026-4127 - Emerson Climate Technologies

image

Contents

1. 2 81 or above UltraSite32 4 81 has a new feature once a board point pointer has been con figured with its board and point address it is now always displayed in Edit Application Document Part 026 4127 Rev 4 02 MAY 2012 Page 10 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above screens as its full AreaController Application Property address with its Board Point address shown next to it for reference The Application shown will be the default name of the Physical Al Physical AO Physical DI or Physical DO application that represents the board point and the Property will be either INPUT or OUTPUT Application Name stoar Defrost Deft Times Inputs Outputs Alarms Notices Advanced tis Value NA ea The example shown above shows a case temperature input that has been configured to 16Al Board 2 Point 3 This input was configured simply by entering the board number as 2 and the point number as 3 This pointer is displayed here in AreaController Application Prop erty format as E2 Unit01 the E2 name Al 01 02 03 a Physical Al application for unit 1 board 2 point 3 OUTPUT the value of the sensor connected to board 2 point 3 i
2. 7 Run DBRefresh Utility DBRefresh is a utility that is run automatically after installation or upgrade and can also be run standalone and will fix database problems caused by corrupted templates and or rules UltraSite32 x 4 _ Database Refresh DB refresh needs to be run UhtaSite will close and run the refresh Please wait until the refresher is finished before running UltraSite again Otherwise the database may get corrupted The DBRefresh utility refreshes your ultra32 mdb database with updated templates and rules for any templates already in your database it will not add templates or rules and gen erates a text file report detailing what was done e Replaced Indicates the data for the specified template rule was replaced e Original with good XML Indicates that no update was made for this ID e Problem Indicates that there is no update available and the data is still corrupted e Repaired Indicates the data for the specified template rule could not replaced but was able to be repaired The report filename is in the following format Filename ultra32_BaselineAndDsc_AuditFileYYYY_MM_DD_HHMMSS txt Step 8 If Necessary Upgrade Custom MON Screens The format used for custom screens has changed as a result of UltraSite32 4 81 The new file format is called MON2 UltraSite32 will automatically upgrade all MON screens to MON2 format when they are first opened Also if a custom MON screen includes links to o
3. control devices the Con troller field had to be filled with the name of the unit controller as shown in Network Ser vices In 2 81 and all upcoming revisions to configure unit controller pointers AreaController must be filled with the name of the unit controller s parent E2 and Appli cation with the name of the unit controller Example In E2 version 2 7 a Control Link CD device connected to an E2 might have a board name such as CD 01 01 and an application name such as CL CD001 Setting up a pointer to the DISCHARGE AIR output of the Control Link CD would require the Controller Application Out put definition to appear as follows CD 01 01 CL CD001 DISCHARGE AIR In E2 versions 2 81 and higher there is not a separate application name for unit controllers the board name is also the application name Furthermore pointers to unit controllers require you to enter the board name in the Application field of the pointer definition So in E2 2 81 the example above would be set up as follows THIS 01 1 CD 01 01 DISCHARGE AIR Where THIS 01 1 is the unit name of the E2 to which the Control Link CD is networked Board Point Pointers In UltraSite32 Display in a Different Format E2 2 81 and above only Pointers configured to board point addresses such as MultiFlex inputs or relay outputs are configured in the same way they have always been configured For E2 controllers version
4. updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above There are several ways to reduce the file size of ultra32 mdb e Delete sites and directories that you are not using e Purge unnecessary log data using System gt Log Purge e Compact the database using System gt System Options check the Enable Auto Com paction check box and click Set Compaction Times to schedule a data compaction time Step 3 If upgrading export any required controller backups and log data During a database upgrade UltraSite32 may encounter site data that cannot be upgraded As aresult of this it may be required to erase this data during the upgrade process see Activities that Occur During Database Upgrade on page 5 If you have controller backups or logs in your UltraSite32 database that you wish to protect export them and save them to a local directory before upgrade Setpoint backups may be exported by right clicking the unit in the Tree View and selecting Export Setpoints File The 001 file created from this export may be re imported after upgrade by right clicking the unit in the Tree View and selecting Import Setpoints File Logs may be saved by right clicking the log name in the Tree View and selecting Export Log Data This exports log data in a comma delimited text file You will not be able to re import the log data after upgrade Step 4 Begin installation an
