Home
Installation Manual PDF
Contents
1. MINUTES e If the pressure rises to 1000 microns or less and remains steady the system is considered leak free proceed to startup e If pressure rises above 1000 microns but holds steady be low 2000 microns moisture and or noncondensibles may be present the system may have small leak Return to step 2 If the same result is encountered check for leaks as previously indicated and repair as necessary then repeat evacuation e If pressure rises above 2000 microns a leak is present Check for leaks as previously indicated and repair as necessary then repeat evacuation Electrical Connections A WARNING HIGH VOLTAGE Disconnect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death due to electric shock Wiring must conform with NEC or CEC and all local codes Undersized wires could cause poor equipment performance equipment damage or fire AA WARNING To avoid the risk of fire or equipment damage use copper conductors NOTICE Units with rotary or reciprocating compressors and non bleed TXV s require Hard Start Kit The condensing unit rating plate lists pertinent electrical data necessary for proper electrical service and overcurrent protec tion Wires should be sized to limit voltage drop to 2 max from the main breaker or fuse panel to the condensing unit Con sult the NEC CEC and all local codes to determi
2. cylinder for faster charging partially immerse it in warm water Never fill a cylinder more than 80 full of liquid refrigerant Never add anything other than R 22 to an R 22 cylinder or R 410A to an R 410A cylinder The service equipment used must be listed or certified for the type of refrigerant used Store cylinders in a cool dry place Never use a cylinder as a platform or a roller A WARNING To avoid possible explosion use only returnable not disposable service cylinders when removing refrigerant from a system Ensure the cylinder is free of damage which could lead to leak or explosion Ensure the hydrostatic test date does not exceed 5 years Ensure the pressure rating meets or exceeds 400 lbs When in doubt do not use cylinder Refrigerant Lines AA Caution The compressor POE oil for R 410A units is extremely susceptible to moisture absorption and could cause compressor failure Do not leave system open to atmosphere any longer than necessary for installation Use only refrigerant grade dehydrated and sealed copper tubing to connect the condensing unit with the indoor evaporator After cutting the tubing install plugs to keep refrigerant tubing clean and dry prior to and during installation Tubing should always be cut square keeping ends round and free from burrs Clean the tubing to prevent contamination Do NOT let refrigerant lines come in direct contact with plumbing ductwork floor joists
3. gauge manifold to base valve service ports Run the system on low stage for two stage units for 10 minutes to allow pressures to stabilize then check subcooling and or superheat as detailed in the following sec tions Superheat Suct Line Temp Sat Suct Temp Subcooling Sat Liquid Temp Liquid Line Temp AQ CAUTION To prevent personal injury carefully connect and disconnect manifold gauge hoses Escaping liquid refrigerant can cause burns Do not vent refrigerant into the atmosphere Recover all refrigerant during system repair and before final unit disposal SYSTEM SUPERHEAT Outdoor Dry Bulb Temperature F Indoor Wet Bulb Temperature F SUPERHEAT FORM ULA SUCT LINE TEM P SAT SUCT TEM P TEM PERATURE CHART TEM PERATURE CHART SATURATED SUCTION SATURATED LIQUID aa pe D o e o f a oo e o u E w ea ie a NOTE SPECIFICATIONS AND PERFORM ANCE DATA LISTED HEREIN ARE SUBJECT CHANGE WITHOUT NOTICE Fixed Orifice b If subcooling is low and superheat is high add charge ae to raise subcooling to 7 to 9 F then check superheat 1 Temporarily install a thermometer 4 6 from the compres 9 p sor on the suction line Ensure the thermometer makes ad If subcooling and superheat are high adjust TXV valve equate contact and is
