1. 8 1 PROP SET BAND POINT e PB2 SP2 Power Supply terminal board pPEMIN2N F 40 OOOO00 0 Control signal SS SS 123458 78810 terminal boards _ II ________ 734 6 se Rr PE When Control signal Terminal boards Contact 9 10 is open the control is MEE ue L1 enabled by Trimmer P2 P3 when this contact is closed the control is pu dr IN closed Fuso enabled by Trimmer P6 P7 The following control devices are found on the control section e Trimmers indicated as Pn e Jumpers indicated as Jn e Led indicated as DIn The GREEN DL1 Led signals delivery of voltage to the load in progress The YELLOW 012 Led signals Set point 2 enabling The following connection devices are found on the power section e Power terminal panel Power supply terminal panel for the connection of the power supply and the load e g fans Control terminal panel for the connection of control signals in other words the two probes transducers or two remote control auxiliary voltage regulators Precautions e During re assembly always make sure that the cover of the external protection is always tightly closed Never modify or damage the equipment s adhesive identification labels Never force the rotation of the trimmers beyond the mechanical stroke foreseen Modify only the positions of the trimmers indicated for ad
2. RAN RAL 1 1 25 07 08 IT EN 23 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS GUIDE TO THE SIZING OF THE EXPANSION TANK The project elements to consider when selecting the dimensions of the buffer tank for a system are C The quantity of water in the system in litres e the expansion coefficient of the water calculated as the maximum temperature difference between when the system is off and when the system is running the values are given in the table below pi The absolute initial pressure equivalent to the pre charge pressure of the buffer tank normally 2 5 bar i e 1 5 bar r p The absolute tolerated pressure which must be less than the pressure at which the safety valve is set taking account of any difference in height between the valve and the tank The total capacity of the buffer tank is expressed as Cxe V using the expansion coefficient values the following table WATER EXPANSION COEFFICIENT LLL It is also possible to calculate the average value of e at 10 C between the initial water temperature generally assumed to be 10 C and the operating temperature 20 9979 00017 using e 75x10 x T 988 1 0 0116 OF WATER CIRCUIT The table below shows the capacity in litres of the water circuit RAL RAL RAL RAN RAL RAL RAL model 0360 0510 0700 075
3. JUNIFLAIR RADIATORI REMOTI DRY COOLERS Modelli Model RAN 750 1000 1500 RAL 360 510 700 1000 1500 2300 3600 5700 MANUALE DI ISTRUZIONI INSTRUCTION MANUAL UNIFLAIR 2008 1 MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS Versione Release 1 1 Data Date Luglio 2008 July 2008 Alcune caratteristiche delle unit in versione speciale potrebbero discostarsi da quelle descritte nel presente manuale UNIFLAIR SpA persegue una politica di costante innovazione tecnologica riservandosi il diritto di variare senza preavviso le caratteristiche qui riportate The following general characteristics are relevant to standard units designed according to the available options found on the units price list UNIFLAIR SpA policy is one of continuous technological innovation The Company therefore reserves the right to amend any data herein without prior notice Smaltimento il prodotto composto da parti in metallo e da parti in plastica In riferimento alla Direttiva 2002 96 CE del Parlamento Europeo e del Consiglio del 27 gennaio 2003 e alle relative normative nazionali di attuazione Vi informiamo che Sussiste l obbligo di non smaltire i RAEE come rifiuti urbani e di effettuare per detti rifiuti una raccolta separata Per lo smaltimento vanno utilizzati i sistemi di raccolta pubblici o privati previst
4. RAL 5700 RAN750 7 300 310 sso 312 4X0 RAN 1000 4ooo 310 490 12 800 RAN 1500 soo 16 890 319 8600 RAN RAL Rev 1 1 25 07 08 IT EN 1 6 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS MANUTENZIONE Controllare frequentemente lo stato di pulizia del radiatore rimuovere dallo scambiatore di calore alettato tutti i corpi estranei foglie semi polvere con un getto d aria compressa Le alette dello scambiatore di calore sono in lamiera di alluminio di piccolo spessore e possono tagliare in caso di contatto involontario Verificare che il funzionamento e l assorbimento elettrico di ciascun ventilatore siano regolari e senza rumori anomali Controllare che sonda e regolatore funzionino regolarmente RAN RAL Rev 1 1 25 07 08 IT EN 17 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS SYMBOLS USED M xx LIVE COMPONENTS RISK OF ELECTRIC SHOCK SAFETY INSTRUCTIONS A 0 Read the instruction manual carefully before c
5. The symbols shown on the unit packaging conform to 1507000 standards Their meaning is explained in the table below EE SYMBOL ______________________ SYMBOL ___ ___________ FRAGILE handle with care x THIS SIDE UP shows the x orientation of the unit 44 PROTECT AGAINST MOISTURE TEMPERATURE LIMITS the the packed unit must be stored i unit must not be stored outside a dry place these limits x CENTRE OF GRAVITY shows the NO HOOKS do not use hooks centre of gravity of the packed ito lift the packed unit unit KEEP AWAY FROM HEAT the NOT STACK unit must be kept away from heat Sources i INSTALLATION Position the dry cooler in the open air out of direct sunlight can be installed with horizontal air discharge for best protection from snow or from objects falling from above and easier maintenance in this configuration the dry cooler must be protected from the wind which could interfere with the operation of the fan with vertical air discharge this configuration is recommended for installation in windy locations or where a horizontal air flow would be easily obstructed available with_optional leg kit Leg kit includes assembly instructions Position the dry cooler on a solid level surface Fix the dry cooler down using the appropriate bolt holes in the base horizontal air discharge or in the bottoms of the legs vertical air
