1. ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044_ENG Revision 2 010 Page 11 of 33 Industrial Electronic Devices USE OF COMPOSITOR SW67044 To configure the Converter use the available software that runs with Windows called SW67044 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present ans i new project ee e on our web site The software works with MSWindows XP Vista SEES bd TERR Seven 8 32 64bit ig Set Communication Step 2 When launching the SW67044 the right window appears Fig 2 a Step3 _M Bus Note It is necessary to have installed Net Framework 4 Step 4 www ADFweb com Figure 2 Main window for SW67044 NEW PROJECT OPEN PROJECT The New Project button creates the folder which contains the entire device configuration Project name Example Select directory of project Wf OK M Cancel Projects gt ad Example 1 gt d house 12 b di PC vecchio gt Er A device configuration can also be imported or exported gt Bb Sontex Supercal 531 To clone the configurations of a Programmable M Bus Master Modbus TCP Slave b gt di Sontex Supercal 531 FF wes f f bee i Converter in order to configure another device in the same manner it is necessary to Test Byte dopo OF i a opa maintain t
2. Data type F Hour 0 23 Day 1 31 Month 1 12 Keano a Time Invalid 0 Valid 1 Invalid Summer Time O Standard Time 1 Summer Time Reserved 0 Data type G Month 1 12 Year 0 99 For example if you have defined e Type of Data Energy J Function Field Instantaneous Value Dimension 32 bit Modbus Register 150 Register 151 declared implicitly because the dimension is 32 bit Modbus Re Scale 152 After the request in Modbus register 150 you read 0x0004 in 151 you read 0x5678 and in register 152 is write 0x0006 The value obtained is 284280 x10 J ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 27 of 33 Industrial Electronic Devices MANUFACTURER SPECIFIC DATA Using this function is possible to save into Modbus registers the part of M Bus frame that is coded like Manufacturer Specific Data Usually these data are at the end of the frame and after a DIF byte with the value OxOF of Ox1F Here an example of the frame and the mentioned data hexadecimal 68 20 20 68 08 01 72 78 56 34 12 86 04 05 00 08 00 00 00 OC 78 78 56 34 12 OF 11 22 33 44 55 66 77 88 99 AA 74 16 If you want to save all ten bytes from Modbus register 200 you have to compile the fields Manufacturer Specific Data Length MSD 1 241 and Offset MSD 0 240 in this way Manufacturer Specific Data 200 Length
3. M Bus Master PROFIBUS Slave Converter www adfweb com Product HD67053M M Bus Concentrator Datalogger www adfweb com Product HD67054M M Bus Slave Modbus Master Converter www adfweb com Product HD67059M 232 Do you need to choose a device Do you want help www adfweb com Cmd helpme User Manual ADFweb com S r l Industrial Electronic Devices INDEX INDEX UPDATED DOCUMENTATION REVISION LIST WARNING TRADEMARKS SECURITY ALERT EXAMPLE OF CONNECTION CONNECTION SCHEME CHARACTERISTICS POWER SUPPLY FUNCTION MODES LEDS MODBUS TCP M BUS USE OF COMPOSITOR SW67044 NEW PROJECT OPEN PROJECT SET COMMUNICATION M BUS MANUFACTURER SPECIFIC DATA UPDATE DEVICE ONLY FOR HD67044 B2 SERIES MECHANICAL DIMENSIONS ORDER CODES ACCESSORIES DISCLAIMER OTHER REGULATIONS AND STANDARDS WARRANTIES AND TECHNICAL SUPPORT RETURN POLICY PRODUCTS AND RELATED DOCUMENTS ADFweb com S r l 9 ODMNDUAWNNNNNYG User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 2 of 33 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this document With this Document Code go to web page www adfweb
4. Third Variable G 0x00 Data Byte 20f4 0x00 Data Byte 10f4 Other Variables 0x55 Check Sum 0x16 Stop Byte ADFweb com S r l Industrial Electronic Devices Copy PASTE AND DELETE ITEMS By pressing the right button of the mouse over an item Variable or Node it is possible to Copy Paste and Delete It is possible to Copy a variable from a Node and copy it to another Node or copy a Variable from a project and paste in another one It is also possible to copy an entire Node with all its Variables Note By pressing the Import Network button is possible to import the file generated by the Analyzer HD67031 ADFweb com S r l M Bus Network 1 test uA HID 5 test2 H ID 10 test3 nf OK User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 20 of 33 Copy Variable Paste Variable Copy Node Paste Node Delete tem XM CANCEL Import Network ies tA eia rables mn Saee Fata vi Enable Variable Dimension bit a Modbus Register 100 Modbus Re Scale Time Point Use five Modbus Register YY lo MM From BCD to Integer Convert in Float Position MODIFY VARIABLE iy User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 21 of 33 Industrial Electronic Devices Possible choices for the fields used to create a variable Type of Data Function Field
