Gree Ducted GFH Installation

image

Contents

1. O 18 2 ga Breaker L N PE Power 220 240V 50 60Hz 24k 60k Figure 3 2 9 66 U Match Series DC Inverter Service Manual 5 Electric wiring of indoor unit side Remove the electric box cover from the electric box sub assy and then connect the wire Duct Type Unit gt Gp Lap an 2 0 H1 H2 P P G amp P 6p GP i C Electric box eet sub assy cove Figure 3 2 10 The F C O connect to the COMMOM CLOSE and OPEN terminal of the fresh air valve respectively N Warning The power cord and the wire of the fresh air valve are high voltage while the communication cord and connection wire of the wired controller are low voltage They should run separately against electromagnetic interference The high voltage and low voltage lines should pass through the rubber rings at different electric box covers Do not bundle the connection wire of the wired controller and the communication cord together or arrange them in parallel otherwise improper operation would occur The high voltage and low voltage lines should be fixed separately and securely with internal big clamps for the former and small clamps for the latter Tighten the indoor outdoor connection cord and power cord respectively on the termi
2. A CAUTION The maximum length of the duct means the maximum length of the supply air duct plus the maximum length of the return air duct The duct is rectangular and connected with the air inlet outlet of the indoor unit Among all supply air outlets at least one should be kept open 2 The default installation location of the rectangular flange is at the back and the return air cover plate is at the bottom as shown in Figure 3 1 21 Rectangular Flange Rear Return Air Figure 3 1 21 3 Ifthe bottom return air is desired just change the place of the rectangular flange and the return air cover plate 4 Connect one end of the return air duct to the return air outlet of the unit by rivets and the other to the return air louver For the sake of the convenience to freely adjust the height a cutting of canvas duct will be helpful which can be reinforced and folded by 8 iron wire 5 More noise is likely to be produced in the bottom return air mode than the backward return air mode so it is suggested to install a silencer and a static pressure box to minimize the noise 6 The installation method can be chosen with considering the conditions of the building and maintenance etc as shown in Figure 3 1 22 56 U Match Series DC Inverter Service Manual Z a rl LZ A S 7 lo Od eN Supply air SSe l Return air Install the return air duct b Figure 3
3. a Ba a 68
4. 1 22 Table 3 1 4 Installation of the return air duct No Name No Name Return Air Inlet with filter a Indoor unit 2 Grille 5 Supply Air Duct 3 Return Air Duct 2 OUTDOOR UNIT INSTALLATION 2 1 Before Installation After receiving the machine please check for any transport damage If finding any surface or internal damage please immediately report to the transport company or equipment company in writing After receiving the machine please check the unit and accessories in reference to the packing list Ensure that the model is correct and the machine is in good condition Please also check if the specification and quantity of accessory parts are correct Determine the correct handling route and methods thus to avoid damaging the unit or causing possible hazard For the sake of protection and safety it is suggested to move the unit with the packaging box Even though it is not permitted to do like this under special occasions do not remove the packaging box thus to avoid loosening or falling during handling Confirm if the installing foundation is solid When this unit is to be installed on the metal section of the building make sure that the electrical insulation must comply with applicable standards Ensure that the place of installation is far from the area where the inflammable or explosive substances are stored thus to avoid possible explosion or fire due to leakage 2 2 Installation Site A
