Contents

1. FROM SUPPLY FROM GENERATOR SUPPLY FROM GENERATOR SUPPLY PI qo M aes B a TE sali pene l SD ET 1 FRONT FRONT_ B i B IT IL U bi 25 E 5 De E ed ML G A g G U PIE mi TEEF H i dh Bi E B IL A FROM GENERATOR SUPPLY ARMI IET BREET TE iman ioan SANDER ENTE UE FROM GENERATOR SURELY ROM UTLITY SUPPLY PATUIT RUBRI STANDARD ALTERNATE E Sb PET al tbc EAT AR BUPPLV TR UTUTY SUPPLY BOTTOM Adr e UY AC FREM GEN ERATOR FROM UTILITY SUPPLY Feo tiry PEEK GK auto Legali iene muss qe B 2 E ARR JE durer Ha DID B si 2 FRONT A FRONT n 4 hg C L d 5 G i U i ie E 1 1 Si GENERATOR
2. 16 17 18 19 20 21 062 REVO 04 11 19 870 TRANSFER SWITCH 9 1 MANUAL OPERATION RECOMMENDED MAINTENANCE FRONT VIEW TYPICAL 3 4 POLE 100A 250A TRANSFER MECHANISM FRONT VIEW TYPICAL 3 4 POLE STYLE 400A 1200A TRANSFER MECHANISM CONNECTION CONFIGURATION OPTIONS CABLE TERMINAL INFORMATION REQUIREMENTS FOR UPSTREAM CIRCUIT PROTECTIVE DEVICES GROUND FAULT SITE TEST REQUIREMENTS 16 1 PERFORMANCE TEST TROUBLESHOOTING REPLACEMENT PARTS PRODUCT RETURN POLICY NOTES PERFORMANCE TEST FORM 16 16 17 19 20 20 21 21 22 25 26 27 28 Thomson Technology 870 TRANSFER SWITCH 1 REVISION HISTORY The following information provides historical summarv of changes made to this product since the original release Operating amp Service Manual Version Rev 0 04 11 19 Original release Contact Thomson Technology to obtain applicable instruction manuals or if in doubt about any matter relating to installation operation or maintenance Soft copy of the most current version is available at www thomsontechnology com NOTE All information contained in this manual is for reference only and is subject to change without notice 2 EQUIPMENT STORAGE The following procedures are required for correct storage of the transfer switch prior to installation CAUTION Failure to store equipment as specified may cause damage and
3. vi Green LED above mimic bus for the Utilitv source is OFF To terminate the test press the Utilitv Power Fail Simulate push button on the TSC 80 faceplate again and hold until the LED above the pushbutton changes state The transfer switch will begin transferring to the utilitv supplv following the 2 minute utility return delay period Note the utility return delay timer will only begin timing if the utility voltage is above 85 nominal on all phases Once the Generator power switching device opens the transfer switch mechanism will pause in the neutral position for the 3 second neutral delay period then the mechanism will complete the transfer and close the Utility power switching device to return the load to the Utility source Once the load has transferred onto the utility source the engine will continue to run for the 2 minute cool down time delay period and will then it will automatically stop Perform a power outage test by opening the upstream utility feeder breaker The TSC 80 controller Utility supply LED lights will de energize the generator set will start after the 3 second engine start delay has expired The generator should transfer on load as described in item 12 above Return the transfer switch to utility power by re closing the upstream utility breaker The load should re transfer back to the utility supply and the engine should stop as described in item 13 above Repeat tests 12 through 14 two or more times to ensure cor
4. A Subsidiary of Regal Beloit Corporation 8 CONTROL 5 870 AUTOMATIC TRANSFER SWITCHES INSTALLATION OPERATING 8 SERVICE MANUAL 9087A 198 Street Langley BC Canada V1M 3B1 7 Telephone 604 888 0110 Telefax 604 888 3381 7 E Mail info thomsontechnology com www thomsontechnology com 870 TRANSFER SWITCH 5 1 PRODUCT REVISION HISTORY 1 2 EQUIPMENT STORAGE 1 3 NOTES TO INSTALLER 1 3 1 UPSTREAM CIRCUIT PROTECTIVE DEVICES ELECTRICAL CONNECTIONS 2 3 2 TRANSFER SWITCHES WITH INTEGRAL OVER CURRENT PROTECTION 2 3 3 TRANSFER SWITCHES WITH MULTI TAP VOLTAGE CAPABILITY 3 3 4 SYSTEM PHASING HIGH LEG DELTA SYSTEMS 3 3 5 REMOTE START CONTACT FIELD WIRING 4 3 6 DIELECTRIC TESTING 5 3 7 INSTALLATION OF OPEN TYPE TRANSFER SWITCHES 5 4 GENERAL DESCRIPTION 5 4 1 PRODUCT MODEL CODE 6 4 2 TYPICAL COMMISSIONING PROCEDURES 7 5 GENERAL THEORY OF OPERATION 8 5 1 STANDARD AUTOMATIC TRANSFER SWITCH 8 5 2 SERVICE ENTRANCE AUTOMATIC TRANSFER SWITCH 9 5 3 TESTMODES 12 6 OVER CURRENT PROTECTION 12 6 1 STANDARD TS 870 AUTOMATIC TRANSFER SWITCH 12 6 2 OPTIONAL TS 870 AUTOMATIC TRANSFER SWITCH WITH INTEGRAL OVER CURRENT PROTECTION 13 7 GENERAL NOTES ON SERVICING ATS MECHANISM 13 8 TRANSFER SWITCH MECHANISM 100A 250 14 8 1 MANUAL OPERATION 15 9 TRANSFER SWITCH MECHANISM 400A 1200 AMP 15 PM062 REVO 04 11 19 Thomson Technology 10 11 12 13 14 15
5. Failure to confirm and match transfer switch voltage with the system voltage could cause serious equipment damage The voltage selections and connections are shown on the engineered drawings attached to each transfer switch The factory default settings will be indicated on the calibration label attached on the inside of the enclosure door supplied loose on open style models A blank label is included to record the applicable settings if the configuration is changed from the factory default settings To change the transfer switch configuration the following must be accomplished e Change voltage taps on potential transformers PT s to correct system voltage refer to drawings Change TSC 80 programming for nominal system voltage Refer to Section 4 of the TSC 80 instruction manual 063 for further information e Once the PT voltage taps and TSC 80 has been re programmed to correct operating voltage the control circuit isolation plug on the mechanism may be reconnected prior to voltage energization 3 4 SYSTEM PHASING HIGH LEG DELTA SYSTEMS For systems using high leg delta 240V 3 phase 4 wire systems connection of supply conductors must have the correct phasing as shown below WARNING Failure to match correct system phasing will result in serious damage to the TSC 80 controller PM062 REV 0 04 11 19 3 Thomson Technology 870 TRANSFER SWITCH Automatic Transfer Switch Utilitv Supplv PHB P
6. 65 000 50 000 35 000 100 000 T J TS 87xA 0800 800 65 000 50 000 35 000 100 000 Consult Factorv TS 87xA 1000 1000 65 000 50 000 42 000 100 000 Consult Factorv TS 87xA 1200 600 1200 65 000 50 000 42 000 100 000 Consult Factory 1 Standard ratings only are shown Consult Thomson Technology for versions with higher withstand current ratings 2 For other model types not shown contact Thomson Technology for further information PM062 REVO 04 11 19 20 Thomson Technology 870 TRANSFER SWITCH Fuse ratings shown maximum allowable to permit use of the transfer switch in application with available fault current not exceeding that shown Consideration must be given to fuse sizing when fuses also provide overload protection Please refer to the factorv for further information on upstream protection requirements if required 16 GROUND FAULT SITE TEST REQUIREMENTS Per NEC and UL1008 a ground fault protected svstem shall be performance tested when first installed on site A written record of this shall be made and be available to the authoritv having jurisdiction A form is provided at the back of this manual for this purpose see Section 21 Confirm and record actual trip setpoints in the form provided which is to be made available on request by inspection authority 16 1 PERFORMANCE TEST Qualified Field Service technicians require a calibrated current injection test apparatus and must be knowledgeable in breake
