WISE – Modbus tables

image

Contents

1. Modbus Name Min Max Parameter Remark Std 4x0022 Pressure sensor 0 2 P_1706 O Not used 1 Analogue 2 ModBus 4x0023 Not used 4x0024 Not used 4x0025_ Not used 4x0026__ Not used 4x0027 Not used 4x0028 Not used 4x0029 Not used 4x0030 ISA flow set point 0 20000 P_1724 Only used when groups are not used l s 0 4x0031 JEA flow set point 0 20000 P_1725 Only used when groups are not used l s 0 4x0032 ISA flow offset 5000 5000 P_1713 Only used in Case C Setp from SM 0 4x0033 EA flow offset 5000 5000 P_1716 0 4x0034 ISA flow Manual 0 100 Maybe not needed 4x0035 JEA flow Manual 0 100 Maybe not needed 4x0036__ Pressure set point 0 300 P_1726 Pa 30 4x0037 Not used 4x0038 Not used 4x0039 Not used 4x0040 Not used 4x0041 Not used 4x0042 Not used 4x0043 Not used 4x0044 Not used 4x0045 Not used 4x0046 SA damper after sensor error 0 100 P_1707 Used only when sensor faulty 50 4x0047 EA damper after sensor error 0 100 P_1708 Used only when sensor faulty 50 4x0048 IP term SA 10 10000 P_1711 P E al P Coane ariy 25 4x0049 I term SA 1 1000 P_1712 50 4x0050 P term EA 1 1000 P1714 tre ella flow control Only 25 4x0051 I term EA 10 10000 P_1715 50 4x0052 Not used 4x0053 Not used 4x0054 ISA 0 value 0 5000 P_1717 Voltage offset for 0 mV 0 4x0055 ISA 100 value 5000 10000 P_1718 Voltage offset for 100 mV 10000 4x0056 EA0 value 0 5000 P_1719 _ Voltage offset for 0 mV
2. 0 4x0057 JEA 100 value 5000 10000 P_1720 Voltage offset for 100 mV 10000 4x0058 Flow calc type 1 2 P_1721 1 Linear 2 Quadratic 1 4x0059 SA K term linear 500 15000 P_1722 Factor se separate tables Scale 1 100 500 4x0060 ISA K term Quadric 10 25000 P_1723 Factor se separate tables Scale 1 10 10 4x0061 EA K term linear 500 15000 P_1727 Factor se separate tables Scale 1 100 500 4x0062 EA K term Quadric 10 25000 P_1728 Factor se separate tables Scale 1 10 10 4x0063 Not used 4x0064 Not used 4x0065 Not used 15 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Zone Holding register 16 bit integer register RAW Modbus Name Min Max Parameter Remark Std 4x0066__ Not used 4x0067 Not used 4x0068 Not used 4x0069 Copy of Coil Status 1 16 0 65535 Bit0 0x0001 Bit15 0x0016 Input register 16 bit integer register Read only Modbus Name Min Max Parameter Remark Std 3x0001 Component Name ID 0 10 X ID for type of controller in Conductor and Wise system A Component Name 0 999 Name built of max 16 char exch char ASCII standard 3x0018 Application ID P_106 Always factory set do not shange for FSFE use 8 8 3x0019 HW Serial No 3x0020 SW version 3x0021 Not used 3x0022
3. Pressure supply Set point Pa sent to GOLD 3x0002 Pressure extract Set point Pa sent to GOLD 3x0004 Start Delay Control Counting down from value given seconds 3x0005 Not used 3x0006 Not used 3x0007 Not used 3x0008 Not used 3x0009 Not used 3x0010 Not used 3x0011 SA damper 01 Supply damper position in 0 closed Pos 1 15 reserved for PSFE A with MBid 1 15 3x0055 SA damper 45 Pos 16 45 reserved for PS with MBid 20 49 3x0061 EA damper 01 Extract damper position in 0 closed Pos 1 15 reserved for PSFE with MBid 1 15 3x0105 EA damper 45 Pos 16 45 reserved for EA with MBid 50 79 Parameters for CONTROL Room and Zone All CONTROL products is supplied with a parameter file The file has all unique data valid for chosen application All parameter data can be set via modbus or TUNE Control On our home page there is excel sheets downloadable for all different applications se example below a Swegon Ordernr 20XX XX XX ver 1 91 CONTROL Zone Damper Setup data an x X Product CONTROL Za xxx PSFE Marking 1 Prog ver Object 0 56 or later Object Description Modbus Address 1 79 BMS Baudrate 9 6 19 2 38 4 unit iD EE BMS Parity 0 Odd 1 Even 2 None BMS Stop bits O O er Param Fa Component type always 2 for this product PY Application type always 8 for this product fs Relay at emer 0 Open 1 Close 2 No action hour Valve exerc
4. 3 5 vated 0x0003 Test Level o ka to set controller to manual mode See Damper 1 pos 0 3 5 0x0004 OCC Manual 0 O Auto 1 Manual set 3 5 0x0005 OCC Set 0 O sets standby 1 sets occupied 3 5 0x0006 Heating present O 1 Heating with water is connected includes cooling with air 1 3 5 0 Only cooling 0x0007 Night cool 0 1 O No action 1 Night cool on 3 5 0x0008 Moorning boost 0 Sets controller to new set point quick heating 28 C 5 0x0009 Valve test 0 Activates heat output for 8 minutes 5 Reversed emergency Makes it possible to have different damper position on slave 0x0010 0 0 5 function products in emergency mode 0x0011 Wentilation boost 0 1 Activates the ventilation boost function after a longer 0 5 unoccupied mode 0x0012 Air quality control 0 1 Activates air quality control in unoccupied mode 0 5 0x0013 Not used 0 1 0x0014 Not used 0 Input Status Discrete Input 1 bit Read only Modbus Name Min Max Remarks Std Version 1x0001 OCC Sensor Status 0 1 Local Device Occupancy Sensor Status 1 occupied 3 5 O standby resets after 1 min 1x0002 OCC Mode 0 1 System occupancy mode 1 occupied O standby resets after 3 5 time set in OCC Delay off 1x0003 Spare 1 0 1 Spare 3 5 1x0004 Spare 2 0 1 Spare 3 5 1x0005 Alarm stroke fault 0 1 Operating Alarm 1 stroke calibration fault LED is red 3 5 1x0006 Alarm actuator 0 1 Operating Alarm 1 actuator fault LED is red 3 5 1x0007 Alarm pressure sensor 0 1 a ng Alarm 1 pres
