Water Specialist CI Control Valve Programming and

image

Contents

1. N Vv DAY Tid SET CLOCK REGEN REGEN rage ps SET CLOCK NEXT REGEN bbr SET CLOCK NEXT REGEN WS1 5CI amp 2LCI Manual Valve History STEP 1VH Press A and V simultaneously for three seconds and release Then press A and V simultaneously and release If screen in step 2VH does not appear in 5 seconds the lock on the valve is activated To unlock press V NEXT A and SET CLOCK in sequence then press A and V simultaneously for 3 seconds and release Then press A and W simultaneously and release STEP 2VH Days total since start up This display shows the total days since startup Press the NEXT button to go to Step 3VH Press REGEN to return to previous step STEP 3VH Regenerations total number since start up This display shows the total number of regenerations that have occurred since startup Press the NEXT button to go to Step 4VH Press REGEN to return to previous step STEP 4VH Volume total used since start up This display shows the total volume of water treated since startup This display will equal zero if a water meter is not installed Press the NEXT button to go to Step 5VH Press REGEN to return to previous step STEP 5VH Error Log This display shows a history of the last 10 errors generated by the cont
2. SET CLOCK NEXT REGEN SET CLOCK NEXT REGEN J RETURN TO NORMAL MODE Page 17 Diagnostics STEP 1D Press A and F simultaneously for three seconds If screen in step 2D does not appear in 5 seconds the lock on the valve is activated To unlock press A NEXT V and SET CLOCK in sequence then press A and Y simultaneously for 3 seconds STEP 2D Days since last regeneration This display shows the days since the last regeneration occurred Press the NEXT button to go to Step 3D Press REGEN to exit Diagnostics STEP 3D Volume since last regeneration This display shows the volume of water that has been treated since the last regeneration This display will equal zero if a water meter is not installed Press the NEXT button to go to Step 4D Press REGEN to return to previous step STEP 4D Volume reserve capacity used for last 7 days If the valve is set up as a softener a meter is installed and Set Volume Capacity is set to Auto this display shows 0 day for today and flashes the reserve capacity Pressing the A button will show day 1 which would be yesterday and flashes the reserve capacity used Pressing the A button again will show day 2 the day before yesterday and the reserve capacity Keep pressing the A button to show the capacity for days 3 4 5 and 6 The W button can be pressed to move backwards in
3. was selected in Step SCS OR PPM 1 2500 if oFF or a number was selected in Step 8S Press NEXT to go to step 3I Press REGEN to exit Installer Display Settings Allowable range may vary depending on system capacity selected STEP 3I Hardness 2 If using a mixing valve set the amount of effluent hardness using the V or A buttons Range of available values may vary depending on system capacity selected and hardness selected in Step 21 This display will show nA if FILTER is selected in Step 2F OR if nA was selected in Step 5CS OR oFF or a number was selected in Step 8S Press NEXT to go to Step 4 Press REGEN to return to previous step STEP 4I Day Override When volume capacity is set to oFF sets the number of days between regenerations When volume capacity is set to AUTO or to a number sets the maximum number of days between regenerations If value set to oFF regeneration initiation is based solely on volume used If value is set as a number allowable range from to 28 a regeneration initiation will be called for on that day even if sufficient volume of water were not used to call for a regeneration Set Day Override using V or A buttons e number of days between regeneration 1 to 28 or OFF See Setting Options Table for more detail on setup Press NEXT to go to step 5I Press REGEN to return to previous step STEP 5I Next Regeneration Time hour Set the ho