7. 80 controller verify output signals with circuit board mounted diagnostic LED s TSC 80 has Transfer Fail alarm activated as indicated by flashing Load on Generator LED Determine cause of alarm and rectify before TSC 80 is reset PM062 REVO 04 11 19 22 Thomson Technology 870 TRANSFER SWITCH Symptom Will not re transfer to utility source upon restoration Will not transfer to generator source upon failure of utility source Transfer to generator source without a power failure in the utility source Isolation plug out Utility disconnect switch is in the de energized position Service Entrance Rated ATS Switch to the Energized position A test mode has been activated check TSC 80 status LED Utility voltage is below the pre programmed limits check utility source for adequate voltage A loose control connection Faulty motor limit switch Defective motor TSC 80 has incorrect voltage programming jumper setting for correct system voltage Defective TSC 80 controller verify output signals with circuit board mounted diagnostic LED s TSC 80 has Transfer Fail alarm activated as indicated by flashing Load on Utility LED Determine cause of alarm and rectify before TSC 80 is reset Isolation plug out Generator set not producing enough voltage frequency or output circuit breaker open TSC 80 has incorrect voltage programming jumper setting for correct system vo
8. 870 Automatic Transfer Switch may be supplied with optional integral over current protection within the enclosed contact power switching units for applications such as Service Entrance Rated equipment Refer to Section 6 of this manual for detailed information on over current protection The TS 870 series transfer switches use a type TSC 80 microprocessor based controller which provides all necessary control functions for fully automatic operation The TSC 80 controller is mounted on the door of the transfer switch enclosure and operating status is shown via LED lights PM062 REV 0 04 11 19 5 Thomson Technology 870 TRANSFER SWITCH For further information on the TSC 80 Transfer Controller refer to separate instruction manual PMO63 The power switching devices used for the Utilitv and Generator sources are operated bv an electricallv driven motor mechanism in the transfer switch The transfer switch motor utilizes the power from the source to which the electrical load is being transferred The mechanism provides a positive mechanical interlock to prevent both power switching units from being closed at the same time which allows an interrupted break before make transfer sequence The TSC 80 transfer controller provides a standard neutral position delay timer to allow adequate voltage decay during transfer operation to prevent out of phase transfers Note For the purpose of this manual the following standard nomenclature is utilize
9. Se A ats Lol U LE JAN TU LOAD LSERNETE 2B PRO CNA TGR UTILITY SUPPLY ALTERNATE F ALTERNATE G LTERN m ej TRANSFER SWITCH ORIEN TATION AND CABLE ENTRY LOCATION i Teo TFANNI Na FEREENIE da Ev pure PM062 REVO 04 11 19 19 Thomson Technology 870 TRANSFER SWITCH 14 CABLE TERMINAL INFORMATION TIGHTNESS TERMINAL RATING In Ibs TERMINAL MOUNTING CABLE SCREW CLAMP 2 4 0 120 120 BASIC MODEL TS 87xA 0100 TS 87xA 0150 TS 87xA 0200 1 TS 87xA 0250 TS 87 0400 TS 87 0600 TS 67xA 0800 210 B00NCM 375 TS 87 1200 4 0 500 375 375 1 Optional terminal ratings are available in some models Consult Thomson Technology 2 For other model types not shown contact Thomson Technology for further information 15 REQUIREMENTS FOR UPSTREAM CIRCUIT PROTECTIVE DEVICES WITHSTAND CURRENT RATING AMPS RMS With Upstream Circuit Breaker With Upstream Fuse RATED Protection Protection BASIC MODEL MAX CURRENT Up to VOLTAGE A 240V 480V 600V 600V Fuse Type TS 87xA 0100 65 000 25 000 18 000 100 000 T J TS 87xA 0150 65 000 25 000 18 000 100 000 T J TS 87xA 0200 200 65 000 N A N A N A T J TS 87xA 0250 250 65 000 35 000 25 000 100 000 T J TS 87xA 0400 400 65 000 50 000 35 000 100 000 T J TS 87xA 0600 60
10. models of transfer switch with adjustable integral over current protection trip units the over current protection must be set prior to operation The equipment will be shipped from the factory with a long time current setting of 100 of the equipment rating and maximum instantaneous short time ground fault if supplied current and time delay settings WARNING Do Not Energize this equipment until device settings have been verified to ensure proper system protection amp coordination Failure to do so may result in equipment failure The TS 870 transfer switches with optional integral over current protection are identified in the product model code Refer to Section 4 1 for further details on model coding 7 GENERAL NOTES ON SERVICING ATS MECHANISM See CAUTION on Page 2 When performing any service work on the transfer mechanism it is imperative that the following be observed 7 1 To maintain mechanical integrity ensure that e All limit switches linkages are correctly adjusted to provide full travel of the power switching device toggles without exerting unnecessary forces associated with 062 REV 0 04 11 19 13 Thomson Technology 870 TRANSFER SWITCH excessive travel Ensure that power switching device travel far enough to reset any internal trip unit it is more important for the toggle to go fully in the off direction than in the direction e Mechanical interlocking is correct when one power
11. power cables to prevent pick up of induced voltages 3 5 4 An interposing relav mav be required if field wiring distance is excessivelv long i e greater than 100 feet 30m and or if a remote contact has a resistance of greater than 5 0 ohms 3 5 5 The remote start contact must be voltage free i e drv contact The use ofa powered contact will damage the transfer controller 3 6 DIELECTRIC TESTING Do not perform any high voltage dielectric testing on the transfer switch with the TSC 80 controller connected into the circuit as serious damage will occur to the controller All AC control fuses or control circuit isolation plugs connected to the TSC 80 must be removed if high voltage dielectric testing is performed on the transfer switch 3 7 INSTALLATION OF OPEN TYPE TRANSFER SWITCHES Please refer to the factory for additional information 4 GENERAL DESCRIPTION Thomson Technology TS 870 series of Automatic Transfer Switches employ two mechanically interlocked enclosed contact power switching units and a microprocessor based controller to automatically transfer system load to a generator supply in the event of a utility supply failure System load is then automatically re transferred back to the utility supply following restoration of the utility power source to within normal operating limits The standard TS 870 series Automatic Transfer Switch is rated for 100 system load and requires upstream over current protection The TS
