Home
CP-13-07.2 9060 Cascade Service Manual Model
Contents
1. 3 2 Figure 15 Controller Start Up Display The controller comes preconfigured for its corresponding handgun from the factory The following table lists the applicator types shown on the display as per the current revision of this manual and is a reference to verify that the gun configuration jumpers are in their correct positions if unexpected behavior is observed START UP DISPLAY C 65 85 After the initial start up delay the unit will be configured for the applicator based on the gun type jumper settings and is ready for standard operation Ransburg WARNING gt DO NOT adjust the gun configuration jumpers if they are incorrect contact your Ransburg representative gt USE ONLY the gun type configuration for the specific applicator being used Us ing the wrong configuration may allow for operation outside the recommended pa rameters and values for the applicator and can result in damage or un safe op eration NOTE gt During start up the gun trigger input should NOT be active An active trigger signal will cause a non resettable boot fault and prevent the unit from being oper ated This is designed to prevent unintena ed firing of the high voltage immediately after start up Please refer to the Fault Section of this manual fo
2. EFEK re Li Tuo 1 13 TRS We LOCKOUT JUMPER LOCATIONS Figure 18 Lockout Jumper Location Front Panel Lockout This feature locks out any changes to the kV setting from the front panel of the Controller 1 Set the kV to the desired value using the front panel buttons This must be set prior to installing the jumper 2 Turn AC power off and access the interior of the Controller Place the jumper across two 2 pins at location 16 on the main PC board See Figure 19 Close the Controller and turn AC power back on Pressing the front panel or setpoint buttons will now have no affect on the kV setting 22 9060 Cascade Low Voltage Controller Operation L JUMPER 16 INSTALLED FRONT PANEL CONTROL DE ACTIVATED Figure 19 Jumper Location Front Panel Lockout Overload The overload circuit may be activated for applications that require overload indication or notification of high current draws of the applica tor The default overload value is set in the software to the maximum microamp rating minus 10 microamps 1 Turn AC power off and access the interior of the Controller 2 Place the jumper across the two 2 pins at location 17 on the main PC board See Figure 20 3 Close the Controller and turn AC power back on An overload fault will now occur if the microamp display exceeds the overload value
3. SED 12 INSTALLATION 13 20 GENERAL INFORMA TION secs e e ek 13 OCA ION OF IIE eee emer ei ee Ye eee er ee 13 ELECTRICAL NOS E Ss O 14 a 15 INPUT CONNECTIONS nn 15 16 SAFET GRO UIND nantes ESE E SEE aS bate 17 INPUT VOLTAGE SELECTION RES E 17 WINER OG IRS 17 19 LOW VOLTAGE ae den atthe edie SESS 19 RELAY CONTACT OUTPUT Sassanid eden 19 HANDGUN TRIGGER SIONAL ca oe ac a ca bse asics eae eae eee 20 OPERATION 21 26 SLA RE UP La E O 21 BASICOPFERATIONS SS ES E RES NE 21 22 LOCKOUT tee ee ne oe ene N 22 23 KY TESTJUMPER kS EDO SASS ia ESE SEG 23 OPERATIONS gasses 24 FAULT DESCRIPTIONS o a ARAS Catia 24 26 13 07 2 9060 Cascade Low Voltage Controller Contents Ransburg CONTENTS PAGE MAINTENANCE 27 30 TROUBLES MOO ING GUIDES sao E 27 FAULT TROUBLESHOOTING GUIDE sss 27 29 PARTS IDENTIFICATION 31 32 LOW VOLTAGE CONTROLLER MODEL IDENTIFICATION
4. 31 a en on O 32 ACCESSORIES 33 34 PRG GES SORES ae etek ee cel 33 WARRANTY POLICIES 35 WARRANTY cr yaa altars vad aan o ohne 35 CP 13 07 2 Ransburg CP 13 07 2 9060 Cascade Low Voltage Controller Safety SAFETY SAFETY PRECAUTIONS Before operating maintaining or servicing any Ransburg electrostatic coating system read and understand all of the technical and safety literature for your Ransburg products This manual contains information that is important for you to know and understand This infor mation relates to USER SAFETY and PRE VENTING EQUIPMENT PROBLEMS To help you recognize this information we use the fol lowing symbols Please pay particular attention to these sections A WARNING states information to alert you to a situation that might cause serious inju ry if instructions are not followed A CAUTION states information that tells how to prevent damage to equipment or how to avoid a situation that might cause minor injury A NOTE is information relevant to the pro cedure in progress While this manual lists standard specifications and service procedures some minor devia tions may be found between this literature and your equipment Differences in local codes and plant requirements material delivery require ments etc make such variations inevitable Compare thi
5. KV uA HV ff a FAULT RESET O 2 fe A LOCAL HV REMOTE CONTROL lt gt ON i POWER O Figure 3 9060 Operator Interface SWITCHES Power Switch The 9060 Controller contains a single rocker switch for power On Off selection When the unit is powered on the screens should be lit and display the gun display type information and the software version number for a short period of time LEDS High Voltage On Indicator The red High Voltage On Indicator is lit when a trigger signal has been received by the unit and the high voltage output from the cascade has been enabled Fault Indicator The red Fault Indicator is lit when a fault occurs as determined by the microprocessor When a fault occurs the light will turn on and the identifi cation code ID for the fault will be displayed blinking on the uA meter display For more information on the faults and fault ID codes please refer the Fault Descriptions section in the Operations portion of this manual Local Mode LED Indicator The local mode LED indicator is a left pointing triangle and is located on the left side the HV CP 13 07 2 control button on the center of the operator interface This LED is lit when the Controller is in local mode Remote Mode LED Indicator The remote mode LED indicator should NOT be lit for handgun units Active Preset LED Indicators 3 The active prese
6. Description 5 80131 21X Vector R70AS Handgun 80131 31X 80131 41X 80131 51X CP 13 07 2 Ransburg 9060 Cascade Low Voltage Controller Introduction SPECIFICATIONS Environmental Operating Temperature 0 C to 40 C Storage and Shipping Temperature 40 C to 85 C Allow power supply to go to room temperature before use Humidity 95 Non Condensing Physical Height 14 0 cm 5 5 inches Width 21 6 cm 8 5 inches Depth 19 1 cm 7 5 inches Weight 3 4 kg 7 5 Ibs Electrical Input Voltage 100 240 VAC Frequency 50 or 60 Hz Current 1 RMS Wattage 40 watts max Output Voltage 20 VDC Output Current 1A DC max Ground Use known good earth ground CP 13 07 2 8 9060 Cascade Low Voltage Controller Introduction Ransburg 9060 CONTROLLER FEATURES No Description Description _1 Display 8 Standard VO Connector _2 Micro Amp Display 9 Fuses _6 Fault Indicator 13 Air Flow Switch Connector Figure 2 9060 Cascade Low Voltage Controller Features CP 13 07 2 Ransburg OPERATOR INTERFACE The 9060 Controller shown in Figure 3 has a simple operator interface consisting of 7 LEDs Light Emitting Diodes one 1 power switch seven 7 buttons one 1 current LED bar graph and two 2 screens containing seven segment displays
