding the reset button apply power to WebRelay 10 The Link and Act lights will flash Continue to hold the reset button for the next step 4 While holding the reset button press the Upload Firmware button at the bottom of the ControlByWeb Programmer window After the programming process begins the reset button can be released 5 Programming will take approximately 20 30 seconds th
69. he time Manually or Sync with NTP server The options that follow this field will change based upon how this option is set Manually requires the user to enter the time and date When this option is selected parameters 3 4 appear Sync with NTP server allows the user to set the clock automatically by using an NTP Network Time Protocol server Manual Time Configuration Date The current date is entered by first selecting the correct month and year using the left and right arrows at the top of the calender The single arrows lt and gt change the month and the double arrows lt lt and gt gt change the year Once the current month and year are displayed select the correct day which will then be highlighted Xytronix Research amp Design Inc page 33 Installation and Setup WebRelay 10 Users Manual Time 24 Hour Format Enter the time as HH MM SS HH represents hours in 24 hour format 00 23 MM represents minutes 00 59 SS represents seconds 00 59 00 WebRelay 10 cA Qr ControlByWeb Sensors Events Script Control Page Setup Control Page PERSA EA Mon 15 Nov 2010 10 14 10 Set Time Sync with NTP server b Server Name IP Address SMe latte Once Daily WeeklyO MonthlyO ieee CA EN Yeso No WEN 7 00 PEITIEN ERE Yes NoO Daylight Savings Start 2nd 3 Sun B Mar E Daylight Savings End Sun 13 Figure 2 4f Date Time Tab Sync with NTP Server
70. his field is O and the event is active then the event is always on lt relay gt Event will apply to the relay specified 1 10 lt action gt One of the follow actions is applied to the event turn relay s on turn relay s off pulse relay s toggle relay s set extVar0 clear extVar0 change schedules lt pulseDuration gt This field indicates the time in seconds that the relay will energized X is replaced by the relay number or input number page 62 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation 3 2 3 XML Diagnostics There is a special diagnostics xml can be requested by by entering the following in the web browser address bar http 192 168 1 2 diagnostics xml The following diagnostics xml file is returned lt datavalues gt lt memoryPowerUpFlag gt 1 lt memoryPowerUpFlag gt lt devicePowerUpFlag gt 1 lt devicePowerUpFlag gt lt powerLossCounter gt 1 lt powerLossCounter gt lt datavalues gt Diagnostic tags are given in the table below Tag Description lt memoryPowerUpFlag gt A loss of power to the capacitor backed real time clock is indicated by a WebRelay 10 Plus value of 1 The internal capacitor can power the real time clock for several only days when main power is lost If the real time clock loses power the time will have to be reset By default the flag value is 1 It is not automatically set and will read
71. his field If the password is not entered identically in both fields the password will not be changed page 32 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 5 Date Time Tab WebRelay 10 Plus only WebRelay 10 Plus uses the time for scheduled events such as turning the relays ON or OFF at scheduled times and for logging a time stamp is included with each logged event The time is stored and displayed in 24 hour time format WebRelay 10 Plus has a capacitor backed real time clock circuit that will keep track of time for several days in the event of a power failure 000 WebRelay 10 Ahtp 192 168 1 2 setup html Q ControlByWeb Ww Setup Main Network Advanced Network Password Date Time Logging Inputs Relays Sensors Events Script Control Page Setup Control Page PESA AA Mon 15 Nov 2010 10 13 35 Set Time ipea NE Su Tu We Th Fr Sa Po fat 2 3 4 ls Te 7 9 10 11 12 MECO CI E CI EC NE Time 24 Hour Format llo 1 13 DENIA E EHE Yes NoO Daylight Savings Start 2nd E Sun E Mar E Daylight Savings End East E sun Es Submit Reser Figure 2 4e Date Time Tab Set Time Manually Current Date Time This is the current date and time stored in WebRelay 10 Plus The time is stored and displayed in 24 hour format Set Time This drop down list offers two options for setting t
72. hown below the relay will pulse for 10 seconds Ten seconds is represented using a floating point number of 41200000 It is transferred as 00004120 Pulse Coil Function Code 1 byte 0x10 Start Address 2 bytes 0x0010 relay 1 0x0022 relay 10 Register Quantity 2 bytes 0x0002 0x0014 2 registers for each relay even number Byte Count 1 byte 0x04 0x28 Multiples of 4 Pulse Duration 4 bytes per relay Ox3DCCCCCC 0x47A8C000 Little endian Format OxCCCC3DCC 0xC00047A8 Request Relay Number Relay Address Relay Number Relay Address 1 0x0010 6 0x001A 2 0x0012 7 0x001C 3 0x0014 8 0x001E 4 0x0016 9 0x0020 5 0x0018 10 0x0022 Modbus TCP Request Frame Example Pulse Coil 4 for 5 s and Coil 5 for 5s Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x000F Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Pulse Coils Write Multiple Registers 0x10 Data 8 42 bytes Start address 0x0010 0x0022 0x0016 Register quantity 0x0002 0x0014 0x0004 Byte count 0x04 0x28 0x08 Pulse Duration OxCCCC3DCC 0x00003F00 0xC00047A8 0x000040A0 Xytronix Research amp Design Inc page 79 Operation WebRelay 1
73. ign Inc page 13 Installation and Setup WebRelay 10 Users Manual Computer Crossover Cable Ethernet Switch Computer WebRelay 10 Figure 2 2a Network Connection WebRelay 10 can be used on a wireless network by connecting through an Ethernet bridge or a wireless router WebRelay 10 is connected directly to the wireless device Wireless Ethernet Bridge or Router WebRelay 10 Figure 2 2b Wireless Connection Note The wireless Ethernet bridge or router must be properly configured for the wireless network Refer to the installation instructions for the wireless device Terminal Connector WebRelay 10 Plus only The removable 5 position terminal connector is used for connecting temperature sensors humidity sensors or discrete inputs The terminals are described in the table below IMPORTANT MAKE SURE WIRES ARE PROPERLY ATTACHED TO THE TERMINALS AND THAT THE SCREW TERMINALS ARE TIGHT page 14 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 5 pin connector pinout Pin Description Temperature Humidity Data This is the data line Dala connection for the digital temperature humidity sensors 5V Out This output voltage is used to provide power for the digital temperature humidity sensors Ground Ground connection for 5VDC output and Inputs Input 18 2 Discrete Inputs Terminal Connector
74. imal temperature or humidity web10 webrelay ten sensorTwo 0 Value x x Decimal temperature or humidity TRAPS WebRelay 10 can send SNMP messages when a relay or input changes state or when a particular sensor value is reached The SNMP Trap must be configured for each sensor input or relay in the setup pages The following Traps are supported Relay Traps A change in state of the relay will cause the WebRelay 10 to send a Trap message Object Description Value web10 75 Relay one state change 0 or 1 0 OFF 1 ON web10 76 to 84 Relay xxxx state change 0or1 Input Traps WebRelay 10 Plus only When an input on the WebRelay 10 Plus changes state a Trap message will be sent Object Description Value web10 95 Input one state change 0 or 1 0 OFF 1 ON web10 96 Input two state change Oor1 Sensor Traps WebRelay 10 Plus only Two alarm thresholds can be configured for each sensor An SNMP Trap messages can be sent when page 96 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix F SNMP Requests Objects and Community Strings the temperature boundaries are crossed See 2 3 9 Sensor Tab for more information on configuring the sensor alarms Object Description Value web10 65 Sensor one alarm x x Decimal temperature or humidity web10 66 Sensor two alarm x x Decimal te
75. ing will occur Xytronix Research amp Design Inc page 37 Installation and Setup WebRelay 10 Users Manual relative to this start time For example if the start time is 01 00 and the logging rate is 6 hours logging will occur at 01 00 07 00 13 00 and 19 00 Start time is specified in 24 hour time format The default setting for this field is 01 00 Logging Rate This field is used to specify the time period of logging A numerical value is entered into the text field and the unit of time is selected using the adjacent radio buttons The range of values in this field is 1 20864 Time units are Minutes Hours and Days Periodic logging can be disabled by selecting the Event Logging Only radio button Sensor Trigger Delta WebRelay 10 Plus can be configured to log data when the temperature humidity measured by a sensor changes by the amount specified in this field This can be set from 1 0 to 24 0 degrees in 0 1 increments The default setting for this field is 2 0 degrees Logging Configuration This table is used to select which relays inputs and sensors get logged and which events trigger the logging The first column in the table identifies the relays inputs sensors etc that can be logged or cause logging events The second column is used to specify what gets logged The third column is used to specify which events can cause a log entry to be created When relays are selected as an Event Trigger logging will occ
76. is function returns the state of the discrete inputs Start Address 0x0000 input1 to 0x0001 input 2 Input Quantity 0x0001 to 0x0002 The sum of the starting address and the quantity of coils must not be greater than 0x0002 For example if you want to read 0x0002 both inputs then the start address must be 0x0000 To read the second input only the start address is 0x0001 with a quantity of 0x0001 Request Modbus TCP Request Frame Example Read Inputs 1 2 Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0006 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Read Inputs 0x02 Data 4 bytes Start Address 0x0000 0x0001 0x0000 Quantity 0x0001 0x0002 0x0002 TX String 00 01 00 00 00 06 FF 02 00 00 00 02 Response The inputs states are indicated by bits one and two of the status byte A1 indicates that the input is switched to ground ON A 0 indicates that the input is open OFF Data Byte hex LS Data Bits binary Input 2 State Input 1 State 0x00 0000 OFF OFF 0x01 0001 OFF ON 0x02 0010 ON OFF 0x03 0011 ON ON Xytronix Research amp Design Inc page 71 Operation WebRelay 10 Users Manual WebRelay 10
77. is option selects whether or not the selected script will be run after it has been uploaded The Submit button must be clicked to run the script External Variables External Variables are variables that can be used in BASIC scripts They are called External Variables because their values can be changed externally to the BASIC script using xml requests or through the Control Page This allows basic scripts to react to user input These variables are considered to be floating point numbers just like other variables in the BASIC script The following page is displayed when configuring External Variables la 00 http 192 168 1 2 extVarSetup html cQ ControlByWeb x External Variable Display State Display Button 1 Display Button 2 Display Input Box PEA LN extVard Button 1 Label ON AA OFF Status 1 Text ON ACERA ce OFF Figure 2 40 extVar Setup External Variable This drop down menu offers the option to configure each of the four External Variables Display State Checking this box will display the state of the selected External Variable on the Control Page Display Button 1 Checking this box will display a button on the Control Page Clicking this button on the Control Page will set the extVar to value 1 Display Button 2 Checking this box will display a button on the Control Page Clicking this button will set the extVar to value 2 Display Input Box Checking this box will display an input box o
78. l Page Network parameters require reboot before they take effect SAA YesO No calle tm 192 168 AE 255 255 rc CE Wim 192 Preferred DNS Server 192 Alternate DNS Server sl rin un un Ri i e w BBE w in HTTP Port 80 BN 10 Mbps 100 MbpsO TERA Half Duplex Full DuplexO Mail Server SMTP Mail Server Port 25 User Name If Required Password If Required Return Email Email 1 Email 2 Email 3 Email 4 Email 5 EAT 1 08 OFull Message OShort Message Figure 2 4b Network Tab Use DHCP WebRelay 10 Plus only This option allows DHCP to be enabled or disabled If this option is set to Yes WebRelay 10 Plus will wait for an IP address from a DHCP server each time it is powered The default setting is No this is recommended for most installations If DHCP is set to Yes the Network page must be submitted and WebRelay 10 Plus must be rebooted before an IP address will be assigned Once WebRelay 10 Plus is assigned an IP address by the DHCP the new IP address can be found through the clients list kept by the DHCP server For most instances this is found on the local page 24 Xytronix Research 8 Design Inc WebRelay 10 Users Manual Installation and Setup gateway or router Brief Notes About DHCP All devices on an IP network require an IP address This is a unique address that identifies each device on th
