Home
Service Manual
Contents
1. 11 VI SERVICE PROCEDURES amp ADJUSTMENTS WARNING CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE EXERCISE EXTREME CAUTION AT ALL TIMES IF TEST POINTS ARE NOT EASILY ACCESSIBLE DISCONNECT POWER ATTACH TEST EQUIPMENT AND REAPPLY POWER TEST a SYSTEM ACCESS All external indicators should be checked as part of system diagnosis before determining the refrigerant pressures Improper access may expose the refrigerant to contaminates and non condensables which will result in system failure VI b SWEAT ON PIERCING VALVES NOTE Sweat on piercing valves are used for system diagnostics but may be left on after service is complete They may be installed while the system is fully charged 1 Place one piercing valve on the compressor process tube and one on the liquid line process tube Follow the installation instructions provided by the manufacturer of the piercing valve 2 When complete follow the guidelines as outlined under LEAK CHECK and EVACUATING SYSTEM VI c REFRIGERANT LEAK CHECK DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED THIS PROCEDURE REQUIRES THE USE OF REFRIGERANTS BE CERTAIN THE WORK AREA IS WELL VENTILATED SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN NOTE
2. The use of R 22 in small quantities is recommended as a trace gas for leak detection NOTE This leak check procedure is to be used only after the refrigerant has been properly reclaimed 1 Access the refrigeration system note see section V a SYSTEM ACCESS 2 Attach gauge manifold set to the system low side to process tube on the compressor and the high side to the process tube 3 Connect refrigerant bottle to the center of gauge manifold and open the valve on the bottle Bleed charging hose at the manifold gauge to remove air from the system 4 Open valve on low side of gauge manifold and charge system with one ounce of R 22 5 Close low side valve on gauge manifold and the valve on the refrigerant bottle 6 Disconnect refrigerant bottle and connect nitrogen bottle 12 VI c REFRIGERANT LEAK CHECK cont d NOTE The use of a nitrogen requlator is required 7 Set output valve on nitrogen valve to 120 psi 8 Open nitrogen bottle valve and low side gauge manifold valve Allow pressure to equalize 9 Shut off both valves and disconnect nitrogen bottle 10 Use a leak detector or a thick soapy solution and check for leaks at all tubing connections A If leaks are found repair leaks and repeat process B If no leaks are found evacuate system as outlined in section V d EVACUATING SYSTEM 11 Charge the system by weighing in the exact charge and check for proper operation
3. VI EVACUATING SYSTEM Introduction Refrigeration reclaiming equipment is required Our goal in system evacuation is to remove all the non condensables possible No evacuation method will remove 100 of the moisture and air from within the refrigeration circuit Because of this guidelines and methods must be developed and adhered to ensuring only harmless amounts of contaminants remain in the system GUIDELINES WARNING DO NOT PRESSURIZE SYSTEM ABOVE 150 PSIG PRIOR TO EVACUATION OR DURING LEAK TEST PROCEDURES Use only a two stage vacuum pump 2 CFM or greater and electronic micron Evacuate from high and low sides of the system No chemical additive or alcohols are to be used to dry up a system Blow down of system with DRY NITROGEN prior to evacuation is acceptable and many times desirable See System Clean Up Evacuate to 200 microns PROCEDURE WARNING DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED WARNING THIS PROCEDURE REQUIRES THE USE OF REFRIGERANTS BE CERTAIN THE WORK AREA IS WELL VENTILATED SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN VI SERVICE PROCEDURES amp ADJUSTMENTS cont d WARNING CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE EXERCISE EXTREME CAUTION AT ALL TIMES IF TEST PO