4. REGEN to return to previous step Step 4F Select the time for the second cycle which in this example is dn BRINE using the V or A button Press NEXT to go to Step 5F Press REGEN to return to previous step NOTE The display will flash between cycle number and time and brine direction dn Brine Step 5F Select the time for the third cycle which in this example is RINSE using the V or A button Press NEXT to go to Step 6F Press REGEN to return to previous step Step 6F Select the volume in liters for the fourth cycle which in this example is FILL using the Y or A button Press NEXT to go to Step 7F Press REGEN to return to previous step Page 12 STEP 7F SET a REGEN 4 Ht anne NEXT REGEN SETTIME REGEN E n i NORMAL Ja NEXT Recen CLOCK RETURN TO NORMAL MODE WS1 5Cl amp 2LCI Manual Step 7F Set Volume Capacity using the V or A button If value is set to e OFF regeneration will be based solely on the day override set see Installer Display Settings Step 41 or e a number regeneration initiation will be based off the value specified in M See Setting Options Table for more detail Press NEXT to go to Step 8F Press REGEN to return to previous step Step 8F Set Regeneration Time Options using the V or A button If value is set to e NORMAL means regeneration will occur at the pres
5. be automatically estimated e OFF regeneration will be based solely on the day override set see Installer Display Settings Step 4I or e a number regeneration initiation will be based on the value specified in M e norES for no reserve operations if nA was selected in Step 5CS If oFF or a number is used hardness display will not be allowed to be set in Installer Display Settings Step 21 amp 3I See Setting Options Table for more detail Press NEXT to go to Step 9S Press REGEN to return to previous step Step 9S Set Regeneration Time Options using the V or A button If value is set to e NORMAL means regeneration will occur at the preset time e on O means regeneration will occur immediately when the volume capacity reaches 0 zero or e NORMAL on 0 means regeneration will occur at one of the following the preset time when the volume capacity falls below the reserve or the specified number of days between regenerations is reached whichever comes first or immediately after 10 minutes of no water usage when the volume capacity reaches 0 zero See Setting Options Table for more detail Press NEXT to go to Step 10S Press REGEN to return to previous step Step 10S Set Low Salt Warning using the V or A button If value is set to e OFF no low salt level warning will appear for the user or e a specific value FILL SALT will flash on the display when the calculated
6. it to the amount of salt added to the brine tank The example at the left would indicate 100 Kg of salt being added to a brine tank that has 20 Kg SET x clock NEXT Recan remaining SET REMAINING Step 4US Press SET CLOCK to exit Adding Salt SET clock NEXT RecN RETURN TO NORMAL MODE Power Loss If the power goes out the system will keep time for 24 hours or until the battery is depleted If a power F outage of more than 24 hours occurs the time of day will flash on and off which indicates the time of day rror should be reset The system will remember the rest If a power outage lasts less then 24 hours and the time az of day flashes on and off the time of day should be reset and the non rechargeable battery replaced Error Message o o 4 If the word ERROR and a number are alternately flashing on the display contact the OEM for help This indicates that the valve was not able to function properly WS1 5Cl amp 2LCI Manual SET CLOCK NEXT REGEN v REGEN DAY x SET CLOCK NEXT REGEN Z REGEN Pq SET CLOCK REGEN DAY H 6 SET CLOCK NEXT REGEN DAY B
7. remaining Kg of salt falls below that level Allowable values range from 5 to 200 Kg in 5 Kg increments REMAINING Press NEXT to exit OEM Softener System Setup Press REGEN to return to previous step Page 10 WS1 5Cl amp 2LCI Manual Setting Options Table Filters should only use shaded options Volume Re generation D Result Capacity Time Option Override Reserve capacity automatically estimated AUTO NORMAL o Regeneration occurs when volume capacity falls below the reserve capacity at the next Regen Set Time Reserve capacity automatically estimated AUTO NORMAL Any Regeneration occurs at the next Regen Set Time when volume capacity number falls below the reserve