6. C pos m ai 20 C pos M Con le sonde NTC la banda di lavoro NON deve essere troppo stretta soprattutto nel caso di rilevazione indiretta della temperatura es per contatto in un sistema che varia repentinamente il valore da rilevare Regolazione del punto di lavoro trimmer P3 FASE 2 P3 Permette la regolazione del Set point ovvero del punto di Set point C lavoro SP Agendo sul trimmer P3 possibile regolare il punto di inizio della regolazione automatica P2 P3 5 In figura sono riportati i valori e le posizioni dei trimmer nelle T T SET POINT 1 diverse configurazioni 3 C 40 C 6 C 35 C 11 C 30 C Soft Start Trimmer P1 P1 Regola la rapidit con cui varia la velocit del ventilatore slow start e slow stop soft start rendendo il sistema lento o veloce in relazione alle variazioni del segnale di comando automatico 2 La posizione M trimmer completamente girato in senso orario rallenta la velocit di 35 modulazione della tensione Nella posizione m minimo la variazione di velocit quasi istantanea sistema pronto regolatore viene fornito con un tempo di slow start stop minimo pari a circa 2 secondi In fase di installazione per evitare eventuali pendolazioni che potrebbero essere favorite da una taratura di P1 non adatta verificare il funzionamento del regolatore rgf in regolazione automatica ATTENZIONE Non
7. DIUI RAL RAL RAL RAN RA RA RAL RAL RAL Modello 0360 0510 0700 0750 1000 1500 2300 3600 5700 RAN RAL Rev 1 1 25 07 08 IT EN JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS TRASPORTO E MOVIMENTAZIONE radiatore ha lasciato la fabbrica in perfetto stato al momento della consegna controllarne l integrit e notificare subito per iscritto al trasportatore ogni danno che possa essere attribuito ad un trasporto rude Durante il trasporto e il tiro in sito o capovolgere il radiatore prima di rimuovere l imballo trasportare il radiatore nel punto pi vicino al luogo d installazione per mezzo di un transpallet oppure di un carrello trasportatore stabile assicurando l unita per evitarne il ribaltamento e rimuovere l imballo prestando attenzione a non danneggiare l unit La simbologia applicata sull imballo conforme alla norma 1507000 il significato dei segni grafici riportato in tabella JA TR RR RR SR GR RR S 4 Gg STR NINNA NANNA RS y y RS S y gg S S 4 GT E S g y GG S S gy SET RS gu SER S S GUGSE T S G Gg GGG GGG GO SR KG AR RT R SR SEGNO GRAFICO SIGNIFICATO _SEGNOGRAFICO SIGNIFICATO FRAGILE manipolare ALTO indica posizione precauzione corretta dell imballaggio di spedizione L UMIDIT indica che u u LIMITI DI TEMPERATURA l imb
8. EN attacchi tipo gas 1 4 maschio 0360 0510 1 1 2 maschio 0700 0750 2 maschio 1000 2300 3 maschio 3600 5700 N N e w ae lt _ i De L k Fig 4 Fig 5 8 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS COLLEGAMENTI IDRAULICI Il radiatore caricato in fabbrica con azoto chiuso con tappi modelli 2300 5700 PRIMA DI RIMUOVERE TAPPI SUGLI ATTACCHI SCARICARE L AZOTO PER MEZZO DELLA VALVOLA A SPILLO SUL COLLETTORE D ENTRATA i di pre pcm t Co qr B LE WN gt 1 2 3 4 1 Svitare il tappo E avvitato sull attacco 2 Rimuovere la guarnizione nera in gomma D questa guarnizione utilizzata solamente per garantire tenuta del circuito precaricato con azoto 3 Inserire una guarnizione B sull attacco 4 Avvitare il giunto femmina C sull attacco A Fig 6 Rispettare il corretto collegamento del radiatore evitando di invertire l ingresso con l uscita t vedi fig 7 OK gt 2 I Fig 7 a Fig 7 b UTILIZZO DI GLICOLE ETILENICO In caso di utilizzo di miscele anticongelanti alcuni dei dati tecnici della macchina riportati nelle tabelle resa portata d acqua perdite di carico subiscono alcune variazioni Di seguito sono indicati fattori di correzione per calcolare
9. deve essere modificata in nessun caso la posizione dei trimmer contrassegnati con un punto rosso di vernice taratura di fabbrica RAN RAL Rev 1 1 25 07 08 IT EN 14 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS Scheda Set Point 2 applicazioni in cui indispensabile l utilizzo di un secondo Punto di lavoro es Giorno Notte o Estate Inverno possibile utilizzare la scheda di espansione PG 7 Sulla scheda sono presenti n M e Trimmer P6 Per la regolazione della Banda Proporzionale del Set point 2 27 w e Trimmer P7 Per la regolazione Set point 2 Jumper J21 Per il funzionamento della regolazione in MODO REVERSE 3 C 20 C Jumper J22 Per il funzionamento della regolazione in MODO DIRECT m m m Jumper J23 Selezione di posizione non effettuabile Taratura di fabbrica v v Led DL2 Led GIALLO di segnalazione attivazione del Set point 2 6 C 16 Le modalit di taratura dei Trimmer P6 e P7 sono le stesse descritte alla fase 2 per P2 e P3 m M pm M In figura sono riportati i valori e le posizioni dei trimmer nelle diverse configurazioni CJ 11 C 12 C Banda Proporzionale 2 Set Point 2 T TOCCARE T P6 P7 OOOO UP Selezione Modo Reverse H J21 Selezione Modo Direct LI J22 L2 CN DOWN Per attivare il Set point 2 chiudere con un contatto liber
10. discharge RAN RAL Rev 1 1 25 07 08 IT EN 21 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS WORKING SPACE Indicated in fig 3 minimum recommended distance to be left clear for a correct unit function and to allow access to the unit for maintenance Fig 3 a HORIZONTAL AIR FLOW Fig 3 b VERTICAL AIR FLOW sim gt gt V gt DS LLL INSTALL THE DRY COOLER IN A POSITION WHICH IS INACCESSIBLE TO UNAUTHORISED PERSONNEL The heat exchanger fins are made from aluminium sheet which is only 0 1 mm thick and could cause cuts in the event of forceful accidental contact N B the fan characteristic does not allow any ducting of the air flow SIZE OF HYDRAULIC CONNECTIONS The dry cooler has male GAS connections Female valves must be connected to the male connections inlet outlet placing a seal between connections NB the diameter of the hydraulic line that connects the unit to its remote dry cooler De must be chosen according to the length of the hydraulic line itself RAN RAL Rev 1 1 25 07 08 IT EN GAS connections 14 male 0360 0510 1 1 2 male 0700 0750 2 male 1000 2300 3 male 3600 5700 Fig 4 N N we CL 2X 7 i I De L 8 i c Fig 5 22 32 JUNIFLAIR MANUALE DI ISTR