7. 8 8 7 O Ll 11 9 L JUMPER 17 INSTALLED OVERLOAD ACTIVATED Figure 20 Jumper Location Overload 23 Ransburg a KV TEST JUMPER To assist in testing and troubleshooting a jumper J8 has been added to the main PC board By covering shorting both terminals of this jumper the high voltage of the spray applicator can be activated Thus for testing and troubleshooting high voltage output can be obtained without the need to trigger air through the spray applicator After testing the jumper must be repositioned so that it covers onl one terminal open or the high voltage will stay all the time See Figure 21 for the location of test jumper J8 WARNING gt If jumper J8 is left covering shorting both terminals high voltage will be on whenever the AC power is turned on NOTE gt Use Ransburg Calibrated Equipment ONLY for testing and troubleshooting Re fer to the Accessories section of this man ual for part numbers for testing equipment SETPOINT OPERATIONS Voltage Setpoints The voltage on the 9060 Cascade Low Voltage Controller is adjustable between 20 kV and full CP 13 07 2 Ransburg kV DC There are 3 voltage setpoints presets 1 2 and 3 Each of these setpoints can be individually adjusted between 20 kV and full kV DC The three 3
8. ing materials Inadequate grounding will cause a spark hazard A spark can ignite many coating materials cause fire or explosion SAFEGUARDS Tells how to avoid the hazard Parts being sprayed must be supported on conveyors or hangers and be grounded The resistance between the part and ground must not exceed 1 megaohm Reference NFPA 33 or EN 501 76 All electrically conductive objects in the spray area with the exception of those objects required by the process to be at high voltage must be grounded Any person working in the spray area must be grounded Unless specifically approved for use in hazardous lo cations the power supply and other electrical control equipment must not be used in Class 1 Division 1 or 2 locations or Class 1 Zone 0 for European Applica tions CP 13 07 2 Ransburg Ransburg 9060 Cascade Low Voltage Controller Safety NOTES CP 13 07 2 6 9060 Cascade Low Voltage Controller Introduction INTRODUCTION GENERAL DESCRIPTION The Ransburg 9060 Cascade Low Voltage Controller 80131 XXX is used to provide high voltage for electrostatic application equipment It uses a combination of proven high voltage generation technology and microprocessor based control It uses a variable voltage output to drive an external cascade that amplifies the voltage to a high KV level It also uses current feedback information to maintain the desired set point The processor circuitry
9. If desired and codes permit cabling may be used for these signals but for maximum noise immunity the cabling must contain overall foil and braided shields and be terminated as described in the preceding paragraph Cable is recommended for all of the analog and digital remote control signals including the relay controlled DC I O high voltage output signal fault output signal Again for maximum noise immunity the cabling must contain overall foil and braided shields and be terminated in a continuous 360 manner as described in the preceding paragraph Special fittings have been provided on the control panel for termina tion of these cables at that point The use of these fittings is described in the corresponding sections of this manual Using the methods previously described the 9060 Controller have been successfully tested to the stringent standards of the Electromagnet ic Compatibility Directive of the European Union The results conclude that these units are neither a source of electrical noise nor 9060 Cascade Low Voltage Controller Installation 14 9060 Cascade Low Voltage Controller Installation affected by electrical noise when the above methods are utilized CONNECTIONS For maximum noise immunity I O wiring should be run in conduit or cables having a foil shield with an overall braided shield The foil shield provides 100 shielding while the braid provides a means of making proper 360 shield
10. The interlock contacts Supplied by us er should be rated for at least 1 amp at 240 VAC NOTE gt The total resistance of the series inter locks between L2 and L3 should be less than 300 LOW VOLTAGE CABLE Insert the connection control unit end of the low voltage cable into the controller Make sure that the male notch on the low voltage cable lines up with the female notch on the controller push in by hand as far as it will go then tighten the nut Use the same procedure to connect the low voltage cable to an external cascade unit Refer to Figure 12 A WARNING gt The Controller MUST be OFF when the applicator is removed or reinstalled Ransburg Connection Cascade End BETE Connection Control Unit End Figure 12 Low Voltage Cable RELAY CONTACT OUTPUTS A set of relay contacts for high voltage CR1 and fault CR2 conditions is provided at 2TB 2 and 21B 4 See Figure 8 One end of these relay contacts are connected together and also connected to a source input terminal 21B 3 See Figure 11 When a source voltage is present at 2TB 1 and either the high voltage is on or a fault condition occurs the source voltage will become available at the output end of the corresponding contact Maximum contact ratings are as follows MAXIMUM
11. holes in the braid and the braid allows for practical 360 termination at both ends of the cable The AC input cord is not shielded but is di rected to an AC line filter as soon as it enters the cabinet This method filters out most of the noise that comes in on the AC line For maxi mum noise immunity if the AC line is wired using conduit instead of the provided AC line cord it should connect to the filter as soon as It enters the cabinet with as short of leads as possible Additional noise protection can be provided by running the AC input line to the control panel in grounded conduit For maximum noise protection any user supply input output I O wiring should be made using shielded cable or conduit which is connected to earth ground in a continuous 360 fashion at both ends The best way to do this is to use a connector conduit fitting at each end of the cable conduit that makes contact to the shield conduit in a full 360 circle around the cable conduit and makes contact to the grounded enclosure in the same fashion Connecting the drain wire of a shield to a ground point on or in the cabinet usually referred to as pigtailing is not an effective method of shielding and actual ly makes things worse see Figure 5 CP 13 07 2 4 r 360 Termination to ground F 1 good shielding Figure 5 Pigtailing Connection is recommended that all AC interlocks be run in conduit