4. in the cooling cycle tion should have subcooling of 7 to 9 F and superheat of 7 to 9 F If subcooling and superheat are low adjust TXV to 7 to 9 F superheat then check subcooling NOTE To adjust superheat turn the valve stem clock wise to increase and counter clockwise to decrease Troubleshooting Information COOLING ANALYSIS CHART System Compressor Stuck No Cooling Unsatisfactory Cooling Heating Operating Pressures POSSIBLE CAUSE Test Method Remedy DOTS IN ANALYSIS GUIDE INDICATE POSSIBLE CAUSE Compressor will not start fan runs Comp Fan will not start Evaporator fan will not start Condenser fan will not start Compressor runs goes off on overload Compressor cycles on overload System runs continuously little cooling htg cool and then too warm Not cool enough on warm days Certain areas too cool others too warm System runs blows cold air in heating Unit will not terminate defrost Unit will not defrost Low suction pressure High suction pressure High head pressure Compressor is noisy System will not start Power Failure Test Voltage Blown Fuse nspect Fuse Size amp Type Unbalanced Power 3PH Test Voltage Loose Connection nspect Connection Tighten Shorted or Broken Wires Test Circuits With Ohmmeter Open Fan Overload Test Continuity of Overload Faulty Thermostat Test Continuity of Thermostat amp Wiring Faulty Transformer Check Contro
5. insulated for best possible readings to 7 to 9 F superheat then check subcooling Use vapor temperature to determine superheat d If subcooling is high and superheat is low adjust TXV 2 Refer to the superheat table provided for proper system su m 7 9 superheat ane remove charge to perheat Add charge to lower superheat or recover charge to ower the subcooling to 7 to 9 F raise superheat NOTE Do NOT adjust the charge based on suction pressure un Expansion Valve System less there is a gross undercharge NOTE Units matched with indoor coils equipped with non adjust able TXV should be charged by subcoolingonly NOTE Check the Schrader ports for leaks and tighten valve cores if necessary Install caps finger tight 1 Temporarily install a thermometer on the liquid line at the liquid line service valve and 4 6 from the compressor on Heat Pump Heating Cycle the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use lig The proper method of charging a heat pump in the heat mode is by uid line temperature to determine sub cooling and vapor weight with the additional charge adjustments for line size line temperature to determine superheat length and other system components For best results on out door units with TXVs superheat should be 2 5 at 4 6 from the 2 Check subcooling and superheat Systems with applica compressor Make final charge adjustments
6. then apply the detector to suspect areas If leaks are found repair them After repair repeat the pressure test If no leaks exist proceed to sys tem evacuation System Evacuation Condensing unit liquid and suction valves are closed to contain the charge within the unit The unit is shipped with the valve stems closed and caps installed Do not open valves until the system is evacuated A WARNING REFRIGERANT UNDER PRESSURE Failure to follow proper procedures may cause property damage personal injury or death NOTE Scroll compressors should never be used to evacuate or pump down a heat pump or air conditioning system Prolonged operation at suction pressures less than 20 psig for more than 5 seconds will result in overheating of the scrolls and primanent damage to the scroll tips drive bearings and internal seal 1 Connect the vacuum pump with 250 micron capability to the service valves 2 Evacuate the system to 250 microns or less using suction and liquid service valves Using both valves is necessary as some compressors create a mechanical seal separating the sides of the system 3 Close pump valve and hold vacuum for 10 minutes Typi cally pressure will rise during this period 5000 4500 4000 LEAK S PRESENT 3500 3000 2500 2000 CONDENSIBLES OR SMALL LEAK PRESENT VACUUM IN MICRONS 1000 NO LEAKS 500 NO CONDENSIBLES
7. 4 CONDENSING UNIT HEAT PUMP INSTALLATION amp SERVICE REFERENCE Important Safety Instructions The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards It isthe owner s and installer s responsibility to read and comply with all safety information and instructions accompanying these symbols Fail ure to heed safety information increases the risk of personal in jury property damage and or product damage A WARNING power sources may be present Failure to do so may HIGH VOLTAGE Disconnect ALL power before servicing Multiple sl cause property damage personal injury or death f WARNING ONLY individuals meeting the requirements at a minimum of an Entry Level Technician as specified by the Air Conditioning Heating and Refrigeration Institute AHRI may use this information Attempting to install or repair this unit without such background may result in product damage personal injury or death AX CAUTION Scroll equipped units should never be used to evacuate the air conditioning system Vacuums this low can cause internal electrical arcing resulting in a damaged or failed compressor Shipping Inspection Always keep the unit upright laying the unit on its side or top may cause equipment damage Shipping damage and subsequent in vestigation is the responsibility of the carrier Verify the model number specifications electrical ch