5. P_1507 Airflow at occupied mode l s 4x0041 Min extract airflow UnOCC 10000 P_1508 Airflow at unoccupied mode l s 4x0042__ Not used 4x0043 Not used 4x0044 Not used 4x0045 Not used 4x0046 Supply damper pos 0 100 P_1529 Damper position when sensor fault 50 4x0047 Extract damper pos 0 100 P_1530 Damper position when sensor fault 50 4x0048 P term Supply air 1 1000 P_1522 PI controllers internal factor 25 4x0049 I term Supply air 10 10000 P_1523 PI controllers internal factor 50 4x0050 P term Extract air 1 1000 P_1524 PI controllers internal factor 25 4x0051 I term Extract air 10 10000 P_1525 PI controllers internal factor 50 4x0052 Not used 4x0053 Not used 4x0054 Supply air damper limit 0 5000 P_1514 Min output signal mV 0 4x0055 Supply air damper limit 5000 10000 P_1515 Max output signal mV 10000 4x0056 Extract air damper limit 0 5000 P_1516 Min output signal mV 0 4x0057 Extract air damper limit 5000 10000 P_1517 Max output signal mV 10000 4x0058 Flow calculation method 1 2 P_1541 1 Linear 2 Quadratic 1 10 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Swegon Holding register 16 bit integer register R W Modbus Name Min Max Parameter Remark Std 4x0059__ Supply K factor linear 1 15000 P_15
6. cold fall protection is active or not 3x0022 CAC level 0 100 Actual air quality level is only available for ADAPT Damper extract 5 3x0023 CAC gt CO ppm 400 2000 Calculated CO ppm value from the CAC level 5 3x0024 Airflow set point 0 10000 I s Calculated airflow set point from controller 6 www swegon com Modbus tables Notes for 3x0011 also presented as separate bits 1x0005 1x0011 B0000001 B00000010 B00001000 B00010000 B00100000 BO100000 B1000000 Stroke calibration fault LED is red Actuator fault LED is red Pressure sensor values out of range LED is red Room temp sensor values out of range LED is red Internal temp sensor fault values out of range LED is red Set point for heating and cooling are overlapping LED is red VOC sensor fault LED is red Notes for 3x0012 also presented as separate bits 1x0012 1x0015 B0000001 B00000010 B0000100 B00010000 Temperature deviation CO deviation Not defined spare Not defined spare Notes for 3x0015 also presented as separate bits 0x0001 0x0007 B0000001 B0000010 B00001000 B00010000 B00100000 BO100000 B1000000 Activates emergency of the actuator in the product Emergency action 0 Damper closes when emergency contol is active 1 Damper opens when emergency contol is active Used to manually controll the damper into defined positions LED is orange OCC Manual O Normal operation with internal or external OCC sensor 1 Manua
7. only takes place if heating is 5 4 5 activated 4x0071 ICAC use 0 1 Activates the CAC function in ADAPT Damper extract air 5 4x0072 CAC min 15 80 _ Lower set point where increase of air starts 25 5 4x0073 CAC max 30 90 aaa point where increase of air has reached max set 35 5 4x0074 Vent boost delay 24 300h Time limit for ventilation boost if occupancy is activated 72h 5 after the limit airflow is set to maximum for a short time 4x0075 Vent boost time 0 60min Ventilation boost after longer unoccupied time 5m 5 4x0076 CAC calc factor 1 0 32000 Calculation factor for CAC to a CO value 5 4x0077 CAC calc factor 2 0 32000 Calculation factor for CAC to a CO value 5 4x0078 ICAC calc factor 3 0 32000 Calculation factor for CAC to a CO value 5 4x0079 Temp Calibrating Au 0 32000 Correction factor coold supply air 5 1 4x0080 Temp Calibrating Bu 0 32000 Correction factor coold supply air 5 1 4x0081 Temp Calibrating Cu 0 32000 Correction factor coold supply air 0 5 1 5 Swegon reserves the right to alter specifications 20150223 www swegon com Swegon reserves the right to alter specifications 20150223 a Modbus tables Swegon Modbus Name Min Max Remarks Std Version 4x0082 Temp Calibrating Du 0 32000 Correction factor coold supply air 0 5 1 4x00
