Instruction manual Hx5xxR
Contents
1. 1 General safety rules The following summary is designed to prevent injury hazards or device damage Operate the instrument in accordance with this manual to prevent electric trauma Service should be performed by a qualified person only Use a safety ac dc adapter Use only an adapter with the power voltage recommended by its manufacturer and which is approved by proper standards Check that the adapter has undamaged cables and cover Connect and disconnect correctly Do not connect and disconnect a LAN cable or lead in cables if the device is under electric voltage Do not use the instrument without the cover Do not use the instrument if it does not work correctly If the instrument seems not to work correctly have it checked by a qualified service person Do not use the instrument in an explosive environment Read instruction manual before the first device connection please 4 IE HGS HX531R 07 2 General description Monitoring systems of Hx531R line are designed for online monitoring of temperature in C or F relative humidity of air without aggressive ingredients barometric pressure and three binary inputs for detection of binary signals Measured temperature and relative humidity are recomputed to following humidity expression dew point temperature absolute humidity specific humidity mixing ratio and specific enthalpy It 1s possible to set correction for altitude pressure offset and to choose one of the follow
2. Signalization of binary inputs status LED diode lights if input contact is open Acoustic alarm Ore 6 1 Installation procedure e run TSensor software default monitoring system IP address is 192 168 1 213 or use command line at PC with command telnet 192 168 1 213 9999 Telnet provides to set all Ethernet services For setting of measurement and controlling of output relays use keys see chapter 9 4 e assign new device IP address make your own device setting by your requirements alarm settings used units email and trap sending e save setting 10 IE HGS HX531R 07 7 Operation checking 7 1 Visual check When power source is on there are actually measured values shown on LCD display if the LCD has not been switched off When Ethernet cable is connected there is one light on its connector lighting 7 2 Communication check via a LAN Open a browser of www pages and enter the devices IP address into appropriate field Example http 192 168 1 213 Monitoring system shows its name serial number measured values alarm status and alarm settings or shows message Access denied in case of web pages are disabled or setting through Telnet is in operation IE HGS HX531R 07 11 8 Description of device function and setting Information from device is available directly through LCD or you can read them with one of next communication protocols For communication through some communication protocol SNMPv1 Modb
3. OFF 34 IE HGS HX531R 07 SD 280 optical smoke detector This device 15 designed to detect the presence of fire inside residential or commercial buildings 12V TMP ALARM n n TE DIP OFF Notice The connecting cables should be located as far as possible from the potential interference sources The cable shield connect to Shield terminal of regulator only IE HGS HX531R 07 35
4. h 0 363 to 9 427 PSI 18 8 to 487 5 mmHg 0 74 to 9 19 inHg 10 0 to 261 0 25 0 to 650 0 mBar 2 5 to 65 kPa Show temperature at LCD display This item provides to choice if actual measured temperature may be displayed at LCD display or not It is possible to change it after SET key pressing show value on LCD don t show value on LCD E VI E UL d Un Show relative humidity at LCD display This item provides to choice if actual measured relative humidity may be displayed at LCD display not It is possible to change it after SET key pressing show value on LCD don t show value on LCD on C2 d Un IE HGS HX531R 07 17 Show computed value at LCD display This item provides to choice if actual computed value may be displayed at LCD display or not There is shown the name of computed value on the top LCD line see Computed value selection below It is possible to change it after key pressing show value on LCD don t show value on LCD dP dP d Un Show barometric pressure at LCD display This item provides to choice if actual barometric pressure may be displayed at LCD display or not It is possible to change it after SET key pressing show value on LCD don t show value on LCD Pre d un Computed value selection It shows the actually selected computed value name It is possible to change it after SET key
5. noo EUR o Ge Ev PoS eras is 28 IE HGS HX531R 07 IZ PREVENTIVE MAINTENANCE wisciccccccssccscccscecsisccasssssesscssdeseseosscenssccsosenes 29 13 TECHNICAL SPECIFICATION tese 30 TECHNICAGPARAMETER Ia mad ded dun 30 30 13 1 2 Accuracy range and resolution of monitoring 5 eene 30 13 1 3 Value computed from measured relative humidity and temperature ees 32 13 2 OPERATING CONDITIONS ia audet 33 19 35 TION iucundius victa E 33 134 TECHNICALSUPPORT AND SER 33 14 APPENDIX e In 34 15 APPENDEX Diano aO EP Dm PII i 34 Models marked HxxxxZ are non standard versions of the devices Description is not included in this manual Copyright COMET System Ltd It is prohibited to copy and edit this instruction manual and make any changes at all without explicit agreement of COMET System Ltd All rights reserved COMET System Ltd makes constant development and improvement of all its products That is why it reserves the right to make any technical changes on the device product without previous notice IE HGS HX531R 07