5. Open UltraSite32 If you installed over a previous version of UltraSite32 the database con version process will begin the first time you start UltraSite32 after the installation process is complete When running UltraSite32 for the first time after upgrading you will receive the dialog box shown below Click OK and allow the database conversion to complete When finished do not start UltraSite32 again Proceed to Step 6 UltraSite32 x Database Error DB convert needs to be run Ultradite will close and run the converter Please wait until the converter is finished before running Ultradite again Otherwise the database will get corrupted Activities that Occur During Database Upgrade Select Optional Data Conversion UltraSite32 4 82 and above Because large databases can take a very long time to upgrade UltraSite32 version 4 82 and above will give you the option to skip conversion of certain types of stored data e Alarms advisories all stored alarm logs for all sites in your database e Event activity data logs of UltraSite32 activity such as logins logouts autopolling starts etc e Point logs all stored log data for all sites in your database The Optional Conversion Verification dialog box shows the amount of time it will take to convert for each data type If you wish to skip conversion for a data type remove the check from the checkbox next to it When you click OK the database conversion will ignore data for al
6. PC to version 4 81 or above will make it impossi ble for you to downgrade to a version of UltraSite32 that is version 4 70 or lower Contact Technical Support if your PC must be downgraded NOTE FOR USERS OF ULTRASITE32 NETWORK INSTALLATION Numerous changes have been made to the network installation process If you are auser of UltraSite32 Refer to Technical Bulletin 026 2503 Net work Mode Installation for UltraSite32 4 81 and above Document Part 026 4127 Rev 4 02 MAY 2012 Page 2 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above NOTICE UltraSite32 4 81 or above is not supported on Windows Server 2000 Dur ing install on a Windows Server 2000 PC you will receive the error mes sage as shown below and installation will be cancelled This incompatibility applies ONLY to Windows Server 2000 UltraSite32 is still compatible with the Windows 2000 operating system Crystal Reports 2008 Runtime x Requirement for installation of Crystal Reports 2008 Runtime Microsoft Windows XP SP2 or Windows Server 2003 or higher You need local machine Administrator privileges to install this product Step 1 Plan on upgrading ALL PCs before upgrading E2s All personnel that will c
7. and above may only export using the 002 for mat and 002 files cannot be converted to 001 or 000 files for use by previous versions of UltraSite32 Document Part 026 4127 Rev 4 02 MAY 2012 Page 9 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above Network Services Device Naming and Data Pointer Changes In versions of E2 before 2 81 every peripheral device that networks with an E2 had two dif ferent names a board name which is entered in Network Services to name the device and an application name that is given to the application that handles the interface between the device and other E2 applications In 2 81 the application name and the board name are now the same name This name will be used in place of the Application name in all input and output pointers The Controller Application Property format of input and output pointers in E2 has under gone two significant changes First the format is now displayed as AreaController Applica tion Property Second the first value of this pointer AreaController must always be the name of the parent E2 of the application In older versions of E2 when pointing to inputs or outputs on unit
8. ated if the database being converted is a ver sion below version 4 8 It is an export in XML format of the directory and site tree struc ture for the database being upgraded This file can be used to import into a blank ultra32 mdb file creating a new database with the same directories and sites including site communication settings This is the file UltraSite32 will attempt to use if it encoun ters unrecoverable corrupted data see What To Do If The UltraSite32 Database Cannot Be Upgraded on page 6 Before starting up UltraSite32 again follow the instructions below 1 Create a temporary directory somewhere on the PC s hard drive that is NOT a subdirec tory of the UltraSite32 program folder such as C US32temporary 2 Copy the files ultra32_pre date_time mdb ultra32_post date_time mdb ultra32_AuditFile txt and ultra32_UnitIinfo xml into the temporary directory 3 Ifusing any customized MON files such as custom floor plan views copy the MON files into the temporary directory These files may be used to revert to a previous version of UltraSite32 if necessary Document Part 026 4127 Rev 4 02 MAY 2012 Page 7 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above Step
