1. ALC AD Product Guide EEN Priectronies Ceiling mounted photocell for 1 10V dimming Overview The ALC AD dimming photocell automatically adjusts the light output of luminaires depending on the amount of natural light available to maintain constant brightness maintained illuminance using 1 10V control An optional manual control using a switch input allows the user to override the dimming levels and turn the output on and off In addition to changing the output level the photocell can be set to turn lighting on when the ambient light falls below a preset level The lighting can also be set to turn off when the total light level rises above a separate preset level An integral adjustable time delay prevents nuisance switching caused by for example dark clouds All functionality is fully programmable using an IR handset Front features Mounting Bezel Ng a i Sensor Lens which covers IR Receiver Light Level Sensor Status LED Back features Retaining Spring Dimmable Control Output Connector Channel 2 Power Input amp Switched Output Connector Channel 1 Switch Input Retaining Spring Connector IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor Measures the overall light level in the detection area Status LEDs The LED flashes Red to indicate the following I o gt lt 4 Valid setting received SRS Power Input
2. amp Switched Output Connector Channel 1 Used to connect mains power to the unit and to connect a switched load Dimmable Control Output Connector Channel 2 Used to connect 1 10V controllable ballasts and transformers for dimmable loads Switch Input Connector Two input terminals can be used to manually override the dimming levels and override the lights on or off Installation Choosing a Suitable Location The ALC AD is designed to be ceiling mounted and must satisfy the following criteria e Avoid positioning the unit where direct sunlight may enter the sensor element Sensor functionality Switch Level On Off The device can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Brighter Lux Off Level Ambient Light Level Lux On Level Darker Maintained Illuminance daylight harvesting The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level maintained illuminance or daylight harvesting Overview It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time to guarantee lamp life refer to the manufacturer s datasheet for details As this ALC AD is able to dim the lamps using 1 10V the product provides a facility to disable this for a given period of time Operation By setting the Burn in para
3. LVD 2006 95 EC Part numbers Part number Description Detector ALC AD Ceiling mounted photocell for 1 10V dimming Accessories DBB Surface mounting box UHS5 Programming IR handset UNLCDHS Universal LCD IR handset IMPORTANT NOTICE This device should be installed by a qualified electrician in accordance with the latest edition of the IEE Wiring Regulations and any applicable Building Regulations 9001 14001 Quality Environmental Sa Management Management SSS energy services and technology association FM 45789 EMS 534520 Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice 8 lectronics intelligent energy control C P Electronics Ltd Brent Crescent London NW 10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Ref WD482 Issue 1
4. UHS5 which are not shown below are not applicable to this product UHS5 Handset Graphics Turn lights on or to raise lights Turn lights off or to lower lights Lux level setting to prevent the luminaires being switched on if the ambient light level is sufficient adjustable between 1 and 9 The luminaires will always be switched on at level 9 Sets a target light level to be maintained by the lighting system Lux level setting to switch the luminaires off the ambient light level goes above the setting adjustable between 1 and 9 Level 9 will always keep the lights on This setting can be used for window row switching Note the Lux Off Level value must always be greater than the Lux On Level value Returns the unit to the default settings Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Advanced programming Detector Parameters Lux time 0 disabled If the detector measures the lux level and decides that the output needs switching x Y 4 99 minutes on or off as a consequence the lux time must elapse first If at any time during the timed delay the lux change reverses then the process is cancelled Lux Time enables absence detection to be implemented with a lux off level set When the button is pressed the l
5. bility to read back the settings stored in a device To read back individual parameters Navigate to the parameter and press the R Read button whilst pointing at the device The handset will click when the parameter has been read back the device will flash its LED and the value will be shown against the parameter in the menu To read back all of the parameters in a menu Press and hold the R Read button for more than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Notes If a parameter s has been missed because of a communication error the missing value s is replaced by dashes When reading back the Channel 1 relay where fitted will temporarily be switched off and will return to it s normal State 2 seconds after the read back has been completed 3 Wiring diagrams Standard wiring schematic also showing optional manual override switch This is a general wiring diagram In this configuration the unit will switch the supply to a luminaire using the switched output and dim using 1 10V Manual dimming and switching can be achieved using the optional centre biased retractive switch MK K4900 or similar i J DIMMING D ERLLAST mv DIMMING LUMINAIRE NEUTRAL LIVE o