4. cont d Il j CONTROL LOCATION Il SPECIFICATIONS On all TE Series refrigerator models the micro 7 processor control is located on the louver assembly TE Series Refrigerated Equipment Stands The louvers refrigeration system are mounted standard on the left side but as an option are available mounted Horsepower on the right see figure 2 Condensing Unit BTU HR Condensing Unit Amp Draw Fan Lights Etc Amp Draw Refrigerant Refrigerant Charge oz a cado TE Series Refrigerated Equipment Stands ll OPERATING DATA CHART Condensing Unit BTU HR Condensing Unit Amp Draw Refrigerated Models cabinet temperature set at 38 F Fan Lights Etc Amp Draw Ambient 70 F 100 F Refrigerant Suction Pressure 35 PSIG 50 PSIG Refrigerant Charge oz Suction Temperature 3 F 16 F Discharge Pressure 200 PSIG 295 PSIG Discharge Temperature 88 F 115 F TE Series Refrigerated Equipment Stands Horsepower Condensing Unit BTU HR Condensing Unit Amp Draw Fan Lights Etc Amp Draw Refrigerant Refrigerant Charge oz TE Series Refrigerated Equipment Stands Horsepower Condensing Unit BTU HR Condensing Unit Amp Draw Fan Lights Etc Amp Draw Refrigerant Refrigerant Charge oz IIl REMOVAL amp REPLACEMENT OF BASIC PARTS WARNING DISCONNECT THE ELECTRICAL POWER TO THE
5. Frame slides Microprocessor Control Condensate Drain Pan Accessing Start Components TABLE OF CONTENTS Installation See Owner s Manual Refrigeration System Theory Of Operation Air Flow Requirements The Microprocessor Control I REMOVAL amp REPLACEMENT OF PARTS Condenser Fan Motor and or Blade Evaporator Fan V a b Condenser Coil C d Evaporator Coil WWWNHNNNNNN DNDN N ananhh RP IV REPLACING THE d f Compressor 10 V WIRING DIAGRAMS a 115V Refrigerator Models 11 VI SERVICE PROCEDURES amp ADJUSTMENTS a System Access 12 b Sweat On Piercing Valves 12 Refrigerant Leak Check 12 d Evacuating System 13 e Charging System 13 f System Clean Up 14 g Heater Test Drawer Perimeter Heater 14 Vil ELECTRICAL OPERATION a Sequence Of Operation Normal Operation 14 b Sequence Of Operation Defrost Mode 14 Component Function 15 d Installation of Sensors 15 Vill REPLACEMENT PARTS LISTING 16 IX TROUBLESHOOTING 17 nnulsen FORT WORTH TX SERIAL VOLTS TOTAL CURRENT MINIMUM CIRCUIT MODEL Hz PH AMPS AMPS MAXIMUM OVERCURRENT PROTECTION LIGHTS HEATERS REFRIGERANT DESIGN PRESSURE REFRIGERANT DESIGN PRESSURE LISTED US WATTS AMPS TYPE HIGH TYPE HIGH 370 60294 00 REV A I THE SERIAL TAG The serial tag is a permanently affixed sticker on which is recorded vital electrical and refrigeration data about you
6. MACHINE AND FOLLOW LOCKOUT TAGOUT PROCEDURES LOUVER ASSEMBLY SYSTEM ACCESS b EVAPORATOR HOUSING COVER To remove the louver assembly first place your hands Remove the back cover by removing the four screws under the louver panel and lift this up off the bracket which secure this to the cabinet see figure 6 and then away from the cabinet face see figure 3 Fig 6 Reverse the procedure when done to reinstall c REMOVING THE DRAWERS Figs Remove the drawer s from the drawer frame by lifting To gain full access to the refrigeration system from up on the drawer and then pulling out the side remove the cover by removing the bottom screws see figures 4 amp 5 Ill d REMOVING THE DRAWER FRAME Once the drawer s have been removed the drawer frame module can also be removed by loosening the front and back clamping knobs 2 of each located on the cross rail and liner locks see figures 7 amp 8 Slide the front cross rail locks towards the center of the drawer frame module and allow the liner locks to drop down from the top of the liner Pull the drawer frame module forward tip forward and pull out The entire Fig 4 frame assembly is now free to slide out of the cabinet Screw Locations Front Cross Rail Locks Fig 7 Fig 5 Side System Access When finished lower the louver assembly into position and replace the side panel Secure these in place using the previ
7. PARTS 509 50118 03 Marine Top for TEO65HT models TEOG0HT amp TE125HT 509 50118 04 Marine Top for TE072HT 550 10067 00 Drawer Assembly 509 50118 05 Marine Top for TEO84HT 550 10076 00 Drawer Face 509 50118 06 Marine Top for TEO96HT 550 10077 00 Drawer Frame 509 50118 07 Marine Top for TE110HT SER 60537 03 Drawer Frame Insert 509 50118 08 Marine Top for TE125HT 341 60176 04 Drawer Gasket 509 50118 09 Marine Top for TE139HT 344 60155 00 Drawer Roller LOUVER PANELS DRAWER PARTS 500 70075 00 For System on Left model TEO72HT only 500 70075 01 For System on Right 550 10074 00 Drawer Assembly 550 10069 00 Drawer Face CONTROL PARTS 550 10070 00 Drawer Frame 337 60403 00 Control Head SER 60537 02 Drawer Frame Insert 337 60405 03 Cabinet Temp Sensor 341 60176 01 Drawer Gasket 337 60406 03 Coil Temp Sensor 344 60155 00 Drawer Roller 337 60407 01 Liquid Line Sensor 337 60317 00 Relay Module 16 IX TROUBLESHOOTING WARNING CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL AND REFRIGERA TION SYSTEM TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE EXER CISE EXTREME CAUTION AT ALL TIMES IF TEST POINTS ARE NOT EASILY ACCESSIBLE DISCON NECT POWER ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST Compressor will not run compressor has no current draw Main circuit breaker open Compressor overload tripped Cabinet temperature satisfied Wired wrong or faulty connection INTELA TRAUL control malfunction Start component malfun