79. lByWeb products Users access WebRelay 10 through the web server rather than communicating directly with it This method is sometimes referred to as web services and allows programmers to create powerful custom web pages to multiple devices using the web programming languages of their choice Remote Services initiates the connection to the external web server rather than the web server initiating communications to WebRelay 10 This has two main benefits First the web server does not need to know the IP address of WebRelay 10 This means that WebRelay 10 can get its IP address dynamically from a DHCP server simplifying the installation Second since the connection from WebRelay 10 is outgoing rather than incoming the local router on the network where WebRelay 10 resides doesn t need to be configured to forward sockets This also simplifies the installation Since the router configuration is not modified the risk of compromising security on the local network is eliminated For more information about the Remote Services see Appendix E External Server and Remote Services SNMP Simple Network Management Protocol SNMP is used to manage and administer network devices WebRelay 10 supports SNMP V1 0 and can be configured here Using SNMP the input and relay states of WebRelay 10 can be read as well as some basic information about the device See Appendix F SNMP Requests for information about how to request informatio
80. lay OFF 1 Relay ON coil energized 1 Turn relay ON 2 Pulse relay 5 Toggle the state of the relay lt units gt F Fahrenheit n a X C Celsius lt sensorXtemp gt x x Indicates that no digital n a X temperature sensor is attached 77 3 Current temperature H24 9 Current humidity reading lt extvarX gt Value of each External Variable n a lt serialNumber gt 00 00 00 00 00 00 serial n a number of WebRelay 10 lt time gt 1253030401 Time displayed in n a epoch time number of seconds since January 1 1970 X is replaced by the relay number or input number Control relayXState commands can be sent to WebRelay 10 to control the relays X is replaced by 1 for Relay 1 2 for Relay 2 and so forth The following are a few examples Command Description state xml relaylState 0 Turn Relay 1 OFF state xml relaylState 1 Turn Relay 1 ON state xml relay2State 0 Turn Relay 2 OFF state xml relay2State 1 Turn Relay 2 ON When the pulse command is sent the relay will energize for the Pulse Duration specified in the Relays setup page It is possible however to send a pulse time command that is different than the configured Pulse Duration This is done by sending a pulseTime variable The pulseTime variable does not change the Pulse Duration in the setup page and it is not stored or recorded The pulseTime variable only changes the duration for the
81. ld may be up to 24 characters long The default text is Input On Status Text The text in this field specifies the text that will be displayed in the Control Page and in email messages when the input is ON input tied to ground Up to 14 characters may be entered in this field The default text is ON Off Status Text The text in this field specifies the text that will be displayed in the control page and in email messages when the input is OFF input is open Up to 145 characters may be entered in this field Xytronix Research 8 Design Inc page 39 Installation and Setup WebRelay 10 Users Manual The default text is OFF Counter Options The inputs can be used as counters This field specifies counter operation Note The input voltage must remain ON or OFF for the minimum hold time before the counter will be incremented see Appendix H Specifications counter off The counter is deactivated and will not be incremented increment when input on Each time the input is tied to ground the counter will increment increment when input off Each time the input is open the counter will increment increment when input changes Each time the input is open or tied to ground the counter will increment Reset Count The counter will reset to O as soon as the count reaches the value specified in this field The counter is reset immediately when it reaches this value so this value will never be returned when the counter i
82. ll Wireless i Folder Options WLAN Utility Network 4 Network Setup Phone and Java Mouse P Wizard Modem Options Portable Media Power Options Printers and Regional and Scannersand Scheduled Tasks Security Center Devices Faxes Language O SigmaTel Audio Sounds and Speech Symantec Taskbar and User Accounts Audio Devices LiveUpdate Start Menu Windows Wireless Link Wireless Network Firewall Setup Wizard Figure 2 3b Control Panel page 20 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 Double click on the icon labeled Network Connections DER Network File Edit View Favorites Tools Advanced Help ay Connections The Q Back O O po Search i gt Folders EE Network l ceed i ae mn xa window will open LAN or High Speed Internet Network Tasks Figure 2 3c El Create a new connection Set up a home or small office network Change Windows Firewall settings See Also Other Places Details Figure 2 3c Network Connection 3 Right click on the icon labeled Local Area Ecco Bie mC One Cron Prope 2 X Connection In the menu that follows select the General Authentication Advanced option at the bottom of the menu labeled Properties Ginestiuaig The Local Area Connection Properties window will E9 Broadcom 440x 10 100 Integrated C ST appear Figure 2 3c si Siti This connection uses the foll
83. lt sensor5 lt sensor6 lt sensor7 lt sensor8 lt extvar0 gt 0 lt extvarl1 gt 0 lt extvar2 gt 0 lt extvar3 gt 0 lt extvar4 gt 0 temp gt x temp gt x temp gt x temp gt x temp gt x temp gt x x lt sensor6temp gt temp gt x temp gt x 00 lt extvar0 gt 00 lt extvarl gt 00 lt extvar2 gt 00 lt extvar3 gt 00 lt extvar4 gt lt serialNumber gt WebRelay 10 Serial Number lt serialNumber gt x lt sensorltemp gt x lt sensor2temp gt x lt sensor3temp gt x lt sensor4temp gt x lt sensor5temp gt x lt sensor7temp gt x lt sensor8temp gt lt time gt 1290165251 lt time gt lt datavalues gt The numbers enclosed by the tags lt tag gt indicate the current state or value monitored by WebRelay 10M Values for each tag are described in the table below XML computer applications will open a TCP IP socket with the WebRelay 10 and send a GI command followed by the state xml command string E Xytronix Research amp Design Inc page 59 Operation WebRelay 10 Users Manual XML Tags Monitor Values Control Values WebRelay 10 Plus Only lt inputXstate gt 0 Input OFF n a X 1 Input ON lt hightimeX gt The amount of time in seconds n a X that the input was last on lt countX gt Current number of times the n a X input has been counted counting must be enabled lt relayXstate gt 0 Relay OFF coil off 0 Turn re
84. mat Clock time is formatted as hh mm ss 24 hour clock Example If date 01 01 2014 Then If time gt 12 30 00 Then Let relay2 1 Let relay3 0 End If End If Note Current date and time can only be set in the Date Time tab Event Variables WebRelay 10 Plus only Up to five actions can be configured to occur at specified days and times This is done by setting the day and time of the event and then comparing it to the current date and time The event date variables are designated ed1 to ed5 They are set using the LET command and setting the desired event date variable equal to the date the event should occur in the format mm dd yyyy The event date variables store the number of days that have passed since January 1 1970 The event time variables are designated et1 to et5 They are likewise set using the LET command and setting the corresponding event time variable equal to the event time in the format hh mm ss in 24 hour time The event time variables store the number of seconds from the beginning of the day If the event time variable is incremented more than the number of seconds in a day 86400 seconds the variable is reset to O and the event date variable is incremented by one The following example demonstrates defining the event variables and comparing it to the current date and time Assume current time is April 10 2010 at 1 30 AM and the event should occur in one hour and every hour thereafter
85. mp alarm message sent to recipients in the Sensors tab END The END statement ends the main body of code CALL The CALL statement is found within the main body of code but requires the interpreter to skip to a subroutine found at the end of the program After the subroutine is finished the interpreter returns to the line immediately following the CALL statement The format is CALL name of subroutine SUB END SUB The SUB statement defines the beginning and name of a subroutine The END SUB statement defines the end of the respective subroutine Subroutine names can be up to 20 characters long and are case sensitive The SUB and END SUB statements always must follow the END statement The format is END kkk Subroutines Go Here SUB name of subroutine contents of subroutine END SUB SUB name of subroutine contents of subroutine END SUB REM or The REM or apostrophe statement designates remarks made by the programmer The interpreter will disregard any characters on the line following these statements PRINT The PRINT statement relays a variable or message to the display The PRINT statement is only available for the PC version of the BASIC interpreter The device will not recognize the command since it does not have an operator display The format is page 100 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix G BASIC Scripts PRINT variable relay variable v
86. mperature or humidity Web10 67 Sensor three alarm x x Decimal temperature or humidity Web10 68 Sensor four alarm x x Decimal temperature or humidity Web10 69 Sensor five alarm x x Decimal temperature or humidity Web10 70 Sensor six alarm x x Decimal temperature or humidity Web10 71 Sensor seven alarm x x Decimal temperature or humidity Web10 72 Sensor eight alarm x x Decimal temperature or humidity Password WebRelay 10 uses the Control Password for both the read and write community strings If the Control Password is disabled any object can be read without the need for a correct community string By default the Control Password is webrelay Xytronix Research amp Design Inc page 97 Appendix G BASIC Scripts WebRelay 10 Users Manual Appendix G BASIC Scripts BASIC Beginners All purpose Symbolic Instruction Code is a computer programming language that has been in use for many years The WebRelay 10 has an integrated BASIC interpreter for simple BASIC scripts This provides a great deal of flexibility by allowing users to customize basic functions of the unit The interpreter only supports a small subset of the BASIC commands that are available for computers Some non standard commands have been added and some commands may function differently on the WebRelay 10 BASIC interpreter than on other platforms The following is a short tutorial on the supported BASIC functions Contact customer sup
87. n the input is tied to ground the relay will remain in its current state toggle relay when input 1 changes Each time the input is tied to ground or open the relay will change states pulse relay when input 1 on When the input is tied to ground the relay will pulse for the Pulse Duration specified The input may stay tied to ground and the pulse time will not be affected If the input is tied to ground opened and then tied to ground again before the end of the pulse time the Pulse Duration timer will be restarted it will re start each time the input is tied to ground and the relay will continue to remain ON until the timer expires pulse relay when input 1 off When the input is open the relay will pulse for the Pulse Duration specified The input can remain open and the pulse time will not be affected If the input is tied to ground and re opened before the end of the pulse time the Pulse Duration timer will be re started it will re start each time the input is open and the relay will continue to remain ON until the timer expires pulse relay when input 1 changes Each time the input is tied to ground or opened the relay will pulse for the Pulse Duration specified If the state of the input changes before the end of the pulse the timer will be re started it will re start each time the input changes and the relay will continue to remain ON until the timer expires Control Input WebRelay 10 Plus only Selects which input