11. i dati alle diverse percentuali di glicole etilenico Percentuali di glicole etilenico variazione della portata d acqua 96 296 45 46 596 9 11 5 14 variazione delle perdite di carico 96 7 96 14 24 33 96 45 96 57 96 Limiti operativi 10 15 20 Temperatura di congelamento 4 7 C 10 C Attenzione Nel caso di utilizzo di acqua senza glicol occorre essere sicuri che la temperatura ambiente sia sempre superiore a 0 C Per evitare il pericolo di gelo durante il periodo di fermo vuotare il radiatore insufflando aria a pi riprese e introdurre glicol RAN RAL Rev 1 1 25 07 08 IT EN 9 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS DIMENSIONAMENTO DEL VASO DI ESPANSIONE Gli elementi di progetto nella scelta del vaso di espansione per un impianto sono Cla quantita d acqua contenuta nell impianto espressa in litri e ilcoefficiente di espansione dell acqua valutato alla massima differenza di temperatura tra l acqua ad impianto spento e l acqua alle condizioni di esercizio i valori sono indicati in tabella p la pressione assoluta iniziale che equivale alla pressione di precarica del vaso di espansione tipicamente 2 5 bar cio 1 5 bar r la pressione assoluta finale tollerata che dev essere inferiore alla pressione alla quale stata calibrata la valvola di sicurezza tenendo conto dell eventuale dislivello esiste
12. regolazione ovvero e Trimmers indicati con Pn e Ponticelli indicati con Jn e Led indicati con Dln DL1 Led VERDE di segnalazione erogazione di tensione al carico in corso DL2 Led GIALLO di segnalazione attivazione del Set point 2 Nella parte di potenza sono presenti organi di collegamento ovvero Morsettiera di potenza morsettiera Alimentazione per il collegamento dell alimentazione e del carico es ventilatori e Morseitiera di comando per il collegamento dei segnali di comando ovvero di due sonde trasduttori o di due regolatori ausiliari di comando remoto Precauzioni e rimontare e verificare sempre la perfetta chiusura del coperchio di protezione esterno non alterare o danneggiare gli adesivi di identificazione delle apparecchiature non forzare mai la rotazione dei trimmer oltre la corsa meccanica prevista modificare unicamente la posizione dei trimmer indicati per la regolazione non modificare in nessun caso i trimmer con il punto rosso di vernice 12 32 RAN RAL Rev 1 1 25 07 08 IT EN JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS Taratura Fabbrica Factory Calibration P3 PS P6 SOFT PROP SET MAX CUT OFF PROP SET START BAND POINT OUT BAND POINT PB1 oP 1 PB2 SP2 29sec 6 C 35 C 230VAC 90 6 C 12 C NB le tarature sopra descritte sono gia state verificate in fase di collaudo Prima di procedere alla modifica
13. 0 1000 1500 2300 3600 5700 61 136 121 142 191 305 536 91 0 RAN RAL Rev 1 1 25 07 08 IT EN 24 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS ELECTRICAL CONNECTIONS A correct electrical connection carried out accurately and in compliance with local regulations is extremely important in order to prevent accidents and to ensure long trouble free operation Before working on the electrical parts of the unit make sure that the power is off and that the isolator switch on the electrical panel is in the O position POWERISUPPLY CABLES PROTECTION see wiring diagram SECA attached The electric power supply must not be supplied by a connected unit but by the nearest electric panel Check that the voltage and frequency of the power supply correspond to the data shown on the nameplate of the dry cooler Connect the power supply cable to the isolator introducing the cable into the switch box through an IP 55 rated cable gland and screw the terminals down tightly The table indicates main electric power supply data used for power supply cable dimensioning IMPORTANT Install an electrical protection circuit breaker of appropriate rating upstream the power supply all safety legislations regarding the installation site must be respected START UP Switch on the power supply to the dry cooler and close the isolator switch to positio
14. 02160760282 di PD R E A 212586 del 21 04 1988 R I N 02160760282 M PD004505 06MM095 200MO1 10
15. 07 08 IT EN 27 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS Proportional band regulation trimmer P2 PHASE 2 P2 This trimmer is used to set the proportional band or in other words the point in Prop Band C which the automatic control is at the Maximum value 100 The work range indicates the increment to the incoming control signal C used by the Rgf series to pilot the fans from the minimum voltage P5 to the maximum voltage P4 The work range runs from 2 C position m to 20 C position M With NTC probes the proportional band MUST NOT be overly restricted especially in the event of indirect temperature measurement e g by a contact in a system that repeatedly varies the value being measured Set Point regulation trimmer P3 PHASE 2 P3 This permits the adjustment of the Set point or in other Set point C words the work point SPI The P3 trimmer is used to starting point for automatic control The figure shows the values and the P2 P3 SET POINT 1 positions of the trimmers in the various configurations 3 C 40 C 6 C 35 C 11 C 30 C Soft start regulation trimmer P1 P1 This trimmer adjusts the rapidity with which fan speed is varied slow start and slow soft start stop thereby making the system slow or fast depending on the variations in the automatic 9 control signal Position trimmer rotated compl