8. STEP 5 STEP 6 IV c REPLACING THE EVAPORATOR FAN Begin by removing the back cover by first removing the four screws which secure this to the cabinet see illustration 1 All evaporators and fans are located along the back wall of the cabinet and best accessed from the rear see illustration 2 Remove the holding rod and unhook the rod from the other end This evaporator fan can then be lifted away from the assembly see illustration 3 Disconnect the wires from the assembly Reverse the procedure to install the new evaporator fan Reconnect power to the unit Reset the microprocessor control defrost time settings to the correct time of the day WARNINGS 1 DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT TAGOUT PROCEDURES E Screw E Locations ZA Illustration 01 Illustration 03 IV d REPLACING THE EVAPORATOR COIL WARNINGS 1 DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT TAGOUT PROCEDURES 2 THIS PROCEDURE REQUIRES THE USE OF REFRIG ERANTS BE CERTAIN THE WORK AREA IS WELL VENTILATED SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 NOTE NOTE STEP 6 STEP 7 STEP 8 STEP 9 STEP 10 STEP 11 Remove evaporator housing cover as outlined in section Ill b Recover the refrigerant in the system following the current EPA G
9. closed on the gauge manifold Open the valve on the bottle Bleed charging hose at the manifold gauge to remove air NOTE Initially charge system through high side to prevent liquid refrigerant from reaching compressor 5 Open the high side gauge valve red Allow refrigerant to flow into the system until the nameplate charge is reached or until the high side will not accept any more refrigerant At this point shut the gauge and bottle valves 6 Reconnect power to the unit and check for proper operation and high pressure leaks 13 VI e CHARGING SYSTEM cont d 7 Add the remaining amount of refrigeration charge through the low side with the compressor running 8 Check for proper operation and leaks 9 Disconnect power to the unit and replace any covers removed VI f SYSTEM CLEAN UP INTRODUCTION When a compressor burn out or moisture infiltration is encountered the service person must make the determination as to the degree of system contamina tion Normally a compressor burn out will fit into one of three catagories CONTAINED compressor oil not acidic no oil dis coloration CONTAMINATED COMPRESSOR oil acidic discoloration of oil contamination limited to compressor MASSIVE CONTAMINATION contaminated oil and or refrigerant pumped through system CONTAINED 1 Replacement of liquid line drier 2 Install suction filter drier for clean up and then remove it when service is complete Usua
10. INTS ARE NOT EASILY ACCESSIBLE DISCONNECT POWER ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST VI d EVACUATING SYSTEM GUIDELINES cont d 1 Access the refrigeration system as outlined under SYSTEM ACCESS 2 Connect low blue side of gauge manifold to schrader valve on compressor process line and high red side of gauge manifold to schrader valve on filter drier process line 3 Connect center line of gauge manifold to vacuum pump 4 Turn vacuum pump on and open both sides of gauge manifold 5 Pull a vacuum to 200 microns 6 Break the vacuum with 3 psig of dry nitrogen 7 Repeat steps 5 and 6 8 Pull vacuum to 200 microns 9 Charge system and check for proper operation VI e CHARGING SYSTEM WARNING DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED WARNING THIS PROCEDURE REQUIRES THE USE OF REFRIGERANTS BE CERTAIN THE WORK AREA IS WELL VENTILATED SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN 1 Access the refrigeration system 2 Attach gauge manifold set to system low side to process tube on the compressor and the high side to the process tube on the drier NOTE See SYSTEM ACCESS 3 Be sure the system is properly leak checked and evacuated before charging as outlined under LEAK CHECK and EVACUATING SYSTEM 4 Make certain both valves are
