SERVICE MANUAL**** 77096-00 Liqui-Sense
Contents
1. of all the jumpers and how they are attached to the board Remove the jumper connections Remove the screws holding the circuit board to the case Remove the old circuit board and install the new one Replace the screws holding the circuit board to the case Reinstall the jumpers as noted in step 3 CAUTION Failure to reinstall the jumpers correctly could destroy the new circuit board 8 Replace the cover and attach it with the screws removed in step 2 RAAB 6 REPLACEMENT PARTS DESCRIPTION PART NUMBER 115 VOLT UNITS 77096 00 877 9600 230 VOLT UNITS 77096 05 877 9605 CIRCUIT BOARD FUSE 10 AMP LINE CORD CIRCUIT BOARD FUSE 6 3 AMP 20mm LINE CORD EUROPEAN 7 CALIBRATION PROCEDURE D 2808 0001 B 1115 0052 B 3384 0001 D 2808 0002 B 1115 0054 B 2938 Follow CAL 1593 to calibrate the new circuit board installed in the unit 8 FUNCTIONAL TEST Follow CAL 1592 to test unit
2. 77096 00 77096 05 877 9600 877 9605 SERVICE MANUAL Liqui Sense Controller 115V units Liqui Sense Controller 230V units Liquid Sensor Controller 115V units Liquid Sensor Controller 230V units Information contained in this manual is proprietary to the Barnant Company division of Cole Parmer Instrument Company Inc No reproduction for other than the intended use of maintaining the product described herein is permitted without the permission of Barnant Barnant Company Division of Cole Parmer Instrument Company Inc 625 East Bunker Court Vernon Hills Illinois 60061 1844 847 549 7600 847 247 2929 Fax 800 323 4340 A 1299 0511 Edition 02 TABLE OF CONTENTS PAGE INTRODUCTION og er ns A eal a A aaa en eee 3 SAFETY CONSIDERATIONS tii nein nen 3 FUNCTIONAL DESCRIPTION nannte 3 EROUBEESHOO TIN isis EN I A AR 3 REPAIR PROCEDURES ua dp 4 REPLACEMENT PARTS 0 a a 5 CALIBRATION PROCEDURE 2 ne 5 FUNCTIONAL TEST A Eee 5 1 INTRODUCTION This manual is for service performed at the distributor level Customer service procedures are described in the Operator Manual Customers are encouraged to perform service as described in the Operator Manual as well as in special circumstances where special skills and safety are not considerations To use this manual begin with the troubleshooting section to isolate the fault to a replaceable part The Functional Description and Check out Procedure Sections are also helpful
3. and cable to channel 1 Unit should be in a non alarm state Put a few drops of water on the sensor pad The alarm should go on alarm SW is on and LED DS2 is on 5 Power should now be applied to Aux Power Output There should be no power to Main Power Output If this is not the case then the safety output circuit is not working and the board should be replaced Repeat above steps for channel 2 With the unit in non alarm state use the jumper to short out the external contact closure for channel 1 The alarm should sound and the power transfer from main to auxiliary as above Repeat the test for channel 2 When the jumper is removed the unit should return to non alarm state Replace the circuit board is any of the tests fail 8 Connect an ohm meter across the contact closure The contact should be open on non alarm conditions and closed on alarm conditions Replace the circuit board if the condition is not met 9 Test switch When the test switch is pressed it simulates a fault condition The power should transfer from main to auxiliary output The contact closure should close and the alarm will sound Releasing the switch removes the fault condition If the test fails replace the circuit board ga A an 5 REPAIR PROCEDURES 1 To remove the circuit board from the case disconnect power first Turn unit over so the underside is facing up Remove the screws holding the cover and then remove the cover 3 Make note
4. in determining the faulty part Dealer repair is limited to replacement of modules as detailed in the REPLACEMENT PARTS LIST section The REPAIR PROCEDURES SECTION details disassembly and assembly procedures After repair the product should be calibrated and checked for proper performance Please refer to the appropriate Operator Manual P N A 1299 0512 for APPLICATION DATA PRODUCT DESCRIPTION INSTALLATION SETUP OPERATION USER CALIBRATION USER TROUBLESHOOTING amp MAINTENANCE ACCESSORIES 2 SAFETY CONSIDERATIONS Power should be connected only to a grounded outlet Check power cord for frayed wear or exposed conductors Replace with a new power cord if these conditions are found Check that proper power level is available to supply the instrument 3 FUNCTIONAL DESCRIPTION The function of the Liqui Sense controller is to monitor various sensor types and when a fault condition occurs to deactivate the main output activate the auxiliary output and signal an audible and visual alarm The sensitivity of detection is adjustable by means of a front panel trimpot 4 TROUBLESHOOTING Troubleshooting should be done to isolate to which channel 1 or 2 there is a problem or to a back panel connection problem Equipment on hand to test the unit should include 1 known good cable and sensor pad 1 digital voltmeter 1 jumper for simulating conduct closure Test Channel 1 and 2 Power up unit Connect sensor pad
Download Pdf Manuals
Related Search
Related Contents
Avital 4000 Remote Starter User Manual User Guide for a Kodak CARESTREAM System OrthoView 3 ( DV User`s Guide Chief SLB193 Interfacing the T4000 & T4400 to Electronic Speed Controllers リングジョイントガスケット VENTS TT SILENT 100 Use and Care Manual アンパンマン 夢中知育 おしゃべりことばカード アンパンマン Hotpoint BZ71 User's Manual カタログダウンロード - ベックマン・コールター Copyright © All rights reserved.
Failed to retrieve file