12. terminations at the cable to cabinet connection points To make I O connections using shield ed cable perform the following 1 Remove the cable grommet hardware trom the desired I O connector housing See Figure 6 2 Route the desired length of I O cable through the connector housing and mark 1 span of cable that passes through the connector housing to be stripped to braid See Figure 7 3 Remove cable and strip marked 1 section to cable braid 4 Slide the cable grommet hardware onto the cable in the order shown in Figure 7 5 Route the cable back through the connector housing and connect its wires to the desired I O terminals inside the 9060 Controller 6 Tighten the cable grommet ensuring the grommet spring makes 360 contact with the exposed braid of the cable for maxi mum noise immunity 7 For maximum noise immunity connect the braid of the cable to earth ground at the end opposite the Controller Ransburg 4 Cable lt Figure 6 Cable Grommet Analog 1 0 Cable ae 1 Inside of Cabinet Connector Housing Figure 7 Cable Stripping AC INPUT CONNECTIONS For non conduit installations plug the detacha ble AC line cord into the receptacle on the side of the 9060 Controller Plug the other end of the line cord into a properly grounded 120 volt AC outlet CP 13 07 2 Ransburg NOTE gt In general conduit must be used for approv
13. CONTACT RATINGS Tec Ka 6OW 62 5VA 125VDC 125VAC 7 When wiring to 21B use a shielded cable and route the wiring through the standard 1 connector as described in the I O Connectors section of this manual NOTE gt An internal 24 VDC source voltage is available at 2TB 1 Using a jumper wire this voltage may be connected to 2TB 3 to be used as the source voltage for the relay contact outputs In this case the total current sourced should not exceed 1 amp CP 13 07 2 Ransburg 9060 Cascade Low Voltage Controller Installation HANDGUN TT TRIGGER SIGNAL Handguns use a flow switch 13742 01 or i 13742 02 to provide the trigger signal One of the listed flow switches is mounted inside the 9060 Controller chassis via the Air Flow Switch Connector on the side panel When the hand gun trigger is pressed and flow starts the flow switch is activated and triggers the high volt 0 Ground Screw For reference when replacing a flow switch perform the following NO 1 Turn the 9060 Controller off disconnect Back of Cabinet it from AC source and remove the fuses Figure 13 Grou
14. Cascade Low Voltage Controller Operation 24 9060 Cascade Low Voltage Controller Operation Cable Fault CF This fault will occur if high voltage is active and the microprocessor detects that no current 15 being supplied to the applicator This indicates a connection problem from the control unit to the handgun barrel assembly Typical causes include a faulty low voltage cable stuck pins on the plug assembly or contaminated contacts on the applicator This may also indicate a faulty barrel assembly for a handgun For additional information refer to the Fault Troubleshooting Section CABLE FAULT ILLUMINATES FAULT INDICATOR AND DISPLAYS Figure 23 Cable Fault Display Ground Fault GF this fault occurs the fault indicator on the control unit will illuminate a GF indication will show in the uA display This fault will occur if the microprocessor detects a loss of ground at the high voltage section If this fault occurs reset the fault This fault can be caused by a broken ground path between the handgun and the control unit and may indicate a faulty cable or plug assembly For more information refer to Fault Troubleshooting Section GROUND FAULT ILLUMINATES 1 FAULT INDICATOR AND DISPLAYS GF i Figure 24 Ground Fault Display 20 Ransburg Overload Fault OL This fault will occur if the overload feature is active see Overload Activation previously in th
15. 1910 North Wayne Street Angola Indiana 46703 9100 Telephone 260 665 8800 Fax 260 665 8516 Technical Service Assistance 320 Philips Ave Toledo Ohio 48612 1493 Telephone toll free 800 233 3366 Fax 419 470 2233 Technical Support Representative will direct you to the appropriate telephone number for ordering Spare Parts Form No CP 13 07 2 Litho in U S A 05 13 2013 Ransburg All rights reserved Models and specifications subject to change without notice CP 13 07 2 36
16. ACT CLOSURES a eR ee BOOTH FAN INTERLOCK CONVEYOR INTERLOCK SOLVENT SUPPLY INTERLOCK INTERLOCK INTERLOCK SSE IN COMMON NEUTRAL N LO O IN EARTH GROUND gt AC IN HOT LINE rt ee ee ee Figure 9 TB1 Interlock Wiring 1 Conduit Adapter Plate M il SIDE VIEW Figure 10 Installation of Conduit Adapter Plate 16 9060 Cascade Low Voltage Controller Installation 17 SAFETY GROUND Crimp the appropriate connector onto the ground wire assembly and install from the Controller ground stud located on the side panel to a true earth ground gt The ground wire assembly MUST be connected from the Controller ground stud to a true earth ground INPUT VOLTAGE SELECTION The 9060 Controller accepts universal input voltage between 100 and 240 VAC at 50 or 60 Hz There is no need to change any switch settings when changing input from 110 to 240 VAC or from 240 to 110 VAC NOTE gt All 9060 units 80131 XXX shipped from the factory for either 110 VAC input or 240 VAC input will have a 72771 06 1 Amp front panel fuses installed INTERLOCKS Interlocks required by code are as follows Booth Fan Interlock When the booth fan is on a contact closure is made e Conveyor Interlock When the conveyor is moving a contact closure
17. Handgun Model Reference Table B Plug Selection Domestic Dash CP 13 07 2 Ransburg 9060 Cascade Low Voltage Controller Parts Identification 9060 Cascade Low Voltage Controller Parts List 9060 Cascade Low Voltage Controller PC Mainboard for 80131 21X 9060 Cascade Low Voltage Controller PC Mainboard for 80131 31X 51X 9060 Cascade Low Voltage Controller PC Mainboard for 80131 41X Power Supply 24V 24VDC Power Supply 1PS Switch Rocker On Off Switch 13742 01 13 742 02 76434 01 72771 06 Figure 31 Identifications 13 07 2 32 9060 High Voltage Controller Accessories Ransburg ACCESSORIES 9060 Low Voltage Controller Accessories List HV Probe Meter w Test Leads Paint Test Probe w Meter Deluxe Kit Include HV Probe Meter w Test Leads and Paint Test Probe 33 CP 13 07 2 Ransburg 9060 High Voltage Controller CP 13 07 2 34 9060 Cascade Low Voltage Controller Warranty Policies 35 WARRANTY POLICIES LIMITED WARRANTY Ransburg will replace or repair without charge any part and or equipment that falls within the specified time see below because of faulty workmanship or material provided that the equipment has been used and maintained in accordance with Ransburg s written safety and operating instructions and has been used under normal operating conditions Normal wear items are excluded THE USE OF OTHER THAN RANSBURG APPROVED PARTS VOID ALL
18. SERVICE MANUAL Ransburg CP 13 07 2 MAY 2013 9060 CASCADE LOW VOLTAGE CONTROLLER LV3 Handguns u A RESET A Ransburg 9060 MODEL 80131 IMPORTANT Before using this equipment carefully read SAFETY PRECAUTIONS starting on page 1 and all instructions in this manual Keep this Service Manual for future reference Service Manual Price 50 00 U S Ransburg CP 13 07 2 Ransburg 9060 Cascade Low Voltage Controller Contents CONTENTS PAGE SAFETY 1 6 SAFETY PRECAUTIONS SSIS SRE SRS lod ah cure es 1 HAZARDS SAFEGUARDS SSE ALOE ERAS Aenea ate ata 2 5 INTRODUCTION 7 12 GENERAL DESCRIPTION SSS SESS DESE E SDE EDD 7 SAFETY T 000 plas ae ee en ee a ne er ee ee eee 7 II SER NG 7 SPE CIFICATION bs tee eae ean EA 8 CONTROLLER FEATURE SS ese 9 ee a 10 A Pt On ee CS ee ON eS 10 LE ee ee oe E eRe eee eee eee 10 BUTTONS O O 10 11 CONNEC HONINTERFACE eee et Ee aes 11 CONNECTOR SEE 11 FUSE a E 12 SIGONALINTERFAGCE SSCS SEED AIEE
