Data Sheet 85001-0527

image

Contents

1. Security Open w Tamper Short sends security alarm open sends tamper 41 Security Closed w Tamper open sends security alarm short sends tamper 42 Basic Security open or short sends security alarm 43 Security Tamper open or short sends tamper 44 Security Open short sends active open sends fault 45 Maintenance open or short sends maintenance 48 Active Non Latching short sends active open sends trouble 3 Security Closed open sends active short sends fault 46 The Dual Input Security Module shall be a Edwards model SIGA SEC2 85001 0527 Issue 3 1 Typical Wiring From Signature Loop Controller or previous device Data In Data In Data Out Data Out To next Signature device Signature loop Signature Series Overview The Signature Series intelligent analog addressable system from Edwards is an entire family of multi sensor detectors and mount ing bases multiple function input and output modules network and non network control panels and user friendly maintenance and service tools Analog information from equipment connected to Signature devices is gathered and converted into digital signals An onboard microprocessor in each Signature device measures and analyzes the signal and decides whether or not to input an alarm The microprocessor in each Signature device provides four additional benefits Self diagnos tics Automatic Device Mapping and Fast
2. Stable Communication Self diagnostics and History Log Each Signature Series device constantly runs self checks to provide important mainte nance information The results of the self check are automatically updated and permanently stored in its non volatile memory This information is accessible for review any time at the control panel PC or using the SIGA PRO Signature Program Service Tool The information stored in device memory includes e Device serial number address and type e Date of manufacture and hours of operation e Most recent trouble code logged by the device 32 possible trouble codes may be used to diagnose faults Automatic Device Mapping The Signature Data Control ler SDC learns where each device s serial number address is installed relative to other devices on the circuit The SDC keeps a map of all Signature Series devices connected to it The Signa ture Series Data Entry Program also uses the mapping feature With interactive menus and graphic support the wired circuits be tween each device can be examined Layout or as built drawing information showing branch wiring T taps device types and their address are stored on disk for printing hard copy This takes the mystery out of the installation The preparation of as built drawings is fast and efficient Page 3 of 4 Tamper Circuit 1 Aarm input EOL EOL EOL Basic Security Alarm Tamper N C with tamper N O with ta
3. EST Life Safety amp Communications Dual Input security Module SIGA SEC2 Overview The SIGA SEC2 is an intelligent analog addressable device used to connect one or two normally open or normally closed dry con tact security circuits The actual function of this module is determined by the person ality code selected by the installer This code is downloaded to the module from the Signature loop controller during system configuration The input module gathers information from the devices connected to them and converts it into digital signals The module s on board microprocessor analyzes the signal and decides whether or not to input an alarm tamper or maintenance condition The intelligence built into every SIGA SEC2 means that the mod ule can decide when to report information and when to suppress sending information to the host system As an example when the SIGA SEC2 module is disarmed changes of state that would normally create an alarm are recognized by the module and sent to the host as a background task This enhances reponse time by removing the burden of normal room activity on the network Should a trouble or tamper condition be detected these events are immediately transmitted to the host helping to ensure system integrity is maintained Once the module is armed alarms are sent immediately to the host The module is housed in a small attractive thermo plastic enclo sure designed for surface mounting Wi
4. XX UUKL and SYZV UL 294 category ALVY UL 609 category AOTX UL 636 category ANET UL 1076 category APOU UL 365 category APAW UL 1610 category AMCX UL 1635 category AMCX ULC S527 ULC S301 ULC S302 ULC S303 ULC S306 ULC ORD C1076 ULC ORD C693 Please refer to ESTS Installation and Service Manual for complete system requirements Ordering Information Catalog Number Description Shipping Wt Ib kg SIGA SEC2 Dual Input Security Module 0 4 0 15 Page 4 of 4 ET 85001 0527 Issue 3 1 L Z 90
5. e devices may be turned off temporarily from the control panel Quality and Reliability Edwards Signature devices are manu factured in North America to strict international ISO 9001 stand ards All electronics utilize surface mount technology SMT for smaller size and greater immunity to RF noise A conformal coat ing is used for humidity and corrosion resistance 1 Retrievable with SIGA PRO programming tool 85001 0527 Issue 3 1 EDWARDS Contact us Email edwards fire fs utc com Web www est fire com EST is an EX WARDS brand 1016 Corporate Park Drive Mebane NC 27302 In Canada contact Chubb Edwards Email inquiries chubbedwards com Web www chubbedwards com 2013 UTC Fire amp Security Americas Corporation Inc All rights reserved Specifications subject to change without notice Edwards is part of UTC Climate Controls amp Security a unit of United Technologies Corporation Specifications Agency Listings UL ULC See Note Dimensions 1 7 8 x 3 x 1 HWD 4 52cm x 7 62cm x 2 54cm Wire Size 16 AWG 1 0mm to 22 AWG 0 25mmz Mounting Surface mount directly on wall or in a 4 square electrical box Finish White Cycoloy Operating 30 F to 120 F 0 C to 49 C Environment O to 93 Humidity non condensing Current Draw Standby 720 uA Tamper Active 850 pA Note The EST3 is modularly listed under the following standards UL 864 categories UOJZ UO