5. 10 Offset O On Modbus you will have this result reg 200 1122h reg 201 3344h reg 202 5566h reg 203 7788h reg 204 99AAh If you want to save only the byte 33 and 44 in the Modbus register 200 you have to compile the fields Manufacturer Specific Data Length MSD 1 241 and Offset MSD 0 240 in this way Manufacturer Specific Data 200 Length 2 Offset 2 On Modbus you will have this result reg 200 3344h If you want to save only the byte 66 in the Modbus register 200 you have to compile the fields Manufacturer Specific Data Length MSD 1 241 and Offset MSD 0 240 in this way Manufacturer Specific Data 200 Length 1 Offset 5 On Modbus you will have this result reg 200 6600h ADFweb com S r l Industrial Electronic Devices UPDATE DEVICE ONLY FOR HD67044 B2 SERIES By pressing the Update Device button it is possible to load the created Configuration into the device and also the Firmware if necessary User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 28 of 33 Insert the IP Address of HD67044 B2 If you don t Know the actual IP address of the device you have to use this procedure 92 aes 2 pa Turn off the Device Put Dip1 of Dip Switch A at ON position Turn on the device Connect the Ethernet cable Insert the IP 192 168 2 205 Press the
6. Bus ACCESSORIES Order Code APWO20 Power Supply for M Bus Master device that supports up to 20 Slaves Order Code APWO40 Power Supply for M Bus Master device that supports up to 40 Slaves Order Code APWO8O Power Supply for M Bus Master device that supports up to 80 Slaves Order Code APW160 Power Supply for M Bus Master device that supports up to 160 Slaves Order Code APW250 Power Supply for M Bus Master device that supports up to 250 Slaves ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 32 of 33 Industrial Electronic Devices DISCLAIMER All technical content within this document can be modified without notice The content of the document is a under continual renewal For losses due to fire earthquake third party access or other accidents or intentional or accidental abuse misuse or use under abnormal conditions repairs are charged to the user ADFweb com S r l will not be liable for accidental loss of use or inability to use this product such as loss of business income ADFweb com S r l shall not be liable for consequences of improper use OTHER REGULATIONS AND STANDARDS WEEE INFORMATION Disposal of old electrical and electronic equipment as in the European Union and other European countries with separate ps collection systems m his symbol on the product or on its packaging indicates that this product may not be treated as household rubbish
7. Instead it should be taken to an applicable collection point for the recycling of electrical and electronic equipment If the product is disposed correctly you will help prevent potential negative environmental factors and impact of human health which could otherwise be caused by inappropriate disposal The recycling of materials will help to conserve natural resources For more information about recycling this product please contact your local city office your household waste disposal service or the shop where you purchased the product RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE 4 The device respects the 2002 95 EC Directive on the restriction of the use of certain hazardous substances in OHS electrical and electronic equipment commonly referred to as Restriction of Hazardous Substances Directive or ROHS 2002 95 EC CE MARKING The product conforms with the essential requirements of the applicable EC directives ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 33 of 33 Industrial Electronic Devices WARRANTIES AND TECHNICAL SUPPORT For fast and easy technical support for your ADFweb com SRL products consult our internet support at www adfweb com Otherwise contact us at the address support adfweb com RETURN POLICY If while using your product you have any problem and you wish to exchange or repair it please do the following Obtain a Product Return
8. Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve months it will be repaired or exchanged and returned within three weeks If the product is no longer under warranty you will receive a repair estimate ADFweb com S r l Via Strada Nuova 17 IT 31010 Mareno di Piave TREVISO Italy Phone 39 0438 30 91 31 Fax 39 0438 49 20 99 www adfweb com ADFweb com S r l
9. Ping button must appear Device Found Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn off the Device Put Dip1 of Dip Switch A at OFF position Turn on the device At this point the configuration firmware on the device is correctly updated If you know the actual IP address of the device you have to use this procedure 4 4 Turn on the Device with the Ethernet cable inserted Insert the actual IP of the Converter Press the Ping button must appear Device Found Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK the device automatically goes at Normal Mode ADFweb com S r l Check the Connection the device Update Device Options rl Firmware af Read Firmware when finish il Project ral Read Project when finish Execute update firmware INIT Waiting e FIRMWARE Waiting PROJECT Waiting Figure 5 Update device windows iy User Manual M Bus Master Modbus TCP Slave Document code MN67044_ENG Revision 2 010 Page 29 of 33 Industrial Electronic Devices At this point the configuration firmware on the device is correctly update lt K Note When yo
