Home

Instruction Manual 2600

image

Contents

1. INPUT TYPE RANGE F RANGE C Type J or L Thermocouple 100 to 1607 73 to 871 Type K Thermocouple 200 to 2500 129 to 1371 Type T Thermocouple 350 to 750 212 to 398 Type E Thermocouple 100 to 1800 73 to 982 Type R Thermocouple 0 to 3200 17 to 1760 Type S Thermocouple 0 to 3200 17 to 1760 Type B Thermocouple 75 to 3308 24 to 1820 Type C Thermocouple 0 to 4208 17 to 2320 Type N Thermocouple 100 to 2372 73 to 1300 100 Q Plt 0 00385 DIN RTD 328 to 1607 200 to 875 100 Q Plt 0 00392 NIST RTD 328 to 1607 200 to 875 120 Q Nickel 0 00628 US RTD 112 to 608 80 to 320 1000 Q Pit 0 00385 DIN RTD 328 to 1607 200 to 875 Current Voltage A Voltage Scalable Units from 1999 to 9999 1 These Input Types can be set for 0 1 display If temperature goes above 999 9 or less than 199 9 the display will return to whole degree resolution 2 The 0 to 20 mADC 4 to 20 mADC 0 to 10 VDC 2 to 10 VDC and 10 to 10 mVDC inputs are fully scalable from a minimum of 100 counts span placed anywhere within the within the range of 1999 to 9999 Decimal point position is adjustable from the zero place 9999 tenths 999 9 hundredths 99 99 thousandths 9 999 or ten thousandths 9999 October 2005 Page 49 of 52 949 1194 6 DIMENSIONS 95 9mm 3 774in SERIES He ALIAL a PpO i 95 9mm m REM 3 774in g 5 Li a ee LOVE CONTROLS MADE IN U
2. A Hi L3 Ei OFF ON OFF ON D D y A Loy Low Alarm y Low Alarm EE A Lo ji ES ON OFF ONTOFF D D l pA Log AtHiq High and Low High and Low Alarm Alarm D 1 degree F 1 degree C or 1 count Note that when Alarm Power Interrupt 4 iF is programmed amp and Alarm Reset A upon a p present lf Alarm irE is programmed for Hald the alarm will automatically reset ower failure and subsequent restoration if no alarm condition is Inhibit 44 4 is selected Gn an alarm condition is suspended upon power up until the process value passes through the alarm set point once Alarm inhibit can be restored as if a power up took place by pressing both the amp INDEX and ENTER keys for 3 seconds WARNING IF INHIBIT IS ON AND A POWER FAILURE OCCURS DURING A HIGH ALARM RESTORATION OF POWER WILL NOT CAUSE THE ALARM TO OCCUR IF THE PROCESS VALUE DOES NOT FIRST DROP BELOW THE HIGH ALARM SET TING Do NOT USE THE ALARM INHIBIT FEATURE IF A HAZARD IS CREATED BY THIS ACTION BE SURE TO TEST ALL COMBINATIONS OF HIGH AND LOW ALARM INHIBIT ACTIONS BEFORE PLACING CONTROL INTO OPERATION The following menu items apply only to the alarm ALi October Alarm 1 function Select GFF Lo Ha H ia or Elink OFF Alarm 1 is disabled No Alarm 1 menu items appear in the Secondary or Secure menus Lo Low Alarm Only Lo appears in the Secondary Menu Hi High Alarm Only 4i appears in the Secondary Menu 2005 Page 37
3. 934 Analog Retransmission of Process Variable or Set Variable 0 to 20 mAdc scalable may be programmed for 1 to 5mA 4 to 20 mA etc 936 Analog Retransmission of Process Variable or Set Variable 0 to 10 Vdc scalable 948 4 Stage Set Point One of four pre set set point values can be implemented via contact closure 992 RS 485 Serial Communications Lovelink protocol 993 RS 232 Serial Communications Lovelink protocol 995 RS 232 Serial Communications Modbus protocol 996 RS 485 Serial Communications Modbus protocol Lovelink Lovelink I and Mother Node are Trademarks of Love Controls MODBUS is a trademark of Schneider Automation 949 1194 6 Page 4 of 52 October 2005 INSTALLATION Mount the instrument in a location that will not be subject to excessive temperature shock or vibration All models are designed for mounting in an enclosed panel Select the position desired for the instrument on the panel If more than one instrument is required maintain the minimum of spacing requirements as shown on the drawing below Closer spacing will structurally weaken the panel and invalidate the IP66 UL type 4X rating of the panel Prepare the panel by cutting and deburring the required opening Mounting Collar m jf a TT 92 0 mm 35 3 620 in 22 lt Lit Tit 11 Dever i Panel PANEL CUTOUT From the front of the pan
4. percent output and the 57 percent output Error messages are listed on pages 41 43 PROGRAMMING AND OPERATION FOR RAMP SOAK FEATURE The ramp soak feature offers a great deal of flexibility by allowing changes in the set point to be made over a predetermined period of time Dwell times can be programmed and the alarm output relay can be programmed to open or close during any of the segments Theory of Operation The 2600 Series controls offer a very simple approach to programming a ramp Rather than requiring the operator to calculate an approach rate usu ally in degrees per minute the 2600 does the calculation internally Thus the operator only needs to program the target set point and the time desired to reach that point When the ramp segment is executed by the control it October 2005 Page 15 of 52 949 1194 6 calculates the ramp required to move the process from the starting value current PV to the desired value programmed SP in the time allowed Soaks or dwells are ramp segments where the target set point is the same as the beginning process value This allows for multistage ramps without wasting intermediate soak steps Care must be taken however that the process does actually reach the soak value before the soak time starts If not the next segment will calculate a slope from the starting PV to the target SP Depending on your process requirements this differ ence may be important Make sure to test any progr
5. 1 start 1 stop no parity Number of units on line port 32 Cable Length 6 000 ft 1 828 m Termination 120 Ohms balanced 993 RS 232 Serial Communications Port Compliance RS 232C Isolation 500 VAC Protocol Lovelink II Address Range 001H to 3FFH Baud Rates 300 1200 2400 4800 9600 19 2k 28 8k Mode Half duplex Character 8 bits 1 start 1 stop no parity Number of units on line port 1 Cable Length 25 ft 7 6 m 995 RS 232 Serial Communications Port Compliance RS 232C Isolation 500 VAC Protocol MODBUS RTU Address Range 001H to OFFH Baud Rates 300 1200 2400 4800 9600 19 2k 28 8k Mode Half duplex Character 8 bits 1 start 1 stop no parity Number of units on line 1 Cable Length 25 ft 7 6 m 996 RS 485 Serial Communications 1 Port Compliance EIA 485 Isolation 500 VAC Protocol MODBUS RTU Address Range 001H to OFFH Baud Rates 300 1200 2400 4800 9600 19 2k 28 8k Mode Half duplex Character 8 bits 1 start 1 stop no parity Number of units on line 32 Cable Length 6 000 ft 1 828 m Termination 120 Ohms balanced Number can be increased through use of a repeater such as the Mother Node Consult factory for details Lovelink Lovelink I and Mother Node are Trademarks of Love Controls MODBUS is a trademark of Schneider Automation 949 1194 6 Page 48 of 52 October 2005 INPUT RANGES
6. Press and hold key for three seconds to activate See section on Ramp Soak page 15 for further details Z3 UP ARROW amp ENTER Menu Access Pressing these keys simultaneously brings up the secondary menu starting at the alarm tune or cycle item depending on programming Pressing these keys for 5 seconds will bring up the secure menu amp INDEX amp DOWN ARROW Menu navigation Pressing these keys simultaneously will allow backing up one menu item or if at the first menu item they will cause the display to return to the primary menu amp INDEX amp DOWN ARROW Alarm Reset If an alarm condition has occurred press and hold these keys for three seconds to reset the alarm Note that the alarm condition will not reset if the alarm condi tion still exists INDEX amp ENTER Global Reset Pressing these keys simulta neously and holding them for 5 seconds forces a warm boot restart ing the control similar to turning power off and on Global Reset will allow recovery from errors and reset the following menu items 949 1194 6 Page 12 of 52 October 2005 AL A Alarm inhibit GFEn inf Input error message bad inf Input error message CHEC LAL Check calibration error Correct the problems associated with the above conditions before using these reset keys More than one error could be present Caution is advised since several items are reset at one time While in the Primary or Secondary Menu if no key is pre
7. 2005 Page 9 of 52 949 1194 6 DUIT OR CHASE AS THE POWER WIRING ERRATIC OPER ATION OR DAMAGE TO THE CONTROL CIRCUITRY WILL RESULT WIRING FOR OPTION 948 4 STAGE SET POINT CAUTION DO NOT RUN SIGNAL WIRING IN THE SAME CON SWITCH CONTACTS FOR OPTION 948 MUST BE ISOLATED AND CAN NOT SHARE WIRING WITH OTHER CONTROLS gt SHARE A COMMON GROUND WITH OTHER EQUIPMENT OR OTHER CONTROLS Option 948 Wiring for Relay control Coil wiring not shown TRANSISTOR DRIVE MUST BE ISOLATED AND MAY NOT open open 1SP1_ Alternate wiring for Transistor control Use NPN open collector transistors Drive circuit not shown 949 1194 6 Page 10 of 52 October 2005 DUIT OR CHASE AS THE POWER WIRING ERRATIC OPER ATION OR DAMAGE TO THE CONTROL CIRCUITRY WILL RESULT CAUTION DO NOT RUN SIGNAL WIRING IN THE SAME CON WIRING FOR OPTION 992 993 995 996 SERIAL COMMUNICATIONS Options 992 996 DIP Switch Positions Half Duplex Full Duplex ed aa 1 wo gt o D N wo gt oa O Options 998 995 data ground For half duplex operation wire only A and B Do not connect to Y and Z DB 25 WIRING RS 232 DB 9 WIRING VIEWED FROM WIRE SIDE VIEWED FROM WIRE SIDE DATA IN 30 DATA OUT 32 DATA OUT 32 DATA IN 30 DATA GROUND 31 DATA GROUND 31 PIN DESCRIPTION 1 DCD 2 RECEIVE 3 TRANSMIT 4 DTR 5 GROUND 6 DSR PIN DESCRIPTION PIN DESCRIPTION 7 RT
8. If 5 54 is set for Int 357 is made active 45F Set Menu Items to display Stage 4 for view and change access If 554 is set for int 57 is made active Option 948 4 Stage Set Point Adjust Control Point 1 for Stage selected above Note The menu items for unt below are modified when Option 948 is active Then the menu items are shortened or shifted right and preceded with the stage number selected in 57 above Each stage has its own set of kunt parameters as indicated by tun tun wie Option 948 4 Stage Set Point or Tuning Choice Select SELF Pid SLB nor or FASE SELF The Controller will evaluate the Process and select the PID values to maintain good control Active for SP1 only Lire Select 465 or na SES Start Learning the Process After the process has been learned the menu item will revert to na no Learning will stay in present mode 949 1194 6 Page 26 of 52 October 2005 dFAL Damping factor Select GFF ito 7 Sets the ratio of Rate to Reset for the 5EL F tunk mode 7 most Rate Factory set to 3 For a fast response process the value should be low ered less Rate For a slower process the value should be increased more Rate Pid Manually adjust the PID values PID control consists of three basic parameters Proportional Band Gain Reset Time Integral and Rate Time Derivative 751 Option 948 4 Stage Set Point or Phi Proportional Band Bandwidth Select to 3999 F C o
