Home

SP2 Service Manual:SP2 Service Manual.qxd.qxd

image

Contents

1. Ensure the spring action cuts off the Oxygen flow when the button is released Check that the whistle does not sound when the Oxygen flush is operated If this occurs check that the Oxygen Cylinder Valve is fully open If the problem is not rectified instruct the service engineer to check a filters and Non return valves for restriction b the pressure of the primary Oxygen regulator Connect the oxygen pipeline and close the cylinder valve and repeat tests 3 6 Auxiliary Outputs Test Check outputs for security and correct function With a suitable flowmeter measure the output from each outlet to ensure that greater than 100 litres min can flow to free air Ensure that the oxygen failure alarm does not function during this test Repeat the test for both pipeline and cylinder supplies 7 FAULT FINDING 7 1 Introduction Provided the Anaesthetic Machine is regularly serviced and correctly used it is unlikely that seri ous component faults will occur After several years usage some items may require replacement and regular performance checks see section 8 To trace possible faults refer to the Fault Diagnosis Table which will indicate the required action In many cases apparent machine faults may be attributable to causes other than machine mal functions these causes are also listed 39 FAULT FINDING 7 2 Fault Diagnosis Table Component Cylinder pressure reducing valves
2. Wire 18 AWG PVC Equip green yellow CSA Circuit Breaker 110 v 10 amp Wire black 16 30 18 AWG PVC Equip wire white 16 30 18 AWG PVC Equip Fuse 5 A Ceramic HR INT Star Washer M5 M5 Plain Washer ST ST Nut M5 Earth Label M4 Int S Proof Washer Mains Wiring Colour Label Mains Lead Wiring Ref O2 Monitor Mains Lead 92 Quantity a gt MM a a CO gt 7A N Ch N PARTS LIST REF LIVE BLACK REF EARTH REF NEUTRAL WHITE REF NEUTRAL WHITE REF LIVE BLACK REF EARTH 300mm 93 PARTS LIST Frame Assembly Item Part No 5000254 5001281 5001280 5000230 5000231 5000232 5000221 5000255 5000226 5000233 800185 019155 025208 019167 800291 019142 5000288 019163 019001 85366 01011 01043 800233 019135 019130 800451 019166 019171 019010 5000284 5000258 5000257 5000340 5000365 025002 034069 01008 5000438 019049 Description Base Casting Castor Castor with brake Main Leg M C Front Leg LH Front Leg RH Work Surface Assembly Main Box Assembly Top Shelf Side Panel Mounting Strip M6 X 30 SKT C SK SS 16 Spring Washer M8 X 20 ST ST Button HD Cylinder Support M4 X 10 LG CSK HD ST STL Back Panel M8 X 30 LG Cap Screw M8 X 25 LG Cap Screw Bump Stop M4 Plain Washer M4 x 20 Cap Head SS Gas Carrier 102 SS M6 X 12 LG Cap Screw M6 X 12 Button HD SS Main Box Clamp Plate M6 X 16 SKT Button HD SS M4
3. CAUTION When the auxiliary gas outlets are in use on a machine with cylinder supply only or if the pipeline supply is not in use check flow rate requirements and ensure that adequate back up cylinders are available Oxygen and Air Auxiliary outlets 1 are mounted on the rear of the machine Supply pressure See section 4 5 3 11 A200SP Absorber The A200SP Absorber and ventilator bellows assembly is mounted on a polemount bracket attached to the machine frame upright Refer to the user instruction manual for A200SP for detailed information on installation and operation 3 12 A AV S Ventilator Interface to Prima SP2 3 An interface cable links the rear of the ventilator control unit to the gas delivery switch on the anaesthetic machine Ventilator ON OFF function a Turn the machine Gas Delivery Switch C ON The ventilator will power up b While the Prima SP2 power is ON the Ventilator can be turned OFF and ON using the ventilator On Off switch refer to ventilator user manual c Turn the Gas Delivery Switch to OFF The ventilator will power down Refer to the user instruction manual for AV S for detailed information on installation and operation 13 e e eo o o jf ER oo 66 60 60 4 SPECIFICATION 4 1 Physical Dimensions Overall frame size Work surface Height Size Loading Writing tablet Top shelf Loading
4. ni Penlon Prima SP2 Anaesthetic Machine Range Service Manual Partnership for Life IMPORTANT Servicing and Repairs In order to ensure the full operational life of this anaesthetic machine servicing by a Penlon trained engineer should be undertaken periodically The machine must be serviced to the schedule and methods detailed in sections 8 and 9 For any enquiry regarding the servicing or repair of this machine contact the nearest accredited Penlon agent or communicate directly with Technical Support Penlon Limited Abingdon Science Park Abingdon OX14 3PH UK Tel 44 0 1235 547076 Fax 44 0 1235 547062 E mail technicalsupport penlon co uk Always give as much of the following information as possible Type of equipment Product name Serial number Approximate date of purchase Apparent fault oa cd im FOREWORD This manual has been produced to provide authorised personnel with information on the function routine performance maintenance and repair applicable to the Prima SP anaesthetic machine range Information contained in this manual is correct at the date of publication The policy of Penlon Limited is one of continued improvement to its products Because of this policy Penlon Limited reserves the right to make any changes which may affect instructions in this manual without giving prior notice Personnel must make themselves familiar with the contents of this manual
5. 4 Reverse the removal procedure 59 SERVICING PROCEDURES 9 7 Mechanical AHD System 9 7 1 Check and Adjust Basal Flow Cascade flowmeter models Oxygen basal flow 50 75 ml min Single flowmeter models Oxygen basal flow 100 200 ml min NOTE The machine must be on a flat surface 1 Check that all flowmeter controls are OFF 2 Switch the gas delivery switch 1 to ON 3 Check that a basal flow of oxygen is indicated as D shown above ol If the basal flow is outside the range given a J eo uw C above a adjust the output of the secondary Oxygen 1 regulator see section 9 7 2 to achieve the J pU correct basal flow b check the oxygen concentration see section 9 7 2 4 Switch the Gas Delivery switch to OFF 5 If the correct basal flow can not be achieved reset the gear linkage see section 9 7 3 60 SERVICING PROCEDURES 9 7 2 Check Oxygen Concentration NOTE The machine must be on a flat surface 1 10 11 If the machine is not fitted with an Oxygen monitor connect a stand alone analyser to the CGO outlet Set the Gas Delivery switch 1 to ON Turn the Nitrous Oxide flowmeter control to maximum Refer to the table below and check Oxygen concentration at the oxygen flows specified Adjust the Oxygen Flowmeter control only Do NOT adjust the N20 flowmeter Note that flow rates for N2O are given as a guide only O2 Flow 9602 in O2 N
6. Common Gas Outlet CGO Electrical Power Supply Auxiliary Gas Outlets A200SP Absorber AV S Ventilator MRI Compatibility SPECIFICATION Physical Dimensions Gas Supplies Flowmeters Gas Pressures Auxiliary Gas Outlets Oxygen Failure Warning Devices Oxygen Flush Mechanical AHD System Environmental including MRI compatibility Electrical Supply PRE USE CHECKS Pre use Check List Pre use Checks Gas Supply Gas Pipeline Supplies Gas Cylinder Supplies Flowmeters Vaporizers Electrical Supply Patient Breathing System iii Page No nm O CO ON GM O1 CI e 4 LE L 1X aa X Po NM NY O 14 19 15 16 16 17 17 17 17 18 19 19 21 21 21 22 23 24 25 CONTENTS 5 6 Leak Rate Check Low pressure gas system 5 7 Oxygen Flush 5 8 Anaesthetic Gas Scavenge System AGSS 5 9 Ventilator 5 10 Alarm System Testing 6 FUNCTION TEST 6 1 Introduction 6 2 Machine Frame 6 3 Electrical Supply 6 4 Pipeline Supply and Non return Valve 6 5 Cylinder Supply and Pressure Reducing Valves 6 6 Flowmeter Unit 6 7 Gas Safety Devices 6 8 Vaporizers and backbar Manifold 6 9 Reduced Pressure Gas Circuit Leakage Test 6 10 Oxygen Flush Control 6 11 A Auxiliary Outputs 7 FAULT FINDING 8 SERVICE SCHEDULE 9 SERVICE PROCEDURES 9 1 Servicing Information 9 2 Ancillary Equipment including A200SP Absorber 9 3 Cleaning and Sterilisation 9 4 Internal Gas System 9 5 Front Cover Removal 9 6 Flo
7. For A200SP refer also to the user documentation supplied with the absorber 5 5 6 Pre use Test for Complete System Connect the CGO outlet on the machine to the fresh gas inlet of the A200SP absorber NOTE This machine must be fitted with a breathing system complying with approved design parameters at the selection of the qualified practitioner The breathing system components do not constitute part of the machine but connections between the machine and breathing system should be verified as follows 1 Fit a patient circuit to the inspiratory connector 1 and expiratory connector 2 on the absorber and a breathing bag to the bag arm connector 3 2 Set the bag ventilator switch 4 on the absorber to Bag 3 Close the adjustable pressure limiting APL valve 5 and occlude the patient connection port on the patient circuit Press the oxygen flush valve button on the front of the machine briefly Check that the reservoir bag inflates and the manometer 6 indicates approximately 40 cmH20O 2f Release the oxygen flush valve Check that the pressure is maintained in the system with less than 200 ml min fresh gas delivered into the breathing system showing that no leaks are present If this test fails check the low pressure system on the machine section 5 6 If the machine low pressure test is successful check the ventilator and absorber referring to the relevant user instruction manual P
8. N LLI zZ LLI LLI 0 89 PARTS LIST Flowmeter Assembly continued Item 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 52 53 54 55 56 Part No 019067 462544 A R 01027 019083 019025 01023 054514 054519 054518 462543 A R 15278 5000507 462543 A R 800506 800224 800653 054543 054517 462542 A R 800389 5000447 Description M4 X 12 SKT HD Cap 8 Mm Tube M4x6 Grubscrew Cup P t SS M4 X 4 LG Grub Screw M4 X 8 LG Grub Screw M4 Nut Elbow 6 mm Tube Coupling Tube Conn 6 mm Tube Label Air Product Label PNA 6 mm Tube Flow Tube Low Air Flow Tube Air Needle Valve Air Elbow 5 mm Tube Tube Conn 5 mm Tube Manifold Block Panel Flowmeter US 90 Quantity N MB NON Cc gt AA n gt ND PARTS LIST I a PZZ ZEN ao lama Red Bas a yji C JG SECTION A A 91 PARTS LIST Electrical Panel Assembly Item oOo N OO oO RH W MN N o O N O Oo A CQ N gt O NO Part No 800280 103994 103241 103237 103299 103223 104033 01023 103484 102973 103460 103461 103995 01222 01057 020001 104012 01035 15477 See 800218 800603 Description Electrical Panel CSA 102 INT PWR Fuse Holder 1 4 Spade Red Crimp Shrouded Crimp Connector 3 16 Mains Socket CSA Eyelet Connector M5 Red Fuse 2 A Ceramic Nut M4
9. Remove the screws at the rear of the machine to allow removal of the manifold block Overhaul and Refit 5 Dismantle the block as illustrated 6 Renew all O seals 7 To refit reverse the dismantling procedure Function test the machine see section 6 68 SERVICING PROCEDURES 9 12 Flowmeter Tubes Removal CAUTION Ensure that any residual gas in the machine is exhausted before commencing the dis mantling procedure Removal 1 Remove all cylinders and disconnect all pipeline supplies 2 Remove the flowmeter cover see section 9 7 9 Hold the tube as illustrated and press upwards X against the resistance of the spring 4 Carefully detach the lower end of the tube from the bobbin 5 Remove the tube ensuring that the top bobbin remains in place Y Overhaul Bobbin Assemblies 6 Remove and refit the components as illus trated below taking care not to damage the O seals when refitting the bobbins Refitting the Flowmeter T Reverse the removal procedure noting a the scale must be centralised b the tube is touching the contact strip 1 8 Carry out a machine Function Test sec tion 6 377 ET M 2 s Sy z 8 s i T 400262 0293 O seal 0691 O seal 36075 Washer DS ev 400224 Bobbin 01057 Washer 36247 Bobbin 36247 Bobbin Bobbin 0508 Filter 69 Cascade flowmeter system illustrated On non cascade mo
10. Hose Backbar Outlet to CGO O seal Hose assembly Backbar Outlet to CGO 37947 Seal Support NNNM UN S S SOD PARTS LIST 0691 O ring 462545 Tubing 043 Important Apply a small amount of Loctite pi 243 to the threads of this screw when OS K A refitting SPR Tu s EP Pr N Y lt 5 ZF P r s SN D 2 bos d F p 1 p 90183 Clippard Valve 400262 0293 Bobbin 01057 O seal E d E Washer o gt E 0691 36247 O seal Ex p Bobbin d Washer nd JH 0691 se dim O seal S uU 36247 0293 Bobbin O seal 0508 Filter 0508 Filter 78 PARTS LIST Main Assemblies and Miscellaneous Components Note that parts lists for sub assemblies are on following pages Item CON OO FP WD gt D 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Part No 01013 01017 01028 01056 01148 019033 019048 019127 019142 019166 019171 019175 045055 045076 045077 054540 054945 15023 402948 462544 462544 462544 462545 5000220 5000265 5000272 5000276 5000280 5000281 5000285 5000286 Description Screw M4 X 10 SKT HD Cap Screw M6 X 12 Screw M6 X 30 Screw M5 x 12 Washer M8 Screw M4 X 40 Slotted CSK SS Screw M4 x 10 Pan Head SS Screw MA x 12 But CB Screw M4 X 10 LG CSK HD ST STL Screw M6 X 16 SKT Button HD SS Screw M4 x 10 But Flanged HD Screw M8 X 1
11. Item CON OO O1 WN gt N NO NO c O N ON DD O1WN o Part No 9000282 9000283 041212 0360 71577 01056 045051 019067 700634 01059 022533 71553 01250 9000431 5000360 15464 0408 700650 045435 15447 5000430 Description Three Station Backbar Selectatec Compatible Backbar Sealing Screw O ring 019 1 X 91 6 Viton 1 4 Ball Location Button Screw M5 X 12 SKT HD Valve Capsule Screw M4 X 12 SKTHD Clip Retaining Plate Screw M2 5 X 6 Dzus Spring Interlock Peg Nut M2 5 Stem Adaptor PRV Manifold Block Label Leak Check Dowty Seal G1 4 Outlet Connector PRV Warning Label Coupling 85 Quantity Mae N OO OO GO OO OO OO O A A a PARTS LIST Backbar Manifold Assembly 2 Station Selectatec Item CON DOO AN gt 11 13 14 15 16 17 18 20 SEE NOTE 2 Part No 045051 019067 11577 01056 100634 01059 71553 022533 01250 15464 054540 054525 800238 045435 0408 700650 5000204b Description Valve Capsule Screw M4 X 12 SKT HD Location Button Screw M5 x 12 SKT HD Clip Retaining Plate Screw M2 5 X 6 Interlock Peg DZUS Spring Nut M2 5 Label Leak Check Coupling Stem Adaptor PRV Manifold Block PRV Dowty Seal G1 4 Outlet Connector 2 Station Backbar 86 Quantity SB SNDRRBDDNDOoNDNNDDRAARR PARTS LIST Therapy Flowmeter Item Part No Description Quantity 1 900042
12. Replace switch front panel Reset circuit breaker rear panel 8 annama N 2 1 2 2 3 1 3 2 3 4 4 1 4 2 4 3 4 4 SM 6 1 6 2 6 4 6 5 7 2 7 4 SERVICE SCHEDULE Initial Checks Check serial number to determine service required Check general condition and configuration of any attachments Inspect internal tubing Replace tubing that is discoloured or has lost flexibility Check Castors Operation and security Locking mechanism if fitted Examine Cylinder Yoke Assemblies Check for damage cleanliness all fitting are tight and clamping screws for freedom of movement Replace Bodok seals Replace yoke inlet filters annual service Replace cylinder and pipeline NRV O rings 4 year service Check Pipeline Hoses Examine pipeline connectors probes and hoses for cleanliness and damage Replace seals if required check for anti confusion Replace hoses at 3 year intervals and date replacement hose Note age of hose on service report If hoses not dated work from age of machine Pressure Leak Test Hoses with cylinders removed and machine OFF Replace pipeline inlet filters annual service Pressure Gauge Checks Examine each Pressure Gauge for damage Check they read zero with no gases supplied and operate smoothly with gases con nected Mechanical AHD Linkage Inspection annual service Connect O2 and switch on machine Note basal flow reading Rem