19. TB L3 as shown in Figure 11 The shielded cable must have a minimum rating of 300V CP 13 07 2 9060 Cascade Low Voltage Controller Installation Ransburg DJOUAS V LOA HOLIMS MOTANIT NOD QAZ a 1 7142 7141 lt z ROS NS z lt v 100 NY T7 4144015 28 XIANISSY 24 H3LSYW Wada NIHIN gt i ATSNASSY 3072592 AH JANIGVD OL 4000 ON 0 34 WHLNAN NMOMA SNOLLOANNOO 4 xr ic CO ONY HLM INN O 181 OL Controller Schemati Figure 11 18 CP 13 07 2 9060 Cascade Low Voltage Controller Installation and 105 C and its conductors should be 0 8mm 18 AWG minimum Secure the cable to the interlock connector as de scribed in I O Connections the Installation section of this manual so that the shield of the cable is connected to the chassis of the enclosure 5 Replace the top cover secure the screws replace the fuses and reconnect the AC source NOTE gt Some codes may require the interlock wiring to be run in conduit In this case shielded cable is not necessary but the conductors used should still meet the rat ing specified above NOTE gt
20. WARRAN TIES SPARE PARTS One hundred and eighty 180 days from date of purchase except for rebuilt parts any part number ending in for which the warranty period is ninety 90 days EQUIPMENT When purchased as a complete unit i e guns power supplies control units etc is one 1 year from date of purchase WRAPPING THE APPLICATOR ASSO CIATED VALVES AND TUBING AND SUPPORTING HARDWARE IN PLASTIC SHRINK WRAP OR ANY OTHER APPROVED COVERING WILL VOID THIS WARRANTY RANSBURG S ONLY OBLIGATION UND ER THIS WARRANTY IS TO REPLACE PARTS THAT HAVE FAILED BECAUSE OF FAULTY WORKMANSHIP OR MAT ERIALS THERE ARE NO IMPLIED WAR RANTIES NOR WARRANTIES OF EITHER MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE RANSBURG ASSUMES NO LIABILITY FOR INJURY DAMAGE TO PROPERTY FOR CONSEQUENTIAL DAMAGES FOR LOSS OF GOODWILL OR PRODUCTION OR INCOME WHICH RESULT FROM USE OR MISUSE OF THE EQUIPMENT BY PURCHASER OR OTHERS EXCLUSIONS If in Ransburg s opinion the warranty item question or other items damaged by this part was improperly installed operated or maintained Ransburg will assume responsibility for repair or replacement of the item or items The purchaser therefore will assume all responsibility for any cost of repair or replacement and service related costs if applicable CP 13 07 2 Ransburg Ransburg 9060 Cascade Low Voltage Controller Warranty Policies Manufacturing
21. able 76298 The low voltage cable connects the 9060 controller to the external cascade Standard I O Connector The standard I O connector is located just left of the high voltage cable connector This connect or is provided as the entry point for a shielded multi conductor cable used for remote signals and includes the required cable grom met hardware to keep the cable in place with minimal strain This connector is NOT used for Ransburg handgun units Interlock I O Connector The interlock I O connector is located just to the right of the AC inlet receptacle This connector is provided as the entry point for interlock signal wiring for the booth fan conveyor and solvent supply The connector includes the required cable grommet hardware to keep wiring in place with minimal strain For more information on the interlock connections please see the Installation section of the service manual Ground Lug Connection The ground lug connection is located below the standard I O and has a ground logo sticker to the right of it This lug is provided as an exter nal ground connection point used to ground the 9060 to an earth ground via a ground cable This ground lug connection can also be used as the ground point for the high voltage cable ground AIR FLOW CONNECTORS REMOTE LOW VOLTAGE 5 Figure 4 9060 Connection Interface Air Flow Switch Connection The air flow switch connection is installed to p
22. e Operation section and the output current exceeds the overload current value This can be caused by excessive overspray on the ap plicator or paint formulation that is too conduc tive Clean the applicator check the paint for mulation or move overload jumper JP17 to the open position OVERLOAD FAULT ILLUMINATES FAULT INDICATOR AND DISPLAYS OL Figure 25 Overload Fault Display Current Limit Fault CL This fault occurs if the output current exceeds the maximum current by 20A This fault can be caused by excessive overspray on the ap plicator or a paint formulation that is too con ductive It may also be caused by a failed handgun barrel or faulty pc board Clean the applicator check the paint formulation and re test See Fault Troubleshooting Section for more information CURRENT LIMIT FAULT ILLUMINATES FAULT INDICATOR AND DISPLAYS CL Figure 26 Current Limit Fault Display CP 13 07 2 Ransburg Voltage Cable Fault UC This fault will occur if the microprocessor de tects a loss of the voltage feedback signal This may indicate a failed pc board See Fault Troubleshooting Section for more information VOLTAGE CABLE FAULT ILLUMINATES FAULT INDICATOR AND DISPLAYS UC Figure 27 Voltage Cable Fault Display Over Voltage Fault OU This fault will occur if the microprocessor de tects the unit is trying to output voltage above the required for t
23. ed AC installation however if na tional and local codes permit the AC power may be supplied via the factory supplied line cord If conduit is utilized the Controller AC input wiring may be routed through an optional explosion proof switch mounted on or near the spray booth where it will be convenient to the operator For installations where it is required to run the AC input wiring in conduit perform the follow ing 1 Ensure the AC line cord is unplugged and remove the AC inlet receptacle wiring from 1TB N 1TB L1 and 1TB EARTH GROUND See Figures 8 and 9 2 Remove the mounting hardware from the AC inlet receptacle and remove it from the side of Controller 3 Install the Conduit Adapter Plate supplied in the hole where the AC inlet receptacle was removed see Figure 10 4 Install the AC input wiring 0 8mm 18AWG minimum through the Conduit Adapter Plate using conduit and wire to 1 as follows Hot Line to 1TB L1 Neutral Common to 1TB N Ground to 1TB EARTH GROUND CP 13 07 2 9060 Cascade Low Voltage Controller Installation 1 Back of Cabinet Figure 8 Location of TB1 in Controller USER SUPPLIED _ CONT
24. el assembly send low voltage controller in for repair 28 9060 Cascade Low Voltage Controller Maintenance Ransburg Voltage Cable Fault UC 29 Boot Fault bF The Voltage Feedback Fault indi cates the cascade drive signal is not present It typically occurs when high voltage is triggered The Boot Fault indicates that an active trigger signal was detected during the start up sequence Replace the barrel assembly and re test Replace the main pc board and re test Turn off the voltage controller Ensure that the gun trigger is not pressed so the remote trigger input signal is not ac tive Turn on the voltage controller to verify that a trigger signal is not present and that the unit enters the ready state Send the voltage controller in for repair or contact technical support CP 13 07 2 Ransburg 9060 Cascade Low Voltage Controller Maintenance NOTES CP 13 07 2 30 9060 Cascade Low Voltage Controller Parts Identification Ransburg PARTS IDENTIFICATION 9060 CASCASDE LOW VOLTAGE CONTROLLER MODEL IDENTIFICATION When ordering use 80131 A1B as indicated by Table A and B Three digits must follow the basic part number for example 80131 Basic Part Number Plug Selection TABLE B Model Selection TABLE A Model number and serial number of the voltage controller is located on the left outside face of the main enclosure Table A Model Selection