88. n from WebRelay 10 using an SNMP manager as well as where to find MIB files for WebRelay 10 Note The read and write community strings used for SNMP are actually the Control Password found on the Password setup tab see Section 2 4 4 If the Control Password is disabled then WebRelay 10 does not check for the community string when issued a Get or GetNext request from the SNMP manager page 30 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 4 Password Tab WebRelay 10 requires a password to log into the setup pages The password can be changed on this page Additionally the installer can enable the requirement for a Control Page password WebRelay 10 http 192 168 1 2 setup html Qr ControlByWeb Setup sensors Levent script contrat age setup conta rege Setup Password Re enter Setup Password Enable Control Password Control Password Re enter Control Password YesO No Figure 2 4d Password Tab Setup Password The Setup Password which is required to access the setup pages can be modified by entering a new password here Passwords that are 8 characters or longer up to 13 characters can be entered in this field with both alphabetic and numeric characters are recommended For security purposes the password will not be displayed as it is entered Note that the username required for accessing the setup pages is admin all lowe
89. n order to prevent several different devices from simultaneously requesting a time and overwhelming the NTP server The default setting is Yes Note Enabling the daylight savings time adjustment scheduled events will be adjusted for the new time Logged data includes a time stamp based upon the current time in the device so it is possible to duplicate log times in the spring and miss log times in the fall To avoid confusion many servers and data loggers are set to remain on GMT time and do not shift for daylight savings Daylight Savings Start This is the date that daylight savings will start Note that on this date between the hours of 12 00 AM 5 00 PM the current time will be shifted forward by one hour i e the time will jump from 12 02 AM 00 02 to 1 02 AM 01 02 By default this is set to the 2nd Sunday in March which is the date used in the United States Daylight Savings End This is the date that daylight savings will end On this date between the hours of 12 00 AM 5 00 PM the current time will be shifted backward by one hour i e the time will jump from 12 02 AM 00 02 to 11 02 PM 23 02 the day before By default this is set to the 1st Sunday in November which is the date used in the U S page 36 Xytronix Research 8 Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 6 Logging Tab WebRelay 10 Plus only WebRelay 10 Plus can be configured to record data such as changes in r
90. n the Control Page Entering a value on the Control Page in this field and clicking Set will set the selected extvar to the new value Values entered can be either positive or negative numbers Xytronix Research amp Design Inc page 53 Installation and Setup WebRelay 10 Users Manual Description Text entered here will be displayed in the left column of the control page Up to 24 characters may be entered here The default text is extVar Button 1 Label This text field is used to describe the function of button 1 of the selected extVar The text also appears to the right of the corresponding extVar status Up to 14 characters may be entered here By default this text is ON for a value of 1 Button 2 Label This text field is used to describe the function of button 2 of the selected extVar The text also appears to the right of the corresponding extVar status Up to 14 characters may be entered here By default this text is OFF with a value of 0 Status 1 Text The text in this field specifies the text that will be displayed when the extVar is value 1 with a gray background The text also appears in the status column on the Control Page Up to 14 characters may be entered here By default the text is ON Status 2 Text The text in this field specifies the text that will be displayed when the extVar is value 0 with a gray background The text also appears in the status column on the Control Page Note that if the extVar i
91. n the Main Header Text field on the Control Page Setup tab in the setup pages Input 1 and 2 WebRelay 10 Plus only These rows display the current state of the two inputs These rows can be displayed as shown or not displayed by checking or unchecking the appropriate boxes in the Control Page Setup tab in the setup pages The text in the left column by default reads Input 1 and Input 2 is specified in the Description field in the Inputs tab in the setup pages The state of the input is shown to the right of the input description text By default the status text will read ON or OFF however the status text can be changed in the Inputs tab To the right of the input status a button is provided to reset the counter The button will be shown when selected on the Control Page Setup tab Relays 1 10 These rows display the current state of the ten relays and allow the user to change the relay state Each of these rows can be displayed as shown or not displayed by checking or unchecking the appropriate boxes on the Control Page Setup tab in the setup pages The text in the left column by default reads Relay 1 Relay 2 etc is specified in the Description field in the Relays tab in the setup pages The state of the relay is shown to the right of the relay description text By default the status text will read ON or OFF however the status text can be changed in the Relays tab To the right of the relay status buttons are provided to control th
92. nce from WebRelay 10 to sensors Combined cable length of 600 ft using Cat 5e Additional Sensors WebRelay 10 Plus only Temperature Humidity Sensor X DTHS WM Humidity Sensor 0 100 RH Accuracy 1 8 Network 10 Base T or 100 Base T Ethernet IPv4 Setup Static IP address assignment or DHCP HTTP port selectable Network Connector 8 pin RJ 45 socket 13 LED Indicators Power On Relay Coils Energized 1 10 Network Linked Network Activity Real Time Clock WebRelay 10 Plus only Manual or NTP Network Time Protocol setup NTP Sync Period Once Daily Weekly On Power up Automatic Daylight Savings Adjustment Battery capacitor Power Backup Capacitor Power Backup WebRelay 10 Plus only Backup Functions Retain Real Time Clock External Variables Relay State Backup Duration 3 days minimum Xytronix Research amp Design Inc page 105 Appendi x H Specifications WebRelay 10 Users Manual Nonvolatile Memory Memory Type Flash Function All user settings are stored in nonvolatile memory Settings will not be lost when power is disconnected Physical Operating Temperature 40 C to 65 5 C 40 F to 150 F Size 9 125in 232mm wide 2 423in 62mm tall 4 25in 126mm deep Weight 22 oz 626 grams Monitor Control Web Browser XML Modbus TCP SNMP Logging WebRelay 10 Plus only Storage Nonvolatile Flash Buffer Archit
93. nection when triggered by an event such as a relay state changing This is done by setting the Remote Service SNMP checkbox in the relay and input setup tabs Connection String With Remote Services enabled a connection attempt will be made periodically according to the Connection Interval setting in the Advanced Network setup tab The Connection String is a user defined character string configured in the Advanced Network tab The connection string is also sent at the same interval once the connection is open The external server is responsible for closing the connection when it is done Remote Commands Once the connection is open the remote server can issue HTTP GET requests to the device for XML files Request about html GET about html HTTP 1 1 r n r n Turn Relay 1 ON GET state xml relaylState 1 HTTP 1 1 r n r n Events When an event occurs and a connection is open the state xml file is be sent If a connection is not open and Remote Services is enabled a connection will be established by sending the connection string Once the connection is established state xml will be sent page 94 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix F SNMP Requests Objects and Community Strings Appendix F SNMP Requests Objects and Community Strings Relay states input states some simple network parameters and temperature humidity measured by WebRelay 10 can be retrieved using Sim
94. ned by setting it to 100 Mbps There are advantages however to operate this device at 10 Mbps At 10 Mbps less power is required the unit runs cooler and the lifetime of the product will be extended Any changes to the Ethernet settings will require a removing and re applying power to WebRelay 10 page 6 Xytronix Research amp Design Inc WebRelay 10 Users Manual Section 1 Introduction Introduction WebRelay 10 is a robust 10 relay module with a built in web server lt can be controlled and or monitored over any IP network including private networks IP based industrial control networks and the Internet Users can operate WebRelay 10 using a web browser or a custom application Computers PLCs or automation controllers may control and monitor WebRelay 10 without user intervention This works by sending text commands over the network and reading XML status pages from WebRelay 10 or by using Modbus TCP protocol e Zash Neo s109 JW 6 SIOASII AVES LO gsa0ngose Figure 1 1 Product Image Xytronix Research amp Design Inc page 7 Introduction WebRelay 10 Users Manual 1 1 Features WebRelay 10 includes the following features Ten independent 30 Amp Relays Form C SPDT Built in Web server for browser based setup and control No special software or device drivers required Customizable email alerts XML status and Control Page make communicati
95. ning Relay 1 on send the following request using the default IP address http 192 168 1 2 eventSetup srv e5 1290168000 1 3 0 0 1 4 0 Event5Desc 127 1 The basic format of the request is e event epoch time period period units count scheduleH action pulse duration 0 description days action Parameter Description e5 Parameter Name Each event has an identifier 0 99 In this case the parameter name is e5 Event 100 would be e99 1290168000 Epoch Time The number of seconds up to the desired start date since January 1 1970 Period The period value Period Units The units of the period O0 Seconds 1 Minutes 2 Hours 3 Days 4 Weeks Count Number of times the event will occur 0 continuous Schedule The schedule where the event will occur 0 4 0 schedule 0 1 schedule 1 and so forth Action 0 No Action 1 Turn relay on 2 Turn relay off 3 Pulse relay 4 Toggle relay 5 change schedules 7 Set extVar0 8 Clear extVar0 Pulse Duration Pulse duration when using the pulse relay action Next Occurrence This is a report value only indicating the next time this event will occur in Epoch Time When setting an event leave this at 0 Event5Desc Description Text description of the event up to 20 characters can be entered 127 Days This number represents which days the event will occur This value is the base ten version of a binary number where
96. nternet IP Addresses Every device on the Internet is identified by a unique address called an IP Internet Protocol address IP addresses are somewhat similar to mailing addresses in that they identify the precise logical location of the device on the Internet The IP address identifies the global region down to the network and then the specific device on that network IP addresses are globally maintained and assigned by an entity called the Internet Assigned Numbers Authority IANA IP addresses consist of four numbers that range from 0 to 255 and are separated by a decimal For example 192 168 200 167 is an IP address Every device that is directly connected to the Internet uses a public IP address WebRelay 10 can be assigned a public IP address for direct connection to the Internet Typically a public IP address to would only be assigned to WebRelay 10 when it is the only device on the local network The IP address would be obtained from an Internet Service Provider ISP Due to the limited number of public IP addresses private networks can be set up with private IP addresses These addresses are used withing a local network and have no global designation they are not routed on the Internet The following address blocks are designated for private networks where x represents decimal numbers from 0 to 255 192 168 x x 10 x x x and 172 16 x x A Simple Local Area Network A small Local Area Network LAN
