IS-010/1A Morsettiere serie CS . . - SSA ATEX
Contents
1. Ponte per il collegamento in serie Bridge for series connection IP30 insulating cover made by terminal N N manufacturer to use A 2 when is not possible 2 A remove voltage from the h A Ex e terminals before 4 opening the enclosures 4 f The cover is marking not 4 A open when energized A Ba z 4 zazrli distanziale per guida din DIN rail spacer Setto separatore per portare la distanza superficiale tra morsetti Ex e ed Ex ia minimo 50 mm spessore minimo 0 9 mm per materiale isolante e 0 45 in metallo in accordo alla norma EN 60079 11 Caratteristiche costruttive delle morsettiere AN l SN gt 30 gt 50 Morsetti Terminals Morsetti Terminals 220 so Separator to bring the superficial distance among terminals Ex e and Ex ia at least 50mm Minimum thick 0 9mm for insulating material and 0 45 in metal according to EN 60079 11 Fixed to the DIN rail or to the inside plate through screws or rivets Fissato alla guida din o alla piastra interna x i Morsetti Terminals Verdi meal Q gt gt 30 Ex e Exia 250 220 7 gt 50 IP Protection degree The minimum protection degree from accessing of solid bodies and external liquids is IP 66 with gasket Electrical Features Maximum voltage 630 V the voltage written on the plate is the lowest nominal voltage of the installed terminals Maximum current from 12 to 125 A Ambient temperatures the enclosures have temp
2. collegato elettricamente con la cassetta tramite ponticello con la vite di terra o attraverso la connessione morsetto guida DIN piastra interna Per una descrizione dettagliata fare riferimento all allegato Dispositivi di messa a terra Il collegamento di terra ha un dispositivo antiallentante e antirotazione come da disegni allegati al certificato Non rimuovere o sostituire questi dispositivi Cablaggio dei morsetti Tutti i cablaggi all interno delle cassette devono essere fatti rispettando le caratteristiche dei componenti I conduttori devono essere collegati al morsetto senza ridurre le distanze minime in aria e superficiali dello stesso la parte isolante del conduttore deve essere a ridosso della parte metallica del morsetto con distanza non superiore a lmm e devono essere bloccati lungo il percorso la loro lunghezza all interno della custodia non deve superare la diagonale interna massima I morsetti devono essere ben serrati per evitare resistenze di contatto elevate e quindi dei surriscaldamenti La corrente nominale massima che pu essere installata dipende dalla sezione del morsetto e viene indicata sulla targhetta d identificazione Verifiche e manutenzione Le verifiche e la manutenzione degli impianti elettrici nei luoghi con pericolo d esplosione devono essere eseguite secondo i criteri della norma EN 60079 17 Il coperchio deve essere ben serrato Per garantire la protezione IP 66 occorre che la
3. attesta sotto la propria responsabilit che le custodie sono state costruite a regola d arte quanto concerne la sicurezza che sono conformi alle Direttive CE applicabili e che le verifiche e prove individuali prescritte ed indicate sul certificato sono state eseguite con esito positivo Luoghi d installazione Le morsettiere sono da considerarsi costruzioni elettriche del gruppo II quindi destinate ad essere utilizzate in impianti di superficie Sono destinate in luoghi classificati come Zona 1 21 o Zona 2 22 secondo le norme EN 60079 10 ed EN 61241 10 L installatore e l utilizzatore sono sempre responsabili della rispondenza delle caratteristiche dei luoghi d installazione ai limiti ed alle caratteristiche di cui sopra Documento riservato Ogni modifica deve essere sottoposta all organismo notificato data Festa Atm ioni Soritto AF AD Einn E Istruzioni ATEX it 25 09 2006 VIGANO i Verificato NM Concorezzo MI Italia 15 010 1A Morsettiere serie CS SSA Approvato FF foglio 3 di 11 Terminal boxes manufacturing characteristics dispositivo in materiale isolante previsto dal costruttore del morsetto con grado di protezione minimo IP30 da utilizzarsi quando non possibile togliere tensione ai morsetti Ex e prima dell apertura della cassetta sull involucro presente la dicitura non aprire sotto tensione Morsetto o setto separatore Terminals or separator