6. pressing There is possible choice one of the following computed values dew point temperature absolute humidity mixing ratio specific humidity SEL SEL SEL SEL dP Hb 5H r Hk GPcH specific enthalpy JEL SP ce 18 IE HGS HX531R 07 8 5 Restore to Factory default measurement part This item provides device restoring to factory setting Press SET key select YES and confirm it by pressing of key It reset regulator parameters to following values Value assigned to relay 1 and relay 2 none Password for setting through keys PASS 0000 Display on Temperature unit E Pressure unit hPa Correction for altitude O hPa absolute pressure Computed value preset dew point temperature Relay response for error stay unchanged at previous condition Signalization of binary inputs status LED diode lights if input contact LS open Acoustic alarm off restore to factory default dEF dEF no YES 8 6 Monitoring system configuration Ethernet interface The Ethernet configuration is performed by TSensor software or Telnet setup Setting through the Telnet is described in separated document Access to the Setup can be protected by a password TSensor program you can find on manufacture web http www cometsystem cz or on installation CD This program is free for use and supports firmware update too The newest firmware is available at web pages too 8 7 Alarms Ethernet int
7. 2 m 00008 8 r status word described below Int 000071 7 r firmware version Hi BCD 0 3001 1289 r firmware versionLo BCD 0 3002 1290 r RH hysteresis temperature alarm status ASCI Ox500D 20493 RH alarm status ASCIP Ox500E 2044 22 IE HGS HX531R 07 Variable Unit Format pud ip Status hex dec computed value alarm status ASCII 0x500F 20495 CV depen 5010 20496 d 0 2 upper pressure limit CV depend 0 5011 20497 CV depend 0 5012 20498 E 5 0 S S S pressure limit status pressure time delay relay 1 alarm status _ uw Ld MN KE a 03015 20501 r relay 2 alarm status ASCIP 055016 20800 r binary input 1 alarm saus ASC 015017 20808 r binary input 2 alarm status ASC 20504 r binary input alarm status ASC 0 509 20808 r binary input I time delay ht 0x501A 20800 Ww bmaryimpu2 medeay _____ s 0 501 20507 mw a binary input 3 time delay Ox501C 20508 rw r r w r w r w r r w r r r r r r w r w r w register 15 designed for read e register is designed for write Int 10 register 1s in format of integer 10 1 register is in format o
8. error during pressure sensor initialization Under this condition device does NOT measure atmospheric pressure Value read from device is 999 9 Pressure sensor is probably damaged It is a serious error contact distributor of the device Error 5 6 There is problem with assigned value to output relay there is some wrong setting mismatch This error appears if incorrect writing procedure to device s memory occurred Error 9 Inserted password 15 not valid there is shown for short time message Err9 on LCD display Try to insert password again If you forgot the password see chapter Change of Password for setting through keys PASS at page 16 IE HGS HX531R 07 24 11 Readings LCD display C oF RH hPa PSI C F DP g m g kg reading next to this symbol is measured temperature or error state of value reading next to this symbol is measured relative humidity or error state of value reading next to this symbol is measured pressure or error state of value If selected pressure unit 15 mBar or oz in or mmHg or inH O or kPa there is shown only value number without corresponding pressure unit reading next to this symbol 15 calculated dew point temperature or error state of value reading next to this symbol 15 calculated absolute humidity or error state of value reading next to this symbol is calculated specific humidity or mixing ratio depends on device setting or error state of value I
9. for relay outputs external sensors and detectors binary inputs temperature humidity probe H4531R Output BIN1 U1 BIN2 U2 BIN3 U3 relay outputs external Pt1000 temperature probe It is NOT recommended to use the device for long time under condensation conditions It could be the cause of water steam condensation inside the sensor s cover into water phase This liquid phase stays inside sensor s cover and can t escape from the cover easily It can dramatically increase response time to relative humidity change If water condensation occurs for longer time it can cause sensor damage Similar effect can occur under water aerosol conditions External temperature probe connectable to H4531R must be type of two wires with shielding The probe cable length and size of conductor affects measurement accuracy If connected probe is equipped with metal stem we recommend using probes with metal stem not connected to cable shielding Or else it is necessary to arrange metal stem is not connected to any other circuitry power supplies for external sensors and detectors binary inputs Binary inputs are designed for dry contact or external voltage connection see picture external voltage open collector contact binary input BIN1 U1 E DIP ON DIP OFF DIP OFF 6 IE HGS HX531R 07 The maximal length of binary inputs and external Pt1000 temperature probe H
10. input signal wiring shielded max 10 m long cable should not be led in parallel along power cabling Power output 12 V and 5 V for powering of external sensors and detectors Total load max 5 W 12 V max 400 mA 5V max 500 mA EMC EN 61326 1 EN 55011 EN55022 13 1 2 Accuracy range and resolution of monitoring systems Temperature H3531R H4531R H7531R 0 4 C 0 7 F 0 2 0 4 F 0 4 C 40 7 F 30 to 105 C 22 to 200 to 600 C 30 to 105 C 22 to 221 F includes probe 328 F to 998 6 F 221 F includes probe cable cable 0 1 C 0 2 F 0 1 C 0 2 F 0 1 C 0 2 F 30 IE HGS HX531R 07 Relative humidity a H3531R H4531R H7531R accuracy 2 5 RH from 5 to 95 2 5 from 5 to 95 RH at 23 C 73 4 F RH at 23 73 4 F 0 to 100 0 to 100 0 1 ____ 04 Barometric pressure H7531R Unit _______ hPa PSI mmHg inHg inE O ozin kPa Pange 1926000 accuracy __ 930 care 9 Response time with stainless steel mesh sensor cover F5200B and bronze sensor cover FOOOO selectable option air flow approximately m s temperature t90 lt 9 min temperature step 20 C 36 F relative humidity 190 lt 30 5 humidity step 65 RH constant temperature pressure 190 44s Measuring temperature and humidity range is limited in accordance w
