1. i f 8 C The Series A3000 PHOTOHELIC Switch Gage is a versatile 2 in 1 instrument combining a time proven Magnehelic differen tial pressure gage with low high pressure switches It is designed to measure and control positive negative or differential pressure of air or other non combustible non corrosive gases Gage reading is unaffected by switch operation Switch set points are easily adjusted with knobs located on gage face Applied pressure and switch set points are fully visible at all times Deadband is one pointer width less than 1 of full scale Each set point controls a DPDT relay and both relays can be interlocked to provide variable deadband control SPECIFICATIONS GAGE SPECIFICATIONS Service Air and non combustible compatible gases Wetted Materials Consult factory Accuracy 2 of full scale at 70 F 21 1 C 3 on 0 and 4 on 00 models Pressure Limits 20 Hg to 25 psig 0 677 to 1 72 bar MP option 35 psig 2 41 bar HP option 80 psig 5 52 bar 836003S 36010S 150 psig 10 34 bar 836020S and higher 1 2 x full scale pressure Temperature Limits 20 to 120 F 6 67 to 48 9 C Low temperature option available Process Connections 1 8 female NPT Size 4 101 6 mm dial face 5 127 mm O D x 8 1 4 209 55 mm Weight 4 Ib 1 81 kg SWITCH SPECIFICATIONS Switch Type Each setpoint has 2 Form C relays DPDT Repeatability 1 of full scale Electrical Rating
2. 7 Dual Set Point Automatic and Manual Reset Combinations Circuit Style HH may be used with either set point wired and operating as in paragraph 5 above and the other set point wired and operating as in paragraph 6 8 High Low Limit Control Dual Set Point Circuit Style HH may be used to control fans dampers pumps etc between the set points of a PHOTOHELIC Switch Gage To accomplish this use one set point relay to reset the other as shown in the wiring diagram Fig L In this typical application the load for instance a fan would be connected to the N C contacts for the right set point relay Section A Fig H On pressure rise to the right set point its relay would pull in and hold even though pressure might then fall below that set point the pressure continued to fall to the left set point its relay would automatically be DE ENERGIZED return to its normal position and in so doing open the holding coil circuit from Section B Fig H The right set point relay would thus be reset and the cycle could repeat 9 Dual Set Point Special Purpose Circuits Circuit Style LL may be used where manual reset following maintained contact on pressure decrease to either set point is required Circuit Styles HL and LH are combination units For special combinations of fea tures special units and detailed instructions regarding their use consult the factory 10 Single Set Point PHOTOHELIC The single set point PHO TOHELIC
3. Switch Gage is furnished with the right set point only Terminals in Sections A and B Fig H are connected to this relay Circuit Style SRH is wired for automatic reset as in paragraph 5 above Manual reset is accomplished by adding a normally closed reset switch or push button to the circuit as described in para graph 6 above Copyright 2009 Dwyer Instruments Inc DWYER INSTRUMENTS INC P O BOX 373 MICHIGAN CITY INDIANA 46361 U S A Printed in U S A 7 09 Phone 219 879 8000 Fax 219 872 9057 Bulletin B 33 A 11 Single Set Point Special Manual reset after actuation on falling pressure can be obtained by using Circuit Style SRL Consult the factory for special units and detailed instructions regarding their use 12 Placing in Service In normal operation each relay is de ener gized when the pressure applied to the instrument is below its set point Special low latching units will ordinarily have to be reset before placing on the line in normal operati n AA SET JUMPERS YA 8 Nc NC ae gt 8 eg JAE ot ak B a Note For larger motors use the Photohelic Switch Gage in a maintained contact 120 Volt Control or Push Button Circuit of the motor Fig L 13 Failure Mode The PHOTOHELIC Switch Gage circuit design provides certain protection in the event of a loss of pressure or electr