13. and the machine s function before using the apparatus Copyright Penlon Limited 2008 All rights reserved THE IMPORTANCE OF PATIENT MONITORING WARNING Anaesthetic systems have the capability to deliver mixtures of gases and vapours to the patient which could cause injury or death unless controlled by a qualified anaesthetist There can be considerable variation in the effect of anaesthetic drugs on individual patients so that the setting and observation of control levels on the anaesthesia systems does not in itself ensure total patient safety Anaesthesia system monitors and patient monitors are very desirable aids for the anaes thetist but are not true clinical monitors as the condition of the patient is also dependent on his respiration and the functioning of his cardio vascular system IT IS ESSENTIAL THAT THESE ELEMENTS ARE MONITORED FREQUENTLY AND REGULARLY AND THAT ANY OBSERVATIONS ARE GIVEN PRECEDENCE OVER MACHINE CONTROL PARAMETERS IN JUDGING THE STATE OF A CLINICAL PROCEDURE CONTENTS 3 1 9 2 3 3 3 4 3 9 3 6 Sel 3 8 3 9 3 10 3 11 3 12 3 13 4 1 4 2 4 3 4 4 4 5 4 6 4 7 4 8 4 9 4 10 5 1 9 2 o2 5 2 2 9 2 3 5 3 5 4 5 5 USER RESPONSIBILITY WARNINGS AND CAUTIONS PURPOSE DESCRIPTION Framework and General Construction Gas Circuit Gas Circuit Schematic Gas Supply Safety Devices Mechanical Anti Hypoxic Device AHD Pressure Gauges Flowmeters and Controls Vaporizers
14. falling towards zero Maximum acceptable leak is 200 kPa Turn the Air Cylinder ON Check that the Air pressure gauge responds in a smooth sweeping movement Check that the Oxygen Nitrous 34 20 21 22 29 24 20 26 Oxide and Air pressure Check again that the only indicated flow is the Oxygen Basal Flow indicate gauges Turn the Air Cylinder OFF Observe the pressure gauge reading leak will be indicated by the needle pointer falling towards zero Maximum acceptable leak is 500 kPa Turn the Air Cylinder ON Set all gas flows as required to 5 litres min Connect a manometer to each Primary regulator test point in turn and check regulator is set in accordance with specification for relevant country Connect a manometer to each Secondary regulator test point in turn and check regulator is set in accordance with specification for relevant gas Reduce gas flows to minimum settings FUNCTION TEST 6 6 Flowmeter Unit 1 Visually inspect the flowmeter tubes for damage Check that the transparent shield is in place 2 Turn the Gas Delivery Switch 1 to ON Check that a basal flow of oxygen is delivered as follows Cascade O2 flowmeter 50 75 ml min Single O2 flowmeter 100 200 ml min 3 Open the Oxygen Flowmeter control slowly Check that a full flow can be obtained 4 Seta flow rate of 6 L min Check that the float is stable in its setting and spins freely
15. machine system the warning whistle is prolonged by an oxygen reservoir built into the gas circuit allowing a minimum warning whistle of 7 seconds duration The whistle will start to sound when the pressure falls to 200 21kPa 29 3 psig and will continue to sound until the pressure falls to approximately 70 kPa 10 psig Oxygen consumption of the whistle is approximately 2 L min when sounding and nil at other times WARNING Gas supply failure systems will not necessarily operate as indicated during any procedures that are outside the scope of the indications for use of the machine see section 2 Machine set to deliver Oxygen only through Auxiliary Outlets The oxygen failure alarm is designed to operate during normal use of the machine i e when providing controlled concentrations and flows of gases to a patient breathing system Do not use the machine solely to provide large flows of oxygen via the anaesthetic machine auxiliary outlets to external devices which may not be equipped with a supply failure alarm 3 3 3 Fresh Gas Pressure Relief Valve The valve is designed to prevent fresh gas being delivered to the breathing system at pressures exceeding 41 kPa 6 psi This valve also protects machine components against excessive pressure in the event of a total blockage of the CGO 3 3 4 Oxygen Supply Visual Indicator The indicator 1 is mounted on the front of the machine and is operated from the oxygen supp
16. maximum Refer to the table below and check 96 Oxygen concentration at the Oxygen flows specified Adjust the Oxygen Flowmeter control only Do NOT adjust the N20 flowmeter Note The flow rates for N20 are given as a guide only O2 Flow 02 N20 Flow in O2 N20 mixture 0 25 L min 27 33 0 5 0 67 0 5 L min 27 33 1 0 1 35 0 8 L min 27 33 1 6 2 1 1 5 L min 27 33 3 0 4 1 3 0 L min 27 33 6 1 8 1 If the 02 concentration is outside the range given above at any of the set flows adjust the output of either or both of the secondary regulators see 9 7 2 NOTE Maintain output pressures within the range 152 241 kPa 22 35 psi 26 Check the Oxygen basal flow see 9 7 1 2 Recheck the Oxygen Concentration 28 Remove the O2 control knob 29 Carefully refit the control knob cover 8 and screws 7 ensuring that the basal flow does not change Fit the O2 and N2O control knobs 64 SERVICING PROCEDURES 9 8 Control Valve Capsule Removal Replacement CAUTION Needle valves are designed to seal with a light torque only and may be damaged if tightened excessively Note There are no user serviceable components within each flow control valve capsule 1 This procedure relates only to the exchange of the complete factory set valves 1 Remove all gas cylinders and disconnect all gas pipeline hoses CAUTION Ensure that all gas supplies are exhausted befor
17. oxide flowmeter needle valve and check that there is no nitrous oxide flow 3 Operate the oxygen flowmeter needle valve Check that full scale of flow of oxygen and nitrous oxide can be achieved and that the floats in both tubes move freely and rotate when at a steady flow 4 Check that the nitrous oxide flow can be turned off by gentle rotation of the oxygen knob Check also that the nitrous oxide float reseats on the bottom stop and that the oxygen basal flow continues to flow 5 Operate the other flowmeter control knobs in turn to check the full scale of flow can be obtained the floats move freely and rotate at a steady flow the flow can be turned off by gentle rotation of the knob and that the floats reseat on the bottom stop 6 Dual cascade flow tubes Check that gas flow is through the low flow tube initially until full flow is achieved then through the high flow tube 7 Auxiliary flowmeter 2 Rotate the flowmeter control and check that a gas flow can be obtained 22 PRE USE CHECKS 5 3 Vaporizers 5 3 1 On ALL vaporizers before use Pre use Checks 1 Check all joints for gas tightness 2 Check vaporizer agent level 3 Check for correct agent delivery concentrations use an agent analyser Always follow the procedures and checklist given in the instruction manual supplied with the vaporizer particularly when filling the vaporizer with anaesthetic agent 5 3 2 General Info
18. that the oxygen pipeline pressure gauge indicates the correct pipeline pressure Check the security of the Oxygen Hose connections by tug testing the hose 2 Perform this test at both ends of the hose by tugging gently whilst grasping the hose between thumb and forefinger Firm leak free joints should be maintained without any relative movement of the spigot ferrule or hose Note Renew all faulty hose assemblies Hoses Test for leaks from each hose by brushing leak detecting fluid generously about both end fittings Pipeline Non return Valve NRV Test for leaks using a pipeline non return valve or ball valve assembly The leak rate should be less than 10 kPa in one minute Alternatively fit a tube securely to cover the hole in the centre of the Oxygen Cylinder Yoke Seal 3 Brush leak detecting fluid over the other end of the tube Leaks will be indicated by bubbling of the fluid Dry with paper towel fix any leaks replace hose NRV if necessary Connect the Nitrous Oxide Supply to the anaesthetic machine using the pipeline hose Repeat tests 5 to 10 for this gas Connect the Air Supply to the anaesthetic machine using the pipeline hose Repeat tests 5 to 10 for this gas 32 FUNCTION TEST 6 5 Cylinder Gas Supply And Pressure Reducing Valves CAUTION This machine is fitted with an hypoxia guard known as a Mechanical Anti Hypoxic Device MAHD This device prevents the delivery of hypoxic
19. x 10 But Flanged HD M4 x 12 Pan Head SS Tube Hook Drawer Runner Set Draw Assembly Installation Elesa Lock CSU 13 32 Boxing Plate 020 Washer SS Dome Plug 219 0 M4 X 12 LG CSK HD Lighting Sub Assembly M3 X 10 LG Pan HD 94 Quantity 1 RRRSRSPKU P amp 4P P NO NO BRA WWANNAN KABA WOK AR A NO PARTS LIST PARTS LIST P TE si DETAIL B DETAIL C ES 22 o nm LE BG 0 Dre WAN QE VIEW D DETAIL A 96 PARTS LIST Work Surface Assembly Part No Item CON O1 AN 12 13 T9 16 9000222 9000239 01043 9000235 019003 9000224 01011 019147 9000227 019048 9000270 Description O2 Push Button Assembly Work Surface Rail M C M4 x 20 Cap Head Ss Work Surface Rail Bracket M3 X 20 SS SK HD Slide Out Work Surface M4 Plain Washer M4 X 14 SKT HD Cap Worksurface M4 X 10 Button HD Worksurface Runner 97 Quantity N gt a NNa NN NN gt APPENDIX Prima SP2 Schematic for models built up to March 2007 USA specification three gas machine with dual cascade oxygen and nitrous oxide flowmeters v L Flowmeter Assembly al A TH Gas Tray o LJ Ve L S L Li 2 2 tr t t t t t 9 o 9 DO S rir 98 APPENDIX Key to Gas Schematic Pneumatic pressure Source Filter Pressure gauge u
20. 0 L min against 270 kPa 40 psig resistance 50 L min against 297 kPa 44 psig resistance Air on machines with Air supply option One self sealing connection on rear of machine 16 UK 400 kPa 58 psig 380 kPa 15 kPa 35 kPa 55 psig 2 psig 5 psig 2800 kPa 406 psig 600 kPa 87 psig 41 kPa 10 6 psi 10 SPECIFICATION 4 6 Oxygen Failure Warning Devices l Gas system whistle 2 Visual indicator direct pressure operated 4 7 Oxygen Flush Button on front edge of worksurface The system supplies 35 75 L min when fully depressed 4 8 Mechanical AHD System Minimum oxygen concentration 30 3 of total O2 N20 flow Basal Flow Cascade flow tubes Oxygen basal flow 50 75 ml min Single Flow tubes Oxygen basal flow 100 200 ml min Reduced pressure from secondary regulators See section 4 4 4 9 Environmental Operating Conditions Temperature 10 to 389C 50 to 1009F Atmospheric Pressure range 70 kPa to 106 kPa Altitude 2438 m 8000 ft maximum Humidity 10 95 R H non condensing Transport and storage temperature Basic machine 5 to 609C 23 to 1409F Oxygen monitor option 5 to 509C 23 to 1229F Cleaning Wipe external surfaces with dry or damp cloth Use mild soap or disinfectant solution if necessary 17 SPECIFICATION 4 10 Electrical Supply Power Input NOTE The internal power circuit feeds the machine lighting systems only Option 1 Internal power au
21. 0 LG Selector Switch O2 N20 Manifold Assembly secondary regulators Air Manifold Assembly secondary regulator Coupling Visual indicator oxygen failure Product Label Cable Retainer Pipe Flush In 28 Pipe Flush Out 28 Pipe O2 In 28 Pipe CGO 910 Frame Assembly Fresh Gas Manifold Gas Bar Installation Auxiliary Outlet Assembly Gauge Cover Backbar Assembly Vertical Access Panel Top Shelf Assembly Parts List continues on following pages 79 Quantity me cl cA cl cl cA gt N NNa Na Na NA i 80 PARTS LIST Main Assemblies and miscellaneous parts continued Note that parts lists for sub assemblies are on following pages Item 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 09 56 Part No 5000298 5000332 5000333 5000337 5000362 5000401 5000402 5000422 5000426 5000427 5000454 5000455 5000456 5000457 5000458 5000469 5000470 5000471 5000539 700615 800217 800289 800313 800429 800651 Description Flowmeter O2 N2O Cascade CGO Outlet Plug CGO Outlet Gauge Cover Clamp Plate Dome Plug 228 0 Black V Bracket GCX Assembly V Bracket Assembly RH Forward Therapy Flowmeter Assembly Cable Management 2 Hook Drip Pole Assembly On Off Label Label Visual indicator oxygen failure Label Auxiliary Outlet Label CGO Outlet Label L
22. 0762 Filter Yoke and pipeline 19 PARTS LIST Preventive Maintenance Kit 24 Month Service 400262 0293 Bobbin O seal E es E 5 3 0691 os EE O seal gt ucc 36075 Washer i 0691 i osea t 0293 O seal Bobbin 0508 Filter 0508 Filter 37947 37951 F Split O ring Seal Support 022533 T 3 OT MM eee Dzus Clip e LI NNN A SUA WZA NIEA 37946 Hose Support O ring 043 O ring 76 01057 Washer 36247 Bobbin 36247 Bobbin PARTS LIST Prima SP 2 3 Preventive Maintenance Kit 48 Month Service Part No 57291 Kit Contents Part No 041115 016 400224 400262 0762 0508 36247 01057 36075 0691 0293 462545 Qty Oo oo oO BR Oo 0000 Component Description O ring Selectatec Bodok Seal Flowmeter Bobbin Metal with Filter Flowmeter Bobbin Metal without Filter Filter Yoke and Pipeline Filter Flowmeter Flowmeter Bobbin Tube Seals Washer Shock Washer O seal Flowmeter Tube O seal Flowmeter Tube Tubing CGO O2 fush button to rear outlet 041115 O ring 0762 Filter Yoke and pipeline 7 043 90183 0314 0691 3 946 3 947 3 951 022533 Following not shown 1 35 m 462526 0226 1 1 2 6 4 4 4 2 2 37951 Split O ring O seal Safelock Clippard Valve Oxygen Flush O ring Oxygen Flush Clippard Valve O ring Cylinder Pipeline NRV Hose Support Seal Support Split O ring Dzus Clip
23. 20 mixture N20 Flow 0 25 L min 27 33 0 5 0 67 0 5 L min 27 33 1 0 1 35 0 8 L min 27 33 1 6 2 1 1 5 L min 27 33 9o 3 0 4 1 3 0 L min 27 33 6 1 8 1 If the 02 concentration is outside the range given above at any of the set flows adjust the output of either or both of the secondary regulators as follows Switch the Gas Delivery switch to OFF Remove the front cover follow the procedure given in section 9 5 Retighten the screws 2 securing the gas blocks Reconnect the cylinder and pipeline supplies Attach a pressure gauge to the regulator test point 3 oxygen or 4 nitrous oxide Switch the Gas Delivery switch to ON To increase output turn the regulator cap 5 or 6 slowly clockwise To decrease output turn the regulator cap fully anti clockwise then clockwise to the correct setting Maintain the output pressure within the range Secondary regulator pressure 152 241 kPa 22 35 psi If the correct basal flow can not be achieved reset the gear linkage see section 9 7 3 Recheck the Oxygen Concentration 61 17 v Quan S pol xm Ve Q5 mm all anon QT Hox I se LN 4 Q 3 7 I Wii NT IA H aT Ari DT DE 1 SERVICING PROCEDURES 9 7 3 Gear Linkage Reset Cascade and Single Flowmeter Tube Systems NOTE The machine must be on a flat surface Set the secondary regulators 1 10 11 Set the Gas Deli