8. value for CO start point for airflow control 4x0020 2 500 3 5 4x0032 CO max 500 2000 Max value for CO endpoint where airflow has reached max 1000 3 5 2 ppm 4x0020 2 Calculated CO if voltage measurement is used with 4x0033 CO in room Application type 2 Must reset to O if appl type 2 is not 0 3 5 used Value might be set by BMS system 4x0034 OCC delay off 0 60 min Time before switching from occupied to economy 20 3 5 4x0035 OCC delay on 0 120s Time before switching from economy to occupied 3 5 4x0036 Manual Damper pos 0 100 Manual device position for device when Test Level 1 3 5 O No LED indication 1 Function control 2 Comfort 4x0037 LED function ile 3 Function Comfort 4 Function no LED at stand by f ies 4x0038 Alarm set time 10 120 m Time before alarm code is set 60 3 5 4x0039__ Alarm reset time 0 60 m__ Time before alarm is reset 1 3 5 4x0040 Max temp deviation 1 10 K Max deviation before alarm is set 2 3 5 4x0041 Max CO deviation 100 1000 Allowed deviation ppm of CO value before alarm is set 200 3 5 ppm Resets automatically 4x0042 Security access Enter 0 9999 Entry of security code for accessing protected values Resets 3 5 to protected mode after 30 minutes 4x0043 CoolHeatTempDiff 0 50 C Minimum difference between room set point and supply air 10 3 5 temperature before using Air cooling or Air heating 4x0044 Room temp gain Cool 1 20000 PI controller gain for cooling x16del 500 3 5 4x0045 Room temp
9. 42 Scale 1 100 500 4x0060 Supply K factor Quadratic 1 25000 P_1543 Scale 1 10 10 4x0061 lExtract K factor linear 1 15000 P_1544 Scale 1 100 500 4x0062 Extract K factor Quadratic 1 25000 P_1545 Scale 1 10 10 4x0063 Not used 4x0064 Not used 4x0065 Not used 4x0066 CO min 350 1000 P_1538 Min level where increasing of airflow starts 800 4x0067 CO max 350 2000 P_1539 Max level when airflow is equal tom max set point 1000 4x0068 CO per volt 10 500 P_1540 Signal level from sensor 0 10V DC ppm volt 200 4x0069 Copy of Coil Status 1 16 0 65535 BitO 0x0001 Bit15 0x0016 Input register 16 bit integer register Read only Modbus Name Min Max Parameter Remark Std 3x0001 Product ID 0 10 ID defining the product type in the WISE system oe Product mark 0 999 Mark with max 16 char ASCII standard 3x0018 Application ID 1 10 P_106 FSFE normal 5 FSFE with 2 step cooling 6 6 3x0019 HW serial number 3x0020 SW version 3x0021 Not used 310022 Running mode n Nigh cool mene E 3x0023 Not used 3x0024 Not used 3x0025 Time count Year Time count since last power up 3x0026 Time count Hours 0 8760 After 8760 hours year count is updated 3x0027 Time count Minutes 0 60 After 60 min hour count is updated 3x0028 Supply temperature Temperature Scaled 1 10 Cx10 3x0029 Room temp unit 1 Temperature Scaled 1 10 Cx10 3x0030 Room temp unit 2 Temperature Scaled 1 10 Cx10 3x0031 Set point from room unit Manually changed set poi
10. 52 Not used x0053 Duct group member missing Not used in CONTROL Zone x0054 Negative pressure ALARM resets automatically Holding register 16 bit integer register RAW Modbus Name Min Max Parameter Remark Std 4x0001 Relay in Emergency 0 1 P_107 0 Close 1 Open 2 No Action 4x0002 Application transition 1 4 1 Operational 2 Manual 3 Emergency 4 Closed 4x0003 Room number 0 32000 P_114 4x0004 Not used 4x0005 Not used 4x0006 Not used 4x0007 Pl overload warning time 0 60 P_111 Warning delay Pl overload minutes 10 4x0008 Set point warning time 0 60 P_112 Warning delay Set point minutes 10 4x0009 o sensor warning 0 60 P_113 Warning delay pressure sensor minutes 1 4x0010 Not used 1 4x0011 Not used 0 4x0012 Not used 1 4x0013 Not used 1 4x0014 Case selection 1 3 P_1701 1 PSFE 2 PS FS 3 PE FE 1 4x0015 Control type 1 2 P_1702 1 Flow 2 Pres 4x0016 Ext Switch 0 2 P_1703 O Not used 1 Normally Closed 2 Normally Open 0 4x0017 Not used 4x0018 Not used 4x0019 Not used 4x0020 ISA Flow sensor 0 2 P_1704 0 Not used 1 Analogue 2 ModBus 4x0021 EA Flow sensor 0 2 P_1705 O Not used 1 Analogue 2 ModBus 14 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Zone Holding register 16 bit integer register RAW
11. 83 Temp Calibrating Eu 0 32000 Correction factor coold supply air 0 5 1 4x0084 Temp Calibrating Fu 0 32000 Correction factor coold supply air 0 5 1 4x0085 Temp Calibrating Ao 0 32000 Correction factor warm supply air 0 Sal 4x0086 Temp Calibrating Bo 0 32000 Correction factor warm supply air 0 5 1 4x0087 Temp Calibrating Co 0 32000 Correction factor warm supply air 0 5 1 4x0088 Temp Calibrating Do 0 32000 Correction factor warm supply air 0 Dal 4x0089 Temp Calibrating Eo 0 32000 Correction factor warm supply air 0 Se 4x0090 Temp Calibrating Fo 0 32000 Correction factor warm supply air 0 5 1 Input register 16 bit integer register Read only Modbus Name Min Max Remarks Std Version 3x0001 Room temp 0 500 Temperature in room Value is actual Deg C 10 3x0002 Supply temp 0 500 Temperature in supply air Value is actual Deg C 10 Calculated room set point value when controller is in neutral 3x0003 Cale actual set point 9 300 zone the room temp is shown Value is actual Deg C 10 3x0004 Room temp deviation 0 500 eae between set value and actual value Value is actual 3 5 f Calculated airflow set point from external controller 0 lowest 9 3x0003 Pt point extern 0 100 airflow 4x0028 or 4x0029 100 max airflow 2a Calculated airflow set point from internal controller 0 lowest 9 d PORIG Cale AON 0 100 airflow 4x0028 or 4x0029 100 max airflow ok 3x0007 Airflow 0 10000 V s Actual airflow exactly calculated a