16. Control Devices Adjustment 25 Technical data 30 Maintenance 31 RAN RAL Rev 1 1 25 07 08 IT EN 3 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS SIMBOLOGIA IPTE pbs uous ISS TORTORICI CAICOS CAFE PICCO RI TETTE RE ETE tease nines COMPONENTI IN TENSIONE PERICOLO ELETTRICO NORME DI SICUREZZA A 0 Prima di qualsiasi intervento leggere attentamente il libretto d istruzioni radiatore caricato in fabbrica con azoto 2 bar modelli 2300 5700 Prima di rimuovere i tappi sugli attacchi in fase di installazione scaricare l azoto per mezzo della valvola sul collettore radiatore lavora in pressione la manomissione dei raccordi o delle tubazioni pu provocare fuoriuscite di liquido compresso INSTALLARE IL RADIATORE IN POSIZIONE INACCESSIBILE A PERSONE NON AUTORIZZATE le alette dello scambiatore di calore sono in lamiera d alluminio di piccolo spessore e possono tagliare in caso di contatto involontario radiatore in tensione e contiene parti rotanti prima di intervenire su qualsiasi parte elettrica oppure sul ventilatore i aprire il sezionatore portare la manopola in posizione O Tutte le operazioni di servizio o manutenzione dev
17. OLERS GENERAL DESCRIPTION AIR DISCHARGE ARRANGEMENT HORIZONTAL VERTICAL Propeller Fan Holding Brackets Holding Legs Connections Mains Isolator Speed Regulator Identification Plate Inlet temperature sensor G N N B Fan number and layout depend on dry cooler model Fig ref model 2300 5700 RAN RAL Rev 1 1 25 07 08 IT EN 1 9 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS DESCRIPTION AND USE Remote dry cooler with axial fans for outdoor installation fully factory assembled and tested The dry cooler can be installed in a vertical position with horizontal air flow or in a horizontal position with vertical air flow Units can be equipped with either a fan speed regulator control with an ON OFF switch type or a modulating speed control Case self supporting and constructed entirely in aluminium for outdoor installation in demanding operating conditions Fan motor of the axile type electric motor is of the outside rotor type protection grade IP54 CLASS F offering the opportunity for a stepless speed adjustment via a TRIAC voltage controller Safety protection grilles fitted on the fans comply with safety standards Finned Coil with large frontal area for an efficient air distribution constructed of copper tubes mechanically expanded into aluminium fin
18. UZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS HYDRAULIC CONNECTIONS The dry cooler is factory charged with dry nitrogen the connections are sealed with plugs model 2300 5700 BEFORE REMOVING THE PLUGS FROM THE CONNECTIONS DISCHARGE THE NITROGEN BY MEANS OF THE NEEDLE VALVE ON THE INLET MANIFOLD t C qr B LE WN C L 2 3 4 Fig 6 1 Unscrew the cap E on the connection 2 Remove the black rubber seal D this is only used to seal the circuit charged with nitrogen 3 To put a seal B on the connection A 4 Screw the female joint C on to the connection A Take care that the connections are correctly made and in particular do not invert the inlet gt lt and outlet connections fig 7 4 Fig 7 Fig 7 b USE OF ETHYLENE GLYCOL Correction factors are given to calculate data for various glycol percentages Increase of water flow 96 2 96 4 5 6 5 9 11 5 14 Increase in distributed pressure drop 7 96 14 24 33 96 45 96 57 96 Operation Limits Minimum fluid temperature with unit operating 10 15 20 4 7 109 Freezing Caution For water without glycol make sure that the ambient temperature is always higher than 0 C To prevent freezing during arrest drain off the dry cooler by blowing air several times and introduce Glycol
19. allaggio dev essere tenuto indica i limiti di temperatura luogo asciutto i entro i quali l imballaggio x dev essere conservato i manipolato CENTRO DI GRAVITA indica il UTILIZZARE GANCI i centro di gravit dell imballaggio di indica che sono proibiti i ganci spedizione per i sollevamento i dell imballaggio di spedizione _ IL CALORE indica che SOVRAPPORRE gl SIL l imballaggio di spedizione deve imballi ZN essere tenuto distante da fonti di AN calore O 4 4 6 n INSTALLAZIONE Porre il radiatore all aperto evitando l esposizione all insolazione diretta Esso puo essere installato con flusso d aria orizzontale per una migliore protezione dalla neve da oggetti provenienti dall alto e una facile manutenzione con quest assetto il radiatore necessita di protezione dal vento che potrebbe interferire con il funzionamento del ventilatore con flusso d aria verticale quest assetto consigliato per l installazione in zone ventose o laddove il flusso d aria orizzontale sia ostruito ed realizzabile per mezzo del kit gambe opzionale Per l
20. arrying out any work on the equipment The dry cooler is factory precharged with dry nitrogen to 2 bar model 2300 5700 Before removing the plugs from the inlet and outlet connections for installation discharge the nitrogen by means of the valve on the inlet manifold The dry cooler contains gas above atmospheric pressure tampering with connections or pipework can cause leakage of compressed liquid INSTALL THE DRY COOLER IN A POSITION WHICH IS INACCESSIBLE TO UNAUTHORISED PERSONNEL the fins of the heat exchanger are made from thin aluminium sheet and can cause cuts in the event of accidental contact A The dry cooler contains live electrical parts and rotating devices before carrying out any work on the electrics or on the fan isolate the unit turn optional isolator to position All service and maintenance operations which require access to the inside of the unit while it is in operation must be performed by qualified and experienced personnel who are aware of the precautions which must be taken In the event of fire water and other conductive substances must not be used to put out the fire near live electrical components This warning must be displayed on notices in the unit installation location Make sure that the power supply voltage corresponds to the shown the data plate RAN RAL Rev 1 1 25 07 08 IT EN 1 8 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY CO