24. 21 Inlet Bellows Drive Gas Absorber valve block 22 Outlet to breathing system Heat and moisture exchanger 23 Input socket Oxygen monitor sensor Patient 24 Input socket Prima SP interface CGO Block on anaesthetic machine Fresh Gas Supply SP on off switch Auxiliary Outlet on anaesthetic machine Drive Gas Supply 25 Input socket Flow sensor expiratory i A200SP Absorber Bag Vent control position Flow sensor inspiratory ii Spirometer sensor signal Connectors sensor pressure monitor 26 Interface connections on Prima SP and A200SP Expiratory Valve Absorber 27 APL Valve Inspiratory Valve Absorber 28 Outlet from APL Valve to AGSS Inlet from Ventilator Bellows 29 Oxygen sensor Connector Reservoir Bag 30 AV S remote screen Inlet Absorber Fresh Gas Supply 31 Cable AV S control unit to screen 26 PRE USE CHECKS 5 5 5 Breathing Circuit Schematic Note 1 To protect the expiratory limb of the breathing circuit and the spirometer use a breathing circuit bacterial filter 4 and a heat and moisture exchanger 6 at the patient Y piece CAUTION Replacement Disposal always follow the instructions supplied with the filter or heat and moisture exchanger Always renew components at the recommended interval 2 Follow the instructions in the relevant user manual for connection to analysers and monitors 3 Ventilator connections shown are for AV S with spirometry and oxygen monitor 4
25. 3 Flowmeter GCX Bracket 1 2 5000424 Therapy Flowmeter 1 9 054519 Coupling 1 4 5000441 Hose Tail 1 D 019026 M5 X 40 SKT HD Cap 2 6 5000425 Flowmeter Adaptor Block 1 f 041202 O Ring 96 1 X 01 6 1 8 5000392 M6 X 16 SKT Set Screw ST STL Cup Point 2 9 019006 M5 X 30 SKT HD Cap 2 87 PARTS LIST Flowmeter Assembly Part No 10 11 12 13 14 15 16 17 19 20 21 22 24 25 26 27 29 30 31 32 33 34 800341 019123 15277 800196 800230 800337 01031 15051 800231 800222 800226 800652 015043 015044 031048 0360 019133 800622 800708 800270 5000432 800234 5000446 5000433 019011 38349 01067 054515 054524 800225 800223 Description Flowmeter Overlay M4 x 10 CSK ST STL CHEM BLK Label N20 Flow Tube Cover Knob N20 Air CO2 Anti Tamper 3 Hole M4 x 35 Cap Head SS Label O2 US Knob O2 Flow Tube N2O Cascade Flow Tube N2O Low Needle Valve N2O Spur Gear 50 Teeth Spur Gear 20 Teeth Spring 27 62 X 17 46 LG 1 4 Ball Screw M3 X 6 Needle Valve Assembly O2 Needle Valve Assembly N2O left hand thread Spacer Plate Top Cover Flowmeter Panel Prima Us Label Cascade Mixing Chamber M3 X 6 LG SKT HD Stop Pin M3 Plain Washer Elbow 8 mm Tube Elbow 10 mm Tube Flow Tube O2 Low Flow Tube O2 Cascade Parts List continues on following pages 88 Quantity 1 2 1 1 2 1 K a o n N OO CO NO PARTS LIST
26. Basal Flow Single O2 flowmeter 100 200 ml min f Turn on the Gas Delivery Switch 5 Check that the warning whistle sounds briefly Check that a basal flow of oxygen is delivered as indicated in the table 33 FUNCTION TEST Leak Tests For each gas leak test allow a minimum 2 minute period 8 9 10 11 12 13 14 15 16 17 18 19 Turn OFF Gas Delivery Switch 5 Turn the Oxygen Cylinder OFF Drain down the oxygen system and blank off the output of the O2 secondary regulator Turn on the O2 cylinder then turn off again Observe the pressure gauge reading a leak will be indicated by the needle pointer falling towards zero Maximum acceptable leak is 500 kPa Drain down the oxygen system and remove the blank Reconnect the output of the secondary regulator Turn the Oxygen Cylinder ON Turn the Gas Delivery Switch 5 ON warning whistle will sound briefly Check that all flow control valves are in the OFF position and that the only flow indicated is the Oxygen Basal Flow Turn the Nitrous Oxide Cylinder ON Check that the Nitrous Oxide pressure gauge responds in a smooth sweeping movement Check that the only Gauges indicating pressure are those for Oxygen and Nitrous Oxide Check again that the only indicated flow is the Oxygen Basal Flow Turn the Nitrous Oxide Cylinder OFF Observe the pressure gauge reading a leak will be indicated by the needle pointer
27. Drawers Loading Castors Ventilator bellows post Loading Gas scavenging fixing Loading Common gas outlet Height x Width x Depth cm 139 x 71 x 70 86 cm 58 cm x 25 cm 30 kg 66 Ib evenly distributed 30 x 22 cm 71 cm x 35 em 30 kg 66 Ib evenly distributed 12 x 54 5 x 35 cm 10 kg 22 Ib evenly distributed Diameter 5 inches Front pair braked Bushed to accept 25 4 mm 1 inch or 22 mm 7 8 inch poles 30 kg 66 Ib Bracket on frame upright 30 kg 66 Ib 22 mm male taper with coaxial 15 mm female taper connections Safelock fitting Weight approximate depending on specification 75 kg 165 Ib 14 SPECIFICATION 4 2 Gas Supplies Cylinders A maximum of four cylinder fittings can be specified All cylinder yokes are pin indexed Special order options Helium Xenon Pipeline Maximum of three oxygen nitrous oxide air All to relevant national standards Medical gas colour codes Oxygen green or White Nitrous oxide Blue Medical air Yellow or Black White Carbon dioxide Grey Helium Brown Xenon Green bright To comply with relevant national standards Internal pipework is diameter indexed for each gas Oxygen 8 mm Carbon Dioxide 4 mm Nitrous oxide 6mm Helium 4mm Air o mm Xenon 4 mm Mixed gas 10 mm 4 3 Flowmeters Flow ranges Single flow tubes Oxygen 0 10 L min Nitrous Oxide 0 10 L min Air 0 10 L min Helium 0 10 L min Cascade flow tubes Ox
28. RE USE CHECKS 5 6 Machine Low Pressure Leak Test NOTE This test is necessary if the system fails the low pressure test 5 5 6 1 Attach a side branch connector to the CGO outlet Connect the side branch tube to a sphygmomanometer 2 Turnona flow of 150 ml min of oxygen Block the open port of the connector with a finger The pressure in the low pressure gas system will rise and be displayed on the sphygmomanometer 3 Check that the pressure rises to at least 100 mmHg Release the finger seal immediately the pressure is reached CAUTION Do not maintain closure of the open port longer than necessary to perform the test This test should be performed a With all vaporizers off and isolated b With each vaporizer in turn set to 196 NOTE This test is equivalent to and in some cases exceeds the requirements for system leakage rates quoted in national standards worldwide 5 7 Oxygen Flush Check for a high flow of oxygen through the CGO outlet when the flush valve button is pressed and that the flow ceases when the button is released This test is most conveniently done after the breathing system has been attached using the reservoir bag as an indicator of gas flow 28 5 8 Anaesthetic Gas Scavenge System AGSS By inspection check that all sources of expired anaesthetic gases e g the absorber APL valve and the ventilator bellows patient gas exhaust port are connected to an approved
29. Repeat test at a flow rate of 500 ml min 5 Without rotating the control knob check for wear by gently pulling on the knob and check that any fluctuation in flow rate is within the range of 100 ml min 6 Close the Oxygen Flowmeter control valve gently until the mechanical stop engages 7 Check Oxygen Basal Flow operation 2 See 8 Nitrous Oxide Oxygen Linkage 9 Fully open the Nitrous Oxide Flow control and check that no flow is indicated on the flow tube 10 Slowly open the Oxygen Flowmeter control and check that the Nitrous Oxide flow tube float rises Pause briefly at an indicated Nitrous Oxide flow of 4 L min Check that the Nitrous Oxide flow tube float is stable in its setting and spins freely Increase the Oxygen flow until maximum flow of Nitrous Oxide has been achieved 35 11 12 13 14 15 Close the Oxygen Flowmeter control valve gently Pause briefly when Nitrous Oxide flow indicates 500 ml min Check the stability of the Nitrous Oxide float and that it spins freely Decrease the Oxygen flow until the mechanical stop engages Check that as the Oxygen flow rate is reduced so is the flow of Nitrous Oxide Check again that the only flow indicated is the Oxygen Basal Flow Close the Nitrous Oxide Flowmeter control Open the Air Flowmeter control slowly and see that a full flow can be obtained Set an Air flow of 5 L min and check that the Air flow tube float is
30. achine AV S with interface link to Prima SP See section 3 15 a Turn the machine Gas Delivery Switch ON The ventilator will power up b While the Prima SP power is ON the Ventilator can be turned OFF and ON using the ventilator On Off switch c Turn the Gas Delivery Switch to OFF The ventilator will power down AV S Ventilator Back up Battery If the power supply to the ventilator fails the ventilator back up battery will power the ventilator for 30 minutes if the battery has been maintained in a fully charged condition Refer also to the user instruction manual supplied with the ventilator Battery charging takes place automatically when the ventilator mains lead is connected to a live mains supply The OFF indicator on the ventilator front control panel will show a yellow light during charging NOTE The stated battery back up period will only be available if the battery is kept fully charged If the battery has been allowed to discharge below the LOW BATTERY condition the ventilator will not function correctly until the voltage raises above the LOW BATTERY level A fourteen hours recharge will be necessary to bring the battery to full charge 3 9 5 Monitor and other Accessories The mains lead or adaptor for a monitor system or other accessories requiring an electrical supply can be plugged into one of the auxiliary sockets on the rear of the machine 12 DESCRIPTION 3 10 Auxiliary Gas Outlets
31. ation manifold The installation of non interlock vaporizers allows the possible operation of more than one vaporizer at the same time If two vaporizers only are mounted on a three station manifold they must be installed on adjacent stations Check that the interlock mechanisms of all the vaporizers on the manifold are working correctly i e check that only one vaporizer at a time can be turned on PRE USE CHECKS 5 4 Electrical Supply 1 Connect the machine power lead to a 1 suitable mains supply socket 2 Set the switch 1 to ON Check for correct function of each auxiliary power outlet 3 Check all electrical equipment including devices powered by the auxiliary power outlets on the rear of the machine 4 Machines with optional flowmeter lighting Check for correct operation 24 PRE USE CHECKS All models 5 5 Patient Breathing System 5 5 1 Hose Connections Check that all hoses are secure 5 9 2 Breathing System Hose Reservoir Bag Ventilator Connectors for the Inspiratory hose and Expiratory hose and the reservoir bag connector are 22 mm male All connectors comply with ISO 5356 1 The ventilator connection point is also 22 mm male Hose and bag connections are fitted with Penlon Safelock high security fittings Check all connections for gas tightness 5 5 3 Fresh Gas Supply The fresh gas hose assembly supplied with the machine has a Penlon connector at the absorbe
32. be used if any of the alarm monitoring or protection system devices are not functioning correctly The machine must not be fitted with more than four operator accessible mains socket outlets There is a risk of an excessive leakage current WARNINGS AND CAUTIONS 12 13 14 15 The use of antistatic or electrically conductive breathing hoses is not recommended when using high frequency electrical surgery equipment e g Diathermy Burns may be caused Before any electrically powered machine is used clinically for the first time check that the hospital engineering department has carried out an earth continuity test Before using any additional electrical equipment powered by the auxiliary sockets on the machine check that the additional equipment is correctly wired and is earthed through its plug A missing or defective protective earth conductor may increase earth leakage currents to the patient to values exceeding the allowable limits resulting in ventricular fibrillation or interference with the pumping action of the heart Additional equipment placed on the top shelf must be securely attached Take care when moving a fully loaded machine particularly when negotiating ramps Check that hoses or power leads are not trailing on the floor CAUTIONS 1 Flowmeter needle valves are designed to seal with light torque and may be damaged if tightened excessively Do not force the control knob pas
33. blies for vaporizer connector block attachment When a vaporizer is installed on a station the valves on that station open automatically to allow gas flow into and out of the vaporizer Removal of the vaporizer from the station closes the valves on that station Selectatec compatible vaporizer interlock systems are described in the literature supplied with the vaporizer 10 3 8 Common Gas Outlet CGO The outlet 1 is at the rear of the machine and has a 22 mm male taper and concentric 15 mm female taper The male taper incorporates the Penlon Safelock system designed to prevent accidental disconnection of the breathing system Note front mounted CGO available as an option Oxygen Flush An emergency oxygen flush valve button 2 is mounted at the font of the machine and is marked O2 FLUSH Depressing the button provides a delivery of between 35 75 litres min of oxygen through the common gas outlet 1 Releasing the button allows the spring loaded valve to return to its normal position DESCRIPTION 3 9 Electrical Power Supply 3 9 1 Mains Power Supply Power is fed to the machine via the mains lead to power an optional auxiliary output panel and or lighting system Mains Power Indicator The warning lamp 1 is illuminated when mains power is connected Current Leakage NOTE a It is the user s responsibility to ensure that the total sum of leaka
34. collection system leading to an AGSS WARNING Do not connect a vacuum system directly to the APL valve on the absorber A receiving system with a positive and negative pressure control function must be interposed Systems must comply with standard ISO 8835 part 2 5 9 Always follow the pre use check procedures given in the ventilator instruction manual Check all hose and tubing connections for gas tightness Check all wiring connections for correct fitment and security Ventilator AV S Ventilator Check for correct fitment of the interface cable at each connector Check that the cable between the control unit and remote screen is securely in place Check the interface system function a Turn the Gas Delivery Switch ON The ventilator will power up b While the Prima SP2 power is ON the ventilator can be turned off and on using the ventilator On Off switch c Turn the Gas Delivery Switch to OFF The ventilator will power down PRE USE CHECKS 5 10 Alarm System Test WARNING The anaesthetic machine must not be used if any alarm is not functioning correctly Primary Oxygen Failure Alarm The machine is fitted with a warning whistle and a visual indicator 1 These components act as oxygen supply failure devices and constitute the primary alarm system powered only by the residual oxygen supply as described in section 3 The system can be checked whenever the low pressure oxygen system is first pressuris