12. Application state 0 4 a 1 Operational 2 Manual 3 Emergency 3x0023 Control method 3x0024 Case 3x0025 Time since last boot Year 3x0026 Time since last boot Hours 0 8760 After 8760h Year is updated 3x0027 Time since last boot Min 0 60 After 60min Hour is updated 3x0028 Not used 3x0029__ Not used 3x0030 Not used 3x0031 Not used 3x0032 Not used 3x0033 Not used 3x0034 SA pressure MB sensor Not used in CONTROL Zone 3x0035 SA flow pressure MB sensor Not used in CONTROL Zone 3x0036 JEA flow pressure MB sensor Not used in CONTROL Zone 3x0037 Input Analog 1 0 10000 mV 3x0038 Input Analog 2 0 10000 mV 3x0039 Input Analog 3 0 10000 mV 3x0040 Input Analog 4 0 10000 mV 3x0041 Output PWM 1 0 100 Not used in CONTROL Zone 3x0042 Output PWM 2 0 100 Not used in CONTROL Zone 3x0043 Output PWM 3 0 100 3x0044 Output PWM 4 0 100 3x0045 Output Analog 1 0 10000 Not used in CONTROL Zone 3x0046 Output Analog 2 0 10000 Not used in CONTROL Zone 3x0047 Output Analog 3 0 10000 mV 3x0048 Output Analog 4 0 10000 mV 3x0049 Not used 3x0050 Not used 3x0051 PID SA Out 100 100 3x0052 PID EA Out 100 100 16 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Zone Input register 16 bit integer register Read only Modbus Name Min Max Parameter Remark Std 3x0053__ Not used 3x0054__
13. Not used 3x0055 ISA Damper pos 0 100 3x0056 EA Damper pos 0 100 3x0057 Duct Pressure Pa 3x0058 Airflow Supply l s 3x0059 Airflow Extract l s 3x0060 Not used 3x0061 Not used 3x0062 Not used 3x0063 Copy of Input Status 1 16 0 65535 Bit0 0x0001 Bit15 0x0016 3x0064 Copy of Input Status 17 32 0 65535 Bit0 0x0017 Bit15 0x0032 3x0065 Copy of Input Status 33 48 0 65535 Bit0 0x0033 Bit15 0x0048 3x0066 Copy of Input Status 49 64 0 65535 Bit0 0x0049 Bit15 0x0064 17 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Optimize Coil Status Discrete Output 1 bit RAV Modbus Name Min Max Parameter Remark Std 0x0001 AHU status 0 1 O not running 1 running ae Manual o eee Manager AHU control set to Manual Mode Ox0003 Emergency control 0 1 O No emergency 1 Emergency state 0x0004 0x0005 Restart 0 1 Writing 1 to this register Restarts AHU control 0x0006 Night Cool 0 1 0O No night cool 1 Night cool Input Status Discrete Input 1 bit Read only Modbus Name Min Max Parameter Remark Std 1x0001 Alarm Code Supply If supply pressure not reached bit is 1 1x0002 Alarm Code Extract If extract pressure not reached bit is 1 1x0003 Alarm Damper If
14. WISE Modbus tables Technical documentation for designers commissioning and management engineers 20150223 New versions and functions gt ADAPT Device and Damper version 5 2 gt ADAPT Damper with CAC control gt CONTROL Room and Zone Modbus tables Contents Modbus variables for ADAPT products Modbus variables for CONTROL Room Modbus variables for CONTROL Zone Modbus variables for CONTROL Optimize Parameter system for CONTROL products Constant tables Flow constant tables for Room and Zone applications has been moved to the Service Manual Table 1 Version code for the ADAPT controller 14 19 20 ADAPT device amp damper Versions code in the version controller 3x0018 3 3 4 4 or 256 5 768 5 1 1024 and 1025 5 2 1280 2 E Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Swegon Modbus variables for the ADAPT products Coil Status Discrete Output 1 bit RAW Modbus Name Min Max Remarks Std Version 0x0001 Emergency control O Activates the Emergency control function which opens or 0 3 5 closes the dampers 0 Damper closes when Emergency control is 0x0002 Emergency action 0 activated 1 Damper opens when Emergency control is acti 0
15. Water heat Needs DETECT Ta 4 Air cool and Water cooling 2 step cooling O Internal controller 1 External controller CO Temp T 2 External signal CO intern Room temp 4x0020 Application type 0 10 Selva tuncion 0 3 5 4 External set point adjuster 5 Volt 5 External 0 10 V temp sensor 10 0 V 30 10 V Internal temperature sensor if DETECT Ta is defined it replaces the room temp sensor in the ADAPT products O Sensor 1 room temp Sensor 2 supply temp 4x0021 Temp sensor use 0 3 1 Sensor 1 not used Sensor 2 room temp 0 3 5 2 Sensor 1 not used Sensor 2 supply temp Note O All Supply devices 1 Damper in extract duct 2 Damper in supply duct When 4x0020 5 set 4x0021 to 0 4x0022 CoolSetpointTempOcc 0 50 C Cool set temperature occupied 23 4x0023 HeatSetpointTempOcc 0 50 C Heat set temperature occupied 21 4x0024 CoolSetpointIempEcon 0 50 C Cool set temperature economy 25 3 5 4x0025 HeatSetpointlIempEcon 0 50 C Heat set temperature economy 20 3 5 4x0026 SetpointTempNight 0 50 C Set point night cooling room controller from BMS 18 3 5 4x0027 SetpointTempMBoost 0 50 C Set point for morning boost function 25 3 5 4x0028 Min flow economy 0 32000 I s Min flow set point at standby supply air 5 3 5 4x0029 Min flow occupied 1 32000 I s Min flow set point at occupied supply air 10 3 5 4x0030 Max flow occupied 1 32000 I s Max flow set point at occupied I s 40 3 5 300 1000 i f 4x0031 CO min ppm Min