25. f their Output voltage It can be wired to either an AC or DC signal It is most commonly connected to the 24 VDC power provided at 2TB 1 This allows the relays to output 24 VDC signals without the use of any outside power sources 9060 Cascade Low Voltage Controller Introduction 12 9060 Cascade Low Voltage Controller Installation 13 INSTALLATION GENERAL INFORMATION The following section contains general infor mation on the installation of the 9060 Cascade Low Voltage Controller A WARNING gt The 9060 Controller MUST be located outside of the hazardous area gt The User MUST read and be familiar with the Safety section of this manual gt This manual MUST be read and thor oughly understood by ALL personnel who operate clean or maintain this equipment Special care should be taken to ensure that the warnings and requirements of operating and servicing safely are followed The user should be aware of and adhere to ALL local building and fire codes and ordinances as well as NFPA 33 OSHA and all related country safety codes prior to installing op erating and or servicing this equipment gt Only approved applicators should be used with the 9060 Cascade Low Voltage Controller NOTE gt As each installation is unique this infor mation is intended to provide general in stallation information for the 9060 Control ler Consult your authorized Ransburg distributor for specific directi
26. factory preset voltages are listed in the following table Factory Presets Full kV minus 10 kV NOTE gt The full kV DC value is determined by the gun type configuration for the particu lar applicator that is being used NOT the full KV value of the cascade Setting the Setpoint When the applicator is off the present setpoint can be changed by pressing the 1 2 or 3 buttons on the front panel shown in Figure 22 The setpoint that is currently selected will have the LED light in the upper right corner of the button lit Single Pushes Increment Voltage Down or Up in Single Increments Holding Button Increments Voltage Down or Up in Increments of 5 kV 7 2 HV el Oo O O 1 2 3 POWER OFF Set Point Select Button Figure 22 kV Adjust Setpoint Buttons Adjusting Presets To adjust one of the preset setpoints ensure the applicator is off in local mode and select the desired setpoint by pressing the corresponding setpoint button The setpoint can then be adjusted between 20 kV and full using the CP 13 07 2 and buttons on the front panel of the 9060 Controller shown in Figure 22 Single pushes of the or buttons will increment or dec
27. ff and back on Check Fuses and replace if blown using the replacement fuses inside the lid of the unit FAULT TROUBLESHOOTING GUIDE WARNING Before troubleshooting gun and control unit problems flush the gun with solvent and purge with air Some of the tests will require high voltage to be applied to the gun so the gun must be empty of paint and solvent Cable Fault CF The Cable Fault indicates the con 1 Check for a loose connection on the low trol unit does not detect a high voltage cable and tighten if necessary voltage section on the end of the Insure both connectors are secure and re cable The fault typically occurs at test for CF fault a high voltage trigger Replace low voltage cable and re test Send unit in for repair 27 13 07 2 Ransburg Ground Fault GF Over Voltage Fault OU Over Load Fault OL Current Limit Fault CL Feedback Fault FF CP 13 07 2 9060 Cascade Low Voltage Controller Maintenance The Ground Fault is typically caused by a ground connection problem and can create a safety hazard It can occur without high voltage and will not reset The Over Voltage Fault indicates the output voltage exceeds the design specifications It typically occurs during a high voltage trig ger The Over Load Fault indicates the current output has exceeded the overload threshold This fault is only active if jumper 17 is shorted The overload threshold is norma
28. he specific applicator type If this occurs reset the Controller If this fault continues to occur replace the main PC board OVERVOLTAGE FAULT j ILLUMINATES FAULT INDICATO R AND DISPLAYS OU Figure 28 Over Voltage Fault Display CP 13 07 2 9060 Cascade Low Voltage Controller Operation Feedback Fault FF This fault will occur if the microprocessor de tects loss of the current feedback signal If this occurs reset the fault If this fault occurs repeatedly replace the handgun barrel or the oc board FEEDBACK FAULT ILLUMINATES FAULT INDICATOR AND DISPLAYS FF Figure 29 Feedback Fault Display Boot Fault bF This fault will occur during the start up se quence if an active trigger signal is present It is designed to prevent immediate triggering after start up as the unit should be allowed to enter the ready state prior to being triggered This fault also prevents the high voltage from being fired if the microprocessor resets For additional information refer to the Fault Trou bleshooting Section BOOT FAULT ILLUMINATES FAULT INDICATOR AND DISPLAYS Figure 30 Boot Fault Display 26 9060 Cascade Low Voltage Controller Maintenance Ransburg MAINTENANCE TROUBLESHOOTING GUIDE Blank Display No power Check the power connections and verify 2 Blown fuse they are fully connected and power is avail able Power cycle the unit o
29. ights or other safety indicators The physical signal interface is provided via the terminal block 2TB and the connector J3 on the PC Mainboard Trigger Signal The trigger signal input J3 5 for handgun units comes preconfigured as a sinking signal input wired directly to the air flow switch Please refer to the Installation section of this service manual for more information High Voltage On Relay Output Dry Contact The HV on signal 2TB 2 is a relay controlled signal can be configured as either an AC or DC signal using the Relay Common Input as the signal source For information regarding the relay contact voltage ratings please refer to the Relay Output Contacts portion of the Installation section of the manual This relay signal is activated when the High Voltage cascade is turned on Fault Relay Output Dry Contact The Fault signal 2TB 4 is a relay controlled CP 13 07 2 signal can be configured as either an AC or DC signal using the Relay Common Input as the signal source For information regarding the relay contact voltage ratings please refer to the Relay Output Contacts portion of the Installation section of the manual This relay signal is activated when a Fault Condition or Overload Condition has faulted the 9060 Controller Relay Common Input The relay common input 2TB 3 is a shared connection between the Fault and HV on relay outputs This is the source o