12. screen to display additional detailed information on the operation and settings of the TSC 80 controller for simplified servicing trouble shooting procedures For detailed information refer to the separate SDM module instruction manual PMO65 Symptom 1 Possible Causes Will not re transfer to utility source Isolation plug out upon restoration Utility disconnect switch is in the de energized position Service Entrance Rated ATS Switch to the Energized position A test mode has been activated check TSC 80 status LED Utility voltage is below the pre programmed limits check utility source for adequate voltage A loose control connection Faulty motor limit switch Defective motor TSC 80 has incorrect voltage programming jumper setting for correct system voltage Defective TSC 80 controller verify output signals with circuit board mounted diagnostic LED s TSC 80 has Transfer alarm activated as indicated by flashing Load on Utility LED Determine cause of alarm and rectify before TSC 80 is reset Will not transfer to generator source Isolation plug out upon failure of utility source Generator set not producing enough voltage frequency or output circuit breaker open TSC 80 has incorrect voltage programming jumper setting for correct system voltage Warm up time delay function has not timed out yet verify TSC 80 timer setting A loose control connection Faulty motor limit switch Defective motor Defective TSC
13. void warranty Before storing unpack sufficiently to check for concealed damage If concealed damage is found notify Thomson Technology and the Carrier immediately Repack with the original or equivalent packing materials Protect from physical damage Do not stack Store indoors in a clean dry well ventilated area free of corrosive agents including fumes salt and concrete cement dust Apply heat as necessary to prevent condensation The following storage temperature and humidity must be maintained 20 to 70 Celsius 9596 Humidity non condensing 3 NOTES TO INSTALLER Before opening the transfer switch enclosure to perform any service task or to manually transfer the mechanism it is imperative to isolate the transfer switch from any possible source of power Failure to do so may result in serious personal injury or death due to electrical shock 062 REV 0 04 11 19 1 Thomson Technology 870 TRANSFER SWITCH CAUTION installation and or service work performed must be done by qualified personnel only Failure to do so may cause personal injury or death 3 1 UPSTREAM CIRCUIT PROTECTIVE DEVICES ELECTRICAL CONNECTIONS To ensure satisfactorv installation of this equipment be sure to observe Cable Terminal Information regarding power cable connection tightness and Requirements for Upstream Circuit Protective Devices located in this manual All mechanical and electrical connecti
14. 80 A STANDARD 0600 U 416 X SPECIAL bie va p 21 CONNECTION CONFIGURATION i SEE DRAWING M 007450 00051 X SPECIAL A STANDARD 12 APPLICATION FOR 50HZ APPLICATION ALTERNATE 400 1200 A STANDARD C ALTERNATE C 400 1200A B SERVICE ENTRANCE 16 CONTROLLER D ALTERNATE D 400 1200A X SPECIAL 1 TSC 80 13 OPERATION TYPE 1 OPEN TRANSITION 2 MANUAL ELEC OP 7 NONE MANUAL 17 ENCLOSURE TYPE NEMA 1 ASA 61 GREY B NEMA 2 ASA 61 GREY X SPECIAL C NEMA 12 ASA 461 GREY 14 GERTIFICATION D SD ASA 61 GREY A UL 1008 E NEMA DD ASA 61 GREY GSA 22 2 178 NOT APPLICABLE F NEMA 4X STAINLESS STEEL G NONE OPEN STYLE X SPECIAL 4 2 TYPICAL COMMISSIONING PROCEDURES CAUTION Commissioning procedures must be performed by qualified personnel only Ensure the Automatic Transfer Switch ATS Isolation Plug is disconnected prior to energizing the supply sources Manually place the transfer switch mechanism in the neutral position prior to applying power Failure to do so may result in equipment failure or personal injury Note The TYPICAL AUTOMATIC TRANSFER SWITCH COMMISSIONING PROCEDURES MODEL SERIES TS 870 attached as Appendix A is provided for general information PM062 REVO 04 11 19 7 Thomson Technology 870 TRANSFER SWITCH only pertaining to typical site installations and applications Con
15. AIN THE CORRECT ATS PHASING WILL RESULT IN EQUIPMENT MALFUNCTION AND DAMAGE 3 Confirm cable size is correct for the lugs supplied in the transfer switch line and load Confirm the cables were meggered by the electrical contractor to ensure no cross phase connections or conduction to ground 4 Confirm cable lugs are properly torqued Confirm cable installation ensure the cables do not interfere with normal equipment operation or which may cause component damage 5 Manually operate the transfer mechanism to the appropriate source of supply Leave the Isolation Plug disconnected until final Transfer Switch Commissioning is to be completed Final Commissioning 1 Verify installation of the Automatic Transfer Switch as per installation manual and verify wiring also see the Pre Commissioning Checks Confirm phase neutral and grounding conductors are installed as per electrical code requirements Note Confirm neutral conductors of both sources are correctly installed and are solidly grounded for 3 phase 4 wire configurations 2 Check for mechanical damage shipping or installer 3 Check for cable interference with mechanical moving parts or the motor brake on 100A 250A ATS mechanism 4 Verify correct control wire interconnects to the engine generator set auto start stop circuitry Ensure the engine controller automatic start circuit does not draw more than 5 0 amps resistive across the TSC 80 Engine Start contact TSC80 Engine
16. HC Neural UB UC N Orange High Leg C Red L Yellow CAUTION All installation and or service work performed must be done by qualified personnel only Failure to do so may cause personal injury or death Where transfer switches are supplied without power isolation transformers PT1 amp PT2 for ATS control logic it is essential that the orientation of phase conductors of the supply source be arranged such that the phase of highest potential with respect to ground is not connected to the power supply inputs to the controller A Phase for both supplies Failure to do so will result in equipment damage Per NEC Article 384 3 f The B phase shall be that phase having the higher voltage to ground on a 3 phase 4 wire delta connected systems 3 5 REMOTE START CONTACT FIELD WIRING As a minimum the remote engine start control field wiring shall conform to the local regulatory authority on electrical installations Field wiring of a remote start contact from a transfer switch to a control panel should conform to the following guidelines to avoid possible controller malfunction and or damage PM062 REVO 04 11 19 4 Thomson Technology 870 TRANSFER SWITCH 3 5 1 Minimum 14 AWG 2 5mm wire size shall be used for distances up to 1008 30m For distances exceeding 100 ft 30m consult Thomson Technologv 3 5 2 Remote start contact wires should be run in a separate conduit 3 5 3 Avoid wiring near AC