16. al 500 dPa Pressure sensor offset to calibrate to 0 Pa 3 5 4x0058 _ Modbus address 1 248 Controller Modbus address 3 5 4x0059 Baud rate 0 2 Communication speed Modbus 0 9600 1 19200 2 3 5 2 38400 4x0060 Parity 0 2 Parity O ODD 1 EVEN 2 NONE 2 3 5 4x0061 Stop bits 1 2 Number of stop bits 1 1 stop bit 2 2 stop bits 1 3 5 4x0062 OCC time counter 0 32767 Counts time in hours when 1x0002 is 1 3 5 4x0063 Run time counter 0 32767 Counts time in hours when controller has power 3 5 4x0064 _ MotorZeroReturn 0 500 steps Return of Zero point for the damper 1 step 10 9 3 5 4x0065 _ MotorRuntime 30 180s Runtime in seconds between 0 100 damper stroke 30 3 5 Min airflow with If this variable sets gt 0 the controller assumes there are a 4x0066 0 32000 electrical heater in the duct In heating mode this is the min 0 5 1 electrical heater airflow to prevent the heater to get overheated Theoretical stroke length for damper motor 1 mm is equal to 4x0067 Damper stroke 15 200 1 turn of the motor Se 3x0020 15 4 5 4x0068 Min output on heat 10 50 Sets lower limit on heat output used for prevent cold 0 4 5 level influence from window mit torminiset oint Sets highest cold level when min output on heat can be 4x0069 eat p 0 50 activated if Cool value is higher than set level the output on 50 4 5 heat is always 0 Sets time between exercise off Heat output O inactivated 4x0070 Valve exercise interval 0 14 Ivalue is in days x24h Exercise
17. ed 0 1 x0004 External switch 0 1 x0005 Not used 0 1 x0006 No active alarms 0 1 ALARM INFO x0007 No Room Unit 1 0 1 Not used in CONTROL Zone x0008 No Room Unit 2 0 1 Not used in CONTROL Zone x0009 No Pressure sensor 0 1 ALARM resets automatically x0010 Supply Flow sensor error 0 1 ALARM resets automatically x0011 Extract Flow sensor error 0 1 ALARM resets automatically x0012 Room Unit 1 Temp error 0 1 Not used in CONTROL Zone x0013 Room Unit 2 Temp error 0 1 Not used in CONTROL Zone x0014 Regulator KTY short circuit 0 1 Not used in CONTROL Zone x0015 Regulator KTY open circuit 0 1 Not used in CONTROL Zone x0016 Room Unit Low Battery 0 1 Not used in CONTROL Zone x0017 Pl controller overload 0 1 ALARM resets automatically x0018 Set point not reached 0 1 ALARM resets automatically x0019 Not used 0 1 x0020 Not used 0 1 x0021 No device list 0 1 ALARM resets automatically x0022 AC overload 0 1 ALARM resets automatically x0023 System fault 0 1 ALARM x0024__ No serial number 0 1 ALARM x0025 Not used 0 1 x0026 Short circuit Output X11 0 1 ALARM requires Hardware reset x0027 Short circuit Output X12 0 1 ALARM requires Hardware reset x0028 Short circuit Output X13 0 1 ALARM requires Hardware reset x0029 Short circuit Output X14 0 1 ALARM requires Hardware reset x0030 SPI Flash broken 0 1 ALARM requires Hardware reset x0031 Radio chip broken 0 1 ALARM requires Hardware reset x0032 Parameter file revision 0 1 ALARM requires Ha
18. irflow from device pos and dev 3 5 pressure Calculated airflow set point is not shown in any variable hn 3x0008 Cool value 0 100 Shows controllers cooling level 100 max cooling Slave 3 5 output is shown in this variable 3x0009 Heat value 0 100 Shows controllers heating level 100 max heating 3 5 3x0010 Controller mode 0 10 Controller mode 0 Occupied 1 Standby 2 night cool 3 5 3 morning boost will not be presented to market 3x0011 Alarm function A 0000000 Summary of alarms A from variables 1x0005 1x0011 3 5 3x0012 Alarm function B 0000 Summary of alarms B from variables 1x0012 1x0015 3 5 3x0013 Device pressure 0 2500 dPa Actual Device pressure dPa 3 5 3x0014 OCC sensor level 0 10000 Momentary sensor level from internal IR sensor 3 5 3x0015 Configuration set Binary Summary of the Coil Status variables 1 16 3 5 3x0016 Configuration set Binary Summary of the Input Status variables 1 16 3 5 iO 2 3x0017 Actual device position 0 100 Actual device damper position in where O closed and 100 is 3 5 fully open 3x0018 Program version Software programme version id 3 5 3x0019 Controller serial number 100 32767 Controller serial number values higher than 100 is for official 3 5 release 3x0020 Actual damper stroke 15 100 Actual detected stroke after power up Used for position and 4 5 flow calculation correction 3x0021 Heat valve output 0 100 This variable shows the output level for heat Valve Important to 4 5 see if