9. Select La or GFF Gn When selected n the HOME lower display will indi cate the output of the controller in percent The indicator lamp will light and an s will appear in the right hand side of the lower display to indicate percent output for SP1 An s will appear on the right hand corner of the lower display to represent percent output for SP2 if the control is so equipped The display will alternate between these values Percent Output display is disabled 949 1194 6 Page 28 of 52 October 2005 Prod Ramp Soak Select fa or GFF Gn Allows Programmed Ramp Soak function to be started by the Run Hold key on the control front panel OFF Turns Ramp Soak function GFF and resets program to beginning PSE Programmer function set Select or GFF DEF Skip Ramp Soak Programming Go to next Secondary Menu Item InPC next page Gn Enable Ramp Soak Programming SEA Programmer Status Display in the Primary Menu when Prog above is On Select fa or GFF OFF The Primary Menu operates as normal Gn The Primary Menu is altered to have the following items inserted before the SP1 menu item H time remaining in active segment total time in active segment 5P segment target set point boas Ramp Soak Time Base Select 5 or 6_5 15 Ramp Soak time base is in 1 second increments Pro gram time 4 is measured in seconds 605 Ramp Soak time base is in 60 second increments min utes
10. Time Proportioning Control is adjustable in 1 second steps Recommended for mechan ical outputs relays solenoids etc For best contact life a time should be selected as long as possible without causing the process to wander 74 Pulsed Time Proportioning Output Select ut to Wut PuL Linear and PuL most non linear Changes output linearity for use in cool ing applications or for extremely fast response processes At the center of the proportional band a pulse value of 1 provides an output of one second on and one second off 50 output A pulse value of 2 provides an output of one second on and two seconds off 33 output Output at center of band equals one second on 2 se value seconds off Prot For Current Code 5 outputs only The following menu items apply only if your control is equipped with a second set point last digit of model number is not zero If your control does not have a second set point jump to the 17 menu on the next page Gute Output selection Select Half 47 FuL or Prat Gale A setting of 843 allows the control to operate in simple on off mode This setting forces the control to turn off at set point and on at the set point plus the differential SP24 When selected the Su G GF menu item is fol lowed by 52 and the Fh selection in the Sec ondary menu and the 25 and S cGH selections in the Secure menu are suppressed SPd Set Point On Off Differential hysteresis
11. alarm contact is closed Alarm 1 Loop Break Select la or GFF Gn Loop Break Condition will cause an Alarm Condition OFF Loop Break will not affect the Alarm Condition 949 1194 6 Page 38 of 52 October 2005 Ale Alarm 2 function Select GFF Lo Ha H ibe or Eliot OFF Alarm 2 is disabled No Alarm 2 menu items appear in the Secondary or Secure menus Lo Low Alarm Only La appears in the Secondary Menu Hi High Alarm Only H appears in the Secondary Menu Hike High and Low Alarms Both f2io and 24 appear in the Secondary Menu and share the same Alarm 2 Relay output Elink Alarm 2 is controlled by the Ramp Soak program func tion See pages 15 18 and 29 2 for further informa tion If ALZ is set to GFF and the control is not equipped with options the Secure Menu ends here If ALZ is set to GFF and the control is equipped with options proceed to 5f54 Addr or SCL below If FL2 is set to Elink go to AeSt below Ad Alarm 2 Type Select 465 or of Ab Absolute Alarm that may be set anywhere within the values of SCAL and SfAH and is independent of 57 dE Deviation Alarm that may be set as an offset from 4 i As SP iis changed the Alarm Point will track with 57 A devia tion alarm will also track any active ramp or soak set point Are Alarm 2 Reset Select Half or Haid Gage Automatic Reset Hot Manual Reset Reset acknowledge by simultaneously pressing the 3 amp INDEX amp DOWN ARROW keys for 3 sec
12. and Sth Ifthe analog signal fails the control will display the error message LHEL SPE and revert to the SP i local value 949 1194 6 Page 30 of 52 October 2005 Lore Option 992 993 995 996 Serial Communications Local Remote Status Select L5 or Does not affect other instru ments on daisy chain Lor The host computer is advised that remote write com mands will be rejected Any write commands sent to this control will be rejected All read commands are accepted The host computer is allowed to send write commands If the control is not addressed within the time set in nf No Activity Timer in the Secure Menu the CHED LarE error message will be displayed i nm Addr Option 992 993 995 996 Serial Communications Control Address Display address from to 3FF for Options 992 and 993 Display address from toFF for options 995 and 996 This number hexadecimal base 16 must match the address number used by the host computer Not settable in this menu To change this parameter see Add in the Secure Menu SECURE MENU Hold 8 UP ARROW amp ENTER for 5 Seconds Press INDEX to advance to the next menu item Press 8 UP ARROW or amp DOWN ARROW to change the value in the display Press ENTER to retain the value OUTPUTS ARE DISABLED TURNED OFF WHILE CONTROL IS IN SECURE MENU SELr Security Code See the Security Level Selection and the Password Table in this manual in order to enter the correct p
13. for decades The only modification to the application of the Ziegler Nichols equations is controlled by the gF menu item This menu item controls the amount of rate derivative that is applied A ofA setting of 7 factory default or less allows for less damping A FAL setting of 4 allows for critical damp ing as set forth in Ziegler Nichols A F4f setting of 5 or more allows over damping of the process Program Setup and Operation Do not cool the process or add heat while the tuning is occurring In the secondary menu set tun to SELF Skip LErn and check to make sure that aFAL is set to the desired value Back up to 4 amp rn and set to 4 amp 5 The control will begin the Self Tune function While the Self Tune function is active the right hand decimal point on the lower display will blink When Self Tune is complete the blinking will stop After Self Tune is complete the tun setting automatically switches to 7 ut This allows examination and or modification of the values calculated We recommend that you do not change the calculated values unless you have a firm understanding of the parameters involved and their function OPERATION AND PROGRAMMING OF OPTIONS Options 924 926 928 Analog Remote Set Point The analog remote set point allows the control set point to be determined by an outside analog signal The signal may be 0 to 10 VDC Option 924 0 or 4 to 20 mADC Option 926 or 0 to 10 000 Ohms Option 928 Wire
14. iirinn 12 PASSWORD TABLE 0 ccesccceceseeeseeeeeeneeeceneeeseaeeseaeeeteeaeseaeeesenenenee 13 SECURITY LEVEL SELECTION 0 ccc eccecceseseeeeeeeeeeeeeeeeeeeeseneeeeeaeees 13 NOTATION CONVENTIONS FOR THE MENUS eee 14 DISPLAY CONVENTIONS tsi secserstetsvdte evista 14 THE HOME DISPLAY 0 cccccceeeeeeeeeeeeeeeeeeeeeeeeteeeeeeaeeeseaeeseeaeesenaeeesaes 15 PROGRAMMING AND OPERATION FOR RAMP SOAK FEATURE 15 AUTO MANUAL OPERATION 0 0 ccceeceeeeeeeeeeeeeeeeneeeteaeeeeeaeetenaeeeteaes 18 SELF TUNE FUNCTION iiciicrtentines cinch edie an iaaeaie a Eni 18 Operation AND PROGRAMMING OF OPTIONS e 19 Options 924 926 928 Analog Remote Set Point eeeeee 19 Option 934 936 Isolated Analog Retransmission ccceeee 20 Option 948 4 Stage Set Pointas sincronia 21 Option 992 993 995 996 Serial Communication cceee 21 Serial Communications Options and Nonvolatile Memory 22 MENU SELECTIONS issiiccttrcctiiedans tel eccessnsaheen ten iaedes EAA EE 23 PRIMARY MENU jcssccstscvie enindi erotik iia nin aes 23 SECONDARY MENU cccceeccceeceeeeeeeeeeeeeneeeeeneeeeeneeeeeeaeeeeneeeeseaeeeee 24 SECURE MENU escchitin neni nisin ee ie ead 31 ERROR MESSAGEG ccccceccceeeeeeeeeeeeeeeneeeeeneeeeeeeeseneeeteneeetenaeeeeaas 41 43 CONFIGURATION MENU ssri naimisen ieina ainda 44 SPECIFICATIONS 1 000 eeccceeceeeeeeneeeeeeeeeeeneeeeeeeeseeeeeseeeeeeneeeeseeeeseneeeeseaeees 4
15. information regarding computer programming for the Serial Communications options see our web site at http www love controls com protocol MENU SELECTIONS PRIMARY MENU Press INDEX to advance to the next menu item Press E UP ARROW or amp DOWN ARROW to change the value in the display Press ENTER to retain the value If 5t4t Secondary Menu is Gn the three program status menu items shown on Page 17 will precede the following SP i Option 948 4 Stage Set Point or P Set Point 1 Adjust Control Point 1 o ore Set Point 2 Adjust if equipped Control Point 2 October 2005 Page 23 of 52 949 1194 6 SECONDARY MENU Hold 8 UP ARROW amp ENTER Press INDEX to advance to the next menu item Press 8 UP ARROW or amp DOWN ARROW to change the value in the display Press ENTER to retain the value If your instrument is not equipped with alarms third character of part number is 0 the Secondary Menu starts with Gut f below aun Ailo Alarm 1 Low The Low Alarm point is ual set below the Set Point May not appear depending on AL setting in Secure Menu AIH Alarm 1 High The High Alarm Point is usually set above the Set Point May not appear depending on AL setting in Secure Menu Ada Alarm 2 Low The Low Alarm point is usually set below the Set Point May not appear depending on AL setting in Secure Menu Ha Alarm 2 High The High Alarm Point is usually set above the Set Point May not appear
16. the display to time out or by pressing the ZS UP ARROW amp ENTER keys and then the EA DOWN ARROW amp INDEX keys The home display will read as it normally does The HOLD indica tor by the RUN HOLD key will be lit To start the program press the RUN HOLD key for three seconds The HOLD indicator will go out and the program will start To suspend the program at any time press the amp 2 RUN HOLD key Press the key again to resume Pressing the 9 AUTO MANUAL key will also suspend the program operation The difference is that AUTO MANUAL also puts the control into manual mode See Auto Manual Operation on page 18 The function of the Primary Menu will change depending on the setting of the 5t4t menu item in the Secondary Menu If St is GFF then the Pri mary Menu is not changed If the StAk menu item is set to Gn then the Primary Menu has three additional information items added before 57 appears The first INDEX item displays the time remaining in the current segment in the top display and the message in the lower display The next INDEX item displays the total time for the active segment in the upper display and the message it i5t in the lower display The third INDEX item displays the segment set value in the top display and the message 57 57 65 in the lower display The next INDEX press resumes the normal Primary Menu October 2005 Page 17 of 52 949 1194 6
