Home

N30 Supervisory Controller User`s Manual: Chapter 30: Working

image

Contents

1. Password Priority Filter B 4 Items SNR Dial Out Level 80 Category Filter B 5 Items Msg Type Filter B 3 Items Login ID Phone Number F3 Save F4 Cancel Page Enter an alphanumeric string Figure 30 1 Remote Destination Object Configuration Screen 1 30 8 N30 Supervisory Controller User s Manual Aspen Elementary ADMIN Wed 17 Jan 2001 10 35 cst Modem Config Object ieee Remote Device Name Process Identifier Max SNR Queue Za Ack Required True F3 Save F4 Cancel Page Enter object name Figure 30 2 Remote Destination Object Configuration Screen 2 4 Fill in the fields using Table 30 2 Table 30 2 Remote Destination Object Attributes Screen Area Attribute Required Default Options Range Object Object No Blank Maximum 32 characters Name Invalid characters If not completed the system assigns a name Description No Blank Maximum 40 characters Object Type Yes Remote The default is preset and cannot be changed Destination Object Yes HVAC HVAC Fire Security Services Administrative Category Continued on next page Screen Area Cont Engineering Values Attribute Port Number Dial Connect Timeout Retry Interval Retries Password SNR Dial Out Level Login Id Phone Number Active Filter Priority Filter A Category Filter A Msg Type Filter A Priority Filter B Category Filter B Msg Type Filter B Modem Config Object Remote Device Name Proc
2. Specifies how many times the Remote Destination object resends the Dial command If the dial up connection could not be made in the time defined as the Retry Interval the Remote Destination object sends the Dial command again Retry Interval Indicates the amount of time in which Retries occur If the Error State attribute is set to Disconnected the Remote Destination object retries sending the Dial command periodically in this interval SNR Dial Out Level The percentage of the queue that needs to be full before dial out occurs Login ID Identifies which user is connected during a dial up session with an M Series Workstation Password Identifies which password is connected during a dial up session with an M Series Workstation 30 4 N30 Supervisory Controller User s Manual Process Identifier Used to route notifications alarms to this destination Must be a unique number for each device If not specified a value is automatically assigned on download Ack Required Setting this value to True allows the BACnet Acknowledgement Notification messages to be passed to the M3 workstation Status The Metasys Common Object LIT 694020 chapter of the Object Dictionary details this attribute A list of relevant states follows listed in hierarchical order from highest to lowest Normal Expected operating condition Active Filter Selects the type of filtering in effect for this remote destination The filter types are as fo
3. given device when it is being added from the VT100 3 100 True False Passes BACnet Event Notify messages to M3 Workstation Press F3 to save the new object Check the User Assistance area of the screen to verify if the save was sucessful or if there were errors If errors were detected correct them and resave the entries Once the save is successful continue with Step 7 30 10 N30 Supervisory Controller User s Manual 7 8 Press any key to continue Press the F4 Cancel key to return to the container hierarchy Editing a Remote Destination Object To edit a Remote Destination object 1 2 3 7 8 Browse to and highlight a Remote Destination object Press Enter to open the object Press the F3 Edit key The Remote Destination object attribute screen appears See Figure 30 1 and Figure 30 2 Edit the fields according to Table 30 2 Press the F3 Save key Check the User Assistance area of the screen to verify if the save was successful or if there were errors If errors were detected correct them and resave the entries Once the save is successful continue with Step 7 Press any key to continue Press the F4 Cancel key to return to the container hierarchy Deleting a Remote Destination Object To delete a Remote Destination object 1 2 3 4 Browse to and highlight a Remote Destination object Press Enter to open the object Press the Delete key Press the Tab key to confirm th
4. Chapter 30 N30 Supervisory Controller Users Manual 30 1 Working with Remote Destination Objects Introduction The Remote Destination object ensures delivery of Status Notification Reports SNRs to a workstation via a modem It also makes and maintains a connection with the workstation allowing the workstation to make a connection permanent or to deny a connection This chapter describes how to e adda Remote Destination object e edit a Remote Destination object e delete a Remote Destination object Note Remote Destination objects are not commandable November 01 2001 Johnson Controls Inc www johnsoncontrols com Code No LIT 6892300 Software Release 5 0 30 2 N30 Supervisory Controller User s Manual Key Concepts Remote Destination Object Operation Attributes SNRs received from Alarm objects initiate a connection if either the Dialout Required flag is set or the Max SNR Queue reaches the percentage set in the SNR Dial Out Level attribute The Remote Destination object is connected to the Serial Datalink object by setting the Port Number attribute The Remote Destination object performs the following tasks e receives status notification report messages from the Message Router object e sends Dial commands to the Serial Datalink object when status notification report messages need to be sent e notifies the Serial Datalink object to disconnect when the Dial Connect Timeout expires Dial Conn