5. 8 Inch 60 65 N m 1 2 Inch 45 50 N m 3 4 Inch 70 75 N m 7 8 Inch 80 85 N m N cautions Be sure to connect the gas pipe after connecting the liquid pipe completely 3 1 4 Connecting the Pipe at the Outdoor Side Unit Tighten the flare nut of the connection pipe at the outdoor unit valve connector The tightening method is the same as that as at the indoor side 3 1 5 Checking the Pipe Connections for Gas Leaking For both indoor and outdoor unit side check the joints for gas leaking by the use of a gas leakage detector without fail when the pipes are connected Gas pipe Liquid pipe Pipe coupling r Sore 3 way valve 2 way valve Figure 3 2 2 61 U Match Series DC Inverter Service Manual 3 1 6 Heat Insulation on the Pipe Joints Indoor Side Only Stick coupler heat insulation large and small to the place where connecting pipes Reference A Coupler heat insulation large on the pipe Front outlet Reference A Cover this portion with heat insulating material also without fail Coupler heat insulation small u on the pipe Te L LE Vly h 77 gt RER A No gap Heat insulation pipe Liquid pipe Gas pipe Figure 3 2 3 3 1 7 Vacuum and Gas Leakage Inspection AN cautions Do not purge the air with refrigerants but use a vacuum pump to vacuum the inst
6. Forthe units GFH60S3GI GFH60S3G1I I Bi m BE q 0 A 2 e u ae R i 7 H Table 3 1 1 Item Model A 2 c D E F G H l j GFH24S3GI GFH2ASaGIHI 1011 748 820 1115 1225 775 978 160 230 290 GFH36S3GI GFH36S3G11 GFH42S3GI GFH4283G11 1175 646 852 1150 1340 750 953 190 316 350 GFH48S3GI GFH48S3G1 GFH60S3GI GFH60S3G1I 1353 632 992 1150 192 340 1500 390 800 u Table 3 1 2 Installation Accessories List for Duct type Indoor Unit Name amp Shape QTY Notes Installation and Operating 4 Instructions Insulation materials for gas pipe 1 Used for gas pipe connector on indoor unit insulation jez for liquid 1 Used for liquid pipe connector on indoor unit Insulation materials for drainage 2 Used for wrapping the condensate pipe and pipe rubber plug Nut 1 To connect liquid pipe Nut 1 To connect gas pipe Nut M6 with gasket 8 Use for fixing the hanger hook Nut M10 with gasket 4 Use for fixing the hanger hook Nut M10 4 4 sets used for ceiling mounting of the indoor spring gasket 4 unit Hook 4 Used for ceiling mounting of the indoor unit Wired controller 1 Screw M4 2 To fix the base plate of wired controller an
7. Insulated drain hose Drain hose insulation Drain cap Unit Drain port Unit 7 Drain port m l f Omm Oinch A Omm Oinch Insulated drain hose l Drain cap Figure 3 1 13 Figure 3 1 14 There is adhesive on one side of the insulation so that after removing the protective paper over it the insulation can be directly attached to the drain hose 11 Considerations for the unit with the condensate pump 1 For the unit with the condensate pump only one drain port at the side close to the electric box is prepared and only through it the drain hose can be connected 2 See table 3 for the size of the drain port of the unit with the condensate pump which is different from that of the unit without the condensate pump 3 For the unit with the condensate pump two drain ports at the bottom are defaulted to be factory plugged with drain caps After the installation of the drain hose these two drain ports also need to be insulated properly with the same way aforementioned 4 The drain hose for the unit with the condensate pump should be arranged as shown in the figure below Ceiling lt 300mm 11 3 4inch Hoisting stand 1000 1500mm 39 3 8 59inch Drain hose attachment Drain raising 7 A hose qi lt 100mm 39 3 8inch Clamp attachment Figure 3 1 15 The vertical height of the drain hose should be 75mm or less so that it is unnecessary for the a drain port to withstand add
8. U Match Series DC Inverter Service Manual Level Instrument 7 wh N a 5 he 4 Condensate hie ee Aink Ses Asus Drainpipes E Ir Intake fiot ir Supply I et Enlarged View As the inside of the unit is in the negative Condensate Drainpipe pressure status it is required to set up a backwater elbow The requirements is E A B2 0 145P 10000 20 25 4 inch lt m P is the absolute pressure inside the unit D The unit of the pressure is psig Figure 3 1 5 1 1 4 Dimension Data Forthe units GFH24S3GI GFH24S3G11 E Gas Pipe Liquid Pipe Max Air Intake 5 Il les I Ze Drainage Pipe Electric Box i NR ERDE Pa T oO iw amp P gt ers E Cc w T y D z G T For the units GFH36S3GI GFH36S3G11 GFH42S3GI GFH42S3G11 GFH48S3GI1 GFH48S3G1 F z 3 Fal In Fr mo lie 4 Be Figure 3 1 6 50 U Match Series DC Inverter Service Manual