8. Low Voltage Connections The indoor transformer must supply 24 volt AC low voltage power to the outdoor section for the control wiring Cooling only units require 25VA minimum and heat pump units require 40VA mini mum Low voltage wiring for two stage units depends on the ther mostat used and the number of control wires between the indoor unit and the condensing unit Route control wires through the low voltage port and terminate in accordance with the wiring diagram provided inside the control panel cover SYSTEM COMPOSITE DIAGRAM HEAT PUMPS 10 KW amp BELOW HEAT PUMP BOOM TAI ea 18GA 7WRE CRO INDOOR UNIT wool yik Ot 1 L H R E E E uj 1 A L D tq A io E T N L BON R R RED UW r o i r Gonn G HGH GREEN p panna 4 4 i W w2 WHITE EOE Wp 1 A Beas ROSS SETE B BLHCH BLUE pia ac a a aca E asoa od eee EGJ OPTIONAL OUTDOOR THERMOSTAT CLOSE ON TEMPERATURE FALL 18 GA 6 WIRE NEEDED WHEN OT IS USED SYSTEM COMPOSITE DIAGRAM HEAT PUMPS ABOVE 10 KW TYPICAL H P HEAT PUMP ROOM THERMOSTAT 18 GA 7 WIRE INDOOR UNIT OPTIO
9. NAL OUTDOOR THERMOSTAT CLOSE ON TEMPERATURE FALL 18 GA 7 WIRE NEEDED WHEN TWO OT S ARE USED NOTES NOMENCLATURE 1 OUTDOOR THERMOSTAT 1 SHOULD BE THE 3 REMOVE WIRE WHEN USING OUT 4 TERMINAL BLOCK MARKINGS ARE FOR AMANA BRAND W WHITE COLOR CODES OT OUTDOOR THERMOSTAT OPTIONAL R RED FIRST TO CLOSE AND THE LAST TO OPEN EHR EMERGENCY HEAT RELAY OPTIONAL Y YELLOW 2 CONNECT WHITE AND BROWN WIRES FROM AIR BL BLUE HANDLER TOGETHER IF OT 2 IS NOT USED DOOR THERMOSTAT AIRHANDLERS G GREEN Thermostat with Low Voltage Wires to Heat Pump Unit System Start Up NOTE Units with crankcase heaters should have high voltage power energized for 24 hours prior to start up Heat pumps are equipped with a time temperature defrost control with field selectable defrost intervals of 30 60 or 90 minutes This setting should be adjusted at this time if needed The defrost control also has SmartShift technology which delays compressor operation at defrost initiation and termination If disabling this function is desired move the jumper from DLY to NORM onthe defrost control Adequate refrigerant charge for the matching HSVTC evaporator coil and 15 feet of lineset is supplied with the condensing unit If using evaporator coils other than HSVTC coil it may be necessary to add or remove refrigerant to attain proper charge If line set exceeds 15 feet in length refrigerant should be added at 6 oun
10. ORRECT THE PROBLEM IF YOU REPEATEDLY RESET THE BREAKER OR REPLACE THE FUSE WITHOUT HAVING THE PROBLEM CORRECTED YOU RUN THE RISK OF SEVERE EQUIPMENT DAMAGE 12 Check the electrical panel for tripped circuit breakers or failed fuses Reset the circuit breakers or replace fuses as necessary Check the disconnect switch near the indoor furnace or blower to confirm that it is closed Check for obstructions on the outdoor unit Confirm that it has not been covered on the sides or the top Remove any obstruction that can be safely removed If the unit is cov ered with dirt or debris call a qualified servicer to clean it Check for blockage of the indoor air inlets and outlets Confirm that they are open and have not been blocked by objects rugs curtains or furniture Check the filter If it is dirty clean or replace it Listen for any unusual noise s other than normal operat ing noise that might be coming from the outdoor unit If you hear unusual noise s coming from the unit call a quali fied servicer
11. aracteristics and accesso ries are correct prior to installation The distributor or manufac turer will not accept claims from dealers for transportation dam age or installation of incorrectly shipped units 100 4002 9 2013 INSTALLATION INSTRUCTIONS _ Ool o Codes amp Regulations This product is designed and manufactured to comply with na tional codes Installation in accordance with such codes and or prevailing local codes regulations is the responsibility of the in staller The manufacturer assumes no responsibility for equip ment installed in violation of any codes or regulations Rated performance is achieved after 72 hours of operation Rated per formance is delivered at the specified airflow See outdoor unit specification sheet for split system models or product specifica tion sheet for packaged and light commercial models Specifica tion sheets can be found at www daikincomfort com for Daikin brand products Within the website please select the residential or commercial products menu and then select the submenu for the type of product to be installed such as air conditioners or heat pumps to access a list of product pages that each contain links to that model s specification sheet The United States Environmental Protection Agency EPA has is sued various regulations regarding the introduction and disposal of refrigerants Failure to follow these regulations may harm the environment and can lead to the imposi