10. have to select None otherwise see the section Swap Identification page 24 of this document for select the swap mode ADFweb com S r l go M CANCEL Import Network Figure 4 M Bus Network window User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 14 of 33 Industrial Electronic Devices If the field Send SND_NKE is checked the Converter send the SND_NKE frame to start the communication Inthe field Send Reset App Is checked the Converter send the Application Reset command to the slave Inthe field Variables List it is possible to select which type of variables definition to use If is selected By Type it is necessary to fill all fields in the section Variables with the correct values otherwise if By Position is selected you can insert the progressive number of the variable that you need page 19 for more information Inthe field Cut after it is possible to select after how many frames stops data requests It is used when the slave has got many data frames and you don t need to read all them Inthe field Manufacturing Specific Data is possible to insert the starting address Modbus from which you want to save the information of Manufacturer Specific after DIF OxOF or DIF Ox1F Inthe field Length MSD 1 241 is possible to insert the length of the data you need to save Inthe fie
11. is not necessary you have to insert the number O in this field It is possible to insert from Modbus Register 1 to 60000 M Bus Network GID 1 test WAR war2_1 GID S test HID 10 test3 ff OK User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 17 of 33 Variables Enable Variable Lenath variabe Len Modbus Register Dimension bit Modbus Re Scale Time Point X CANCEL Import Network C Use five Modbus Register From BCD to Integer Convert in Float Position MODIFY VARIABLE If the field Use Five Modbus Register and the Type of Data is Time Point it is possible to read the information of Year Month Day Hour Minutes on five consecutive Modbus registers without decoding the data if not selected the values are the same of the reply of the slave device so coded with a determinate structure page 26 for more information You have to insert the first Modbus Register ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 18 of 33 Industrial Electronic Devices If the field From BCD to Integer is checked the Converter converts the BCD value of variable in Integer format This happens only if the variable is in BCD format if it isn t nothing changes If the field SWAP is checked the byte of data of that variabl
12. of the Converter used for going out to the net Inthe field TCP Port insert the number of the port used for communicate M Bus Baudrate Parity The means of the fields for M Bus are M Bus Poll on request Cyclic request Inthe field Baudrate it is possible to select the baudrate of the M Bus line Inthe field Parity it is possible to select the parity of the line Delay If the field M Bus Poll on request is checked the Converter makes the request only if a Modbus Node State value when slave device register is requested otherwise if Cyclic request is checked the Converter makes the request in is not present M bus network each time the time defined under passes Inthe field Delay insert a time expressed in seconds This time is used for the Cyclic request In the field Node State value when slave device is not present it is possible to insert the value to assign to the Node State when the Converter doesn t find the interrogated slave M Bus A 3 Set Communication window 100 H A ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 13 of 33 Industrial Electronic Devices M BUS By Pressing the M Bus button from the main window for SW67044 Fig 2 the window M Bus Network appears Fig 4 SECTION NODES In the section Nodes it is possible to creat
13. the LEDs will have specifics functions see LEDS section Dip Switch A Dip1 Functioning Mode Normal Mode Boot Mode Dip2 Must be at ON A Warning Dip2 of Dip Switch A must be at ON position for working even if the Ethernet cable isn t inserted ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 9 of 33 Industrial Electronic Devices LEDS The device has got two LEDs that are used to give information of the functioning status The various meanings of the LEDs are described in the table below LED Normal Mode Boot Mode 1 Device State green Blinks slowly 1Hz Blinks quickly 2 M Bus Comm Suite dalek wich Aep OA PO Blinks quickly Bus request arrives 3 M Bus Error Paame a anan me dear one Blinks quickly Bus interrogation isn t arrived 4 Modbus Comm enange gt ore Wen IeceWwee Blinks quickly correct Modbus request ON Ethernet cable connected ON Ethernet cable connected 5 Ethernet Link green OFF Ethernet cable disconnected OFF Ethernet cable disconnected 0008 80000088 1 Power Supply M Bus MAC 10 64 E2 07 1E 19 Ov 4 Serial Nr B7481 ISIA On LED Fr ery pe Chrwite Stat at i 2 As A n Hius Comm re Tr Pie aes Est ween eas pata 3 Modes Comm www ADFweb com a M Bus Master Modbus TCP Stave Converter gt M Bus Error a HD67044 B2 20 l i Dip Sw