17. the input as shown on pages 8 and 9 To set up the analog remote set point first determine the scale range that the analog signal will represent The maximum span is 11 998 degrees or counts In the Secure Menu set 5ft for the scale value that will be represented by the low end of the analog signal 0 Volts 0 mA 0 Ohms Set 5TH for the scale value that will be represented by the high end of the analog signal 10 Volts 20 mA 10 000 Ohms If you require a suppressed scale or input use the following equations to determine the proper settings for 5 1 and SiH October 2005 Page 19 of 52 949 1194 6 K Highest desired scale reading Lowest desired scale reading Maximum desired analog signal Minimum desired analog signal rSfH Maximum possible analog signal Maximum desired analog signal K Highest desired analog reading r5tt Lowest desired scale reading Minimum desired analog signal K Make sure that a valid analog signal is available to the control In the Secondary Menu set the 5Ft to Hn The REM indicator on the front of the control will turn on When the control returns to the HOME position the displayed SV will be the value supplied from the analog remote signal If the analog remote signal fails or goes out of range of the SF or SFH set tings the control will revert to the internal 5 or 57 i and flash the error message CHED SFt If SPL or SPH are set outside of SEL or SfH then the error
18. thermocouple current and RTD and output wiring for cur rent and 15 VDC is rated CLASS 2 Control wiring is as shown view is from rear of instrument showing wiring terminals ot I 21 22 23 24 25 26 Fa 1 24 VDC el H Td lee Ele SE eens 2 amp RTD V a CURRENT SSR RELAY L ISOLATED 3 13 a EP ip SET POINT L balk 1 OUTPUT O 5 15 ALARM 1 16 OUTPUT T a SET POINT a a 2 OUTPUT 8 ALARM2 d amp O 18 OUTPUT 19 paan 10 z 28 29 30 31 32 20 CE U U U U F ony SP1 SP2 LINE INPUT 18 VDC 20mA 85 TO 240 VAC IF SWITCHING INDUCTIVE LOADS RELAYS 50 60 Hz MOTORS SOLENOIDS ECT USE AN R C SNUBBER ACROSS COIL F1 3 8A 250VAC MEDIUM LAG Note Illustrations shown inside the wiring terminals repre sent internal circuitry See next page for output wiring chart INPUT WIRING Wire inputs as shown in the chart below Terminals 1 3 4 5 Thermocouple RTD 3 wire A B B RTD 2 wire A B amp J J Jumper 3 to 4 Voltage Current Key positive negative A odd colored lead B common leads J Jumper 949 1194 6 Page 6 of 52 October 2005 OUTPUT WIRING Wire outputs as shown in the chart below 28 ISP1SSR_ SP1 15VDC SP1 Relay SP1 Guret SP2 SSR_ sP215vDC_ SP2Relay SP2 Curr
19. will be suppressed and the control will attempt to work with the remote value To clear the error message change Sk to GFF Option 934 936 Isolated Analog Retransmission The analog retransmission option allows the Process Variable or the Set Variable to be sent as an analog signal to an external device The signal may be either O to 10 VDC Option 936 or 0 or 4 to 20 mADC Option 934 The output may be changed in the field from one to the other by the toggle switch located on the top printed circuit board Wire the output as shown on page 9 To set up the analog retransmission first determine the scale range that the analog signal will represent The maximum scale is 9999 F 5530 C or 9999 counts In the Secondary Menu set F amp L for the scale value that will be represented by the low end of the analog signal 0 Volts or 0 mA Set GH for the scale value that will be represented by the high end of the analog signal 10 Volts or 20 mA If you require a suppressed scale or output use the following equations to determine the proper settings for F amp L and FSH K Highest desired scale reading Lowest desired scale reading Maximum desired analog signal Minimum desired analog signal PGH Maximum possible analog output Maximum desired analog signal K Highest desired analog reading PG Lowest desired scale reading Minimum desired analog output K Next select whether you want the retransmission s
20. 26 4 kbaud This number must match the baud rate used by the host computer Power to instrument must be turned off and on before change takes effect see Page 21 Option 992 993 995 996 Serial Communications No Activity Timer Select GFF or to 99 minutes 1 99 Maximum time between host computer accesses lf the timer counts to 0 CHET Lar will be displayed DEF No Activity Timer function is disabled Option 992 993 995 996 Serial Communications Store to EEPROM Select YES orna See additional information on pages 22 23 SES Menu Item changes made through the Serial Commu nications are stored directly to the EEPROM no Menu Item changes made through the Serieal Commu nications are stored in RAM Option 924 926 928 Analog Remote Set Point Remote Scale Low Select 100 to 11998 counts below 5fH The total span between Slt and StH must be within 11998 counts Maximum setting range is 1999 to 9999 counts 949 1194 6 Page 40 of 52 October 2005 SCH Option 924 926 928 Analog Remote Set Point Remote Scale High Select 100 to 11998 counts above 5tt The total span between r Sti andr Sth must be within 11998 counts Maximum setting range is 1999 to 9999 counts ERROR MESSAGES Any error message may be cleared by using the Global Reset by press ing and holding the INDEX amp ENTER keys for five seconds DISPLAY MEANING SP OUTPUTS ACTION REQUIRED A ER Alter nates with PV T
21. 6 INPUT RANGES wie ncncdies teeth aetna teed 49 DIMENSIONS iscica iniedaiet ate teerd orea aroen a ceeded E Eaa ETEN 50 2001 Love Controls All rights reserved No portion may be copied without the express written consent of Love Controls 949 1194 6 Page 2 of 52 October 2005 GETTING STARTED Install the control as described on page 5 2 Wire your control following the instructions on pages 5 11 If you are using a two wire transmitter as an input see the drawing and instruc tions on page 7 Option wiring instructions are on pages 8 11 Option descriptions and specific instructions start on page 19 3 Most controls do not need many if any program changes to work on your process For best results when changing the programming make all the necessary changes in the Secure Menu page 31 before making changes to the Secondary Menu page 24 If error messages occur check the Error Messages on page 41 43 for help Take the example of a Model 26010 that comes from the factory pro grammed for type J thermocouples Suppose for this example you wish to change the input to a 100 ohm Platinum RTD and limit the set point range between 0 and 300 C First enter the Secure menu by pressing and holding the 8 UP ARROW amp ENTER keys for 5 Seconds Press the INDEX key until the display shows n and press the DOWN ARROW until the display shows 7345 Don t forget to press the ENTER key to retain your set ting Next pre
22. AM every few milliseconds EEPROM can not keep up to that pace and even if it could it would be used up in a matter of days If you think about how long it would take to make a million changes to the control programming through the front key pad you will see that it would take a very long time to get to use up the life of the EEPROM Adding one of the computer communications options e g 992 993 995 996 changes the picture The speed of computer communications is such that hundreds of instructions can be made in less than a minute In such a situation the million erase write cycles could be used up in a couple of months causing the chip and the control to fail Usually in such a situation the control is under close observation by the host computer It may not be necessary then to have the data written to the EEPROM as it is transitory in nature changing set points for a ramp soak sequence for example Controls equipped with a Serial communications option have a menu item in the Secure menu Star that allows the serial communications to write to RAM Star na The factory default is write to EEPROM Stor YES If your computer system will be making frequent changes to the control we strongly recommend that you select the write to RAM parameter Star na If you are primarily reading from the control there is no need to change the setting For further information on protocols and technical
23. AUTO MANUAL OPERATION The AUTO MANUAL function allows you to manually adjust the output of the control This is normally used during process setup or start up It can also be used for troubleshooting To switch from AUTO to MANUAL press the DS AUTO MANUAL key and hold for three seconds The MANual indicator will light and the lower display will change from normal to show ing the actual output in percent The value will be the actual percentage of output that was active when the key was pressed This is usually known as bumpless transfer If you wish to change the output while in manual press the UP ARROW or DOWN ARROW keys to change the value and press ENTER to retain it It is important to remember that the value of the display is read as 0 to 100 of the full control output NOT the range between S1OL and S10OH or S2OL and S2OH For example if the set point one output is programmed for 4 to 20 mA S1OL 20 S1OH 100 a reading of 50 in MANUAL represents 10 mA not 12 mA This allows the operator to go above and below the output range to allow for improperly function equipment that may be connected to the control output To return to AUTOmatic control press the ga AUTO MANUAL key again The MANual indicator will go out and the set point will take over However if you want bumpless transfer back to AUTO slowly change the percentage of output until the process variable matches or at least is close to the set point The fu
24. Band The 4 lt time and the time are independent and have no effect on each other To increase damping effect and reduce overshoot set the approach rate time for a value greater than the natural rise time of the process natu ral rise time process value time to set point Fuzzy Logic Intensity Select to 80 0 is OFF disables Fuzzy Logic The function defines the amount of impact Fuzzy Logic will have on the output Fuzzy Logic Error Band Select to GG F C or counts Sets the bandwidth of the Fuzzy Logic Set Fang equal to PID propor tional band for best results Fuzzy Logic Rate of Change Select 2 23 to 95 99 counts second For best initial setting find the counts second change of process value near Set Point 1 with output ON 100 Multiply this value by 3 Set Fr to this calculated value The Peak feature stores the highest input the control has mea sured since the last reset or Power On At Power On FEA is reset to the present input To manually reset the value FEF must be in the lower display Press the ENTER key to reset PEA will be reset and display the present input value The Valley feature stores the lowest input the Instrument has measured since the last reset or Power On At Power On 4AL is reset to the present input To manually reset the value VAL must be in the lower display Press the ENTER key HAL will be reset and display the present input value Percent Output Feature
