3300 Installation - Protec Fire Detection

image

Contents

1. 42 APPENDIX 4 3300 MAIN 5 2 2 21 1 1 1 1 1 1 211 uuu 43 APPENDIX 5 3300 PROGRAMMING QUICK REFERENCE GUIDE 44 93 530 70 Issue 0 Page 4 of 44 Protec Fire Detection PLC 2007 og Protec 1 0 3300 System Overview The main features of the Protec 3300 Fire Alarm system are e Four and eight detector zone models available e Four monitored alarm circuits rated at 150mA each e Common negative allowing three wire operation e Manual call point activation can override zone delays e Re sounding of outputs if a zone changes from automatic to manual activation e Three auxiliary inputs Keyswitch Class Change and Remote Alarm e Global Fire and Global Fault clean contact connections e Monitored Auxiliary 24V output Overload Protected 100mA maximum e Programmable capacitive or resistive detector circuit end of line monitoring e Extensive range of engineering functions accessed via a 5 digit code entry or key switch activation Delays to zones Disablement of zones Coincidence Operation testing of zones Non latching zones Disablement of alarm circuits Disablement of fire link output Comprehensive fault diagnosis features e Expansion outputs to drive one fire link interface and one eight way zonal mimic interface e Repeat panel output to drive up to eight 3300 Repeat Panel
2. 17 12 3 SWICNING OM ina E 17 13 0 PROGRAMMING OVERVIEW U u u uuu u u u T 18 1221 PACCOSS LOVOIS OONO OEE 18 13 2 Zone Programming Choices a 19 14 0 PROGRAMMING DETAILS U U u u uuu uu uu u u 20 141 PROGRAMMING ZONE DISABLEMENTS u u u u u 20 14 2 Programming Alarm Disablements a senere 21 14 3 Programming Zone 2 00222020002 0000000000000000000000000000 22 14 4 Programming Zones into Test 0 200220 0 000 0000 000 23 14 5 Programming Coincidence 2 2 22 2222 2 00 20 000000000000000000 000 24 14 6 Programming Non Latching 2 2 22 2 440220 1 0 10 010 000000000000 25 14 7 Programming Expansion Interface Node 26 15 0 OVERRIDING SYSTEM DELAYS rrnvnnnnvvnnnnvnnnnnnnnnnvnnnnvnnnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnr 27 16 0 DISABLING THE FIRE LINK INTERFACE i ernnnnvvnnnnvnnnnvnnnnnnnnnnnnnnnennnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnenennnnnr 28 17 0 DELAYING FIRE LINK ACTIVATIONS errnnnvnnnnvvnnnnvnnnnvnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnr 29 18 0 PSU MONITORING TYPE SET UP annnnn
3. 7 Protec 3300 NON ADDRESSABLE FIRE ALARM CONTROL PANEL INSTALLATION COMMISSIONING AND MAINTENANGE MANUAL Zone Location 3300 Fire Alarm Control Panel ENS4 Parts 2 and 4 1997 c O Fire Zones e Go o _ 0 0 bo Mute e 2 Fault Disablement Test Zones Buzzer Disablements cesec Fire FiroLink Lavel2 General Output Gonoral Alarm jperated Accessed Test Delay Disablement Outputs Supply Present 0 Sound mn Oo 606 5 Generel gt w Fault Faul Protec Fire Detection PLC Protec House Churchill Way Nelson Lancashire BB9 6RT Telephone 44 0 1282 717171 Fax 44 0 1282 717273 Web www protec co uk Email sales protec co uk Document Revision Details Issue Modification Detail Author Date 0 Document Creation NH 12 02 07 93 530 70 Issue 0 Page 2 of 44 Protec Fire Detection PLC 2007 og Protec Table of Contents 1 0 3300 SYSTEM OVERVIEW usasapa emnene renal ner aaeain 5 2 0 IMPORTANT NOTES PLEASE READ U U u u uuu uu uu uu 6 3 0 ITEMS SUPPLIED WITH THE 3300 PANEL u u u uu uu 6 4 0 CABLING REQUIREMENTS U 7 4 1 Detector Alarm and Auxiliary Wiring a 7 42 Mans WIN E EA EEE AREE EE EEEE EAA EOE
4. 93 530 70 Issue 0 Page 36 of 44 Protec Fire Detection PLC 2007 PLA Protec Fire Detection pic 27 0 Fault Rectification Guidelines Fault Suggested Action Detector Circuit Open Short Disconnect the faulty zone and re connect the end of line unit resistive or Circuit capacitive directly at the 3300 zone terminals If the zone fault clears the zone wiring and detector base connections should be thoroughly investigated and any faults rectified In particular check that all detectors are connected properly into their bases If the fault remains check the correct end of line monitoring is programmed ensure it is set up for the type of end of line monitoring being used resistive or capacitive If the fault still remains either the end of line or the Main PCB is faulty EEPROM checksum fault A checksum error has been detected in the site data stored in EEPROM Enter access level 2 and press Silence Alarms then Reset Panel to clear the fault If it re appears within 10 minutes the Main PCB is suspect and should be replaced PROGRAM checksum fault A checksum error has been detected in the system program memory Enter access level 2 and press Silence Alarms then Reset Panel to clear the fault If it re appears within 3 minutes the Main PCB is suspect and should be replaced WATCHDOG fault A watchdog time out has been detected by the program Enter access level 2 and press Silence Alarms
5. Fault Disablement Test Zones Disablements O O Supply Fire Link Level2 General Output General Alarm Fire Present Operated Accessed Test Delay Disablement Outputs Link Faults Alarms General System Alarm Power Fire Aux Repeat Silenced Fault Fault Fault Supply Link 24v Panel Fai Fault Fault Fault 93 530 70 Issue 0 Page 33 of 44 Protec Fire Detection PLC 2007 og Protec 24 0 Alarm Fault Details The 3300 will display the fault status of its alarm outputs if the Alarm Fault indicator is illuminated in the fault diagnosis mode Display row 1 shows any open circuit faults e Zones 1 amp 2 will be illuminated when alarm circuits 1 or 2 have an open circuit fault e Zones 3 amp 4 will be illuminated when alarm circuits 3 or 4 have an open circuit fault Display row 2 shows any short circuit faults e Zones 1 amp 2 will be illuminated when alarm circuits 1 or 2 have a short circuit fault e Zones 3 amp 4 will be illuminated when alarm circuits 3 or 4 have a short circuit fault Figure 24 0 shows alarm circuits 1 or 2 having an open circuit fault condition and alarm circuits 3 or 4 having a short circuit fault condition Figure 24 0 Example of an alarm fault display Fire Zones OO O 1 2 3 4 5 6 7 8 O O e O O O Fault Disablement Test Zones Disablements o eoo Supply Fire Link Level2 General Output General Alarm Fire Present Operated Accessed Te
6. then Reset Panel to clear the fault If the fault persists the Main PCB is suspect and should be replaced SW_ERROR fault An expected software function has not been carried out Enter access level 2 and press Silence Alarms then Reset Panel to clear the fault If the fault persists the Main PCB is suspect and should be replaced Expansion Node fault A node has been detected as missing or faulty on either the internal or external expansion ports Check all nodes to ensure their address switches are all correct set from address 1 onwards If so determine which node is missing or faulty then rectify the problem on that node Alarm Open Short Circuit Fault Disconnect the faulty alarm circuit and re connect the end of line unit directly at the 3300 alarm terminals If the alarm fault clears the alarm wiring and sounder connections should be thoroughly investigated and any faults rectified In particular ensure all sounders are polarity protected and suppressed If the fault remains the Main PCB is suspect and should be replaced Power Supply Fault If the mains has failed first verify the mains supply to the panel is correct If it is check the mains fuse FS2 on the power supply PCB and replace it if it has ruptured 1A HRC 20mm If a battery over voltage condition exists the power supply PCB is suspect and should be replaced If a battery under voltage condition exists replace the batteries with a new fully