4. guarnizione venga mantenuta integra verificare ad ogni apertura che non presenti lacerazioni o tagli Controllare il serraggio dei morsetti per verificare il loro antiallentamento La sostituzione dei gommini e parti delle entrate di cavo devono essere effettuati con componenti identici a quelli forniti dal costruttore per garantire il mantenimento della protezione le viti di chiusura devono essere in acciaio inox filettatura passo grosso Documento riservato Ogni modifica deve essere sottoposta all organismo notificato data Explosion Proof ADE en Istruzioni ATEX Concorezzo MI Italia IS 010 1A Morsettiere serie CS SSA Approvat FF Scritto AF Verificato NM 25 09 2006 foglio 5 di 11 Repairs All repairs of explosion proof devices must be made according to the specified criteria of IEC 60079 19 rule Repairs made by persons that not belong to AD Vigan staff are not allowed unless a specific written authorization by AD Vigan that granted for persons duly trained Cable entries The connections must be performed using cable entries in accordance to the EN 60079 14 rule The cable entries must be made using locking fittings mixed nipples or cable glands Ex and certified in accordance to the EN 60079 7 rules If the entrance of the cables is made by cable glands this must be correctly chosen depending on the type of equipment the enclosure IP protection the
5. ambient temperature range of the enclosure and the cable type The cable glands must be duly tightened so that the sealing rings reach the necessary pressure a to avoid mechanical stress transmission to the terminals b to guarantee the mechanical protection IP degree of the terminal blocks box Breather and drain valve The boxes could be furnished with breather and drain valve For the operation needs that periodically is completely unscrewed to put in connection the inside ambient of the box with the outside ambient When the operation is finished the screw has to be screwed completely to guarantee the gasket use and the maintenance of IP 66 protection Riparazioni Le riparazioni delle apparecchiature antideflagranti devono essere effettuate secondo i criteri specificati dalla norma IEC 60079 19 Non sono ammesse riparazioni da personale non appartenete alla AD Vigan a meno che non sono ritenuti idonei ed autorizzati dalla stessa con una dichiarazione per iscritto ed adeguatamente formati Entrate di cavo I collegamenti devono essere realizzati mediante entrate di cavo conformi alla norma EN 60079 14 Le entrate di cavo devono essere realizzate con raccordi di bloccaggio nippli miscelati o pressacavi Ex e certificati secondo le norme EN 60079 0 ed EN 60079 7 Se l ingresso cavi viene fatto a mezzo di pressacavo questo deve essere scelto correttamente in rapporto al tipo d impianto idonee al tipo di protezione IP d
6. responsibility that the enclosures are manufactured at a state of art for safety and are in accordance to applicable CE Directives and that verifications and individual tests required and indicated on the certificates have been done with positive result Installation places The terminal blocks are to be considered group H electrical equipments therefore to be used in surface plants They are intended for areas classified as Zone 1 21 or Zone 2 22 in accordance to EN 60079 10 and EN 61241 10 Installers and users are always responsible for the characteristics accordance of the places where the equipments are installed to the limits and features as above Marcatura ATEX Tutte le morsettiere sono dotate di targhe indelebili e durevoli fissate al corpo della cassetta La targa riporta i seguenti dati Destinazione d uso della custodia Nome e indirizzo del fabbricante Indicazione della serie e della grandezza della custodia Matricola anno di costruzione Tensioni correnti e frequenza N morsetti x sezione ripetuto secondo le diverse sezioni La targa riporta la seguente marcatura ATEX II2G Ex eII T6IP66 o Ex e ia IIC T6 IP66 o Ex ia IIC T6 IP66 II 2D Ex tD A21 IP66 T85 C o Ex tD iaD A21 IP66 T85 C o Ex iaD 21 T85 C IP66 Numero dell organismo sorveglianza Il numero di certificato incaricato della Contrassegnando le morsettiere con gli elementi sopraccitati AD Vigan