6. he circuit is shorted Outputs are non latching BASIC SECURITY Personality code 43 Assign to one or both circuits Configures circuit 1 or 2 or both to transmit an alarm condition when the input circuit is opened or shorted Outputs are non latching TAMPER Security Personality code 44 Assign to one or both circuits Configures circuit 1 or 2 or both to transmit a tamper condition when the input circuit is opened or shorted For use in conjunction with another circuit used to detect security alarm condition Outputs are non latching MAINTENANCE Security Personality code 48 Assign to one or both circuits Configures circuit 1 or 2 or both to trans mit a maintenance condition when the input circuit is opened or shorted For use with device such as a motion detector providing a separate maintenance contact indicating the device is opera tional but requires service Outputs are non latching NORMALLY OPEN w TROUBLE Personality code 3 Active Non Latching Assign to both circuits Configure both circuits to transmit an active condition when the input circuit is shorted and transmit a trouble condition when the circuit is opened SECURITY OPEN w FAULT Personality code 45 Assign to one or both circuits Configures circuit 1 or 2 or both to transmit a security alarm condition when the input circuit is shorted and transmit a fault condition when the circuit is opened Outputs are non latching SECURITY CLOSED w FAULT Per
7. mper Circuit 2 EOL EOL EOL input Tamper Security open with fault Secuity closed with fault Device mapping allows the Signature Data Controller to discover e Unexpected additional device addresses e Missing device addresses e Changes to the wiring in the circuit Most Signature modules use a personality code selected by the installer to determine their actual function Personality codes are downloaded from the System Definition Utility SDU during system configuration and are indicated during device mapping Fast Stable Communication Built in intelligence means less information needs to be sent between the device and the Signa ture Data Controller SDC Other than regular supervisory polling response Signature devices only need to communicate with the SDC when they have something new to report This provides very fast control panel response and allows a lower baud rate speed to be used for communication on the circuit The lower baud rate offers several advantages including e Less sensitivity to circuit wire characteristics e Less sensitivity to noise glitches on the cable e Less emitted noise from the data wiring e Twisted or shielded wiring is not required Testing amp Maintenance Automatic self diagnosis identifies when a Signature device is defective and causes a trouble mes sage The user friendly maintenance program shows the current state of each device and other pertinent information Singl
8. ring terminals are provided for up to 16 AWG 1 00 mm to 22 AWG 0 25 mm wires Page 1 of 4 Intelligent Initiating PJ 7300 1657 0209 Standard Features e Two input circuits Suitable for doors windows and other locally powered security devices such as motion detectors etc e Small aesthetic enclosure e Multiple applications e Automatic device mapping e Electronic addressing e Intelligent device with microprocessor e Non volatile memory e Diagnostic LEDs for service e Designed in accordance with ISO 9001 Quality System 85001 0527 Issue 3 1 Application The duty performed by the SIGA SEC2 is determined by its personality code SIGA SEC2 provides two security circuits each circuit can be assigned a personality code The SIGA SEC2 is ideal for connection to door contacts motion detectors glass break detectors or any sensor offering dry contact alarm trouble or tamper contacts NORMALLY OPEN w TAMPER Personality code 41 Secu rity Assign to one or both circuits Configures circuit 1 or 2 or both to transmit a security alarm condition when the input circuit is shorted and transmit a tamper condition when the circuit is opened Outputs are non latching NORMALLY CLOSED w TAMPER Personality code 42 Security Assign to one or both circuits Configures circuit 1 or 2 or both to transmit a security alarm condition when the input circuit is opened and transmit a tamper condition when t
9. sonality code 46 Security Closed Assign to one or both circuits Configures circuit 1 or 2 or both to transmit an alarm condition when the input circuit is opened and transmit a fault condition when the circuit is shorted Outputs are non latching Page 2 of 4 Installation The SIGA SEC2 should be mounted in the protected space and in close proximity to the device it is monitoring Electronic Addressing The loop controller electronically ad dresses each module saving valuable time during system com missioning Setting complicated switches or dials is not required Each module has its own unique serial number stored in its on board memory The loop controller identifies each device on the loop and assigns a soft address to each serial number used by the systems Compatibility The SIGA SEC2 is compatible with the EST3 Signature loop con trollers and requires two Signature addresses Engineering Specifications Provide intelligent dual input security modules at the locations shown on the drawings The Dual Input Security Module shall provide two 2 input circuits each capable of a minimum of 6 per sonalities each with a distinct operation The module shall have an aesthetically pleasing enclosure for unobtrusive mounting in visible areas and shall be capable of being directly surface mounted without the need for an electrical box The dual input security module shall support the following circuit configurations