capacity or the specified number of days between regenerations is reached Reserve capacity not automatically estimated Any Puree oF Regeneration occurs at the next Regen Set Time when volume capacity reaches 0 a Reserve capacity not automatically estimated OFF y Regeneration occurs at the next Regen Set Time when the specified number Reserve capacity not automatically estimated Na N Regeneration occurs at the next Regen Set Time when volume y NORMAL y capacity reaches 0 or the specified number of days between number number regenerations is reached number of days between regenerations is reached Reserve capacity not automatically estimated Any Regeneration occurs immediately when volume capacity reaches 0 OnO F i number Time of regenerati
8. valve motor Configuring the Control Valve for No Hard Water Bypass Operation Select nHbP for control operation with a no hard water bypass valve Selection requires that a connection to a Clack Motorized Alternator Valve MAV is made to the two pin connector labeled ALTERNATOR DRIVE located on the printed circuit board The B port of the MAV must be plugged and the valve outlet connected to the A port The MAV will be driven closed before the first regeneration cycle that is not FILL or SOFTENING or FILTERING and be driven open after the last regeneration cycle that is not FILL Press NEXT to go to Step 4CS Press REGEN to return to previous step Step 4CS Allows selection of one of the following using the A or Y buttons SET REGEN veaunnn reese PITEAN SET CLOCK e an outside signal to initiate a regeneration e an outside signal to prevent or delay regeneration Selection only matters if a connection is made to the two pin connector labeled DP SWITCH located on the printed circuit board Following is an explanation of the options OFF Feature not used dPon0 If the dP switch is closed for an accumulative time of 2 minutes a regeneration will occur immediately dPdEL If the dP switch is closed for an accumulative time of 2 minutes a regeneration will occur at the scheduled regeneration time HoLd If the dP switch is closed a regeneration will be prevented from occuring Press NEXT t
9. EXT SET clock REGEN LV Step 6CS Press the V or A buttons until BACKWASH appears Press NEXT to go to Step 7CS Press REGEN to return to previous step Step 7CS Press the V or A buttons until dn BRINE appears Press NEXT to go to Step 8CS Press REGEN to return to previous step For a WS1 control valve prior to selecting a regenerant flow cycle verify the correct valve body main piston regenerant piston and stack are being used and the injector or injector plug s are in the correct location Refer to WS1 amp WS1 25 Common Information manual Valve Body Compliance Table Step 8CS Press the V or A buttons until RINSE appears Press NEXT to go to Step 9CS Press REGEN to return to previous step Step 9CS Press the V or A buttons until FILL appears Press NEXT to go to Step 10CS Press REGEN to return to previous step Step 10CS Press the VW or A buttons until END appears Press NEXT to exit OEM Cycle Sequence Press REGEN to return to previous step Page 8 WS1 5Cl amp 2LCI Manual OEM Softener System Setup In OEM Softener System Setup the OEM chooses the time for the cycles selected in OEM Cycle Sequence and specifies other operating parameters for the system The upper and lower limits of the allowable values for the cycles are as follows up Brine combination of brining and slow rinse 1 to 180 0 05 to 90 00 1 to 480 Note Fill is in Kilograms of salt Since no time is assoc
10. SETTIME SET CLOCK Page 16 WS1 5Cl amp 2LCI Manual Salt Remaining or Adding Salt If the Low Salt Warning was activated in the last step of OEM Softener System Setup the following screens will be viewed in the User Display Note The salt used per regeneration setting can be set in increments of 0 05 Kg but the Kg REMAINING screen will round up or down to the closest whole number 4 REMAINING CALF NEXT REGEN SET CLOCK Once the salt remaining has gone below the set point the display will automatically flash Salt Fill SALT SET clock NEXT REGEN When adding salt to the brine tank if the salt remaining feature is activated the following steps must be completed ea ae Step 1US Press the NEXT button until SALT appears in the display It does not matter if the SALT l display alternates with the Kg REMAINING display SALT FILL SET Next REGEN CLOCK ATV SET CLOCK Step 2US Press SET CLOCK ie e Step 3US Set Kg REMAINING Use the V or A button to adjust the Kg remaining in the brine tank Kg crock NExT REGEN SET REMAINING Kg H g NOTE Estimate the Kg of salt in the brine tank and add