7. Consult the relevant interface installation sheet for further details 93 530 70 Issue 0 Page 15 of 44 Protec Fire Detection PLC 2007 Protec Protec Fire Detection plc 12 0 Commissioning 12 1 Connecting the Mains Important Note Pay particular attention that the earth cable is firmly connected to the earth terminal of the power supply and that the earth strap from the power supply PCB to the earth post is sound Ensure the fused double pole isolator is in the OFF position then connect the incoming mains cable to the appropriate terminals on the power supply PCB see figure 12 0 Figure 12 0 Power Supply Terminal Details Wm AST INCOMING MAINS CABLE 230V s0Hz N aw PCOS 93 530 70 Issue 0 Page 16 of 44 Protec Fire Detection PLC 2007 ER 12 2 Installing and Connecting The Standby Batteries The panel is designed to house two 12V 3 3Ah Valve Regulated Sealed Lead Acid SLA batteries These fit into the left hand compartment of the 3300 and should be secured with the Tie Wraps provided The two batteries must be connected in series a connecting link is supplied for this purpose The batteries must then be connected to the Power Supply PCB using the wires provided please observe polarity when connecting Ensure all spade connectors are pushed fully home onto the battery terminals Figure 12 1 shows the location and connection details for the batteri
8. charged set If the fault does not clear within two hours the power supply PCB is suspect and should be replaced If a battery faulty condition exists verify the connections to the batteries are sound If the connections are sound and the fault persists replace the batteries with two new fully charged ones and leave to charge for two hours 93 530 70 Issue 0 Page 37 of 44 Protec Fire Detection PLC 2007 PLA Protec Fire Detection pic 28 0 3300 Technical Specification Power Supply Mains 230V AC Nominal 10 Integral Charger 1A switch mode temperature compensated 250mA battery charge current Batteries monitored for disconnection failure and deep discharge Auxiliary 24V output 24V dc 100mA max monitored for fuse failure fuse self resetting Maximum Battery Size 2 x 12V 3 3Ah Mains Fuse 1A HRC ceramic 20mm Battery Fuse 1 6A F 20mm Working Voltage 20V to 30V dc Current Consumption 15mA 24V dc Supply not in alarm mains failed buzzer slow beeping General and PSU fault light illuminated detector load Number of Detector Zones 4 or 8 depending on the model purchased Maximum Zone Cable Length 500 Metres Maximum Zone Cable Capacitance 0 27uF measured with no end of line fitted Maximum Zone Cable Resistance 15Q per conductor Detector Circuit EOL Values Resistive 8 2kQ or capacitive 1004 220 Maximum Quiescent Zone Load 1 5mA per zone Maximum Number of Detectors 20 per
9. overridden 93 530 70 Issue 0 Page 27 of 44 Protec Fire Detection PLC 2007 og Protec 16 0 Disabling The Fire Link Interface It is possible for the authorised user at access Level 2 or 3 to disable the Fire Link interface if fitted Disabling the interface inhibits Fire Link faults and activations 1 From access level 1 enter the 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available Using button 2 scroll to the Alarm Outputs indication Any current settings in this option will be displayed on row 1 of the display on zone 4 Accept this option by pressing button 3 The Alarm Outputs indicator will flash showing this option has been accepted Select the Disable Fire Link option by pressing button 2 until the row 2 indicator for zone 4 is Illuminated Press button 1 to show that the fire link is to be disabled not disabled The row 1 zone 4 indicator will be illuminated if the fire link is disabled Press button 3 to return to the selection menu Press button 4 to accept and program the set up and return to access level 2 The Fire Link and General Disablement indicators will be illuminated 93 530 70 Issue 0 Page 28 of 44 Protec Fire Detection PLC 2007 og Protec 17 0 Delaying Fire Link Activations It is possible for an engineer at access Level 3 to allow
10. 2 will display the special software version if applicable The software versions are displayed in 8 bit binary with the least significant bit being indicated at zone 8 and the Most significant bit being indicated at zone 1 Please consult the binary to decimal converter given in appendix 3 for clarification An example of software version 10 and special version 5 is given in figure 22 0 Figure 22 0 Example of Software Version Display Fire Zones 1 2 3 4 5 6 7 8 00000908 Fault Disablement Test Zones Disablements o eoo Supply Fire Link Level2 General Output General Alarm Fire Present Operated Accessed Test Delay Disablement Outputs Link Faults O O O O O O O Alarms General System Alarm Power Fire Aux Repeat Silenced Fault Fault Faull Supply Link 24v Panel Fault Fault Fault Fault 93 530 70 Issue 0 Page 32 of 44 Protec Fire Detection PLC 2007 23 0 Detector Zone Fault Details The 3300 will display the fault status of the detector zones if the General Fault indicator is illuminated in fault diagnosis mode e Display row 1 shows any open circuit zone faults e Display row 2 shows any short circuit zone faults The example in figure 23 0 shows Zone 2 as having an open circuit fault and Zone 7 as having a short circuit fault Figure 23 0 Example of a Detector Zone Fault Display Fire Zones 09000000 1 2 3 4 5 6 7 8 O O O O O O
11. Accessed indicator by repeatedly pressing button 2 Any zones currently programmed as coincidence will be displayed on row 1 of the display Accept the option by pressing button 3 3 The Level 2 Accessed indicator will flash to indicate this option has been accepted 4 Scroll to the detector zone to be set as coincidence by pressing button 2 5 Press button 1 to set un set that zone as a coincidence zone the relevant row 1 indicator will be illuminated when the zone is set as coincidence 6 Program any other zones required into coincidence by following steps 5 and 6 7 Press button 3 to return to the selection menu 8 Press button 4 to accept and program the coincidence set up and return to access level 2 93 530 70 Issue 0 Page 24 of 44 Protec Fire Detection PLC 2007 og Protec 14 6 Programming Non Latching Zones With the 3300 it is possible to program one or more of the detector zones to operate as non latching In this mode the zone activates as normal but when the cause of the activation is removed the 3300 will reset The Global Fire contacts and fire link if fitted do not operate on a non latching zone activation This feature is of use when connecting fire alarm systems together and ensures a latch up situation cannot occur where each panel triggers the other due to latched zone activations The procedure for programming a zone as non latching is given below 1 From access level 1 enter
12. E E A 7 5 0 INSTALLATION PROCEDURE mrnnnnvnnnnvnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnennnr 8 6 0 TESTING OF CABLING PRIOR TO CONNECTION u u 11 7 0 DETECTOR CIRCUIT CONNECTIONS u u u uu uu uu 11 8 0 ALARM CIRCUIT CONNECTIONS u u uuu uu uu u 12 9 0 AUXILIARY INPUT AND OUTPUT WIRING u 13 KOVSWICN INU ek u oa na dre ed eee es 13 9 2 Remote Alarm 13 9 3 Class Change ranerne sasawa nasqa 13 94 Global u uuu ua aa apana 13 95 Global Fire OUIDUL l desis bien eee Wetec egies 13 10 0 PANEL WIRING 222252000224 en eaten ee 14 11 0 INTERNAL EXPANSION PORT ernnnnvnnnnvnnnnnvnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnennnnnr 15 12 0 22 22 16 12 1 Connecting 16 12 2 Installing and Connecting The Standby Batteries 000022 2 21 000 000000000000 0