21. ase 2 for P2 and P3 C 6 The figure shows the values and the positions of the trimmers the various configurations 11 C 12 C Proportional band 2 Set Point 2 Do Not Touch Factory J2 23 selection CN UP Reverse mode h J21 Direct mode gt H J22 DL2 O w DOWN In order to enable Set point 2 close Control Terminal Board Terminals 9 10 with a potential free contact RAN RAL Rev 1 1 25 07 08 IT EN 29 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS pa 0360 roo 1090 1500 29 eoo 50 Power supply V ph Hz 230 1 50 400 3 50 Total nominal power absorption 0 36 0 54 0 54 0 87 1 16 2 04 2 72 6 30 n in ae an mo mo Nominal capacity 16 6 20 9 30 2 36 9 51 3 81 2 127 9 200 5 Nominal airflow m h 5800 6470 9560 11820 16000 31800 41600 54000 Sound pressure level at 10 m free dB A 46 0 46 5 48 0 49 0 50 0 55 0 56 0 60 5 field conditions Power supply V ph Hz 230 1 50 Total nominal power absorption kW 1 28 1 92 2 56 Nominal capacity 34 6 46 0 64 1 Nominal airflow m h 11490 16140 21820 Sound pressure level at 10 m free dB A 56 5 58 5 field conditions Air temp 25 C water inlet temp 40 C water outlet temp 35 C glicol 0 Pressure drop by liquid supply function MODEL Pressure drop liquid supply Pressure drop liquid s
22. contattare il servizio tecnico UNIFLAIR La regolazione dei parametri di lavoro essere suddivisa in due fasi 1 definizione dei limiti di lavoro del regolatore in questa fase vengono definiti valori di e 5 2 definizione del campo di lavoro del regolatore in questa fase vengono definiti i valori di P2 e P3 P6 e P7 set point 2 Alla fase 1 segue necessariamente la fase 2 con la definizione della Banda di Lavoro e del Set point Regolazione tensione minima di CUT OFF trimmer P5 FASE 1 P5 Regola la minima tensione di rotazione erogabile al ventilatore in funzionamento automatico CUT OFF il ventilatore non sar mai alimentato con una tensione inferiore al valore prefissato che non m 0 sarebbe sufficiente a fornire la coppia necessaria a mantenere in rotazione il ventilatore _ Per questo comando il Jumper di configurazione J1 in posizione 1 M z 9596 1 1 ll trimmer P5 permette di stabilire il punto di entrata in rotazione CUT OFF cio la tensione minima fornibile al carico in funzionamento automatico prima di attivare o disattivare il comando automatico Per regolare correttamente la tensione di CUT OFF agire nel modo seguente 1 ruotare il trimmer P5 comando manuale di velocit con J1 2 partendo dalla posizione m fino a quando si ottiene il valore di tensione di rotazione minima desiderata 2 spostare il Jumper di configurazione J1 dalla posizione 2 alla posizione 1 3 in regolazio
23. e operazioni di montaggio vedi lo schema allegato al kit gambe Poggiare il radiatore su una superficie solida e piana Fissare il radiatore utilizzando gli appositi fori sulle staffe di base flusso d aria orizzontale oppure sulle estremit inferiori delle gambe flusso d aria verticale RAN RAL Rev 1 1 25 07 08 IT EN 7 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS SPAZIO OPERATIVO Rispettare le distanze minime indicate in fig 3 necessarie per una libera circolazione dell aria e per manutenzione dell unit Fig 3 a FLUSSO D ARIA ORIZZONTALE a 5 gt 1m gt 4m na gt 1m LLL Fig 3 b FLUSSO D ARIA VERTICALE INSTALLARE IL RADIATORE IN POSIZIONE INACCESSIBILE A PERSONE NON AUTORIZZATE L alettatura dello scambiatore di calore in lamiera d alluminio spessa 0 1 mm ed potenzialmente tagliente in caso di violento contatto involontario NB la caratteristica dei ventilatori non consente la canalizzazione dell aria DIMENSIONI DELLE CONNESSIONI IDRAULICHE l radiatore provvisto di connessioni tipo GAS maschio Gli attacchi femmina devono essere avvitati sulle estremit ingresso uscita intraponendo una guarnizione NOTA Il diametro delle linee idrauliche De tra condizionatore e radiatore remoto dev essere scelto in funzione della lunghezza delle stesse RAN RAL Rev 1 1 25 07 08 IT
24. ema elettrico allegato SECA L alimentazione elettrica non deve provenire dall unit cui esso collegato bensi dal quadro elettrico pi vicino o pi conveniente Verificare che la tensione e la frequenza di rete corrispondano ai valori riportati sulla targa di identificazione del radiatore Collegare il cavo di alimentazione al sezionatore introducendo il cavo nella scatola attraverso un passacavo IP55 e serrare a fondo le viti dei morsetti NOTA BENE Prevedere l installazione di una protezione o interruttore automatico di portata adeguata a monte della linea di alimentazione in conformit alle normative vigenti AVVIAMENTO Alimentare il radiatore e chiudere il sezionatore portare la manopola posizione I Nella versione P il ventilatore si attiva automaticamente quando la temperatura del fluido di raffreddamento raggiunge il valore di intervento del regolatore di velocit pre tarato in fabbrica ORGANI DI REGOLAZIONE TARATURA radiatore dotato di un organo di regolazione della velocit ventilatori opzionale consistente alternativamente in 1 Controllo termostatico ON OFF versione costruttiva S 2 Controllo modulante taglio di fase versione costruttiva L organo di regolazione pretarato in fabbrica In caso di modifica della taratura seguire le istruzioni seguenti regolatore della serie rgf un regolatore di tensione di rete che utilizza il principio della pa