35. ded methods Monitor Refer to the monitor user instruction manual Ventilator AV series Ventilator Bellows Assembly Cleaning he user must follow the detailed instruc tions included in section 7 5 of the ventilator user instruction manual Never use any hard object or abrasive agent to clean any of the components only a soft cloth If the valve seat is damaged the diaphragm valve will leak and this may cause serious malfunction CAUTION Do not use any cleaning solution containing alco hol or any harsh abrasive cleaning agent on the bellows housing Sterilisation The user must follow the detailed instruc tions included in section 7 of the ventilator user instruction manual WARNING Do not autoclave the bellows housing The exhalation diaphragm valve assembly must be disassembled prior to sterilisation do not sterilise the diaphragm SERVICING PROCEDURES 9 4 Internal Gas System 9 4 1 Pipework Identification Internal pipework is colour coded and diameter indexed as follows Colour codes Oxygen Green or White on non US specification machines Nitrous Oxide Blue Medical Air Yellow or Black white on non US specification machines Tubing diameter Oxygen 8 mm Nitrous Oxide 6 mm Medical Air 5 mm Mixed Gas 10 mm 9 4 2 Tubing Connectors Push in type fittings are used throughout the low pressure circuit To connect and disconnect the tubing from TH the connectors follow the procedures deta
36. dels a filter 0508 is fitted to each flow tube SERVICING PROCEDURES 9 13 Flowmeter Assembly Removal CAUTION Ensure that any residual gas in the machine is exhausted before commencing the dismantling procedure Removal 1 Remove all cylinders and disconnect all pipeline supplies 2 Disconnect the machine from the mains electrical supply 3 Remove the flowmeter cover see section 9 6 4 Remove the four screws 1 securing the flowmeter assembly to the machine frame 5 Disconnect the tubing 2 where nec essary to allow the removal of the flowmeter assembly Refitting 6 Reconnect the tubing at the back of the flowmeter assembly see section 9 4 T Reverse the removal procedure 8 Carry out a machine Function Test section 6 70 SERVICING PROCEDURES 9 14 Oxygen Monitor Sensor Sensor Cleaning and Disinfection In case of contamination the sensor may be cleaned with distilled water and allowed to dry naturally CAUTION The sensor is not suitable for sterilisation by steam or exposure to chemicals such as ethylene oxide or hydrogen peroxide Do not immerse the sensor in any cleaning solution Do not autoclave or expose the sensor to high temperatures Sensor Replacement WARNING The sensor contains a A small quantity of electrolyte classified as a harmful irritant which is potentially hazardous b Lead Do not attempt to open a cell ALWAYS check the integrity of th
37. e N20 In Oxygen Supply o Visual Indicator Gas Delivery On Off Switch O2 Pipeline Supply Block 02 Sensing line To To Auxiliary Outlet Oxygen Flush of SERVICING PROCEDURES 9 5 Front Cover Remove and Refit CAUTION Ensure that any residual gas in the machine is exhausted before commencing the dismantling procedure Removal 1 Remove all cylinders and disconnect Pipeline supply hoses 2 At the rear of the machine slacken the screws 1 securing the gas blocks 9 Remove the two top fixing screws 2 securing the panel to the front of the machine 4 Slacken each screw 3 on the side of the machine to loosen the side clamp plates 5 Carefully pull the cover 4 away from the front of 1 the machine Note that the gas delivery switch and oxygen fail Refit 6 Line up the cover with the gauges and switches 7 Check that the clamp plate on each side of the machine is positioned to allow the sides of the cover to fit between each plate and the frame 8 Carefully push the cover into place 9 Screw in the top fixings 2 Do NOT tighten 10 Tighten the clamp plate screws 3 11 Tighten the top fixings 2 12 Atthe rear of the machine tighten the screws 1 58 SERVICING PROCEDURES 9 6 Flowmeter Cover Removal 1 Slacken the screws 1 securing the spacer strip 2 2 Remove the screws 3 and top guard 4 3 Remove the cover 5 Refitting
38. e commencing these procedures High pressure gas can fire the valve out of the machine Remove the cover and flowmeter knobs as detailed in section 9 7 3 To remove a capsule first loosen the grub screws 2 and remove the gear 3 Undo the two securing screws and washers 4 and withdraw the capsule 1 65 To replace the flow control valve lightly smear the O seals 5 with Fomblin and insert the capsule into the manifold block Align the two slots 6 with the securing screw holes and refit the screws and washers 4 If necessary reset the gears as detailed in section 9 7 3 and check the gas flows Replace the flowmeter knobs and cover Perform a function test section 6 SERVICING PROCEDURES 9 9 10 11 12 13 Secondary Regulators Check and Reset Pressure Output Turn the Gas Delivery Switch 1 to OFF Disconnect all pipeline and cylinder supplies Remove the front cover see section 9 5 Retighten the screws 2 securing the gas blocks Reconnect the cylinder and pipeline supplies Attach a pressure gauge to the oxygen regulator test point 3 Turn the Gas Delivery Switch to ON Set a flow of 5 L min Oxygen Reset the Oxygen secondary regulator to the figure given in the table To increase output turn the regulator cap 4 slowly clockwise To decrease output turn the regulator cap fully anti clockwise then clockwise to the correct setting Re
39. e sensor assembly before use Once exhausted the sensor must be disposed of according to hospital local state and federal regulations Sensor Unit Remove and Refit 1 Pull out the cable connector A from the expired sensor B Remove sensor from the absorber or Tee adaptor Discard the expired sensor and flow diverter C Insert the cable connector into the new sensor B If necessary screw the new flow diverter C onto the new sensor and fit new O rings Fit the assembly into the absorber Reconnect the cable Calibrate the new sensor see section 5 12 Dispose of the used components according to hospital regulations and relevant national legislation B as der De li eS 71 Sensor location on A200SP Absorber Replacement part number 102714 Sensor assembly 10 PARTS LIST Preventive Maintenance Kits PMKs Prima SP2 3 range is serviced on a 6 month 1 year 2 year and 4 year cycle 6 month Kit Part No 57288 1 year Kit Part No 57289 2 year Kit Part No 57290 4 year Kit Part No 57291 NOTE 1 Pipeline hoses must be replaced at three years 2 Primary regulators must be replaced at five years 12 PARTS LIST Prima SP2 3 Range Preventive Maintenance Kit 6 Month Service Part No 57288 Kit Contents Part No Qty Component Description Bodok Seal 016 5 041115 6 O ring Selectatec 043 1 O ring Safelock Connector on CGO outlet 016 Bodok Seal 041115 O r
40. ed by turning on a cylinder or connecting a pipeline a The whistle will sound briefly as pressure increases and b The visual indicator will turn from red to green Whistle Visual Indicator and Gas Cut off Device Test A formal test including the action of the internal gas cut off device is performed as follows 1 Connect oxygen nitrous oxide and air supplies 2 Set the Gas Delivery switch 2 to ON and check that the warning whistle sounds briefly Seta flow of 2 L min on both flowmeters 4 Disconnect the oxygen supply at the wall socket or close the oxygen cylinder valve and check a that as the oxygen flow slows down the whistle starts to sound and continues for at least 7 seconds b that the flow of nitrous oxide is cut off completely before the oxygen flowmeter shows zero flow c that the visual indicator 1 turns red before the oxygen flow is entirely stopped d air continues to flow NOTE All gases must be included in the pre use check 5 Reinstate the oxygen supply Check that the flow of nitrous oxide is reinstated and that the visual indicator turns green again ad 29 6 FUNCTION TEST 6 1 Introduction Commissioning a New Machine Every PrimaSP anaesthetic machine is tested thoroughly before leaving the factory but it is essential to undertake a complete performance check as described in this section before the machine is first used clinically This can be done by a Penlon tra
41. eedle valve is operated and that the oxygen valve is open NOTE cylinder supply can be used if necessary for this test Air supply 6 Connect the Air pipeline hose Check the gauge reading Check for a flow of air when the flowmeter needle valve is operated 5 2 2 Gas Cylinder Supplies CAUTION Open the cylinder valves slowly to avoid damage to the pressure reducing valve and pressure gauges Ensure that valves are at least one full turn open when in use 1 Fit the gas cylinders to their respective yokes open the cylinder valves one at a time and check the pressure on each gauge NOTE A When two cylinders are provided for a single gas test each separately clearing pressure after each test by open ing the flowmeter valve B Turn off the reserve cylinders during normal use C N2O cylinder pressure does not indicate cylinder content 2 Ensure that all flowmeters are kept closed until gas supplies are required 21 CAUTION The mechanical AHD system requires that the oxygen flowmeter control is restricted to prevent the needle valve from fully closing This ensures a minimum oxygen basal flow DO NOT attempt to close the flow to zero Do not overtighten the knob PRE USE CHECKS 5 2 3 Flowmeters 1 Turn on the Gas Delivery switch 1 and check that the warning whistle sounds briefly briefly and that the correct basal flow of oxygen is delivered see section 4 2 Open the nitrous
42. elling This symbol denotes Refer to the User Manual A N 18 9 PRE USE CHECKS 5 1 Pre use Checklist A pre use checklist for the Prima SP2 range of machines is printed on the next page This checklist is also supplied with the machine Where necessary subsequent sections in this manual provide an explanation and procedure for setting up the machine and ancillary equipment and the various checks that must be carried out before clinical use WARNING Pre use checks must be performed before each period of clinical use These checks must be supplemented by periodic Function Testing and full Service Testing by a Penlon trained engineer to the Service Schedule given in this manual These checks will not in themselves ensure the safe use of the apparatus which remains the responsibility of the qualified practitioner in charge of it 19 PRE USE CHECKS PRE USE CHECKLIST The machine must be carefully inspected and checked as follows An incorrectly functioning machine must be repaired by a suitably qualified person before use N or Ol e p 0 1 Check for visible damage machine stability and condition of gas supply hoses Check for labelling which may indicate status of machine including faults or recent servicing Check correct connection of electrical supply Check correct connections of gas supplies Check adequate pipeline supply and back up cylinder supply owitch on gas delivery switch and note s
43. etailed in the AGSS user instruction manual SERVICING PROCEDURES 9 2 5 Circle System Absorber A200 Absorber 6 months Inspection and Function Check 12 months Component replacement 48 months Additional component replacement Removing the Absorber Assembly CAUTION The canister 1 may contain condensate Before removing the absorber from the pole mount assembly refer to the A200SP user manual for instructions on draining the canister and disposing of absorbent 1 Set the brakes on the anaesthetic machine front castors 2 Slacken the knob 2 and lift the absorber assembly from the pole mount 9 2 6 User Maintenance The Prima SP series user manual states that user maintenance is restricted to cleaning the external surfaces of the machine All other maintenance and servicing must only be carried out by Penlon trained engineers The Prima SP2 must be only be serviced according to the schedule and procedures given in this Service Manual o4 9 3 Cleaning and Sterilisation Frequently wipe over the external surfaces of the machine the vaporizers with a damp cloth Always allow the machine to dry off thoroughly before using it Mild antiseptic solutions may be used but should be rinsed off with clean water Breathing system hoses and other compo nents must be sterilised to the manufactur er s recommen
44. ew Loctite 242 15 Check that each gear slides easily on its shaft 16 Set the Gas Delivery Switch to ON 17 Open the N2O valve to maximum to check full flow 18 Close the valve gently until the N2O bobbin ceases to rotate Do not over tighten the valve when closing this will cause irreparable damage to the valve seat 19 Fit the O2 gear 9 on the shaft 20 Fit the O2 control knob and open the O2 control valve to check full flow Cascade Flowmeter Tube Models Close the valve until a flow of 50 75 ml min is obtained Single Flowmeter Tube Models Close the valve until a flow of 100 200 ml min is obtained 21 Distance the inner face of the O2 gear 9 with a 0 1 mm feeler gauge at A Tighten the grubscrews 10 to secure the O2 gear Check the flow returns to the basal flow set in operation 20 above 22 With the O2 gear against the stop replace the N2O gear 11 and push on so that the front faces of the gears are flush see X X as illustrated Note that the rear face of the N2O gear is closer to the manifold block than the O2 gear 23 Tighten the grubscrews 12 to secure the N2O gear Apply a small amount of Molycote BG87 grease evenly distributed to the O2 and N2O gear teeth 24 f the machine is not fitted with an Oxygen monitor connect a stand alone analyser to the CGO outlet 63 SERVICING PROCEDURES 25 Check Oxygen concentration Turn the Nitrous Oxide flowmeter control to
45. gauges and yokes Pressure relief valve leaks or out of adjust ment Symptom Leaking high pressure connection from cylin der to yoke Diaphragm or valve disc worn damaged Outlet pressure too high may occur with leak ing pressure relief valve Outlet pressure too low Diaphragm valve disc worn damaged or regu lator out of adjustment Pressure gauge reads zero when cylinder valve opened Pressure gauge pointer sticks at above zero reading Leaking high pressure non return valve 40 Possible Fault Bodok seal absent or worn Cylinder clamp screw assembly damaged Inadequate engage ment of pin index sys tem Adjust replace regulator as necessary Faulty relief valve Diaphragm worn dam aged or out of adjust ment Regulator seat dam aged Loose connections Tighten leaking joints DO NOT use exces sive force Adjust replace regulator as necessary Cylinder empty Bodok seal absent or worn Cylinder clamp screw assembly damaged Pressure gauge seal damaged Inadequate engagement of pin index system Defective gauge Defective gauge Gas trapped in system Damaged O seal Remedy Fit replace seal Replace as necessary Ensure correct gas cylinder is attached Check index pins not loose or damaged Replace as necessary Fit new relief valve Adjust replace regulator as necessary Replace regulator Test for leaks Rep