4. 10A 28 VDC 10A 120 240 VAC Electrical Connections Screw terminals Use 167 F 75 C copper conductors only Power Requirements 120 VAC 50 60 Hz 240 VAC amp 24 VAC Power optional Mounting Orientation Diaphragm in vertical position Consult factory for other position orientations Set Point Adjustment Adjustable knobs on face Agency Approvals UL File No E88121 Vol 1 Sec 4 CSA File No LR22541 34 CE EN 61000 6 2 1999 EN 6100 3 2 2000 EN 61000 3 3 2000 DWYER INSTRUMENTS INC P O BOX 373 MICHIGAN CITY INDIANA 46361 U S A Series A3000 Photohelic Differential Pressure Switch Gage Specifications Installation and Operating Instructions Phone 219 879 8000 Fax 219 872 9057 Bulletin B 33 A 2 1 2 63 50 _ 4 6 32 HOLES E NEA 2 1 16 52 39 EQUALLY SPACED ON 2 50 80 A 5 1 8 130 18 B C 1 8 FEMALE NPT LOW 1 1 4 PRESSURE CONNECTION 31 75 i am i fons 4 47 64 i 3 7 8 SQ 120 281 los d i 98 43 5 127 00 Ley i a 1 3 4 CONDUIT Pan CONNECTION 3 7 8 98 43 J 5 8 15 88 5 1 8 130 18 k 5 1 2 139 70 6 3 8 161 931 S PSBB PANEL O D 4 3 8 111 13 H 7 5 8 193 68 l 376 4 76 MOUNTING HOUSING REMOVAL RING Fig A NOTE Detailed dimension drawings are available from our Customer Service Dept for PHOTOHELIC switch gages as
5. Electrical access to the connection box portion of the relay housing is by bottom opening for 3 4 conduit Use of flexible conduit is recommended It should be supported from the panel or other suitable surface to prevent the wiring system from exerting undue strain on the instrument See Fig G COVER MOUNTING SCREWS 4 3 8 111 13 I CLEARANCE UJ ive FLEXIBLE CONDUIT FOR COVER REMOVAL SUPPORT CONDUIT FROM PANEL Fig G 3 Terminal or Connection Board Layout In Fig H Terminal Board Section A contains the connections for the load or slave relay actuated by the high or right set point This relay is a double pole double throw type The two right connections are normally closed the two middle connections are normally open and the left connections are the common pair The relay is in its normal or De Energized position when pressure is below the right hand set point Section D is exactly the same as Section A except that its load or slave relay is controlled by the low or left set point The De Energized position is below the left hand pointer set point Section B contains the external connections to the holding coil circuit for the high or right set point relay and Section C contains similar connections for the low or left set point relay The function and use of these connections varies somewhat depending on the circuit style of the instrument See paragraphs 5 and 6 fo
6. installed in two optional enclosures For weatherproof housing request no 13 700132 00 For explosion proof housing request no 13 700113 01 INSTALLATION 1 Location Select a clean dry vibration free location where ambient temperatures will be between 20 and 120 F 6 67 and 48 9 C Tubing supplying pressure to the instrument can be prac tically any length but long runs will increase response time slightly 2 Position The PHOTOHELIC Switch Gage is factory calibrated for use with scale in a vertical plane Operation at other angles may affect accuracy and or require zero adjustment Most models can be specially calibrated at the factory for other positions if specified at time of ordering Ranges below 1 W C must be used only with scale vertical 3 Mounting The PHOTOHELIC Switch Gageis normally mount ed before making electrical connections The electrical enclosure is removable at any time regardless of mounting method A Panel Mounting Normal mounting is flush or through panel as shown in Fig B Allow 4 s 111 13 mm clearance behind the unit for removal of electrical enclosure Make a 4 13 16 122 24 mm diameter hole in panel Insert the PHOTOHELIC Switch Gage unit from front of panel and slip mounting ring over case from behind with stepped side facing rear Fit the snap ring into narrow groove at back edge of the bezel Thread four 6 32 x 1 1 4 mounting screws into tapped holes in mounting ring an