11. To unlock press V NEXT A and SET CLOCK in sequence then press NEXT and Y simultaneously for 3 seconds and release Then press NEXT and simultaneously for 3 seconds and release Step 2CS Use the A or to select 25 for WS1 valve 32 for WS1 25 valve 38 for WS1 5 valve or 50 SET veers FETAL NANAS SET CLOCK NEXT REGEN J AV for WS2L valve Press NEXT to go to Step 3CS Press REGEN to exit OEM cycle sequence Step 3CS Allows selection of one of the following using the A or V buttons ALE A SET CLOCK NEXT REGEN 4 ATV e the Control Valve to act as an alternator or e the Control Valve to have no hard water bypass Selecting the Control Valve to act as an alternator Note Also must do one of the following e If set up for a softener in Step SCS select nA in Step 7S set Volume Capacity in M in Step 8S select norES in Step 9S select Regeneration Time Option on 0 and in Step 4I select Day Override oFP e If set up for a filter in Step 7F set Volume Capacity in M in Step 8F select Regeneration Time Option on 0 and in Step 4I select Day Override oFF Select OFF when feature is not used Select ALTA for the control valve that has the two pin connector labeled DRIVE connected to the alternator valve motor Select ALTb for the control valve that will not be connected to the alternator
12. Water Specialist Cl Control Valve Programming and Cover Drawing Manual For Software Revision 317 3 Page 2 WS1 5Cl amp 2LCI Manual WS1 5Cl amp 2LCI Manual CI Front Cover and Drive Assembly Drawing No Order No Description 1 V3175CC 01 WS1CC FRONT COVER ASSEMBLY 2 V3107 01 WS1 MOTOR 3 V3106 01 WS1 DRIVE BRACKET amp SPRING CLIP 4 V3108CI O2BOARD WS1 THRU2L CI PCBRD ALT REPLACE 5 V3110 WS1 DRIVE REDUCING GEAR 12X36 6 V3109 WS1 DRIVE GEAR COVER V3186 WS1 AC ADAPTER 110V 12V V3186EU WS1 AC ADAPTER 220 240V 12V EU Not Shown V3186UK WS1 AC ADAPTER 220 240V 12V UK V3186 01 WS1 AC ADAPTER CORD ONLY AC Adapter US International Supply Voltage 120 V AC 230V AC Supply Frequency 60 Hz 50 Hz Output Voltage 12 VAC 12 VAC Output Current 500 mA 500 mA When replacing the battery align positives and push down to fully seat lt gt YY Battery Fully Seated Correct a Battery gt lt Battery replacement is Orienta A e 3 volt lithium coin cell tion type 2032 Page 3 Quantity 1 w m m m Page 4 WS1 5Cl amp 2LCI Manual Refer to Water Specialist 1 5 and 2L Control Valve Service Manual for the following Drawings and Part Numbers e WS1 5 Drive Cap Assembly Downflow Piston Regenerant Piston Spacer Stack Assembly Main Body and Meter e WS2L Drive Cap Assembly Downflow Pis
13. ener System Setup or the OEM Filter System Setup allow the OEM to set how long cycles will last The OEM may choose up to 9 cycles in any order RINSE UP BRINE SOFTENING END WS1 Only OR FILTERING END must be used as the last cycle option The SERVICE cycle should only be used in brine prefill applications OEM Cycle Sequence instructions allows the OEM to set the order of The upflow cycle may not be used on the WS1 25 WS1 5 or WS2L control valves because the V3407 piston is designed for downflow use only For WS1 valves prior to selecting DN brine or UP brine or not selecting a regenerant flow cycle verify the correct valve body main piston regenerant piston and stack are being used and that the injector or injector plug s are in the correct locations See Valve Body Compliance Table in WS1 amp WS1 25 OEM General Information Manual The following is an example of how to set a valve so that when regeneration is initiated BACKWASH occurs first dn BRINE occurs second RINSE occurs third and FILL occurs fourth Page 6 STEP 1CS SET crock NEXT REGEN SET crock NEXT REGEN ATV WS1 5CI amp 2LCI Manual Step 1CS Press NEXT and V simultaneously for 3 seconds and release Then press NEXT and V simultaneously for 3 seconds and release If screen in Step 2CS does not appear in 5 seconds the lock on the valve is activated