46. ge currents from additional equipment plugged into the auxiliary sockets plus the leakage current from the machine does not exceed the values specified in any relevant national standards that may apply in the country where the machine is in use b Each socket is protected with two 5 A fuses 3 9 2 Auxiliary Power Supply Sockets The optional mains electricity outlet panel is fitted to the rear of the machine The supply is controlled by an ON OFF switch 2 which also incorporates a circuit breaker 3 9 3 Flowmeter Bank Lighting The lighting system is controlled by a three way switch 3 The three positions denote A Off B Bright light C Dim light Battery charging takes place automatically when the ventilator mains lead is connected to a live mains supply The OFF indicator on the ventilator front control panel will show a yellow light during charging NOTE The stated battery back up period will only be available if the battery is kept fully charged If the battery has been allowed to discharge below the LOW BATTERY condition the ventilator will not function correctly until the voltage raises above the LOW BATTERY level A fourteen hours recharge will be necessary to bring the battery to full charge 11 DESCRIPTION 3 9 4 Ventilator Power Supply The mains lead for an AV series ventilator can be plugged into one of the auxiliary power sockets on the rear of the m
47. heck Emergency Oxygen Flush Flow rate is between 35 75 l min on cylinder and pipeline supply Ensure Oz fail does not alarm 50 SERVICE SCHEDULE 12 Check Oxygen Fail Alarm 12 1 Set 02 at 2 l min set N2O at 3 l min set Air at 3 l min 12 2 Shut Off O2 supply 12 3 Check audible warning operates between 221 172 kPa dropping 12 4 Check N2O ceases flowing between 200 172 kPa dropping 12 5 Visual indicator is Red between 138 200 kPa dropping 12 6 Audible warning operates for 7 seconds minimum 12 7 Check that after O2 flow has ceased that Air continues to flow 12 8 Turn On 02 supply Ensure visual indicator is Green and whistle sounds briefly Ensure all flows are re instated Reset all flowmeter controls to minimum 13 Check Flowmeter Operation 13 1 Check needle valves for smooth operation and positive off position 13 3 Check flowmeter tube and freedom of bobbin 13 4 Inspect flowmeter upper and lower seals replace if necessary 13 5 Replace flowmeter upper and lower seals and filters 2 year service 14 Additional Mechanical AHD Checks 14 1 Connect O2 monitor to CGO 14 2 Turn On Gas Delivery switch Ensure whistle sounds briefly Ensure a basal flow 50 75 ml min Cascade machines 150 50ml min single flow tube machines 14 3 Fully open N2O control and ensure No N20 flow 14 4 Slowly increase O2 control throughout range Ensure reading correspond to table below Set O2 Flow Observe N20 Flow Observe N20 M
48. ighting Power Supply Unit Mains Lead Lighting PSU Lighting Loom PSU 2 M6 X 10 SKT Cap SCR ST ST Pipe Back Bar Backbar Selectatec 2 station Safety Panel Electrical Panel Int Power CSA Pipeline Connector USA Reservoir Norgren 81 Quantity 1 1 1 2 2 1 1 1 1 1 PARTS LIST Fresh Gas Manifold Item N o A N gt co Part No 9000266 700650 054519 054515 0258 054524 9000443 Description Gas Block Outlet Connector Coupling Elbow 8mm Tube O ring 00 45 X 0 070 CS Elbow 10 mm Tube 22 mm Outlet Male Connector 82 Quantity PARTS LIST CORY NOY 7 NN S Gas Regulator Bar Assembly Item 1 2 3 4 5 6 11 12 13 14 Part No 800306 800305 800206 054528 054519 01007b 053207 800209 800208 800309 Description High Pressure Gas Block Air USA High Pressure Gas Block O2 USA Low Pressure Gas Block Air Stem Adaptor Coupling Screw M6 X 16 O ring G 1 8 Plug C W Low Pressure Gas Block N20 Low Pressure Gas Block O2 USA High pressure Gas Block N2O 83 Quantity 1 2 1 PARTS LIST Auxiliary Outlet assembly Item Part No Description 1 9000277 Auxiliary Outlet Block 2 34410 O2 Outlet DISS 1240 3 0408 Dowty Seal G 1 4 4 053207 Plug G 1 8 complete with O ring 5 054515 Elbow 8 mm Tube 84 Quantity N N PARTS LIST Backbar Manifold Assembly 3 Station Selectatec
49. iled below Do not use excess force A Disconnecting tubing from connector Push in the tube and the connector end piece A Hold the end piece A in place Pull the tube out to disconnect Fitting tubing to connector Push in the tube as far as possible mil Do not use excessive force The connector end piece A will also move inwards Pull the tube carefully outwards The end piece A will be pulled outwards to the locked position tes 55 Gas System Components Rear view p wo DA XP com ll PO P LA d CY zr eT il l e ar SA DITT Ol SI 4 O i Pan TE i PI ne g C j LO ms R Qa DER CGO outlet optional front position also shown Oxygen flush button High pressure regulator High pressure block Low pressure block Test point low pressure block Fresh gas pressure relief valve Pipeline supply inlet block 10 11 12 13 15 16 Auxiliary outlets Secondary regulator Test point primary regulator Vaporizer Manifold block Warning whistle Oxygen failure visual indicator Gas delivery switch Therapy Flowmeter SERVICING PROCEDURES O2 Circuit March 2007 onwards Reservoir To O2 Flowmeter To N2O Flowmeter TA T OR fA Supply in to Warning i _ 02 N20 Whistle C C Gas Block Non return Valv
50. in this Prima SP2 Service Manual available only to Penlon trained engineers Mechanical AHD System Additional servicing for the mechanical AHD system only Function Test At 6 month intervals see section 6 7 Additional Servicing At 12 month intervals Secondary Regulators check pressure setting Gear linkage inspect Service Tools 015067 Regulator Spanner Regulators manufactured by Gas Arc 800612 Flow setting tool 53 9 2 Ancillary Equipment 9 2 1 Sigma Delta Vaporizer Follow the instructions given in section 8 of the user instruction manual These include Every 6 months Function test and calibration test Every 10 years Major overhaul if unit to be used beyond 10 years Note Halothane vaporizers major overhaul required at 5 years On vaporizers with interlock test the function of the interlock system during the vaporizer calibration test 9 2 2 Monitor Folow the service recommendations detailed in the monitor user instruction manual 9 2 3 AV S Ventilator If the anaesthetic machine was supplied with an AV series ventilator refer to section 7 of the ventilator user instruction manual for servicing requirements These include 6 months Inspection and Function Check 12 months Replace bellows Replace O seals and drive gas inlet filter etc Additional component replacement 24 and 48 months 9 2 4 Anaesthetic Gas Scavenging System Follow the service recommendations d
51. ined engineer as part of the commissioning of a new machine Regular Function Test Full function testing should be carried out at six month intervals by a Penlon trained engineer or other persons certificated by Penlon Limited Procedures for servicing and repair are described in subsequent sections in this Service Manual Read the procedure carefully before carrying out each test noting references to machine specifications and equipment Perform these tests in sequence Equipment Required No complex test equipment is required for the series of tests described below Leak tests Apply a Leak Test Spray or a diluted solution of soap in water to the suspect connector not on high pressure cylinders and check for a stream of bubbles at the joint Flow rates Check with a respirometer or other suitable flow measurement device Electrical circuits Check with a multi meter Pressure Check with a manometer 30 Safety Precautions WARNING Before commencing any test work ensure that all vaporizers are in the Off position Note that the OFF position may be indicated on the vaporizer as a 0 zero Refer to the vaporizer instruction manual WARNING During any test procedure the release of Nitrous Oxide or anaesthetic vapours into the working environment must be controlled Connect the machine to an approved anaesthetic gas scavenging system AGSS WARNING Do not contaminate pipeline connections cylinder
52. ing gj 043 O ring 9 PARTS LIST Prima SP2 3 Preventive Maintenance Kit 12 Month Service Part No 57289 Kit Contents Part No 462526 3 946 37 947 37951 022533 041115 016 0762 043 Qty Component Description Hose Backbar Outlet to CGO not shown Hose Support Seal Support Split O ring Dzus Clip O ring Selectatec 2 station shown Bodok Seal Filter Yoke and Pipeline O seal Safelock N OO OO RA 0226 O seal Hose assembly Backbar outlet to CGO not shown 37947 d Seal Support Split O ring 0762 016 Filter Yoke and pipeline Bodok Seal 74 PARTS LIST Prima SP2 3 Preventive Maintenance Kit 24 Month Service Part No 57290 Kit Contents Part No 462526 37946 37947 37951 041115 016 400224 400262 0762 0508 36247 01057 36075 0691 043 011017 022533 0226 0293 Qty 1235 m 4 ONO NN OO OO OO OO O1 OO fF FA Component Description Hose Backbar Outlet to CGO not shown Hose Support Seal Support oplit O ring O ring Selectatec Bodok Seal Flowmeter Bobbin Metal with Filter Flowmeter Bobbin Metal without Filter Filter Yoke and Pipeline Filter Flowmeter Flowmeter Bobbin Tube Seals Washer Shock Washer O seal Flowmeter O seal Safelock Tubing Sample Block Dzus Clip O seal Hose Assembly backbar to CGO outlet not shown O seal Flowmeter Tube 016 Bodok Seal
53. lace cylinder Fit replace seal Replace as necessary Replace as necessary Ensure correct gas cylinder is attached Check index pins not loose or damaged Replace gauge Replace gauge Open flowmeter and empty system Replace plunger O seal assembly FAULT FINDING Component Pipeline supply hoses and inlet blocks Flowmeter units Symptom Pressure gauge reads zero when connection to supply made Insufficient free flow Float stays at bottom of tube when control valve opened 41 Possible Fault Loose connections Tighten leaking joints DO NOT use excessive force Defective gauge Faulty probe or hose Blocked filter Pipeline supply defective Blocked filter Pipeline supply defective No gas supply Pressure reduction valve defect Pipeline supply defective Control knob loose on shaft Remedy Test for leaks Replace gauge Replace as necessary Replace as necessary Contact hospital engi neer Replace as necessary Contact hospital engi neer Check cylinder pipeline connections See instructions under component group See instructions under component group Tighten FAULT FINDING Component Flowmeter units Mechanical AHD sys tem Symptom Float stays at bottom of tube when control valve opened N20 flowmeter Restricted flow through flowmeter Control valve opening does not achieve expected flow Incorrect O2 co
54. ly and shows GREEN when the supply is at working pressure and RED if the pressure falls WARNING Gas supply failure systems within the anaesthetic machine will not necessarily operate as indicated during any procedures that are outside the scope of the indications for use of the machine see section 2 Machine set to deliver Air only When the machine is operated with an Air flow only note that there may still be retained oxygen in the system and that the visual O2 alarm will continue to indicate green even though oxygen is not being delivered 3 3 5 Mechanical AHD A mechanical link between the oxygen control valve and a needle valve in the nitrous oxide flow ensures that the machine delivers a fresh gas mixture with a minimum 30 43 oxygen irrespective of the flow of nitrous oxide set by the anaesthetist With the nitrous oxide control valve fully open the oxygen and nitrous oxide flows are then both controlled by the oxygen control valve See section 3 4 for a full description 3 3 6 Low Pressure Gas Tubing Diameter indexed tubing is used for the low pressure gas system see section 4 DESCRIPTION 3 4 Mechanical AHD Anti Hypoxic Device 3 4 1 Introduction The Mechanical AHD is housed within the flowmeter module and comprises a gear linkage between the oxygen control valve and a needle valve in the nitrous oxide flow The system controls the relative flow rates of oxygen and nitrous oxide A predetermi
55. mixtures to the patient and must only be adjusted by a Penlon trained Engineer or other persons certificated to do so by Penlon Limited Incorrect adjustment of the MAHD could result in the failure of this device and the loss of hypoxia protection The oxygen control is restricted to prevent the needle valve from fully closing This ensures a minimum flow of oxygen at all times while the machine is switched on This small flow of oxygen is known as the Basal Flow DO NOT attempt to fully close the oxygen flow to zero DO NOT overtighten Flow Control knobs for the other gases as this will reduce the life of the needle valves 1 Ensure that all flowmeter control valves are shut Disconnect all the pipeline gas supplies 2 Remove all gas cylinders 3 Check each cylinder yoke for security of attachment and free movement of the clamp bar 1 and clamp screw 2 Check Pin Index system pins 3 are secure and undamaged 4 Check that a seal 4 is in place and undamaged in each cylinder yoke 5 Attach each gas cylinder to its appropriate yoke ensuring full engagement of the Pin Index system Note Use full bottles only 6 Turn on the Oxygen Cylinder Check that the Cylinder pressure is indicated on the Oxygen Cylinder pressure gauge in a smooth sweeping movement Check that all other gauges indicate zero pressure Check that there is no flow of gas indicated on Cascade O2 flowmeter 50 75 ml min the Oxygen flow tube
56. n be turned on 3 Selectatec Manifold check all pillar valves open and seal correctly Check pillar valve inserts sit proud or flush with the pillar valve A sunken pillar valve insert denotes failure of the internal spring 6 8 2 Cagemount Vaporizer if fitted Vaporizers fitted with the Cagemount tapers have the male taper Inlet Port 3 on the left and the female taper on the right as viewed from the front of the vaporizer Two M6 studs with nuts washers and a clamp plate 4 are provided to fix the vaporizer to the anaesthetic machine NOTE Some international standards demand that this type of vaporizer should only be used on machines with a single mounting station In addition use a safety clip Catalogue No 52275 to retain the Cagemount taper cones in position on the vaporizer Fitting the Vaporizer 1 The taper cone joints must be engaged axially and not sideways loaded Use the shims 5 provided so that the distance from the back bar to the taper joint can be adjusted by adding or removing shims from the vaporizer 2 The cone joints should then be lightly smeared with an Oxygen compatible lubricant such as Fomblin The taper joints must be engaged by applying axial pressure and the fixing nuts tightened Check all joints for gas tightness 3 Check flexible hoses for security of attachment and integrity 37 FUNCTION TEST 6 9 Reduced Pressure Gas Circuit Leakage Back Bar Leak Test and P