97. nutes Hours Days or Weeks by selecting the appropriate option in the drop down menu Default settings is 0 Days Note that selecting 0 will disable the event Days When a Period of one day is selected the day or days on which that event will occur can be specified by marking the appropriate check boxes Count The number of times the event will occur is specified The default text is 0 Note that entering O in this field will cause the event to occur continuously Action This drop down menu specifies which action will take place when the event occurs The following options may be selected no action When this option is selected nothing will happen when event occurs turn relay s on This option causes the relay s specified in the Affected Relay s field to turn ON coil energized when event occurs turn relay s off This option causes the relay s specified in the Affected Relay s field to turn OFF coil de energized when event occurs pulse relay s This option causes the relay s specified in the Affected Relay s field to turn ON coil energized when the event occurs and then turn OFF coil de energized after the Pulse Duration time specified below expires toggle relay s This option causes the relay s specified in the Affected Relay s field to change states change schedules This option causes the schedule s specified in the Affected field to be enabled or disabled See section Schedules at the end of
98. occurs because there is more than a single value to the left of the comparison operator a 2 is to the left of IF a 2 3 THEN this will return an error To fix the above line replace a 2 One of the following options may be used IF a 1 THEN OP LET b at 2 page 98 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix G BASIC Scripts IF b 3 THEN Supported Statements The following are the statements supported by the ControlByWeb BASIC interpreter LET The LET statement assigns a variable a value The format is LET variable expression IF THEN ELSE END IF The IF THEN statement tests the truth of a condition The ELSE statement defines a second function if the condition is found false In other words if the condition is true then a function is performed If it is not true a second function may be performed The second function may or may not be necessary depending on the application The IF THEN ELSE statement must always be followed with an END IF statement The format is IF variable lt gt lt gt lt gt expression THEN Function 1 ELSE Function 2 END IF Note In most BASIC interpreters Function 1 see above may be placed after the THEN statement This interpreter requires Function 1 to be put on the following line FOR TO NEXT The FOR TO statement loops a section of code a predefined number of times
99. ode ina human readable form The code is comprised of the original function code plus 0x80 For example an error during the read coils function 0x01 would return 0x81 Each error has a qualifying exception number The following are the possible exception codes and their meanings 0x01 Function code not supported also when Modbus is disabled in the setup pages 0x02 Incorrect starting address quantity of relays combination The structure of these commands is described in the following sections PLC Device Addressing There are generally two schemes for accessing Modbus devices The first is by specifying the Modbus function code memory type and address The second sometimes called PLC addressing requires only the address Modbus protocol uses four different address ranges for discrete inputs coils input registers and holding page 66 Xytronix Research amp Design Inc WebRelay 10 Users Manual Operation registers The function code determines the address range of the message The following are common function codes and their respective address ranges Code Name Modbus Data Type PLC Address PLC Address Function Mode 485 Mode 584 984 Coils Read Write 01 05 15 Discrete 1 1000 1 10000 Discrete Inputs Read only 02 Discrete 1001 2000 10001 20000 Registers Read only 04 8 64 bits 3001 4000 30001 40000 Holding Registers 03 06 16 8 64 bits 4001 5000 40001 50000 Read Write
100. ommended that the port be left unchanged unless the user has an understanding of TCP IP and ports For more information on TCP ports and IP addressing see Appendix C Accessing WebRelay 10 Remotely Over the Internet Speed This option sets the data rate clock rate of the Ethernet port Either 70 Mbps or 100 Mbps can be Xytronix Research amp Design Inc page 25 Installation and Setup WebRelay 10 Users Manual selected The 100 Mbps option offers faster communications but the amount of data to and from WebRelay 10 is so small that users will not likely notice much if any difference When the WebRelay 10 is set to 10 Mbps it draws less power and runs a little cooler which may translate into a longer product life The default setting for this field is 10 Mbps IT IS RECOMMENDED THAT THIS SETTING BE LEFT AT 10Mbps UNLESS THE USER HAS A SPECIFIC REASON TO USE 100Mbps Mode This option allows the Ethernet port to be set to Half Duplex or Full Duplex Legacy Ethernet operates in Half Duplex mode which means that devices can either send data or receive data but not both at the same time Full Duplex means that devices can send and receive data at the same time The default setting for this field is Half Duplex Mail Server SMTP The name of the SMTP Simple Mail Transfer Protocol mail server for example mail example com or the IP address of the mail server for example 192 10 10 10 should be entered in this field
101. on the WAN side of the router has an IP address that has been assigned by the Internet Service Provider such as 266 70 164 97 This is not a valid IP address because each number cannot be larger than 255 It is used in this example for illustration purposes only WebRelay 10 WebRelay Internet Ethernet Switch Router Computer Figure Appendix C 2 LAN Connected to the Internet In the example when a user on the computer needs to access a server on the Internet the computer sends the request to the router at 192 168 1 1 The router sends the request to the ISP server on the Internet The ISP server does not send the response directly to the computer on the LAN but to the router at the IP address of 266 70 164 97 The router then forwards the response to the computer This Xytronix Research amp Design Inc page 87 Appendix C Accessing WebRelay 10TM Over the Internet WebRelay 10 Users Manual way all devices on the LAN share a single public IP address This is called Network Address Translation NAT Port Forwarding The router can be configured to allow outside access to WebRelay 10 and WebRelay All requests from the Internet to any device on the local network must use the public IP address 266 70 164 97 With only a single IP address TCP ports are used to identify the intended device for the incoming message Using the mailing address analogy the port is similar to a post office box The IP address
102. ons with custom computer applications simple Can operate as a Modbus TCP slave On Off and Pulse modes Advanced functionality through BASIC scripts Wide power supply range 10 36 VDC DIN Rail Mountable LED relay state indicators inch tab connectors UL CUL listed relays E197852 WebRelay 10 Plus Model X WR 10R12 IP also includes the following features Event scheduler with yearly calendar Schedule up to 100 events Up to eight temperature and or humidity sensors can be added for environmental monitoring Dry contact sensors or switches can be connected for local control of relays or for monitoring external devices Logging log relay changes events Modbus requests high low temperatures input changes network traffic and more Real time clock can automatically adjust for daylight savings time Sync with NTP server System log provides detailed diagnostic information Configure manually or with DHCP Note WebRelay 10 sends out email messages only Most wireless carriers provide free services to convert email messages to text messages 1 2 Applications WebRelay 10 has many applications It works very well as a stand alone device that can be controlled using a web browser or as a convenient way to add I O to a computer It can be used in industrial applications to control motors lights coils pumps valves etc Using the additional features found on WebRelay 10 Plus
103. ould be used to energized all of the relays in the range or 0x0000 to turn them OFF In the above example the output value OxFF would turn relays 7 9 ON Xytronix Research amp Design Inc page 77 Operation WebRelay 10 Users Manual Response WebRelay 10 Response Frame Example Write Coils 7 9 ON Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0004 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Write Multiple Coils Ox0F Data 4 bytes Start address 0x0000 0x0009 0x0006 Relay count 0x0001 Ox000A 0x0003 RX String 00 01 00 00 00 06 FF OF 00 06 00 03 Errors Multiple Coil Write Error Function Code 1 Byte Ox8F Exception codes 1 Byte 0x01 Function not supported 0x02 Incorrect combination of start address and relay quantity 0x03 Byte count out of range Error Response Frame Example Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization between messages of 0x0001 server and client Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0003 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function
104. ould include any information required by the server at connection For example it may include an ID number customer number password etc The format is entirely dependent upon the server requirements This field can be up to 80 characters long Default text is provided only as an example placeholder The default text is lt serialAddress gt ControlByWeb X 10 Connection Interval This field specifies the periodic interval in which WebRelay 10 attempts to connect to the remote server or if WebRelay 10 is already connected it is the interval in which WebRelay 10 sends the connection string This field can be set within the range of 1 to 34452 minutes The default setting for this field is 1 minute SNMP Enabled When this option is set to Yes WebRelay 10 will support SNMP The default setting for this option is No See 2 4 3 2 SNMP for more information SNMP Manager IP When SNMP is used this field is used to specify the IP address of the SNMP manager The default setting for this field is 192 168 1 25 SNMP Port When SNMP is used this field is used to specify the SNMP port that WebRelay 10 listens on The default setting for this field is 161 SNMP Trap Port When SNMP is used this field is used to specify the SNMP Trap port of the SNMP manager The default setting for this field is 162 IP Filter Range 1 and IP Filter Range 2 For additional security WebRelay 10 has a simple built in firewall If desired WebRela
105. owing items 5 005 Packet Scheduler 3F AEGIS Protocol IEEE 802 1x v2 3 1 7 Uy Intemet Protocol TCP IP Ail gt Il Description Transmission Control Protocol Intemet Protocol The default wide area network protocol that provides communication across diverse interconnected networks Show icon in notification area when connected 4 Notify me when this connection has limited or no connectivity Figure 2 3d Local Area Connection Xytronix Research amp Design Inc page 21 Installation and Setup WebRelay 10 Users Manual 4 Inthe Local Area Connection Properties window in the Connection Uses box scroll down and internet ProtocolL ICE IP Properties x highlight Internet Protocol TCP IP Click the General button labeled Properties The Internet Protocol You can get IP settings assigned automatically if your network supports Wa i i this capability Otherwise you need to ask your network administrator for TCP IP Properties menu appears Figure 2 3e e ce Hiern 5 Select the radio button labeled Use the following IP address and type in the IP address Obtain an IP address automatically Use the following IP address 192 168 1 50 IP address 192 168 1 50 6 Type in the subnet mask Subnet mask 255 255 255 0 255 255 255 0 Default gateway No need to change the default gateway field Click Obtain DNS server address automa