25. INSTRUCTIONS FOR THE 2600 SERIES MICROPROCESSOR BASED TEMPERATURE PROCESS CONTROL SERIES 2600 Hoora LOVE CONTROLS MADE IN U S A CE LOVE CONTROLS LOVE a Division of Dwyer Instruments Incorporated PO Box 338 O Michigan City IN 46361 0338 800 828 4588 O 219 879 8000 O FAX 219 872 9057 www love controls com October 2005 Page 1 of 1 949 1194 6 CONTENTS GETTING STARTED i cccecdscecdusee desamar naanin iaaa aianei EREA 3 MODEL IDENTIFICATION wii iieccia cia nae oi media 4 INSTALLATION 0 cccccceceeeeeeeeeeeeeeeeeeseaeeeceaeeeseaeeeseaaeeseaeeeseeaeeesneeeeseeeeseaes 5 WIRING oe iei eisein eet tania iin tenn 5 POE WANING E E T E A E T duet oa 6 Output WINNO sanin eee es een 7 Wiring for 4 to 20mA Transmitter inputs 00 eee eee eeeeeeteeeeeeeeeaees 7 Wiring for Optional Inputs and Outputs ccceeeeeeeeseeeeesteeeteneees 8 Wiring for Option 924 Remote Set Point ccceeceeeeeeeeeeeeteeeteteees 8 Wiring for Option 926 Remote Set Point ceeeeeeeeeeeeesteeeeeeeees 8 Wiring for Option 928 Remote Set Point cccececeeeeeeeeeeteeeteteees 9 Wiring for Option 934 Analog Retransmission ccceeeeeeeees 9 Wiring for Option 936 Analog Retransmission ccceeeeeeeees 9 Wiring for Option 948 4 Stage Set Point ccceeeeeeeeeeeetteeeteees 10 Wiring for Option 992 993 995 996 Serial Communications 11 FRONT PANEL KEY FUNCTIONS
26. Program time St is measured in minutes The following items repeat in the following order ik 5 fi and ife if 202 1 AL i is programmed as tnk cbs PSP cA ead Bka 6GP IBRI 65f2 To avoid repetition each item will only be described once ika Segment Time Select to 9999 units minutes if 545 is set to 654 5 seconds if 675 is set to 5 sf Segment Set Point Set to target value desired hi Segment Alarm 1 Event Select a or GFF Gn Alarm 1 is active during segment 1 time it GFE Alarm 1 is inactive during segment 1 time Ae Segment Alarm 2 Event Select or GFF Gn Alarm 2 is active during segment 1 time it GFE Alarm 2 is inactive during segment 1 time Program End action Select Haid or GaFF fold Stay at the Present Set Point 55 GoFF Turn Off SP1 and SP2 Outputs at the end of the pro gram i 5 October 2005 Page 29 of 52 949 1194 6 oe POL Loo Repeat program starting at t SP i Revert to 5 value Input Correction Select 568 to amp to 500 F C or counts This feature allows the input value to be changed to agree with an external reference or to compensate for sensor error Note inf is reset to zero when the input type is changed or when decimal position is changed Factory default is Digital Filter Select G77 to 99 In some cases the time constant of the sensor or noise could cause the display to jump eno
27. R at AcPt nea to exit and retain the old configuration Otherwise press UP ARROW and ENTER at Act YES to retain the new configuration The instrument will re boot with factory settings October 2005 Page 45 of 52 949 1194 6 SPECIFICATIONS Selectable Inputs Thermocouple RTD DC Voltage or DC Current selectable Input Impedance Thermocouple 3 megohms minimum RTD current 200 pA Current 10 ohms Voltage 5000 ohms Sensor Break Protection De energizes control output to protect system after customer set time See inf in Secure Menu Set Point Range Selectable See Input Ranges Page 49 Display Two 4 digit 7 segment 0 56 high LEDs Control Action Reverse usually heating Direct usually cooling select able Proportional Band 1 to 9999 F C or counts Reset Time Integral Off or 0 1 to 99 9 minutes Rate Time Derivative Off or 0 01 to 99 99 minutes Cycle Rate 1 to 80 seconds On Off Differential Adjustable 1 F 1 C or 1 count to full scale in 1 F 1 C or 1 count steps Alarm On Off Differential 1 F 1 C or 1 count Fuzzy Percent 0 to 100 Fuzzy Rate Off or 0 01 to 99 99 counts per second Fuzzy Band Off or 1 to 4000 F C or counts Accuracy 0 25 of span 1 least significant digit Resolution 1 degree or 0 1 degree selectable Line Voltage Stability 0 05 over the supply voltage range Temperature Stability 100 ppm C typical 200 ppm C max
28. S 1 SHIELD DSR 8 CTS 2 TRANSMIT 7 GROUND 3 RECEIVE 8 DCD 4 20 DTR 5 CTS October 2005 Page 11 of 52 949 1194 6 FRONT PANEL KEY FUNCTIONS Heater Fail Lamp SERIES 2600 Alarm 1 Lamp Set Point 1 Lamp Alarm 2 Lamp Set Point 2 Lamp F Indicator Process Display C Indicator Set Point Display Remote Set Lamp Manual Indicator Aona Percent Lamp Hold Lamp LOVE CONTROLS MADE IN U S A The decimal point flashes when Self Tune is operating INDEX Menu Navigation Pressing the INDEX key advances the display to the next menu item May also be used in conjunction with other keys as noted below S UP ARROW Increments a value changes a menu item or selects the item to ON The maximum value obtainable is 9999 regardless of decimal point placement amp DOWN ARROW Decrements a value changes a menu item or selects the item to OFF The minimum value obtainable is 1999 regardless of decimal point placement ENTER Pressing ENTER stores the value or the item changed If not pressed the previously stored value or item will be retained The display will flash once when ENTER is pressed gJ AUTO MANUAL This key toggles the control output between Auto matic mode and Manual mode Press and hold key for three seconds to activate See section on AUTO MANUAL operation on page 18 RUN HOLD This key toggles the Ramp Soak program functions between Run mode program runs as set up and Hold mode pro gram functions are suspended
29. S A Meets IP66 UL Type 4X 114 3mm 13 5mm 0 530in 91 3mm aaan 95 9mm 3 774in es Maximum Panel Thickness 6 53mm 0 250in gt lt Panel All dimensions are in millimeters with inches in parenthesis Panel cutput for all models is 92mm x 92mm 3 625in x 3 625in Allow for 13mm 0 5in clearance at the rear of the instrument 949 1194 6 Page 50 of 52 October 2005 October 2005 Page 51 of 52 949 1194 6 949 1194 6 Page 52 of 52 October 2005
30. Select to 9999 direct acting or to 9599 reverse acting See 57 is on the previous page LP Time Proportioning Cycle Time Select it to 2P EP A setting of it is recommended for solid state Dupas SSR or 15VDC ctf to GLP Time Proportioning Control is adjust able in 1 second steps Recommended for October 2005 Page 25 of 52 949 1194 6 mechanical outputs relays solenoids etc For best contact life a time should be selected as long as possible without causing the pro cess to wander 7 Pulsed Time Proportioning Output Select fut to Wut PuL Linear and Pu most non linear Changes output linearity for use in cool ing applications or for extremely fast response processes At the center of the proportional band a pulse value of 1 provides an output of one second on and one second off 50 output A pulse value of 2 provides an output of one second on and two seconds off 33 output Output at center of band equals one second on 2 se vaue seconds off Prot For Current Code 5 outputs only Option 948 4 Stage Set Point Active Set Point Stage Select ISP i e5F i 35F i 4S i See Page 21 for more detail SP Set Menu Items to display Stage 1 for view and change access If SPS is set for int SF i is made active ese Set Menu Items to display Stage 2 for view and change access If 5 54 is set for Int 257 i is made active 35F Set Menu Items to display Stage 3 for view and change access
31. am for desired results before running production material Do not operate Self Tune while a ramp function is operating The ramp function will prevent the Self Tune from operating properly Make sure that all tuning is set up before operating Ramp Soak Program Setup All of the programming for the Ramp Soak function is done in the Sec ondary Menu You may wish to work out your program on paper before going into the programmer menu sequence In the Secondary Menu G3 INDEX to amp ro4 and make sure that 7 04 is set to GFF INDEX to amp S and turn Gn Press ENTER Skip the 54 setting this is discussed later and press INDEX to ie The following items repeat in the following order ik 5 if and or ie if AL i or AL in the Secure Menu are programmed set to Eun ib cbs 25 eAi its 65 i544 i642 To avoid repetition each item will only be described once Set to the amount of time you want for the first ean This value is in time units determined by the 445 menu item from to 9999 Press ENTER Set 5 to the G value desired for the first ramp This value is in actual units just like 57 i If the control is programmed for temperature then the SP displays are in temperature If the control is programmed for some other engineering unit the SP is set in that unit Press INDEX to continue If Alarm 1 is programmed as an event At i Elink then Ai will appear If you wish the Alarm 1 contact to
32. and Voltage Inputs all Menu Items related to the Input will be affected a No decimal Point is selected This is available for all Input Types One decimal place is available for Type J K E T L RTD s Current and Voltage Inputs Two decimal places is only available for Current and Voltage Inputs goan Three decimal places is only available for Current and Voltage inputs 949 1194 6 Page 32 of 52 October 2005 inPe Input Fault Timer Select GFF amp i to 542 4 minutes Whenever an Input is out of range HFL or GFL displayed shorted or open the timer will start When the time has elapsed the controller will revert to the output condition selected by inf below If GFF is selected the Input Fault Timer will not be recognized time infinite D y 3 z Sensor Rate of Change Select GFF to 4800 F C or counts per 1 second period This value is usually set to be slightly greater than the fastest process response expected during a 1 second period but measured for at least 2 seconds If the process is faster than this setting the 5En2 44 error message will appear The outputs will then be turned off This function can be used to detect a run away condition or speed up detection of an open thermocouple Use the INDEX amp ENTER keys to reset LA 2 Scale Low Select 100 to 11998 counts below SAH The total span between SAL and 5 44 must be within 11998 counts Maxi mum setting range is 1999 to 9999 c