11. ON Generally TE Series refrigeration products are installed by the dealer or others contracted by the dealer or owner Detailed installation instructions are included along with each unit when shipped ll e CLEANING Detailed cleaning instructions are included with each unit however special care MUST be given to the condenser coil The condenser coil must be cleaned at a minimum of every six months This can be done with a vacuum cleaner using a brush attachment or a stiff brush or wisk broom For more information please refer to Section V a of the TE Series Owner s Manual ll f TOOL REQUIREMENTS For most jobs a standard set of hand tools a VOM and AC current tester along with a temperature tester or thermometer are adequate However in some cases the following additional tools may be required as well Refrigeration Guage Manifold Refrigeration Reclaiming Equipment Acetylene Torch Anti Static Grounding Kit TL 84919 Nitrogen Bottle With Gauges Thin 5 16 Open End Wrench Refrigerant Reclaim Unit ll g REF N SYSTEM THEORY OF OPERATION The refrigeration system is the mechanism whereby heat is transferred from the cabinet to the outside air It works under the principle that the heat moves from hot to cold as it tries to establish equilibrium The microprocessor control signals a need for heat to be removed from the cabinet The compressor begins by compressing the refrigerant gas as itis di
12. P 6 Reverse the procedure to install STEP 7 Reconnect power to the unit STEP 8 Resetthe microprocessor control defrost time settings to the correct time of day Illustration 03 IV REPLACING THE CONDENSER COIL WARNINGS 1 DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT TAGOUT PROCEDURES 2 THIS PROCEDURE REQUIRES THE USE OF REFRIG ERANTS BE CERTAIN THE WORK AREA IS WELL VENTILATED SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 STEP 7 STEP 8 STEP 9 STEP 10 Remove the louver assembly as outlined in section Ill a Recover the refrigerant in the system following the current EPA Guidelines for refrigerant recovery NOTE The use of reclaiming equipment is required Disconnect the input and output lines to the condenser coil at the soldered joints closest to the condenser Remove the four 4 screws which secure the condenser coil to the mounting brackets see illustration 1 Remove the condenser coil Reverse the procedure to install the new condenser coil Install anew drier Charge the refrigeration system as outlined under CHARGING SYSTEM in SERVICE PROCEDUES AND ADJUSTMENTS Reconnect power to the unit Reset the microprocessor control defrost time settings to the correct time of the day STEP 1 STEP 2 STEP 3 STEP 4
13. Traulsen Refrigeration SERVICE MANUAL 07 Instructions For The Troubleshooting And Repair Of All Traulsen TE Series Refrigerated Equipment Stand Models Traulsen s equipment stands are solely intended for use with cooking equipment m AM NOTICE This Manual is prepared for the use of trained Authorized Traulsen Service Agents and should not be used by those not properly qualified This manual is not intended to be all encompassing but is written to supplement the formal training on the job experience and other product knowledge acquired by Autho rized Traulsen Service Agents Before proceeding with any work you should read in its entirety the repair procedure you wish to perform to determine if you have the necessary tools instruments and skills required to perform the procedure Procedures for which you do not have the necessary tools instruments and skills should be performed only by a trained Authorized Traulsen Service Agent Reproduction or other use of this Manual without the express written consent of Traulsen is prohibited FORM NUMBER TR35896 REVISED 06 15 l THE SERIAL TAG Il GENERAL INFORMATION Introduction Model Designations Wiring Diagrams Cleaning Tools Control Locations Specifications Operating Data Chart moop Tw Louver Assembly Drawer Gaskets 20500070 IV REPLACING THE Evaporator Housing Cover Removing The Drawer Removing The Drawer