13. Page 13 of 44 Protec Fire Detection PLC 2007 og Protec 10 0 Repeat Panel Wiring The 3300 can drive up to eight 3300 Repeat Panels directly from its External Expansion Interface port No extra driver boards are required The external expansion port has four connections present on a terminal block labelled EXT EXP on the Main PCB These are 1 24V fused at 100mA self resetting when overload and power is removed non monitored 2 OV 3 Data 4 Data This port connects to all Repeat Panels and should be wired in screened cable to ensure compliance with relevant EMC regulations Figure 10 0 shows a typical installation Figure 10 0 Typical 3300 External Expansion Interface Installation To further Repeat Panels REPEAT PANEL REPEAT PANEL 1 2 93 530 70 Issue 0 Page 14 of 44 Protec Fire Detection PLC 2007 og Protec 11 0 Internal Expansion Port The 3300 can accept various internal interfaces these must be located within the 3300 panel enclosure The interfaces currently available are e Fire Link Interface a maximum of one per panel e 8 way Volt free contact zonal fire fault mimic A maximum of one per panel These interfaces connect using the 10 pin expansion port J2 located at the middle left of the Main PCB If both the fire link and the 8 way mimic interfaces are used the fire link must be connected to the 3300 then the 8 way mimic to the fire link interface
14. across the remote alarm terminals When activated the 3300 will activate alarm outputs fast intermittently sound the internal buzzer and illuminate the General Fire indicator The Global Fire output is NOT activated 93 Class Change Input The class change input is active when a short circuit less than 50Q is connected across the Class Change terminals When activated the 3300 will activate alarm outputs continuously The Global Fire output is NOT activated 9 4 Global Fault Output The Global Fault output is a set of Volt free relay changeover contacts rated at 1A 24V dc max to allow interfacing to other equipment The contacts are normally activated the N C and C contacts are high resistance and will release when the 3300 has any fault 95 Global Fire Output The Global Fire output is a set of Volt free relay changeover contacts rated at 1A 24V dc max to allow interfacing to other equipment The contacts are normally released the N C and C contacts are low resistance and operate as follows The Global Fire output WILL activate if e standard zone has activated manual or automatic e A delayed zone has expired e Acoincidence zone has expired or a second coincidence zone has activated The Global Fire output WILL NOT activate if A remote alarm activation occurs A zone in test mode is activated A non latching zone is activated The Sound Alarms button is pressed in access level 2 or 3 93 530 70 Issue 0
15. disabled 7 Follow the procedure above until all zones that are to be disabled have their row 1 indicators illuminated 8 Press button 3 to return to the programming selection menu 9 Press button 4 to accept and program the disablement set up and return to access level 2 10 The yellow General Disablement indicator will be illuminated steady as will the row 2 disablement indicator for the relevant zone s 93 530 70 Issue 0 Page 20 of 44 Protec Fire Detection PLC 2007 og Protec 14 2 Programming Alarm Disablements The 3300 can have alarm circuits 1 and 2 and or alarm circuits 3 and 4 disabled When an alarm circuit is disabled faults and activations on that circuit are inhibited 1 From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key switch depending on the model purchased 2 Level 2 Accessed indicator will illuminate 3 Using button 2 scroll to the Alarm Outputs indication Any current alarm disablements will be displayed on row 1 of the display Accept this option by pressing button 3 4 The Alarm Outputs indicator will flash showing this option has been accepted 5 Highlight the alarm circuit pair to be disabled by pressing button 2 e Highlight zone 1 indicator if alarm circuits 1 and 2 to be disabled e Highlight zone 2 indicator if alarm circuits 3 and 4 to be disabled Note Zone 3 and zone 4 indicators can also be selected in this opt
16. the 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Scroll to the Fire link Operated indicator by repeatedly pressing button 2 Any zones currently programmed as non latching will be displayed on row 1 of the display Accept the option by pressing button 3 3 The Fire Link Operated indicator will flash to indicate this option has been accepted 4 Scroll to the detector zone to be programmed as non latching by pressing button 2 5 Press button 1 to set un set that zone as non latching the relevant row 1 indicator will be illuminated when the zone is non latching 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the non latching set up and return to access level 2 93 530 70 Issue 0 Page 25 of 44 Protec Fire Detection PLC 2007 og Protec 14 7 Programming Expansion Interface Node Information The 3300 can accept interfaces on its expansion ports The 3300 must be programmed with the number of nodes to expect on its expansion ports both internal and external The number of nodes is expressed in binary using a 5 bit code Please note that the 3 remaining bits indicated on zones 1 2 and 3 are reserved for future features and should be left clear The procedure for programming expansion information is as follows 1 From access level 1 enter the 5 di
17. to distinguish between automatic and manual zone activations the resistor value in the manual call point must be 1800 In retrofit situations values up to 5600 be used but MCP fire may not be given in all instances Protec 3300 manual call points incorporate the series 1800 resistor as standard 93 530 70 Issue 0 Page 11 of 44 Protec Fire Detection PLC 2007 og Protec 8 0 Alarm Circuit Connections The 3300 has four alarm circuit outputs all are rated for continuous use at 150mA and protected from over load by an auto resetting thermal fuse The fuse will reset when the cause of overload has been removed and the alarm output has been de activated Figure 8 0 shows typical connections for a 3300 alarm circuit Figure 8 0 Typical 3300 Alarm Circuit Connection Alarm Circuit Connection Polarised Sounder Polarised Sounder Polarised Sounder Resistor e Ensure the length of the alarm circuit wiring is no more than 500 metres e Ensure the capacitance of the alarm circuit wiring is no more than 0 27uF micro Farads e The 10kQ end of line resistor must be connected at the very end of the alarm circuit wiring ensuring the whole line is monitored for open circuit faults e Spurs should not be connected from the alarm wiring as the spur will not be monitored for open circuit faults e Only polarised and suppressed sounders should be used on the 3300 alarm circuits Failure to use polarised sou
18. zone smoke or heat Maximum Number of Devices 32 Manual Call Points and Detectors per zone Manual Call Point Series Resistor Value 1800 5 Number of Alarm Circuits 4 open and short circuit monitored Alarm Circuit End Of Line Value 10kQ 1 4W 5 Maximum Alarm Load 150mA from each alarm output Sounders must be polarised and suppressed Class Change Input Activates alarm outputs when connected to OV Remote Alarm Input Activates alarm outputs internal buzzer and general fire indicator when connected to OV Global Fault Contacts Rated at 24V dc 1 Amp maximum Global Fire Contacts Rated at 24V dc 1 Amp maximum Expansion Port Communications 2 wire Communication 2 wire Power Temperature Range 0 to 40 degrees C Humidity Limit 85 Non Condensing Environment Meets IP30 if mounted in a dry position that does not exceed the temperature and humidity limits given Mounting 3 or 4 points surface mount 93 530 70 Issue 0 Page 38 of 44 Protec Fire Detection PLC 2007 PLA Protec Fire Detection pic 29 0 3300 Features Specification Delay to Zone Activation Coincidence on Zones Non latching Zones Zone Disablements Alarm Disablements Fire Link Disablement Fire Link Delay Zonal Test Ability to Distinguish Between Manual or Automatic Zone Activation Ability to re activate a silenced zone by a manual Call Point Activation Ability to Accept Repeat Panels Ability to Accept a Fire Link Interfa