7. targa o nel certificato La marcatura ATEX delle morsettiere pu essere x IH 2G Exeia IIC T6 or Ex ia IIC T6 x II 2D ExtDiaD A21 T85 C or Ex iaD 21 T85 C La custodia riporter targhe aggiuntive con le seguenti avvertenze Contiene circuiti a sicurezza intrinseca In prossimit delle entrate di cavo dei circuiti Ex i contrassegnati dal colore blu la seguente avvertenza Circuiti a sicurezza intrinseca Dettagli sul montaggio delle morsettiere all interno delle custodie CSA CSX e SSA Normalmente vengono montate alloggiandole su barre DIN Le morsettiere verranno montate seguendo strettamente le istruzioni per l uso ATEX dei relativi costruttori La distanza minima tra la morsettiera la custodia dovr essere di almeno 20 mm I morsetti devono essere bloccati orizzontalmente utilizzando come terminali della morsettiera o 2 morsetti di terra o due elementi terminali forniti come accessori dei morsetti come indicato tuttavia nelle istruzioni di montaggio delle barre DIN Temperature Class T and maximum installable power Must follows the general instructions for power dissipation calculation inside the terminal block however conforming to EN 60349 1 The maximum number of terminals installable must be compatible with the layout of the enclosure with the admitted distances so that don t hinder the wiring of the terminal block Cables terminations The inside connections cables to the terminals must all
8. 41 11 2006 EN 60529 1991 A1 Ente notificato Notified Body CESI 0722 Notifica della produzione EC Type Examination CESI 03 ATEX 019 Q Certificato di conformit Conformity certificate BVI 06 ATEX 0039 Signature of manufacturer function of the signer Data Date 25 09 06 Managing Director A D VIGANO s r l Via T Tasso 50 20049 Concorezzo MI Tel 0039 039 61153 1 R A Fax 0039 039 6040695 E mail info ad vigano com http www ad vigano com Cap Sociale 199 000 000 I V P I C F 02046450967 R E A NR 1339422 R I N MI 149 44418
9. ATEX Instructions Istruzioni ATEX Terminal blocks series CSA CSX SSA Morsettiere serie CSA CSX SSA x II 2G Exell T6 o or Ex eia IIC T6 o or Ex ia IIC T6 x II 2D ExtD A21 IP66 T85 C o or Ex tD iaD A21 IP66 T85 C o or Ex iaD 21 T85 C Grado di protezione Protection degree IP66 Temperatura ambiente Ambient temperature 20 C 40 C oppure or 20 C 55 C Test Certificate BVI 06 ATEX 0039 Certif di Conformit BVI 06 ATEX 0039 Documento riservato Ogni modifica deve essere sottoposta all organismo notificato data AD ire struzioni ATEX Ato SE 25 09 2006 VIGANO 3 Verificato NM Concorezzo MI Italia IS 01 0 1A Morsettiere serie CS SSA Approvato FF foglio 1 di 11 Instructions for ATEX usage General usage The safety measures and the equipment used on CSA series terminal blocks installation use and maintenance places must follow the specific instructions explained in this manual book and the applicable installation rules main installation rule CEI 64 8 and or the installation location rule It must also follow the additional rules for hazardous areas with explosion danger EN 60079 14 and EN 60079 17 due to the gas presence and EN 61241 14 ed EN 61241 17 due to the dust presence for installation and tests and IEC 60079 19 for the maintenance and repair unless otherwise indicated Usage These rules are applied to the terminal blocks series CSA CSX e SSA
10. ella custodia al range di temperatura ambiente a cui destinata la custodia e al tipo di cavo Il pressacavo va stretto a fondo affinch gli anelli di tenuta realizzino la pressione necessaria c ad impedire la trasmissione di sollecitazioni meccaniche ai morsetti d a garantire la protezione meccanica grado IP della scatola morsettiera Valvola di respirazione e drenaggio Le cassette possono essere dotate di dispositivo di respirazione e drenaggio Per il funzionamento occorre che periodicamente venga allentato completamente per mettere in collegamento l ambiente interno della cassetta con l esterno terminata l operazione la vite deve essere avvitata completamente per garantire la tenuta della