14. with the installation assembly commissioning and operation of this equipment and who have appropriate qualifications for their job RESIDUAL RISKS The device is state of the art and is safe The instruments can represent a potential hazard if they are inappropriately installed and operated by untrained personnel These instructions refer to residual risks with the following symbol This symbol indicates that non observance of the safety instructions is a danger for people that could lead to serious injury or A death and or the possibility of damage CE CONFORMITY The declaration is made by our company You can send an email to support adfweb com or give us a call if you need it ADFweb com S r l Industrial Electronic Devices EXAMPLE OF CONNECTION HD67044 B2 xxx ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 4 of 33 S GEE 54i comme OLL LEL Nma Slave M Bus 004185 Se User Manual AL Document code MN67044 ENG M Bus Master Modbus TCP Slave Revision 2 010 Page 5 of 33 Industrial Electronic Devices i CONNECTION SCHEME Dipi Functioning Mode E Normal Mode Boot Mode Dip2 Must be at ON M Bus MAC 10 64 E2 07 1E 19 Fa Vv W Serial Hr B7481 14 20 AC Qn LED on 10 ISV Be M Bus Master Modbus TCP Slave Convert Connector1 Power Supply OV Grou
15. 481 LS UY AC LS 60 mm 2 36 inch Figure 7 Mechanical dimensions scheme for HD67044 B2 xxx ADFweb com S r l iy User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 31 of 33 Industrial Electronic Devices ORDERING INFORMATIONS The ordering part number is formed by a valid combination of the following HD67044 B 2 xxx L Maximum number of slaves supported 20 up to 20 standard slaves 1 5mA consumption connected to M Bus 40 up to 40 standard slaves 1 5mA consumption connected to M Bus 80 up to 80 standard slaves 1 5mA consumption connected to M Bus 160 up to 160 standard slaves 1 5mA consumption connected to M Bus 250 up to 250 standard slaves 1 5mA consumption connected to M Bus Connectors Type 2 Fixed Screw Terminal Enclosure Type B Modulbox 4M 35mm DIN Rail mounting Device Family HD67044 M Bus Master Modbus TCP Slave Converter Order Code HD67044 B2 20 Converter M Bus Master Modbus TCP Slave up to 20 slaves connected to M Bus Order Code HD67044 B2 40_ Converter M Bus Master Modbus TCP Slave up to 40 slaves connected to M Bus Order Code HD67044 B2 80_ Converter M Bus Master Modbus TCP Slave up to 80 slaves connected to M Bus Order Code HD67044 B2 160 Order Code HD67044 B2 250 Converter M Bus Master Modbus TCP Slave up to 160 slaves connected to M Bus Converter M Bus Master Modbus TCP Slave up to 250 slaves connected to M
16. User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 1 of 33 Industrial Electronic Devices User Manual Waeunoceeced Revision 2 010 zi EAIA ere O AUA S 1 38VDC MAC 10 64 E2 07 18 0C www ADFweb com HD6 7044 B2 M Bus Ethernet Converter LUDDIOU LOTUS 0 HD67030 B2 2 KoHS Ady M Bus Master Modbus TCP Slave Converter loa ofr Order Code HD67044 B2 20 HD67044 B2 40 HD67044 peserene _eHEDET BE ads nro B2 80 HD67044 B2 160 HD67044 B2 250 jz For Website information www adfweb com Product HD67044 B2 For Price information For other M Bus products see also the following link www adfweb com Price HD67044 B2 20 e ter M Bus www adfweb com Price HD67044 B2 40 www adfweb com Product HD67021 RS232 www adfweb com Price HD67044 B2 80 www adfweb com Product HD67022 RS485 www adfweb com Price HD67044 B2 160 www adfweb com Product HD67030 Ethernet www adfweb com Price HD67044 B2 250 Analyzer amp Scanner M Bus www adfweb com Product HD67031 Benefits and Main Features M Bus Repeater Isolator Very easy to configure www adfweb com Product HD67032 Up to 250 standard M Bus devices connected to the Converter Converter M Bus Master Modbus Slave www adfweb com Product HD67029M 232 on RS232 Power Supply 15 21V AC or 18 35V DC www adfweb com Product HD67029M 485 on RS485 Temperature range 40 C 85 C 40 F 185 F