25. etely clockwise decelerates the voltage to load modulation M 35 In position m minimum speed variation is almost instantaneous system ready The voltage regulator is supplied with a minimum slow start stop time equal to approximately 2 seconds During installation in order to prevent swings that might be caused by an inappropriate P1 calibration check the operation of the Rgf series voltage regulator during automatic control IMPORTANT Never under any conditions modify the position of the trimmers marked by a spot of red paint Manufacturer s setting RAN RAL Rev 1 1 25 07 08 IT EN 28 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS Set Point 2 Board SP2 In all applications where the use of a second set point e g Day Night or Summer Winter is absolutely required the expansion board can be used P6 P7 This board features m M m M Trimmer P6 for the adjustment of the Set point 2 Proportional Band C Trimmer 7 the adjustment of Set point 2 i Jumper J21 for the operation of the adjustment in REVERSE MODE 3 C 20 C Jumper J22 for the operation of the adjustment in DIRECT MODE m MI m Jumper J23 position selection cannot be adjusted Factory calibration Yellow DL2 Led signals Set point 2 enabling 6 C 16 The methods to be used for the calibration of Trimmers P6 and P7 are the same as those m m described in Ph
26. he establishment of the rotation start point during rotation CUT OFF or in other words the minimum voltage that can be supplied to the load during automatic operation before the enabling or disabling of the automatic control Proceed as follows to correctly adjust the CUT OFF voltage 1 Rotate the P5 trimmer manual speed control with J1 2 by starting from the m position until reaching the minimum rotation voltage value desired 2 Shift the J1 configuration jumper from position 2 to position 1 3 During automatic adjustment the load will be fed starting from the minimum voltage value selected Maximum operating speed regulation trimmer P4 PHASE 1 P4 This trimmer limits the maximum operating speed from 100 0 max speed Used to limit the fan s maximum air flow or operating noise level at peak speed This value is set in the Factory to the maximum value M that corresponds to the maximum speed equivalent to 100 of the automatic control value M 10096 0 The P4 trimmer can be used to limit the maximum operating voltage when the automatic control signal is at maximum value In order to set the Maximum limit value the Max automatic control value in C for the voltage regulator must first be generated in order to make the fans rotate at maximum speed Starting from the M position rotate the P4 trimmer clockwise until reaching the value desired as the maximum limit output voltage RAN RAL Rev 1 1 25
27. i dalle leggi locali inoltre possibile riconsegnare al distributore l apparecchiatura a fine vita in caso di acquisto di una nuova Questa apparecchiatura pu contenere sostanze pericolose un uso improprio o uno smaltimento non corretto potrebbe avere effetti negativi sulla salute umana e sull ambiente simbolo contenitore di spazzatura su ruote barrato riportato sul prodotto o sulla confezione e sul foglio istruzioni indica che l apparecchiatura stata immessa sul mercato dopo il 13 Agosto 2005 e che deve essere oggetto di raccolta separata In caso di smaltimento abusivo dei rifiuti elettrici ed elettronici sono previste sanzioni stabilite dalle vigenti normative locali in materia di smaltimento Disposal the product is made up of metal parts and plastic parts In reference to European Union directive 2002 96 EC issued on 27 January 2003 and the related national legislation please note that WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately The public or private waste collection systems defined by local legislation must be used In addition the equipment can be returned to the distributor at the end of its working life when buying new equipment The equipment may contain hazardous substances the improper use or incorrect disposal of such may have negative effects on human health and on the environment The symbol crossed out wheeled bin shown on the product or on the
28. justment Never under any circumstances modify the trimmers marked with a spot of red paint RAN RAL Rev 1 1 25 07 08 IT EN 26 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS Taratura di Fabbrica Factory Calibration P5 P6 SOFT PROP SET MAX CUT OFF PROP START BAND POINT OUT BAND PB1 SP1 2 2sec 6 C 35 230VAC 90VAC 6 C Note the calibrations described above have already been checked during the final test inspection phase Contact the UNIFLAIR Technical Service prior to proceeding to modification The adjustment of the work parameters can be divided in two phases 1 the definition of the voltage regulator s work limit values the P4 and P5 values are set in this phase 2 the definition of the voltage regulator s work range the P2 and and P7 set point 2 values are set in this phase Phase 1 must be followed by Phase 2 with the definition of the Proportional Band and the Set point Minimum CUT OFF voltage regulation trimmer P5 PHASE 1 P5 This trimmer adjusts the minimum rotation voltage that can be delivered to the fan during CUT OFF automatic operation in which the fan will never be fed with a voltage that is lower than the established value which would not be sufficient to deliver the torque required to keep the fan m 0 rotating 95 For this control the J1 configuration jumper is in position 1 J1 1 The P5 trimmer permits t
29. n T On P version the fan motor starts automatically when the liquid temperature reaches the preset value of the speed regulator factory set CONTROLIDEVICES ADJUSTMENT The radiator is equipped with an optional fan speed control device consisting in either 1 ON OFF thermostat control constructive version 5 2 Modulating phase cut off control constructive version P The control device is pre set in the Factory Whenever the calibration must be changed follow the instructions below The Rgf series is a mains voltage regulation device based on the principle of the regulation or cut off of the phase and has been designed to adjust the active voltage according to a control signal The device has been constructed for industrial use and complies with EMC Standards for industrial surroundings Adjustment is made through the regulation of the voltage of the mains simple harmonic current input The Rgf series voltage regulator is composed of an electronic board installed inside a techno polymer container with IP55 Protection Rating The control section is found on the board s upper side while the power section is positioned on its lower side RAN RAL Rev 1 1 25 07 08 IT EN 25 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS Single phase voltage regulator Selection MODE 1 Cut Off 2 MIN OUT P3 P4 UU A SOFT PROP SET MAX CUT START BAND POINT OUT OFF