9. 2 U Match Series DC Inverter Service Manual As the inside of the unit is in the negative pressure status it is required S to set up a backwater elbow The Enlarged View requirements is A B2 0 145P 10000 20 25 4 inch P is the absolute pressure inside the a O unit The unit of the pressure is psig a Ta 4 Condensate Drainpipe Figure 3 1 11 5 Use a suitable drain hose and see Table 3 2 4 for its size 6 There is a drain port on both the left and right sides Select the drain port to match the local conditions Figure 3 1 10 7 When the unit is shipped from the factory the drain port is defaulted to be the one on the left side electric box side the port on right side has been plugged 8 When using the drain port on the right side of the unit reinstall the drain cap to the left side drain port Figure 3 1 12 Drain port Drain cap Fastener Figure 3 1 12 IN CAUTION Always check that the drain cap is installed to the unused drain port and is fastened with the nylon fastener If the drain cap is not installed or is not sufficiently fastened by the nylon fastener water may drip during the cooling operation 9 Be sure to insulate where the drain port and the drain hose is connected Figure 3 1 13 10 The unused drain port also should be insulated properly Figure 3 1 14 53 U Match Series DC Inverter Service Manual Drain hose insulation
10. Caution for Installation The outdoor unit shall be so installed that the air discharged out of the outdoor unit will not flow back and that enough space shall be maintained around the machine for repair The installing position shall be in good ventilation so that the machine can breathe and exhaust enough air Ensure that there is no obstruction at the inlet and outlet of the machine If any please remove the obstructions blocking the air inlet and outlet If the outdoor unit is installed on concrete or solid ground it shall be fixed by using M10 bolts and nuts And ensure that the machine is kept vertical and horizontal The outdoor unit must be lifted by using the designated lift hole During lifting take care to protect the air conditioner and avoid knocking the metal parts thus to prevent rusting in the future To meet the noise and vibration requirements the outdoor unit shall be installed by using rubber damping pad or spring damper To install the drainage pipe please insert the drainage joint to the drainage hole on the outdoor chassis and connect a drainage pipe on the drainage joint The installing height of outdoor unit shall be at least 5cm if drainage joint is to be used To insert the pipe through the wall the wall cross tube must be installed The installing dimension shall comply with the installation requirements in these instructions The outdoor unit must be fixed at the installing position The installation shall be do
11. U Match Series DC Inverter Service Manual INSTALLATION 47 U Match Series DC Inverter Service Manual INSTALLATION 1 INDOOR UNIT INSTALLATION 1 1 Installation of Duct Type 1 1 1 Before Installation After receiving the machine please check for any transport damage If finding any surface or internal damage please immediately report to the transport company or equipment company in writing After receiving the machine please check the unit and accessories in reference to the packing list Ensure that the model is correct and the machine is in good condition Please also check if the specification and quantity of accessory parts are correct Determine the correct handling route and methods thus to avoid damaging the unit or causing possible hazard For the sake of protection and safety it is suggested to move the unit with the packaging box Even though it is not permitted to do like this under special occasions do not remove the packaging box thus to avoid loosening or falling during handling Confirm if the installing foundation is solid When this unit is to be installed on the metal section of the building make sure that the electrical insulation must comply with applicable standards Ensure that the place of installation is far from the area where the inflammable or explosive substances are stored thus to avoid possible explosion or fire due to leakage 1 1 2 Installation Site Ensure the top hanging piece has strong strengt