17. _ Energy Wh _ Instantaneous Value _ Energy J _ Minimum Value _ Volume m Maximum Value Mass Kg _ Value During Error State On Time Operating Time Power W Dimension bit _ Power J h _ 8 _ Volume Flow m h 16 _ Volume Flow Ext m min 24 _ Volume Flow Ext m s 32 Mass Flow Kg h 32 real Flow Temperature C 48 Return Temperature C _ 64 Temperature Difference K _ Variable Length _ External Temperature C _ Pressure bar _ Averaging Duration _ Actuality Duration _ Type of data in VIFE _ Time Point _ VIF is in ASCII Unit for H C A _ Fabrication No _ Enhaced Identification _ Bus Address ADFweb com S r l Industrial Electronic Devices VIFE Not Selected Credit of the nominal local legal currency units _ Debit of the nominal local legal currency units Access Number transmission count Medium as in fixed header _ Manufacturer as in fixed header Parameter set identification _ Model Version _ Hardware Version Firmware Version Software Version _ Customer Location Customer _ Access Code User Access Code Operator _ Access Code System Operator _ Access Code Developer _ Password _ Error flags binary _ Error mask _ Digital Output binary _ Digital Input binary Baudrate Baud _ response delay time bittimes Retry _ First storage for cyclic storage _ La
18. com download and search for the corresponding code on the page Click on the proper Document Code and download the updates REVISION LIST Revision Date Author Chapter Description 1 030 04 03 2011 Fl All Software changed v1 300 2 000 03 12 2012 Fl All New hardware version 2 001 29 03 2013 Fl All Added new chapters 2 010 19 09 2014 Fl All Software changed v1 800 WARNING ADFweb com reserves the right to change information in this manual about our product without warning ADFweb com is not responsible for any error this manual may contain TRADEMARKS All trademarks mentioned in this document belong to their respective owners User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 3 of 33 Industrial Electronic Devices SECURITY ALERT GENERAL INFORMATION To ensure safe operation the device must be operated according to the instructions in the manual When using the device legal and Safety regulation are required for each individual application The same applies also when using accessories INTENDED USE Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator i e independent limit switches mechanical interlocks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar
19. d the unit it is recommended to not cover the paths of air Take care to not cover the fan It is recommended to put the device into a ventilated cabinet ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 7 of 33 Industrial Electronic Devices POWER SUPPLY The devices can be powered at 15 21V AC and 18 35V DC The consumption depends to the code of the device For more details see the two tables below Consumption at 24V DC vevice No Load CW VAl er os er A 5 HD67044 B2 160 14 This value is with all the Slave M Bus devices of the code 20 40 80 160 250 connected to the line Caution Not reverse the polarity power V Positive wire lv AC min 15V max 21V vV DC min 18V max 35V ES HD67044 B2 xxx ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044_ENG Revision 2 010 Page 8 of 33 Industrial Electronic Devices O y FUNCTION MODES The device has got two functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dipi of Dip Switch A at ON position is used for upload the Project and or Firmware For the operations to follow for the updating see UPDATE DEVICE section According to the functioning mode
20. e are swapped Example from 0x01020304 to 0x04030201 Inthe field Position insert the number of the variable that you want on Modbus ADFweb com S r l iy User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 19 of 33 Industrial Electronic Devices Example 0x68 Start Byte OxBD L Fied OxBD L Field 0x68 Start Byte 0x08 C Field 0x02 A Field 0x72 CI Field Identification Number or Secondary Address put in the Identification Number Byte 3of4 selected register if Identification Number is checked 0x45 4 Identification Number Byte 2of4 0x28 Identification Number Byte 1of4 0x4D Manufacturer Byte 2of2 Ox6A Manufacturer Byte 1of2 0x81 Version 0x04 Medium Ox3E Access Number 0x71 0x65 Fixed Data Header Status of the meter put in the selected register if Node 0x00 Signature Byte 2of2 0x00 Signature Byte 1of2 State is checked 0x04 DIF 0x79 VIF Identification 0x00 Data Byte 4of4 0x00 Data Byte 3of4 First Variable 0x00 Data Byte 2of4 0x00 Data Byte 1of4 0x04 DIF 0x06 VIF Energy 0x00 Data Byte 4of4 0x00 Data Byte 30f4 Second Variable 2 0x00 Data Byte 2of4 0x00 Data Byte 10f4 To be use in the Position field 0x44 DIF 0x06 VIF Energy 0x00 Data Byte 40f4 0x00 Data Byte 30f4
21. e the nodes of M Bus line In order to create a new node it is necessary to Enable Node description te select which address use selecting Primary ID VAR var2_1 e a or Secondary ID to makes the requests and BAD mn testa Wee DNs then insert the Primary Address from 1 to 250 7 397 tst a hode atie or the Secondary Address from O to 99999999 S rioni cion NomBer of M Bus device Convert BCD in Integer Identification Num In the field Description it is possible to write a Swap Identification Num None short description of the node Send SND_NKE In the field Node State it is possible to insert So By Type Fl an address Modbus that contain the Status of the it ka ame Gomes M Bus device If you don t need to know this put ee a this register at O nse ER In the field Identification Number it is Offset MSD 0 240 possible to insert an address Modbus that contain the Identification Number of the M Bus device You have to read two consecutive registers for knowing the value If you don t need to know this put this register at 0 If the field Convert BCD in Integer Identification Num is checked the Converter converts the Identification Number that is normally expressed in BCD in a Integer In the field Swap Identification Num it is possible to select the swap mode of the Identification Number If swap isn t necessary you