19. ise O Notused min Motion timer not used for this product min Waring delay romstatup f o min Warning delay Provera O Number tor identification optional 0 65000 Case selection 12PSFE 22PS FS 32PEFE P_1702 2 Control type 1 Flow 2 Pressure _ x 7 O e alv w N lt D ojlolojlojo gt Njw 2 om ad 19 Swegon reserves the right to alter specifications 20150223 www swegon com
20. itime Cool 1 1800 PI controller Itime for cooling x16del 10 3 5 4 www swegon com a Modbus tables Swegon Modbus Name Min Max Remarks Std Version 4x0046 Room temp gain Heat 1 20000 PI controller gain for heating x1 6del 500 3 5 4x0047 Room temp itime Heat 1 1800 PI controller Itime for heating x16del 10 3 5 0 Normal mode controller is in operation 4x0048 Man flow option 0 10 1 max flow 2 min flow 3 min flow unoccupied Controller 3 3 5 sets fixed airflow led orange for values 1 3 10 CO ppm per volt if analogy sensor is used If value 0 CO ore CO pervo 5000ppm Ivalue must be sent to 4x0033 200 oa 4x0050 Device constant 1 32000 Constant used in flow calculation 2997 3 5 4x0051 Device constant 2 32000 Constant used in flow calculation 1001 3 5 4x0052 Device constant 3 32000 Constant used in flow calculation 501 3 5 4x0053__ Device constant 4 32000 Constant used in flow calculation 6840 3 5 Time constant used to calculate opening interval on heat 4x0054 HeatValveOpenTime 0 1000 valve when using proportional control Set to 60 sec when 350 3 5 controlling electrical heater 4x0055 OCC sensor set level 100 1000 Sets level for detecting Occupancy 250 3 5 4x0056 Security access code 0 9999 Code needed for changing protected variables XXXX 3 5 4x0057 Device pressure zero c
21. l control OCC Set 0 Manual control to unoccupied mode 1 Manual control to occupied mode Heating present 1 Heat regulation with water is activated 0 Only air cooling The controller is activated externally from a BMS SCADA system O0 Normal operation 1 Night cooling on Notes for 3x0016 also presented as separate bits 1x0001 1x0004 B0000001 OCC Sensor Status 1 Occupancy detected O Unoccupied mode value resets to O after 1 minute BOO00010 Controller Mode 1 Occupancy O0 Unoccupoed mode resets after expiration of time delay setting in 4x0034 B0000100 Not defined spare B0001000 Not defined spare Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Room This Modbus listings are only valid when controller is set to BMS position dip sw 2 On Coil Status Discrete Output 1 bit RAW Modbus Name Min Max Parameter Remark Std 0x0001 Not used 0 0x0002 ae pos supply 0 1 P_1526 0 Close 1 Open 0 0x0003 wA pos extract 0 1 P_1527 l0 Close 1 Open 0 0x0004_ Not used 0 0x0005 Not used 0 Ox0006__ Not used 0 0x0007 CO sensor use 0 1 P_1537 O not connected 1 connected 0 Input Status Discrete Input 1 bit Read only Modbus Name Min Max Parameter Remark Std x0001 Ala
22. mally open 4x0017 DETECT Occupancy 0 2 P_1520 Q Not used 1 Normally closed 2 Normally open 4x0018 Cool valve output 1 2 P_1546 1 24V AC on off 2 0 10V DC 1 4x0019 Heat valve output 1 2 P_1547 1 24V AC on off 2 0 10V DC 1 4x0020 Air flow sensor type 0 2 P_1531 O Not used 1 Analogue 2 Modbus 2 4x0021 Not used 4x0022 Not used 4x0023 Freeze protection level 5 15 C P1513 su a FAN neatinig is 10 4x0024 Cool set point occupied 15 30 C P_1508 Set point for cooling 23 4x0025__ Heat set point occupied 15 30 C P_1509 Set point for heating 21 4x0026 Cool set point unoccupied 10 30 C P_1510 Set point for cooling 25 4x0027 Heat set point unoccupied 10 30 C P_1511 Set point for heating 19 4x0028 Cool set point night cool 5 20 C P_1512 Set point for cooling 15 4x0029 Room unit min set point 10 30 C P_1550 Min set point from room unit 10 4x0030 Room unit max set point 25 50 C P_1724 Max set point from room unit 40 4x0031 Not used 4x0032 Not used 4x0033 Not used 4x0034 Not used 4x0035 Room unit reset time 0 1200 min P_1549 Time before manual set point goes back to normal 480 4x0036 Min supply airflow OCC 10000 P_1502 Airflow at occupied mode l s 4x0037 Max supply airflow OCC 20000 P_1503 Airflow at occupied mode l s 4x0038 Min supply airflow UnOCC 10000 P_1504 Airflow at unoccupied mode l s 4x0039 Min extract airflow OCC 10000 P_1505 Airflow at occupied mode l s 4x0040 Max extract airflow OCC 1 20000