106. ple Network Management Protocol SNMP The states of the relays can be changed through SNMP requests For most cases using SNMP is as simple as locating the appropriate Management Information Bases MIB files and loading them into the SNMP manager software WebRelay 10 can make use of the following MIB files RFC1213 MIB and XYTRONIX_V1_0 mib Note As additional ControlByWeb products are introduced the Xytronix MIB file will remain reverse compatible older MIB files can be overwritten SNMP is configured under the Advanced Network setup tab See section 2 3 3 Advanced Network Tab for more information WebRelay 10 supports the following Packet Data Units PDU GetRequest GetNextRequest SetRequest Trap Standard Objects WebRelay 10 supports several standard RFC1213 objects that usually come with SNMP management software If not an Internet search for RFC1213 MIB will turn up multiple links RFC1213 Object Response system sysDescr Device description X 10 Event Scheduler 10 Relay Controller system sysObjectID Object identifier OID 1 3 6 1 4 1 30586 13 system sysUpTime Time in hundredths of seconds since WebRelay 10 was last powered system sysName Device name WebRelay 10 Xytronix Objects WebRelay 10 also supports some special objects that can be found in the XYTRONIX mib This MIB can be downloaded from our website Relays Read Write A Get request will
107. plication baii 8 AD lo llocs 18 19 B AA cise ate E E ome ees 61 BASIC Scripts ss sonion eiii 98 C Cd ekanna e eE N A Shee 17 C lor coded oiae AEA N 48 AA a A E E E di A PUE id 15 Power SUupplyY ooooonooccnonccnonccnonocionnconnccnnnccnnnnnnnos 13 DS To 1519 en PO a 16 Control Page Setup Tab ooooooonnnnoccccnonoooconcnononcnnnos 55 Control PasswoTd ooooooooooonnccnoccninonocnnnnanananananes 31 32 Counter OPONSE eaS 40 CrOS SOVE esena a A a a a 13 CU a a abia 104 Switch Input seerne o enaena 15 D Date Time Taba da 33 Daylight SavidgS oooconnnnononcononncnonncnanccnnnoos 8 36 105 Deadbandiiciain a da adi 46 Detalla OY PO PS PE di IP address ccceeeeeee 18 23 57 64 82 84 90 PaSSWOMG cccccccsessssssssssscssssecceeeseeseseeeeeeeens 23 61 Us MAME iio 23 31 PHCP aran odas 24 25 DIN Raba ce ee tao ta OE Pe 12 Discrete I PUES co it di 14 IN ccccccccecceeesssssssseceeeeeeeeeececeeeeeeeeeeeenes 25 DSIBB iii cis 105 E Email NotificatiOW oooonnnnnnnnnnononccnnnnnnnnncnnnannnnnonoss 81 Email Optical 40 43 46 Ethernet 6 11 12 13 14 18 25 26 87 88 93 105 Dd as 25 Events Scheduler Taban Snr eard aeh i i 48 External Sevei nitanna AE E S 93 External Variables oooooocnnnonocccccnononancnnnononnnnnnnonons 58 F Factory Default ooooonnocnnoccnocccoooncnonnconnnconcoconcnnonnnnnos 83 Farin Ware ii Ns alo ents 84 Full Duplex acid in 26 G GaleWay ica ss 18 25
108. port if further assistance is required Structure ABASIC script is written as a txt file which is then uploaded to the device using the Script setup tab The maximum script size is 2K bytes Each line within the script contains a single statement Line numbers are not used Statements are not case sensitive however variables are IF THEN FOR loops and DO loops can only be nested up to 5 times per command For those not familiar with nesting the following is an example of nested FOR loops FOR a 0 to 100 FOR b 0 to 100 NEXT b NEXT a Every program must end with an END statement Subroutines would then follow after the END statement if required The last line of the script should be left blank Line Format Every line follows the same format The basic format is statement variable lt gt lt gt lt gt expression THEN The fields in parentheses are optional depending on the statement Spaces must be used between all statements numbers variables operators expressions etc Multiple spaces are valid Comments may be inserted but must begin with an apostrophe All text on a line after the apostrophe is ignored Examples LET a 1 this will return an error because of insufficient spacing LET a 1 this is valid LET a 1 this is valid Only a single variable or literal is allowed on the left side of any operator The following example is incorrect and will return an error The error
109. r case The default Setup Password is webrelay also all lower case Re enter Setup Password When the Setup Password is changed it must be entered twice One time in the previous field and a second time in this field If the password is not entered identically in both fields the password will not be changed Enable Control Password The Control Page can be viewed without entering a password For security purposes a password can be required for access to the Control Page When this field is set to Yes a password will be required to view the Control Page The default setting for this field is No Control Password When the Enable Control Password option above is set to Yes this field is used to specify the password which will be required to access the Control Page Passwords that are 8 characters or longer with both alphabetic and numeric characters are recommended For security purposes the password will not be displayed as it is entered Note that WebRelay 10 requires a password but does not require a user name to access the Control Page However some browsers require that a user name be entered In this instance enter none as the user name The default Control Password is webrelay Xytronix Research amp Design Inc page 31 Installation and Setup WebRelay 10 Users Manual Re enter Control Password When the Control Password is changed it must be entered twice One time in the previous field and a second time in t
110. r damage resulting from improper use or misuse unauthorized repair tampering modification improper connection or operation outside the electrical environmental specifications for the product Further the warranty does not cover Acts of God such as fire flood hurricanes and tornadoes This warranty does not cover damage to property equipment direct indirect consequential or incidental damage including damage for loss of business profit business interruption loss of data and the like arising out of the use or misuse of this product UNDER NO CIRCUMSTANCES WILL THE LIABILITY OF XYTRONIX RESEARCH 8 DESIGN INC TO THE PURCHASER OR ANY OTHER PARTY EXCEED THE ORIGINAL PURCHASE PRICE OF THE PRODUCT REGARDLESS OF THE FORM OF THE CLAIM No other warranty is expressed or implied Xytronix Research 8 Design Inc specifically disclaims the implied warranties or merchantability and fitness for a particular purpose Some jurisdictions may not allow the exclusion of limitation of liability for consequential or incidental damage page 4 Xytronix Research 8 Design Inc WebRelay 10 Users Manual FCC Statement FCC Statement This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions This device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation Warning This equipment has been te
111. re read from 16 bit register pairs Consequently senors addresses and registers must be even numbers Start Address 2 bytes 0x0110 0x0112 0x011E Sensors 1 2 8 respectively Sensor Register Count 2 bytes 0x02 0x04 0x10 Request Modbus TCP Request Frame Example Read Sensor 1 and 2 Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0005 Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Read Sensors 0x03 Data 3 bytes Start Address 0x0110 0x0112 0x0110 0x011E 0x0004 Sensor Count 0x02 0x04 0x10 TX String 00 01 00 00 00 05 FF 03 01 10 00 04 Response Each value is returned as two registers in IEEE 754 floating point formats The four data bytes are treated as two individual big endian 16 bit words with the least significant word being sent first In other words the 32 bit floating point number represented as 1234 ABCD is sent as ABCD 1234 For example if we were to read two registers starting at address 0x110 and Sensor 1 measured the temperature to be 81 25 degrees then we would get the following value 800042A2 The least significant word would be 8000 hex and the most significant word would be 42A2 Using a conversion utility we could then convert
112. re to be effective page 40 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 8 Relays Tab This page provides configuration options for the ten relays 000 _ WebRelay 10 PA i http 192 168 1 2 setup html aQ ControlByWeb W Setup sensors evens sip conta page sep conor paa 7 Relay COEL Relay 1 On Button Label ON Off Button Label OFF Pulse Button Label PULSE On Status Text ON Off Status Text OFF Pulse Duration 1 5 Seconds Relay State At Powerup off unless overridden by event E Relay Option Control Input Email Option O o Use Email Address O m O AE ASA LN Send State Msg Trap on Relay Change Figure 2 4i Relays Tab Relay This drop down menu is used to select the relay for which the options below will apply Relay 1 to Relay 10 Selects the relay Relay Description This text field is used to describe the function of the selected relay The text appears to the left of the corresponding relay status on the Control Page and in the email message when email alerts are enabled Up to 14 characters may be entered in this field The default textisRelay On Button Label The text entered in this field appears in the On button for the corresponding relay on the Control Xytronix Research amp Design Inc page 41 Installation and Setup WebRelay 10 Users Manual Page Up to 10 ch
113. return the current state A Set request of 0 or 1 will turn the relay ON or OFF A Set request of 2 will pulse the relay for the time configured in the setup page Xytronix Research amp Design Inc page 95 Appendix F SNMP Requests Objects and Community Strings WebRelay 10 Users Manual Object Response Set Value web10 webrelay ten relayOne 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten _sensorTwo 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relayThree 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relayFour 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relayFive 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relaySix 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relaySeven 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relayEight 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relayNine 0 Value 0 or 1 0 OFF 1 ON 2 Pulse web10 webrelay ten relayTen 0 Value 0 or 1 0 OFF 1 ON 2 Pulse WebRelay 10 Plus Inputs Object Response web10 webrelay ten inputOne 0 Value 0 or 1 0 OFF 1 ON web10 webrelay ten inputTwo 0 Value 0 or 1 WebRelay 10 Plus Sensors Object Response web10 webrelay ten sensorOne 0 Value x x Dec
114. rgized the common and normally open contacts are closed When the relay is not energized the common and normally closed contacts are closed Module Power Indicator The green power LED indicator is located on the main relay board in between relays 1 and 6 Ethernet Indicators The LINK LED is illuminated green when the module is properly connected to an Ethernet network and is ready to communicate Network communications will only occur if this LED is illuminated The ACT LED flashes amber when activity is detected on the network 1 5 Accessing WebRelay 10 Standard Access Using a Web Browser WebRelay 10 has a built in web server that provides simple web pages that can be accessed directly using a standard web browser This allows users to access the unit with NO SPECIAL SOFTWARE installed on their computer This is ideal for applications that require a quick simple solution that does not need to be accessible to more than a few people This configuration is simple to setup simple to use and can be accessed from any computer Note Network routers may need to be configured to allow access from computers outside of the local network see Appendix C Accessing WebRelay 10 Over The Internet Xytronix Research amp Design Inc page 11 Installation and Setup WebRelay 10 Users Manual Section 2 Installation and Setup Installation consists of mounting WebRelay 10 connecting it to an Ethernet network providing po
115. rserserserserereereereereereereereete 13 Usedes ida 23 o NS 7 Dela toco 18 23 31 57 83 e UU oe 42 TTC O EE n ores E T AEN ae ass 35 Relays Tabu a ees 41 W State at POWETUD coooococcnonccnoooncncnoncncnnoncncnnnnnonnnno 42 VAN e a eee iS oe 4 Remote Service sscccccccsscsssscscvsevssssveevevsreees 93 94 NENA A a raa 11 Remote Service SNMP cccccccee eee 40 44 47 94 WED S CVC diana do adios 11 93 Remote Services 25 28 29 30 44 47 93 94 Wireless nr rt A estar 8 Restoring Factory Default Settings 83 Write Multiple CollS oooonoconnccnnncononncnonnconnncnnnonos 77 Route tds 11 18 88 93 Write Multiple ReglsSterS oooonooocnnconoocnnonncnonncnonnno 79 S Write Single Coldl ooooooocnoncciociconccnonccconaconnncnnnnconnnnos 75 Schedule 8 33 36 48 49 50 51 62 64 102 x Script Tab iii as 52 AML Operatoria 59 Xytronix Research amp Design Inc page 109