22. e variable the button ADD VARIABLE must be pressed In order to modify a created variable it is necessary to select the desired variable change the wrong items and then press the MODIFY VARIABLE button ADFweb com S r l AL Industrial Electronic Devices SECTION VARIABLES BY POSITION Selecting the desired node it is possible to add a variable In order to create a new variable it is necessary to fill these items al To use the created variable the field Enable Variable must be checked If you have created a variable but for the moment it is unused it is possible to uncheck the field Enable Variable without delete it In the field Description it is possible to write a description of the variable it isn t a necessary information it helps the readability of the tree of network The field Dimension is used to select the dimension of the variable 8 16 24 32 32 real 48 64 bit Variable Length In the field Length Variable Len insert the length of the data in the case of the dimension is Variable Length In the field Modbus Register it is necessary to insert the value of Modbus Register that contains the data of the M Bus device It is possible to insert from Modbus Register 1 to 60000 In the field Modbus Re Scale it is necessary to insert the value of Modbus Register that contains the value of measure scale If the scale
23. ent code MN67044 ENG Revision 2 010 Page 24 of 33 Industrial Electronic Devices Swap Identification This field is used for select the Swap mode of Identification Number At the moment there are these possibilities None Type l Examples Identification Number Secondary Address 12345678 Address Register 1000 Convert BCD in Integer Identification Num not checked None Type 1000 0x1234 1000 0x5678 1001 0x5678 1001 0x1234 Identification Number Secondary Address 12345678 Address Register 1000 Convert BCD in Integer Identification Num checked None Type 1000 0x00BC 1000 0x614E 1001 0x614E 1001 OxOOBC ADFweb com S r l iy User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 25 of 33 Industrial Electronic Devices To Know the meaning of value read in the Modbus Re Scale field you must follow this table x Value read in Modbus Re Scale Seconds On Time Minutes Hours ays D Oo Oo Eee aI EM eratuce 0 001 C to 1 C 1 mbar to 1000 mbar W C Return Temperature 0 001 C to 1 C K C Averaging Duration coded like On Time Actuality Duration codedlikeOnTime x Date Data type G Data type F Time Point xsi Time amp Date Unit for H C A ADFweb com S r l iy User Manual M Bus Master Modbus TCP Slave Document code MN67044_ENG Revision 2 010 Page 26 of 33 Industrial Electronic Devices
24. he folder and all its contents b ab Trisko_rev2 To clone a project in order to obtain a different version of the project it is sufficient to b Jo Zenner Zelsius Slave Fedezz duplicate the project folder with another name and open the new folder with the button Open Project ADFweb com S r l iy User Manual M Bus Master Modbus TCP Slave Document code MN67044_ENG Revision 2 010 Page 12 of 33 Industrial Electronic Devices SET COMMUNICATION This section define the fundamental communication parameters of two Buses Modbus and M Bus By Pressing the Set Communication button from the main window for SW67044 Fig 2 the window oo Set Communication appears Fig 3 The window is divided in three sections the first used for select the device one for the Modbus TCP Ethernet and the other for the M Bus Ethernet IP Address The means of the fields for Select Device are h92 se e pa If the hardware in your possession is the HD67044M xxx you have to select HD67044M SubNet Mask otherwise if the hardware in your possess is the HD67044 B2 xxx you have to select HD67044 ss 255 255 o W B2 Gateway 502 The means of the fields for Ethernet are Inthe field IP Address insert the IP address of the device TCP Port Inthe field Subnet Mask insert the Subnet Mask If the field Gateway is checked it is possible to insert in the field under the IP Address