14. components are located behind the front louver inside a metal tray To access the start components first remove the louver assembly as shown in section Ill a Next loosen the top set screw see figure 10 and remove the molex connection in the back of the box to gain access to the back set screw Slide the electrical box out the font on its tracks See figure 11 for component detail Ill h ACCESSING START COMPONENTS cont d Control Head TOP Mounting Screw Fig 10 Bottom Mounting Screw On Off Switch Compressor Start Relay Modular Relay Start Capacitor Run Capacitor On Off Compressor Relay Switch Fig 11 IV REPLACING THE CONDENSER FAN MOTOR AND OR BLADE STEP 1 Remove the louver assembly as outlined in WARNINGS section Ill to gain access through leftside 1 DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT TAGOUT STEP2 Remove the screws holding the fan motor PROCEDURES bracket to the compressor mounting base see illustration 1 STEP 3 Remove the blade from the motor shaft by removing the nut see illustration 2 NOTE Install the concave side of the fan blade toward the motor NOTE If the blade is all that is being replaced stop here and reverse procedure to install STEP 4 Remove the mounting bracket from the motor see illustration 3 Illustration 01 STEP 5 Disconnect the lead wires at the compressor junction box STE
15. ction Compressor motor windings open RON Compressor will not run current draw and trips overload Low voltage Start component malfunction Compressor windings shorted Locked rotor Excessive discharge pressure Compressor short cycles on overload Low voltage Low refrigerant charge Dirty condenser coil and or filter Wired wrong or faulty connection Condenser fan inoperative Run capacitor malfunction Start component malfunction INTELA TRAUL control malfunction High head pressure ov Compressor short cycles Improper air flow over evaporator coil Low ambient conditions INTELA TRAUL control malfunction Bad sensors Temp differential set too close Continuous unit operation Loss of refrigerant Excessive drawer openings INTELA TRAUL control malfunction Broken compressor valves Very dirty condenser and or filter Check the DL if higher than 160F DIRNS Compressor run time lengthy Partial loss of refrigerant High ambient conditions Dirty condenser coil or improper air flow over condenser coil Excessive product load Excessive drawer openings Drawer gasket requires replacement INTELA TRAUL control malfunction Contaminates in refrigeration system Compressor valve leakage Inadequate defrost cycle 1 2 3 4 5 6 7 8 9 10 Low suction pressure Capillary tube restricted Drier plugged Loss of refr
16. e discharge and suction lines to the compressor see illustration 1 Remove the compressor which is secured by either four 4 nuts or pins Install the new compressor and connect the input and output lines Connect the lead wires at the junction box Install a new drier Charge the refrigeration system as outlined under CHARGING SYSTEM in SERVICE PROCEDUES AND ADJUSTMENTS Reconnect power to the unit Reset the microprocessor control defrost time settings to the correct time of day 10 WARNINGS 1 DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT TAGOUT PROCEDURES 2 THIS PROCEDURE REQUIRES THE USE OF REFRIG ERANTS BE CERTAIN THE WORK AREA IS WELL VENTILATED SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN Illustration 01 V WIRING DIAGRAM MIT TE RELAY MODULE 6 DOOR SWITCH S NEUTRAL 4 DOOR HEATER 3 BLOWER CABINET SENSUR GREEN COIL SENSOR BLUE DISCHARGE SENSOR YELLOW DEFROST 1 COMPRESSOR 1 COMPRESSOR EVAPORATOR FANS DOOR HEATERS COMPRESSOR RELAY P N 379 60463 00 REV E Li BLACK 0 amp j GRAY WHITE DRANGE WHITE TANK pmp Iu COMP FAN vei mu COMPRESSOR DUMMY TERMINAL CONNECTION NOTE CONNECT YELLOW WIRE FROM START RELAY TO TERMINAL 3 CONNECT RED WIRE FROM NEUTRAL TO TERMINAL 1
17. igerant Poor air flow Iced evaporator coil o High head pressure Improper air flow across condenser High ambient conditions Overcharge of refrigerant Air in system Dirty condenser coil Oo Defrost heater malfunction Wired wrong or faulty connection Cabinet air leak Coil sensor failure INTELA TRAUL control malfunction Will not defrost or inadequate defrost ORWN gt Coil icing Number of defrost cycles too few Defrost duration too short Cabinet air leak Drain tube plugged Defrost heater not working Non frozen product put into cabinet Coil sensor failure NOaRON gt The cabinet amp coil sensors show high temperature Sensor needs rreplacing place sensor tip and thermometer in ice water Change sensor ir readings differ or if sensor displays 40 02 266 18 For More Information On The Proper Installation Use and Maintenance Of Traulsen Refrigerated Equipment Stand Models Please Refer To The Following Materials Available From Your Local Hobart Traulsen Sales amp Service Location INTELA TRAUL Master Service Manual Form Number TR35705 For Questions Regarding Repair or Warranty Service Please Contact Traulsen Service At 800 825 8220 ext 6509 HOURS OF OPERATION Monday thru Friday 7 30 am 4 30 pm CST Traulsen 4401 Blue Mound Road Fort Worth TX 76106 Phone 800 825 8220 Fax Svce 817 740 6757 Website www traulsen com Qual