11. kg Mixing ratio Accuracy 2g kg at ambient temperature T lt 35 C 95 F Range 0 to 995 g kg Specific enthalpy Accuracy 3kJ kg at ambient temperature T lt 25 C 77 F Range 0 to 995 kJ kg 13 2 Operating conditions Operating temperature and relative humidity electronics 30 to 80 C 22 to 176 F 0 to 100 RH without condensation probe H3531R H7531R 30 to 105 C 22 to 221 F probe cable included 0 to 100 RH external probe for HA531R by probe type not included It is recommended to switch off the LCD display at ambient temperatures above 70 158 F around electronics Outer characteristics in accordance with Czech National Standard 33 2000 3 Normal environment with the specifications AEI ANI ARI BEI Not allowed manipulations It is not allowed to operate the device under conditions other than specified in technical parameters Devices are not designed for locations with chemically aggressive environment Temperature and humidity sensors must not be exposed to direct contact with water or other liquids It is not allowed to remove the sensor cover to avoid any mechanical damage of the sensors Dimensions see dimensional drawing Weight approximately H4531R 1025 H3531R 1m probe H7531R 1m probe 1090 H3531R 2m probe H7531R 2m probe 1100 H3531R 4m probe H7531R 4m probe 11302 13 3 of operation Device itself after its life is necessary to liquidate ecologic
12. too This procedure is described at file Calibration manual pdf which is installed commonly with the software 8 4 2 Setting with using monitoring system keys If Actual monitoring system preset is displayed see chapter Actual monitoring system preset measurement part at page 12 it 1s possible to enter into edit mode and edit displayed value by pressing key Then you are asked for valid password PASS If password is not valid there is shown for short time message Err9 on LCD You can edit selected value if right password 15 entered During value editing there 15 range check executed and edited value 1s still compared with limits for corresponding value range If inserted value 1s higher or lower then edited number 15 automatically changed to its maximum minimum value for possible range see chapter Technical parameters at page 30 Value can be changed with using and wv keys Edited value is switched in round 9 8 7 2 1 0 1 2 8 9 To edit next number digit press 5 key for moving back to previous digit press ESC key Edited value is stored by next SET key pressing It is possible to cancel editing by pressing ESC key if necessary If valid password is once inserted right then there 1s possible to edit next items without asking for password insertion again till Actual monitoring system preset 1s left till actual measured values are shown
13. 4531R only 15 10 m Connect probe cable shielding to proper terminal and do not connect it to any other circuitry and do not ground it The cables for binary inputs and external sensor must be placed as far as possible from potential interference sources It 15 possible to connect optionally accessory for more information see www cometsystem cz Method of connection 15 shown in Appendix B of this document Electrical system wiring may be done only by a worker with required qualification by rules in operation IE HGS HX531R 07 4 Preparation to operation To provide all Hx531R monitoring systems functions it is necessary to make its setting through PC to satisfy your requirements Requested parts necessary for operation ac dc adapter 12V RJ 45 LAN connection free IP address in your network temperature probe with a Pt1000 sensor for the H4531R monitor Contact network administrator to get free IP address Warning Reliability of warning messages reception e mail trap depends on current accessibility of required network services It is recommended to protect device from unauthorized access to device settings and cables connection 4 1 Procedure of instrument connection The cables and temperature probe for H4531R connect in order as shown in the pictures After power supply connection make monitoring system configuration Connection of H3531R and H7531R Connection of H4531R Pt1000 8 IE HGS HX531R 07 PoE
14. LED diodes This option defines at which binary input status should LED diode indication lights LED diode lights if binary input is OPEN CLOSED LED lights if binary input is OPEN LED lights if binary input is CLOSED UPEn LLU Temperature unit choice It is possible to measure temperature at C or F There is shown preset unit It is possible to change it after key pressing preset to C preset to F 16 IE HGS HX531R 07 Barometric pressure unit choice It 1s possible to measure barometric pressure at hPa PSI inHg mBar oz in mmHg inH O and kPa There is shown preset unit It is possible to change it after key pressing preset to hPa preset to PSI preset to inHg preset to mbar PrES PrES 5 5 H3 hPR nbHr preset to oz in preset to mmHg preset to preset to kPa 05 Setting of pressure correction for altitude If is there necessary to read value of barometric pressure corrected with respect to altitude it 15 possible to set corresponding pressure offset for this altitude It is possible to change it after SET key pressing Pressure correction value is then automatically added to measured pressure value See chapter Error States of the device at page 26 Error 2 correction for altitude pressure correction value is from hPa 25 0 to 650 0 hPa 5 8 to 150 8 oz in H
15. Rack mount environment monitor H3531H H4531R H 531R Monitoring of temperature humidity barometric pressure and other derived humidity values with Ethernet interface Instruction Manual Table of content EY M nl ee 10 4 GENERAL SAFETY RULES aae eee NEM Ive eene Eel 4 GENERAL DESCRIPTION 5 MONITORING SYSTEM MOUNTING AND CONNECTION 6 PREPARATION TO OPERATION 1 ceccccccccccccccccccccccccccccccccccecs 8 PROCEDURE OF INSTRUMENT CONNECTION cccsccsccsceccscecceccecsceccscescescscescescscesceces 8 DIMENSIONJS 9 INSTALLATION aa 10 INSTALLATION PROCEDURE 5 3t 10 OPERATION CHECKING 5 icr Ya vea eS Eres erus 11 Ree 11 COMMUNICATION CHECK VIA 11 DESCRIPTION OF DEVICE FUNCTION AND SETTING 12 AY OUTPUTS 12 BINAR INPUT ERN Geena CREER 12 ACTUAL MONITORING SYSTEM PRESET MEASUREMENT 12 MONITORING SYSTEM SETTING CHANGE PART OF MEASUREMENT UNIT 14 Settino WILMA SOTtWAk uses seq