9. d follow the prompts Depending onthe method in which UltraSite32 was delivered begin installation by inserting the CD or if delivered or downloaded as a file double click the file name in Windows Explorer to open the package and start the installer If a version of UltraSite32 is already on the PC it will uninstall before progressing The unin stall only removes program files it does not erase the database or any user configuration data When the uninstall is complete the installer will start again and will prompt for pro gram directory location copy the required files to your PC and depending on your operat ing system restart the PC Unlike previous versions the installer will not upgrade the database after restart Database upgrade occurs the first time you start UltraSite32 after installation see Step 5 If you are installing UltraSite32 on a PC for the first time you may begin using the program immediately The remaining steps below are required for users who are upgrading a version of UltraSite32 before version 4 81 Document Part 026 4127 Rev 4 02 MAY 2012 Page 4 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above Step 5 Start UltraSite32 and Upgrade Database
10. e and re open the MON file in order to make it work properly When all custom screens are converted copy all the newly created MON2 files to a separate directory for archival purposes The MON2 files may also be distributed to other UltraSite32 4 81 users for use when connecting to this site If an E2 2 81 or above site must be downgraded to a version before version 2 81 the con verted MON2 file will not work with the downgraded E2s Each custom screen must be reconfigured to point to the old MON file by selecting the Edit Custom Screens menu option and changing the file name so that the file name points to the original MON file instead of the MON2 file The MON to MON2 conversion process does not delete the old MON file after conversion so the old MON file should still be available in your program direc tory UltraSite32 4 81 can not convert a MON2 file to a MON file This means that if a custom screen must be edited for use in a version of UltraSite32 before version 4 81 and an E2 ver sion before 2 81 it must be edited using a version of UltraSite32 before version 4 81 and saved as a MON file Protection Against Duplicate Application Naming Because no two applications in an E2 can share the same application name special protec tions have been added in E2 to prevent this from occurring In E2 2 81 if an application is Document Part 026 4127 Rev 4 02 MAY 2012 Page 14 of 15 2012 Emerson Climate Technologies Retail Solu
11. e32 4 81 and Above other words if you are using offline programming to program a BX 400 the I O Boards and Controllers screen will allow you to add such devices as ISD 2 0 or Control Link RSC even though the BX is not allowed to communicate with these devices If devices that are not allowed for the unit model type are added in Offline Programming it will not restore those devices to the E2 during a Restore operation Note that offline programming for 16 bit offline programming modules REFLECS is not supported if using a 64 bit machine Microsoft no longer supports 16 bit Windows applica tions on Windows 7 or Vista 64 Graphical Status Screen Editing File Format Change MON is now MON2 Customized graphical status screens have undergone a change in the MON file format UltraSite32 4 81 uses a file format called MON2 when displaying custom screens for E2s whose versions are 2 81 or above The MON2 file format is not compatible with versions of UltraSite32 before version 4 81 or E2 versions before 2 81 After upgrading all E2s to 2 81 or above connect to the site with UltraSite32 4 81 and open each custom screen for the site and all units When the custom screen is first opened UltraSite32 will open the existing MON file and automatically convert the file to a MON2 file When this conversion occurs the MON2 file will be the file UltraSite32 opens every time the custom screen is viewed After conversion you may need to clos
12. escriptions The example below shows the message box shown when an E2 unit fails to respond during site synchronization UltraSite32 E xj The attempt to connect to a unit has failed The gateway thinks it should exist but it will not communicate Abort the site connection Retry the unit Ignore the unit as offline i Retry Ignore Changes to Advisory Duplication Filtering for E2 Alarm Annunciators using UltraSite32 In previous versions of UltraSite32 the site advisory view used to collect and view advisories from all E2s that belong to a single site had special code written to keep a Controller Absent alarm from appearing multiple times in the advisory view Without this code when ever an E2 goes offline every E2 that is a part of the site would generate a Controller Absent alarm announcing the E2 was offline and every one of those alarms would appear in UltraSite32 s site advisory view In UltraSite32 4 81 the site advisory view no longer automatically filters out multiple Con troller Absent alarms In its place a new filtering option has been placed in the Alarm Options dialog box called Allow Duplicates To Be Shown When Allow Duplicates To Be Shown is checked all Controller Absent alarms generated from controller versions before E2 version 2 81 will be displayed in the UltraSite32 site advi sory view regardless of whether or not multiple Controller Absent alarms are ann
