Silent Knight 5207 User Mannual

image

Contents

1. End SILENCE code End SILENCE Walk test Enter Enter Complete instructions appear in 2 2 ENTER code 0 or 1 2 2 ENTER codeOor1 Section 5 2 2 Exit SILENCE SILENCE Exit SILENCE SILENCE CLEAR CLEAR CLEAR CLEAR Zone trouble Enter Enter Complete instructions appear in shooting mode 2 5 ENTER code 0 or 1 2 5 ENTER code 0 or 1 Section 9 3 Exit CLEAR CLEAR Exit CLEAR CLEAR Step programming Enter 2 7 ENTER code Not applicable Step programming is explained mode in detail in Section 7 Exit STEP STEP CLEAR CLEAR 150865 5 3 Model 5207 Fire Control Communicator Installation and Operation Manual 5 1 1 Built in Touchpad Display Codes The following table briefly describes the codes that are displayed on the built in touchpad For complete information and for 5230 display messages see Section 9 Table 5 2 Built in Touchpad Display Codes Display Meaning 0 Fire drill with Alarm Alarm Memory or Trouble LED 1 16 Zone numbers with Alarm Alarm Memory or Trouble LED Al A4 Trouble with specified bell output AC Low AC condition dC Low ba
2. Section 5 Operation To operate the 5207 you can use either the built in touchpad or the Model 5230 Remote Annunciator 7 segment display codes __ In normal operation the display is blank except for 2 LEDs that alternately flash ALARM MEMORY SILENCED TROUBLE o O ac po SETMODE REPORT oS ae Reset CLEAR DIAL pisptay ALARM MEMO RESET LOAD MEMORY Key functions are basically the same as for the 5230 DISPLA set set TRBL DATE TIME TEST 6 7 8 g l o ae a YO ENTER A JN nr gt SILENCE DISABLE CLEAR Figure 5 1 Built in Touchpad Seven Segment Display MODEL 5230 NORMAL TUE AN 10 16 FIRE ALARM ANNUNCIATOR gt on Cen ia A PA Am UG e o Ed ER a 4 2 3 aj 5 DISAB S na WREL E l TEST SILENCE a j ar a ae SIEP SILENT KNIGHT FIRE SYSTEMS Figure 5 2 Model 5230 Remote Annunciator 150865 Model 5207 Fire Control Communicator Installation and Operation Manual 5 1 Built in Touchpad and Model 5230 Operation Basic operation of both the 5230 and the built in touchpad is described in Table 5 1 Note that if no keys are pressed for 15 minutes while in program mode the system will time out and resume normal operation Notes A valid operating code is required for most functions when using the
3. Flashing Panel is running on battery power only or AC power only MEMORY yellow Off Normal condition On An alarm condition has been reset Alarm memory contains data TROUBLE yellow Off Normal condition On Trouble condition exists SET MODE yellow Off Normal condition REPORT On System is in a Set Test or Program mode Flashing System is reporting 5 2 System Testing This section describes operation of fire drills zone testing and the 24 hour automatic test 5 2 1 Fire Drills Fire drills can be run from either the built in touchpad or the Model 5230 Remote Annuncia Code 0 or 1 The system will sound an alarm and report a fire test To end the fire drill press SILENCE code tor To initiate a fire drill press B 0 150865 ENTER 5 5 Model 5207 Fire Control Communicator Installation and Operation Manual 5 2 2 Walk Test Mode 22 The walk test is designed to be used for onsite testing only To enter walk test mode press 2 2 ENTER code 0 or 1 The LCD will indicate that you are in walk test mode When a zone is tripped the 5207 will activate the bell outputs for approxi mately one second and will cycle smoke power off and on for the programmed time interval Pre alarm zones will not be delayed but smoke verification zones will go through the verifi cation delay When smoke power is restored there is a two second power up d
4. 5230 In Table 5 1 code any valid operating code code 0 installeris code and code 1 main useris code If the NEED CODE AT PANEL option is selected in programming Step 3 the following operations will require a valid code when using the built in touchpad Silence Reset alarms Clear alarm memory Test Table 5 1 5207 Operation To 5230 Annunciator Built in Touchpad Additional Information Test the system 0 ENTER code 0 ENTER The system will perform a display lamp test a bell test and a communicator test Note Bells or relays programmed to activate on Pre Alarm or Trouble do not activate during a test Reset alarms or smoke detectors 1 ENTER code 1 ENTER If there is no alarm this procedure resets the smoke detectors When a trouble condition occurs and you reset the alarm the trouble condition is stored in memory until you clear the alarm memory If the alarm memory is not cleared the trouble condition is displayed the next time a trouble condition occurs implying incorrectly that more than one trouble condition exists Clear alarm memory