19. 10 19 00010011 68 01000100 117 01110101 166 10100110 215 11010111 20 00010100 69 01000101 118 01110110 167 10100111 216 11011000 21 00010101 70 01000110 119 01110111 168 10101000 217 11011001 22 00010110 71 01000111 120 01111000 169 10101001 218 11011010 23 00010111 72 01001000 121 01111001 170 10101010 219 11011011 24 00011000 73 01001001 122 01111010 171 10101011 220 11011100 25 00011001 74 01001010 123 01111011 172 10101100 221 11011101 26 00011010 75 01001011 124 01111100 173 10101101 222 11011110 27 00011011 76 01001100 125 01111101 174 10101110 223 11011111 28 00011100 77 01001101 126 01111110 175 10101111 224 11100000 29 00011101 78 01001110 127 01111111 176 10110000 225 11100001 30 00011110 79 01001111 128 10000000 177 10110001 226 11100010 31 00011111 80 01010000 129 10000001 178 10110010 227 11100011 32 00100000 81 01010001 130 10000010 179 10110011 228 11100100 33 00100001 82 01010010 131 10000011 180 10110100 229 11100101 34 00100010 83 01010011 132 10000100 181 10110101 230 11100110 35 00100011 84 01010100 133 10000101 182 10110110 231 11100111 36 00100100 85 01010101 134 10000110 183 10110111 232 11101000 37 00100101 86 01010110 135 10000111 184 10111000 233 11101001 38 00100110 87 01010111 136 10001000 185 10111001 234 11101010 39 00100111 88 01011000 137 10001001 186 10111010 235 11101011 40 00101000 89 01011001 138 10001010 187 10111011 236 11101100 41 00101001 90 01011010 139 10001011 188 10111100 237 11101101 42 00101010 91 01011011
20. 140 10001100 189 10111101 238 11101110 43 00101011 92 01011100 141 10001101 190 10111110 239 11101111 44 00101100 93 01011101 142 10001110 191 10111111 240 11110000 45 00101101 94 01011110 143 10001111 192 11000000 241 11110001 46 00101110 95 01011111 144 10010000 193 11000001 242 11110010 47 00101111 96 01100000 145 10010001 194 11000010 243 11110011 48 00110000 97 01100001 146 10010010 195 11000011 244 11110100 93 530 70 155 0 42 44 Protec Fire Detection PLC 2007 os Profet Protec Fire Detection plc 33 0 Appendix 4 3300 Main PCB Details The diagram below shows the 3300 control PCB and highlights the main connections and controls Repeat Panel Connections Auxiliary Connections Delay Time Setting Control Sounder Connections Clean Contact Outputs Detector Zone Connections GLOBAL GLOBAL SOUNDERS EXT EXP FIRE CLASS REMOTE AUX CHANGE ALARM 24V SND 1 DETECTION ZONES SND 2 SND3 SND 4 ZONE1 ZONE2 ZONE3 ZONE4 20 5 20 6 20 7 ZONES FIRE ZONES O 6600000 FAULT DISABLEMENT TEST ZONES PROTEC FIRE DETECTION Plc 020 FIRELINK LEVEL2 GENERAL CATET GENERAL te PPEP ACCESSED TES OUTPUT UTPUTS DELAY NOI TEST DELAYED ZONE ALARM EXPANSION ZONES ZONES DIS DIS PROG O O O O O O QO GENERAL SYSTEM ALARM FAULT POWER FIRE FAULT FAULT SUPPLY LINK 24V ZONE F
21. AULT FAULT FAULT FAULTS Keypad 24V dc Internal Power Expansion Connector Interface LED Display Connector 93 530 70 Issue 0 Page 43 of 44 Protec Fire Detection PLC 2007 og Protec 34 0 Appendix 5 3300 Programming Quick Reference Guide FUNCTION Level Program Zone Indication Indicator Test Mode 2 General Test Any one specified Zone Test Mode 3 General Test Relevant Zones Disable Zones 2 3 General Disablement Relevant Zones Disable Alarms 2 3 Alarm Outputs Zone 1 Circuits 1 and 2 Zone 2 Circuits 3 and 4 Disable Delays 2 3 Alarm Outputs Zone 3 Disable Fire Link 2 3 Alarm Outputs Zone 4 Fire Link Delay 3 Alarm Outputs Zone 5 PSU Monitoring 3 Alarm Outputs Zone 6 Set Delayed Zones 3 Output Delay Relevant Zones Set Coincidence 3 Level 2 Accessed Selected Zones Set Non Latching 3 Fire Link Operated Relevant Zones Expansion 3 Fire Link Zones Number of devices in Interface Binary Please note that any changes to the system program are not permanently stored until button 4 has been pressed at access level 2 for level 2 programming functions or access level 3 level 3 programming functions 93 530 70 Issue 0 Page 44 of 44 Protec Fire Detection PLC 2007
22. DO NOT SWITCH MAINS POWER ON AT THIS POINT Route the battery cables through to the battery compartment using the channels provided Replace the Main PCB a reversal of removal ensuring it is pushed fully down to the bottom edge of the panel Secure with the two screws removed previously Take care not to over tighten the screws Re connect the three way cable from the Power Supply to the Main PCB do not use undue pressure and ensure the cable is clipped into the locking ramp on the PCB header securely 7 Re fitting the Door Replace the plastic door by offering the top of the door up to the groove at the top of the plastic back box Swing the door down and ensure it pushes fully home into the back box without fouling the rubber keypad or light guides on the main PCB See figure 5 3 for details Tighten the two screws in the lower two corners of the door and replace the screw covers Figure 5 3 Refitting the 3300 Door 93 530 70 Issue 0 Page 10 of 44 O Protec Fire Detection PLC 2007 og Protec 6 0 Testing of Cabling Prior to Connection Before connecting any external cables to any field device detectors sounders auxiliary or outputs or the 3300 tests must be carried out using 500V insulation tester Megger The readings between each cable core and each core and earth should be greater than TA Important Notes e Equipment connected to the cabling durin
23. NOTE Test mode overrides all other programming 93 530 70 Issue 0 Page 19 of 44 Protec Fire Detection PLC 2007 og Protec 14 0 Programming Details In general the front panel buttons have the following alternate functions when the 3300 is in programming mode When Access Level 3 programming functions are being performed the Supply Present indicator will flash Button 1 Toggle Button 2 Scroll Button 3 Accept Button 4 Back Exit Program 14 1 Programming Zone Disablements The 3300 can have one or more of its detector zones disabled When a zone is disabled faults and activations from that zone are inhibited 1 From access level 1 enter your 5 digit user code 1 3 4 4 2 or turn the key switch depending on the model purchased 2 The level 2 Accessed indicator will illuminate 3 Press button 2 once The General Disablement indicator will illuminate steady to show the zone disablement option is selected the normal front panel display is temporarily replaced with the programming display Any current disablements will be displayed on row 1 of the display Accept the option by pressing button 3 4 The General Disablement indicator will flash showing this option has been accepted 5 Highlight the zone to be disabled by repeatedly pressing button 2 6 Press button 1 to show that it is to be disabled not disabled The relevant row 1 indicator will be illuminated if the zone is
24. a delay time before the Fire Link interface if fitted activates 1 From access level 1 enter the 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available Using button 2 scroll to the Alarm Outputs indication Any current settings in this option will be displayed on row 1 of the display on zone 5 Accept this option by pressing button 3 The Alarm Outputs indicator will flash showing this option has been accepted Select the Delay Fire Link option by pressing button 2 until the row 2 indicator for zone 5 is illuminated Press button 1 to show that the Fire Link is to be delayed not delayed The row 1 zone 5 indicator will be illuminated if fire link activations are delayed Press button 3 to return to the selection menu Press button 4 to accept and program the set up and return to access level 2 The Output Delay indicator will be illuminated showing that the system has a delay programmed Note The Fire Link delay time is set up locally on the Fire Link interface Please consult the installation sheet for that product for further details 93 530 70 Issue 0 Page 29 of 44 Protec Fire Detection PLC 2007 og Protec 18 0 PSU Monitoring Type Set up It is possible for an engineer at access Level 3 to alter the Power Supply Monitoring type The default choice allows monitoring of the inte