12. ation in selecting a location for the unit s is the angle to obstructions Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance Corner in stallations are strongly discouraged NOT RECOMMENDED Minimum Airflow Clearance C Moape a 8 MA This unit can be located at ground floor level or on flat roofs At ground floor level the unit must be on a solid level foundation that will not shift or settle To reduce the possibility of sound transmission the foundation slab should not be in contact with or be an integral part of the building foundation Ensure the foun dation is sufficient to support the unit A concrete slab raised above ground level provides a suitable base Rooftop Installations If it is necessary to install this unit on a roof structure ensure the roof structure can support the weight and that proper consider ation is given to the weather tight integrity of the roof Since the unit can vibrate during operation sound vibration transmission should be considered when installing the unit Vibration absorb ing pads or springs can be installed between the condensing unit legs or frame and the roof mounting assembly to reduce noise vibration NOTE These units require special location consideration in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pum
13. ces per foot of liquid line NOTE Charge should always be checked using superheat when using a piston and subcooling when using TXV equipped indoor coil to verify proper charge Open the suction service valve first If the liquid service valve is opened first oil from the compressor may be drawn into the in door coil TXV restricting refrigerant flow and affecting operation of the system AA CAUTION POSSIBLE REFRIGERANT LEAK To avoid a possible refrigerant leak open the service valves until the top of the stem is 1 8 from the retainer When opening valves with retainers open each valve only until the top of the stem is 1 8 from the retainer To avoid loss of refrigerant DO NOT apply pressure to the retainer When opening valves without a retainer remove service valve cap and insert a hex wrench into the valve stem and back out the stem by turning the hex wrench counterclockwise Open the valve until it contacts the rolled lip of the valve body NOTE These are not back seating valves It is not necessary to force the stem tightly against the rolled lip After the refrigerant charge has bled into the system open the liquid service valve The service valve cap is the secondary seal for the valve and must be properly tightened to prevent leaks Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap Tighten cap finger tight and then tighten additional 1 6 of aturn 1 wrench flat o
14. e system This may cause a blockage or failure of the metering device 3 After brazing quench the joints with water or a wet cloth to prevent overheating of the service valve 4 Ensure the filter drier paint finish is intact after brazing If the paint of the steel filter drier has been burned or chipped repaint or treat with a rust preventative This is especially important on suction line filter driers which are continually wet when the unit is operating NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed from refrigerant tubing NOTE Before brazing verify indoor piston size by checking the piston kit chart packaged with indoor unit Leak Testing Nitrogen or Nitrogen Traced WARNING To avoid the risk of fire or explosion never use oxygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve The pressure relief valve must be set to open at no more than 150 psig Pressure test the system using dry nitrogen and soapy water to locate leaks If you wish to use a leak detector charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure
15. higher than the top of the coil Mounting the condensing unit above the evaporator coil will not require an oil trap in the suction line at the evaporator except when the condensing unit is over 80 feet above the evaporator Refer to the latest revision of long line set guidelines TP 107 z Insulation is necessary to prevent condensation from forming and dropping from the suction line Armflex or satisfactory equivalent with 3 8 min wall thickness is recommended In severe conditions hot high humidity areas 1 2 insulation may be required Insulation must be installed in a manner which protects tubing from damage and contamination Where possible drain as much residual compressor oil from ex isting systems lines and traps pay close attention to low areas where oil may collect NOTE If changing refrigerant types ensure the indoor coil and metering device is compatible with the type of refrigerant being used otherwise the indoor coil must be replaced Burying Refrigerant Lines If burying refrigerant lines can not be avoided use the following checklist 1 Insulate liquid and suction lines separately 2 Enclose all underground portions of the refrigerant lines in waterproof material conduit or pipe sealing the ends where tubing enters exits the enclosure 3 If the lines must pass under o