14. erating parameters for the system The upper and lower limits of the allowable values for the cycles are as follows Cycle Options Lower Upper Limit Tto 120 Rinse fast 1 to 120 NOTE Fill is in liters Since no time is associated with the END cycle the END cycle will not appear in the OEM Filter System Setup sequence SET clock NEXT REGEN STEP 2F SET FILTERING SET Ea NEXT REGEN SET H MIN BACKWASH SET CLOCK NEXT REGEN Tt SET c bie BRINE SET CLOCK NEXT REGEN J J Ys RINSE SET CLOCK NEXT REGEN J SET 4 440 FILL SET CLOCK NEXT REGEN J Step 1F Press NEXT and Y simultaneously for 3 seconds and release If screen in Step 2F does not appear in 5 seconds the lock on the valve is activated To unlock press V NEXT A and SET CLOCK in sequence then press NEXT and W simultaneously for 3 seconds and release Step 2F Choose FILTERING using the V or A buttons Press NEXT to go to Step 3F Press REGEN to exit OEM Filter System Setup Step 3F Select the time for the first cycle which in this example is BACKWASH using theV or A button Press NEXT to go to Step 4F Press
15. et time e on O means regeneration will occur immediately when the volume capacity reaches 0 zero or e NORMAL on 0 means regeneration will occur at one of the following the preset time when the volume capacity falls below the reserve or the specified number of days between regenerations is reached whichever comes first or immediately after 10 minutes of no water usage when the volume capacity reaches 0 zero See Setting Options Table for more detail Press NEXT to exit OEM Filter System Setup Press REGEN to return to previous step WS1 5Cl amp 2LCI Manual Page 13 SET CLOCK NEXT REGEN Tir SET HARDNESS Eai SET CLOCK NEXT REGEN J SET HARDNESS g SET CLOCK NEXT REGEN V 4 REGEN DAY city NEXT REGEN STEP 5I SETTIME REGEN cL chock NEXT REGEN STEP 61 SETTIME REGEN cL k NEXT REGEN RETURN TO NORMAL MODE Installer Display Settings STEP 1I Press NEXT and A simultaneously for 3 seconds STEP 21 Hardness Set the amount of influent hardness using the V or A buttons This display will show nA if FILTER is selected in Step 2F OR if nA
16. iated with the END cycle the END cycle will not appear in the OEM Softener System Setup sequence Step 1S Press NEXT and YW simultaneously for 3 seconds and release If screen in Step 2S does not SET NEXT REGEN appear in 5 seconds the lock on the valve is activated To unlock press V NEXT A and SET CLOCK in sequence then press NEXT and YW simultaneously for 3 seconds and release Vv Step 2S Choose SOFTENING using the W or A button Press NEXT to go to Step 3S Press REGEN SET to exit OEM Softener System Setup SOFTENING SET cLOCK NEXT REGEN Step 3S Select the time for the first cycle which in this example is BACKWASH using the V or A SET button Press NEXT to go to Step 4S Press REGEN to return to previous step MIN BACKWASH chock NExT REGEN Step 4S Select the time for the second cycle which in this example is dn BRINE using the V or A SET button Press NEXT to go to Step 5S Press REGEN to return to previous step m H u NOTE The display will flash between cycle number and time and brine direction dn BRINE SET clock NEXT REGEN Step 5S Select the time for the third cycle which in this example is RINSE using the V or A button SET Press NEXT to go to Step 6S Press REGEN to return to previo
17. neration time so REGEN TODAY will not activate if REGEN button is pressed To initiate a manual regeneration immediately press and hold the REGEN button for three seconds The system will begin to regenerate immediately The request cannot be cancelled Note For softeners if brine tank does not contain salt fill with salt and wait at least two hours before regenerating WS1 5Cl amp 2LCI Manual Page 15 Set Time of Da The user can also set the time of day Time of day should only need to be set after power outages lasting more than 24 hours if the battery has been depleted and a power outage occurs or when daylight saving time begins or ends If a power outage lasting more than 24 hours occurs the time of day will flash on and off which indicates the time of day should be reset If a power outage lasts less then 24 hours and the time of day flashes on and off the time of day should be reset and the non rechargeable battery replaced STEP 1U Press SET CLOCK NEXT REGEN SET CLOCK STEP 2U Current Time hour Set the hour of the day using V or A buttons Press NEXT to go to SETTIVE step 3U NEXT REGEN STEP 3U Current Time minutes Set the minutes of the day using V or A buttons Press NEXT to exit Set Clock Press REGEN to return to previous step NEXT REGEN RETURN TO NORMAL MODE SET CLOCK