16. With new entering into edit mode it 15 necessary to enter Password again Default password setting 1s preset from manufacturer to 0000 password change is possible into Extended setting During edit mode device still works and changes are valid immediately after its storing After storing the Ethernet part 1s restarted automatically 8 4 3 Extended setting mode During device operation it is possible to change parameters available through Actual monitoring system preset only see chapter 8 3 at page 12 Rest of device parameters are available 14 IE HGS HX531R 07 through Extended setting mode In this mode device does NOT communicate does NOT do any measurements and does NOT service output relays To leave this mode press ESC key and move DIP switch 4 to OFF To enter into Extended setting mode do following steps 1 disconnect power supply 2 move DIP switch 4 to ON you should see small number 3 at left side of LCD 3 press keys together and keep them down 4 connect power supply to device you should see message SEL on the top line of LCD and on the bottom line you should see number of Firmware version e g 0404 5 release and keys you are into Extended setting mode now Use and keys to inspect each items If you want to change some shown item then press SET key item starts blink Now you can edit setting with using and ke
17. ages display disabled screen with message Access denied 9 5 SNTP The device allows time synchronization with SNTP server The time synchronization is set to every 8 hours If the time synchronization failed in next three hours SNTP trap e mail and Syslog message will be sent 9 6 Syslog protocol Device allows send messages to selected Syslog server UDP protocol port 514 Events are described below Event device restart test message alarm occurred SNTP connection error write to device via Modbus SNMP firmware was changed alarm is down SOAP server communication error e mail sending error 9 7 SOAP Device allows sending SOAP messages with measured values to user defined remote web server in preset time intervals 10 65535 s If the device cannot establish connection with the web server in the whole delay interval device sends trap 1 3 1 5 The file with XML schema is on www cometsystem cz schemas soapHx5xx xsd How to configure sending SOAP messages example SOAP enable Yes Target web page server ohp SOAP server IP address 111 247 123 123 Source port O never set to 80 causes it web server collision Destination port 80 http servers usually listens at this port Sending interval 10 IE HGS HX531R 07 25 10 What to do when 10 1 forgot the IP address of the device Finding the device IP address IP address 1s set to the value 192 168 1 213 by the manu
18. ally 13 4 Technical support and service The adjustment procedure is described at file Calibration manual pdf which is installed commonly with the TSensor software Technical support and service is provided by distributor For contact see warranty certificate You can use discussion forum at web address http www forum cometsystem cz information how to sign up this forum you find at http www cometsystem cz english forum htm This value depends on the atmospheric pressure For computing is used constant value stored in device memory Default value preset by manufacturer is 1013hPa and can be changed by user s software This maximum is reached under conditions about 70 C 100 RH or 80 C 70 RH IE HGS HX531R 07 33 14 Connection of external power relay external power relay Coil data chart of external power relay nominal voltage max 50V nominal power 60 current max 2A 15 Appendix B This chapter contains basic information about connection of the detectors optional accessories to binary inputs of monitoring system The detectors install in accordance with the attached instructions for use SP008 power detector voltage presence sensor with optical indicator green LED input voltage 230Vac 50Hz power plug typeC response time approx sec 5 008 10 12 flood detector This detector 15 a water flood indicator for cellars bathrooms DIP
19. arms while the power is connected In case of power disconnection or a reset of the device e g by modification of configuration a new alarm evaluation is performed and new alarm reports are sent again if any It is possible to set the alarm parameters via telnet Modbus protocol or SNMPv1 protocol TSensor program Detailed description of setting via these protocols can be found in chapters informing about particular services 8 7 2 Binary values The binary values mean status of relay and binary inputs Device can send warning message e mail SNMP trap or Syslog message in the course of relay or binary input change state Every binary value has own time delay relay see chapter 8 3 binary inputs 8 6 Binary inputs can have a name max 14 characters BINI JMMdlimedelay Time delay ALARM hi i low Alarm time A figure shows a simple example Binary input is configured to send an e mail if input change state from high to low lower edge At point a binary input was opened Because at point 2 input was closed before the time delay expired alarm was not set At point 3 was input opened again At point 4 the time delay expires and at this moment e mail SNMP traps are sent The alarm lasted to point 5 where the input was closed 20 IE HGS HX531R 07 8 8 Factory default Ethernet interface This procedure describe how set Ethernet interface of device to factory defaults new IP address 192 168 1 212 ma