33. and holding the INDEX amp ENTER keys for five seconds DISPLAY MEANING SP OUTPUTS ACTION REQUIRED Display is blank Instru ment is not getting power or the supply voltage is too low ae lighted Fail test appears upon power up if the internal diagnostics detect a failure This message may occur during operation if a failure is detected Displays flash Fail test may also occur due to an EEPROM failure mm This message will appear upon power up if SF SP2 5P i or 57 is set outside of the SPL or SPH values x D ch This message ap pears at power up if SFL or SPH values are programmed outside the input range ends This message ap pears if the analog remote set point signal is out of range This message ap pears if the Serial Communications has timed out October 2005 Set point out puts inactive Alarm inactive Set point out puts inactive Alarm inactive Set point out puts inactive Alarm active Set point out puts inactive Alarm active Set point out puts active Alarm active Set point out puts active Alarm active Page 43 of 52 Check that the power supply is on measure supply voltage check that the external fuses are good The display alternates between FA iL ESE and one of the fol lowing messages FACE aflek Memory may be corrupted Press the EA DOWN ARROW and ENTER keys to return control to the fac tory default settings Recheck co
34. assword October 2005 Page 31 of 52 949 1194 6 inf Input Type Select one of the following Refer to the Wiring sec tion for the proper wiring J i Type J Thermocouple cA Type K Thermocouple E Type E Thermocouple E Type T Thermocouple i Type L Thermocouple a Type N Thermocouple c i3 Type R Thermocouple 5 i Type S Thermocouple b Type B Thermocouple E Type C Thermocouple 392 100 ohm Platinum NIST 0 00392 Q Q C aig 120 ohm Nickel 385 100 ohm Platinum IEC DIN 0 00385 9 Q C 39 1000 ohm Platinum IEC DIN 0 00385 2 Q C fuer DC Current Input 0 0 to 20 0 or 4 0 to 20 0 mA iiaLt DC Voltage Input 0 0 to 10 0 or 1 0 to 10 0 volts dF DC Voltage Input 10 to 10 mV ier ee e Reserved SUP Zero Suppression Select Sa or GFF Only with Current and Volt age input types FF The input range will start at O zero Input Gn The input range will start at 4 00 mA or 1 00 V Lin a F G or nonk F F descriptor is On and temperature inputs will be dis played in actual degrees Fahrenheit C descriptor is On and temperature inputs will be dis played in actual degrees Celsius nonk F and C descriptors will be Off This is only available with Current and Voltage Inputs 2 PE Decimal Point Positioning Select 7 0 0 2 80 000G or 000 On temperature type inputs a change here will alter the Process Value SP1 SP2 ALLo ALHi and InPC For Current
35. cked Secondary Locked Secure Locked Primary Unlocked Secondary Locked Secure Locked Primary Unlocked Secondary Unlocked Secure Locked Primary Unlocked Secondary Unlocked Secure Unlocked October 2005 Page 13 of 52 949 1194 6 NOTATION CONVENTIONS FOR THE MENUS Because of the number of features available in this control information is included that may not apply to your specific control All usable features are included in this book but may not be used in your process To increase clarity the following conventions are used 1 Certain features menu items and functions shown in this book may or may not appear on your control depending on other menu item selections At various places in the menus there are notes identifying menu items that control or direct other menu items If you are looking for a particular menu item and can t find it check the menu item that is its control for proper setting 2 The symbol is used in two ways It is used inside a group of charac ters to indicate which set point function 54 or SF is being affected It is also used before a group of characters of a menu item to indicate that there may be more than one selection or value for that menu item This is used for certain repeated items such as in the Ramp Soak Program section DISPLAY CONVENTIONS The instrument front has two four digit displays eleven indicators and six keys The diagram on page 12 shows the l
36. depending on ALe setting in Secure Menu Gut i Output selection Select GnGF 7 PuL or Prat Geile A setting of nF allows the control to operate in simple on off mode This setting forces the control to turn off at set point and on at the set paint plus the dif ferential 57 id When selected the Gut i Gad menu item is followed by 57 id and the tunt Pb 5 GES and rE selections in the Secondary menu and the 5 iL and 5 34 selections in the Secure menu are sup pressed SP i Set Point On Off Differential hysteresis Set for the amount of difference between the turn off point and the turn on point Select to 9999 direct acting or to 9999 reverse acting This value will be negative for reverse acting set points and positive for direct acting outputs The following drawing shows output behavior for reverse and direct action For reverse action note how the output decreases as the input process variable gt gt DIRECT ACTING 5 5t dir UPSCALE O RFERENTIAL V Reverse ACTING S 5t rE foo DIFFERENTIAL a o pDIFF INPUT 0 DIFF INPUT SP 0 Kopra 5P DISPLAYED VALUE SP DISPLAYED VALUE 949 1194 6 Page 24 of 52 October 2005 OUTPUT OUTPUT increases e g heat power goes to zero as the temperature increases to set point LP Time Proportioning Cycle Time Select it to 2er ith A setting of it is recommended for solid state outputs SSR or 15VDC et to AGL
37. ding a bias to the process when needed Factory set to 4 for output codes 1 and 3 Factory set to 2 for output code 5 20 output equals 4 mA output Soia Set Point 2 Output High Limit Select 7 to 2 but not less than 5201 for output codes 1 and 3 Select to i 2 but not less than 5201 for output code 5 This item allows setting the maximum output limit This is useful with processes that are over powered Adjustment to 102 allows setting current output to force a full on condition for output devices which do not have bias adjust ments Factory set to 30 for all output codes If Gute is set to GaGF in the Secondary Menu then the next three menu items can make the 572 and 5724 settings act like a high or low alarm set point See the information on alarm settings and the cautions and warn ings that apply to them on the next pages Note that when Set Point 2 Power Interrupt 5c is Ga and Set Point 2 Reset 5Sc is programmed to Haid the SP2 output will automatically reset upon a power failure and subsequent restoration if the process is below 572 October 2005 Page 35 of 52 949 1194 6 Sere Set Point 2 Reset Select SaF or Hold GAGE Output will automatically reset when process passes back through 5fed Hota Manual Reset Reset acknowledge by simultaneously pressing the amp INDEX amp DOWN ARROW keys for 3 seconds SEP Set Point 2 Power Interrupt Select a or GFF Gn Alarm Power Interrupt is Sa Output w
38. e Auto Manual function the Run Hold function the a 9 function the Fett function and any error message Description of these special displays follows If the JA Auto Manual key is pressed the Manual indicator lights the indicator lights and the home display is changed The upper display con tinues to show the Process Variable PV but the lower display changes to show the percentage of output in tenths of a percent to 99 9 0 0 to 99 9 or 100 if 100 The display digit to the right of the number shows a flashing letter o to indicate that the value displayed is no longer the SV but percent output The 572 percent output is indicated by the use of an overline on the letter Access to the 572 value is made by the INDEX key See Auto Manual Operation on Page 17 for further information If 29 is turned amp the HOME display changes the SV display from 57 i to the Present Set Variable as calculated by the Ramp Soak Programmer function See Programming and Operation for Ramp Soak Feature below for more information If fet Secondary Menu is turned Gn the lower display changes to show the active percentage of output as required to maintain 57 i The display is similar to the Auto Manual display above except that the percent indica tors 2 5 do not flash and the output is displayed in whole percentages of output not in tenths of a percent If the control has both 57 and 52 the lower display will alternate between the
39. ect the stage to modify with the 57 menu item When SP is changed while the 557 is set for r the selected stage is displayed for modification but only used when the appropriate contact is made Option 992 993 995 996 Serial Communication The serial communications options allow the control to be written to and read from a remote computer or other similar digital device Communi cation is allowed either through a RS 485 Option 992 996 port or a RS 232 Option 993 995 port Wire the communication lines as shown on Page 11 Wiring for the RS 485 is run from control to control in a daisy chain fashion with a termi nation resistor 120 ohms across the transmit and receive terminals of the last control in the chain Select the control address and communication baud rate with the Addr and fug menu items in the Secure Menu NOTE THE BAUD RATE AND ADDRESS MENU ITEM SETTINGS WILL TAKE EFFECT ON THE NEXT POWER UP OF THE CONTROL BE SURE TO TURN THE POWER TO THE CONTROL OFF AND ON BEFORE USING THE NEW BAUD RATE AND ADDRESS VALUES In operation you have the option of preventing a write command from the host computer To prevent the host from writing to the control change the iG menu item in the Secondary Menu to 44 To allow the host to write commands to the control set 14 to r The host does have the ability to change the 1 state but it is not automatic If your system depends on constant reading or writing to and fro
40. el slide the housing through the cut out The housing gasket should be against the housing flange before installing From the rear of the panel slide the mounting collar over the housing Hold the housing with one hand and using the other hand push the collar evenly against the panel until the spring loops are slightly compressed The ratchets will hold the mounting collar and housing in place CAUTION It is not necessary to remove the instrument Fas chassis from the housing for installation If the instrument chassis is removed from the housing you must follow indus try standard practice for control and protection against Elec tro Static Discharge ESD Failure to exercise good ESD practices may cause damage to the instrument WIRING Do not run RTD thermocouple or other class 2 wiring in the same A conduit as power leads Use only the type of thermocouple or RTD probe for which the control has been programmed Maintain sepa ration between wiring of sensor optional inputs and outputs and other wiring See the Secure Menu for input selection For thermocouple input always use extension leads of the same type des ignated for your thermocouple October 2005 Page 5 of 52 949 1194 6 For supply connections use No 16 AWG or larger wires rated for at least 75 C Use copper conductors only All line voltage output circuits must have a common disconnect and be connected to the same pole of the disconnect Input wiring for