18. ity Refrigeration
19. lly within 48 hours 3 Replacement of compressor 4 Evacuation to 200 microns 5 Charge by weight CONTAMINATED COMPRESSOR The contaminated compressor requires the same procedure as the contained burn out Plus the system must be flushed with nitrogen after the compressor and drier has been removed VI SERVICE PROCEDURES amp ADJUSTMENTS cont d WARNING CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE EXERCISE EXTREME CAUTION AT ALL TIMES IF TEST POINTS ARE NOT EASILY ACCESSIBLE DISCONNECT POWER ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST VI f SYSTEM CLEAN UP INTRODUCTION cont d MASSIVE CONTAMINATION The replacement compressor MUST NOT be installed until after system clean up procedures have been completed 1 Remove the burned out compressor as outlined under COMPRESSOR in Section IV f 2 Remove the capillary tube metering device 3 Purge nitrogen through the high and low sides of system until moisture and contaminated oil has been removed from the remaining components of the system 4 Reassemble refrigeration system and add a CW style liquid drier and a suction line drier 5 Purge nitrogen through the high and low sides of system for 5 minutes 6 Evacuate refrigeration as outlined under EVACUATING SYSTEM for 30 minutes Repeat nitrogen purge and evacuate two more times 7 Charge system as outli
20. manufactured as other than standard or for older production units please contact the factory PART NO NAME OF PART PART NO NAME OF PART CABINET SUPPORTS COMPRESSORS SER 60536 00 4 High Caster w o Lock 321 60225 00 For Models TE036HT thru TEO84HT SER 60536 01 4 High Caster with Lock 321 60226 00 For Models TE096HT thru TE139HT DRAWER PARTS MISC SYSTEM COMPONENTS models TE036HT amp TE065HT 323 60088 00 Suction Heat Exchange Evap 9 Coil 550 10053 00 Drawer Assembly 350 10000 00 Suction Heat Exchange Evap 18 Coil 550 10057 00 Drawer Face 322 60048 00 Evaporator Coil 9 550 10059 00 Drawer Frame 322 60050 01 Evaporator Coil 18 SER 60537 00 Drawer Frame Insert 325 60103 00 Liquid Line Drier 341 60176 02 Drawer Gasket 325 60144 00 Condenser Fan Motor Assembly 344 60155 00 Drawer Roller 325 60145 00 Evaporator Fan Motor Assembly 325 60135 00 Condenser Fan Blade DRAWER PARTS 338 60050 00 Condenser Fan Motor all models except TE036HT TE060HT 65 TE125HT amp 701 61119 00 Spring Rod 9 Evaporator Coil 072 701 61119 01 Spring Rod 18 Evaporator Coil 550 10054 00 Drawer Assembly 337 60360 01 Compressor Relay 550 10058 00 Drawer Face 550 10060 00 Drawer Frame MISC CABINET PARTS SER 60537 01 Drawer Frame Insert 337 60346 00 ON OFF Power Switch 341 60176 03 Drawer Gasket 509 50118 00 Marine Top for TEO36HT 344 60155 00 Drawer Roller 509 50118 01 Marine Top for 48 509 50118 02 Marine Top for TEOG0HT DRAWER
21. ned under CHARGING SYSTEM Allow for the increased liquid capacity of the liquid line drier 8 Reconnect power and check for proper operation 9 Disconnect power and install any panels removed MASSIVE CONTAMINATION cont d 10 Return between 24 and 48 hours to recover gas replace liquid line drier with a CW style drier Remove the suction drier but do not replace 11 Evacuate and charge system as outlined under EVACUATING SYSTEM and CHARGING SYSTEM VI g HEATER TEST DRAWER PERIMETER HEATER 1 Access the heater wire around the drawer frame 2 Plug the unit in and verify 120 volt supply to the heater 3 The reading should be 25 amp Vil ELECTRICAL OPERATION VII NORMAL OPERATION 1 Conditions a Unit connected to correct voltage check using a volt meter b Microprocessor off cycle defrost settings correct c Condensing unit controlled by the microprocessor control d Cabinet at desired temperature e Door perimeter heaters are powered 100 of the time as preset by the factory this can be adjusted using the microprocessor control f Evaporator fan powered g Microprocessor control operating correctly 2 Cabinet temperature rises above set temperature a Microprocessor control initiates compressor operation b Evaporator fan should be ON all the time 3 Set temperature is met a Conditions return to those outlined in step 1 VII b DEFROST MODE 1 C