17. Start contact is voltage free and the only voltage measured should result from the engine APPENDIX SVF035 DOC 04 11 18 REVO THOMSON TECHNOLOGY 10 11 12 13 14 15 16 TYPICAL AUTOMATIC TRANSFER SWITCH COMMISSIONING PROCEDURES Model Series TS 840 870 controllers internal control logic Note The ATS Engine Start contact CLOSES to start the engine and OPENS to stop the engine Place the generator engine controller in the OFF position and open the generator local circuit breaker Ensure the ATS isolation plug is disconnected prior to application of voltage of the supply sources Energize the utility supply and the generator supply sources and verify these meet the correct voltage phasing and phase rotation for the ATS and system Once these have been confirmed to be correct de energize both sources before installing the isolation plug Once the isolation plug is connected the ATS and system load may be energized with utility power once the site electrical contractor and or owner as required give authorization to proceed If Utility power is within nominal limits the ATS should transfer to the utility source To determine correct operation observe the following on the TSC 80 faceplate i Utility Source green LED is On ii Green LED above mimic bus for the Utility source is iii Load green LED is On To verify all LED s are operational perform a LAMP TEST operation lamp test is initia
18. ally reset the power switching device in the transfer closed to a live source switch by moving it off and then on again with the manual operating handle Limit switch incorrectly adjusted The transfer switch has completed a Limit switch failure or improper adjustment has failed to transfer but the motor has overheated and disconnect motor the internal thermal protector has opened Binding or jamming of the transfer mechanism PM062 REV 0 04 11 19 24 Thomson Technology 870 TRANSFER SWITCH Note There are no user serviceable components located on the TSC 80 printed circuit board If the TSC 80 controller is deemed to be defective it must be returned to the Thomson Technologv Factorv for repair or replacement Please refer to section 19 for further detailed on product return procedures required 18 PARTS Replacement parts are available for the transfer switch as follows Note When ordering replacement parts please provide the following information Transfer Switch Model code e g TS 873AA0200AS Transfer Switch Serial Number e g W 022345 The above information can be found on the transfer switch equipment rating plate located on the outside of the ATS door PM062 REVO 04 11 19 25 Thomson Technology 870 TRANSFER SWITCH D 2 Thomson Technologv Component Description Part Number Comments TSC 80 Controller Board 005712 Must set Program Jumper pri
19. ch mechanism If the position of the transfer switch mechanism is clearly in the neutral position the service has been successfully disconnected Note If the position of the transfer switch mechanism is clearly in the neutral position the service disconnected pilot light may not have illuminated due to the following reasons a Utility and generator supply voltages are not present the pilot light requires AC supply voltage to be present b The pilot light may be burnt out The bulb should be immediately replaced with a suitably rated bulb Failure of one or more of the sensing logic contacts qualified service technician is required to trouble shoot this specific condition PM062 REVO 04 11 19 10 Thomson Technology 870 TRANSFER SWITCH Switch the utilitv control circuit isolation switch to the de energized position to remove utilitv control power To isolate the generator supplv remove the control circuit isolation plug Note The AC power conductors will still remain energized all the control circuits are de energized and isolated the Service Disconnected pilot light will not illuminate due to loss of control power Note To return the transfer switch back to normal operation the utilitv control circuit disconnect switch and control circuit isolation plug must be switched on and reconnected for correct operation e The transfer switch door should then be securely closed using a suitable tool and locke
20. confirm with a copy of our Order Acknowledgement via fax advising the RMA number which should be used to tag the defective controller prior to shipment 062 REV 0 04 11 19 26 Thomson Technology 870 TRANSFER SWITCH 20 5 062 REV 0 04 11 19 27 Thomson Technologv TS 870 TRANSFER SWITCH 21 PERFORMANCE TEST FORM This form should be retained bv those in charge of the building electrical installation in order to be available to the authoritv having jurisdiction Dae Persom Terug pit evvai ST Li BE PM062 REVO 04 11 19 28 Thomson Technology APPENDIX SVF035 DOC 04 11 18 REVO THOMSON TECHNOLOGY TYPICAL AUTOMATIC TRANSFER SWITCH COMMISSIONING PROCEDURES Model Series TS 840 870 Note The following commissioning procedures are provided for general information only pertaining to typical site installations and applications Contact Thomson Technology for further information as may be required CAUTION Commissioning procedures must be performed by qualified personnel only Ensure the Automatic Transfer Switch ATS Isolation Plug is pulled prior to energizing the supply sources Manually place the transfer switch mechanism in the neutral position by opening both Utility and Generator Power Switching devices prior to applying power Failure to do so may result in equipment failure or personal injury NOTE An optiona
21. d e Utility to indicate the source of primary power e Generator to indicate the source of standby power e Power switching device to indicate the transfer switch power switching device 4 1 PRODUCT MODEL CODE The type of TS 870 series transfer switch supplied is identified by way of a 21 digit product code which appears on the equipment rating plate MODEL on the door of the transfer switch and on the transfer switch drawings The model code structure and definitions are as follows PM062 REV 0 04 11 19 6 Thomson Technology 1C 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 870 TRANSFER SWITCH 1 3 SERIES 15 VOLTAGE 18 UTILITY SWITCHING DEVICE TS TRANSFER SWITCH 103 WIRE K MOLDED CASE SWITCH 100 1200A D 120 240 M MOLDED CASE SWITCH C W 4 SS THER MAG TRIP 100 200A 5 GROUNDED NEUTRAL MULTI VOLTAGE CAPABLE Ma MOLDED CASE SWITCH GAN 6 POLES ELECTRONIC TRIP 250 1200A 2 2 POLE aaa P MOLDED CASE SWITCH CAN 3 3 POLE a ELECTRONIC amp GF TRIP 250 1200A 4 4 POLE 220 380 19 GENERATOR SWITCHING DEVICE 7 CONFIGURATION TYPE J 240 416 K MOLDED CASE SWITCH 100 1200A A ATS K 254 440 M MOLDED CASE SWITCH C W X SPECIAL M 277 480 THER MAG TRIP 100 200A N 347 600 MOLDED CASE SWITCH CW 8 ELECTRONIC TRIP 250 1200A pa b P MOLDED CASE SWITCH CAN ELECTRONIC amp GF TRIP 250 1200 0250 R 240 20 POWER CONNECTIONS 0400 S 3
22. d forward list of deficiencies to the appropriate parties where applicable