57. ncentra tion 42 Possible Fault Gas delivery switch left in off position Gear linkage loose on O2 or N2O primary valve shaft Gear linkage loose on valve shaft N2O flow limited by N2O control valve Secondary regulators out of alignment Gear linkage loose on valve shaft Remedy Turn on gas delivery switch Reset gears and tight en Reset gears and tight en Open N20 control valve Check and reset sec ondary regulators Replace if necessary Reset gears and tight en FAULT FINDING Component Symptom Flowmeter unit Float sticks at above zero reading when con trol valve closed Float level unstable after start up 43 Possible Fault Dirt in tube Build up of electrostatic charge Flowmeter unit not ver tical Upper float retaining peg not centralised or moulding flash not removed Worn needle valve Pressure reducing valve defect Flowmeter unit not ver tical Remedy Remove tube and clean Check earthing con tacts at bottom of flowmeter tubes Increase flow rate sharply to break charge then close valve Ensure machine is on level surface Remove flow tube and retaining peg Clean off moulding flash and re position retaining peg Replace complete valve and or seat assembly See instruction under component group Ensure machine is on level surface FAULT FINDING Component Symptom Flowmeter unit Restricted flow thro
58. ndexed to prevent inadvertent incorrect installation All floats indicate flow rate in line with the upper surface as shown below Read flow at this level Each flow control valve is positioned directly underneath the flow tube assembly to which it corresponds and the control knob is colour coded for the gas which it controls The oxygen flow control knob is made physically distinguishable from the other flow controls for identification by touch in accordance with ISO standards When fitted air and carbon dioxide flowmeters are always installed in the inner positions on the flowmeter assembly These positions are blanked out if air or carbon dioxide are not specified for the machine The gas delivery switch positioned on the front panel controls the supply of oxygen and must be in the ON position for normal operation of the machine Flow control of each gas is achieved by a needle valve comprising a polished stainless steel needle mounted concentrically in a common manifold block To minimise wear and material pick up the needle seat is manufactured from silver The flow control knob is turned counter clockwise to increase the gas flow CAUTION Needle valves are designed to seal with light torque and may be damaged if tightened excessively DO NOT USE EXCESSIVE FORCE 3 6 2 Dual Cascade Flow Tubes The flow of gas through dual cascade system flow tubes always flows through the low flow tube first The high flow t
59. ned minimum oxygen concentration of 30 3 in the oxygen nitrous oxide mixture is maintained over the flow range to prevent delivery of a hypoxic mixture 3 4 2 Gas Delivery Switch The Gas Delivery Switch 1 operates on the oxygen supply and must be in the On position for normal operation of the anaesthetic machine The switch consequently controls the supply of all gases provided with a gas cut off triggered by a predetermined pressure level within the oxygen supply see section 3 3 1 A whistle oxygen failure warning whistle will sound briefly whenever the gas delivery switch is turned on or off Note that the whistle functions continuously if the oxygen supply fails see section 3 3 2 NOTE The switch also controls the electrical supply to the ventilator and optional flowmeter lighting unit 3 4 3 Gear Linkage and Nitrous Oxide Control Valves A gear linkage connects the oxygen control knob on the flowmeter module and a needle valve in the nitrous oxide flow This linkage limits the flow of nitrous oxide relative to the flow of oxygen set by the user Note that this needle valve acts as the primary nitrous oxide valve and is actuated only by movement of the oxygen control The nitrous oxide control knob on the flowmeter module operates a secondary needle valve in the nitrous oxide flow It is positioned downstream of the primary valve and therefore is used only to restrict the flow already set by the primary
60. ng connector 5 5 To refit reverse the above procedure and then carry out a full function test see section 6 Yoke Filter Remove and Refit CAUTION Ensure that any residual gas in the machine is exhausted before commencing the dismantling procedure 1 Remove all cylinders and disconnect all pipeline supplies 2 Remove the Bodok seal 1 3 Unscrew the yoke insert 2 4 Use a suitable rod to carefully remove the filter 3 5 To refit reverse the above procedure Fit a new Bodok seal Function test the machine see section 6 67 SERVICING PROCEDURES 9 11 Selectatec Compatible Manifold Block 1 The valve capsule top O seal arrowed A on the illustration must be regularly changed to prevent the possible occurrence of leaking Check for splitting perishing and expansion and also check if the seal is sticking to the vaporizer To ensure satisfactory performance a ALWAYS perform a leak test before using the manifold block or after changing the vaporizer b Replace these O seals regularly maximum 6 months interval DO NOT apply grease or lubricant Overhaul CAUTION Ensure that any residual gas in the machine is exhausted before commencing the dismantling procedure Removal 1 Remove all cylinders and disconnect all pipeline supplies 2 Remove the front cover see section 9 6 to gain access to the manifold block 3 Disconnect the inlet and outlet fresh gas hoses 4
61. on Science Park Barton Lane Abingdon OX14 3PH UK Technical Support Tel 44 0 1235 547076 Fax 44 0 1235 547062 E mail technicalsupport penlon co uk UK Sales Tel 01235 547036 Fax 01235 547023 E mail uksales penlon co uk International Sales Tel 44 0 1235 547001 Fax 44 0 1235 547021 E mail export penlon co uk
62. ondary Pressure Regulator A second stage regulator reduces the pressure supplied to each flowmeter control see section 4 The fitment of a secondary regulator for oxygen and nitrous oxide enhances the performance of the mechanical AHD system Secondary regulation of the air supply aids the stabilisation of the output at the flowmeter Prima SP2 Models built from March 2007 see Appendix for earlier models Three gas machine with dual cascade oxygen and nitrous oxide flowmeters Flowmeter Assembly Pneumatic pressure Gas cut off valve Flowmeter Source normally open Vaporizer Pressure gauge Reservoir Oxygen flush valve Pressure regulator Pneumatic on off Non return valve Pressure relief valve switch Power take off point Audible alarm Flow control valve or test point variable Visual indicator Restrictor Filter DESCRIPTION 3 3 Gas Supply Safety Devices 3 3 1 Gas Supply Cut off Device A gas cut off device triggered by low oxygen supply pressure cuts the supply of nitrous oxide and carbon dioxide if fitted The cut off operates when the oxygen pressure falls to 186 14 kPa 27 2 psig Gas supplies are reinstated only when the oxygen supply pressure rises above 227 14 kPa 33 2 psig 3 3 2 Oxygen Supply Failure Warning Whistle A whistle gives an audible warning when there is a reduction of oxygen supply pressure Operated solely by the remaining oxygen in the
63. onitor L min L min O2 0 25 0 5 0 67 27 33 0 5 1 0 0 35 27 33 0 8 1 6 2 2 27 33 1 5 3 0 4 1 27 33 3 0 6 1 8 1 27 33 Denotes Cascade machines only 15 15 4 15 5 15 6 15 7 Additional Mechanical AHD Checks Partially close N2O control Ensure N20 flow is reduced and O2 increases Fully open N20 control Set O2 flow at 8 l min Gradually decrease O2 control ensuring readings correspond to table above When fully closed basal flow should be 50 75 ml min Cascade flowmeter 150 50 ml min single tube flowmeter Fully close N2O control Refit flow tube cover 51 SERVICE SCHEDULE 16 Check Back Bar Assembly Selectatec fitting only 16 1 Replace selectatec O rings 16 2 Replace vaporizer locking springs annual service 16 4 Ensure pillar valves protrude check for positive spring function 16 5 Gently twist valve body and ensure valve is secure 17 Fresh Gas Pressure Relief Valve 17 1 Occlude CGO Outlet with a manometer 17 2 At 10 l min PRV relieves at 41 kPa 10 18 Leak Test From Flowmeter to Common Gas Outlet 18 1 Occlude CGO with manometer 18 2 Set flow to maintain a pressure of 20 kPa 3 psi If flow is greater than 200 ml investigate and rectify internal leak 18 3 Repeat this check on all stations with and without vaporizers fitted and with vaporizers On and Off 18 4 Remove manometer from CGO 19 Auxiliary Outlets 19 1 Check auxiliary outlets for minim
64. ove Rotameter control knobs Remove manifold block cover Inspect the gears for alignment wear and damage Reset or replace if required lightly lubricate with Molykote BG87 Ensure grub screws are tight Refit manifold block cover and Rotameter control knobs Ensure that basal flow is at the same rate as noted in 6 1 Gas Delivery Switch Inspection Set a flow of 2 l min O2 and 2 l min N2O Operate the Gas Delivery switch to the OFF position and ensure both flows go to zero oet the Gas Delivery switch to ON and ensure the flows are correctly re instated Set O2 and N20 flows back to minimum Ensure that flowmeter backlight operates if fitted as switch is operated Ensure that ventilator operates if fitted as switch is operated 49 SERVICE SCHEDULE 8 1 8 2 8 3 8 4 8 5 8 6 9 1 9 2 9 3 9 4 9 5 9 8 9 10 9 14 9 15 9 16 9 17 9 18 10 10 2 10 3 10 4 10 7 11 Check Regulators Set relevant gas flow to 5 litres min Check primary regulator outlet pressures refer to section 4 Specification Replace Primary regulators 5 year service Check secondary O2 and N2O regulator outlet pressures refer to section 4 Specification Secondary regulator pressures can be adjusted as required to obtain MAHD readings Note Maximum flow rates MUST be available from the flow tubes Check secondary Air regulator refer to section 4 Specification Operate the gas delivery switch OFF then ON En
65. pecial operating system Check functioning of flowmeters Check function of Mechanical AHD Check correct connection and functioning of the vaporizers Check functioning of oxygen flush Check leak rate of low pressure gas system Check the integrity of the patient circuit Test the alarm system Refer to Section 5 in the User Manual for further information 12 19 14 Ancillary equipment Check operation of the AGSS Check functioning of ventilator including disconnect alarm Check that the oxygen analyser and other patient monitoring equipment functions correctly Refer to the relevant user manual for further information 20 PRE USE CHECKS 5 2 Pre use Checks Gas Supply 5 2 1 Gas Pipeline Supplies Oxygen supply 1 Connect the oxygen pipeline hose only Check that the correct pressure gauge reading is obtained 2 Turn on the Gas Delivery switch 1 Check that the warning whistle sounds briefly and that the correct basal flow of oxygen is delivered see section 3 8 3 Open both oxygen and nitrous oxide flowmeter valves Check that flow is only shown in the oxygen flowmeter 4 Close both valves Turn off the Gas Delivery switch Check that the warning whistle sounds briefly and that the oxygen basal flow is stopped Nitrous Oxide supply 5 Connect the Nitrous Oxide pipeline hose Check the gauge reading Turn on the Gas Delivery switch 1 Check for a flow of nitrous oxide when the flowmeter n
66. pipeline combinations can be added to the basic specification of oxygen and nitrous oxide cylinder and pipeline supply For example two extra gas cylinders choose from one additional oxygen one additional nitrous oxide one air and one extra pipeline supply Air Cylinder Yokes The yokes are rear mounted and conform with ISO standards for pin index fitting To ensure that only cylinders of the appropriate gas may be installed the yokes are designed so that the retaining latch cannot be closed unless the index pins are fully engaged Pipeline Inlets 1 Up to three rear mounted pipeline gas inlets can be fitted Pipeline supply hoses are connected by non interchangeable screw threaded unions DISS diameter indexed safety system Filters To prevent dirt entering the gas system cylinder yokes and pipeline inlets are fitted with filters Gas Inlet Block Each individual cylinder or pipeline supply is routed through a separate gas block Each gas block has an integral high pressure gauge tapping for direct mounting of a pressure gauge and a non return valve to prevent back flow of gas In addition cylinder gas blocks have a diaphragm pressure regulator to reduce the pressure of the compressed gas supply and a factory set pressure relief valve This prevents pressure build up under the diaphragm should any leakage develop across the reducing valve seat Sec
67. r inlet and a 22 mm Safelock taper at the other end This should be connected to the common gas outlet of the anaesthetic machine Check all connections for gas tightness 5 5 4 A200SP Absorber Always follow the pre use check procedures given in the instruction manual supplied with the absorber The use of an oxygen monitor and a carbon dioxide analyser is highly recommended when using any partial rebreathing anaesthetic system A200SP Connections Inspiratory connector Expiratory connector Bag connector Inlet from DRIVE GAS outlet on ventilator control unit Inlet fresh gas hose from Common Gas Outlet Exhaust outlet from APL Valve connect to Anaesthetic Gas Scavenge System 7 Oxygen monitor sensor 8 Outlet sample line to Pressure Monitor Port on ventilator 9 Interface cable Bag Vent switch and spirometer connects internally to Prima SP On Off Switch interface then to connector on ventilator control unit rear panel AON own 25 PRE USE CHECKS O1 Note 1 AV S has spirometry and oxygen monitor 2 Interface cabling is shown for Prima SP2 On Off switch and A200SP a mom I m o dec A 12 T9 14 13 16 Tf Bag Vent switch Bellows 18 Drive Gas Inlet Ventilator Ventilator Control Unit 19 Drive gas Outlet ventilator control unit to bellows Outlets to Anaesthetic Gas Scavenging System AGSS 20 Outlet Exhaust Valve Bacterial Filter
68. rations The range has been designed to give a wide choice of configurations and accessories as follows Gas supplies Up to three gases Oxygen nitrous oxide and air with pin index cylinder yokes and provision for up to three pipeline supply inlets Vaporizer mounting systems Backbar manifold for Selectatec compatible vaporizers Anti hypoxic Device AHD The mechanical AHD system is designed to minimise the risk of a hypoxic mixture reaching the patient see section 3 3 DESCRIPTION 3 1 General Construction Frame The machine has a cast aluminium base extruded aluminium uprights with aluminium and plastic panels Mobility Four castors are fitted with a brake on each of the front castors The castors are five inches diameter A footrest is built into the front of the machine and to aid manoeuvrability two handles are provided Mounting posts and brackets A mounting system is built into each side upright to allow the use of pole mount brackets V brackets and ventilator mounting brackets The pole mount upright can be used to mount an A200SP Absorber assembly Work surfaces The work surface has raised edges to retain instruments vials etc A pull out writing tablet is mounted under the work surface 3 2 Gas Circuit Gas Circuit Schematic A gas circuit schematic is shown on the following page All available gas supply options are shown Gas Supplies A variety of cylinder and