16. l Circuit with Voltmeter Shorted or Open Capacitor Test Capacitor Internal Compressor Overload Open Test Con y of Overload Shorted or Grounded Compressor Test Mot indings Compressor Stuck Test Faulty Compressor Contactor Test Con y of Coil amp Contacts Faulty Fan Relay Test Continuity of Coil And Contacts Open Control Circuit Test Control Circuit with Voltmeter Low Voltage Test Voltage Faulty Evap Fan Motor Repair or Replace Shorted or Grounded Fan Motor st M otor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage of Refrigerant Test For Leaks Add Refrigerant Restricted Liquid Line Remove Restriction Replace Restricted Part Open Element or Limit on Elec Heater Test Heater Element and Controls Dirty Air Filter nspect Filter Clean or Replace Dirty Indoor Coil nspect Coil Clean Not enough air across Indoor Coil Check Blower Speed Duct Static Press Filter Too much air across Indoor Coil Reduce Blower Speed Overcharge of Refrigerant Recover Part of Charge Dirty Outdoor Coil nspect Coil Clean Noncondensibles Recover Charge Evacuate Recharge Recirculation of Condensing Air Remove Obstruction to Air Flow Infiltration of Outdoor Air Check Windows Doors Vent Fans Etc Improperly Located Thermostat Relocate Thermostat Air Flow Unbalanced Readjust Air Volume Dampers System Undersized Refigure Cooling Load Broken Internal Parts Replace Compressor Broken Valves Test Compressor Efficiency Inefficie
17. ne the correct wire gauge and length Local codes often require a disconnect switch located near the unit do not install the switch on the unit Refer to the installation instructions supplied with the indoor furnace air handler for spe cific wiring connections and indoor unit configuration Likewise consult the instructions packaged with the thermostat for mount ing and location information Overcurrent Protection The following overcurrent protection devices are approved for use e Time delay fuses e type circuit breakers These devices have sufficient time delay to permit the motor com pressor to start and accelerate its load Three Phase Compressor Rotation AA CAUTION Use care when handling scroll compressors Dome temperatures could be hot Three phase compressors are power phase dependent and can rotate in either direction Verify proper rotation for three phase compressors by ensuring the suction pressure drops and discharge pressure rises when the compressor is energized NOTE When operated in reverse a three phase scroll compressors is noisier and its current draw sub stantially reduced compared to marked values To correct disconnect power and switch any two leads at the unit contactor and re observe High Voltage Connections Route power supply and ground wires through the high voltage port and terminate in accordance with the wiring diagram pro vided inside the control panel cover
18. nt Compressor Test Compressor Efficiency Wrong Type Expansion Valve ace Valve Remove Restriction or Replace Expansion Device Oversized Expansion Valve Replace Valve Expansion Valve Bulb Loose Tighten Bulb Bracket Inoperative Expansion Valve Check Valve Operation Loose Hold down Bolts Tighten Bolts Faulty Reversing Valve Replace Valve or Solenoid Faulty Defrost Control Test Control Faulty Defrost Thermostat Test Defrost Thermostat Flowrator Not Seating Properly Check Flowrator amp Seat or Replace Flowrator Cooling or Heating Cycle Heat Pump Heating Cycle Only Heat Pump For detailed service information refer to the Remote Condensing Unit Service manual NOTICE Units with rotary or reciprocating compressors and non bleed TXV s require a Hard Start Kit THIS PAGE LEFT INTENTIONALLY BLANK 11 SPLIT SYSTEM 5 AIR CONDITIONING AND HEAT PUM P HOM 5 ROUTINE MAINTENANCE RECOM MENDATIONS We strongly recommend a bi annual maintenance checkup be performed before the heating and cooling seasons begin by a qualified servicer Replace or Clean Filter IMPORTANT NOTE Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of efficiency equipment damage and possible fire An ind