25. ce Peripheral Interfaces Available Fault Diagnosis 0 to 10 minutes programmable applies to all zones programmed for delay 2 or more zones programmable 2 or more zones must activate together to trigger panel A default time out is given if only one coincidence zone activates The time out is the same as the one programmed for zone delays A manual activation on a coincidence zone will also activate the panel 1 or more zones may be programmed non latching Panel resets when cause of the fire is cleared Global fire and fire link outputs if fitted do not activate 1 or more zones can be disabled to prevent faults and activations Alarm Circuits 1 2 and 3 4 can be disabled to prevent faults and activations The fire link PCB if fitted can be disabled to prevent faults and activations The fire link PCB if fitted can be set to have an activation delay 1 or more zones When triggered operates alarm outputs for 4 seconds then resets panel assuming no other non test zone are activated When the Manual Call Point Incorporates a 1800 resistor A zone activated by an automatic detector then silenced can be re triggered by a Manual Call Point Activation Up to eight 3300 Repeat Panels may be connected on the external expansion port to provide full main panel display mimic and allow access to all level 2 functions from remote parts of a site No extra drivers are required to run the repeat panels One Fire Link Interface may be
26. connected to the internal expansion port 8 way zonal fire fault Volt free contact Interface connects to the internal expansion port Comprehensive fault diagnosis features can be accessed at level 3 These give further details of PSU faults Zone Faults Alarm Faults System Faults Fire Link faults Note Due to a policy of continuous improvement Protec Fire Detection PLC reserve the right to alter the specification without prior notice 93 530 70 Issue 0 Page 39 of 44 Protec Fire Detection PLC 2007 og Protec 30 0 Appendix 1 Accessories Available for the 3300 The following accessories are available for the 3300 control panel 1 3000 Optical Smoke Detector 3000 OP A high performance optical smoke detector 2 3000 Optical Heat Detector 3000 OPHT A high performance thermally enhanced optical smoke detector designed to give higher immunity against false alarms 3 3000 Heat Detectors 3000 TEMP56 64 and 84 Three high performance heat detectors The TEMP56 provides anticipatory rate of rise action with a final set point of 56 degrees C The TEMP64 is a fixed set point unit with a trip level of 64 degrees The 84 is a high temperature device with a fixed trip level of 84 degrees 4 53000 Base 3000 BASE A base with in built low Voltage drop diode for use with all the detector products mentioned above 5 3300 Manual call point 3100 BGK A Manual Call P
27. delines on how to rectify the faults 93 530 70 Issue 0 Page 35 of 44 Protec Fire Detection PLC 2007 og Protec 26 0 Power Supply Fault Details The 3300 will display any current power supply faults if the Power Supply Fault indicator is illuminated when in fault diagnosis mode Display row 1 gives details of the power supply fault as detailed in figure 26 0 Figure 26 0 Details of Power Supply Fault Information Fire Zones Ooo o oo oO oD 1 2 3 4 5 6 7 8 212122224020 Fault Disablement Test Zones Disablements Supply Fire Link Level2 General Output General Alarm Fire Present Operated Accessed Test Delay Disablement Outputs Link Faults oG O Oe 000 Alarms General System Alarm Power Fire Aux Repeat Silenced Fault Fault Fault Supply Link 24v Panel Fault Fault Fault Fault Zone 1 indicator will be illuminated if the battery charge voltage is too high Zone 2 indicator will be illuminated if the battery charge voltage is loo low Zone 3 indicator will be illuminated if the battery is faulty or has been removed Zone 4 indicator will be illuminated if the battery has reached its deep discharge level Zone 5 indicator will be illuminated if the mains has failed to the charger All the zone indications will be illuminated if the communication channel to the power supply has failed Please see section 27 0 for guidelines on how to rectify the faults
28. e 15 055 40 93 530 70 Issue 0 Page 6 of 44 Protec Fire Detection PLC 2007 og Protec 4 0 Cabling Requirements 4 1 Detector Alarm and Auxiliary Wiring All external wiring associated with the system must conform to the current Regulations and cabling must conform to the relevant BS specifications ECA recommended Cable Separation for Electromagnetic Compatibility in Buildings must be followed To comply with EMC regulations Protec recommends the use of screened cabling throughout the installation The screens must be securely connected to the screwed earthing studs provided inside the 3300 enclosure Screened cables that are suitable for wiring are MICC Pyro Pirelli FP200 FireTuff or any other cable which complies with BS 6387 categories C W Z Proper glanding of the cable is vital to the correct performance of the system 4 2 Mains Wiring The 3300 requires a mains supply exclusive to the panel that uses fixed three core wiring between 0 75mm and 2 5mm which is fed from a double pole isolating fused spur fused at 3A Unauthorised operation of the mains supply should not be allowed and the fused spur should be labelled FIRE ALARM DO NOT SWITCH OFF 93 530 70 Issue 0 Page 7 of 44 Protec Fire Detection PLC 2007 og Protec 5 0 Installation Procedure The 3300 fire alarm panel circuit boards are housed in a plastic enclosure When the front is removed from the pa
29. e 3300 user manual The procedure for programming a zone delay is given below 1 From access level 1 enter the 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Scroll to the Output Delay indicator by repeatedly pressing button 2 Any currently programmed zone delays will be displayed on row 1 of the display Accept the option by pressing button 3 3 The Output Delay indicator will flash to indicate this option has been accepted 4 Scroll to the detector zone to be delayed by pressing button 2 5 Press button 1 to set delayed not delayed for that zone The row 1 indicator will be illuminated when the zone is delayed 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the delayed zones and return to access level 2 The yellow Output Delay indicator will be illuminated steady showing that at least one zone or the fire link interface if fitted has a delay programmed 93 530 70 Issue 0 Page 22 of 44 Protec Fire Detection PLC 2007 og Protec 14 4 Programming Zones into Test Mode The 3300 can have one or more of its detector zones programmed into test mode When a zone is programmed into test mode any activation on that zone will cause the alarm outputs to activate for 4 seconds after which the 3300 will reset This feature is used to enable rapid tes
30. es Figure 12 1 Installation of 3300 Standby batteries shown with 3300 lid removed 25060006 68060606 6000060060009000090900060606 i O O 0000 OG 0 6 O oO O O O O O 000000 Q Oo 0 0 0 0 0 0 J 12 3 Switching On Switch the fused isolator to the ON position The Supply Present indicator should illuminate on the front of the panel and assuming all other connections are correct and the end of line units are present and the correct value no other faults should be displayed The 3300 is now ready to be programmed 93 530 70 Issue 0 Page 17 of 44 Protec Fire Detection PLC 2007 og Protec 13 0 Programming Overview The 3300 has many programming features making it extremely flexible These can be accessed by users at different authorisation levels The programming features and authorisation levels are detailed below 13 1 Access Levels Access Level 1 User code not entered The panel s front panel display indicators are visible providing a clear status of the 3300 at that time The functions that may be performed at access level 1 are e Muting of the panel s internal buzzer e Entry of the 5 digit user code to access level 2 functions Access Level 2 User code entered Only authorised use