13. f site data but must be done to enable the database to be usable by UltraSite32 Corrupted and invalid site data removed during this process will be logged in a special text file see UltraSite32 Post Installation Instructions which may be reviewed after installa tion What To Do If The UltraSite32 Database Cannot Be Upgraded In some cases a database from previous versions of UltraSite32 before version 4 81 will not be upgradable This is due to severe corruption in the database that cannot be processed by UltraSite32 s new database engine To prevent total loss of database information UltraSite32 will create an export file of the database s Tree View structure complete with site communications information If a data base cannot be upgraded the installer will ask you if you wish to use the tree structure exported from your database If you select Import UltraSite32 will automatically import Document Part 026 4127 Rev 4 02 MAY 2012 Page 6 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above the tree into a blank ultra32 mdb file and when UltraSite32 starts for the first time you will start with the directory amp site structure from the database but without any uni
14. g E2 Controller Firmware Using UltraSite32 PRE INSTALLATION NOTES Do NOT clean out E2 Before or After Upgrade The E2 must be allowed to upgrade the existing pre 2 81 setpoints Do not clean out the unit before upgrading Upgrade the E2 with the setpoints loaded Upon application of the upgrade the E2 will automatically upgrade the setpoints FSD Pointers Must Be Re Entered After Upgrade If you are upgrading a pre 2 81 E2 site that uses a Facility Status Display FSD and the FSD contains temperature status pointers that point to val ues outside of the FSD s host E2 unit in other words box to box pointers these pointers will be deleted during upgrade You must manually re pro gram these pointers from the E2 front panel This will only occur when upgrading from a version before 2 81 to a version that is 2 81 or later Software Changes Introduced in E2 2 81 and UltraSite32 4 81 This section of the document highlights several important differences between E2 2 81 UltraSite32 4 81 and above and previous versions New Setpoint Export Format 002 For E2 2 81 Setpoint Files UltraSite32 now uses a new file format for import and export of E2 files versions 2 81 or greater This new format has a file extension 002 to distinguish it from previous setpoint file versions 000 and 001 UltraSite32 can load 000 and 001 files and convert these for use in E2 2 81 and above con troller versions However UltraSite32 4 81
15. hnologies Retail Solutions Inc All rights reserved
16. l the unchecked data types Document Part 026 4127 Rev 4 02 MAY 2012 Page 5 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above Optional Conversion erification The conversion will include the selected data items stated below You may choose to not convert specific data items by un checking the box beside the data item Un checking the item will result in the that specific data being lost IV Convert the 817859 alarms advisories estimated time is 86 minutes Vv Convert the 110527 event activity data estimated time is 12 minutes Convert the 0 point logs M estimated time is 1 minutes Insertion of E2 Templates During the database conversion process UltraSite32 will also write the templates for all release versions of E2 into the database up to the most current release ver sion of E2 This will increase the size of the ultra32 mdb file but will enable offline programming for all E2 versions without need for a site synchronization to down load templates Deletion of Corrupted Invalid Site Data Also during the database conversion process UltraSite32 will remove all corrupted and invalid site data from the database This may result in partial loss o
17. ltraSite32 page 12 e Network Services Screen Changed in UltraSite32 page 13 e Improved I O Boards and Controllers Screen page 13 e In Offline Programming I O Board and Controllers Screen Shows All Devices Even Invalid Ones page 13 Document Part 026 4127 Rev 4 02 MAY 2012 Y 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use EMERSON Visit our website at http www emersonclimate com for the latest technical documentation and updates Climate Technologies update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above e Graphical Status Screen Editing File Format Change MON is now MON2 page 14 e Protection Against Duplicate Application Naming page 14 This document is provided as a supplement to the newest revision of the 026 1610 E2 User s Manual Revision 14 For more information about E2 and the changes made to E2 in the lat est version obtain and read a copy of the E2 User s Manual UltraSite32 4 81 Installation and Upgrade Installing UltraSite32 on Your Local Machine Windows 2000 XP Vista Windows 7 Significant changes have been made to the database used by UltraSite32 beginning in ver sion 4 81 As a result it is critically important that you follow the instructions below when installing UltraSite32 especially if you are upgrading a version of UltraSite32 before version 4 81 WARNING Installing or upgrading a