12. WARNING Install the unit where it will not be tilted by more than 5 During installation if the outdoor unit has to be exposed to strong wind it must be fixed securely If possible do not install the unit where it will be exposed to direct sunlight If necessary install a blind that does not interfere with the air flow 1 Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible 2 Install the outdoor unit where it is convenient to connect with the indoor unit 3 Install the outdoor unit where the condensate water can be drained out freely during heating 57 U Match Series DC Inverter Service Manual operation Do not place animals and plants in the path of the warm air Take the air conditioner weight into account and select a place where noise and vibration are Zus OE small Install the outdoor unit where is capable of withstanding the weight of the unit and generates as 2 less noise and vibration as possible Provide the space shown in Figure 3 2 1 so that the air flow is not blocked Also for efficient 7 operation leave three of four directions of peripheral constructions open ES 0000000 GE ETE eles E8 ES ES ES 85 E8 S fi gn Be RN eS gt 2000mm SA eee EE Ar a A 1 2 3feet gt 2000mm i 6 5 9feet Figure 3 2 1 2 3
13. a special receptacle to supply power to the air conditioner Use a special branch circuit breaker and receptacle matched to the capacity of the air conditioner The special branch circuit breaker is installed in the permanent wiring Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3 mm between the contacts of each pole Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively O 8 8 8 8 8 Install a leakage special branch circuit breaker in accordance with the related laws and regulations and electric company standards N Cautions The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances When the current contracted capacity is insufficient change the contracted capacity When the voltage is low and the air conditioner is difficult to start contact the power company to raise the voltage 4 2 Electrical Wiring 1 For solid core wiring Figure 3 2 6 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation about 25 mm 15 16 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using pliers bend the solid wire to form a loop suitable for the terminal screw 64 U Match Series DC Inverter Service Manual 4 Shape the loop wire properly p
14. allation There is no extra refrigerant in the outdoor unit for air purging 3 1 7 1 s N YS HS So Vacuum Remove the caps of the liquid valve gas valve and also the service port Connect the hose at the low pressure side of the manifold valve assembly to the service port of the unit s gas valve and meanwhile the gas and liquid valves should be kept closed in case of refrigerant leak Connect the hose used for evacuation to the vacuum pump Open the switch at the lower pressure side of the manifold valve assembly and start the vacuum pump Meanwhile the switch at the high pressure side of the manifold valve assembly should be kept closed otherwise evacuation would fail The evacuation duration depends on the unit s capacity generally 30 minutes for the 24 36k units 45 minutes for the 42 48 60 units And verify if the pressure gauge at the low pressure side of the manifold valve assembly reads 1 0Mp 75cmHg if not it indicates there is leak somewhere Then close the switch fully and then stop the vacuum pump Wait for some time to see if the system pressure can remain unchanged 5 minutes for the 24 36k units 10 minutes for the units more than 42k During this time the reading of the pressure gauge at the low pressure side can not be larger than 0 005Mp 0 38cmHg Slightly open the liquid valve and let some refrigerant go to the connection pipe to balance the pressure inside and outside of the connect
15. d installation hole of the wall together 51 U Match Series DC Inverter Service Manual 1 1 5 Installation Clearance Data PA oe FE A Pa A A Nut with Nut Spring J Washer Washer fo ste Tete u Jy g fp a gt 250mm gt 250mm 9 7 8inch 9 7 8inch ES Ec SS OS ae AS Figure 3 1 7 Warning The height of installation for the indoor unit should be 2 5m above 1 1 6 Drain Piping Work IN CAUTION Installation of Drainage Pipeline Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enough to prevent condensation Problems with the piping may lead to water leaks 1 Install the drain hose with downward gradient 1 50 to 1 100 and no risers or traps are used for the hose Figure 3 1 8 2 Be sure there is no crack or leak on the drain hose to avoid the formation of air pocket Figure 3 1 8 3 When the hose is long install supporters Figure 3 1 9 4 Always use the drain hose which has been insulated properly 4 A Drain hose J Trap Arrange the drain hose x lower than this drain port Rise L Air bleeding x x Figure 3 1 8 WB MLL MLM i 3 I Q Supporter 1 1 5m 3 2 7 5feet Drain hose Figure 3 1 9 Figure 3 1 10 5