31. es are removed from test mode when testing of the system is complete 93 530 70 Issue 0 Page 23 of 44 Protec Fire Detection PLC 2007 og Protec 14 5 Programming Coincidence Zones With the 3300 it is possible to program two or more zones as coincidence zones This mode is useful on sites where the consequence of a false alarm is onerous for example if the panel is connected to an extinguishing system If only one coincidence zone activates the panel will flash the relevant zone indicator fast intermittently sound the internal sounder and wait for one of the following to occur e Asecond coincidence zone to activate e Anin built 2 minute time out on the first coincidence zone to expire e Amanual call point activation any non disabled zone to occur The 3300 will then activate its alarm outputs global fire contacts and fire link interface if fitted If the cause of the first activation is found to be legitimate the Sound Alarms button can be pressed at access level 2 or 3 to activate the alarm outputs If the cause is found to be a false alarm the Silence Alarms then Reset Panel buttons can be pressed The procedure for programming a zone into a coincidence group is given below 1 From access level 1 enter the 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Scroll to the Level 2
32. esent rated Accesse elay pamant ou Link O O O O O O O O Alarms General System Alarm Power Fire Aux Repeat Silenced Fault Fault Fault Supply Link 24 Panel Fault Fault Fault Fault 93 530 70 Issue 0 Page 26 of 44 Protec Fire Detection PLC 2007 og Protec 15 0 Overriding System Delays It is possible for the authorised user at access Level 2 or 3 to override any delays zonal or fire link that may have been set up at access level 3 The procedure to do this is as follows 1 From access level 1 enter your 5 digit user code 1 4 4 2 or turn the key switch depending on the model purchased 2 The Level 2 Accessed indicator will illuminate 3 Using button 2 scroll to the Alarm Outputs indication Any current setting in this option will be displayed on row 1 of the display on zone 3 Accept this option by pressing button 3 4 The Alarm Outputs indicator will flash showing this option has been accepted 5 Select the delay override option by pressing button 2 until the row 2 indicator for zone 3 is illuminated 6 Press button 1 to show that delays are no be overridden not overridden The row 1 zone 3 indicator will be illuminated if delays are overridden 7 Press button 3 to return to the selection menu 8 Press button 4 to accept and program the set up and return to access level 2 9 The Output Delay indicator will be extinguished All delays zonal and fire link are now
33. g insulation tests could be damaged with the high voltages used during the test e Field devices and the 3300 MUST NOT be connected when high voltage insulation tests are being performed on the cabling the cabling must be completely discharged prior to connection to any field devices or the 3300 7 0 Detector Circuit Connections Figure 7 0 shows a typical connection regime for a detector zone on the 3300 Figure 7 0 Typical 3300 Detector Connection Zone _ Connection Manual Call Point e Ensure the length of the zone wiring is no more than 500 metres e Ensure the resistance of each conductor is no more than 15Q e Ensure the capacitance of the zone wiring is no more than 0 27uF micro Farads when no end of line capacitor is present e end of line unit 8k2 resistor or 100uF 220 network must be placed at the very end of the detector zone wiring ensuring the whole zone is monitored e Spurs should not be connected from the zone wiring as the spur will not be monitored for open circuit faults e To ensure compliance with EN54 Part 2 each detector base must include a series low voltage drop diode such that manual call points following a removed detector still function correctly Protec S3000 bases incorporate the diode as standard e Manual call points must incorporate a series resistor to ensure the zone does not enter a short circuit fault condition when the manual call point is activated If the panel is to be able
34. git engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Scroll to the Fire link indicator within the disablements section by repeatedly pressing button 2 Any node information currently programmed will be displayed on row 1 of the display Accept the option by pressing button 3 3 The Fire Link indicator will flash to indicate this option has been accepted 4 Using button 2 and button 1 enter the number of system nodes present in a binary format The zone 8 indicator is the least significant bit of the number and the zone 4 indicator is the most significant bit Please consult Appendix 3 for clarification of decimal to binary conversion Note The number of nodes must include all nodes on the external expansion port and any nodes on the internal expansion port For example if the 3300 has two repeat panels on its external expansion port and one fire link Interface on its internal expansion port the total number of nodes entered would be three 5 Press button 3 to return to the selection menu 6 Press button 4 to accept and program the expansion set up and return to access level 2 Figure 14 1 Example of programming 5 nodes into the 3300 Fire Zones OO O O 04908 1 2 3 4 5 6 7 8 lO O O O O O O Fault Disablement Test Zones O Oq Supply Level General Quip ut Pr
35. ily touching a solid earth point a non painted part of a radiator for example Handle the PCBs by their sides and DO NOT touch the electronic components on them The PCB should be stored a clean dry place away from the place of work Retain the PCBs in a cardboard box for safety until they are required Disconnect the 3 way connector from the main PCB taking care not to strain the connector or the PCB Leave the connector attached to the Power Supply PCB Unscrew and remove the two mounting screws on the main PCB Carefully slide the Main PCB upward stage 1 and lift away from the plastic enclosure stage 2 See figure 5 1 Store all screws and PCBs in a safe dry place Figure 5 1 Removal of the 3300 Main PCB w Stage 2 PCB fixing screw 3 way power connector PCB fixing screw 93 530 70 Issue 0 Page 9 of 44 Protec Fire Detection PLC 2007 og Protec 5 Preparing and Fixing the Panel Back box The mains cable entry position should be kept away from other system cabling Carefully knock out the required cable entry positions and mount the enclosure at the position prepared in 2 whilst feeding the cables into the enclosure 6 Refitting the Main PCB Note Before re fitting the main PCB the mains power connections to the Power Supply PCB should be connected See section 12 0
36. ion See sections 15 0 and 16 0 for details 6 Press button 1 to show that it is to be disabled not disabled If the alarm circuit is disabled the relevant row 1 indicator will be illuminated 7 Press button 3 to return to the selection menu 8 Press button 4 to accept and program the disablement set up and return to access level 2 9 The yellow General Disablement indicator will be illuminated steady as will the yellow Alarm Outputs indicator 93 530 70 Issue 0 Page 21 of 44 Protec Fire Detection PLC 2007 og Protec 14 3 Programming Zone Delays The 3300 can have a delay programmed on one or more of its detector zones When a zone delay is programmed a fixed time delay 0 to 10 minutes is given from activation of that zone to activation of the alarm outputs global fire relay and fire link output if fitted However a manual call point activation on a delayed zone will override the delay The delay time is set by adjusting a potentiometer VR1 on centre of the Main PCB See appendix 4 for the location of the potentiometer If the Silence Alarms button is pressed while a delay is running the alarm outputs will not be activated when the delay expires The global fire contacts however will still be activated Note e delay time applies to ALL zones programmed with delays e The exact delay time should be verified during commissioning and noted on the system set up record in th