23. d in the closed position with the key Once the transfer switch door has been positively locked closed and secured and only then is it is safe to perform any maintenance procedures as required e If the position of the transfer switch mechanism is_not in the neutral position further procedures are required refer to the following procedure WARNING Failure to positively lock closed and secure the transfer switch door may result in serious personal injury or death due to electrical shock e If the position of the transfer switch mechanism is not in the neutral position the transfer switch mechanism must be manually operated as follows To operate manually pull the manual release plunger on the mechanism releasing the motor drive rod from motor drive arm and move the knob and yoke to the marked Neutral position WARNING Failure to move the mechanism to the Neutral Position may result in serious personal injury or death due to electrical shock The transfer switch door should then be securely closed using a suitable tool and locked in the closed position with the key Once the Transfer switch door has been positively locked closed and secured and only then is it is safe to perform any maintenance procedures as required PM062 REV 0 04 11 19 11 Thomson Technology 870 TRANSFER SWITCH WARNINGI Failure to positivelv lock closed and secure the transfer switch door mav result in serious personal injurv
24. e Energized position A test mode has been activated check TSC 80 status LED Utility voltage is below the pre programmed limits check utility source for adequate voltage A loose control connection Faulty motor limit switch Defective motor TSC 80 has incorrect voltage programming jumper setting for correct system voltage Defective TSC 80 controller verify output signals with circuit board mounted diagnostic LED s TSC 80 has Transfer Fail alarm activated as indicated by flashing Load on Utility LED Determine cause of alarm and rectify before TSC 80 is reset Will not transfer to generator source Isolation plug out upon failure of utility source Generator set not producing enough voltage frequency or output circuit breaker open TSC 80 has incorrect voltage programming jumper setting for correct system voltage Warm up time delay function has not timed out yet verify TSC 80 timer setting A loose control connection Faulty motor limit switch Defective motor Defective TSC 80 controller verify output signals with circuit board mounted diagnostic LED s TSC 80 has Transfer Fail alarm activated as indicated by flashing Load on Generator LED Determine cause of alarm and rectify before TSC 80 is reset Power is not available at the load The power switching device s over current protection unit has terminals but the utility or generator opened due to a fault on the system Correct the fault and power switching device appears to be manu
25. ith the control components in the circuit 10 2 Check if control components are tight in sockets 10 3 Periodicallv inspect all terminals load line and control for tightness Re torque all bolts nuts and other hardware Clean or replace anv contact surfaces which are dirtv corroded or pitted 10 4 Transfer switches should be in a clean drv and moderatelv warm location signs of moisture are present dry and clean transfer switch If there is corrosion try to clean it off If cleaning is unsuitable replace the corroded parts Should dust and or debris gather on the transfer switch brush vacuum or wipe clean DO NOT blow dirt into power switching devices 10 5 Test the transfer switch operation While the unit is exercising check for freedom of movement hidden dirt corrosion or any excessive wear on the mechanical operating parts Ensure that the power switching device travel is correct 10 6 Verify all program settings on the TSC 80 controller as per the TSC 80 component calibration label on the rear cover of the controller 10 7 Transfer Mechanism 100 250A confirm that the yoke operates freely on the yoke pivot bushings Should lubrication be required apply medium weight SAE 20 oil sparingly at these points PM062 REVO 04 11 19 16 Thomson Technology 870 TRANSFER SWITCH 10 8 Transfer Mechanism 400 1200 ensure that the manual handle moves freelv the hub when the lock pin is disengaged If lubrication i
26. l hand held plug in Service Display Module SDM is available for the TSC 80 Transfer Controller The SDM module provides an LCD screen to display additional detailed information on the operation and settings of the TSC 80 controller for simplified servicing trouble shooting procedures For detailed information refer to the separate SDM module instruction manual PMO65 Pre Commissioning Checks Prior to Commissioning Agent On Site to allow loads to be supplied prior to final commissioning 1 Verify supply source voltage to be applied to the transfer switch is of the correct nominal value Confirm this to be the same as listed on the ATS drawings and the ATS equipment label NOTE The factory default system voltage setting for multi voltage TS 840 870 transfer switches is 480 which will be indicated by a letter Y in the voltage code as shown on the ATS model code e g TS 873A0250A1AY 1AKKAA and a warning tag attached to the isolation plug For other system voltages refer to the ATS instruction manual for re configuring procedures prior to energization FAILURE TO RE CONFIGURE ATS VOLTAGE TO MATCH SYSTEM VOLTAGE WILL RESULT IN EQUIPMENT MALFUNCTION AND DAMAGE If ATS voltage is changed record the new voltage on the TSC 80 Component Calibration Label on the rear cover of the controller 2 For 240V High Leg Delta systems refer to the ATS instruction manual for correct phasing required and re configuring procedures FAILURE TO OBT
27. ltage Warm up time delay function has not timed out yet verify TSC 80 timer setting A loose control connection Faulty motor limit switch Defective motor Defective TSC 80 controller verify output signals with circuit board mounted diagnostic LED s TSC 80 has Transfer Fail alarm activated as indicated by flashing Load on Generator LED Determine cause of alarm and rectify before TSC 80 is reset A test mode has been activated check TSC 80 status LED Utility supply voltage is slightly below voltage sensing setpoints Verify TSC 80 has correct voltage programming jumper setting for system voltage Defective TSC 80 controller verify output signals with circuit board mounted diagnostic LED s Utility power switching device has tripped due to an over current condition and TSC 80 Transfer Fail alarm activated as indicated by flashing Load on Utility LED Determine cause of alarm and rectify before TSC 80 is reset Generator does not start up or stop Verify remote engine control panel is set for automatic mode when it should No time delay when there should be Verify time delay setting of the TSC 80 controller 062 REV 0 04 11 19 23 Thomson Technology 870 TRANSFER SWITCH Symptom Will not re transfer to utility source Isolation plug out upon restoration Utility disconnect switch is in the de energized position Service Entrance Rated ATS Switch to th