23. nt 3x0032 Not used 3x0033 Battery level in room unit Volt scaled 1 10 3x0034 Not used 3x0035 Supply flow sensor pressure Pressure scaled x10 dPa 3x0036 Extract flow sensor pressure Pressure scaled x10 dPa 3x0037 Analogue Input 1 0 10000 mV Window contact switch 3x0038__ Analogue Input 2 0 10000 mV Occupancy 3x0039 Analogue Input 3 0 10000 mV 3x0040 Analogue Input 4 0 10000 mV CO 3x0041 PWM 1 output 0 100 Cooling 11 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Input register 16 bit integer register Read only Modbus Name Min Max Parameter Remark Std 3x0042 PWM output 2 0 100 Heating 3x0043 PWM output 3 0 100 Supply damper 3x0044 PWM output 4 0 100 Extract damper 3x0045 Analogue output 1 0 10000 mV 3x0046 Analogue output 2 0 10000 mV 3x0047 Analogue output 3 0 10000 mV 3x0048 Analogue output 4 0 10000 mV 3x0049 PID controller out level 100 100 Shows cooling 100 0 and heating gt 0 100 3x0050 Not used 3x0051 PID supply level 0 100 Regulator level 3x0052 PID extract level 0 100 Regulator level 3x0053 Cool output 0 100 Outlevel 3x0054 Heat output 0 100 Outlevel 3x0055 Supply damper position 0 100 3x0056 Extract damper position 0 100 3x0057 Not used 3x0058 Supply airflow l s 3x0059 Extract airfl
24. ow l s 3x0060 Room temperature Temperature scaled 1 10 Cx10 3x0061 Supply air temperature Temperature scaled 1 10 Cx10 3x0062 CO in room Displays the CO value of the connected sensor ppm 3x0063 Copy of Input Status 1 16 0 65535 Bit O 0x0001 Bit 15 0x0016 3x0064 Copy of Input Status 17 32 0 65535 Bit O 0x0017 Bit 15 0x0032 3x0065 Copy of Input Status 33 48 0 65535 Bit O 0x0033 Bit 15 0x0048 3x0066 Copy of Input Status 49 64 0 65535 Bit O 0x0049 Bit 15 0x0064 3x0067 Not used 3x0068 Not used 12 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Zone This Modbus listings are only valid for CONTROL Zone set to BMS function dip SW 2 On Coil Status Discrete Output 1 bit RAW Modbus Name Min Max Parameter Remark Std 0x0001 Not used 0 1 0 0x0002 Emergency action supply 0 1 P_1709 0 Close 1 Open on supply dampers 0 0x0003 Emergency action extract 0 1 P_1710 0 Close 1 Open on extract dampers 0 0x0004 Not used 0 1 1 clears alarm 0 0x0005 Not used 0 1 0 0x0006 Not used 0 1 0 0x0007 Not used 0 1 0 Input Status Discrete Input 1 bit Read only Modbus Name Min Max Parameter Remark Std x0001 Condensation 0 1 x0002 Relay state 0 1 x0003 Not us
25. rdware reset x0033 Parameter file format error 0 1 ALARM requires Hardware reset x0034 No Modbus ID 0 1 ALARM requires Hardware reset 13 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Zone Input Status Discrete Input 1 bit Read only Modbus Name Min Max Parameter Remark Std x0035 No Application ALARM requires Hardware reset x0036 No parameters ALARM requires Hardware reset x0037 Parameter missing ALARM requires Hardware reset x0038 Parameter value error ALARM requires Hardware reset x0039 Parameter file size ALARM requires Hardware reset x0040 Wrong parameter file ALARM requires Hardware reset x0041 ae Group Contro ALARM resets after right parameters x0042 Check Duct Group ALARM resets after right parameters x0043 Previous parameters are lost ALARM requires Hardware reset x0044 Factory parameters take up ALARM requires Hardware reset x0045 Not used x0046 Not used x0047 No supply pressure from AHU Not used in CONTROL Zone x0048 No extract pressure from AHU Not used in CONTROL Zone x0049 Supply duct 100 open Not used in CONTROL Zone x0050 Extract duct 100 open Not used in CONTROL Zone x0051 Low voltage detect ALARM resets automatically x00
26. rm condensation 0 1 If risk of condensation with water cooling x0002 Relay status 0 1 Shows if the internal relay is on x0003 Occupancy sensor 0 1 Shows Occupancy mode 1 on ore 2 off x0004 Window switch 0 1 Shows switch mode 1 on ore 2 off x0005 Occupancy status 0 1 Occupancy status including delay off time x0006 No alarm is activated 0 1 Overall information x0007 INo room unit 1 0 1 Alarm resets automatically x0008 No room unit 2 0 1 Alarm resets automatically x0009 No pressure sensor 0 1 Not used in CONTROL Room x0010 No supply flow sensor 0 1 Alarm resets automatically x0011 No extract flow sensor 0 1 Alarm resets automatically x0012 Room unit 1 Temperature 0 1 Alarm resets automatically x0013 Room unit 2 Temperature 0 1 Alarm resets automatically x0014 Supply temp sensor shortcut 0 1 Alarm resets automatically x0015 No supply temp sensor 0 1 Alarm resets automatically x0016 Low battery level in room unit 0 1 Alarm resets automatically x0017 Control overload PI control 0 1 Alarm resets automatically x0018 iControl overload set point 0 1 Alarm resets automatically x0019 Not used 0 1 x0020 Not used 0 1 x0021 INo application parameters 0 1 Alarm resets automatically x0022 Power supply gt 27 V AC 0 1 Alarm resets automatically x0023 System fault 0 1 Alarm resets automatically x0024 No serial number 0 1 x0025 Not used 0 1 x0026 Output X11 shortcut 0 1 Alarm needs hardware reset x0027 Output X12 shortcu