16. e connection cords firmly to the terminal block Imperfect installation may cause a fire Always fasten the outside covering of the connection cord with cord clamps If the insulator is not clamped electric leakage may occur Always connect the ground wire 65 U Match Series DC Inverter Service Manual 4 Electric wiring between the indoor and outdoor units si 1 ngle phase units Separate Power Supply for indoor unit and outdoor unit Outdoor Unit Indoor Unit LIINTL2IN2 up LN PE Power 220 240V 50 60Hz 24k 60k Power 220 240V 50 60Hz GUHD24NS3G0 GFH24S3GI GFH24S3G11 Power cord 3x2 5mm HO7RN F Power cord 3x1 0mm HO5RN F Communication Cords 2x0 75mm HO5RN F GUHD36NS3GO GFH36S3GI GFH36S3G1 GUHD42NS3G0 GFH42S3GI GFH42S83G11 Power cord 3x4 0mm HO7RN F Power cord 3x1 0mm HO5RN F Communication Cords 2x0 75mm HO5RN F GUHD48NS3GO0 GFH48S3GI GFH48S3G1 GUHD60NS3GO GFH60S3GI GFH60S3G1 Power cord 3x6 0mm HO7RN F Power cord 3x1 0mm HO5RN F Communication Cords 2x0 75mm HO5RN F 2 The Power supply for indoor unitis from outdoor unit Outdoor Unit 3 Indoor Unit E L1 N1 L2 N2 aie
17. ering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut until the connection pipe is to be connected so as to prevent dust and impurities from coming into the pipe system When connecting the pipe to the unit or removing it from the unit please do use both the spanner and the torque wrench Figure 3 2 6 When connecting smear both inside and outside of the flare nut with refrigeration oil screw it hand tight and then tighten it with the spanner Refer to Table 10 to check if the wrench has been tightened properly too tight would mangle the nut and lead to leakage Examine the connection pipe to see if it leaks then take the treatment of heat insulation as shown in the Figure 3 2 6 Use the medium sized sponge to insulate the coupler of the gas pipe 60 U Match Series DC Inverter Service Manual Sponge Threaded fastener x4 y Heat insulation sheath er for the liquid tube N D Heat insulation sheath gt for the gas tube Gas inlet pipe Liquid pipe Copper piping Oil applied to reduce friction with the flare nut Torque wrench 7 u Spanner k 3 Flare nut Oil applied improves seal air tightness Flare nut Piping union Figure 3 2 6 Table 3 2 2 Flare nut tightening torque Pipe Diameter Tightening Torque 1 4 Inch 15 30 N m 3 8 Inch 35 40 N m 5
18. ger gt Ll Figure 3 1 1 Figure 3 1 2 Hook Screw Nut a Nut Figure 3 1 3 Install the hanger onto the indoor unit as Figure 3 1 2 and Figure 3 1 3 shows Install the indoor unit at the ceiling as Figure Figure 3 1 4 shows fe S oo Screw N LEK Hanger Co Nut amp vl a FD EN ees Air Intake in Air Supply 4 H i Detail Figure 3 1 4 Precautions for unfavorable installation The preparation of all pipes connecting pipes and drainage pipes and cables connecting lines of wire controller indoor unit and outdoor unit must be ready before the installation so as to achieve smooth installation Drill an opening on the ceiling Maybe it is required to support the ceiling to ensure the evenness of it and avoid the vibration of it Consult with the user or a construction company for details In case the strength of ceiling is not enough use angle iron sections to set up a beam support Place the unit at the beam and fix it Level inspection of the indoor unit After the indoor unit is installed it is required to check the level of the whole unit The unit must be placed horizontally but the condensate pipe shall be installed obliquely so as to facilitate the drainage of condensate 49
19. h to withstand the weight of the unit The drainage pipe has convenient flow of water There is no obstacle blocking the return air inlet and exhaust outlet so as to ensure sound air circulation The installation spaces required by the drawing must be ensured so as to provide enough space for the service and maintenance The installation site must be far away from heat source leakage of inflammable gas or smoke The indoor unit is of ceiling mount indoor unit is hidden inside the ceiling The indoor and outdoor units the power cable and the connecting electrical lines must be at least 1 meter from any TV set or radio This is to avoid image interference or noise of the TV set or radio Even if the distance is 1 meter noise can also exist if there