7. ctly on the zero mark using the zero adjust screw located at the bottom of the front cover Note that this adjustment can only be made with the high and low pressure taps both open to atmos phere Connect the high and low pressure taps to positive negative or differential pressure sensing points Use 1 4 diameter metal or other instrument tubing and 1 8 NPT adapters at the PHOTO HELIC pressure switch gage Adapters for rubber or soft plastic tubing are furnished with the instrument for use where this type of connection is preferred If the PHOTOHELIC Switch Gage is not used to sense differential pressure one of the pressure taps must be left open to atmos phere This will allow the reference pressure to enter In this case installation of a Dwyer Instruments Inc No A 331 Filter Vent Plug or similar fitting in the reference pressure tap is recommended to reduce the possibility of dust entering the instrument NOTE If the PHOTOHELIC switch gage is over pressured point er may jump from full scale back to zero and remain there until the excess pressure condition is relieved Users should be aware of possible false zero pressure indications under this condition ELECTRICAL CONNECTIONS 1 Cover The amplifier relay unit has an easy to remove housing Remove the three 8 screws as shown in Fig G and slide the housing off Make all the electrical connections before reinstalling and refastening the housing 2 Conduit
8. d seat it against snap ring Tighten screws against back of panel See Fig B 000 4 13 16 122 24 HOLE REQUIRED FOR PANEL MOUNTING SNAP RING GROOVE 1 2 NPT M PRESSURE CONNECTION SINGLE HIGH PRESSURE CONNECTION FOR SERIES 36000S MODELS Fig B www dwyer inst com e mail info dwyer inst com B Surface Mounting with Remote Relays Where it is pre ferred to mount the amplifier relay unit separate from the gage assembly the gage is mounted as shown in Fig B without ampli fier relay package or surface mounted as shown in Fig C Use the dimensions in Fig D to locate holes Fig C 3 3 16 4 76 MOUNTING HOLES EQUALLY SPACED ON A a 104 78 B C a B 3 4 19 05 WIRE CONNECTION HOLE a z gt j 1 1 8 28 58 Fig D C Remote Relays Mounting On factory supplied RMR remote mounted relay units the amplifier relay package will be furnished attached to a mounting plate as shown in Fig E Use the hole lay out in Fig F for this option A five foot cable assembly is included for connecting the two components Longer cable lengths are available from the factory 3 16 a 4 PLACES Z OO Ca 4 9 32 108 74 1 4 9 32 108 74 s 5 127 00 SQ Fig F 4 Pneumatic Connections amp Zeroing After installation but before making pressure connections set the indicating pointer exa
9. ical power In either case both relays will de energize return ing to their normal zero pressure state The exceptions to this are models with center zero ranges Because the relays on all standard models are always energized when the indicating black pointer is to the right of their respective set points the relay action on loss of pressure will depend on set point position since either of them could be located to the left of zero As an example if the left point er were set at 2 in w c and negative pressure was 3 in w c a loss of that pressure would allow the black pointer to return to the center and thus cause the low set point relay to energize If the LED should burn out only the left low relay will de energize The right high relay will react as if pressure were above its set point and will remain energized even though pressure might be below that setting In this situation only termination of electrical power will allow the right high relay to de energize MAINTENANCE AND SERVICE Dwyer Instruments Inc PHOTOHELIC Switch Gages are preci sion instruments expertly assembled and calibrated at the factory They require no lubrication or periodic servicing If the interior is protected from dust dirt corrosive gases and fluids years of trou ble free service may be expected Zero adjustment should be checked and reset occasionally to maintain accuracy The PHO TOHELIC Switch Gage is not field serviceable and sh
10. it Style HH may also be used for manual reset applications where it is required to maintain contact on either relay following pressure increase above its set point Load or signal connections are made to the appropriate ter minals in Sections A and D as in paragraph 5 above Connect ter minals in Sections B and C through normally closed switches or push buttons as shown in Fig K Use of dry circuit type switch es such as a Dwyer Part No A 601 with paladium gold etc or rotary wiping action type contacts is recommended Make external ground connections as required and connect power to Section E for the control unit Circuit style LL is used for manual reset