19. oor air filter must be used with your comfort system A properly maintained filter will keep the indoor coil of your com fort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your furnace in a blower unit or in filter grilles in your ceiling or walls The in staller of your air conditioner or heat pump can tell you where your filter s are and how to clean or replace them Check your filter s at least once a month When they are dirty replace or clean as required Disposable type filters should be replaced Reusable type filters may be cleaned You may want to ask your dealer about high efficiency filters High efficiency filters are available in both electronic and non elec tronic types These filters can do a better job of catching small airborne particles Compressor The compressor motor is hermetically sealed and does not re quire additional oiling Motors Indoor and outdoor fan motors are permanently lubricated and do not require additional oiling Clean Outside Coil Qualified Servicer Only A WARNING HIGH VOLTAGE Disconnect ALL power before servicing Multiple power sources may be present Failure to do so may cause property damage personal injury or death Air must be able to flow through the outdoor unit of your comfort system Do not construct a fence near the unit or build a deck or patio over the unit withou
20. p unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation Situate the unit to permit free unobstructed drainage of the defrost water and ice In more severe weather locations it 15 recommended that the unit be elevated to allow unobstructed drainage and air flow The following elevation minimums are recommended Suggested D T t i aetna M inimum Elevation 15 and above 21 2 5 to 14 Safe Refrigerant Handling While these items will not cover every conceivable situation they should serve as a useful guide A WARNING To avoid possible injury explosion or death practice safe handling of refrigerants AQ WARNING Refrigerants are heavier than air They can push out the oxygen in your lungs or in any enclosed space To avoid possible difficulty in breathing or death Never purge refrigerant into an enclosed room or space By law all refrigerants must be reclaimed Ifan indoor leak is suspected thoroughly ventilate the area before beginning work Liquid refrigerant can be very cold To avoid possible frostbite or blindness avoid contact and wear gloves and goggles If liquid refrigerant does contact your skin or eyes seek medical help immediately Always follow EPA regulations Never burn refrigerant as poisonous gas will be produced AA WARNING To avoid possible explosion Never apply flame or steam to a refrigerant cylinder If you must heat a
21. r through a concrete slab ensure lines are adequately protected and sealed Refrigerant Line Connections IMPORTANT To avoid overheating the service valve TXV valve or filter drier while brazing wrap the component with a wet rag or use a thermal heat trap compound Be sure to follow the manufacturer s instruction when using the heat trap compound Note Remove Schrader valves from service valves before brazing tubes to the valves Use a brazing alloy of 2 minimum silver content Do not use flux Torch heat required to braze tubes of various sizes is proportional to the size of the tube Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy Applying too much heat to any tube can melt the tube Service personnel must use the appropriate heat level for the size of the tube being brazed Note The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit 1 The ends of the refrigerant lines must be cut square de burred cleaned and be round and free from nicks or dents Any other condition increases the chance of a refrigerant leak 2 Sweep the refrigerant line with nitrogen or inert gas dur ing brazing to prevent the formation of copper oxide inside the refrigerant lines The POE oils used in R 410A applica tions will clean any copper oxide present from the inside of the refrigerant lines and spread it throughout th