37. ll programming features are available 2 Using button 2 scroll to the Alarm Outputs indication Any current settings in this option will be displayed on row 1 of the display on zone 7 Accept this option by pressing button 3 3 The Alarm Outputs indicator will flash showing this option has been accepted 4 Select the EOL selection option by pressing button 2 until the row 2 indicator for zone 7 is illuminated 5 Press button 1 to select either capacitive monitoring row 1 zone 7 not illuminated or resistive monitoring row 1 zone 7 illuminated 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the set up and return to access level 2 93 530 70 Issue 0 Page 30 of 44 Protec Fire Detection PLC 2007 og Protec 20 0 Programming Pulsing Alarms The alarm circuits 3 and 4 be programmed to pulse 0 55 on 0 55 off when a zone delay is expiring 1 From access level 1 enter your 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Using button 2 scroll to the Alarm Outputs indication Any current settings in this option will be displayed on row 1 of the display on zone 8 Accept this option by pressing button 3 3 The Alarm Outputs indicator will flash showing this option has been accepted 4 Select the Pulsing Alarms op
38. nders will result in an alarm circuit fault All Protec S3000 sounders are polarised and suppressed as standard e Efforts should be made to evenly spread the sounder load across the 4 alarm circuits to avoid overloading any one of the alarm outputs e It is acceptable to connect alarm circuits 1 2 or alarm circuits and 4 in parallel to obtain drive rating of 300mA continuous however the end of line resistor value must be changed to 4k7Q 1 2W 5 This is detailed in figure 8 1 Figure 8 1 Enhanced Alarm Circuit Drive Details Alarm Circuit 1 2 or 3 4 Connection Polarised Sounder Polarised Sounder Polarised Sounder 93 530 70 Issue 0 Page 12 of 44 Protec Fire Detection PLC 2007 og Protec 9 0 Auxiliary Input and Output Wiring The auxiliary input connections Keyswitch Remote Alarm and Class Change and auxiliary output connections Global Fault and Global Fire should be wired in screened cable The screen should be securely connected to the screwed earthing post provided in the panel 9 1 Keyswitch Input The keyswitch input is active when a short circuit less than 500 is connected across the keyswitch terminals In the standard 3300 this is an alternate method of accessing level 2 functions if the code entry feature is not required The keyswitch wiring should be kept local to the 3300 9 2 Remote Alarm Input The remote alarm input is active when a short circuit less than 500 is placed
39. nel the circuit boards and the batteries are fully accessible The panel can still be controlled even though the front has been removed The panel can be surface or flush mounted The panel must be located internally in an area that is not subject to dampness extremes of temperature or physical abuse The environmental limits are given in section 21 0 1 2 3 Unpacking After opening the box remove the installation template and spares pack from the packaging leaving the 3300 in the cardboard box for protection Preparing the Mounting Position Use the installation template in conjunction with a spirit level to mark out the fixing locations for the panel Drill and plug the mounting holes previously marked Removal of the Door Remove the 3300 unit from the packaging Remove the two screw covers from the lower two corners of the front door and unscrew the two front door fixing screws Swing the door upward from the bottom and lift away see figure 5 0 Put all removed parts in a safe dry place Figure 5 0 Removing the door from a 3300 gt ID 93 530 70 Issue 0 Page 8 of 44 Protec Fire Detection PLC 2007 og Protec 4 Removal of the Main PCB NOTES ON ANTI STATIC HANDLING OF THE PCBs Before handling any of the circuit boards in the 3300 it is vital that any operatives discharge themselves of any static charge that may have built up on them This can be done by momentar
40. nnnnnnvnnnnnnnnnnvnnnnvnnnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnr 30 93 530 70 Issue 0 Page 3 of 44 O Protec Fire Detection PLC 2007 og Protec 19 0 20 0 21 0 22 0 23 0 24 0 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 PROGRAMMING END OF LINE TYPE sernnvnnnvvnnnvnnnvnnnvnnnvnnnvnnnvennnennnnnnnennnennnnnnnnnnnnennnnnnnennnvennvenee 30 PROGRAMMING PULSING ALARMNS U u uuu uuu u 31 FAULT DIAGNOSIS FEATURES UU UU UU IIT 31 3300 SOFTWARE VERSION DISPLAY i rnnvennvennnvrnnvrnnvnnnvennnennnvnnnvnnnvennvnnnvennvnnnnnnnnernnennnennnnennnnnr 32 DETECTOR ZONE FAULT DETAILS T u 33 ALARM FAULT DETAILS sne 34 SYSTEM FAULT DETAILS 35 POWER SUPPLY FAULT DETAILS 1 36 FAULT RECTIFICATION GUIDELINES uu uu uuu uuu u 37 3300 TECHNICAL SPECIFICATION u uuu uu uuu 38 3300 FEATURES SPEGIFIGATION uu uu uuu u u 39 APPENDIX 1 ACCESSORIES AVAILABLE FOR THE 3300 40 2 3300 naanin aiaia 41 APPENDIX 3 DECIMAL BINARY CONVERSION CHART
41. oint Unit with built in 1800 resistor 6 3000 Sounder Base 3000 SB A high output 24V powered sounder base that accepts a detector 7 3000 System Sounder 3000 SSR2 A high output low current 24V powered system sounder 8 3000 System Sounder Beacon 3000 SSR2 LED R A high output low current 24V powered system sounder with integral LED beacon array 9 3300 4 Wire Repeat Panel 3300 RP This unit is designed to be connected to the 3300 external expansion port up to eight repeat panels may be connected Each repeat panel must be configured with its own node number by a DIL switch on the PCB 10 3300 Fire Link Interface 3300 FL This unit is designed to be connected to the 3300 internal expansion port One fire link PCB may be fitted into a 3300 control panel The 3300 Fire Link Interface gives a monitored output to a fire station call unit The interface must be allocated a unique node number on the 3300 expansion system using the on board DIL switch on the fire link PCB The 3300 fire link interface must be used in conjunction with a 3300 Fire Link End Of Line unit 3100 FLEOL 93 530 70 Issue 0 Page 40 of 44 Protec Fire Detection PLC 2007 Protec 31 0 Appendix 2 3300 Spares List Description Protec Stock Code Capacitive end of line module 41 804 52 10kQ alarm end of line resistor 41 800 48 1 6A F battery fuse 15 055 40 1A HRC mains fuse 15 131 35 3300 accessory pack all of above 62 602 55 Red ba
42. rnal switchmode charger the alternative choice allows monitoring of the 3300 Dual Supply Interface fitted when an external charger is used 1 From access level 1 enter your 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Using button 2 scroll to the Alarm Outputs indication Any current settings in this option will be displayed on row 1 of the display on zone 6 Accept this option by pressing button 3 3 The Alarm Outputs indicator will flash showing this option has been accepted 4 Select the PSU monitoring option by pressing button 2 until the row 2 indicator for zone 6 is illuminated 5 Press button 1 to select either Internal Charger monitoring row 1 zone 6 not illuminated or Dual Supply Interface row 1 zone 6 illuminated 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the set up and return to access level 2 19 0 Programming End of Line Type The 3300 end of line monitoring type is programmable The standard type of monitoring is capacitive 100 amp 220 The alternate type of monitoring is resistive 8 20 5 and is used to allow the 3300 to be interfaced to existing installations 1 From access level 1 enter your 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and a