69. ressure Relief Test Connect a suitable test pressure gauge Manometer to the Common Gas Outlet CGO using suitable tub ing and connector Ensure all vaporizers attached to the machine are turned OFF Using the Oxygen Flow Control Valve raise the pressure in the circuit slowly until a flow of 10 L min is set Check that the Pressure Relief Valve PRV mounted under the gauge cover on the right hand side begins to leak in the range of 37 to 45 kPa Do not exceed this pressure Alter the pressure by reducing the Oxygen Flow Rate until the displayed reading on the test gauge is 20 kPa 150 mmHg The maximum permissible flow to maintain the above pressure is 200 ml min If a higher flow rate is required to main tain a pressure of 20 kPa 150 mmHg there is a leak in the system that must be fixed Use soap solution to detect leak repair and repeat above tests 5 6 amp 7 Repeat the above tests 5 6 amp 7 with all fitted vaporizers turned on Test one at a time to check gas tightness of each individual vaporizer A leaking vaporizer must be withdrawn from use Return the unit to your supplier 38 6 10 Emergency Oxygen Flush Control Test Ensure all flowmeter control valves are turned off Oxygen Cylinder is turned on and Oxygen Pipeline is unconnected from the wall outlet Depress the Emergency Oxygen Flush O2 Flush button Check that the delivered flow rate is between 35 75 L min
70. rmation WARNING Vaporizers must always be mounted never used free standing Free standing vaporizers may be accidentally tipped resulting in excessive and uncalibrated volumes of anaesthetic drug entering the breathing system Do not install or connect any vaporizer of any description between the CGO and the breathing system unless it is specifically designed for such use This allows the oxygen flush flow to pass through the vaporizer and severe overdosage may result 5 3 3 Selectatec Mounting System Dependent on choice of backbar manifold system up to three Selectatec compatible vaporizers may be fitted To install the vaporizer carefully offer the vaporizer up to the manifold Check that the gas connection ports on the vaporizer are aligned with the valves on the manifold Carefully lower the vaporizer onto the manifold and lock the vaporizer into position by clockwise rotation of the locking lever through 909 NOTE Do not use excessive force to lock the vaporizer onto the manifold Damage to the locking fastener will result CAUTION To prevent damage to the locking shaft ensure that the gas connection ports are aligned with the valves on the manifold and are correctly engaged before tightening the locking lever 23 5 3 4 Selectatec Compatible Vaporizers with Interlock WARNING Only vaporizers with the Selectatec compatible interlock function will interlock if installed on a two station or three st
71. rotating and stable Close the Air Flowmeter control gently until no gas flows FUNCTION TEST 6 7 Gas Safety Devices Mechanical AHD 1 Gas Delivery Switch 1 ON Fully open the Nitrous Oxide Flowmeter and check that there is no flow of gas indicated on the N2O flow tube Fit an Oxygen Analyser to the output of the Common Gas Outlet Refer to the table below and check Oxygen concentration at the oxygen flows specified Adjust the Oxygen Flowmeter control only Do NOT adjust the N20 flowmeter Note The flow rates for N2O are given as a guide only O2 Flow 02 N20 Flow L min in O2 N20 mixture 0 25 27 33 0 5 0 67 0 5 27 33 1 0 1 35 0 8 27 33 16 21 1 5 27 33 3 0 4 1 3 0 27 33 61 81 Turn OFF the Gas Delivery Switch Check that both gas flows are stopped Turn ON the Gas Delivery Switch Check that both flows are reinstated Partially close the Nitrous Oxide flowmeter to check that it limits the Nitrous Oxide flow Check that the reducing flow gives an increased Oxygen concentration Fully open the Nitrous Oxide flowmeter Close the Oxygen flowmeter control valve gently until the mechanical stop engages Check that the same corresponding values of Oxygen and Nitrous Oxide flows are achieved as tabled above Ensure that when the Oxygen flow is at its basal level all Nitrous Oxide flows have ceased Check that only the Oxygen Basal Flow is indicated on the flo
72. s must be replaced immediately Should such a repair become necessary it is recommended that a request for service advice be made to the nearest Penlon accredited agent This device and any of its constituent parts must be repaired only in accordance with written instructions issued by Penlon Limited and must not be altered or modified in any way without the written approval of Penlon Limited The user of this equipment shall have the sole responsibility for any malfunction which results from improper use maintenance repair damage or alteration by anyone other than Penlon or its appointed agents USA and Canadian Federal Law restricts the sale and use of this device to or on the order of a licensed practitioner Statements in this manual preceded by the following words are of special significance WARNING means there is a possibility of injury to yourself or others CAUTION means there is a possibility of damage to the apparatus or other property NOTE indicates points of particular interest for more efficient and convenient operation Always take particular notice of the warnings cautions and notes provided throughout this manual T WARNINGS AND CAUTIONS The following WARNINGS and CAUTIONS must be understood read and before using this anaesthetic apparatus WARNINGS This apparatus is designed for use only with non flammable anaesthetic agents It must not be used with or in close proximity
73. sure regulator returns to set value Any regulator that cannot be correctly adjusted or does not return to set value should be replaced High Pressure Leak Checks Turn OFF and drain all gases from machine Unplug all pipelines from wall outlets Fit all cylinders if not fitted but do not turn on Remove 8 mm O2 pipe from output of cut off block This is the O2 Basal flow feed to the Rotameter Blank the 8 mm O2 Connector from which you have just removed the tubing with the 8 mm blanking plug from your test case Turn on O2 oylinder Turn ON on off switch There should be no basal flow indicated on flow tube Turn on N2O and Air cylinders Turn off O2 Air and N2O Oylinders Check High Pressure for leaks on all gases maximum allowable leak rate O2 and Air 500 kPa in a 2 minute period N20 200 kPa in a 2 minute period Turn off O2 cylinder and drain Oxygen from system Turn OFF on off switch Remove blanking plug and connect 8 mm O2 tube back into connector Turn on O2 oylinder Turn ON on off switch Check that the Oxygen basal flow has been re instated with the O2 Rotameter fully clockwise Check all other Rotameters are fully clockwise Check Common Gas Outlet Check Safelock O ring replace if necessary Replace Safelock O ring annual service Replace O2 flush valve complete with O rings x 2 and seal O ring x 1 4 year service Replace flexible hose from Manifold PRV block to CGO manifold annual service C
74. t either the fully open or fully closed positions Open cylinder valves slowly to avoid damage to pressure reducing valves Ensure that cylinder valves are at least one full turn open when in use Under no circumstances should anaesthetic agents be used for cleaning purposes After use always disconnect the machine from the piped gas supply and or close the gas cylinder valves Mechanical AHD system The oxygen flow control is restricted to prevent the needle valve from fully closing This ensures a minimum basal flow of oxygen DO NOT attempt to close the flow to zero Do not overtighten Compressed gas supplies must be clean and dry When the auxiliary gas outlets are in use on a machine with cylinder supply only or if the pipeline supply is not in use check flow rate requirements and ensure that adequate back up cylinders are available 2 PURPOSE The Prima SP2 anaesthesia workstation range is intended to provide controlled concentrations and flows of anaesthesia gases into a patient breathing system from where the anaesthesia ventilator and breathing circuit will then deliver this fresh gas mixture to the patient Use the Prima SP2 in conjunction with anaesthetic vaporizers breathing hoses and patient connection fittings which comply with the relevant ISO standard or equivalent Depending upon the patient circuit selected the machines can be used in open semi open semi closed or closed circuit configu
75. to flammable anaesthetic agents due to a possible fire or explosion hazard Exterior panels must not be removed by unauthorised personnel and the apparatus must not be operated with such panels missing On machines with an electrical power supply there is a possible electric shock hazard No oil grease or other flammable lubricant or sealant must be used on any part of the machine in close proximity to medical gas distribution components There is a risk of fire or explosion When attaching cylinders of medical gases ensure that the machine yoke and cylinder faces are dust free and clean and that the sealing washer provided is in position between the cylinder valve and the yoke Tighten the yoke securely before opening the cylinder valve Dust and dirt presents a fire hazard in the presence of high pressure gas Leakage of high pressure gas can cause serious injury Anaesthesia apparatus must be connected to an anaesthetic gas scavenging system AGSS to dispose of waste gas and prevent possible health hazards to operating room staff This requirement must be observed during test procedures as well as during use with a patient Prima SP machines must only be used with Sigma Delta vaporizers or other vaporizers approved by Penlon Limited installed by means of the Selectatec system 10 11 Free standing vaporizers may be accidentally tipped resulting in excessive and uncalibrated volumes of anaesthetic dr
76. turn the flow to minimum Attach a pressure gauge to the nitrous oxide regulator test point 5 Set a flow of 5 L min nitrous oxide Reset the N2O secondary regulator to the figure given in the table To increase output turn the regulator cap 6 slowly clockwise To decrease output turn the regulator cap fully anti clockwise then clockwise to the correct setting Return the flow to minimum Turn the Gas Delivery Switch to OFF Check the oxygen basal flow see section 9 7 1 Check oxygen concentration see section 9 7 2 66 CO DIG SS EP i fer me 2 HET AH MON MANN HILL I Finn Il I 8 c UN Le I gt a ETT ETT 4 6 Secondary regulators Pressure output at 5 L min flow Oxygen and Nitrous Oxide 152 241 kPa 22 35 psi Air 207 283 kPa 30 41 psi SERVICING PROCEDURES 9 10 High Pressure Cylinder Gas Block Remove and Refit CAUTION Ensure that any residual gas in the machine is exhausted before commencing the dismantling procedure 1 Remove all cylinders and disconnect all pipeline supplies 2 Atthe rear of the machine remove the two screws 1 at the rear of the block to be removed Refer to 9 6 2 if necessary 3 Remove the screws 2 at the rear of the adjacent gas block 4 At the front of the machine carefully pull the blocks 3 and 4 from the machine Separate the blocks detach the block 4 from the tubi
77. ty capsule valve fails to operate correct ly Leaks at joint between manifold and valve seating Valve cuts flow of nitrous oxide as required but does not restore it 45 Possible Fault Loose manifold or vaporizer retaining screws Missing O seals Damaged or worn gas valves Damaged or worn O seals or seal faces Damaged or worn lock ing system Oxygen supply not turned on Mechanical AHD gas delivery switch left in Off position Faulty safety capsule valve Valve shuttle or seals defective Loose valve retaining SCrews Worn or damaged O seals Vent port blocked Loose valve Worn O seals Valve shuttle or seals defective Remedy Tighten Replace O seals Replace valve Replace as necessary Replace components as necessary Turn on supply Turn on gas delivery switch Replace valve Fit replacement cap sule valve Tighten Replace seals See instructions under component group Tighten retaining screws Replace seals Fit replacement valve FAULT FINDING Component Symptom Warning Whistle Leakage at whistle Whistle continually sounds when oxygen on Whistle fails to sound Pressure relief valve fresh gas circuit Leakage through valve Relief pressure too high Relief pressure too low 46 Possible Fault Loose connection Faulty whistle Faulty whistle Low pressure in circuit Faul
78. ty whistle Low pressure in circuit High pressure in circuit Faulty valve Faulty valve Remedy Tighten DO NOT use excessive force Replace whistle Replace whistle See instructions under component group Replace whistle See instructions under component group Reduce pressure Check for blockage in downstream circuit Replace complete valve Replace complete valve FAULT FINDING Component Symptom Emergency oxygen Valve does not operate flush Low Oxygen flow less than 35 l min Leaks around control button O2 flow into breathing circuit or atmosphere valve does not shut off flow 47 Possible Fault No oxygen supply Defective valve Low oxygen supply pressure Worn valve seals Incorrect adjustment of valve shaft Incorrect control jet Worn valve seals Worn valve seals Incorrect adjustment of valve shaft Defective valve Remedy See instructions under component groups Replace valve See instructions under components group Fit new seals or replace valves as nec essary Replace valve Replace control jet Fit new seals or replace valve as neces sary Replace valve Replace valve Replace valve FAULT FINDING Component Electrical power supply Symptom Machine dead 48 Possible Fault Mains supply socket Faulty on off switch Mains supply faulty Remedy Check supply plug ON
79. ube should not show any flow until more than 1 L min is set At flows above 1 L min the high flow tube reading indicates the rate of flow for that gas 3 6 3 Auxiliary Oxygen Flowmeter An auxiliary oxygen flowmeter 1 is mounted to the left of the machine flowmeter bank Flow range 0 10 L min z B BOOOL B _ a DESCRIPTION 3 Vaporizers CAUTION Read the instruction manual supplied with the vaporizer before clinical use 3 7 1 Vaporizer Mounting Systems Selectatec compatible vaporizers for the administration of volatile anaesthetic agents can be mounted on the compatible universal backbar WARNING Vaporizers must always be securely mounted and never used free standing Unmounted vaporizers may be accidentally tipped resulting in uncalibrated and excessive volumes of liquid anaesthetic drug entering the breathing system Vaporizers of any description must not be installed or connected between the Common Gas Outlet CGO and the Breathing System unless they are specifically designed for such use If this is done the oxygen flush flow will pass through the vaporizer and severe overdosage may result 3 7 2 Selectatec Compatible Vaporizer Selectatec compatible vaporizers e g the Sigma Delta with the Selectatec connector block may be mounted on a universal compatible back bar manifold Two and three station manifolds are available with each station fitted with two valve capsule assem