30. ion Certain material may be harmful if inhaled or if there is contact with the skin SAFEGUARDS Tells how to avoid the hazard The power supply optional remote control cabinet and all other electrical equipment must be located outside Class or II Division 1 and 2 hazardous areas Refer to NFPA 33 or EN 50176 Turn the power supply OFF before working on the equipment Test only in areas free of flammable or com bustible material Testing may require high voltage to be on but only as instructed Production should never be done with the safety circuits disabled Before turning the high voltage on make sure no objects are within the sparking distance Follow the requirements of the Material Safe ty Data Sheet supplied by coating material manufacturer Adequate exhaust must be provided to keep the air free of accumulations of toxic materi als Use a mask or respirator whenever there is a chance of inhaling sprayed materials The mask must be compatible with the material being sprayed and its concentration Equip ment must be as prescribed by an industrial hygienist or safety expert and be NIOSH ap proved 9060 Cascade Low Voltage Controller Safety AREA Tells where hazards may occur Spray Area High Voltage Equipment HAZARD Tells what the hazard is There is a high voltage device that can induce an electrical charge grounded objects which is capable of igniting coat
31. is made e Solvent Interlock When solvent supply to the applicator is off a contact closure is made Ransburg WARNING gt Failure to connect interlocks could re sult in a fire or explosion A WARNING gt ALWAYS ensure that high voltage is OFF before flushing the spray applicator with solvent NEVER flush the spray ap plicator with high voltage ON as this is a severe fire hazard and risk to personnel safety It is recommended that the high voltage control be interlocked with the sol vent flush signal so that high voltage 15 automatically locked out whenever flush ing occurs Consult your authorized Ransburg representative for information on interlocking the high voltage OFF sig nal with the solvent flush signal As outlined NFPA 33 OSHA and EN 50176 the AC power line must be series interlocked with both the exhaust fan and conveyor To install the Controller interlocks perform the following 1 Turn the 9060 Controller off disconnect it from its AC source and remove the fuses A WARNING gt ALWAYS double check that the Con troller is unplugged from its AC outlet before working with any internal wiring 3 Using a small blade screwdriver remove the factory installed test jumper from 1TB L2 to 1TB L3 4 Using a shielded cable for the interlock wiring Supplied by user route through the interlock connector on the side of the 9060 Controller and terminate 1TB L2 and 1
32. lly set at 10 uA below the maximum output of the applicator The Current Limit Fault indicates the current output of the gun has exceeded the maximum allowable output current It typically occurs with the high voltage on The Feedback Fault indicates there is no current feedback or it is incorrect It typically occurs with the high voltage on Check for loose connection on the low volt age cable and tighten if necessary Insure both connectors are secure and re test for GF fault Turn off control unit power Measure re sistance from ground to handgun air inlet fitting if greater than 5 ohms replace low voltage cable and re iest Send unit in for repair Check connections using two finger pull test to ensure they are connected Replace the main pc board send high voltage control unit in for repair This may indicate the paint conductivity is too high resistance too low or the outside of the applicator is contaminated with paint Test paint for proper conductivity or clean applicator with non polar solvent Ensure dump lines are clean This may indicate the paint conductivity is too high resistance too low or the outside of the applicator is contaminated with paint Test paint for proper conductivity or clean applicator with non polar solvent Ensure dump lines are clean Replace applicator and re test If problem still exists replace main pc board send applicator in for repair Replace handgun barr
33. mory The number of hours the unit s high voltage has been on may be displayed by depressing at the same time the preset 1 and reset buttons See Figure 17 The display will show hours of use for 3 seconds This is the resettable register To reset this register press the reset button while the hours are displayed To view the non resettable register press the preset 2 and reset buttons at the same time This display will show the hours for 3 seconds Display of HV ON Time in Hours A 2 Press and hold Both For Resettable On Time Register Figure 17 Display High Voltage On Both For Non Resettable On Time Register CP 13 07 2 9060 Cascade Low Voltage Controller Operation LOCKOUTS There are lockouts that may be done at the PC board see Figure 18 These lockouts may be used individually or in combination as required If the jumpers are disconnected the original functions are re enabled After changing any jumpers the AC power must cycled for the new setting to take affect NOTE gt Some lockouts are sealed using sealant to prevent them from being modified for safety reasons These lockouts should ONLY be modified by Ransburg Authorized Representatives la a
34. nd Screw Base Plate 2 Unscrew the front four 4 screws and slide the cover off ik A WARNING gt ALWAYS double check that the Con troller is unplugged from its AC outlet before working with any internal wiring 1 3 The flow switch should have the ground green lead connected to the ground screw E on the base plate shown in Figure 13 The a trigger signal blue lead should be connect EET ed to the trigger signal input on the J3 5 inal ter Te Figure 14 PC Mainboard Jumper J5 Location o Das 4 Verify that J5 shown on Figure 14 has the shunt covering pins 1 and 2 5 Replace the top cover secure the screws replace the fuses and reconnect the AC source 13 07 2 20 9060 Cascade Low Voltage Controller Operation OPERATION START UP After all installation procedures are completed operation of the applicator may begin When the ON OFF switch is turned on the kV display will show the applicator configuration the 9060 Controller is configured for and the uA microamp display will show current software revision level as shown in Figure 15 These items are displayed for approximately 10 seconds Gun Type Number Software Rev Level KV u A O HV O T On Off Switch 7
35. ons pertaining to the installation of your equipment Ransburg LOCATION OF THE 9060 Install the Controller in an area outside the hazardous location in accordance with feder al state and local codes The area should protect the Controller from the possibility of environmental intrusion Such as dust or mois ture have ambient temperatures that do not exceed 40 C and be as close to the applicator as possible to minimize the length of the high voltage cable gt DO NOT locate the Controller near adjacent to heat producing equipment such as ovens high wattage lamps etc The Controller may be free standing on any flat surface CP 13 07 2 Ransburg ELECTRICAL NOISE Electrical noise refers to stray electrical signals in the atmosphere at various signal strengths and frequencies that can affect the operation of equipment One of the best ways to prevent this is to shield the equipment and cables within a continuous ground envelope such that any incident noise will be conducted to earth ground before it can affect the circuit conductors For conductors inside the control unit or Con troller the grounded enclosures provide this envelope For the cables that connect the applicator to the control unit or Controller a shielded cable has been used The shield consists of an overall foil shield in combination with an overall braided shield This provides the most effective shielding as the foil covers the