43. rs are permitted access to level 2 functions these are e Silencing an alarm condition e Sounding the alarms e Resetting the panel after an alarm activation e Testing the front panel indications and internal buzzer e Programming a zone into test mode only one test zone at once is permitted e Disablement of detector circuits e Disablement of alarm circuits e Disablement of any programmed delays detector and fire link e Disablement of the fire link interface if fitted 93 530 70 Issue 0 Page 18 of 44 Protec Fire Detection PLC 2007 og Protec Access Level 3 Engineer Controls Only engineers are permitted access to level 3 functions these are e All level 2 functions plus e setting of zone delay times e The programming of delayed zones e The programming of coincidence zones e The programming of non latching zones e The programming of test zones one or more zones may be programmed e programming of expansion interface data e Fault diagnosis features e Programming the end of line type e Programming the power supply type 13 2 Zone Programming Choices Each zone of the 3300 may be programmed in the following manner e Non latching mode e Coincidence mode e Delay mode e Test mode Please not that a zone can only be programmed with one of the choices ie a zone cannot be set up as non latching and delay the last programmed choice will be accepted by the 3300
44. s no extra driver board is required e All interfaces supported as standard e Low quiescent current of 15mA 24V dc supply mains fail fault no external equipment Note Due to a policy of continuous improvement Protec Fire Detection PLC reserve the right to alter the specification without prior notice 93 530 70 Issue 0 Page 5 of 44 Protec Fire Detection PLC 2007 og Protec 2 0 Important Notes PLEASE READ e THE FIRE ALARM PANEL AND ITS ASSOCIATED CONNECTIONS MUST BE INSTALLED COMMISSIONED AND MAINTAINED BY A SUITABLY SKILLED AND COMPETENT PERSON e THIS EQUIPMENT MUST BE EARTHED THIS EQUIPMENT IS NOT GUARANTEED UNLESS INSTALLED AND COMMISSIONED IN ACCORDANCE WITH CURRENT NATIONAL STANDARDS THIS EQUIPMENT HAS BEEN DESIGNED AND MANUFACTURED TO CONFORM WITH THE REQUIREMENTS OF ALL APPLICABLE EU COUNCIL DIRECTIVES THIS MANUAL MUST BE THOROUGHLY READ AND UNDERSTOOD BEFORE INSTALLATION AND COMMISSIONING OF THIS EQUIPMENT IS UNDERTAKEN 3 0 Items Supplied with the 3300 panel e Installation commissioning and maintenance manual e User manual e Mounting template e Accessory pack comprising 8 x 100uF 22Q detector circuit end of line units 41 804 52 4x 10kQ alarm circuit end of line units 41 800 48 1 x red battery lead 41 791 64 1 x black battery lead 41 790 63 1 x inter battery connection lead 41 796 44 1 x 1A HRC power supply fuse 15 131 35 1 x 1 6A battery fus
45. st Delay Disablement Outputs Link Faults OO 08900009 Alarms General System Alarm Power Fire Repeat Silenced Fault Fault Fault Supply Link 24v Panel Fault Fault Fault Fault 93 530 70 Issue 0 Page 34 of 44 Protec Fire Detection PLC 2007 7 Protec 25 0 System Fault Details The 3300 will display the system fault status of the system if the System Fault indicator is illuminated when in the fault diagnosis menu Display row 1 gives details of current system faults as detailed in figure 25 0 Figure 25 0 Details of System Fault Information Fire Zones OO OO O O O 0 1 2 3 4 5 6 7 8 9 O GO 9 Fault Disablement Test Zones Disablements o eoo Supply FireLink Level2 General Output Gener Alarm Fire Present Operated Accessed Test Delay Disablement Outputs Link Faults OO e O OO O O Alarms General System Alarm Power Fire Aux Repeat Silenced Fault Fault Fault Supply Link 24 Faul Fault Fault Fault Zone 1 indicator will be illuminated if an EEPROM checksum error has been detected Zone 2 indicator will be illuminated if a PROGRAM checksum error has been detected Zone 3 indicator will be illuminated if a WATCHDOG fault has been detected Zone 4 indicator will be illuminated if a SW ERROR fault has been detected Zone 5 indicator will be illuminated if an external or internal interface fault missing faulty node has been detected Please see section 27 0 for gui
46. ting of detectors on zones without the need to return to the panel to reset it after each activation Note e f any non test zones are active the 3300 will not reset e Zones activated in test mode DO NOT operate the Fire Link and DO NOT activate the Global Fire Contacts The procedure for programming a zone into test is given below 1 From access level 1 enter the 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Scroll to the General Test indicator by pressing button 2 Any zones currently programmed into test mode will be displayed on row 1 of the display Accept the option by pressing button 3 3 The General Test indicator will flash to indicate this option has been accepted 4 Scroll to the detector zone to be put into test mode by pressing button 2 5 Press button 1 to set un set that zone into test mode The relevant row 1 indicator will be illuminated when the zone is in test mode 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the test set up and return to access level 2 The yellow General Test indicator will be illuminated steady showing that at least one zone has been programmed into test mode Any zones programmed into test mode will have their test indicator illuminated steady on row 2 of the display Important Note e Ensure all zon
47. tion by pressing button 2 until the row 2 indicator for zone 8 is illuminated 5 Press button 1 to select either non pulsing alarms row 1 zone 8 not illuminated or pulsing alarms row 1 zone 8 illuminated 6 Press button 3 to return to the selection menu 7 Press button 4 to accept and program the set up and return to access level 2 21 0 Fault Diagnosis Features The 3300 incorporates comprehensive fault diagnosis features designed to aid the service engineer in locating faults on a 3300 system The fault diagnosis menu is reached by 1 From access level 1 enter your 5 digit engineer code 1 3 4 2 4 The Supply Present indicator will flash indicating level 3 has been accessed and all programming features are available 2 Press button 3 to enter the fault diagnosis menu 2 Using button 2 scroll through the various fault menus each time a fault is selected a code will be displayed on rows 1 and 2 of the display Using the following sections the code can be decoded and appropriate action taken 3 Return to access level 2 by pressing button 4 4 Return to access level 1 by pressing button 4 again 93 530 70 Issue 0 Page 31 of 44 Protec Fire Detection PLC 2007 og Protec 22 0 3300 Software Version Display The 3300 will display its software versions when the Alarms Silenced indicator is illuminated in fault diagnosis mode Display row 1 will display the main software version Display row
48. ttery lead 41 791 64 Black battery lead 41 790 63 Battery inter connection lead 41 796 44 3300 User Manual N93 531 79 93 530 70 Issue 0 Page 41 of 44 Protec Fire Detection PLC 2007 PLA Protec Fire Detection plc 32 0 Appendix 3 Decimal to Binary Conversion Chart 0 00000000 49 00110001 98 01100010 147 10010011 196 11000100 1 00000001 50 00110010 99 01100011 148 10010100 197 11000101 2 00000010 51 00110011 100 01100100 149 10010101 198 11000110 3 00000011 52 00110100 101 01100101 150 10010110 199 11000111 4 00000100 53 00110101 102 01100110 151 10010111 200 11001000 5 00000101 54 00110110 103 01100111 152 10011000 201 11001001 6 00000110 55 00110111 104 01101000 153 10011001 202 11001010 7 00000111 56 00111000 105 01101001 154 10011010 203 11001011 8 00001000 57 00111001 106 01101010 155 10011011 204 11001100 9 00001001 58 00111010 107 01101011 156 10011100 205 11001101 10 00001010 59 00111011 108 01101100 157 10011101 206 11001110 11 00001011 60 00111100 109 01101101 158 10011110 207 11001111 12 00001100 61 00111101 110 01101110 159 10011111 208 11010000 13 00001101 62 00111110 111 01101111 160 10100000 209 11010001 14 00001110 63 00111111 112 01110000 161 10100001 210 11010010 15 00001111 64 01000000 113 01110001 162 10100010 211 11010011 16 00010000 65 01000001 114 01110010 163 10100011 212 11010100 17 00010001 66 01000010 115 01110011 164 10100100 213 11010101 18 00010010 67 01000011 116 01110100 165 10100101 214 110101