18. o go to Step 5CS Press REGEN to return to previous step WS1 5Cl amp 2LCI Manual Page 7 SET HARDNESS PPM SET HARDNESS dH Step 5CS Determine the measurement to calculate volumetric capacity The choices are ppm parts per million SET CLOCK NEXT REGEN NEXT REGEN clock FH French degrees dH German degrees nA Using nA will allow the OEM to directly place the volume of water V SET HARDNESS SET HARDNESS H _ treated in place of system capacity in the OEM Softener System Setup level nq NOTE If control is going to be used in a filter application any of these SET CLOCK REGEN V SET BACKWASH SET CLOCK NEXT REGEN V SET E dn BRINE SET CLOCK NEXT REGEN J SET J RINSE SET CLOCK NEXT REGEN a SET 4 FILL SET CLOCK NEXT REGEN SET 5 End SET CLOCK NEXT REGEN RETURN TO NORMAL MODE J settings can be used Press NEXT to go to Step 6CS Press REGEN to return to previous step N
19. on cycle Capacity remaining is the cubic meters that will be treated before the system goes through REGEN TODAY will SOFTENING RJ c a regeneration cycle The third display shows the current treated Flash if a regeneration TODAY water flow rate through the system The fourth display will show is expected Tonight a regres either dP or hold if the dP switch is closed The fifth display ook T shows the Kg of salt remaining or flashes SALT fill when the calculated Kg of salt falls below a safety level The fifth display a will not appear if the valve is set up as a filter or if the Set Low finan g 5 F wah Salt Warning is set to off see last step in OEM Softener System Setup The user can scroll between the displays as desired Cosby NEXT REGEN If the system has called for a regeneration that will occur at the 4 ALY preset time of regeneration the words REGEN TODAY will appear on the display If a water meter is installed the word Softening or Filtering REGEN H oL d flashes on the display when water is being treated i e water is flowing through the system ji 4 REMAINING SALT S SET CLOCK NEXT REGEN Regeneration Mode Typically a system is set to regene
20. on will not be allowed to be set because regeneration will always occur on 0 Reserve capacity automatically estimated AUTO NORMAL on 0 5 Regeneration occurs when volume capacity falls below the reserve capacity at the next Regen Set Time or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0 Reserve capacity automatically estimated Any Regeneration occurs at the next Regen Set Time when volume capacity AUTO NORMAL on 0 number falls below the reserve capacity or the specified number of days between regenerations is reached or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0 Reserve capacity not automatically estimated Any Any Regeneration occurs at the next Regen Set Time when the specified NORMAL on 0 number number number of days between regenerations is reached or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0 Reserve capacity estimate is based on history of water usage ay FF F Reserve capacity not automatically estimated Regeneration occurs immediately when volume capacity reaches 0 AUTO OnO oFF Time of regeneration will not be allowed to be set because regeneration will always occur when volume capacity reaches 0 oFF FF WS1 5Cl amp 2LCI Manual Page 11 OEM Filter System Setup In OEM Filter System Setup the OEM chooses the time for the cycles selected in OEM Cycle Sequence and specifies other op