36. oper or inadequate opera tion and maintenance proce dures will cause a fire hazard Protection against inadvertent arcing that is capable of causing fire or explosion is lost if any safety interlocks disabled during operation Frequent Con troller shutdown indicates a problem in the system requiring correction SAFEGUARDS Tells how to avoid the hazard Fire extinguishing equipment must be present in the spray area and tested periodically Spray areas must be kept clean to prevent the accumulation of combustible residues Smoking must never be allowed in the spray area The high voltage supplied to the atomizer must be turned off prior to cleaning flushing or maintenance When using solvents for cleaning Those used for equipment flushing should have flash points equal to or higher than those of the coating material Those solvents used for cleaning must have a flash point at minimum of 5 C 9 F greater than ambient temperature It is the end users respon sibility to ensure this condition is met Spray booth ventilation must be kept at the rates required by NFPA 33 OSHA and local codes In addition ventilation must be maintained during cleaning operations using flammable or combustible solvents Electrostatic arcing must be prevented Test only in areas free of combustible material Testing may require high voltage to be on but only as instructed Non factory replacement parts or unauthor i
37. provides the maximum in applicator transfer efficiency while main taining the maximum safety The 9060 Controller provides the selection and adjustment of set point values is per formed from the controller front panel The trigger of the HV is initiated by the airflow switch built into the controller which senses airflow triggered by a standard handgun SAFETY FEATURES When used with the appropriate applicators and cascades the Ransburg 9060 Cascade Low Voltage Controller provides maximized operational safety The protections include detection of Ground Faults Cable Faults Feedback Signal Faults Overvoltage and Overcurrent The microprocessor circuits provide a controlled output load curve which limits the high voltage output to safe levels while monitoring control and feedback signals for unsafe conditions Maximum operational safety is obtained when the correct applicator settings are used and when safe distances between the applicator and target are ob served and followed The maximum efficiency of the low voltage controller is based on load Ransburg DISPLAYS The front panel displays the high voltage set point as well as a reading of gun current out put The gun current is derived from feed back signals in the low voltage cable be tween the controller and the cascade Ransburg Figure 1 9060 Cascade Low Voltage Controller The 9060 Low Voltage Controller 80131 XXX is available as follows
38. r more infor mation BASIC OPERATIONS The basic operations are general operations that are available Triggering High voltage is actuated by the presence of an active trigger signal This is normally accom plished by pulling the trigger of the handgun to start the flow of air through the applicator When the applicator is triggered an air flow switch is activated and the trigger signal 15 issued to the 9060 unit The kV setpoint is displayed on the kV display the actual current draw the uA display and the high voltage light illuminates Under the A display is a bar graph meter that illuminates according to the actual current draw shown in Figure 16 The green and yellow regions of the bar graphs meter indicate output current is in the optimum range for maximum transfer CP 13 07 2 Ransburg efficiency The red region of the bar graph indicates high output current causing decreased transfer efficiency If high output check mainte nance of applicator and external equipment of the power supply uA BAR GRAPH METER Figure 16 Bar Graph Meter Display Measuring High Voltage On Time The 9060 Cascade Low Voltage Controller records the amount of time the high voltage is triggered on up to 99 999 hours This value is display on the kV and uA displays of the unit There two registers that retain this infor mation one that may be reset the other that is permanently retained in me
39. rement the currently selected preset in units of 1 When the or buttons are held in for longer than a 1 2 second the kV display will begin incrementing or decrementing in units of five 5 Resetting Faults During operation various faults can occur based upon the operating conditions or if any problems with the 9060 unit arise If a fault occurs to reset a fault the trigger of the gun MUST be off and then press the Reset Button This will clear the fault status and put the unit back into operation unless a fault condition 15 still present Please refer to the Fault Descrip tion portion of the Operation Section of this Service manual for more information on a specific fault and how to correct tt NOTE gt There is a 5 second fault reset delay timer that inhibits the triggering of high voltage immediately after a fault reset FAULT DESCRIPTIONS For in depth troubleshooting information on the 9060 please refer to the Fault Troubleshoot ing portion of the Maintenance Section of this service manual If a fault occurs the Fault Indicator on the front of the Controller will light and a fault code will be displayed on the microamp display Faults can be reset by pressing the Reset button on the front of the Controller or by using the remote I O reset signal NOTE gt fault code not listed that appear the screen are a likely indication of a PC board failure due to possible arc damage 9060
40. rovide a pneumatic trigger signal for handguns indicating that the trigger has been actuated This signal is used to turn on the High Voltage output Both threaded connectors of the air flow switch will come covered with red protect ed caps AC Inlet Receptacle The AC inlet receptacle is a standard IEC C14 Appliance Inlet connector with a maximum rating of 250 VAC It can handle both 110VAC and 240 VAC inputs at 50 or 60 Hz The unit is shipped with the appropriate rated AC cord for the particular installation CP 13 07 2 Ransburg FUSES Fuses There are two 2 time delay fuses 250V 1A 5mm x 20mm installed in fuse holders on the connection interface They are located directly above the ground lug connection They are present to provide a measure of safety against power surges through the AC input The top fuse holder is connected in series between the HOT line L input connection and the Interlock AC line connection terminal 1TB L2 The bottom fuse holder is connected in series between the neutral AC input connection and the neutral input connection of the AC line power filter SIGNAL INTERFACE The 9060 controller local mode is used for handguns or very simple automatic gun systems Handguns require only one signal input for operation the trigger signal Though not necessary for operation there are also two 2 output relay contact signals HV on and Fault that can be useful for triggering remote devices such as l