28. nnected pilot light is illuminated Jf the Light is illuminated the service has been successfully disconnected and it is safe to perform any maintenance procedures as required In this condition the transfer switch is in the neutral position with both utility and transfer power switching devices open The transfer switch will remain in this condition regardless of condition of the utility and generator supplies i e if the utility power fails the generator will not receive a start condition nor will the transfer switch move to the generator position f the Light is not illuminated further procedures are required refer to the following procedure 4 3 Attach safety lockout padlock to the Service Disconnect control switch to prevent unauthorized change in operating condition and verify transfer switch door is locked closed If the door is not locked turn and remove door key 4 If the Service Disconnected pilot light is not illuminated the service will not have been successfully disconnected and it is therefore not safe to perform any maintenance until the following additional procedures are performed WARNING Qualified personnel must undertake the following procedures_only Failure to do so may result in serious personal injury or death due to electrical shock e Open the door to the transfer switch using a suitable tool and opening the door lock with the key e Visually inspect the actual position of the transfer swit
29. ons must be checked for tightness prior to placing this equipment in service to ensure proper operation and to validate applicable warranty coverage 3 2 TRANSFER SWITCHES WITH INTEGRAL OVER CURRENT PROTECTION For models of transfer switch with integral over current protection the over current protection must be set prior to operation The equipment will be shipped from the factory with a long time current setting of 100 of the equipment rating and maximum short time instantaneous current and time delay settings WARNING Do Not Energize this equipment until device settings have been verified to ensure proper system protection amp coordination Failure to do so may result in equipment failure Refer to Section 5 2 2 of this manual for additional information on operation of the Transfer switch following an over current trip condition Refer to information supplied with the transfer switch documentation package for adjustment procedures on the power switching units over current protection trip unit Contact the factory if any additional information is required PM062 REVO 04 11 19 2 Thomson Technology 870 TRANSFER SWITCH 3 3 TRANSFER SWITCHES WITH MULTI TAP VOLTAGE If the transfer switch has programmable multi tap voltage capabilitv i e ATS Model Code with Voltage Code Y confirm the transfer switch has been configured for the correct system voltage prior to installation WARNING
30. or death due to electrical shock To re energize the load the padlock s should be removed from the Service Disconnect control switch and move the switch to the Energized position transfer switch will immediatelv return to the utilitv or generator supplv if within normal operating limits 5 3 TEST MODES The transfer switch may be tested utilizing the TSC 80 controller push buttons or optional four position test switch A simulated utility power failure condition will be activated when the test mode is selected The transfer switch will operate as per a normal utility power fail condition The transfer switch will remain on generator supply until the test mode is terminated lt will then immediately transfer back to the utility supply and then continue to operate the generator set for its cooldown period then stop Note The transfer switch will automatically return to the utility supply if within nominal limits if the generator set fails while in the test mode 6 OVER CURRENT PROTECTION Thomson Technology TS 870 series of Automatic Transfer Switches may be supplied with or without integral over current protection as described below 6 1 STANDARD TS 870 AUTOMATIC TRANSFER SWITCH The standard TS 870 Automatic Transfer Switch does not contain any integral over current protection and requires upstream over current protection devices for both Utility and Generator sources The Standard TS 870 is rated for 10096 contin
31. or to use Refer to TSC 80 Instruction Manual TSC 80 Lexan Faceplate 005336 Contact Thomson Technology Service Dept for installation procedures TSC 80 Rear Cover 005707 Limit Switch 1 1 n c all 004929 Must install and adjust for proper ATS Models operation before use Contact Thomson Technology Service Dept for installation adjustment procedures Transfer Switch Motor 100A 001077 Motor is supplied with gear box 250A 1 PH 120v assembly Contact Thomson Technology Service Department for installation procedures Transfer Switch Motor 400A 001075 Motor is supplied with gear box 1200A 120V 1 10 hp 1 PH assembly Contact Thomson Technology Service Dept for installation procedures 120VAC Auxiliary Plug in 001278 Must ensure coil voltage is correct Relay 11 pin Square UX GX 120VAC Auxiliary Plug in Timer 001515 Must ensure coil voltage is correct 100VA Control Transformer 002159 For other parts not listed please contact Thomson Technology 19 PRODUCT RETURN POLICY Thomson Technology uses a Return Material Authorization RMA process Please complete the Return Authorization Request Form available on our web page for return of goods warranty replacement repair of defective parts or credit consideration and fax to the appropriate department Returns only Sales Fax 604 888 5606 Warranty replacement Warranty Repair Service Fax 604 888 3370 Upon receipt of your request Thomson Technology will
32. ources of supply before opening the enclosure for manual operation With all sources of power de energized to the transfer switch the control circuit isolation plug PL12 can be unplugged to prevent subsequent operation To operate manually pull manual release plunger releasing the motor drive rod from the motor drive arm and push the yoke in the desired direction Automatic operation may be regained by replacing the isolation plug With all sources of power de energized to the transfer switch the control circuit isolation plug PL12 can be re connected The drive system is self engaging and will operate the transfer switch to the required position See manual operation instruction on front of transfer switch mechanism 9 TRANSFER SWITCH MECHANISM 400A 1200 Amp The transfer mechanism consists primarily of the transfer motor a hub assembly two operating rods and two power switching device operating yokes The reversible transfer motor drives the hub assembly which in turn moves the operating rods that are connected to the power switching device operating yokes The power switching device toggles are set inside the yokes and are moved by them There are two limit switches which are contacted by the operating yokes one for each direction of travel which disconnect the transfer motor power supply when the power switching devices have attained full travel The adjuster screws located on the yokes determines the operating