guarnizione e il mantenimento della protezione IP 66 Documento riservato Ogni modifica deve essere sottoposta all organismo notificato data AD Ein Istruzioni ATEX Scritto AF SE IDA0O0E VIGANO i Verificato NM Concorezzo MI Italia 15 010 1A Morsettiere serie CS SSA Approvato FF foglio 6 di 11 ATEX Instruction Attached to the safety instructions IS 010 1A related to the realization procedures for junction box Ex ia ib Ex eia eib series CSA CSX and SSA Referring law EN 60079 11 EN 60079 14 This attached is integral part of the ATEX safety instructions number IS 010 1A these prescriptions if in conflict with the generic ones are the master ones Istruzioni ATEX Al
11. er il calcolo della potenza dissipabile all interno delle morsettiere comunque conforme ad EN 60349 1 Il numero massimo di morsetti installabili deve essere compatibile con il layout della custodia con le distanze ammesse in modo da non ostacolare il cablaggio delle morsettiere Terminazioni dei cavi Le connessioni interne dei cavi ai morsetti devono consentire un cablaggio ordinato in modo che siano separati i circuiti non a sicurezza intrinseca da quelli a sicurezza intrinseca secondo regole determinate dalle EN 60079 11 ed EN 60079 14 I conduttori devono essere collegati al morsetto senza ridurre le distanze minime in aria e superficiali dello stesso la parte isolante del conduttore deve essere a ridosso della parte metallica del morsetto con distanza non superiore almm Le condutture i cavi dei circuiti a sicurezza intrinseca devono essere realizzati solo con cavi a conduttori isolati di tipo A o B art 12 2 2 8 secondo la norma EN 60079 14 e comunque seguendo i requisiti dell art 12 2 2 della EN 60079 14 CEI 31 33 I conduttori vengono fissati o ancorati o separati in modo che non possano essere raggruppati con circuiti non a sicurezza intrinseca anche indirettamente in modo che siano segregati Ad esempio Ex non Ex i Canale Raceway non Ex i Canale Raceway Is Canale separato Separated raceway La minima distanza tra i circuiti a sicurezza intrinseca e quelli non a sicurezza intr
12. eratures class T6 85 C and two ambient temperatures 20 C s 40 C 20 C s 55 C The dissipable power inside the enclosure combined to every temperature combination is listed in a chart in the attached A For the terminals Ex e the inside superficial temperature of the terminals conductors in function of the nominal current and the number of installable terminals is determined with the suitable computational procedure in the attached A tramite viti o rivetti i N 250 Moreny Terminals Morsetti Terminals E Ex i 220 Grado di protezione IP Il grado minimo di protezione dall accesso di corpi solidi e liquidi esterni IP 66 utilizzando una guarnizione di tenuta Caratteristiche elettriche Tensione massima 630 V la tensione indicata in targa la pi bassa tensione nominale dei morsetti installati Corrente nominale max da 12 a 125 A Temperatura ambiente Alle custodie stata attribuita la classe di temperatura T6 85 C e due temperature ambiente 20 C 40 C 20 C 55 C La potenza dissipabile all interno della custodia abbinata ad ogni combinazione di temperatura elencata nella tabella riportata nell allegato A Per i morsetti Ex e la temperatura superficiale interna dei morsetti conduttori in funzione delle correnti nominali e il numero dei morsetti installabili determinata con la procedura di calcolo indicata nell allegato A Documento riservato Ogni modifica d
13. eve essere sottoposta all organismo notificato data Explosion Proof AD Istruzioni ATEX Concorezzo MI Italia IS 010 1A Morsettiere serie CS SSA Scritto AF Verificato NM 25 09 2006 Approvato FF foglio 4 di 11 Earth terminal earth connection The enclosure have two threaded connections for earthing one internal and one external that is against loosening and rotation In the terminal block there is always an earth terminal installed on DIN rail with equivalent section as phase terminals until 35mmq with a minimum of 35mmq for the 70mmq phase conductor The earth terminal is electrical connected with the enclosure through a bridge with the earth screw or through the connection