25. ices In the field Storage Number if it is necessary it is possible to insert the value of storage counter of that variable With this field the slave can indicate and transmit various stored counter states or historical values in the order in which they occur In the field Tariff if it is necessary it is possible to insert the value of the tariff of that variable The Tariff is used for indicates from which device the data come Inthe field VIFE it is possible to select a sub type of Type of Data If the field Use Five Modbus Register and the Type of Data is Time Point it is possible to read the information of Year Month Day Hour Minutes on five consecutive Modbus registers without decoding the data if not selected the values are the same of the reply of the slave device so coded with a determinate structure You have to insert the first Modbus Register If the field From BCD to Integer is checked the Converter converts the BCD value of variable in Integer format This happens only if the variable is in BCD format if it isn t nothing changes If the field Convert in Float is checked the Converter converts the data into Float type Every variable occupies two consecutive Modbus Registers and the first one is the one defined in Modbus Register In this case the float value is multiplied by the Modbus Re Scale automatically Having completed this fields to add th
26. iteh A ETHERNET A ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 10 of 33 Industrial Electronic Devices MODBUS TCP The Modbus TCP connection must be made using Connector3 of HD67044 B2 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the use of a cross cable M BUS The M Bus is a unpolarized bus A two wire standard telephone cable JYStY N 2 0 8 mm is used as the transmission medium for the M Bus The maximum distance between a slave and the repeater is 350m this length corresponds to a cable resistance of up 29Q This distance applies for the standard configuration having Baud rates between 300 and 9600 Baud and a maximum of 250 slaves The maximum distance can be increased by limiting the Baud rate and using fewer slaves but the bus voltage in the space state must at no point in a segment fall below 12V because of the remote powering of the slaves In the standard configuration the total cable length should not exceed 1000m in order to meet the requirement of a maximum cable capacitance of 180nF Taken from M Bus specifics
27. ld Offset MSD 0 240 is possible to insert the offset from where save the data For more information about Manufacturer Specific Data functions see page 27 After that pressing the ADD NODE button a new node appears in the left side of the window In order to modify a created node it is necessary to select the desired node change the wrong items and then press the MODIFY NODE button ADFweb com S r l iy User Manual M Bus Master Modbus TCP Slave Document code MN67044_ENG Revision 2 010 Page 15 of 33 Industrial Electronic Devices SECTION VARIABLES By TYPE Selecting the desired node it is possible to add a variable In order to create a new variable it is necessary to fill M Bus Network these items EID 1 test W Enable Variable To use the created variable the field Enable VAR var2_4 e ote sa Variable must be checked If you have created a ID 5 test2 virasctrstring 7 variable but for the moment it is unused it is BE Function teks 6 pees possible to uncheck the field Enable Variable gs Dimension bit ja without delete it Length Variable eno ooo In the field Description it is possible to write a Unit lo description of the variable it isn t a necessary aii Revels 9 300 information Modbus Re Scale it helps the readability of the tree of network z co p at o The field Type of Data is used to select the uni
28. nd V Positive wire VAC min 15V max 21V V DC min 18V max 35V Figure 1 Connection scheme for HD67044 B2 xxx ADFweb com S r l H Yellow ae M Bus Error iy User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 6 of 33 Industrial Electronic Devices CHARACTERISTICS The HD67044 B2 xxx is a M Bus Master Modbus TCP Slave Converter It allows the following characteristics Electrical isolation between Ethernet and M Bus Mountable on 35mm Rail DIN Power Supply 15 21V AC or 18 35V DC Temperature range 40 C to 85 C t 4 At the Converter can be connected up to 250 standard M Bus devices This number depends of the code expressed by the xxx number HD67044 B2 20 support up to 20 M Bus devices HD67044 B2 40 support up to 40 M Bus devices HD67044 B2 80 support up to 80 M Bus devices HD67044 B2 160 support up to 160 M Bus devices HD67044 B2 250 support up to 250 M Bus devices In the case of HD67044 B2 160 the device must be mounted on 35mm DIN rail which is horizontally mounted on a wall or cabinet back plate To avoid obstructions to the airflow around the unit it is recommended to not cover the paths of air In the case of HD67044 B2 250 the device must be mounted on 35mm DIN rail which is horizontally mounted on a wall or cabinet back plate These units have a fan in the top of the enclosure To avoid obstructions to the airflow aroun