20. ath to the device 1s then iso org dod internet private enterprises comet products hxb5xx MIB tables are available at WWW pages http www cometsystem cz or on the installation CD in the MIB directory Password for a read operation is set by the manufacturer to public password for write is set to private These passwords may be changed in the setup History By means of the SNMPv1 protocol it is possible to display history of the last 100 measured values stored in adjusted time interval This interval is set by configuration program If a value has not been measured yet or an error was detected the value 15 9999 or 9999 if pressure is measured The history is erased after each restart of the device Restart occurred if device configuration 15 changed via keyboard or TSensor software 24 IE HGS HX531R 07 9 4 WWW The device supports display of measured values adjusted limits and alarm states on its WWW pages The address of the WWW pages 15 identical with its IP address It is possible to upload self made web pages to device More info about user defined web you can find on http cometsystem cz section programs Example The device has an IP address 192 168 1 204 Enter http 192 168 1 204 to the browser address field and confirm it with the Enter key WW pages have adjustable automatic refresh interval The manufacturer sets it to 60 seconds The value can be modified in the setup in a range of 10 65535s If the device has WWW p
21. erface 8 7 1 Analogue values It 15 possible to set an upper limit lower limit hysteresis and time delay to each measured value Figure shows a temperature curve with some specified upper limit temp limit high and hysteresis At point temperature exceeds the limit From that moment a time delay is counted time delay after which an alarm 15 set Because at point 2 the temperature dropped below the limit value temp limit limit before the time delay expired alarm was not set telnet some settings are not allowed display settings computed value selection see chapter 8 4 IE HGS HX531R 07 19 temp limit high hysteresis temp Time delay time At point 3 the temperature again exceeded the limit and because it did not drop below the limit value temp limit high before the time delay ended the alarm was set at point 4 At this moment the alarm e mails and traps are sent if they are enabled and the alarm flag is set the flag 1s set when the alarm is active and reset when inactive The state of the flag can be found on the WWW pages or via Modbus or the information console The alarm lasted to point 5 where the temperature dropped below the limit value given by the adjusted hysteresis temp limit high hysteresis For other measured values the principle of alarm activity 15 analogical An alarm report is always sent right after an alarm appears The device memorizes sent alarm reports of current al
22. f integer 10 int 100 int 1000 depend on type BCD register 15 in format of BCD ulnt register is at range of 0 605535 character where a Temperature RH computed value pressure alarm status no no alarm lo value is bigger than specified upper limit hi value is lower than specified lower limit b Relay alarm status op no alarm cl relay 15 closed alarm 15 signaled c Binary inputs alarm status no no alarm lo alarm on falling edge hi alarm on raising edge e Status word 16b value return bite description BitO 0 1 jumper open closed 0 1 relay open closed Bit4 0 1 relay 2 open closed 0 1 internal acoustic alarm status Bit 0 1 binary input status 0 1 binary input status 8 0 1 binary input status e Far relay control open close relay through Modbus protocol Before using remote relay control option is necessary setup FARO or FARI to the relay FARO remote relay control after device reboot relay is open FARI remote relay control after device reboot hPa mBar mmHg oz in Int 10 inHg kPa are Int 100 PSI are Int 1000 IE HGS HX531R 07 23 e Output relay alarm condition configuration For more information please download appendix for user guide from www cometsystem cz 9 2 SMTP In case of exceeding adjusted limits of measured values the device can send e mails to maximum of three addresses It is necessary to set your SMTP server address IP address authentica
23. f specific enthalpy 15 selected there 15 shown only value number without corresponding unit 3 28 this symbol is on if jumper 15 closed IE HGS HX531R 07 12 Preventive maintenance Pay heed to recommended calibration interval Do not subject the device to mechanical stress Recommended calibration intervals H4531R 1 years H353IR 2 year H7531R 2 year IE HGS HX531R 07 20 13 Technical specification 13 1 Technical parameters 13 1 1 Common parameters Power voltage 12 DC Power consumption approx W Power connector coaxial connector diameter 5 5 x 2 1 mm internal contact Measuring interval 18 Display switching interval 4 5 when more than two values are displayed Communication with computer Ethernet connection RJ 45 connector Protection IP30 Relay outputs Amount 2 Maximal voltage 50 Maximal current 2A Maximal power 60 VA Relays contact is not designed for direct control of line voltage output relay contact parameters max 220Vdc 125Vac 2A 60 W 62 5 VA Binary inputs Amount 3 Signal for binary input from floating contact or binary voltage Caution Binary inputs are NOT galvanic isolated Minimal input pulse duration 500 ms detection of shorter pulses 15 not guaranteed Current through closed contact 25 Open contact voltage lt 33V Maximal input voltage 30 V Low level input voltage 0 to 0 5 V Hi level input voltage 3 0 to 430 V Cable for
24. facturer If you changed it and forgot the new IP address run the TSensor program and press the Find button In a new window all sensors will be show 10 2 It is not possible to connect to the device from a LAN In the Find device window is only IP and MAC address displayed The next information is displayed as N A This problem will be occurred when the device IP 15 set to another LAN In TSensor program choose Find device Change IP address Follow the program instruction The sensor IP address in Find device window is not displayed In TSensor program select Find device Help my device Wasn t found Follow the program instruction Finding the MAC address The MAC address 15 a unique address of a device which 15 necessary to be known e g in case when there are several devices connected to the network MAC address 1s on device label It is not possible to find meter after manual MAC enter In TSensor program select Find device Help my device Wasn t found n this select Set IP to ARP only Into device MAC address enter the meters MAC address e g 00 20 4A 84 F0 80 and press the Set IP button Open telnet to the IP address you assigned to the device MAC address by running a telnet command telnet IP address assigned to MAC address 9999 and confirm with the Enter key Choose 0 Global Settings set the meters IP address clear the gate IP no of net mask set to 0 Pres the Enter key until you are not back into a menu Pres