41. ent Key positive negative NC Normally Closed NO Normally Open C Common WIRING FOR 4 TO 20MA TRANSMITTER INPUTS Wire power and outputs as shown above Two wire transmitters wire as shown below View is of instrument as seen from the rear to show wiring terminals For three or four wire transmitters follow the wiring instructions provided with your transmitter CAUTION DO NOT WIRE THE 24 VOLT POWER SUPPLY ACROSS THE INPUT OF THE CONTROL DAMAGE TO THE CONTROL INPUT CIRCUITRY WILL RESULT TYPICAL 2 WIRE TRANSMITTER October 2005 Page 7 of 52 949 1194 6 WIRING FOR OPTIONAL INPUTS AND OUTPUTS All wiring shown below is Class 2 Shielded twisted pair is required for Options 992 and 996 Shielded cable is required for Options 993 and 995 Options 924 926 and 928 share a common ground with input CONDUIT OR CHASE AS THE POWER WIRING ERRATIC OPERATION OR DAMAGE TO THE CONTROL CIRCUITRY WILL RESULT CAUTION DO NOT RUN SIGNAL WIRING IN THE SAME WIRING FOR OPTION 924 REMOTE SET POINT HIME Option 924 WIRING FOR OPTION 926 REMOTE SET POINT Option 926 949 1194 6 Page 8 of 52 October 2005 DUIT OR CHASE AS THE POWER WIRING ERRATIC OPER ATION OR DAMAGE TO THE CONTROL CIRCUITRY WILL RESULT CAUTION DO NOT RUN SIGNAL WIRING IN THE SAME CON WIRING FOR OPTION 928 REMOTE SET POINT Option 928 October
42. function for this segment set A i for Ba If not set for GFF Press ENTER When Ai is set to a the Alarm 1 function will be active for the entire period setin it above Complete setting the segment times ct it 1 segment set points 257 557 and event alarms 24 i i64 BA i to i um Or GFE 949 1194 5 Page 16 of 52 October 2005 For unneeded or unused segments set the segment times 2t 16t to G and set the segment set points lt 5 55 to the same value as the last active set point A segment alarm may be set to indicate end of run at the segment number you select The last menu item for the ramp soak function is FEnd FEnd determines what the control does when the program has ended You may choose to have the program repeat Loaf Hot the last set point 557 revert to the local F i or turn the outputs off fsFF It is important to remember that if you want the program to repeat you must allow the process to return to the same condition that existed when the program first started Remember that the ramp function calculates the slope by drawing a line from the beginning PV to the ramp target set point If the PV at the end of the program is different than the PV at the initial start the ramp will calculate differently Ramp Soak Operation When you wish to start the program enter the Secondary Menu and set the f a9 menu item to a Return to the HOME position by waiting for
43. he process when needed Factory set to 4 for output codes 1 and 3 Factory set to 2 for output code 5 20 output equals 4 mA output 5 ign Set Point 1 Output High Limit Select to 36 but not less than 5 iG for output codes 1 and 3 Select to i 2 but not less than 5 iL for output code 5 This item allows setting the maximum output limit This is useful with processes that are over powered Adjustment to 102 allows setting current output to force a full on condition for output devices which do not have bias adjust ments Factory set to 30 for all output codes If Gut tis set for EP FUL or Prof then skip to 5 iP next page If Gut iis set to GaGF in the Secondary Menu then the next three menu items can make the 57 and 57 ig settings act like a high or low alarm set point See the information on alarm settings and the cautions and warn ings that apply to them on Pages 36 37 Note that when Set Point 1 Power Interrupt 5 iF is Ga and Set Point 1 Reset 5 i is programmed to Haid the SP1 output will automatically reset upon a power failure and subsequent restoration if the process is below 57 i Sire Set Point 1 Reset Select BaF or Hald nF Output will automatically reset when process passes back through 5 id Hold Manual Reset Reset acknowledge by simultaneously pressing the amp A INDEX amp DOWN ARROW keys for 3 seconds SP Set Point 1 Power Interrupt Select a or GFF Gn Alarm Power Inter
44. his message ap pears if the ambient temperature of the control approaches the ends of toler ance This message ap pears if the ambi ent temperature of the control is out of range or RJC sensor is broken October 2005 Set point out puts active Alarm active Set point outputs active Alarms active Page 41 of 52 Correct the ambient tempera ture conditions Ventilate the area of the cabinet or check for clogged filters If internal tem perature sensor RJC located in terminal 2 is broken return to factory for service Correct the ambient tempera ture conditions Ventilate the area of the cabinet or check for clogged filters If internal temperature sensor is broken return to factory for service 949 1194 6 ERROR MESSAGES Any error message may be cleared by using the Global Reset by press ing and holding the INDEX amp ENTER keys for five seconds DISPLAY MEANING SPOUTPUTS ACTION REQUIRED Underflow or Over flow Process value has exceeded input range ends HEL or BEL will sequence to display one of these mes sages if the int is set for a time value For RTD inputs RTD is open or shorted For THERMOCOU PLE inputs thermo couple is open The sensor may be defective heater fuse open heater open or the final power output device is bad Rate of Change exceeded the programmed limits set for SEnL Sensor EREL CAL Check calibration appears as an alter nati
45. ignal to follow the Process Variable or the Set Variable Usually the Process Variable is sent to record ers or other data acquisition devices Usually the Set Variable is sent to other controls to be used as an analog remote set point If you want the analog retransmission signal to follow the PV in the Secondary Menu set FiSr to inf If you want the analog retransmission signal to follow the SV set F25 to SFE Operation is automatic There are no further programming steps required 949 1194 6 Page 20 of 52 October 2005 Option 948 4 Stage Set Point The 4 stage set point option allows four different values to be used for i and all of the values associated with the tun menu items The control will switch to a given stage when an external contact or contacts are made or opened across the appropriate terminals at the rear of the control 5 57 Set Point Switch Action set for remote r or when the stage is selected from the Secondary Menu 5 when 5 54 is set for int When the state of a contact changes or the stage number is changed in the Secondary Menu the values in use are stored and the previously stored values for the new stage are used Wire the input as shown on page 10 Usually the control is configured for external switching of the stages In this case the operation is usually automatic selected by the external switches driven by the machine logic If it is necessary to program the stages in advance you may sel
46. ill automatically reset on power up if no alarm condition exists GEF Alarm Power Interrupt is FF Output will be in the alarm condition on power up regardless of condition of process mw Po ag Set Point 2 Inhibit Select Ba or GFF Gn Alarm Inhibit is a Alarm action is suspended until the process value first enters a non alarm condition DEF Alarm Inhibit is GFF SeLF Set Point 2 Lamp Select on or GoFF Gon Lamp ON when Output is ON FF Lamp OFF when Output is ON 5 ALARM TYPE AND ACTION if alarm function is present Caution In any critical application where failure could cause expensive product loss or endanger personal safety a redundant limit controller is required When setting an alarm value for an absolute alarm 4 it 455 simply set the value at which the alarm is to occur When setting the alarm value for a deviation alarm F ik d set the dif ference in value from the Set Point desired For example if a low alarm is required to be 5 degrees below the Set Point then set 4 iLa to 5 If a high alarm is required 20 degrees above the Set Point then set 4 iH to 27 If the Set Point is changed the alarm will continue to hold the same relation ship as originally set 949 1194 5 Page 36 of 52 October 2005 The diagram below shows the action and reset functions for both absolute and deviation alarms ABSOLUTE ALARMS DEVIATION ALARMS f y A Hi High Alarm 7 5 High Alarm
47. imum Common Mode Rejection 140 db minimum at 60 Hz Normal Mode Rejection 65 db typical 60 db at 60 Hz Isolation Relay and SSR outputs 1500 Vac to all other inputs and outputs SP1 and SP2 Current outputs 500 Vac to all other inputs and out puts but not isolated from each other SP1 and SP2 Switched Voltage outputs 500 Vac to all other inputs and outputs but not isolated from each other 24VDC Loop Power 500VAC to all inputs and outputs Supply Voltage 100 to 240 Vac nominal 10 15 50 to 400 Hz single phase 132 to 240 Vdc nominal 10 20 Loop Power Supply 24 VDC 50 mA regulated Power Consumption 5VA maximum Operating Temperature 10 to 55 C 14 to 131 F Storage Temperature 40 to 80 C 40 to 176 F Humidity Conditions 0 to 90 up to 40 C non condensing 10 to 50 at 55 C non condensing Memory Backup Nonvolatile memory No batteries required 949 1194 6 Page 46 of 52 October 2005 Control Output Ratings SSR 2 5 A 240 Vac at 25 C 77 F Derates to 1 25 A 55 C 130 F Relay SPDT 10 A 240 Vac resistive 1 2 hp 120 Vac or 1 3 hp 240 Vac Alarm Relay SPST 3A 240 Vac resistive 1 5 A 240 VAC induc tive Pilot Duty Rating 240 VA 2A 120 VAC or 1A 240 VAC Current isolated 0 to 20 mA across 600 ohms maximum Switched Voltage isolated 15 Vdc 20 mA Panel Cutout 92 mm x 92 mm 3 625 x 3 625 Depth Behind Mounting Surface 103 mm 4 0 ma
48. is is known as EEPROM elec trically erasable programmable read only memory While the name may be long and somewhat cryptic the EEPROM can be erased and re written many times and yet hold the programmed data even over long periods when the power is off This is the type of memory that Love Controls uses to save the settings you program in your control The reliability and lon gevity of the data retention is what allows us to guarantee a 10 year data retention without power In normal operation the control uses RAM just as any other computerized device Whenever you make a change to one of the parameters in the con trol the set point for example the new value is written into the EEPROM This way if power goes off for whatever reason when power resumes the latest settings are preserved When power is turned on the data is copied from the EEPROM to the RAM to restore operation You might ask If EEPROM is such a wonderful thing why bother with RAM One reason is that is that RAM is much faster than EEPROM Faster speed gives you better performance in critical control functions Perhaps the most important reason is that RAM allows an unlimited number of writes while EEPROM has a limit to the number of times that it can be erased and re written Current technology now sets that limit at 949 1194 6 Page 22 of 52 October 2005 about one million erase write cycles In a dynamic control situation it may be necessary to update R