22. onditions a Unit operating in normal mode 2 Defrost initiated by the microprocessor control an off cycle defrost should occur every 60 minutes 3 Defrost terminated by either 1 Evaporator Coil Temperature or 2 Maximum Set Time Interval 4 Cabinet returns to normal operation a Temperature controlled by the microprocessor control b Evaporator fan stays ON evaporator coil will reach desired temperature Vil ELECTRICAL OPERATION VII c COMPONENT FUNCTION Compressor Pumps refrigerant thru refrigeration system components and compresses the low pressure vapor into high pressure vapor compressor Condenser Fan Draws air across condenser coil to aid in removing heat from the refrigerant and moves air across compressor to aid in cooling the Start Capacitor Stores electrical charge which helps start the compressor motor Evaporator Fan Draws air from the cabinet and pulls the air thru the evaporator coil Run Capacitor Helps keep the compressor motor running after starting Microprocessor Control Drawer Perimeter Heater Performs the functions of the 1 defrost timer 2 high limit switch 3 thermometer and 4 thermostat Heats drawer opening to prevent condensation from forming Contactor Relay Controls voltage to compressor motors VII d INSTALLATION OF THE SENSORS There are two sensors used inside the cabinet The first one is the Cabinet Sensor that is used to cycle the compre
23. ously removed screws lll REMOVAL amp REPLACEMENT OF BASIC PARTS cont d WARNING DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT TAGOUT PROCEDURES e DRAWER GASKETS To remove the gasket to be replaced grasp it firmly by one corner and pull it out Before attempting to install a new gasket both the unit and the gasket itself must be at room temperature Insert the four corners first by using a rubber mallet or hammer with a block of wood After the corners are properly inserted work your way towards the center from both ends by gently hitting with a mallet until the gasket is completely seated in place see figure 9 for gasket cross section GASKET ASSEMBLY SIDE DRAWER PANEL VERTICAL GASKET RETAINER NOTE The gasket may appear too large but if it is installed as indicated above it will slip into place f THE MICROPROCESSOR CONTROL To remove the microprocessor controller from the unit in which it was installed please refer to section V of your INTELA TRAUL Master Service Manual Ill g DRAIN PAN To remove the drain pan begin by removing the evaporator housing cover as outlined in section ll c Next remove the screws and brackets which secure the drain pan and remove the drain tube from the drain pan Finish by sliding the drain pan out from under the coil Reverse the procedure to install h ACCESSING START COMPONENTS The start
24. r Traulsen product as well as the model and serial number This tag is located on the upper right interior wall of all TE Series models READING THE SERIAL TAG AMPS Serial The permanent ID of your Traulsen Model The model of your Traulsen Volts Voltage Hz Cycle OZ PH Phase LOW Total Current Maximum amp draw Minimum Circuit Minimum circuit required 02 Lights Light wattage LOW Heaters Heater amperage Refrigerant Refrigerant type used Design Pressure High amp low side operating pressures and refrigerant charge Agency Labels Designates agency listings ll GENERAL INFORMATION ll INTRODUCTION This manual applies to the following Traulsen models only TEO36HT TEO48HT TEOGOHT TEOG5HT TE072HT TEO84HT TEO96HT TE110HT TE125HT amp TE139HT Il b MODEL DESIGNATIONS TEOGOHT Position 1 TE Traulsen Equipment Stand Position 2 036 36 Long Model 048 48 Long Model 060 60 Long Model Position 3 Refrigerator Il c WIRING DIAGRAM Refer to the wiring diagram for any service work performed on this unit A copy is located on the unit when shipped Should you require another copy or a wiring diagram for an older production unit please contact Traulsen Service at 800 825 8220 and provide the model and serial number of the unit involved this information is located on the serial tag see page one Il d INSTALLATI