25. ing pressure units hPa kPa mbar mmHg inHg 1nH2O PSI oz in2 The device 15 equipped with two relay outputs for alarming or controlling of external devices It 15 possible to assign any input value to each relay to set comparing limit delay hysteresis and acoustic alarm or change its status by far control with using of Modbus communication protocol The device is communicating through Ethernet interface The device 1s internally separated into two units The first unit provides measurement and controlling of output relays there 1s possible to change these parameters directly through device s keys or TSensor software The second unit provides all Ethernet services its configuration is possible through Telnet terminal or TSensor software this setting is impossible to change through device s keys Humidity Computed value Binary inputs H53IR v v J x ___ the type H4531R is designed for two wires connection of external Pt1000 3850 ppm temperature sensor Measured values are available from Ethernet interface or are displayed on LCD display If there are two values displayed at one LCD line they are periodically switched between both readings with period of 4 seconds Display can be switched OFF totally too The following formats are supported WWW pages with user design possibility Modbus protocol SNMPVv1I protocol SOAP The instrument may send a warning message to several defined points if
26. ith the graph below O t 7o O 70 60 relative humidit relativn vlhkos continuous use oblast trval ho pouziti 40 30 20 30 20 10 10 20 30 40 50 60 70 80 90 100 110 temperature teplota C 3 There is possible to change response time For more details see file Description of calibration and adjustment procedure pdf which is installed together with Users software IE HGS HX531R 07 31 13 1 3 Value computed from measured relative humidity and temperature relative humidity oRH 32 Dew point temperature 60 to 80 C 76 to 176 F 1 5 C 2 7 F at ambient temperature T lt 25 C 77 F and relative humidity RH gt 30 for more details see graphs below Nc il 2 5 Accuracy 100 80 60 40 20 dew point temperature Tdp C 20 7 0 20 40 60 80 Er 120 ambient temperature T C Absolute humidity Range Accuracy accuracy g m3 0 to 400 g m 1 5 g m at ambient temperature T lt 25 104 F for more details see graph below P d 0 20 40 60 80 100 120 ambient temperature T C a HH TT 2H process temperature T C IE HGS HX531R 07 Specific humidity 2g kg at ambient temperature T lt 35 95 F Range 0 to 550 g
27. m condition configuration 15 made using Modbus protocol keyboard is blocked for this time During this configuration is a word bloc shown in the display 12 IE HGS HX531R 07 uedo 1ndino enjeA siy Aq eseoJoep ueuj IH JeuBiu s anjeA asnse w snw Aejas uonipuoo si 3194 3 ejyeudoudde uedo jeseJd snw sy 51 35 peunseeui jusisueJ pesojo SI SUI siu Joye pue enJ eq 4 uonipuoo 9 spuooes SUI 1esaJd uey 07 JO si en eA jenjoe peso si Aejal ji USUM NIS on eA 5 195 SS9O922P 104 Aejai peuBisse Ca IE HGS HX531R 07 13 It is possible to display actual device preset on its LCD display by pressing of key LCD shows information about relay 1 and then relay 2 setting step by step Information about relay are indicated with symbol B ALARM 1 for relay 2 with symb
28. ol A at right top corner of LCD It is possible to edit parameters after pressing key and entering of correct password PASS see chapter 8 4 2 at page 14 Following examples are for relay 1 setting similarly are displayed values for relay 2 Pressing of key ends this mode and switch to actual value displaying the same occur if more than 20 s is not pressed any key 8 4 Monitoring system setting change part of measurement unit 8 4 1 Setting with PC and TSensor software User s software TSensor is available free to download at web page www cometsystem cz It provides setting of all device parameters Run the TSensor program and follow the program instructions Device includes hardware write protection of internal setting except of Ethernet setting which 15 protected by password new setting 15 possible to write only while 1 during write period press key do requested setting in TSensor software press key on device and keep it down then click on the button Save Changes into TSensor software and after end of write release 5 key 2 when DIP switch 4 is ON available at back side of the device if it is ON then you can see small number 3 at left side of LCD and new setting can be write Don t forget to move DIP switch 4 to OFF after setting procedure finish restore write protection TSensor software supports to make the adjustment of the device
29. ree LED diodes placed on the left side from LCD Green one represents input Binary 1 yellow input binary 2 and red input binary 3 Configuration of binary inputs is done by DIP switch one to three placed at backside of the device DIP switch 1 is assigned to binary input 1 DIP2 to BIN2 DIP3 to BIN3 If corresponding DIP switch is ON then appropriate binary input 1s configured as voltage input It means that without connection of external voltage there is binary input read as 0 after external voltage 15 applied there is binary input read as 1 This setting 1s for suitable for optional accessory Power detector 5 008 for example If corresponding DIP switch is OFF then appropriate binary input 15 configured as dry contact input It means that if the binary input 15 open disconnected then binary input status 15 read as 1 if the binary input is closed closed contact then binary input status 15 read as 0 For each binary input there is possible to set indication LED function if is lighting when binary input is closed or opened Binary input status can be assigned to any of output relays It is possible to choice if output relay is closed or opened when binary input is closed opened Binary inputs are not galvanic isolated 8 3 Actual monitoring system preset measurement part It is NOT possible to make any changes of Ethernet services for their setting see chapter 8 6 at page 19 If output relay alar