49. ly press and hold the INDEX amp ENTER keys while the lamp test or self test is displayed Hold the keys down until the ROM ID code appears 2 Press the INDEX key to advance to the next menu item FALE Flt This function restores the control to original factory settings It will also remove all of the hardware option and software configuration values After selecting FALE Fit you will need to restore the configuration values as shown above to allow the instrument to operate correctly To restore factory default values press and hold the ENTER key While holding the ENTER key also press the DOWN ARROW key The display will blink momentarily and the instrument will reboot The instrument will then display the ROM ID Press INDEX to step through FALE dFL and continue at step 3 3 Press INDEX to Ft i If your instrument is equipped with Option 924 926 or 928 press the UP ARROW or DOWN ARROW as necessary to display 57 The display will be flashing To select press ENTER while 57 is displayed When selected the option number will stop flashing DO NOT SELECT AN OPTION IF THE INSTRUMENT DOES A NOT HAVE THE HARDWARE TO SUPPORT IT SELECTION OF AN UNSUPPORTED OPTION MAY CAUSE IMPROPER OR UNPREDICTABLE OPERATION OF THE INSTRUMENT 949 1194 6 Page 44 of 52 October 2005 Press INDEX to fnF Press INDEX to cft If you do not want to retain the re configuration this is your last chance to return to the old configuration Press ENTE
50. m the host you may wish to set the No Activity Timer nt to monitor the addressing October 2005 Page 21 of 52 949 1194 6 of the control When the 14 lt is set to and the nft is set to any value other than GFF the control will expect to be addressed on a regular basis If the control is not addressed in the time set by the value of mt then the control will display the error message SHEL 1G To clear the message setiLa to LIL SERIAL COMMUNICATIONS OPTIONS AND NONVOLA TILE MEMORY There are many different types of memory used in computer driven devices The terms RAM random access memory and ROM read only memory are a couple with which you may be familiar RAM is used in computers to run programs and hold data for a short period of time This is the memory that is used primarily in PCs RAM is very fast and can be read and written to over and over again Its major weakness is that it is erased when the power is turned off ROM is used in computers to hold the permanent programming that allows a PC to start This memory is burned in to the chip itself and can not be changed Unlike RAM however this memory is permanent While it can not be changed it can not lose its programming when power is turned off This is the type of memorythat is used to store the permanent programming for the control There is a third type of memory that is now currently used to combine the characteristics of both RAM and ROM Th
51. ng message if the instrument cali bration nears toler ance edges Check calibration appears as a flash ing message if the inst rument calibra tion ex ceeds speci fication 949 1194 6 Set point out puts active Alarm active Set point out puts inactive Alarm active Set point out puts inactive Alarm active Set point out puts inactive Alarm active Set point out puts active Alarm active Set point out puts inactive Alarm active Page 42 of 52 May be normal if Input signals go above or below range ends If not the case check sensor input wiring and correct When aft input fault timer has been set for a time the outputs will be turned off after the set time Setting the time to GFF causes the outputs to remain active however Fi or GFL will still be displayed Correct or replace sensor Correct or replace sensor Clear with Global Reset Correct or replace sensor or any element in the control loop that may have failed Correct the problem Clear with Global Reset Check for the cause of the error The value setting may be too slow for the process or the sensor is intermittent Correct the problem Clear with Global Reset Remove the instrument for service and or recalibration Remove the instrument for service and or recalibration October 2005 ERROR MESSAGES Any error message may be cleared by using the Global Reset by press ing
52. ntroller programming rft FALE Unrecoverable error return to factory for service SP i Correct the etc or adjust the SPL or 5PH values by pro gramming new values 2 SPL Correct the or 5PH values by programming new values The control will revert to 5 i Correction of the analog signal or turning SFF the SPtr clears the error message Change the tor to iar Restore the communications line and switch Lor back to r 949 1194 6 CONFIGURATION MENU DO NOT ENTER THE CONFIGURATION MENU UNLESS YOU HAVE BEEN INSTRUCTED TO BY THESE INSTRUCTIONS INCORRECT ENTRY OF DATA IN THE CONFIGURATION MENU MAY CAUSE IMPROPER OR UNPREDICTABLE OPERATION OF THE INSTRUMENT The Configuration Menu is used to quickly recover the instrument after certain Error Codes The configuration for your particular model is shown on the Model Serial label located on the left side when viewed from the front of the instrument housing A label found inside on the right side of the chassis shows the same information If you do recover the instrument from a FA a amp St error the memory con figuration is restored to the factory settings All hardware inputs and out puts are automatically recognized except for Options 924 926 and 928 If you have a instrument equipped with one of these options Factory Default will not automatically restore these settings They must be set by hand To re configure 1 At power up simultaneous
53. ocation of the displays and descriptors During normal operation the top four digit display indicates the temperature that is being read by the sensor The bottom display indicates the set point When you are programming the instrument the bottom display indicates the Menu Item being programmed and the top display the value selected for that Menu Item Error messages use both the top and bottom displays to indicate a particular error Each character can only be displayed with seven light segments Alphabet characters may look peculiar when seen presented this way The following is an example of the seven segment alphabet as used in the instrument ABCDEFGHtHIHsdJSKLUMNOPQRS TUVWXYZ AeCPG EF GH IJ L vnBP GStuus 012345678 9 91234956749 Notice that some characters are in upper case while others are in lower case Some look the same e g G 4 and 9 f and must be interpreted by context Others are close e g B 4 and 6 45 but different Usually the context of the term or value will help you determine the correct character 949 1194 6 Page 14 of 52 October 2005 THE HOME DISPLAY The home display is the normal display while the control is operating If no errors or functions are active the HOME display will indicate the Process Variable the temperature pressure flow RH etc that is being measured on the top display and the Set Variable Set Point 1 on the bottom Items that can change the HOME display are th
54. of 52 949 1194 6 If AL If Ae A ik AIP Ala d Do D AiL AiL or Hike High and Low Alarms Both 4 iLa and 4 it appear in the Secondary Menu and share the same Alarm 1 Relay output Elink Alarm 1 is controlled by the Ramp Soak program func tion See pages 15 18 and 29 i for further informa tion is set to GFF goto AL next page is set to Ent go to A St below Alarm 1 Type Select 465 or dE AS Absolute Alarm that may be set anywhere within the values of SCAL and SfAH and is independent of 57 dE Deviation Alarm that may be set as an offset from 4 i As 5F iis changed the Alarm Point will track with 57 A devia tion alarm will also track any active ramp or soak set point Alarm 1 Reset Select Half or Hold Gate Automatic Reset Haid Manual Reset Reset acknowledge by simultaneously pressing the J amp INDEX amp DOWN ARROW keys for 3 seconds Alarm 1 Power Interrupt Select fn or GFF Gn Alarm Power Interrupt is a GEF Alarm Power Interrupt is GFF Alarm 1 Inhibit Select a or GFF Gn Alarm Inhibit is 44 Alarm action is suspended until the process value first enters a non alarm condition GEF Alarm Inhibit is GFF Alarm 1 Output State Select 195 or GF En ELOS Closes Contacts at Alarm Set Point OP En Opens Contacts at Alarm Set Point Alarm 1 Lamp Select on or GaFF fan Alarm Lamp is ON when alarm contact is closed Gof F Alarm Lamp is OFF when
55. onds AZP Alarm 2 Power Interrupt Select amp or GFF Gn Alarm Power Interrupt is a GEF Alarm Power Interrupt is GFF Ad Alarm 2 Inhibit Select a or GFF Gn Alarm Inhibit is 44 Alarm action is suspended until the process value first enters a non alarm condition GFF Alarm Inhibit is GFF o DI Ww eo Alarm 2 Output State Select 15 or GFEn ELOS Closes Contacts at Alarm Set Point OP En Opens Contacts at Alarm Set Point October 2005 Page 39 of 52 949 1194 6 Alarm 2 Lamp Select on or GaFF fan Alarm Lamp is ON when alarm contact is closed laff Alarm Lamp is OFF when alarm contact is closed Alarm 2 Loop Break Select la or GFF Gn Loop Break Condition will cause an Alarm Condition OFF Loop Break will not affect the Alarm Condition Option 948 4 Stage Set Point Switch Action Select r amp or int rE Set Point Stage selected by external contact closures ink Set Point Stage selected by internal menu selection See 57 menu item in Secondary Menu Option 992 993 995 996 Serial Communications Control Address Set from to 3 F for Options 992 and 993 Set from i to FF for Options 995 and 995 This number hexadecimal base 16 must match the address number used by the host computer Power to instrument must be turned off and on before change takes effect see Page 21 Option 992 993 995 996 Serial Communications Communi cation Baud Rate Select 300 i290 2400 4890 9500 baud 19 2 or
56. ounts For Current and Voltage inputs this will set the low range end Value not adjust able for Thermocouple and RTD ranges LA 3 Scale High Select 100 to 11998 counts above 5241 The total span between SLA and 5 44 must be within 11998 counts Maxi mum setting range is 1999 to 9999 counts For Current and Voltage inputs this will set the high range end Value not adjust able for Thermocouple and RTD ranges wm a r Set Point Low Select from the lowest input range value to 5FfH value This will set the minimum SP1 or SP2 value that can be entered The value for SP1 or SP2 will stop moving when this value is reached GPH Set Point High Select from the highest input range value to L value This will set the maximum SP1 or SP2 value that can be entered The value for SP1 or SP2 will stop moving when this value is reached Set Point 1 State Select d ir or r ow Direct Action As the input increases the output will increase Most commonly used in cooling processes Reverse Action As the input increases the output will decrease Most commonly used in heating processes Ww a m rE October 2005 Page 33 of 52 949 1194 6 If Gut i Page 19 is set for LP PLUL or Prof then 58 and 5 iH appear If Gut fis set for Balf then skip to ir mm Oh Set Point Output Low Limit Select to 42 but not greater than 5 iG4 This item limits the lowest output value This is useful for adding a bias to t