is strong electric wave 1 1 3 Caution for Installation Generally the unit is installed indoor on ceiling For ceiling mounting ensure that the hangers on ceiling have adequate strength to support the weight of the unit To meet the noise and vibration requirements the unit shall be installed by using rubber pad thickness 220mm and rubber connector Insert a M10 expansion bolt into the hole Drive a nail into the bolt Refer to the profile dimensions drawing of the indoor unit for the distance between the holes Refer to Figure 3 1 1 for the installation of the expansion bolt 48 U Match Series DC Inverter Service Manual H Ceiling mount Screw Y Air conditioning Unit Han
20. ion pipe so that air will not come into the connection pipe when removing the hose Note that the gas and liquid valve can be opened fully only after the manifold valve assembly is removed Place back the caps of the liquid valve gas valve and also the service port 62 U Match Series DC Inverter Service Manual Pressure gauge Low pressure gauge manifold en m g fs ken M Pressure gauge Hi pressure RS Switch Low pressure A Less m Switch Hi pressure i Connection pipe to indoor unit n Y l Connection pipe ou BA Cap Low pressure gauge Liquid valve N H D ma O igh pressure gauge N N E FA 9 Gauge manifold kit Gas valve RN Service pipe 4 S Xe i SNAC valve Service port Hose lt ap Qoram N Hose with the valve pin Cap Vacuum pump a Vacuum pump Figure 3 2 4 Note For the large sized unit it has the service port for both the gas valve and the liquid valve During evacuation it is available to connect two hoses of the manifold valve assembly to two service ports to quicken the evacuating speed 3 1 7 2 Additional Charge Refrigerant suitable for a piping length of 7 5m is charged in the outdoor unit at the factory When the piping is longer than 9 5 m additional charging is necessary For the additional amount see Table 3 2 3 Table 3 2 3 Model Additional Refrigerant Amount for Extra Item Pipe 24 60K 60g m When the height difference between
21. itional force Drain hose attachment 5 ES n hye t gS 5 vg N Figure 3 1 16 b When multiple drain hoses are used their installation should be performed as shown in the figure below 54 U Match Series DC Inverter Service Manual 2100mm 3 7 8inch T joint converging drain pipes t 1 4 44 0 1000mm 0 39 3 8inch T joint converging drain pipes BER j ji Figure 3 1 17 1 1 7 Installation of air duct Dimensions of the Supply Air Outlet Return Air Inlet 21mm 7 8inch re Lms B Figure 3 1 18 Supply Air Outlet C Figure 3 1 19 Return Air Inlet Table 3 1 3 Item Supply Air Outlet Return Air Inlet Model A B CG D a 158 818 950 206 5 ci 190 850 941 286 ah a 190 850 941 286 ip Be 190 850 941 286 a 190 990 1108 288 55 U Match Series DC Inverter Service Manual 1 1 8 Installation of the Supply Air Duct 1 Installation of the Rectangular Duct Air Intake gt 7 Air Intake Air supply No Name No Name 1 Hanger 5 Filter 2 AirintakePipe 6 Main Air Supply Pipe 3 Canvas Air Pipe 7 Air Supply Outlet 4 Air Intake Figure 3 1 20
22. lace it on the terminal board and tighten securely with the terminal screw using a screwdriver 2 For strand wiring Figure 3 2 6 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation about 10 mm 3 8 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using around terminal fastener or pliers securely clamp a round terminal to each stripped wire end 4 Position the round terminal wire and replace and tighten the terminal screw with a screwdriver Figure 3 2 7 A Solid wire B Strand wire A Solderless 5 Fr terminal xN IN Ee og X Eu J i Lo N T 8 m KS z Insulation layer 5 Figure 3 2 6 Screw with Screw with special washer special washer Round Ke Insulation tube terminal p Round IS f terminal AN i TPP 77 Tem 2 SE IS L Vz Pau 7 fe Insulation tube Z 7 Q Z Wire Cord clamp Wire F Figure 3 2 7 Figure 3 2 8 3 How to fix connection cord and power cord by cord clamp After passing the connection cord and power cord through the insulation tube fasten it with the cord clamp Figure 3 2 8 N Warning Before starting work check that power is not being supplied to the indoor unit and outdoor unit Match the terminal block numbers and connection cord colors with those of the indoor unit side Erroneous wiring may cause burning of the electric parts Connect th