80. ug entering the breathing system Do not install or connect any vaporizers of any description between the Common Gas Outlet CGO and the breathing system unless they are specifically designed for such use If this is done the oxygen flush flow will pass through the vaporizer and may result in gross overdosage when the flush valve is operated The breathing system which conveys gases from the anaesthetic machine to the patient and disposes of expired gases is a vital part of the anaesthetic delivery system Because breathing systems require frequent cleaning and disinfection they are not a permanent part of the anaesthetic machine and therefore cannot be directly under the control of the anaesthetic machine manufacturer However we strongly recommend that only breathing systems which have been approved and authorised by Penlon for use with the Prima SP range should be employed This is particularly important when mechanical ventilation is employed When mechanical ventilation is employed the patient breathing system must be connected directly to an over pressure relief valve to prevent the possibility of barotrauma Always perform a pre use check of the machine including vaporizers ventilator circle absorber and monitors before clinical use Follow the pre use checklist see section 5 as a minimum requirement Many clinical incidents occur because of a failure to check for correct function The machine must not
81. ugh flowmeter Control valve opening does not achieve expected flow Float level falls after ini tial setting 44 Possible Fault Faulty cylinder pres sure reducing valve yoke or connections Faulty pipeline supply hoses or connections Blocked flowmeter filter Control knob loose on shaft Incorrect valve restric tion shimming Damaged valve seat assembly Reducing valve defect Pipeline supply defect Leak in upstream con nection Blockage in down stream gas circuit Not oxygen flowmeter Gas cut off units in operation or defective Worn needle valve and or seat Remedy See instruction under component group See instructions under component group Clean or replace lower bobbin assembly Tighten Reset valve shims Replace complete valve See instructions under relevant component group See instructions under component group Test for leaks Tighten leaking joints DO NOT use exces sive force Trace site of blockage and clear See instructions under component group Replace complete valve assembly FAULT FINDING Component Vaporizer mounting facility Selectatec compatible system Gas cut off unit Symptom Leakage at back bar manifold or vaporizer interlock joints Leakage from back bar Leakage from vaporizer connections Vaporizer difficult to remove No nitrous oxide No N20 or restricted flow Safe
82. um of 100 l min to free air 20 Final Gas Concentration Test 20 1 Carry out final gas concentration tests using the table below All machines Set O2 Set N20 Set Air O2 Concentration L min L min L min Check No 1 0 5 0 5 I 50 2 2 3 0 3 0 50 2 3 3 0 3 0 60 2 Additional check for machines with CO2 not available on US spec machines Set O2 Set N20 Set CO2 O2 Concentration L min L min L min 1 0 5 0 5 0 5 33 2 22 Electrical Safety Checks 22 1 Earth Continuity Max 0 2 ohms at 1 Amp or less 22 2 Insulation Resistance not less than 20 Meg Ohms at 340 500 Vdc 22 3 Earth Leakage Max 500 micro amps 22 4 Enclosure Leakage Max 100 micro amps 22 5 Check Flow tubes for continuity from glass tube to metal contact clip Approx 5 kohms 22 6 Fit Electrical Safety Test Label if requested to do so by hospital 23 Paperwork 23 1 Fill out appropriate service report 52 9 SERVICING PROCEDURES 9 1 Servicing The Prima SP2 range of anaesthetic machines must only be serviced by a Penlon trained engineer to the following service schedule Every 6 months Inspection and Function Check Every 12 months Annual service which includes routine replacement of seals etc as preventive maintenance At 3 years interval Pipeline hoses replace At 5 years interval Primary regulators replace Every 2 and 4 years Additional tests component replacement Details of these service operations are given
83. valve which itself has been determined by the position of the oxygen control knob Therefore for any oxygen flow set by the user the mixture delivered will still contain a minimum 30 3 oxygen even with the nitrous oxide control knob fully open As the nitrous oxide knob is progressively closed the oxygen content of the mixture increases to 100 3 4 4 Oxygen Basal Flow To allow the system to function correctly an oxygen basal flow is continuously supplied Single Flow Tubes 100 200 ml min Dual Cascade System Flow Tubes 50 75 ml min This basal flow can only be turned on and off by using the Gas Delivery Switch CAUTION The oxygen control is restricted to prevent the needle valve from fully closing This ensures a minimum oxygen basal flow DO NOT attempt to close the flow to zero Do not overtighten the knob 3 5 Pressure Gauges Pressure gauges 50 mm diameter are located on the front panel below the flowmeter bank The gauge for Air is positioned between oxygen and nitrous oxide Unused gauge positions are blanked out All pressure gauges are colour coded and labelled for the gases whose pressures they are indicating Cylinder gauges are marked CYLINDER Pipeline gauges are marked PIPELINE The gauges are calibrated in kPa x 100 DESCRIPTION 3 6 Flowmeters and Controls 3 6 1 All models he flowmeters mounted behind the perspex cover on the left hand side of the machine are length i
84. very Switch 1 to OFF Disconnect all pipeline and cylinder supplies Remove the front cover see section 9 6 Retighten the screws securing the gas blocks Reconnect the cylinder and pipeline supplies Attach a pressure gauge to the oxygen regulator test point 2 Set the Gas Delivery Switch to ON Set a flow of 5 L min Oxygen Reset the O2 secondary regulator to 172 kPa 25 0 psi To increase output turn the regulator cap 3 slowly clockwise To decrease output turn the regulator cap fully anti clockwise then clockwise to the correct setting Return the flow to minimum Attach a pressure gauge to the N2O regulator test point 4 Set a flow of 5 L min nitrous oxide Reset the N2O secondary regulator to 186 kPa 27 0 psi To increase output turn the regulator cap 5 slowly clockwise To decrease output turn the regulator cap fully anti clockwise then clockwise to the correct setting Return the flow to minimum Set the Gas Delivery Switch 1 to OFF Gear Linkage 12 13 Remove the flowmeter control knobs 6 screws 7 and control knob cover 8 Loosen the grubscrews and remove the O2 gear 9 and small N2O gear 10 62 4 HO Cx a A Ju Hi i TETTE NN Tr MON MAN AD l SERVICING PROCEDURES 14 Check the condition of the gears and grubscrews Replace with new components if necessary Clean all traces of Loctite from the grubscrews and apply n
85. w Pressure regulator Pressure relief valve Audible alarm Restrictor Gas cut off valve normally open Reservoir Pneumatic on off switch Flow control valve variable Flowmeter Vaporizer Oxygen flush valve Non return valve 4D OO AMO ml ese Power take off point or test point Visual indicator 99 APPENDIX APPENDIX 1 Product Classification and Labelling Terminology The terms Class 1 and Type B are defined in IEC 601 1 the standard for electrical medical equipment e This symbol denotes Type B equipment Type B equipment calls for a particular degree of protection against electric shock Class 1 equipment has additional protection such that metal parts of the unit that are accessible to the user e g the metal casing of the oxygen monitor unit cannot become live in the event of failure of the basic insulation of the electrical components within the unit This symbol denotes Refer to the User Manual N APPENDIX 2 Disposal at end of useful life risk assessment There are no risks associated with disposal of this product Follow your hospital local state and federal regulations Check the relevant user manual for information relating to disposal of major system components AVS ventilator Delta Vaporizer A200SP Absorber 100 C 0473 Cat No 52966 Doc No PR SP2 3 0108 SM January 2008 O Penlon Ltd 2008 All rights reserved Penlon Limited Abingd
86. w tubes Close the Nitrous Oxide Flowmeter and switch off the Gas Delivery Switch 36 HO 4e OC Oc A Oxygen Fail Cut off 8 10 11 Set the following flow rates Oxygen 5 L min N20 5 L min C Oz if fitted 500 ml min Turn Off the Oxygen Cylinder and observe that the Oxygen Cylinder pressure gauge indicates falling Oxygen pressure Check that the warning whistle Oxygen Fail Alarm sounds before the supply of oxygen is exhausted from the anaesthetic machine and that its duration is a minimum of 7 seconds Check that before the supply of Oxygen is exhausted from the anaesthetic machine that Nitrous Oxide flow is cut off automatically by the Oxygen Fail System Oxygen Fail Warning 12 13 14 Check that before the supply of Oxygen is fully exhausted that the visual indicator 2 has turned fully red Turn OFF all Flowmeters and turn ON the Oxygen cylinder so that only the Oxygen Basal Flow is indicated Check that the visual indicator 2 is showing fully green FUNCTION TEST 6 8 Vaporizers and Back Bar Manifold Assembly 6 8 1 Selectatec Compatible Vaporizer 1 Check that all the vaporizers are securely mounted on the manifold If a vaporizer is not secure check the condition of the locking shaft 1 2 On interlock vaporizers check that the interlock mechanism interlock bolt 2 of each vaporizer is working correctly i e only one vaporizer at a time ca
87. wmeter Cover Removal 9 7 Mechanical AHD System 9 8 Gas Control Valve Capsule Replacement 9 9 Secondary Regulators 9 10 High Pressure cylinder Gas Block 9 11 Selectatec Compatible Manifold Block 9 12 Flowmeter Tubes 9 13 Flowmeter Assembly 9 14 Oxygen Monitor Sensor 10 PARTS LISTS APPENDIX Product Classification and Labelling Terminology Disposal at end of useful life risk assessment iv 28 28 28 28 29 30 31 31 32 33 35 36 37 38 38 38 40 49 53 53 51 54 55 58 59 60 65 66 67 68 69 70 71 72 98 98 USER RESPONSIBILITY This anaesthetic machine has been built to conform with the specification and operating procedures stated in this manual and or accompanying labels and notices when checked assembled operated maintained and serviced in accordance with these instructions To ensure the safety of this device it must be checked and serviced to at least the minimum standards laid out in this manual A defective or suspected defective product must not under any circumstances be used The user must accept responsibility for any malfunction which results from non compliance with the servicing requirements detailed in this manual Additionally the user must accept responsibility for any malfunction which may result from misuse of any kind or non compliance with other requirements detailed in this manual Worn broken distorted contaminated or missing component
88. xiliary power sockets US CSA specification machines 110 120 VAC 60 Hz 1350 VA maximum Non US CSA specification machines 100 240 VAC 50 60 Hz 1100 2500 VA maximum Option 2 Auxiliary power outlets No internal power US CSA specification machines 110 120 VAC 60 Hz 1200 VA maximum Non US CSA specification machines 100 240 VAC 50 60 Hz 1000 2400 VA maximum Option 3 Internal power No power outlets Non US CSA specification machines only 100 240 VAC 50 60 Hz 100 VA maximum Fuses internal power T2AH ceramic 74 x 17 inch high breaking capacity fuses Power cable Permanently attached 3 metre lead Stowage hooks for cable on rear Power Outlets Auxiliary power outlets Four outlets 5 per outlet 10 A maximum total Fuses T5AH ceramic 1 4 x 1 inch high breaking capacity fuse on Live and Neutral on each outlet Overload Protection 10 thermal circuit breaker incorporated within the power outlet On Off switch Electromagnetic Compatibility The Prima SP2 meets the requirements of EN 60601 1 2 Electromagnetic compatibility requirements and tests 4 11 Device Classification and Labelling Type B Applied Part Degree of protection against electric shock This symbol denotes Type B equipment R Class 1 Classification Type of protection against electric shock Class 1 IPXO Ingress Protection Classification according to the degree of protection against ingress of water IPXO not protected Lab
89. ygen Air Nitrous Oxide 1 0 1000 ml min 2 0 10 L min Flowmeter Accuracy The accuracy of the flowmeter tubes is 2 5 of full scale reading 15 SPECIFICATION Flowmeter construction and dimensions Tubes and floats are matched and must not be interchanged Flowmeter tubes have antistatic coatings Tubes are length indexed Oxygen Nitrous oxide Other gases Scale length 4 4 Gas Pressures Pipeline supplies Cylinder supplies Reduced pressure from regulator at 5 L min flow Regulator diaphragm bursting pressure Reduced pressure system safety valve Safety valve to protect flowmeter vaporizer etc 260 mm 10 24 inch 250 mm 9 84 inch 240 mm 9 45 inch see 3 12 152 mm 6 in minimum all flow tubes except carbon dioxide USA Canada Japan 340 kPa 50 psig 310 kPa 15 kPa 35 kPa 45 psig 2 psig 5 psig 2800 kPa 406 psig 600 kPa 87 psig 41 kPa 10 6 psi 10 Reduced pressure from secondary regulators at 5 L min flow 152 241 kPa 22 35 psi 207 283 kPa 30 41 psi Oxygen and Nitrous Oxide Air 4 5 Auxiliary Gas Outlets Gas is supplied at pipeline supply pressure see above Gas is supplied at reduced pressure from cylinder regulator see above Pipeline supply Cylinder supply Oxygen Two self sealing connections on rear of machine Total flow rate not less than 100 L min to free air 80 L min against 243 kPa 36 psig resistance 7
90. yokes regulators or pressure gauges with oil or grease or any other flammable lubricant or sealant FUNCTION TEST 6 2 6 3 Machine Frame Check the main structure of the machine is firmly assembled free from obvious distortion and damage and that all attachments are secure Check that the castor wheels are securely attached to the machine frame and that the wheels run and swivel freely Check that each front wheel locking mechanism is working Check the drawer unit open and close smoothly Check that the writing tablet if fitted opens and closes smoothly Electrical Safety Tests Disconnect the mains lead from the electrical supply Disconnect all equipment from the auxiliary power outlet panel A Perform Electrical Safety Tests as specified by the National Standards applicable to your country Check electrical outlet sockets for correct output and earth continuity 31 FUNCTION TEST 6 4 Pipeline Gas Supply and Non Return 10 11 12 Valve Ensure that all reserve gas cylinders are turned off and removed from the machine Leave the Gas Delivery ON OFF switch 1 in the OFF Position Check ALL Pipeline Hose assemblies for correct probes colour coding and attachment to the machine Inspect ALL Pipeline hoses for cracks and check that all clips and connections are secure Connect the Oxygen Supply to the anaesthetic machine using the pipeline hose Check

Download Pdf Manuals

image

Related Search

Related Contents

lettore dvd/ videoregistratore - Hobbyelectronics.it main page  Samsung E378 用户手册  contrat de location et règlement 2014 ok  単回使用医療機器 (医療用具)  Spektrum DX8  デジタルコードレス電話機「UCT-002」  Floculation - Cholat Jardins  

Copyright © All rights reserved.
Failed to retrieve file