30. s 9 Save and Exit The connection will be closed Now you can connect to meter by the TSensor program 10 3 LCD display is Off check if power supply is connected properly e disconnect and connect the power supply watch the display at the moment of connecting the power If all LCD segments light for 1 second and go out again the display is turned off by the software 10 4 Error States of the device Device continuously checks its state during operation In case error is found LCD displays corresponding error code 26 IE HGS HX531R 07 0 First line of LCD displays Err0 Check sum error of stored setting inside device s memory This error appears if incorrect writing procedure to device s memory occurred or if damage of calibration data appeared At this state device does not measure and calculate values It is a serious error contact distributor of the device to fix Error 1 Measured or calculated value except in pressure 15 over upper limit of allowed full scale range There is a reading Err1 on LCD display Value read from the device is 999 9 This state appears in case of Measured temperature is higher than approximately 600 C i e high non measurable resistance of temperature sensor probably opened circuit Relative humidity is higher than 100 1 damaged humidity sensor or humidity calculation of humidity is not possible due to error during temperature measurement Computed val
31. sk 255 255 255 0 power off device close the jumper near the Ethernet connector power on the device wait approximately 155 remove open the jumper pud IE HGS HX531R 07 21 9 Communication protocols 9 1 Modbus protocol The device contains support for the Modbus TCP protocol to communicate with control systems The port is set to 502 Port 502 enables full access 1 e both read and write operations are supported Access to port can be disabled in the Setup Maximal number of client transaction 15 set to 1 Supported Modbus commands Code Read multiple register s 0x03 Reads 16 bit register s Write multiple register s 0x10 Writes 16 bit register s Modbus registers of monitoring system hex dec 0x0031 measured relative humidity RH 0x0032 computed value CV CV depen 0x0033 52 BCD 0 1035 4149 depen 0 0034 52 device serial number Lo 0 1036 5150 relay 1 status 0 1 0x003B relay 2 status 0 1 r NE MN _ 61 r Int Int 0x003C 60 Int Int F O d d X Em EE __ nt ___ 1 ___ nt binary input 2 status 0 m binary input 3 status 0 1 _ In 0 0038 63 r far relay 1 control see below a Int 0 0042 r w 0 relay open 1 relay closed far relay 2 control see below EIN Int 0x0043 67 r w 0 relay open 1 relay closed status of all binary inputs bit0 1
32. splitter 5 Dimensions T ALARM 2 IE HGS HX531R 07 6 Installation It 15 necessary to assign a new suitable IP address to the device at the first connection to it in order to prevent collisions with already existing network IP addresses and make the address conform to the local habits If installing several new devices connect them to the network one after another If a suitable IP address is not known contact your network administrator and ask him for the following IP address of monitor IP address of gateway Network mask The IP gate address and the network mask need not be specified if the device will be operated only in a local network If you set the IP address to one which is already used in the network the device will NOT work correctly and collisions in the network will appear It 15 possible to set the IP address by DHCP server Device setting from the manufacturer IP address Gateway not set Value assigned to relay 1 and relay 2 none Password for setting through keys PASS 0000 Password for setting via TSensor none Value shown at first LCD line temperature temperature pressure Value shown at second LCD line relative humidity dew point temperature Temperature unit Correction for altitude 0 hPa absolute pressure Computed value preset dew point temperature Relay response for error stay unchanged at previous condition
33. the measured value gets out of adjusted limits There are the following possible ways to deliver the warning report to send an e mail to maximum of three e mail addresses to send a SNMP trap to maximum of three IP addresses to display an alarm state on the device WWW page to send a message to Syslog server Alarm limits may be set via TSensor software Modbus Telnet or a 5 protocol The alarm state may be read via the device WWW pages Modbus or the SNMPv1 protocol The value assign to each relay is possible through TSensor software or through device s keys If Power over Ethernet is needed it is necessary to use some PoE Splitter Tested 1s e g D Link DWL P50 Device itself does NOT support PoE internally Monitoring system supports Internet protocol version 4 IPv6 is NOT supported IE HGS HX531R 07 3 Monitoring system mounting and connection The devices are designed for mounting into 19 inch rack mounting screws and female screws included At back side of the device there are connectors for power source 24pins CAGE CLAMP connector and RJ 45 Ethernet connector There is possible to use 12V and 5V power output for powering of external sensors and detectors see picture below gt 12V 1 tiTemperature Humidity Relays 1 2 H3531R Output BIN1 U1 BIN2 U2 BIN3 U3 Output Temperature Humidity Relays 1 Relays 2 5 1 218 8101 Sd power supplies