41. s manual with your system instal lation drawings and appropriate Ransburg equipment manuals to reconcile such differ ences Careful study and continued use of this manual will provide a better understanding of the equipment and process resulting in more effi cient operation longer trouble free service and faster easier troubleshooting If you do not have the manuals and safety literature for your Ransburg system contact your local Ransburg representative or Ransburg Ransburg A WARNING gt The user MUST read and be familiar with the Safety Section in this manual and the Ransburg safety literature therein identified gt This manual MUST be read and thor oughly understood by ALL personnel who operate clean or maintain this equipment Special care should be taken to ensure that the WARNINGS and safety requirements for operating and servicing the equipment are followed The user should be aware of and adhere to ALL local building and fire codes and ordinances as well as NFPA 33 SAFETY STANDARD prior to installing operating and or servicing this equipment A WARNING The hazards shown on the following page may occur during the normal use of this equipment Please read the hazard chart beginning on page 2 CP 13 07 2 Ransburg AREA Tells where hazards may occur Spray Area CP 13 07 2 9060 Cascade Low Voltage Controller Safety HAZARD Tells what the hazard is Fire Hazard Impr
42. stem will enter the general diagnostic mode 9060 Cascade Low Voltage Controller Introduction 10 9060 Cascade Low Voltage Controller Introduction 11 Left Right Buttons The left right buttons in the normal operat ing mode are used to modify decrease and increase respectively the currently selected preset value If the button is pressed and released the preset value is changed by 1 kV at a time If the button is held for over a 1 2 second the value will begin changing by 5 kV increments Reset Button The reset button is used in the normal operating mode to clear fault or overload conditions This will NOT prevent any other active fault condi tions from triggering a new fault HV Control Button This button shown in the center of Figure 3 is not functional for handgun units CONNECTION INTERFACE The 9060 Controller connection interface shown in Figure 4 provides all of the required connec tions for setting up a local controlled painting system This connection interface consists of one 1 low voltage cable connector one 1 standard connector one 1 interlock I O connector one 1 ground lug connection one 1 air flow switch connection two 2 fuses and one 1 AC inlet receptacle CONNECTORS Low Voltage Cable Connector The low voltage cable connector is located on the far lower right of the connection interface This connector is designed for use with stand ard low voltage c
43. t LED indicators are located directly above each of the Preset Buttons When a preset button is pushed to select the desired preset in READY mode the preset LED indicator directly above the button pressed will light up Only one 1 preset light should be lit at any one time BUTTONS The seven buttons on the operator interface are used to select the KV presets reset overloads and faults access other modes and to navigate as well as modify information that is displayed on the two seven segment display screens UA and kV The following lists the standard operating mode behavior for each button Preset 1 Button The Preset 1 Button to the left below the kV display is used by itself to select Voltage Preset 1 in the normal operating mode If pressed with the reset button at the same time the screen will display the resettable High Voltage ON operating hours for 3 seconds on the display screens Preset 2 Button The Preset 2 Button in the center below the kV display is used by itself to select Voltage Preset 2 in the normal operating mode If pressed with the reset button at the same time the screen will display the non resettable High Voltage ON operating hours for 3 seconds on the display screens Preset 3 Button The Preset 3 Button to the right below the kV display is used by itself to select Voltage Preset 3 in the normal operating mode If pressed with the reset button at the same time the sy
44. ystem which requires correc tion Always turn the control panel off prior to flush ing cleaning or working on spray system equip ment Ensure that the control panel is interlocked with the ventilation system and conveyor in accord ance with NFPA 33 EN 50176 Have fire extinguishing equipment readily availa ble and tested periodically Personnel must be given training in accordance with the requirements of NFPA 33 EN 60079 0 Instructions and safety precautions must be read and understood prior to using this equip ment Comply with appropriate local state and nation al codes governing ventilation fire protection operation maintenance and housekeeping Ref erence OSHA NFPA 33 EN Norms and your insurance company requirements CP 13 07 2 Ransburg AREA Tells where hazards may occur Electrical Equipment Toxic Substances CP 13 07 2 9060 Cascade Low Voltage Controller Safety HAZARD Tells what the hazard is High voltage equipment is utilized Arcing in areas of flammable or combustible materials may occur Personnel are exposed to high voltage during operation and maintenance Protection against inadvertent arc ing that may cause a fire or explo sion is lost if safety circuits are dis abled during operation Frequent power supply shut down indicates a problem in the system which requires correction An electrical arc can ignite coating materials and cause a fire or explo s
45. zed equipment modifications may cause fire or injury If used the key switch bypass is intended for use only during setup operations Production should never be done with safety interlocks disa bled Never use equipment intended for use in water borne installations to spray solvent based mate rials The paint process and equipment should be set and operated in accordance with NFPA 33 NEC and European Health and Safety Norms 9060 Cascade Low Voltage Controller Safety Ransburg AREA Tells where hazards may occur Spray Area General Use and Maintenance HAZARD Tells what the hazard is Fire and or explosion Improper operation or mainte nance may create a hazard Personnel must properly trained in the use of this equip ment SAFEGUARDS Tells how to avoid the hazard Electrostatic arcing MUST be prevented The 78789 control panel LEPS5001 power sup ply and all other electrical equipment must be located outside Class or Il Division 1 or 2 haz ardous areas in accordance with NFPA 33 Test only in areas free of flammable or combus tible materials The current overload sensitivity MUST be set as described in the OVERLOAD ADJUSTMENT Procedures section of this manual Protection against inadvertent arcing that is capable of causing fire or explosion is lost if the cur rent overload sensitivity is not properly set Frequent power supply shutdown indicates a problem in the s
Download Pdf Manuals
Related Search
Related Contents
Schwinn 170 Assembly & Owner's Manual Lève-vitres électrique T-4070 ファームウェア更新手順 電子音目覚まし時計取扱説明書 保 証 書 Pelco SD4N-B0-X User's Manual Acer TravelMate 6410 Owner's Manual Neutralisants d`0deurs advertencia - Chamberlain Copyright © All rights reserved.
Failed to retrieve file