116. s any other value than 1 or 0 the value will be displayed in the same column with a gray background Up to 14 characters may be entered here By default the text is OFF page 54 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 12 Control Page Setup Tab The Control Page Setup page is used mainly to set parameters that affect the view of the Control Page how often it will refresh etc 000 WebRelay 10 Qr ControlByWeb x Ww Setup Sensors Events Script Control Page Setup Control Page This C E WebRelay 10 MAA AN Yes NoO Refresh Rate ME Seconds Display Display Display Counter Display Display State Counter Reset Button On Off Buttons Pulse Button EN EA Eales 2 tt Display Configuration Jaa i EIEIENE JRR ii i l Sensor 3 Figure 2 4p Control Page Setup Tab Main Header Text The text entered here appears at the top of the Control Page It also appears in the header of the email text when the email notification is used This field can be up to 40 characters in length The default text is WebRelay 10 Auto Refresh The Auto Refresh Page option will cause the Control Page to continually update its contents by setting a timer in the web page that causes it to be reloaded at a specified time interval When set to Yes the web page will be refreshed at the time interval specified in the
117. s erased to make room for new data a full sector 4K bytes is erased at one time Log File log txt This log file is user configurable under the Logging setup tab see section 2 4 6 Logging Tab for more information and stores real world data such as temperatures and events such as relay contact changes It can be up to 512K bytes long and is stored using a comma separated value formatting scheme Relays sensors and inputs will only be displayed if they are selected in the Logging setup tab The file is read by requesting the log txt file from WebRelay 10 For example using the default IP address the following command would be used to request the log file http 192 168 1 2 log txt File Format MM DD YYYY HH MM SS Input 1 Input 2 Relay 1 Relay 2 Relay 10 Sensor 1 Sensor 2 Sensor 8 Source State Date and Time Format MM Month 1 12 DD Day 1 31 YYYY Year 1970 2106 HH Hour in 24 hour time 0 23 MM Minutes 0 59 SS Seconds 0 59 Sample File Date Time 1I1 12 R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 S1 82 83 Source 11 15 2010 11 00 46 0 1 1 1 1 0 1 0 1 0 1 1 078 0 076 4 082 7 Input02 on 11 15 2010 11 00 48 0 0 1 1 1 0 1 0 1 0 1 1 078 0 076 4 082 7 Input02 off 11 15 2010 11 01 08 0 0 0 0 0 0 1 0 1 0 1 1 078 0 076 5 082 9 Relay03 off 11 15 2010 11 02 04 0 0 0 0 0 1 1 0 1 0 1 1 077 7 076 4 083 4 Relay04 on 11 15 2010 11 05 00 0 0 0 0 0 1 1 0 1 0 1 1 077 7 076 4 083 4 XmlReq
118. s for WebRelay 10 to initiate a connection using the Remote Services The settings under the Advanced Network tab in the setup pages will enable the WebRelay 10 to open a TCP connection with an external server Once the connection is open the external server can send commands and or read the device The external server can leave the connection open so that it never closes or close the connection Remote Services is ideal for installations where the server and WebRelay 10 are installed on different networks This is especially useful when each WebRelay 10 is installed on a separate private network For example if the user doesn t control the network connections where WebRelay 10 is installed Remote Services would initiate a TCP connection over the Internet with the control computer Since WebRelay 10 initiates the connection Xytronix Research amp Design Inc page 93 Appendix E External Server and Remote Services WebRelay 10 Users Manual the control computer doesn t have to know the IP address of WebRelay 10 This means that WebRelay 10 can be installed using DHCP In addition no special router configuration is required This makes the network installation of WebRelay 10 very simple and since no incoming ports need to be opened in the router security is not compromised See section 2 4 3 Advanced Network Tab for more information WebRelay 10 can be configured to establish a con
119. s port It can be set within the range of O to 65535 Remote Services Enabled This option enables or disables Remote Services If Yes is selected Remote Services will be enabled as soon as the submit button is pressed and WebRelay 10 will immediately attempt to make a connection with the remote server power cycle not required Once a connection is established the connection will remain until it is disconnected by the remote server Proper connection with the remote server can be verified by viewing the system status log file see page 28 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup Appendix D Log Files The default setting for this field is No Most users should leave this setting at its default See Remote Services at the end of this section for more information Server Name IP Address Specify the name or IP address of the Remote Services server here If the IP address is specified enter it in this format aaa bbb ccc ddd For numbers that are less than 100 preceding zeros should not be included for example enter 80 rather than 080 This field can be up to 40 characters long and has no default setting Server Port Enter the TCP port used for the Remote Services server This can be set within the range of 0 65535 The default setting for this field is 8000 Connection String This text is sent to the Remote Services server when the connection is established This string sh
120. s read For example if the Reset Count is set to 10 the counter will cont from O to 9 and return to O on the next count This value can be set from 1 to 4000000000 Email Option Simple email messages can be sent in response to input changes This parameter is used to specify what input changes if any will cause email messages to be sent Note that email notification will work only if the email settings are correctly set up in the Network setup page The following options are available No Email Messages No email notifications will be sent due to input changes Send Email when input on Email notifications will be sent when input state changes to On Send Email when input off Email notifications will be sent when input state changes to OFF Send Email when input changes state Email notifications will be sent when input changes state to ON or OFF Note The default setting for this field is No Email Messages Use Email Address If email messages are to be sent out based on input changes these check boxes specify to which email addresses the message will be sent Email addresses specified on the Network setup tab will be displayed next to each check box By default no boxes are checked Remote Service SNMP When this box Send State Msg Trap on Input Change is checked SNMP traps and or State messages will be sent whenever the input state changes Remote Services or SNMP must be enabled and properly configured for this featu
121. s will be sent due to Alarm 1 conditions Send Email on Alarm 2 Email notifications will be sent due to Alarm 2 conditions Send Email on Alarm 1 and Alarm 2 Email notifications will be sent due to Alarm 1 or Alarm 2 conditions Send Email on Alarm 1 Alarm 2 and Normal Email notifications will be sent due to Alarm 1 Alarm 2 or when normal conditions are regained Use Email Address If email messages are to be sent out based on alarm conditions these check boxes specify to which email addresses the message will be sent Email address specified on the Network setup tab will be shown next to each check box Remote Service SNMP This field specifies the action with a remote server due to an alarm condition No Action No action is taken Send State Msg Trap An event string will be sent to the remote server For more information regarding the event string or other commands see Appendix E External Server and Remote Services The second drop down box specifies the conditions that will cause an alarm trigger The following alarm conditions are available Alarm 1 The specified action occurs due to Alarm 1 Alarm 2 The specified action occurs due to Alarm 2 Alarm 1 or Alarm 2 The specified action occurs due to Alarm 1 or Alarm 2 Xytronix Research amp Design Inc page 47 Installation and Setup WebRelay 10 Users Manual 2 4 10 Events Scheduler Tab WebRelay 10 Plus only Events can be programme
122. ses including direct indirect special incidental or consequential damages or losses arising from either the use of any information contained within this manual or the use of any products or services referenced in this manual Xytronix Research 8 Design Inc reserves the right to change any product s features specifications documentation warranties fee schedules and conditions at any time and without notice Xytronix Research amp Design Inc page 3 Warranty WebRelay 10 Users Manual Warranty This Xytronix Research amp Design Inc product has a warranty against defects in material and workmanship for a period of one year from the date of shipment During the warranty period Xytronix Research 8 Design Inc will at its option either repair or replace products that prove to be defective This warranty is extended to the original purchaser of the equipment only For warranty service or repair the product must be properly packaged and returned to Xytronix Research 8 Design Inc The purchaser shall prepay all charges for shipping to Xytronix Research amp Design Inc and Xytronix Research amp Design Inc will pay the shipping charges to return the product to the purchaser as long as the product is shipped within the United States If the product is shipped outside of the United States the purchaser shall pay all shipping charges duties and taxes Limitation The foregoing warranty shall not apply to defects o
123. sion 2 3 Locations may vary on older modules Relay z Indicator Gnd vins y NC p no qn ME A g t 8 Relay Number Power a Indicator e WebRel ay 10 j E gs Serial He Number Ig Hi 2 Pia S00 E a 3 3 g Terminal ACT LINK Strip Connector WebRelay Plus only Ethernet Connector Figure 1 4a Connections amp Indicators Version G Older version Relay s Indicator Vin Gnd MFG CO IN CONCORD CA NG NO J A ove 2485 3000BR 8 COM Relay Number Power Indicator Serial Number Terminal Strip Connector ACT LINK Ethernet Connector Xytronix Research amp Design Inc page 10 WebRelay 10 Users Manual Introduction Module Power Connectors Two 1 4 tab connectors located on the circuit board are used to apply power to the module Relay Connectors Each relay has three tab connectors for common normally open and normally closed contacts Female mating connectors not included are required for connecting user circuits Network Connector The Ethernet connector is located on a small CPU daughter card that is mounted to the main relay board I O Connector WebRelay 10 Plus includes a 5 position removable terminal connector for discrete inputs and temperature and or humidity sensors Relay Indicators Ten green LEDs indicate when each relay is energized The LEDs are located next to the corresponding relays When the relay is ene
124. stallation and Setup WebRelay 10 Users Manual 2 3 2 Method 2 Assign a Temporary IP Address to Configuration Computer If the first option above is not used you can use this option to communicate with WebRelay 10 By default WebRelay 10 comes from the factory with an IP address of 192 168 1 2 Communications with WebRelay 10 may be established by assigning an IP address to the configuration computer that is on the same network as WebRelay 10 for example the configuration computer could be assigned to 192 168 1 50 The following example is for those running the Windows operating system 1 Windows XP Open the control panel by clicking on the start menu and then on Control Panel Programs 2 ncpa cpl Windows Vista 7 Select the Windows Icon Start Menu and enter ncpa cpl into the search bar and press Enter Figure 2 3a P Search Everywhere P Search the Internet AE AA Figure 2 3a Vista 7 Start Menu CARTE Note The control panel E z a ds i File Edit View Favorites Tools Help shown Figure 2 3b is in gu 9 3 Poo rome E Classic View If the Address E Control Panel control panel is in Category View select i A A Accessibility Add Hardware Add or Remove Administrative Automatic BDE the Classic View option Options Programs Tools Updates Administrator Control Suite 2 H See Also 2 A before proceeding 2 21 Rh Windows Update hi felp and Ai Date and Time De
125. sted and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause interference to radio communications There is no guarantee however that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into a relay on a circuit different from where the receiver is connected Consult the dealer or an experienced radio TV technician for help Notice Changes or modification not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment Xytronix Research amp Design Inc page 5 Installation Guidelines Read Before Installing WebRelay 10 Users Manual Installation Guidelines Read Before Installing This unit must be installed by qualified personnel This unit must not be installed directly outdoors This unit must not be used for medical life savin