30. ne automatica il carico sar alimentato a partire dal valore di tensione minima selezionata Regolazione velocit massima di funzionamento trimmer P4 FASE 1 Limita la velocit massima di funzionamento da 100 a 0 E utile per limitare la portata massima o la rumorosit del ventilatore al max regime di giri Viene settato in fabbrica al valore massimo M che corrisponde alla velocit massima pari al 100 del valore di comando automatico Agendo sul trimmer P4 possibile limitare la tensione massima di funzionamento quando il segnale di comando automatico al valore massimo Per impostare il valore di limite Massimo occorre generare il Max valore di comando automatico in C per il regolatore in modo da avere i ventilatori alla massima velocit Partendo dalla posizione M ruotare P4 in senso orario fino al valore desiderato come limite di massima tensione in uscita RAN RAL Rev 1 1 25 07 08 IT EN 1 3 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS Regolazione banda proporzionale trimmer P2 FASE 2 2 trimmer regola la banda di lavoro cio il punto cui il comando automatico al banda di lavoro valore Massimo 100 C campo di lavoro indica l incremento segnale di comando in ingresso C che serve all rgf per pilotare ventilatori dalla tensione minima alla tensione massima il Campo di lavoro varia dai 2
31. nte tra la stessa ed il vaso di espansione La capacit totale del vaso di espansione viene espressa dalla seguente relazione CXe t jP utilizzando del coefficiente di espansione ricavati dalla tabella COEFFICIENTE DI ESPANSIONE DELL ACQUA T dell acqua In alternativa possibile valutare il valore medio di C kg m riferito a 10 C tra la temperatura iniziale dell acqua in genere Ls 999 6 assumibile pari a 10 C e la temperatura di esercizio 997 9 0 0017 utilizzando la relazione 9956 0 0040 e 7 5x10 T C 9922 0 0075 92 sns so 953 00955 CAPACIT DEL CIRCUITO IDRAULICO In tabella riportata la capacit del circuito idraulico espresso in litri i 136 121 142 191 305 536 910 RAN RAL Rev 1 1 25 07 08 IT EN 1 0 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS COLLEGAMENTI ELETTRICI La corretta esecuzione degli allacciamenti elettrici a regola d arte e nel rispetto delle norme vigenti importante ai fini della prevenzione degli infortuni e del buon funzionamento inalterato nel tempo del radiatore Prima di eseguire qualsiasi operazione su parti elettriche assicurarsi che non vi sia tensione e che il sezionatore di bordo sia aperto in posizione O CAVI DI ALIMENTAZIONE PROTEZIONI vedi sch
32. o da potenziale i morsetti 9 10 della morsettiera di comando RAN RAL Rev 1 1 25 07 08 IT EN 1 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS MODELLO 0360 os10 1000 1500 2900 eoo 50 Alimentazione V ph Hz 230 1 50 400 3 50 Potenza assorbita nominale kW 0 36 0 54 0 54 0 87 1 16 2 04 2 72 6 30 complessiva Resa nominale 16 6 20 9 30 2 36 9 51 3 81 2 127 9 200 5 Portata d aria nominale 5800 6470 9560 11820 16000 31800 41600 54000 moneo 0750 1000 1500 Alimentazione V ph Hz 230 1 50 Numero di ventilatori N poli Potenza assorbita nominale 1 28 1 92 2 56 complessiva Corrente eletrica assorbila MENES Resa nominale 34 6 46 0 64 1 portata d aria nominale 11490 16140 21820 Livello di pressione sonora a 10 m dB A wawa T aria 25 C T ing acqua 40 C T usc acqua 35 C glicol 096 Perdita di carico in funzione della portata del fluido di raffreddamento MODELLO perdita kPa portata I h perdita kPa portata I h perdita kPa portata I h RAL 030 4 w 2 0510 14 200 21 250 230 300 0700 i2 300 15 8350 20 400 1000 400 10 450 42 500 1500 i4 500 16 550 19 600 2300 600 9 650 10 700 RAL3S600 70 zo 2 800
33. ono essere effettuate con macchina ferma e devono essere condotte da personale esperto e qualificato In caso d incendio l acqua e le altre sostanze conduttrici non devono essere usate per lo spegnimento in prossimit delle parti elettriche sotto tensione Tale divieto dev essere esposto nel luogo d installazione della macchina mediante avvisi Assicurarsi che la tensione d alimentazione corrisponda a quella riportata nei valori di targa RAN RAL Rev 1 1 25 07 08 IT EN 4 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI DRY COOLERS DESCRIZIONE GENERALE DISPOSIZIONE FLUSSO D ARIA ORIZZONTALE VERTICALE Fig 1 Fig 2 Ventilatore Staffe di supporto Gambe di supporto Connessioni idrauliche Sezionatore Regolatore di velocit Targa d identificazione Sonda temp entrata acqua ND Q N N B l numero e la disposizione dei ventilatori varia con il modello del radiatore Figure riferite ai modelli 2300 5700 RAN RAL Rev 1 1 25 07 08 IT EN 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS DESCRIZIONE E DESTINAZIONE D USO Radiatori remoti con ventilatore assiale idonei ad installazione all aperto completamente assemblati e collaudati in fabbrica radiatori possono essere installati sia in posizione verticale fl
34. packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be desposed of separately In the event of illegal disposal of electrical waste the penalties are specified by local disposal legislation RAN RAL Rev 1 1 25 07 08 IT 2 L JUNIFLAIR Simbologia Norme di sicurezza Descrizione generale Descrizione e destinazione d uso Targa d identificazione Trasporto e movimentazione Dimensioni e pesi Installazione Spazio operativo Dimensioni delle connessioni idrauliche Collegamenti idraulici Utilizzo di glicole etilenico MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS Indice e 5 RV OO sy NJ wy o gt 6 1 5 Dimensionamento del vaso di espansione 10 Capacita del circuito idraulico 10 Collegamenti elettrici 11 d alimentazione protezioni 11 Avviamento 11 Organi di regolazione taratura 11 Dati tecnici 16 Manutenzione 17 Index Page Symbols used 18 Safety Instructions 18 General Description 19 Description and use 20 Nameplate 20 Transport Positioning On Site 21 Dimensions And Weight 21 Installation 21 Working Space 22 Size of hydraulic connections 22 Hydraulic Connections 23 Use of ethylene glycol 23 Guide to the sizing of the expansion tank 24 Capacity of water circuit 24 Electrical Connections 25 Power Supply Cables Protection 25 Start Up 25
35. rzializzazione o taglio di fase E stato progettato per la tensione efficace in funzione di un segnale di comando L apparecchio costruito per uso industriale e risponde quindi alle norme EMC a riguardo dell ambiente Industriale La regolazione avviene per parzializzazione della sinusoide di rete in entrata regolatore costituito da una scheda elettronica montata all interno di un contenitore in tecnopolimero con grado di protezione IP55 Sulla scheda posizionata la parte di controllo lato superiore e la parte di potenza lato inferiore RAN RAL Rev 1 1 25 07 08 IT EN 11 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS Regolatore monofase Selection MODE 1 Cut Off 2 MIN OUT P2 P3 P4 M m M m M T PROP SET CUT START BAND POINT OUT OFF PB1 5 1 SET POINT 5 Morsettiera Alimentazione PEMIM2N F 4 Dav 2 Dev amp N OOOO0O0 Morsettiera di ccm 42345 6 7 B 9 10 O i i ________ 3 um NTC 1 C NTG 2 C SP 1 oe PE Quando il contatto 9 10 della morsettiera di comando aperto viene ET ue L1 abilitato il controllo mediante trimmer P2 P3 mentre quando chiuso viene AY Fuga i attivato 1 controllo mediante il trimmer 6 7 Nella parte di controllo sono presenti gli organi di
36. s for maximum exchange efficiency RAL RAL RAL RAN RA RA RAL RAL RAL Modello 0360 0510 0700 0750 1000 1500 2300 3600 5700 Electrical Panel main Switch in an IP 54 box the electric connection box is easily accessible from the outside Speed regulator device either modulating or ON OFF control option NAMEPLATE The nameplate located on dry cooler contains the following data Unit model Serial number Year of manufacture Current and power absorbed Standard settings DIMENSIONS AND WEIGHT For dimension see drawing DIUI attached RAL RAL RAL RAN RA RA RAL RAL RAL Model 0360 0510 0700 0750 1000 1500 2300 3600 5700 Net weight kg RAN RAL 1 1 25 07 08 IT EN 20 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS TRANSPORT POSITIONING ON SITE The dry cooler leaves the factory in perfect condition at the moment of delivery its condition should be carefully checked and any damage which might have been caused in transit should be notified in writing to the haulier During transit and positioning on site Do not overturn or lean the dry cooler on its side Before removing the packaging carry the dry cooler to the nearest possible point to the actual installation location by using a pallet truck or a forklift securing the unit to ensure that it does not fall off remove all packing with care make sure that the unit is not damaged in any way
37. upply Pressure drop liquid supply kPa I h kPa I h kPa I h RALO360 4 w s 150 2 0510 14 2000 2 250 830 30 0700 12 15 o 20 40 1000 400 10 450 1500 14 soo 16 so 319 2300 9 650 10 RAL 3600 700 3 750 850 27 900 RANTS 7 390 170 so 12 400 RAN 1000 d 10 4500 12 500 RAN 1500 500 16 sso 319 600 RAN RAL Rev 1 1 25 07 08 IT EN 30 32 JUNIFLAIR MANUALE DI ISTRUZIONI INSTRUCTION MANUAL RADIATORI REMOTI DRY COOLERS MAINTENANCE Regularly check the state of the dry cooler fins remove from them all foreign objects leaves feathers seeds dust etc using a jet of compressed air The heat exchanger fins are made of thin aluminium sheet and can cause cuts in the event of the accidental contact Check that the operation and current absorbed by each fan is normal and without any unusual noises Check that the control device and sensor are operating normally 31 32 RAN RAL Rev 1 1 25 07 08 IT EN JUNIFLAIR JUNIFLAIR Net ICIM UNIFLAIR S p A ISO 9001 Cert n 3412 Sede legale ed amministrativa Viale della Tecnica 2 35026 Conselve Tel 39 049 5388211 Fax 39 049 5388212 uniflair com info uniflair com P IVA
38. usso aria orizzontale oppure in posizione orizzontale flusso aria verticale Le unit sono dotate di controllo opzionale della velocit dei ventilatori del tipo termostatico ON OFF oppure modulante a taglio di fase Carrozzeria i radiatori sono realizzati con struttura autoportante in alluminio goffrato con elevatissima resistenza alla corrosione Ventilatori di tipo assiale il motore elettrico del tipo a rotore esterno con protezione termica incorporata IP54 classe F particolarmente adatto alla regolazione di velocit con sistemi a taglio di fase La griglia di sicurezza a protezione del ventilatore conforme alle vigenti norme di sicurezza Batteria ad ampia superficie frontale per un ottimale distribuzione dell aria realizzata con tubi in rame espansi meccanicamente su alette d alluminio per la massima efficienza di scambio Collegamenti idraulici le connessioni sono di tipo GAS maschio disposte su un lato dell unit per un collegamento rapido e sicuro Impianto elettrico interruttore sezionatore generale con grado di protezione IP54 regolatore di velocit o termostato controllo unit opzionali precablati TARGA D IDENTIFICAZIONE La targhetta d identificazione applicata sul radiatore riporta le seguenti indicazioni Modello della macchina Numero di Anno di costruzione Corrente e potenza assorbite Valori di taratura standard DIMENSIONI E PESI DIMENSIONI vedi disegni allegati