25. scharged The high pressure refrigerant now circulates through the condenser removing heat from the refrigerant and condensing it into a liquid From there the refrigerant flows to the filter drier which removes all traces of moisture and particles from the system After the filter drier the refrigerant passes through a metering device Traulsen uses a capillary tube to regulate the flow of refrigerant into the evaporator coils In the evaporator coil heat is transferred from the cabinet to the refrigerant which changes from a cold liquid to a warm low pressure gas When the desired cabinet air temperature has been reached the microprocessor control shuts off the compressor Evaporator aa Capillary Tube Compressor Suction Line Condenser air from this vaporizes condensate Filter Drier T Discharge Line Fig 1 The Refrigeration System Il h AIR FLOW REQUIREMENTS To assure optimum performance the condensing unit of your Traulsen unit MUST have an adequate supply of air for cooling purposes Therefore the operating location must allow a minimum of 12 clearance in front of the louvers to allow for unrestricted air flow to the condensing unit ll i THE MICROPROCESSOR CONTROL For detailed information on replacement repair or adjustment of the INTELA TRAUL microprocessor control please refer to it s service manual form number TR35705 Il GENERAL INFORMATION
26. ssor on and off at the correct temperature The cabinet sensor is mounted between the two coils just below the top of the cabinet thru the 1 2 holes in the back wall and the tip should be 1 inside the cabinet Refer to the drawing below The part number for the Cabinet Sensor is 337 60405 03 Insert sensor inside the cabinet thru 1 2 holes in back wall 1 inside cabinet The Evaporator Coil Sensor is to be mounted in the evaporator in the center of the coil and fully inserted into the coil until only the wire is visible and then pinch the fins around the cable to hold it in place The part number for the Evaporator Coil Sensor is 337 60406 03 Fully insert probe of Coil 756 between 1 and 2 hair bend 15 Attach sensor to the liquid line using the The third sensor used is a Liquid Line Sensor This sensor is to be installed on the liquid line as it comes out of the condenser coil The part number for this sensor is 337 60407 01 wrap When the condensing temperature reaches 140 F or greater the control will display CLN FIL Should the condensing temperature increase to 160 F the compressor will automatically shut off When the liquid line temperature drops below 140 F the compressor will restart and when the line temperature drops to 120 F the alarm will reset Vill REPLACEMENT PARTS LISTING NOTE Part numbers listed are for standard products as currently manufactured For products
27. uidelines for refrigerant recovery NOTE The use of reclaiming equipment is required Remove the screws which secure the evaporator to the mounting brackets Disconnect the evaporator output line Unsolder the liquid line leading into the capillary tube When removing the capillary tube care must be taken toheat protect Heat sink or wrap a cold dampcloth over the capillary tube to protect it from overheating Inspect the end of the liquid line after disassembly it could become plugged with solder Remove the evaporator coil and capillary tube from the unit Reverse the procedure to install the new evaporator coil and capillary tube Install a new drier Charge the refrigeration system as outlined under CHARGING SYSTEM in SERVICE PROCEDUES AND ADJUSTMENTS Reconnect power to the unit Reset the microprocessor control defrost time settings to the correct time of day IV e REPLACING THE COMPRESSOR NOTE Compressor models will vary with each cabinet model but the basic removal instructions can be followed STEP 1 NOTE STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 STEP 7 STEP 8 STEP 9 STEP 10 STEP 11 Recover the refrigerant in the system following the current EPA Guidelines for refrigerant recovery The use of reclaiming equipment is required Remove the compressor junction box cover Disconnect all wire leads coming into the junction box Disconnect th
Download Pdf Manuals
Related Search
Related Contents
« L`écrit du corps» - La farouche compagnie ACR INV222 MSDS - 同仁化学研究所 User Manual IP Router User Manual SIP-CB/a - Honeywell Process Solutions Iced Tea Maker Bostitch N66C-1 Installation Guide Copyright © All rights reserved.
Failed to retrieve file