18. n degrees View E1 E2 Setpoints Operation NOTE The View E1 E2 Setpoints does not work with setpoint files from non English versions of E1 and E2 Previously the command File gt View E1 E2 Setpoints allowed a basic although not fully functional way to view the contents of an exported setpoints file in UltraSite32 In version 4 81 this feature is now fully functional View E1 E2 Setpoints may be used to look at any setpoints file 000 001 or 002 formats and see important data about the setpoints such as e Model type and version e An application summary with counts e Whether the templates required to use this setpoint file exist in the current database if not the templates for the version shown must be loaded by performing a site synchroni zation with an E2 with that version installed Updated Message Boxes In several message boxes that announce problems or errors option buttons such as Abort Retry Ignore are given without explanations of the effect they will have when chosen These Document Part 026 4127 Rev 4 02 MAY 2012 Page 11 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above message boxes have been updated with more detailed d
19. n Changed in UltraSite32 For E2 units the Device Setup gt Network Board Setup screen has been reformatted so it contains all the same information that is currently on the E2 Network Summary screen for E2 2 81 For more details about changes to the E2 s Network Summary screen refer to 026 1610 E2 User s Guide Revision 10 Improved I O Boards and Controllers Screen 1 0 Boards and Controllers Associated With This Controller Unk Name JOFRED Unit Number F The I O Boards and Controllers Associated With This Controller dialog box has been improved for E2 2 81 This dialog box now separates device types by tabs and dynamically displays device types and maximum numbers of device types based on what is licensed in the E2 In Offline Programming I O Board and Controllers Screen Shows All Devices Even Invalid Ones When using offline programming to configure a site due to the changes made to how the I O Boards and Controllers dialog box works see above the dialog box will show all devices that can connect to the E2 even devices that are not allowed for the specified model type In Document Part 026 4127 Rev 4 02 MAY 2012 Page 13 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSit
20. ommunicate with E2s version 2 81 or above must be upgraded to UltraSite32 version 4 81 or above before any E2s can be upgraded This includes e The PC that will be used to perform the E2 firmware upgrade e Any on site PCs touchscreens etc running floor plan views for E2 sites e All service technician PCs e Any PCs used in dispatch or monitoring centers that receive alarm dialouts from E2s Identify all PCs that must be upgraded before beginning the installation process and plan on upgrading them all at the same time Step 2 When upgrading an database from a pre 4 81 version of UltraSite32 reduce the database size below 800 MB The maximum database size for an UltraSite32 database file ultra32 mdb is and has always been 1 GB If you are upgrading to UltraSite32 4 81 or above and will be using a database from a previous version of UltraSite32 you must check the file size of the ultra32 mdb file and verify it is below 800 MB During upgrade UltraSite32 will add a large amount of data to your database which will result in the file size exceeding 1GB If this occurs your database may be rendered unrecoverable You must reduce the file size BEFORE upgrading the data base Document Part 026 4127 Rev 4 02 MAY 2012 Page 3 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and
21. ouncing the same offline event When Allow Duplicates To Be Shown is unchecked site advisory view will never show any Controller Absent alarms from controller versions before E2 version 2 81 referring to offline E2 units Every Controller Absent alarm referring to an E2 will be filtered out meaning you will never be able to use the UltraSite32 advisory view to detect an offline E2 unit The previous feature of filtering out all but one of the duplicate E2 Controller Absent alarms has been removed from UltraSite32 4 81 and may not be selected For controller ver sions before E2 version 2 81 users are now limited to either showing all Controller Absent alarms regardless of how many times they may be duplicated in the advisory view or not showing any Controller Absent alarms for E2s for any reason Controller versions 2 81 and above do not use the Allow Duplicates To Be Shown filter set ting when an E2 offline alarm occurs it will always show only once in the site advisory view regardless of this filter setting Document Part 026 4127 Rev 4 02 MAY 2012 Page 12 0f 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above Network Services Scree