33. point of these limit switches Should adjustment be required it is advisable to consult Thomson Technology for further information The transfer switch mechanism has three possible positions a Utility power switching device closed and generator power switching device open b Generator power switching device closed and utility power switching device open Both utility and generator power switching devices open but NEVER both utility and generator power switching devices closed at the same time PM062 REVO 04 11 19 15 Thomson Technology 870 TRANSFER SWITCH 9 1 MANUAL OPERATION See CAUTIONI on Page 2 Isolate the transfer switch from all sources of supplv before opening the enclosure for manual operation With all sources of power de energized to the transfer switch the control circuit isolation plug PL12 can be unplugged to prevent subsequent operation To operate manually pull the release plunger and operate the handle in the desired direction Automatic operation may be regained by replacing the isolation plug With all sources of power de energized to the transfer switch the control circuit isolation plug PL12 can be re connected The drive system is self engaging and will operate the transfer switch to the required position See manual operation instruction on front of transfer switch mechanism 10 RECOMMENDED MAINTENANCE See CAUTION on Page 2 10 1 DO NOT perform dielectric tests on the equipment w
34. r testing to provide primary neutral CT injection up to or greater than the trip setpoint as selected by the responsible party As indicated in the NEC the maximum setting of the ground fault protection shall be 1200 amps and the maximum time delay shall be 1 second for ground faults equal to or greater than 3000 amps The inspection authority should be contacted to confirm actual test requirements as these may vary by region or local code requirements The interconnected system shall be evaluated to ensure compliance with the appropriate schematic drawings The proper location of sensors and power cabling shall be determined The grounding points of the system shall be verified to determine that ground paths do not exist that would bypass the sensors The use of high voltage testers and resistance bridges may be required A simulated fault current is to be generated by a coil around the sensors The reaction of the circuit interrupting device is to be observed for correct response The results of the test are to be recorded on the test form provided PM062 REVO 04 11 19 21 Thomson Technology 870 TRANSFER SWITCH 17 TROUBLESHOOTING CAUTION trouble shooting service work performed must be done by qualified personnel only Failure to do so may cause personal injury or death Note An optional hand held plug in Service Display Module SDM is available for the TSC 80 Transfer Controller SDM module provides LCD
35. rect operation APPENDIX SVF035 DOC 04 11 18 REVO THOMSON TECHNOLOGY 18 19 20 21 TYPICAL AUTOMATIC TRANSFER SWITCH COMMISSIONING PROCEDURES Model Series TS 840 870 A toraatic Plant Exercise Operation OPTIONAL If an automatic weekly plant exercise feature is desired press the GENERATOR EXERCISE Mode push button on the TSC 80 faceplate Hold the push button on for approximately 5 seconds until the LED light changes state Once the mode is initiated the engine will immediately start and the generator will transfer on load as previously described Note The generator may or may not transfer on load which is dependent on the TSC 80 program setting The factory default setting is for a Load Transfer plant exercise test The engine will remain operating on load until the plant exercise time delay period of 20 minutes expires then the load will re transfer back to the utility supply following the 2 minute utility return timer engine will be automatically re tested on load every week i e 7 days at the same time of day that the first test was initiated Refer to TSC 80 manual for further information On completion of commissioning ensure all controls are left in automatic If required forward document or drawing updates to Thomson Technology if revisions are required and provide the end user with a set of marked ups to be retained on site Ensure copies of manuals for the equipment are on site Record an
36. s necessary apply medium weight SAE 20 oil sparingly 10 9 Transfer Mechanism 400A 1200A yoke pivot bearings and rod ends are permanentiv lubricated and do not require maintenance 10 10 The motor and gearbox are permanently lubricated and should not require attention under normal operating circumstances 11 FRONT VIEW TYPICAL 3 4 POLE 100A 250A TRANSFER MECHANISM Ne TTT THOMSON TECHNDI Z imeErrrrmt Vaa f f f m A f owo oo 062 REV 0 04 11 19 17 Thomson Technologv 870 TRANSFER SWITCH 12 FRONT VIEW TYPICAL 3 4 POLE STYLE 400 1200 TRANSFER MECHANISM 1 y i ik E da i e 13 a E PM062 REV 0 04 11 19 18 Thomson Technology 870 TRANSFER SWITCH 13 CONFIGURATION OPTIONS
37. switching opens well before the other should close e All fasteners are adequately tightened e The operating linkages are not damaged or bent and that all bearing points operate freely 7 2 To maintain electrical integrity ensure that e All electrical connections especially power connections are clean and adequately tightened Corroded or loose power connections will cause destructive heating and may cause premature tripping e All insulating devices are in place and in good condition e No moisture or other contamination is present e Electrical conductors are adequately secured away from moving parts 7 3 To maintain operational integrity ensure that e All control devices in good condition and correctly calibrated All control devices are adequately secured in their plug in fixtures Only qualified personnel should undertake Service work Failure to correctly maintain an automatic transfer switch may present a hazard to life and equipment Full operational testing must be done prior to placing a transfer switch in service subsequent to any maintenance or repair Any service work involving electrical components requires high potential testing to ensure that required insulation levels have been maintained 8 TRANSFER SWITCH MECHANISM 100A 250 Amp The transfer mechanism consists of the transfer motor and drive assembly which operates a common yoke which in turn operates both utility and generator power switching de
38. tact Thomson Technology for further information as may be required Note An optional hand held plug in Service Display Module SDM is available for the TSC 80 Transfer Controller The SDM module provides an LCD screen to display additional detailed information on the operation and settings of the TSC 80 controller for simplified servicing trouble shooting procedures For detailed information refer to the separate SDM module instruction manual PMO65 5 GENERAL THEORY OF OPERATION 5 1 STANDARD AUTOMATIC TRANSFER SWITCH 5 1 1 NORMAL OPERATION When utility supply voltage drops below a preset nominal value adjustable from 7096 to 10096 of nominal on any phase an engine start delay circuit will be initiated and the transfer to utility supply signal will be removed i e contact opening Following expiry of the engine start delay period adjustable from 0 to 60 sec an engine start signal contact closure will be given Once the engine starts the transfer switch controller will monitor the generator voltage and frequency levels Once the generator voltage and frequency rises above preset values adjustable from 7096 to 9596 of nominal the engine warmup timer will be initiated Once the warmup timer expires adjustable from 0 to 60 sec the Transfer to Generator Supply signal contact closure will be given to the transfer switch mechanism The load will then transfer from the utility supply to the generator supply via the mo