57. r counts Pod Proportional Band Bandwidth Select to 9999 F C or counts Appears only if control is equipped with second set point and fute is NOT selected as nF E5 Option 948 4 Stage Set Point or r S Automatic Reset Time Select GFF amp i to 95 minutes Select GFF to switch to GF5 375 Option 948 4 Stage Set Pani GES Manual Offset Correction Select GFF 2 to 93 9 percent Select GFF to switch to oe E Option 948 4 Stage Set Point or rte Rate Time Select FF 2 0 i to 99 99 minutes wo Derivative Sud PID values are preset for a slow response process nar PID values are preset for a normal response process FASE PID values are preset for a fast response process P ide Linkage of PID parameters between SP1 and SP2 Select a or ne E Gn Applies SP1 5 rt Find and Frt terms to SP2 for heat cool ie GEF SP2 functions without 5 ct Fhad and FrEE Aru Anti Reset Windup Feature Select Ha or GFF Gn When ru is Ga the accumulated Reset Offset value will be cleared to 0 when the process input is not within the Proportional Band When 4 u is GFF the accumulated Reset Offset Value is retained in memory when the process input is not within the Proportional Band eon D y October 2005 Page 27 of 52 949 1194 6 Arke UAL Approach Rate Time Select GFF 24 to 99 99 minutes The function defines the amount of Rate applied when the input is outside of the Proportional
58. rther away the PV is from the set point the greater the bump or upset there will be in the output SELF TUNE FUNCTION Self Tune allows automatic selection of the necessary parameters to achieve best control operation from your 2600 Series control If you are using the contro output as a simple on off function Gut set for 8nGF none of the following will apply Theory of Operation The Self Tune function calculates the Pb ES and tE parameters under the Pid tum selection and the Find and FrEE parameters as shown in the Secondary Menu These values are determined by measuring the response of the process connected to the control When Self Tune is started the control temporarily acts as an on off control While in this mode the control measures the overshoot and undershoot of the process and the period of the process the time from peak value to the next peak value These measurements are collected over a period that lasts three periods of overshoot and undershoot The data collected over this time is then compared and calculated into final PID and Fuzzy Logic values The effect of Fuzzy Logic on the process is still controlled by the F nt fuzzy intensity setting If F nt is Q the Food and Frt will be calculated but will 949 1194 6 Page 18 of 52 October 2005 have no effect The calculations for the PID values are the same as used in the standard Ziegler Nichols equations that have been recognized as standard
59. rupt is Sa Output will automatically reset on power up if no alarm condition exists GFF Alarm Power Interrupt is amp 7F Output will be in the alarm condition on power up regardless of condition of process SiH Set Point 1 Inhibit Select a or GFF Gn Alarm Inhibit is a Alarm action is suspended until the process value first enters a non alarm condition OFF Alarm Inhibit is GFF 949 1194 6 Page 34 of 52 October 2005 SP Set Point Lamp Select 4 an or GaFF Gan Lamp ON when Output is ON Goh F Lamp OFF when Output is ON If your control is not equipped with Set Point 2 then proceed to the alarm section next page Sek Set Point 2 type Select 455 or dE Ab Absolute 572 582 is independent of 57 i and may be set anywhere between the limits of 571 and SPH JE Deviation 572 572 is set as a deviation from SF and allows 57 to retain its relationship with 57 when 57 is changed 5F tracks 5 i Sc St Set Point 2 State Select dur or r dur Direct Action As the input increases the output will increase Most commonly used in cooling processes rE Reverse Action As the input increases the output will decrease Most commonly used in heating processes If Duke is set for EP PUL or Praf then S20 and S294 appear If Ouke is set for Ga8F then skip 52 and Scau Sei Set Point Output Low Limit Select to 55 but not greater than 52GH This item limits the lowest output value This is useful for ad
60. ss the INDEX key to display Unt Press the E DOWN ARROW until the display shows Press ENTER Next press the INDEX key until 574 is displayed pass the dft inft and 5 amp nf selections Press the 8 UP ARROW until the display shows G Press ENTER Finally press INDEX key to display 5P Press the amp amp DOWN ARROW until the display shows 322 Press ENTER The necessary program changes are now complete After 30 seconds the display will switch back to the temperature reading If you want to return faster press the 8 UP ARROW and ENTER keys at the same time and then press the amp DOWN ARROW and INDEX keys again at the same time This will back out of the menu and immediately display the temperature reading If you want to use Self Tune Auto Manual or the Ramp Soak Program mer features see the special sections on these items Page numbers for these are in the Contents section on the previous page October 2005 Page 3 of 52 949 1194 6 MODEL IDENTIFICATION 26 L I L Options blank if none Alarm Output A Output B 0 No 1 SSR 0 None 1 Yes 3 Relay 1 SSR 5 Current 3 Relay 5 Current Note Switched15 VDC output standard on Output 1 or Output 3 Option Description 924 Analog Remote Set Point 0 to 10 VDC scalable 926 Analog Remote Set Point 0 to 20 mADC scalable may be pro grammed for 1 to 5mA 4 to 20 mA etc 928 Analog Remote Set Point 0 to 10 000 ohms scalable
61. ssed for a period of 30 seconds the display will return to the HOME position displaying the temperature value While in the Secure Menu if no key is pressed for a period of 60 seconds the display will return to the HOME position display ing the temperature value Outputs are disabled turned off when the Secure Menu is active NOTE To move to the Primary Menu quickly from any other menu press the ES UP ARROW amp ENTER keys followed by pressing the amp INDEX amp DOWN ARROW keys SECURITY LEVEL SELECTION Four levels of security are provided The display shows the current secu rity level To change security levels change the password value using the T3 UP ARROW and amp DOWN ARROW keys and press the ENTER key Refer to the password table following for the correct value to enter for the security level desired The 5 menu item security level may be viewed or changed at any time regardless of the present security level To set the access level to for example at the 5 menu item press the S UP ARROW key until the upper display shows the password for level 2 access ii Press the ENTER key The display will blink and return with the level value 2 in the upper display The password values shown in the table cannot be altered so retain a copy of these pages for future reference This is the only reference made to password values in this instruction book PASSWORD TABLE ecurity Level Menu Status Primary Lo
62. ugh to be unreadable A setting of 2 is usually sufficient filtering 2 represents approximately a 1 second time constant When the 0 1 degree resolution is selected this should be increased to 4 If this value is set too high controllability will suffer Loop Break Protection Select GFF to 9999 seconds If during operation the output is minimum 0 or maximum 100 and the input moves less than 5 F 3 C or 5 counts over the time set for LPbr the LOGE bf message will appear This condition can also be routed to an Alarm Condition if alarms are present and turned On see ALbr in the Secure Menu The loop break error can be reset by pressing the ENTER key when at the F menu item The INDEX amp ENTER keys may also be used Option 934 936 Analog Retransmission Output Process Output Low Select 450 F 260 C or 1999 counts to any value less than FGH Option 934 936 Analog Retransmission Output Process Output High Select from any value greater than PSL to 9999 F 5530 C or 9999 counts Option 934 936 Analog Retransmission Output Process Output Source Select inf or SP in Output follows the Process Variable input SPE Output follows the Set Variable Option 924 926 928 Analog Remote Set Point Remote Set Point Select Gn or GFF GEF The control uses the value set for 5 i Gn The control uses the value set by the analog remote set point signal as established by the Secure Menu items rSfL
63. ximum Weight 454 g 16 oz Agency Approvals UL C UL E83725 CE Front Panel Rating IP66 UL Type 4X OPTIONS 924 Analog Remote Set Point Input O to 10 VDC Input Impedance 1 Meg Ohms Isolation Shares common ground with PV input Scale Programmable from 100 to 11998 counts depending on PV range selected 926 Analog Remote Set Point Input 0 to 20 mADC Input Impedance 10 Ohms Isolation Shares common ground with PV input Scale Programmable from 100 to 11998 counts depending on PV range selected 928 Analog Remote Set Point Input O to 10 000 ohms two wire Search Current 4 pA Isolation Shares common ground with PV input 934 Analog Retransmission of PV SV programmable Output 0 to 20 mADC into 600 Ohms maximum Isolation 500 VAC Scale Programmable from 100 to 11998 counts depending on PV range selected 936 Analog Retransmission of PV SV programmable Output 0 to 10 VDC 20 mA maximum Isolation 500 VAC Scale Programmable from 100 to 11998 counts depending on PV range selected 948 Four Stage Set Point Input Dry contact or Transistor switch NPN open collector type Current 1 mADC Isolation Shares common ground with PV input October 2005 Page 47 of 52 949 1194 6 992 RS 485 Series Communications Port Compliance EIA 485 Isolation 500 VAC Protocol Lovelink II Address Range 001H to 3FFH Baud Rates 300 1200 2400 4800 9600 19 2k 28 8k Mode Half duplex Character 8 bits

Download Pdf Manuals

image

Related Search

Related Contents

Zero DS Bedienungsanleitung  Samsung SWL-2200U User's Manual    取扱説明書 NS-HD597VP  VM 430 - Domyos  SonyEricsson-K700i  Based on file VP103BOOK.DOC. as template (Normal.dot)  2007 Riptide Owners Manual - Trident Pro ONLY.pub  14~25ページ(PDF:1.8MB)  Bedienungsanleitung  

Copyright © All rights reserved.
Failed to retrieve file