126. t from an XML application the html request will need to contain the password encoded as Base64 The following is an html request header without the password GET state xml relaylState 1 amp noReply 1 HTTP 1 1 Terminated w two r n The following example adds the password GET state xml relaylState 1 amp noReply 1 HTTP 1 1 Terminated with r n Authorization Basic bm9uZTp3ZWJyZWxheQ Terminated with two r n bm9uZTp3ZWJyZWxheQ is the Base64 encoded version of the user name password none webrelay A utility is provided at http www controlbyweb com encoder to encode the password Simply type the string username password into the website and press Encode Xytronix Research amp Design Inc page 61 Operation WebRelay 10 Users Manual 3 2 2 Monitoring Events Through eventX xml WebRelay 10 Plus only The relays can be configured to turn ON turn OFF or pulse at specified times Instructions to change the relay state at a given time or periodically are called events WebRelay 10 Plus supports 100 events which can be monitored through the eventX xml page where X is the event number 0 99 This can be demonstrated by entering the following URL into the address bar of a web browser http 192 168 1 2 event0 xml The following event xml page is returned lt event0 gt lt active gt yes lt active gt lt currentTime gt 11 14 2010 15 14 09 lt curren
127. t periodic log time If logging is disabled the next log time will indicate Disabled If logging is enabled but periodic logging is disabled by selecting Event Logging Only the next log time will indicate Event Logging Only Note This information is updated only when the page is refreshed page 38 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 7 Inputs Tab WebRelay 10 Plus only This page provides configuration options for the two control inputs built into WebRelay 10 Plus 000 WebRelay 10 a icali http 192 168 1 2 setup html cl Qr ControlByWeb Wi Setup sensor Levent sept contr Page say Conor ge Input Description Input 1 On Status Text ON Off Status Text OFF Counter Options GEER MEA 4000000000 Email Option No Email Messages Use Email Address 00000 CEA AS ON Send State Msg Trap on Input Change Figure 2 4h Inputs Tab Note In this manual the input is considered to be ON when the input is tied to ground Input This drop down menu is used to select the control input to which the options below will apply Input 1 or Input 2 Selects the corresponding control input Description This text field is used to describe the function of the selected input The text appears to the left of the corresponding input status on the Control Page and in email messages when email alerts are enabled This fie
128. t should be used such as Windows Notepad Programmer s Notepad vi or other text editor that output the file as a txt Rich Text Format rtf used by Microsoft WordPad is NOT compatible 000 WebRelay 10 6 http 192 168 1 2 setup html aQ ControlByWeb 2 Wi Setup Sensors Events Script Control Page Setup Control Page BASIC Script No Script Loaded Interpreter Status Upload BASIC Script no file selected CMA Yeso No SAO EINE El EAN Configure Figure 2 4n Script Tab BASIC Script This field displays the txt file that is uploaded to WebRelay 10 Text displayed in this screen cannot be edited In order to edit any script it must be rewritten in the txt file and uploaded to the unit again Interpreter Status This field displays whether the program is continuing to run has stopped or finished or if there are errors contained in the script If there are errors in the script the line on which the error occurred is displayed Upload BASIC Script This field displays the script selected to be uploaded to the device To upload a script to WebRelay page 52 Xytronix Research 8 Design Inc WebRelay 10 Users Manual Installation and Setup 10M click the Choose File button find the txt file previously written and select Open The location of the file should appear in the neighboring field To upload the script to the unit select Submit Run Script Th
129. tTime gt lt next Event gt 11 15 2010 15 15 00 lt nextEvent gt lt period gt 1 d lt period gt lt coun t gt 0 lt count gt lt relay gt 1 lt relay gt lt action gt turn relay s on lt action gt lt pulseDuration gt 0 5 s lt pulseDuration gt lt event0 gt The tags used by WebRelay 10 are described below Tags Description lt eventX gt Event tag where X represents the event number 0 99 lt active gt This field indicates whether or not the event is active The text yes indicates that the event is active and the event will occur at the next event time The text no indicates that the event is inactive and the event will no longer take place lt currentTime gt This field indicates the current date and time as MM DD YYYY HH MM SS in 24 hour format lt nextEvent gt The next time the event is scheduled to occur is given as MM DD YYYY HH MM SS If an event is inactive this field will display the date and time as XI RR REXK KK PRR lt period gt For events that occur more than one time this field indicates the period of the event time between event occurrences The unit of time is indicated after the value seconds s minutes m hours h days d or weeks w If this field is set to 0 then the event has been disabled For example 1d would be a period of 3 days lt count gt This field indicates the number of remaining times the event will occur If t
130. the same as http 266 70 164 97 80 Router configuration can vary widely Some routers have the capability of translating the addresses and the ports which would require no port configuration change on the WebRelay For example the router would be configured so that messages sent to http 266 70 164 97 8000 would be forwarded to http 266 70 164 97 80 which is the default HTTP port An example screen shot of a router configuration is given below This setup allows the two ControlIByWeb products in the above example to be accessed remotely from the Internet Note This screen shot is simply an example of a typical router setup page Routers will vary page 88 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix C Accessing WebRelay 10TM Over the Internet http 192 168 1 1 Forward htm 4 1 16 52 hup 192 168 1 1 Fonward htm Port forwarding can be used to set up public services on your network When users from the Internet make certain requests on your router they ALAS vii de redirected to the specified IP FORWARDING Ext Port Prntosol Protocol IP Address Enable T8000 To 8000 Y Y 192 168 1 25 192 168 1 192 168 1 192 168 1 192 168 1 192 168 1 0 192 168 1 192 168 1 192 168 1 To lo D 192 168 1 0 WebRelay 3001 To 8001 0 To lo To 0 DORM To lo To o DO To 0 Too a 0 0 0 o Tafo 0 0 0 _UPAP Forwarding _ C Port Triggering
131. their services The default value of this setting is No UTC Offset Time servers return the current time in Universal Time GMT It is common for many servers and data loggers to use GMT as their official time even when they are not located within the GMT time zone The default value for this field is 7 Mountain Standard Time For convenience the time can be converted to local standard time by entering the offset here This manual cannot include the UTC Offset for all parts of the world but the offset for GMT time and the four major US Time zones are listed here GMT Time 0 Eastern Standard Time 5 Central Standard Time 6 Mountain Standard Time 7 Pacific Standard Time 8 Xytronix Research amp Design Inc page 35 Installation and Setup WebRelay 10 Users Manual Daylight Savings In many parts of the United States and in some other countries the time is shifted forward by one hour during the summer months This is an effort to conserve energy by making the daylight last longer into the evening hours If this option is set to Yes the time on WebRelay 10 Plus will automatically be shifted forward by one hour between the hours of 12 00 AM 5 00 PM on the Daylight Savings Start date set below and it will shift back to standard time between the hours of 12 00 AM 5 00 PM on the Daylight Savings End date set below The time change is made at a random time within the previously mentioned five hour time frame i
132. this hexadecimal value into the temperature reading of 81 25 degrees The device returns a value of OXFFFFFFFF NaN if there isn t a valid reading or when the sensor isn t active WebRelay 10 Response Frame Example Sensor 1 and 2 Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization number 0x0001 Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x000C Unit Identifier 1 byte Slave Address Oxff if not used OxFF Function Code 1 byte Read Sensors 0x03 Data 10 14 Byte Count 0x04 0x0C 0x0008 bytes Sensor Value 0x00000000 OxFFFFFFFF 0x999A41B1 Sensor Value 0x00000000 OxFFFFFFFF 0xB85142D2 RX String 017 Rx 00 01 00 00 00 OB FF 03 08 99 9A 41 B1 B8 51 42 D2 Xytronix Research amp Design Inc page 73 Operation WebRelay 10 Users Manual Errors Sensor Read Error Function Code 1 byte 0x83 Exception Codes 1 byte 0x01 Function not supported 0x02 Incorrect combination of start address and input quantity Error Response Frame Example Field Name Length Function Example Data Transaction Identifier 2 bytes Synchronization between messages of 0x0001 server and client Protocol Identifier 2 bytes Zero for Modbus TCP 0x0000 Message Length 2 bytes Number of bytes in frame below 0x0003 Unit Identifier 1 byte
133. this section for more information set extVar0 External variables provide a way for scripts written in BASIC to interact with users and for scripts to execute as a result of event occurrences This option sets the variable extvar0 to 1 when the event occurs If a running script uses this variable it will function as defined in the script when the variable is set to 1 clear extVar0 This option clears extvar0 sets it to 0 when the event occurs See description of set extVar for more information Affected Relay s When an Action is selected the Affected Relay s on which that action will occur can be specified by marking the appropriate check boxes When change schedules is selected only check boxes 1 4 are selectable Pulse Duration If the Relay Action has been set to pulse relay s the Pulse Duration is set in this field The time is specified in seconds and can range from 0 1 seconds to 86400 seconds in 0 1 second increments The default time is 1 5 seconds Schedules Events can be assigned to one of five schedules The schedules are useful for creating complex events that vary with calendar dates such as work shift alarms Schedule 0 is always active it cannot be disabled Other schedules can be enabled and disabled by schedule events Multiple schedules may be active at one time The following is an example of how schedules and events might be used Schedule 0 Event Security system is enabled daily at 8 pm and disabl
134. ticall OK to accept the new settings 3 Use the following DNS server addresses Preferred DNS server Note If Use the following IP address is already selected the computer has been set up witha Static IP address Record these values so that the computer can be restored once the IP address of WebRelay 10 is successfully changed 7 Open the setup pages as described in section 2 4 If the setup pages are not accessible verify that Figure 2 3e TCP IP Properties WebRelay 10 is powered on and that the LINK light is illuminated Check all network connections and settings Altemate DNS server Another way to check communications is to ping WebRelay 10 from the command prompt by typing ping WebRelay 10 IP address page 22 Xytronix Research amp Design Inc WebRelay 10 Users Manual Installation and Setup 2 4 WebRelay 10 Setup Pages WebRelay 10 is configured using a web browser To access the setup pages enter the following URL in the address bar of a web browser http fipaddress setup html For example using the default IP address enter http 192 168 1 2 setup html After the page is requested a password prompt will appear Enter the username and password The default username is admin and the default password is webrela y password is case sensitive 2 4 1 Main Tab This is the initial page that is displayed when setup html is entered into the address