39. ted by pressing and holding the 2 push buttons on the TSC 80 faceplate simultaneously On until all the LED s change state Prior to operating the generator ensure it is ready to be energized and the site electrical contractor and or owner as required give authorization to proceed In preparation for operation turn the generator s engine control switch to the Automatic start position To transfer the generator on load perform a load test by pressing the Utility Power Fail Simulate pushbutton On and holding it for approximately 5 seconds until the LED light above the push button changes state The engine should start following the 3 second engine start delay period and the transfer switch will begin transferring to the generator supply once the 2 second engine warm up timer expires Note the engine warm up timer will only begin timing once the generator s output rises above 8596 nominal voltage and 9096 nominal frequency Once the Utility power switching device opens the transfer switch mechanism will pause in the neutral position for the 3 second neutral delay period then the mechanism will complete the transfer and close the generator power switching device To determine correct operation observe the following on the TSC 80 faceplate i Generator Source green LED is On ii Red LED above mimic bus for the generator source is On iii Load green LED is On iv Utilitv Source green LED is On Utilitv Power Simulate vellow LED is
40. tor driven mechanism The generator will continue to supply the load until the utility supply has returned The retransfer sequence is completed as follows when the utility supply voltage is restored to above the preset values adjustable from 70 to 95 of nominal on all phases a transfer return delay circuit will be initiated Following expiry of the Utility Return Timer adjustable from 0 to 30 min the Transfer to Generator Supply signal will be removed contact opening then the Transfer to Utility Supply signal contact closure will be given to the transfer switch mechanism The load will then retransfer the load from the generator supply back to the utility supply Note A neutral delay timer circuit will delay the transfer sequence in the neutral position i e both power PM062 REV 0 04 11 19 8 Thomson Technology 870 TRANSFER SWITCH switching devices open until the neutral time delav period expires adjustable from 0 to 60 sec An engine cooldown timer circuit will be initiated once the load is transferred from the generator supplv Following expirv of the cooldown delav period adjustable from 0 to 30 min the engine start signal will be removed contact opening to initiate stopping of the generator set 5 2 SERVICE ENTRANCE AUTOMATIC TRANSFER SWITCH Note This applies to service entrance transfer switches 5 2 1 NORMAL OPERATION Under normal conditions the load is energized from the utilitv supplv thro
41. ugh the closed utility transfer power switching device If the utility power fails the generator will start and the load will be re energized via the closed generator transfer power switching device In the normal operating mode the Service Disconnect switch shall be in the energized position 5 2 2 OVER CURRENT TRIP Should the utility power switching device trip open due to an over current condition TSC 80 transfer controller will initiate an engine start signal and will permit transfer of the load to the generator supply The utility source will be locked out and the load will remain on the generator supply until the TSC 80 alarm signal is manually reset Refer to the TSC 80 Instruction Manual for further details on Transfer Fail operation Should the generator power switching device trip open due to an over current condition TSC 80 transfer controller will initiate transfer of the load to the utility supply The generator source will be locked out and the load will remain on the utility supply until the TSC 80 alarm signal is manually reset 5 2 3 SERVICE DISCONNECT PROCEDURE To perform a service disconnect i e to disconnect the utility and generator supplies the following procedure is required 1 Move the Service Disconnect control switch located on the door of the transfer switch to the Disconnected position PM062 REVO 04 11 19 9 Thomson Technology 870 TRANSFER SWITCH 2 Verify that the Service Disco
42. uous loading and can withstand a maximum short circuit fault current as noted in Section 15 of this manual The standard TS 870 transfer switch model without integral over current protection is identified in the product model code Refer to Section 4 1 of this manual for further details on model coding 062 REV 0 04 11 19 12 Thomson Technology 870 TRANSFER SWITCH 6 2 OPTIONAL TS 870 AUTOMATIC TRANSFER SWITCH WITH INTEGRAL OVER CURRENT PROTECTION When integral over current protection is required it may be supplied on either Utility or Generator sources or both sources Service Entrance rated TS 870 transfer switches will have over current protection supplied on the Utility source as standard The type of over current protection utilized is dependent upon ATS amperage size and optional features specified For transfer switches rated 100A through 200A over current protection is non adjustable thermal magnetic type trip units For transfer switches rated 400A through 1200A over current protection is adjustable electronic type with long time amp instantaneous trip unit elements with optional ground fault protection elements Note Ground fault protection is supplied as standard on 1000A and 1200A transfer switches that are used on systems greater than 240V Upstream over current protection devices are required on the sources feeding the TS 870 Transfer Switch that do not have integral over current protection on that source Note For
43. vices Since the power switching devices are oriented opposite to each other the action of turning one power switching device off will result in turning the other power switching device on The geometry of the mechanism ensures that one power switching device always opens before the other closes thus maintaining the required mechanical interlocking The unidirectional motor operating through the motor drive arm and rod assembly which is normally held captive to the yoke via the manual release plunger assembly acts upon the yoke drive arm Both power switching device toggles are set inside the common yoke and are moved by it There are two limit switches that are contacted by the yoke at its extremes of travel disconnecting the motor circuit at the point of full power switching device toggle travel in the intended direction Should adjustment be required it is advisable to consult Thomson Technology for further information PM062 REVO 04 11 19 14 Thomson Technology 870 TRANSFER SWITCH The transfer switch mechanism has three possible positions a Utilitv power switching device closed and generator power switching device open b Generator power switching device closed and utilitv power switching device open c Both utilitv and generator power switching devices open but NEVER both utilitv and generator power switching devices closed at the same time 8 1 MANUAL OPERATION See CAUTION on Page 2 Isolate the transfer switch from all s