22. t information such as application types backups and logs You will need to contact each site and perform a site synchronization to restore controller lists and unit inventory Step 6 Examine Upgrade Log File ultra32_AuditFile txt and Move Database Copies As asafeguard against possible database upgrade errors such as may be caused by attempt ing to upgrade an ultra32 mdb file with a file size above 800MB during the database con version process UltraSite32 will create several backups and log files which it will save to the UltraSite32 data directory C Ultra32 e ultra32_pre date_time mdb This file is a backup copy of the existing ultra32 mdb file before database conversion occurred ultra32_post date_time mdb This file is a copy of the converted database created immediately after the database conversion is completed e ultra32_AuditFile txt This file is only created if the database being converted is a ver sion below version 4 8 This file logs all changes made to the database during the upgrade process and also logs any deletions if any of corrupted data In a 100 suc cessful upgrade that involves no corrupted data this file will simply show changes to the database schema under such headings as Delete Relations Add New Columns etc If corrupted data was removed it will be listed in this text file Note To view the contents of this file use Wordpad or MS Word e ultra32_UnitInfo xml This file is only cre
23. ther cus tom MON screens UltraSite32 will attempt to follow those links and upgrade the MON screens to which they are linked You will need to be connected to the site whose MON screens you are opening so that the conversion process can properly follow each link Also all E2s must be on line and communicating if any E2s are offline UltraSite32 will not be able to follow links More information about MON2 files and rules you must follow when editing custom screens is available in Graphical Status Screen Editing File Format Change MON is now MON2 on page 14 Document Part 026 4127 Rev 4 02 MAY 2012 Page 8 of 15 2012 Emerson Climate Technologies Retail Solutions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above E2 Installation and Upgrade Instructions UltraSite32 4 81 or above must be used to perform firmware upgrades for all E2s you plan to upgrade to version 2 81 or above If you have not yet installed UltraSite32 4 81 or above on the PC you will use to upgrade the E2 firmware follow the instructions in the above section to install the latest version of UltraSite32 The firmware upgrade process is the same for versions 2 81 and above as it is for previous E2 versions Follow the instructions in Technical Bulletin 026 4306 Updatin
24. tions Inc This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above given the same name as an application already in the E2 during the upgrade an underscore _ will be appended to the end of the newly named application so that it will be unique A Service Log entry will also be written to log the name change Document Part 026 4127 Rev 4 02 MAY 2012 Page 15 0f 15 This document may be photocopied for personal use Visit our website at http www emersonclimate com for the latest technical documentation and updates The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability Emerson Climate Technologies Retail Solutions Inc and or its affiliates collectively Emerson reserves the right to modify the designs or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user 026 4127 02 MAY 2012 Emerson is a trademark of Emerson Electric Co 2012 Emerson Climate Tec
25. update advisory Advisory for Installers of E2 2 81 and UltraSite32 4 81 and Above Overview This document applies to all users who have E2 version 2 72F01 or earlier who are upgrading to aversion 2 81F01 or later and all users who have UltraSite32 version 4 72 or earlier who are upgrading to a version 4 81 or higher This document contains special instructions and warnings about changes introduced into the 2 8x 4 8x revisions of E2 and UltraSite32 Please read the entire document before upgrading WARNINGS NOTICES PLEASE READ e DOWNGRADING TO 4 7 OR LOWER AFTER INSTALLING 4 81 OR HIGHER REQUIRES ASSISTANCE FROM RETAIL SOLUTIONS page 2 e IF USING FSD CALL RETAIL SOLUTIONS TECH SUPPORT BEFORE UPGRADE page 9 e DONOT CLEAN OUT E2 BEFORE OR AFTER UPGRADE TO 2 81 OR ABOVE page 9 e IF YOU ARE A USER OF ULTRASITE32 IN NETWORK MODE REFER TO TECHNICAL BUL LETIN 026 2503 NETWORK MODE INSTALLATION FOR UltraSite32 4 81 AND ABOVE Important Changes made since E2 2 81 and UltraSite32 4 81 e UltraSite32 is not compatible with Windows Server 2000 page 3 e New Setpoint Export Format 002 For E2 2 81 Setpoint File page 9 e Board Naming and Data Pointer Changes page 10 e Board Point Pointers In UltraSite32 Display in a Different Format E2 2 81 and above only page 10 e View E1 E2 Setpoints Operation page 11 e Updated Message Boxes page 11 e Changes to Advisory Duplication Filtering for E2 Alarm Annunciators using U