5. e Destination object Press Enter to open the object Press the F3 Edit key Edit the fields according to Table 30 2 Press the F3 Save key Check the User Assistance area of the screen to verify if the save was successful or if there were errors Press any key to continue Press the F4 Cancel key to return to the container hierarchy Browse to and highlight a Remote Destination object Press Enter to open the object Press the Delete key Press the Tab key to confirm the deletion Note The Remote Destination object has no commands N30 Supervisory Controller User s Manual 30 7 Detailed Procedures Adding a Remote Destination Object To add a Remote Destination object 1 Browse to and highlight the Operator Devices container 2 Press the F3 Add key 3 Highlight the Remote Destination object from the list that appears and press Enter The first of two Remote Destination object configuration screens appears Figure 30 1 The second screen is shown in Figure 30 2 Battery OK 2 Jan 2001 00 01 30 Aspen Elementary ADMIN Wed 17 Jan 2001 10 34 CST Aspen Elementary Operator Devices Remote Destinat Object Object Name Description Object Type Remote Destination Object Category HVAC Engineering Values Port Number Port 2 Active Filter Pass All Dial Connect Timeout 60 second Priority Filter A 4 Items Retry Interval 200 second Category Filter A 5 Items Retries 3 Msg Type Filter A 3 Item
6. e deletion
7. ect Timeout Indicates the amount of time the Remote Destination object waits to receive messages before disconnecting following the N30 initiated Dial command Timeout Indicates the amount of time remaining prior to disconnection following the N30 initiated Dial command Error State Indicates the reason for error None No error Dial Out Failed The Serial Datalink object failed to connect in the time set by the Retries and Retry Interval attributes The Serial Datalink object s Connected To attribute does not change to Metasys device If the Error State attribute is set to this state the Remote Destination object s offline status is True Disconnected The Remote Destination object currently does not need to be connected N30 Supervisory Controller User s Manual 30 3 Max SNR Queue Specifies the number of alarm messages that are buffered for this Remote Destination If the queue is full alarm messages sent to this Remote Destination to be printed may be lost Modem Config Object Specifies the Modem Configuration object which holds the modem information used by the Serial Datalink object This attribute must be set to a Modem Configuration Class object Phone Number Indicates the Dial out phone number if a modem is connected to the port Port Number Indicates the port number specifying the port to which data is sent Queue Used Current Indicates the number of active entries in the report list Retries
8. ess Identifier Max SNR Queue Ack Required Required Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes N30 Supervisory Controller User s Manual Default Port 2 60 180 3 Blank 80 Blank Blank Pass All 4 Items 5 Items 3 Items 4 Items 5 Items 3 Items Blank Blank Blank 25 True 30 9 Options Range Port 0 Port 1 Port 2 Port 3 Port 0 is not a valid option for this object Value greater than 0 duration of connection in seconds when call is initiated by the N30 60 600 seconds time between dial attempts when previous dial attempts fail 0 10 number of attempts before failure M Series Workstation connection password 13 character maximum 35 100 percent M Series Workstation Login ID 20 character maximum M Series Workstation modem number to dial Pass None Pass All Filter A Filter B Filter A and B Critical Serious Important Status HVAC Fire Security Services Administrative System Alert Operator Transaction Alarm Critical Serious Important Status HVAC Fire Security Services Administrative System Alert Operator Transaction Alarm Enter the exact name of the Modem Configuration object containing the required dial out information M Series Workstation Device name This value is automatically assigned during download but must be assigned a value between 3 and 15 for the
9. llows e Pass None When selected this destination receives no alarm messages e Pass All When selected this destination receives all alarm messages e Filter A This destination receives alarm messages based on settings of Filter A e Filter B This destination receives alarm messages based on settings of Filter B e Filter A and B This destination receives alarm messages based on settings of Filter A and B Priority Filter A Defines which priorities this destination receives when Filter A is in effect A value of True for a particular selection means messages of that defined priority reach this destination Choices from highest to lowest priority are Critical Serious Important Status Category Filter A Defines which categories of messages the destination receives when Filter A is in effect This filter has no effect for alarm messages without a defined category A value of True for a particular selection means messages of that defined category reach this destination N30 Supervisory Controller User s Manual 30 5 Msg Type Filter A Defines which types of messages the destination receives when Filter A is in effect A value of True for a particular selection means messages of that defined type reach this destination Choices from highest to lowest priority are System Alert Operator Transaction Alarm Priority Filter B Defines which priorities the destination receives when Filter B is in effect A value of Tr
10. ue for a particular selection means that messages of that defined priority reach this destination Choices from highest to lowest priority are Critical Serious Important Status Category Filter B Defines which categories of messages the destination receives when Filter B is in effect This filter has no effect for alarm messages without a defined category A value of True for a particular selection means that messages of that defined category reach this destination Msg Type Filter B Defines which types of messages the destination receives when Filter A is in effect A value of True for a particular selection means messages of that defined type reach this destination Choices from highest to lowest priority are System Alert Operator Transaction Alarm 30 6 N30 Supervisory Controller User s Manual Procedure Overview Table 30 1 Remote Destination Object Procedure Overview To Do This Add a Remote Destination Object Edit a Remote Destination Object Delete a Remote Destination Object Follow These Steps Browse to and highlight the Operator Devices container Press the F3 Add key Highlight Remote Destination and press Enter Fill in the fields using Table 30 2 Press the F3 Save key Check the User Assistance area of the screen to verify if the save was successful or if there were errors Press any key to continue Press the F4 Cancel key to return to the container hierarchy Browse to and highlight a Remot