terminal DIN rail internal plate For a more illustrated description see the attached Earthing devices The earth connection has a device against loosening and rotation as per drawings attached on the certificate Do not remove or replace these devices Terminals cables connection All cables connections inside the enclosures must be made following the components characteristics The conductors must be connect to the terminal without reduction of the minimum distance in air and surface the insulation part of the conductor has to be in contact with the metallic part of the terminal with distance not more than 1mm and blocked in their length Their lengths inside the enclosure has to be min
14. inseca deve essere mantenuta a 6 8 mm e comunque non meno di quella prevista dalla tabella 4 della norma EN 60079 11 Il minimo grado di isolamento elettrico delle condutture deve essere 0 5 kV per i circuiti a sicurezza intrinseca singoli 1 kV tra differenti circuiti a sicurezza intrinseca in cavi multipolari Seguire i requisiti dell art 12 2 2 5 della EN 60079 14 CEI 31 33 The least separation distance of the connection elements of intrinsic safety circuits and other circuits will be held to 50 mm as foreseen by the EN 60079 14 arts 12 2 3 Typical realizations are shown in the following sketches Circuiti Circuit Ex ia Canale dei circuiti a sicurezza intrinseca Ex ia Ex ia intrinsicaly safety circuits raceway Circuiti Circuit Ex ia General realization instructions for circuits Ex i When the separation is made with distances we must maintain 50mm between circuits Ex i and not Ex i when separation it is realized with a separator it must have thickness at least 0 9 1 mm and that cannot be deformed with the mounting of the other inside components when separation is realized with a metallic separator must be earthing in sure way the separator can stretch up to 1 5 mm toward the next side and must guarantee in all the directions rule of tense thread 50mm between the connection elements Ex i and not Ex i with the same principle must be maintained 6mm between differe
15. izzati elencati e ai documenti normativi Dove applicabile un ente competente ha rilasciato l EC Tipo Esame attinente We AD Vigan S r l Italy declare under our sole responsibility that the mentioned product is in accordance with the applicable european directive and to the listed harmonized standards or normative documents Where applicable a competent body has been released the relevant EC Type Examination Explosion Proof Electrical Equipment VIGANO Dichiarazione di conformit CE 010 1A Declaration of Conformity CE 010 1A In accordo alla in conformity to the EN 45014 Questa dichiarazione si applica ai seguenti prodotti This Declaration of Conformity is relevant to the following products Morsettiere Serie Junction boxes Series CSA CSX SSA Modo di protezione Protection mode x 1126 Exell T6 or Exeia IIC T6 or Ex ia IIC T6 e o and or E i 2D Ex tD A21 IP66 T85 C or Ex tD iaD A21 IP66 T85 C or Ex iaD 21 T85 C Grado di protezione IP66 Temperatura ambiente 20 C 40 C oppure 20 C 55 C secondo indicazioni di targa conformi alle direttive europee relevant european directive standards armonizzati applicati applied harmonized standards Altri standards applicati Others applied standards 94 9 EC 89 336 EC EN 60079 0 2004 EN 60079 7 2003 prEN 60079 11 2006 EN 61241 0 2006 EN 61241 1 2006 EN 612
16. legato all Istruzioni di Sicurezza IS 010 1A relativo alle procedure di realizzazione di cassette di derivazione Ex ia ib Ex eia eib serie CSA CSX e SSA Normativa di riferimento EN 60079 11 EN 60079 14 Questo allegato parte integrante dell Istruzioni di Sicurezza ATEX numero IS 010 1A queste prescrizioni qualora in conflitto con quelle generiche prendono il sopravvento Instructions for the use and production of terminal blocks with intrinsic safety circuits Ex e ia or Ex ia or Ex tD iaD or Ex iaD Generality Typology of allowed terminals The terminals block can contain intrinsic safety terminals interfaced with equipments ia or terminals type Ex e or both these must have their own ATEX certification in accord to the rules EN 