21. rate at a time of low water usage An example of a time with F g low water usage is when a household is asleep If there is a demand for water when the system is BACKWASH regenerating untreated water will be used When the system begins to regenerate the display will change to include information about the step of the regeneration process and the time remaining for that step to be completed The system runs through the steps automatically and will reset itself to provide treated water when the regeneration has been completed Manual Regeneration a Sometimes there is a need to regenerate the system sooner than when the REGEN TODAY will be STIRS Ly system calls for it usually referred to as manual regeneration There may __ displayed if a regeneration TODAY 5 be a period of heavy water usage because of guests or a heavy laundry day is expected Tonight SET Jae Reach CLOCK To initiate a manual regeneration at the preset delayed regeneration time when the regeneration time option is set to NORMAL or NORMAL on 0 press and release REGEN The words REGEN TODAY will flash on the display to indicate that the system will regenerate at the preset delayed regeneration time If you pressed the REGEN button in error pressing the button again will cancel the request Note If the regeneration time option is set to on 0 there is no set delayed rege
22. regeneration present flow rate or days remaining before regeneration are shown When stepping through a procedure if no buttons are pressed within five minutes the display returns to a normal user display Any changes made prior to the five minute time out are incorporated To quickly exit OEM Softener Setup OEM Filter Setup Installer Display Settings Diagnostics or Valve History press SET CLOCK Any changes made prior to the exit are incorporated When desired all information in Diagnostics may be reset to zero when the valve is installed in a new location To reset to zero press NEXT and VY buttons simultaneously to go to the Service OEM 1 Screen Press A and Y simultaneously to reset diagnostic values to zero Screen will return to User Display Sometimes it is desirable to have the valve initiate and complete two regenerations within 24 hours and then return to the preset regeneration procedure It is possible to do a double regeneration if the control valve is set to NORMAL or NORMAL on 0 in OEM Softener System Setup or OEM Filter System Setup To do a double regeneration 1 Press the REGEN button once REGEN TODAY will flash on the display 2 Press and hold the REGEN button for three seconds until the valve regeneration initiates Once the valve has completed the immediate regeneration the valve will regenerate one more time at the preset regeneration time OEM Cycle Sequence the cycle The OEM Soft
23. rol E Z during operation Press the A or V buttons to view each recorded error p J Press the next button to exit Valve History Press REGEN to return to previous step SET CLOCK NEXT REGEN RETURN TO NORMAL MODE Values in steps 2VH through 5VH cannot be reset WS1 5CI amp 2LCI Manual Page 19 Revision History 12 7 07 PAGE 6 DP Switch and alternating valve operations separated into Steps 3CS and 4CS PAGE 18 Added Step 5VH Error Log 2 27 08 PAGE 9 Added norES to Step 8S 5 29 08 Moved common valve drawings to V3435 WS1 5 2L Drawing and Service Manual Page 20 WS1 5Cl amp 2LCI Manual Form No V3435Cl 5 29 2008
24. the day series Press the NEXT button at any time to go to Step 5D Press REGEN to return to previous step Ha g Die STEP 5D Volume 63 day usage history This display shows day 1 for yesterday and flashes the volume of water treated yesterday Pressing the A button will show day 2 which would be the day before yesterday and flashes the volume of water treated on that day Continue to press the A button to show the maximum volume of water treated for the last 63 days If a regeneration occured on the day the word REGEN will also be displayed This display will show dashes if a water meter is not installed Press the NEXT button at any time to go to Step 6D Press REGEN to return to previous step STEP 6D Flow rate maximum last seven days The maximum flow rate in liters per minute that occurred in the last seven days will be displayed This display will equal zero if a water meter is not installed Press the NEXT button to exit Diagnostics Press REGEN to return to previous step When desired all information in Diagnostics may be reset to zero when the valve is installed in a new location To reset to zero press NEXT and V buttons simultaneously to go to the Service OEM 1 Screen Press A and Y simultaneously to reset diagnostic values to zero Screen will return to User Display Page 18 SET CLOCK NEXT REGEN SET CLOCK NEXT REGEN