5. ENTER code 0 or 1 9 ENTER See explanation below The SET MODE LED will turn on and the built in touchpad display will flash 9 indicating that you are in Set Time mode Enter six digits for the time The first digit indicates day of the week 10 Sunday 1 Monday etc The second digit indicates time of day 0 AM 1 PM The last four digits are the actual time For example to set the time for Wednesday 4 30 p m you would enter 3 4 0 4 3 0 Once you press the last digit of the time the SET TIME LED will turn off and the time will be changed To exit Set Time mode in the middle of the sequence press CLEAR CLEAR Note If you are powering up the 5207 you will be in Set Time mode with 9 showing on the display In thise case you donit need to press 9 Just enter the six digits for the time Disable Enable zones Zone DISABLE code Zone DISABLE code Disables or enables a zone When a zone is disabled there will be an alert tone that cannot be silenced until the zone is enabled Fire drill Begin Begin Complete instructions appear in 2 0 ENTER code 0 or 1 2 0 ENTER code Qor1 Section 5 2 1
6. 2 ENTER code 2 ENTER Clears alarm memory and resets the 4180 This function removes all memory of alarms Reset the dialer 3 ENTER code 0 or 1 3 ENTER code 0 or 1 Resets the dialer aborts a call Initiate download 4 ENTER code 0 or 1 4 ENTER code 0 or 1 Starts the downloading process Exit downloading mode by pressing CLEAR CLEAR Display alarm 5 ENTER 5 ENTER Displays current alarm memory memory It is recommended that you clear alarm memory after displaying it Display troubles 6 ENTER 6 ENTER Displays trouble conditions Silence troubles or SILENCE code SILENCE If silencing audible signals you alarms OR OR may need to enter a code 7 ENTER code 7 ENTER 150865 Operation Table 5 1 5207 Operation To Additional Information 5230 Annunciator Built in Touchpad Set date 8 ENTER code 0 or 1 8 ENTER See explanation below The SET MODE LED will turn on and the built in touchpad display will flash 8 indicating that you are in SET DATE mode Enter six digits for the date For example to set the date for 08 15 97 enter the following digits 0 8 1 5 91 7 Once you press the last digit of the date the SET TIME LED will turn off and the date will be changed To exit Set Date mode press CLEAR CLEAR Set time 9
7. check inputs and carry out other routine functions If the program should ever stop running the watchdog circuit will automatically detect this and attempt to resume normal operation by resetting the microprocessors Each time the watchdog circuit initiates a reset signal it will also sound the audible trouble signal for approximately four seconds 5 6 150865
8. elay before the zone will respond to additional test inputs The system will time out and resume normal operation in 15 minutes if no keys are pressed or no zones are tripped during the walk test To exit walk test mode press SILENCE SILENCE CLEAR CLEAR Note The ESL 429 series smoke detectors are NOT compatible when operating the 5207 panel in walk test mode In walk test mode the built in self test on the ESL 429 series smoke detectors may be unreliable If the built in self test is required it should be done in the normal operating mode with the zone speed set to 3 seconds or higher Note that these smoke detectors are incompatible only for walk tests not for any other normal 5207 sys tem operation 5 2 3 Automatic Self Test The Model 5207 lets you select the time of day that the 24 hour automatic test signal will be sent to the central station The Auto Test dialer test sent automatically at specified times Immediately following the test the 5207 also sends all unrestored events as required by UL The events will have no indica tion when they occurred so central station personnel should maintain records of unrestored events or if that is not possible treat all alarms troubles and supervisories that come in dur ing an auto test as if they were new events 5 3 Watchdog Circuit During normal operation the control microprocessor of the 5207 is constantly running pro grams to
9. ttery condition dF Dialer failed after programmed number of attempts have been made dL Data lost during attempt to transmit to the central station This condition occurs after total attempts to communicate have been made E0 Trouble with the dialer E7 Trouble with EEPROM FO 5230 annunciator power trouble Fl F7 Trouble with specified annunciator 1 7 L1 L2 Phone line fault on specified phone line PO Printer is out of paper P1 Trouble with smoke detector power P2 Accessory power terminal 26 trouble P3 Earth ground fault to circuit ground See Section 9 2 for more information P4 Earth ground fault to power See Section 9 2 for more information 0 Fire drill 2 Walk test 4 Downloading 5 Zone troubleshooting mode 6 Hex programming mode 7 Step programming mode 8 Set Time mode 9 Set Date mode 2 3 etc Prompts indicating that the user needs to enter a code 150865 5 1 2 LED Indicators Six light emitting diodes LEDs appear in the 5207 cabinet window The chart below explains the meaning of these LEDs Operation LED Status Condition ALARM red Off Normal condition On Supervisory and Tamper condition Flashing Alarm SILENCED yellow Off Normal condition On Alarm or trouble condition has been silenced but condition still exists AC DC green On Panel is running on AC normal condition standby battery fully charged Off Panel has lost all power