60079 0 EN 60079 7 EN 60079 11 in the case of ATEX II 2G marking in accord to the rules EN 61241 0 EN 61241 1 EN 61241 11 in the case of ATEX II 2D marking It is compulsory verify that the environment temperature indicated in the tag is higher or equal to the expected temperature for the use conditions The maximum tension Um of common way applied to the terminals end must be that indicated in the tag or in the certificate The ATEX marking of terminal block can be Ex II 2G Exeia IIC T6 or Ex ia IIC T6 x II 2D Ex tD iaD A21 T85 C or Ex iaD 21 T85 C The enclosure will bring additional tags with the following warning Contain intrinsic safetv circuits In pr
17. lizzarsi quando Terminals or separator non possibile togliere tensione ai morsetti Ex e prima dell apertura della cassetta Ponte per il collegamento in serie 1 sull involucro presente la dicitura Bridge for series connection S non aprire sotto tensione gt 30 250 Morsetti Terminals Morsetti Terminals IP30 insulating cover Ex 5 F made by terminal N N manufacturer to use 2 7 when is not possible Yu A remove voltage from the A A Ex e terminals before 7i 220 opening the enclosures 4 2 The cover is marking not PA jl ATIS open when energized 4 ig i 4 oN zz ZZIZIT7 zz 297 zz zz ZIZZITZ A 250 distanziale per guida din Setto separatore per portare la distanza superficiale Separaror to bring me Sopena deano DIN rail spacer tra morsetti Ex e ed Ex ia minimo 50 mm AO ER S EAN AAA O EAS o AN spessore minimo 0 9 mm per materiale isolante e 0 45 in metallo in accordo alla norma EN 60079 11 according to EN 60079 11 Fissato alla guida din o alla piastra interna i Morsetti Terminals Morsetti Terminale gt 30 Exe Ex ia 250 tramite viti o rivetti 220 gt 30 250 Morsetti Terminals Morsetti Terminals Ex e Ex ia Minimum thick 0 9mm for insulating material and 0 45 in metal Fixed to the DIN rail or to the inside plate through screws or rivets Cables entries of intrinsic safety circuits in Ex ei enclosures The incomi
18. ng of the Ex i circuits must be clearly identified with a label that must be fixed on the enclosure side with rivets or other similar system Examples of labels Warning Cables for Ex i Warning circuits Ex i Circuits In alternative can be used blue colour cable glands type RAL 5015 The cable entries for intrinsic safety circuits must be realized in the opposite side or in the different sides comparing to the other not Ex i circuits that must be however accurately separated with minimum 10cm between the different cables entries Entrate di cavo di circuiti a sicurezza intrinseca in custodie Ex ei Le entrate dei circuiti Ex i devono essere chiaramente identificate con un etichetta che affissa sulla parete della custodia con rivetti o altro sistema di analogo risultato Esempi di targhette Cavi per circuiti Ex i Circuiti Ex i Attenzione Attenzione In alternativa si potranno utilizzare dei pressacavi di colore blu chiaro tipo RAL 5015 Le entrate di cavo per circuiti a sicurezza intrinseca vanno realizzate dal lato opposto o sul pareti diverse rispetto agli altri circuiti non Ex i comunque dovranno essere ben separati da un minimo di 10 cm tra le diverse entrate di cavo Azienda Certificata UNI EN ISO 9001 Noi AD Vigan S r l Italia dichiariamo sotto la nostra responsabilit che il prodotto menzionato in accordo con le direttive europee applicabili ed agli standard armon
19. nt Ex i circuits and 3mm between earth Ex i circuits to check and record in the final testing phase La minima distanza di segregazione degli elementi di connessione di circuiti a sicurezza intrinseca e gli altri circuiti verr tenuta a 50 mm come previsto dalla EN 60079 14 art 12 2 3 Tipiche realizzazioni sono mostrate nei disegni seguenti H Circuiti Circuit Ex e Circuiti Circuit Ex e Istruzioni di realizzazione generali per circuiti Ex i Quando la separazione e fatta con le distanze allora si mantengono tra circuiti Ex i e non Ex i 50 mm Quando realizzata con un separatore questo deve essere di idoneo spessore almeno 0 9 1 mm e che non possa essere deformato con il montaggio degli altri componenti interni Quando e fatto con un separatore