27. some duct is 100 open this bit is 1 Holding register 16 bit integer register R W Modbus Name Min Max Parameter Remark Std 4x0001 JAHU SuPress Supply pressure from AHU 4x0002 AHU Express Extract pressure from AHU 4x0003 Start Delay 1 60 P_1001 Start time in minutes 5 4x0004 Min Press SU 50 5000 P_1004 Min regulated pressure Supply Pa 50 4x0005 Start Press Su 50 5000 P_1002 Start pressure for AHU Supply Pa 100 4x0006 Max Press SU 50 5000 P_1005 Max regulated Supply pressure Pa 200 4x0007 Min Press EX 50 5000 P_1006 Min regulated extract pressure Pa 50 4x0008 Start Press EX 50 5000 P_1003 Start pressure for AHU Extract Pa 100 4x0009 Max Press EX 50 5000 P_1007 Max regulated Extract pressure Pa 200 4x0010 Increase limit 70 100 P_1013 Energy optimization 95 4x0011 Decrease limit 40 80 P_1014 Energy optimization 70 4x0012 Manual SuPress H era setpoint 4x0013 Manual ExPress HTE a set point 4x0014 Alarm delay time 0 60 P1011 E ae before 10 4x0015 Energy optim Step size 100 P_1012 Step in Pa for increase decrease pressure 10 4x0016 Duct reading interval 100 P_1096 Time in minutes between reading values 1 4x0017 Not used 4x0018 Deviation 100 P_1008 ae ee oon 2 18 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Modbus variables for CONTROL Optimize Input register 16 bit integer register Read only Modbus Name Min Max Parameter Remark Std 3x0001
28. sure sensor values out of range LED 3 5 1x0008 Alarm temperature 0 1 Opera ng Alarm 1 room temp sensor values out of range 3 5 sensor LED is red 1x0009 Alarm temperature 0 1 Operating Alarm 1 internal temp sensor fault values out of 3 5 sensor range LED is red 1x0010 Alarm wrong set points 0 1 Opera ng Alarm 1 set point for heating and cooling are 3 5 overlapping LED is red 1x0011 Alarm CAC sensor 0 1 1 value from CAC sensor incorrect or missing 5 Room temperature outside set point 2 K Limit is adjustable OHS Alamicomtort temp o t in variable 4x0040 LED is flashing red green 2 CO level above max level 200 ppm Limit is adjustable in Pls cence a variable 4x0041 LED is flashing red green 2 1x0014 Not used 0 1 1x0015__ Not used 0 1 3 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Holding register 16 bit integer register RAW Swegon Swegon reserves the right to alter specifications 20150223 Modbus Name Min Max Remarks Std Version 4x0001 Component ID 0 10 ID for type of controller in CONTROL Room Zone Optimize 6 3 5 and WISE system 4x0002 18 Component Name 0 999 Name built of max 16 char use ASCII standard table 0 3 5 0 Normal air cool and water heat 1 Not used 4x0019 Operating mode 0 10 2 Not used 0 3 5 3 Air cool Air heat and
29. t 0 1 Alarm needs hardware reset x0028 Output X13 shortcut 0 1 Alarm needs hardware reset x0029 Output X14 shortcut 0 1 Alarm needs hardware reset x0030 ISPI Flash memory empty 0 1 Alarm needs hardware reset x0031 Radio chip broken 0 1 Alarm needs hardware reset 8 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Swegon Input Status Discrete Input 1 bit Read only Modbus Name Min Max Parameter Remark Std 1x0032 Parameter file updated 0 1 Alarm needs hardware reset x0033 Parameter file format error 0 1 Alarm needs hardware reset x0034 No Modbus ID 0 1 Alarm needs hardware reset x0035 No Application 0 1 Alarm needs hardware reset x0036 Parameter file missing 0 1 Alarm needs hardware reset x0037 Parameter missing 0 1 Alarm needs hardware reset x0038 Parameter incorrect 0 1 Alarm needs hardware reset x0039 Parameter file wrong size 0 1 Alarm needs hardware reset x0040 Wrong parameter file 0 1 Alarm needs hardware reset x0041 Not used x0042 Not used x0043 Previous parameter missing 0 1 Alarm needs hardware reset x0044 Parameters uploaded 0 1 Alarm needs hardware reset x0045 Not used x0046 Not used x0047 INot used x0048 Not used x0049 Not used 0 1 x0050 Not used 0 1 x0051 Supply power 24V to low 0 1 Alarm resets automatically x0052 Not used x0053 Not used x0054 Negative press
30. ure 0 1 Alarm resets automatically Holding register 16 bit integer register RAW Modbus Name Min Max Parameter Remark Std 4x0001 Relay at emergency 0 1 P_107 0 Close 1 Open 2 No action 1 4x0002 Controller running mode 1 7 A a 1 4x0003 Room number 0 32000 P_114 Possible to set at room number 4x0004 Valve exercise interval 0 72 P_108 Time in hour between exercise O inactivated 0 4x0005 Delay off time 0 20 P_109 Delay before controller sets to unoccupied mode 20 4x0006 Alarm delay in general 0 60 P_110 Alarm delay in minutes 30 4x0007 Alarm delay controller 0 60 P_111 Alarm delay in minutes 30 4x0008 Alarm delay set points 0 60 P_112 Alarm delay in minutes 30 4x0009 Not used 4x0010__ Not used 1 4x0011 Not used 0 4x0012 Not used 4x0013 Not used 1 4x0014 Control type 1 3 P_1501 1 Heating and cooling 2 Only cooling 1 4x0015 Number of room units 1 2 P_1536 1 or 2 room units 1 Swegon reserves the right to alter specifications 20150223 www swegon com Modbus tables Swegon Holding register 16 bit integer register R W Modbus Name Min Max Parameter Remark Std 4x0016 Window switch 0 2 P_1520 O Not used 1 Normally closed 2 Nor