23. nal boards with screws Faulty connection may cause a fire If the indoor unit connection cord to the outdoor unit and power supply are wired incorrectly the air conditioner may be damaged Connect the indoor unit connection cord properly based on the corresponding marks as shown in Figure 3 2 9 Ground both the indoor and outdoor units by attaching a ground wire Unit shall be grounded in compliance with the applicable local and national codes 6 Electric wiring of outdoor unit side Note When connecting the power supply cord make sure that the phase of the power supply matches with the exact terminal board If not the compressor will rotate reversely and run improperly Remove the big handle 24k front board 36 60k of the outdoor unit and insert the end of the communication cord and the power cable into the terminal board Single phase 1 Separate Power Supply for indoor unit and outdoor unit 24k 60k Figure 3 2 13 67 U Match Series DC Inverter Service Manual 2 The Power supply for indoor unitis from outdoor unit ower suppl to indoor unit x Power lines should go along the right side plate Communication lines between indoor and outdoor units also should go along the right side plate and keep away from power lines a LLIT Z
24. ne by specialist technicians 58 U Match Series DC Inverter Service Manual 2 4 Dimension Data ia __ a je I _ _ ll IHN fp En N i U Mk E N R KL ij BEE A ih w i i Figure 3 2 2 Table 3 2 1 Unit mm Item Model A B C D E GUHD24NS3GO 1005 425 790 610 391 GUHD36NS3GO 1105 440 1105 631 401 GUHD42NS3GO GUHD48NS3GO 1085 425 1365 620 393 GUHD60NS3GO 3 REFRIGERATION PIPING WORK 3 1 Refrigeration Piping Work Procedures and Caution in Connecting 3 1 1 Flare Processing 1 Cut the connection pipe with the pipe cutter and remove the burrs 2 Hold the pipe downward to prevent cuttings from entering the pipe 3 Remove the flare nuts at the stop valve of the outdoor unit and inside the accessory bag of the ind
25. oor unit then insert them to the connection pipe after that flare the connection pipe with a flaring tool 4 Check if the flare part is soread evenly and there are no cracks see Figure 3 2 3 90 H1 3 Figure 3 2 3 59 U Match Series DC Inverter Service Manual 3 1 2 Bending Pipes 1 The pipes are shaped by your hands Be careful not to collapse them gt Extend the pipe by unwinding it Figure 3 2 4 2 Do not bend the pipes in an angle more than 90 3 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than three times 4 When bending the pipe do not bend it as is The pipe will be collapsed In this case cut the heat insulating pipe with a sharp cutter as shown in Figure 3 2 5 and bend it after exposing the pipe After bending the pipe as you want be sure to put the heat insulating pipe back on the pipe and secure it with tape Heat eee Cutt line E LJ Figure 3 2 5 ACAUTION To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 150mm or over If the pipe is bent repeatedly at the same place it will break 3 1 3 Connecting the Pipe at the Indoor Unit Side Detach the caps and plugs from the pipes ACAUTION Be sure to apply the pipe against the port on the indoor unit correctly If the cent
26. the indoor unit and outdoor unit is larger than 10 meters an oil bend should be employed for every 6 meters Outdoor Oil bend 6m Indoor Oil bend Figure 3 2 5 63 U Match Series DC Inverter Service Manual 3 2 Specification of Connection Pipe Table 3 2 4 Size of Fitting Pipe Max Height inch Max Difference between Drainage pipe Outer em Pipe Diameter x wall Indoor Unit and Mod FRE Length thickness Liquid Gas m Outdoor Unit ir m GFH24S3GI GFH24S3G11 GUHD24NS3GO 3 8 5 8 50 15 20X1 2 GFH36S3GI GFH36S311 GUHD36NS3GO 3 8 5 8 50 15 20X1 2 GFH42S3Gl GFH4283G1I GUHD42NS3GO 3 8 5 8 50 30 20X1 2 GFH48S3GI GFH48S3G1I GUHD48NS3GO 3 8 5 8 50 30 20X1 2 GFH60S3GI GFH60S3G1I GUHD60NS3GO 3 8 3 4 50 30 30X1 5 The connection pipe should be insulated with proper water proof insulating material The pipe wall thickness shall be 0 5 1 0 mm and the pipe wall shall be able to withstand the pressure of 6 0 MPa The longer the connecting pipe the lower the cooling and heating effect performs 4 ELECTRIC WIRING WORK 4 1 Wiring Precautions N Warning Before obtaining access to terminals all supply circuits must be disconnected The rated voltage of the unit is as shown as Table 1 4 1 and Table 1 4 2 Before turning on verify that the voltage is within the 198 264V range for single phrase unit Always use a special branch circuit and install