metallico questo va messo a terra in modo sicuro Il separatore pu estendersi fino a 1 5 mm verso la parete pi prossima e deve garantire in tutte le direzioni regola del filo teso i 50 mm tra gli elementi di connessione Ex i e quelli non Ex i con lo stesso principio vengono mantenuti 6 mm tra circuiti Ex i diversi e 3 mm tra i circuiti Ex 1 e terra da controllare e registrare in fase di collaudi finali However the inside enclosure free volume will be maintained to a minimum of 30 of the available volume The enclosure that contain Ex e terminals can t be open when energized and must indicated on the cover do not open when non i
20. ntrinsically safe circuit are energized except if the not intrinsic safety terminals have a mechanical protection IP 30 and on it there is the warning do not open when energized on the enclosure must have a tag with the warning non intrinsically safe circuits protected by internal IP30 cover Following typical schemes of assemblage and distances to respect for junction boxes that contain only clamps Ex i or Ex e or both Comunque il volume libero interno delle custodie sar mantenuto ad un minimo del 30 del volume disponibile Le custodie che contengono morsetti Ex e non possono essere aperte sotto tensione e devono riportare sul coperchio la scritta non aprire quando i circuiti non a sicurezza intrinseca sono sottotensione a meno che i morsetti non a sicurezza intrinseca abbiano una protezione meccanica IP 30 e su di essa vi sia la scritta non aprire sotto tensione sull involucro della cassetta deve esserci una targa con la dicitura circuiti non a sicurezza intrinseca protetti da involucro IP30 Schemi tipici di montaggio e distanze da rispettare per cassette di derivazione contenenti o solo morsetti Ex i o Ex e o entrambi Schema tipico cassette di derivazione Ex eia eib Typical scheme for junction boxes Ex eia eib dispositivo in materiale isolante previsto dal costruttore del morsetto con grado di protezione minimo Morsetto o setto separatore IP30 da uti
21. nuale e le norme impiantistiche applicabili norma base impiantistica CEI 64 8 e o quella del luogo d installazione e quelle aggiuntive nei luoghi con pericolo d esplosione per la presenza di gas EN 60079 14 ed EN 60079 17 per la presenza di polveri EN 61241 14 ed EN 61241 17 per quanto riguarda le installazioni e le verifiche e la IEC 60079 19 per quanto riguarda la manutenzione e riparazione salvo diversamente specificato Applicabilit Queste regole si applicano alle morsettiere serie CSA CSX e SSA con le caratteristiche descritte nel seguito Le morsettiere sono state progettate e realizzate secondo le prescrizioni delle norme europee EN 60079 0 EN 60079 7 prEN 60079 11 EN 61241 0 EN 61241 1 EN 61241 11 e in conformit alla Direttiva ATEX 94 9 CE Queste istruzioni sono state concepite per installatori ed utilizzatori aventi gi esperienza tecnica di base sull utilizzo e la messa in servizio d impianti e macchinario elettrico in luogo con pericolo d esplosione ed essendone stati idoneamente formati ed informati Documentazione d uso Queste istruzioni sono corredate da disegno d ingombro ed ingegneria compresi i dati tecnici necessari per effettuare l installazione correttamente ed in collegamento Riferirsi pertanto ad essi per le istruzioni relative Limiti d utilizzo Le morsettiere sono realizzate secondo il modo di protezione Ex e Ex ia Ex eia Il modo di protezione relativo ad ogni sing
22. ola scatola riportato sul corpo scatola Inoltre sono dotate di un grado di protezione IP66 impiegando una guarnizione di tenuta rispettando le caratteristiche indicate nel relativo certificato La temperatura limite d utilizzo di per gas T6 per le polveri T85 C Temperatura ambiente da 20 C a 40 C o 20 C a 55 C Documento riservato Ogni modifica deve essere sottoposta all organismo notificato data Explosion Proof inni A lectrical Equipment EX Scritto AF AD tica Equpmen Istruzioni AT di 25 09 2006 VIGANO Verificato NM Concorezzo MI Italia 15 010 1A Morsettiere serie CS SSA Approvato FF foglio 2 di 11 Ratings and ATEX marking All the terminal blocks are provided with indelible and