135. ting for this field is 192 168 1 2 Subnet Mask The subnet mask defines the size of the local network This must be obtained from the network administrator For additional information about sub netting and IP networking many tutorials are available on the Internet The default setting for this field is 255 255 255 0 Gateway This specifies the IP address of the gateway router This must be obtained from the network administrator The default setting for this field is 192 168 1 1 Preferred DNS Server The IP address of the Primary DNS server is specified here When DNS services are required this is the address that will be used The default setting for this field is 192 168 1 1 This field is only required when the following options are used Remote Services when server is specified by name and not IP address Sync time clock with remote NTP server when server name is specified by name and not IP address Mail Server when server name is specified by name and not IP address Alternate DNS Server This field is used to specify the IP address of a Secondary DNS server This is used when WebRelay 10 requires DNS services and the preferred DNS server is not available The default setting for this field is 192 168 1 1 HTTP Port The TCP port used for HTTP communications web browser xml get commands with WebRelay 10 is specified here The default setting for this field is 80 which is the standard HTTP port It is rec
136. ts for each relay sensor or input are configured separately Select the the Email Option and the checkbox for the desired email recipient for each relay sensor or input Once the email settings are entered the email functionality can be tested by entering the following command http IP address state xml testEmail 1 For example using the default IP address enter http 192 168 1 2 state xml testEmail 1 This will cause an email message to be sent immediately If the messages don t get through the system log file may have some clues to assist in diagnosing the problem http 192 168 1 2 syslog txt page 82 Xytronix Research amp Design Inc WebRelay 10 Users Manual Appendix A Restoring Factory Default Settings Appendix A Restoring Factory Default Settings In the event that the IP address or passwords are forgotten WebRelay 10 may be restored to its original factory default settings 1 Remove the DC power from the unit This will also de energize any relay coils 2 Use a thin non conductive object such as a toothpick to press and hold the small button located next to the RJ 45 connector A tactile feel can be detected as the button is pressed CAUTION DO NOT USE METAL OBJECTS FOR THIS FUNCTION 3 While depressing the button apply power and wait for about 10 seconds before releasing the button All settings will be back to the original factory defaults log txt and syslog txt are retained
137. u lets the user specify the state of each of the internal relays when WebRelay 10 is powered up The following options can be selected off unless overridden by event The relay will be OFF upon power up This is the default setting on unless overridden by event The relay will be ON when power is applied to WebRelay 10 last state unless overridden by event WebRelay 10 Plus only Upon power up the relay will return to its last state when WebRelay 10 Plus was powered off input state unless overridden by event WebRelay 10 Plus only The relay will turn ON upon power up if the input is on opposite input state unless overridden by event WebRelay 10 Plus only The relay will turn ON upon power up if the input is OFF or be OFF if the input is ON Relay Option WebRelay 10 Plus only The inputs can be configured to control the relay The options in this drop down menu specify how the input affects the relay Note Input states will only affect the relay at the time the input is changed Once the change has taken place the state of the input has no effect on the state of the relay In other words if the input causes the relay to go on a user may turn the relay OFF from the web browser even if the input is Still ON no relay control The input has no effect on the relay set relay equal input 1 When the input is tied to ground the relay turns ON When the input is open the relay turns OFF
138. ur whenever the selected relay is turned ON or OFF When inputs are selected as an Event Trigger logging will occur whenever the input state changes When sensors are selected as an Event Trigger logging will occur whenever the temperature humidity changes by a set amount The following Log Event Trigger options are available Input 1 2 Relay 1 10 Sensor 1 8 Events XML Requests MODBUS Requests SNMP Requests Filter Logged Requests When logging is enabled for XML Requests Modbus Requests or SNMP Requests the user can filter out Reads such as reading the relay or input state via an XML request or Writes such as changing the relay state via an XML commana On the Control Page Setup tab the user can specify the refresh rate of the Control Page Each time the page is refreshed an XML request is sent and logged as a Read Since the default refresh rate is 3 seconds the log file can get cluttered by many XML request logs By filtering out Reads refresh requests will not be shown in the log Likewise by selecting Writes any log created by changing the state of the relay will not be shown in the log file The default selection is None Note When XML Requests are setup to be logged the IP address from which the Read or Write is generated is logged as well as if it was a Read request R or Write request W See Appendix D Log Files for additional information Next Log Time This field displays the nex
139. varl 0 Testing and Debugging A copy of the BASIC interpreter for Windows is also available on our website for the use of testing and debugging The WebRelay 10 will only acknowledge errors as it runs This means that if a path of the script is not encountered errors may still exist The Windows version of the interpreter however will check for errors before the script is run The PRINT function is available for use with the Windows version of the BASIC interpreter The interpreter on the device however will not recognize this command Note The script will be restarted by submitting any of the setup pages or by power cycling the unit Xytronix Research amp Design Inc page 103 Appendix H Specifications WebRelay 10 Users Manual Appendix H Specifi Power Requirements cations Input Voltage 10 36 VDC Current See table below for typical values 10 Mbps Network Speed Power Supply No Relays Energized 5 Relays Energized 10 Relays Energized 12 VDC 122 mA 605 mA 1160 mA 24 VDC 71 mA 292 mA 524 mA 36 VDC 53 mA 203 mA 346 mA 100 Mbps Network Speed Power Supply No Relays Energized 5 Relays Energized 10 Relays Energized 12 VDC 190 mA 676 mA 1194 mA 24 VDC 102 mA 330 mA 563 mA 36 VDC 76 mA 224 mA 370 mA 1 0 10 Relays 2 Inputs WebRelay 10 Plus only Up to 8 Temperature and or Humidity Sensors WebRelay 10 Plus only Relay Contacts
140. wer configuring via a web browser and wiring relay contacts to the device that will be controlled For WebRelay 10 Plus models inputs and sensors can be wired to the device using the 5 position terminal connector 2 1 Mounting WebRelay 10 can be mounted to a standard 35mm by 7 55mm DIN Rail Attach the module to the DIN Rail by placing the top hooks on the back of WebRelay 10 to the DIN Rail and then snapping the bottom hooks into place Remove from the DIN Rail by depressing the latch release on the mounting bracket See Appendix I Mechanical Information for additional mechanical details Figure 2 1a DIN Rail Mount page 12 Xytronix Research 8 Design Inc WebRelay 10 Users Manual Installation and Setup 2 2 Connection CAUTION MAKE SURE POWER IS SHUT OFF BEFORE WIRING CAUTION THIS UNIT SHOULD BE INSTALLED BY A QUALIFIED TECHNICIAN MIS WIRING OR MIS CONFIGURATION COULD CAUSE PERMANENT DAMAGE TO THE WebRelay 10 AND OR THE EQUIPMENT TO WHICH IT IS CONNECTED Relay connections are made through the 1 4 inch male tab connectors Mating connectors 1 4 inch female tab connectors can be purchased at electrical supply stores It is recommended that the load device to be controlled not be connected to WebRelay 10 until after WebRelay 10 has been configured and tested By doing this wiring and configuration mistakes will not cause the attached devices to turn on unexpectedly IMPORTANT WI
141. will control the relay Input 1 or Input 2 Email Option Simple email messages can be sent when relays are turned ON or OFF This parameter is used to specify what conditions if any will cause email messages to be sent Note that email notification will work only if the email settings are correctly set up in the Network setup page The following options are available No Email Messages No email notifications will be sent when relay changes Send Email when relay on Email notifications will be sent when relay state changes to ON Send Email when relay off Email notifications will be sent when relay state changes to OFF Send Email when relay changes state Email notifications will be sent when relay changes state to ON or OFF Note The default setting for this field is No Email Messages Xytronix Research 8 Design Inc page 43 Installation and Setup WebRelay 10 Users Manual Use Email Address If email messages are to be sent out when relays change state these check boxes specify to which email addresses the message will be sent Email addresses specified on the Network setup tab will be displayed next to each check box By default no boxes are checked Remote Service SNMP When this box Send State Msg Trap on Input Change is checked SNMP traps and or State messages will be sent whenever the relay state changes Remote Services or SNMP must be enabled and properly configured for this feature to be ef
142. word is disabled default and Modbus functionality is enabled on the Advanced Network WebRelay 10 functions as a Modbus slave Host devices such as PLCs open a connection with WebRelay 10 on port 502 configurable under Advanced Network tab and then send requests to read or set relay states read input states or read sensor values When WebRelay 10 receives a command it will perform the desired function and return a response WebRelay 10 Function Code Summary WebRelay 10 supports the following function codes Code Name Modbus Feature WebRelay Data Type Manual Function Address Section Read Coils 01 Relays 1 10 0 9 Discrete 3 4 4 Read Discrete Inputs 02 Inputs 1 2 0 1 Discrete 3 4 5 Read Sensors 03 Sensors 1 8 272 286 32 bit 3 4 6 Write Single Coil 05 Relays 1 10 0 9 Discrete 3 4 7 Write Multiple Coils 15 Relays 1 10 0 9 Discrete 3 4 8 Pulse Coils 16 Relays 1 10 0 9 32 bit 3 4 9 Multiple commands may be sent without closing and re opening the connection but if no data is transferred for 50 seconds the connection will time out and close To keep the connection open a read request can be sent periodically WebRelay 10 has two TCP sockets available for Modbus TCP This allows two connections to be open at one time Requests for more than two open connections will be rejected When errors occur an error code is returned Most Modbus client software will interpret this c
143. y 10 can be configured to only allow access to client devices computers servers other ControlByWeb devices etc with certain IP addresses Two IP address ranges are provided and only client devices with addresses that fall within those two ranges will be allowed access Devices with IP addresses that fall outside of those ranges will not receive any response from WebRelay 10 The following are examples To allow access from any device this is the default setting IP Filter Range 1 0 0 0 0 299 299 299 6299 IP Filter Range 2 0 0 0 0 0 0 0 0 Xytronix Research amp Design Inc page 29 Installation and Setup WebRelay 10 Users Manual To limit access to only one device address 192 168 1 33 IP Filter Range 1 192 168 1 33 192 168 1 33 IP Filter Range 2 0 0 0 0 0 0 0 To limit access to only devices on the local network and one device on the internet address 10 143 100 32 IP Filter Range 1 192 168 1 0 192 168 1 255 IP Filter Range 2 10 143 100 32 10 143 100 32 Note The address specified for the Remote Services server if applicable is automatically allowed through the firewall no matter how this is set Remote Services Remote Services initiates an outgoing connection to a server at a remote location This can be used in an environment where a web server on the Internet provides a custom web page to WebRelay 10 and other Contro

Download Pdf Manuals

image

Related Search

Related Contents

Mamiya 645 DF+ and Leaf Credo Digital Back Users Guide  Conférences - Salon du mieux  Manuel de référence - Service Audiovisuel    Rotary Experiment #03: Speed Control SRV02 Speed Control using  Gemstar - Caution in Use FSN final wk 26 03 13 FRE  日本語 - キシダ化学株式会社  Phonix PBTT9+G mobile headset    XC6SLX150 X2 Coprocessor Module User Manual  