22. r to the following specification to properly seat the sealing surfaces 1 3 8 valve to 5 10 in lbs 2 5 8 valve to 5 20 in lbs 3 3 4 valve to 5 20 in lbs 4 7 8 valve to 5 20 in lbs Do not introduce liquid refrigerant from the cylinder into the crankcase of the compressor as this may damage the compressor 1 Break vacuum by fully opening liquid and suction base valves 2 Set thermostat to call for cooling Check indoor and outdoor fan operation and allow system to stabilize for 10 minutes for fixed orifices and 20 minutes for expansion valves Charge Verification A WARNING REFRIGERANT UNDER PRESSURE Do not overcharge system with refrigerant Do not operate unit in a vacuum or at negative pressure Failure to follow proper procedures may cause property damage personal injury or death AA CAUTION Use refrigerant certified to AHRI standards Used refrigerant may cause compressor damage Most portable machines cannot clean used refrigerant to meet AHRI standards NOTICE Violation of EPA regulations may result in fines or other penalties AA CAUTION Operating the compressor with the suction valve closed will void the warranty and cause serious compressor damage Final Charge Adjustment The outdoor temperature must be 60 F or higher Set the room thermostat to COOL fan switch to AUTO and set the temperature control well below room temperature Purge gauge lines Connect service
23. t first discussing your plans with your dealer or other qualified servicer Restricted airflow could lead to poor operation and or severe equipment damage Likewise it isimportant to keep the outdoor coil clean Dirt leaves or debris could also restrict the airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless you first discuss it with your dealer Any cover used must include breathable fabric to avoid moisture buildup CALLING YOUR SERVICER Check the thermostat to confirm that it is properly set Wait 15 minutes Some devices in the outdoor unit or in programmable thermostats will prevent compressor op eration for awhile and then reset automatically Also some power companies will install devices which shut off air conditioners for several minutes on hot days If you wait several minutes the unit may begin operation on its own AX CAUTION TO AVOID THE RISK OF EQUIPMENT DAMAGE OR FIRE INSTALL THE SAME AMPERAGE BREAKER OR FUSE AS YOU ARE REPLACING IF THE CIRCUIT BREAKER OR FUSE SHOULD OPEN AGAIN WITHIN THIRTY DAYS CONTACT A QUALIFIED SERVICER TO C
24. tion of substantial fines Should you have any questions please contact the local office of the EPA If replacing a condensing unit or air handler the system must be manufacturer approved and Air Conditioning Heating and Refrig eration Institute AHRI matched NOTE Installation of unmatched systems is not allowed Outdoor units are approved for operation above 55 F in cooling mode Operation below 55 F in cooling mode requires the use of an approved low ambient kit Operating the unit in a structure that is not complete either as part of new construction or renovation will void the warranty Installation Clearances Special consideration must be given to location of the condensing unit s in regard to structures obstructions other units and any all other factors that may interfere with air circulation Where possible the top of the unit should be completely unobstructed however if vertical conditions require placement beneath an ob struction there should be a minimum of 60 inches between the top of the unit and the obstruction s The specified dimensions meet requirements for air circulation only Consult all appropri ate regulatory codes prior to determining final clearances Our continuing commitment to quality products may mean a change in specifications without notice 2013 DAIKIN MANUFACTURING COMPANY L P 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com Another important consider
25. wall studs floors and walls When run ning refrigerant lines through a foundation or wall openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation Any gap be tween foundation or wall and refrigerant lines should be filled with a pliable silicon based caulk RTV or a vibration damping material Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line These sizes are recommended for line lengths of 79 feet or less to obtain optimum performance For alternate line sizing options or runs of more than 79 feet refer to Remote Cooling Service M anual or TP 107 Long Line Set Application R 410A or contact your dis tributor for assistance RECOM MENDED INTERCONNECTING TUBING Ft Gnd oa 2549 wr Unit Line Diameter In OD Tons Suct liq Sut Liq 4 7 8 Lines greater than 79 feet in length or vertical elevation changes more than 50 feet refer to the Remote Cooling Service Manual or contact your distributor asdstance Liquid Line Suction Line Mounting the evaporator coil above the condensing unit will require an inverted loop in the suction line adjacent or near the connection to the evaporator The top of the loop must be slightly
Download Pdf Manuals
Related Search
Related Contents
AU-32 TP-Link C5 Quick Installation Guide LTVシリーズ LTV1200 添付文書 MONTAGEANLEITUNG MEHRSPURIGES アドバンスドモードについて 仕様書 (ファイル名:22-A27K_S1-2 サイズ:278.03 KB) Rexel 21676030 folder Copyright © All rights reserved.
Failed to retrieve file