applications which require that contact be maintained following pressure decrease below the set point Load connections are made to the appropriate terminals in Sections A and D A normally open type manual reset switch such as Dwyer Instruments Inc Part No A 601 is connected to the terminals in Sections B and C The circuit must be armed by momentarily closing the switch while the black pointer is to the right of the set point From that point on the circuit will latch on pressure decrease below the set point and remain latched on pressure increase until manually reset with the optional switch RESET RESET CAUTION Do not apply electrical current to ter minals in Sections B and C Manual Reset with Circuit HH Fig K
11. ould be returned if repair is needed field repair should not be attempted and may void warranty Be sure to include a brief description of the problem plus any relevant application notes Contact customer service to receive a return goods authorization RGA number before shipping FR 13 440202 04 Rev 5 www dwyer inst com e mail info dwyer inst com
12. r details SECTION B SECTION C SECTION A SECTION D Q NO NC NC c e NO NC NC NO C QO OOOO sectone p a 3 y aiaa i CAUTION Do not apply electrical current to terminals in Sections B and C Fig H Section E contains the power connections for the control unit transformer primary The transformer in turn supplies reduced voltage power for the LED phototransistor amplifier unit and load relay pull in and hold coils Connections must always be made to this section in order to put the unit in operation Standard units are designed for 120 VAC input to the transformer Special units are also available for other voltages Separate Ground Wire attachment is provided for by a No 6 32 screw on the mounting bracket near the conduit opening An addi tional ground wire connection is located on the side of the gage body for use when the amplifier relay unit is mounted remotely Single Set Point instruments are furnished with the right or high set point components and circuitry in place These are connected to Sections A and B of the terminal board The left or low set point components are omitted 4 Circuit Style The PHOTOHELIC SWITCH GAGE is available with several factory installed optional internal circuits They are identified as to style by a label shown in Fig J This label is mount ed prominently on the terminal board of each instrument The letter H deno
13. tes a circuit in which the relay can be made to latch or remain energized after pressure increase to its set point The letter L denotes a circuit in which the relay can be made to latch or remain de energized after pressure decrease to its set point Two letters are required to fully identify a dual set point unit Thus circuit style HH which is standard is a dual set point circuit which has provisions for latching on pressure increase to either set point Single relay unit or L for the special low latch unit Units for use with other than standard 120 VAC will be so indicated on the label PHOTOHELIC CIRCUIT TYPE 2 ENCL POWER SUPPLY VAC 50 60 HZ 6 WATTS CONTACT RATING 10A 28 VDC 120 240 VAC Oey amp 1 3 HP 120 240 VAC IND CONT EQ Fig J 5 Dual Set Point Automatic Reset Circuit Style HH is used for simple on off switching applications To place in service connect load circuits to the appropriate terminals in Section A Fig H for the right set point and Section D for the left set point Note that the N O contacts are open when the gage pressure pointer is to the left of the set point pointers No connections are necessary in Sections B and C Make external ground connections as required and connect power to Section E for the control unit To use circuit style LL for automatic reset a jumper wire must be installed between the two terminals in Sections B and or C 6 Dual Set Point Manual Reset Circu

Download Pdf Manuals

image

Related Search

Related Contents

LIGHTED MIRROR KITS - Harley  Manual de Instruções Central de Comando (Espanhol)  User Manual for Installation & Use of Mobile DVR (SD  ML 150 - MAXILIFT and COBRA Truck Cranes. North Eastern  THS-G  日本語 - GEセンシング&インスペクション・テクノロジーズ  User Manual - lvi cameras  XPS-MC16 XPS-MC32 Configuratore di sicurezza Controlador de  FreePDF XP File 1  User manual Oven  