34. tion etc for correct function of e mail sending If limits of several measured values are exceeded a special alarm e mail is sent for each alarm state Dummy address sensor device IP address 1s displayed as a sender of the e mail It is not possible to reply to this address In the Subject field of the message the sentence Alarm Description of the device is displayed or Test message Description of the device inthe case of sending a test e mail 9 3 SNMPv1 By means of the protocol it is possible to find currently measured values read and set parameters concerning alarms In case of alarm activation warning message a trap can be sent to specified addresses By means of the SNMPv1 protocol it is also possible to display history of last 100 measured values For read and write the device communicates via UDP port 161 Traps are sent via port UDP port 162 Sending of traps can be disabled in the Setup The following traps sent 0 0 device restart e 1 0 testing trap e 1 1 SNTP time synchronization error e 1 2 Ethernet firmware was uploaded 173 2 175 SOAP communication error e 1 6 1 8 e mail sending error e 1 9 Configuration changed via SNMP or Modbus 6 3 6 55 report on a measured value being outside of the limits or a return of the measured value to the limits For the correct function of the 5 server it is necessary to store the MIB table Hx5xx mib and RFC 1213 mib to the MIB client The p
35. ue calculation of the value is not possible error during measurement of temperature or relative humidity or value is over range The value of pressure 999 9 hPa is correct value Error 2 There 15 a reading Err2 on LCD display Measured or calculated value is below lower limit of allowed full scale range Value read from the device is 999 9 This state appears in case of e Measured temperature is lower than approximately 210 C low resistance of temperature sensor probably short circuit Relative humidity is lower than 0 i e damaged sensor for measurement of relative humidity or calculation of humidity is not possible due to error during temperature measurement e Measured pressure value with added correction for altitude is outside of range from 300 hPa to 1350 hPa from 4 351 PSI to 19 580 PSI or the pressure sensor is damaged Please check setting of pressure correction for altitude with User s software e Computed value calculation of computed value is not possible error during measurement of temperature or relative humidity Error 3 There 15 a reading Err3 on LCD display upper line Error of internal A D converter appeared converter does not respond probably damage of A D converter This error does NOT affect pressure measurement Rest values are NOT measured It 15 a serious error contact distributor of the device Error 4 There is a reading 4 on LCD display It is internal device
36. uitur UP DRE D eae 14 Setting With using monitoring system Keys 14 Extended setine MORC 14 RESTORE TO DEFAULT MEASUREMENT PART cene 19 MONITORING SYSTEM CONFIGURATION ETHERNET INTERFACE eene 19 ALARMS ETHERNET INTERFACE ccscsscecescccescscecsceccscscescscescscesescesescecescecevescess 19 Analoge VAINOS airain debits 19 T VOTI ION 20 FACTORY DEFAULT ETHERNET INTERFACE 21 COMMUNICATION PROTOCOLS cccccccccccccccccccccccccccccccccsccccs 22 MODBUS PROTOCOL DADA EIU 22 24 SNMP 24 25 IU E I 25 SYSLOG PRO FOC Oi 25 S18 ere oe TT 25 WAALCTODOWHE N edu E E 26 I FORGOT THE IP ADDRESS OF THE DEVICE cecescecceccscecceccscsceccsceccecescescecescesens 26 IT IS NOT POSSIBLE TO CONNECT TO THE DEVICE FROM A LAN 26 ICD DISPEAY IS OPE ai ien gt _4__ _ DRE 26 ERROR STATES THE DEVICE 26 READINGS ON ECD Y
37. us SOAP there is necessary to have installed appropriate software supporting appropriate communication protocol on PC Such software is not included in the delivery The device is internally separated into two units The first unit provides measurement and controlling of output relays these parameters are possible to change directly through device s keys or TSensor software The second unit provides all Ethernet services its configuration is possible through TSensor software or Telnet terminal this setting is impossible to change through device s keys 8 1 Relay outputs Monitoring system is equipped with two relay outputs It is possible to assign any input or computed value or far control to each relay to set comparing alarm limit if the relay may close if measured value is higher Hi or lower Lo than preset limit delay for while must be preset condition true before relay close its contact and hysteresis for return to open status For binary inputs if it is preset to then output relay is closed when input contact is opened if it is preset to then output relay is closed when input contact is closed Each relay status is indicated with LED diode and shown on LCD with corresponding symbols 8 2 Binary inputs It is possible to read three binary inputs status It 15 possible to connect open contact external voltage Visualization of binary inputs is done by th
38. ys To store preset value press SET key Press ESC key to leave editing changing without save last stored value 1s kept Into this mode you can set following items Acoustic alarm assign to relay 1 acoustic indication of relay 1 is OFF DESDE Hud i 1 d 15 Acoustic alarm assign to relay 2 acoustic indication of relay 2 is OFF d 15 Acoustic alarm deactivation activated acoustic alarm is possible to deactivate by pressing ESC key dERL ESL Relay response for error close of relay 1 contact starts acoustic indication ALARM 1 Hud close of relay 2 contact starts acoustic indication Hude acoustic alarm is still activated for all time and it is impossible to deactivate it dERL iL Monitoring system continuously checks its state during operation In case error of assigned value measurement is found then output relay IE HGS HX531R 07 15 stays unchanged in previous status relay 1 switch OFF relay I switch On stays unchanged in previous relay 2 switch OFF relay 2 switch On status Change of Password for setting through keys PASS This item shows actual password setting It is possible to change it after SET key pressing It 1s number from range 19999 to 19999 password setting Visualization of binary inputs Visualization of binary inputs is done by three