25. ton Regenerant Piston Spacer Stack Assembly and Main Body e Meter Assembly for WS2L Valves e Injector Cap Injector Screen Injector Plug Bolts and O ring s e Refill Flow Control Assembly and Refill Port Plug e Drain Line 4 e Drain Line 1 e V3053 WS2 2 1 2 GROOVELOCK CLAMP ASY The Drive Back Plate displayed on these drawings shows installation of one style of back plate If a Drive Back Plate is needed order V3178 WS1 DRIVE BACK PLATE WS1 5Cl amp 2LCI Manual Page 5 OEM General Instructions The control valve offers multiple procedures that allow the valve to be modified to suit the needs of the installation These procedures are e OEM Cycle Sequence e OEM Softener System Setup e OEM Filter System Setup e Installer Display Settings e User Display Settings e Diagnostics e Valve History Once the OEM Cycle Sequence has been set the other procedures can be accessed in any order Details on each of the procedures are provided on the following pages To lock out access to diagnostic and valve history displays and modifications to settings except hardness day override time of regeneration and time of day by anyone but the manufacturer press W NEXT A and SET CLOCK in sequence after settings are made To unlock so other displays can be viewed and changes can be made press W NEXT A and SET CLOCK in sequence When in operation normal user displays such as time of day volume remaining before
26. ur of day for regeneration using V or A buttons The default time is 2 00 This display will show REGEN on 0 L if on 0 is selected in Set Regeneration Time Option in OEM Softener System Setup or OEM Filter System Setup Press NEXT to go to step 61 Press REGEN to return to previous step STEP 6I Next Regeneration Time minutes Set the minutes of day for regeneration using V or A buttons This display will not be shown if on 0 is selected in Set Regeneration Time Option in OEM Softener System Setup or OEM Filter System Setup Press NEXT to exit Installer Display Settings Press REGEN to return to previous step To initiate a manual regeneration immediately press and hold the REGEN button for three seconds The system will begin to regenerate immediately The control valve may be stepped through the various regeneration cycles by pressing the REGEN button Page 14 WS1 5CI amp 2LCI Manual User Display Settings REMAINING General Operation Saeeitie CAPACITY REWAINING e When the system is operating one of five displays may be shown REGEN A ey Pressing NEXT will alternate between the displays One of the SET SET displays is always the current time of day The second display CLOCK REGEN ctock NEXT REGEN is one of the following days remaining or volume remaining V V Days remaining is the number of days left before the system goes through a regenerati
27. us step J H RINSE SET clock NEXT REGEN Step 6S Select the Kg for the fourth cycle which in this example is FILL using the V or A button T Press NEXT to go to Step 7S Press REGEN to return to previous step 4 430 i I LI FILL SET clock NEXT REGEN J EA WS1 5Cl amp 2LCI Manual Step 7S Set System Capacity using the V or A button See chart SET REGEN Kg CAPACITY vas revere a MAATTE NAAN NEXT J NEXT SETTIME REGEN NORMAL g on L SET CLOCK NEXT REGEN J SALT FILL SET CLOCK NEXT REGEN RETURN TO NORMAL MODE J Page 9 Setting Units Limits Kg of CaCO The System Capacity setting should be based on the volume of resin and Kg of salt fill set in Step 6S When using ppm dH or FH the system capacity and hardness levels entered are used to determine the Volume Capacity Press NEXT to go to Step 8S Press REGEN to return to previous step 0 10 200 nA M 0 10 2000 dH or FH 1 6000 Step 8S Set Volume Capacity using the V or A button If value is set to e AUTO capacity will be automatically calculated and reserve capacity will