6. eventing Switch level off For a higher resolution lights from being turned on by movement a scale of 101 199 is available Channel 2 Dimming Channel Lux on level Lux level setting to prevent the luminaires being switched on if the ambient light Switch level on For a higher resolution level is sufficient adjustable between 1 and 9 The luminaires will always be a scale of 101 199 is switched on at level 9 available Note the Lux Level Off value must always be greater than the Lux Level On value Lux off level Lux level setting to switch the luminaires off the ambient light level goes above the Switch level off For a higher resolution setting a scale of 101 199 is available Light Level 1 to 998 999 Sets a target light level to be maintained by the lighting system maintained illuminance disabled 0 to 100 Maximum dimming output level Memorise N Yes or No If this is set to Yes the last manual lux level set will be memorised and used as the x j new switch on level 0 to 99 Dimming output level when switched on 0 99 Off value 0 to 99 Dimming output level when switched off 0 99 If a non zero off value is set then x J the output will toggle between this value and completely off depending on the switch level on and off values This feature is only enabled if Min value is set to 99 Burn in 0 disabled or Determines how long the output will be at 100 so that lamps burn in The burn 4 to 999
7. gt lt 0 CIRCUIT PROTECTION IF REQUIRED CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING OPTIONAL ALC AD DIMMING OUTPUT PHOTOCELL ALC AD being switched on by presence detector In some configurations it is useful to supply the sensor from a separate presence detector NEUTRAL I lt LIVE SUPPLY CIRCUIT PROTECTION IF REQUIRED DIM ce i E DIM E SW1 UP L sw2 DOWN PRESENCE DETECTOR ALC AD DIMMING OUTPUT PHOTOCELL eu DIMMING PLEASE NOTE OOF pou l f NON DIMMING CPC s OMMITTED FOR CLARITY LUMINAIRE S DIMMING LUMINAIRE S i 1 10V Basic programming The functionality of the ALC AD is controlled by a number of parameters which can be changed or programmed by any of the following devices e UHS5 Infrared Handset See below for programmable functions e UNLCDHS Infrared Handset with LCD See user guide for full programming details For most basic programming operations the UHS5 handset can be used and the following procedures are based on using this device Point the handset at the Sensor and send the required programming commands to the unit as shown Parameter Default 0 2 Name Value TOT e Ko amp 2 e 1 2 ss I Raise Off Lower _ Lux on level Switch level on Light Level 6 600 Lux off level Switch level off below Valid commands will be indicated by a red LED flash See page 1 for details of other LED responses Note other functions on the
8. hours in time is not affected by power supply interruptions Measured in 0 1 Determines the dimming response speed after the setup time has finished x Z sec intervals Measured in 0 1 Determines the dimming response speed during the set up time Measured in 0 1 x V sec intervals sec intervals If set to 0 will disable dimming for Set seconds below used if fittings are required to warm up before dimming Set Seconds 120 1 to 999 seconds Determines how long the dimming response set up period lasts on power up or on setting change This enables the desired lux level to be achieved rapidly when the x v4 lights come on or during setup Technical data Dimensions Weight Supply Voltage Frequency Maximum Load Power consumption Dimming output Terminal Capacity Temperature Humidity Material casing Type IP rating Compliance See diagrams opposite ALC AD 0 15kg 230VAC 10 50Hz Channel 1 switching 10A of lighting and or ventilation including incandescent fluorescent compact fluorescent low voltage by switching the primary of transformer Channel 2 dimming Maximum number of 1 10V ballasts is 10 On 708mW Off 255mW Basic insulation only Although low voltage this is not an SELV output and should be treated as if mains potential Use mains rated wiring 2 5mm 10 C to 35 C 5 to 95 non condensing Flame retardant ABS and PC ABS C DBB IP40 EMC 2004 108 EC
9. ights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off again after the Lux Time Note that whenever the an external switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Factory default OOo s a o Restores factory default settings User Modes e E I scl EA Ci FS ic a E EEE C E eee E Caesa RE EE ioaea E EA Scene Select the individual scene between 0 and 6 1 min output 2 10 3 25 4 50 5 75 6 100 Override On If the lights are off sending the IR command will turn them on immediately and revert to automatic operation using the manual timeout period Override Off If the lights are on sending the IR command will turn them off immediately After the manual timeout period described above the sensor will revert to automatic cancel fe Cancels the on or off override returning the detector to normal operation nee Advanced programming Channel 1 Switching Channel Lux on level 1to9 Sets a minimum light level below which the PIR sensor is enabled allowing lights Switch level on For a higher resolution to be turned on by movement a scale of 101 199 is Note the Lux Level Off value must always be greater than the Lux Level On value available Lux off level 1to9 Sets a maximum light level above which the PIR sensor is disabled pr
10. meter you can select a time during which the lamps are not allowed to deviate from maximum output The unit counts the time and even remembers how long has elapsed in the event of a power failure To cancel the burn in function simply select a time of 0 Note that when the lamps are changed the burn in time should be set again Fault finding What if the load does not turn ON e Check that the live supply to the circuit is good e Increase the Lux on level to switch on at a higher brightness What if the load does not turn OFF e Increase the lux off level to switch off at a lower brightness Load cycles on and off e Increase the difference between the lux on level and the lux off level e Increase the time setting e Angle the sensor away from the light that it is controlling Installation The ALC AD is designed to be mounted using either e Flush fixing or e Surface fixing using the optional Surface Mounting Box part no DBB Both methods are illustrated below Flush Fixing Hole 64mm Warning be careful bending springs when mounting unit Surface Fixing gt Wire stripping details Pull out spring tab and rotate spring arm as shown Important lt 4 Ensure that the cables are formed as shown per before affixing the cable clamp The clamp MUST clamp the outer sheath s only 6 mm Bend cores as shown 35 mm Readback function UNLCDHS handset only The UNLCDHS has the a