29. nt per output pulse on output channel _ per liter per m 3 _ per kg _ per K Kelvin per kWh per GJ per kW per K I Kelvin liter _ per V Volt per A Ampere multiplied by sek _ multiplied by sek V _ multiplied by sek A _ start date time of _ VIF contains uncorrected unit instead of corrected unit Accumulation only if positive contributions _ Accumulation of abs value only if negative contributions _ upper lower limit value of exceeds of lower upper limit _ Date time of begin end of first last lower upper limit exceed ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 23 of 33 Duration of limit exceed Duration of first last Date time of first last begin end Multiplicative currection factor Additive correction constant unit of VIF offset Moltiplicative correction factor 10 3 future value next VIFE s and data of this block are manufacturer specific None Too many DIFE s Storage number not implemented Unit number not implemented Tariff number not implemented Function not implemented Data class not implemented Data size not implemented Too many VIFE s Illegal VIF Group Illegal VIF Exponent VIF DIF mismatch Unimplemented action No data available undefined value Data overflow Data underflow Data error Premature end of record iy User Manual M Bus Master Modbus TCP Slave Docum
30. st storage for cyclic storage _ Size of storage block Storage interval sec s day s _ Storage interval month s _ Storage interval year s Duration since last readout sec s day s Start date time of tariff _ Duration of tariff nn 01 11 min to day _ Period of tariff sec s to day s ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 22 of 33 Period of tariff months s Period of tariff year s dimensionless no VIF Volts Ampere Reset counter Comulation counter Control signal Day of week Week number Time point of day change State of parameter activation Special supplier information Duration since last comulation hour s year s Operation time battery hour s year s Date and time of battery change Energy MWh Energy GJ Volume Mass Volume 0 1 feet 3 Volume 0 1 american gallon Volume 1 american gallon Volume flow 0 001 american gallon min Volume flow 1 american gallon min Volume flow 1 american gallon h Power MW Power GJ h Flow Temperature Return Temperature Temperature Difference External Temperature Cold Warm Temperature Limit F Cold Worm Temperature Limit C Cumul count max power per second Industrial Electronic Devices _ per minute per hour per day per week per month per year _ per revolution measurement _ increment per input pulse on input channel _ increme
31. t VIFE Not Selected gt of measure A ee In the field VIF ASCII String insert the string _ Use five Modbus Register of VIF It is possible to use this field only if the wo e bp Type of Data is VIF is in ASCII HH mo In the field Function Field it is necessary to l From BCD to Integer select the type of data C Convert in Float The field Dimension is used to select the dimension of the variable 8 16 24 32 32 real 48 64 bit Variable Length In the field Length Variable Len insert the length of the data in the case of the dimension is Variable Length lt ae M CANCEL Import Network Inthe field Unit if it is necessary it is possible to select the unit of that variable The Unit is used for indicates from which device the data come Inthe field Modbus Register it is necessary to insert the value of Modbus Register that contains the data of the M Bus device It is possible to insert from Modbus Register 1 to 60000 Inthe field Modbus Re Scale it is necessary to insert the value of Modbus Register that contains the value of measure scale If the scale is not necessary you have to insert the number O in this field It is possible to insert from Modbus Register 1 to 60000 ADFweb com S r l User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 16 of 33 Industrial Electronic Dev
32. u install a new version of the software if it is the first time it is better you do the update of the Firmware in the HD67044 B2 xxx device TA Note When you receive the device for the first time you also have to update the Firmware in the HD67044 B2 xxx device Warning If the Fig 6 appears when you try to do the Update try these points before seeking assistance Try to repeat the operations for the update Try with another PC Try to restart the PC If you are using the program inside a Virtual Machine try to use in the main FIRMWARE PROTECTION Operating System If you are using Windows Seven or Vista or 8 make sure that you have the administrator privileges Take attention at Firewall lock Check the LAN settings INIT PROTECTION Ver 1 002 PROJECT PROTECTION Figure 6 Protection window L In the case of HD67044 B2 xxx you have to use the software SW67044 www adfweb com download filefold SW67044 zip ADFweb com S r l Industrial Electronic Devices MECHANICAL DIMENSIONS or fH 15V BC 95 mm 3 74 inch MBs Master Modbus TCP Slave Converter m HD67044 82 20 E Dip 5witch A _ ETHERNET 71 mm 2 79 inch Housing PYC Weight 200g Approx User Manual M Bus Master Modbus TCP Slave Document code MN67044 ENG Revision 2 010 Page 30 of 33 O0000C00008 Power Supply M Bus MAC 10 64 F2 07 1E 19 OW V Serial Nr B7