enduring tags fixed to the enclosure body The tags show the following data Enclosure usage Manufacturer name and address Series indication and enclosure size Serial number manufacture year Voltage current and powers Number of terminals per section repeated for the different section The tag shows the following ATEX marking II 2G Exe II T6 IP66 or Ex e ia IIC T6 IP66 or Ex ia IIC T6 IP66 II 2D Ex tD A21 IP66 T85 C or Ex tD iaD A21 IP66 T85 C or Ex iaD 21 T85 C IP66 Authority reference number for the inspection check up Certificate number Indicating the terminal blocks with the above mentioned information AD Vigan certifies under its
23. or or equal at the distance between inside low angle and opposite upper inside angle The terminals must be well tightened in order to avoid high contact resistances and consequent warming The max current that can be installed depends on each terminal section and it is marked on the identification plate Verifications and maintenance Verification and maintenance of the electrical equipments in areas with explosion dangers must be made following the instructions of EN 60079 17 rule The cover must be securely locked to the bottom To guarantee IP 66 protection it is necessary that gasket is maintained in good conditions and must verify after every opening that it doesn t show breakage or cuttings Check the terminals locking to verify that they are not loosening Replacement of rubber washers and of parts where cables are entering must be made with identical components of those supplied by the manufacturer in order to guarantee the protection maintenance The locking screws must be in stainless steel big threaded Morsetto di Terra Collegamento di terra Le custodie presentano due connessioni filettate per la messa a terra una interna e una esterna di tipo antiallentante e antirotazione Nella morsettiera previsto sempre un morsetto di terra installato sulla guida DIN di supporto di sezione equivalente al morsetto di fase fino a 35mmq con un minimo di 35 mmq per il conduttore di fase da 70mmq Il morsetto di terra
24. ow an orderly wiring so that the not intrinsic safety circuits are separated from intrinsic safety circuits according to rules EN 60079 11 and EN 60079 14 The conductors must be connected to the terminals without reducing the air and superficial least distances of the same the conductor insulating part must be behind the metallic part of the terminal with distance not upper than Imm The conductors the intrinsic safety circuits cables must be realize only with isolated conductors cables type A or B art 12 2 2 8 according to the rule EN 60079 14 and however following the requisite of art 12 2 2 of EN 60079 14 CEI 31 33 The conductors are fixed or anchored or separated so that cannot be assembled with not intrinsic safety circuits also indirectly in this way they be separated For example Ex non Ex i Canale Raceway Canale Raceway Ex i non Ex i Canale separato Separated raceway The least distance among intrinsic safety circuits to not intrinsic safety must be maintained to 6 8 mm and however not less than that foreseen by the chart 4 of the rule EN 60079 11 The least electric isolation degree of the conductors must be 0 5 kVs for the single intrinsic safety circuits 1 kV between different intrinsic safety circuits in multi poles cables Follow the requisite of art 12 2 2 5 of EN 60079 14 CEI 31 33 Classe di temperatura T e massima potenza installabile Si seguono le istruzioni generali p
25. oximity of the cable entries of the Ex i circuits marked by blue colour the following warning Intrinsic safetv circuits Terminal block mounting details inside the enclosure CSA CSX and SSA Normally terminal blocks are mounted on DIN rail They will be mounted following strictly the instructions for ATEX use of the relative producers The least distance among the terminal block and the enclosure must be at least 20mm The terminals must be blocked horizontally using as end two earth clamps or two end elements furnished as terminals accessories as indicated in the DIN rail mounting instructions Istruzioni per l uso e fabbricazione delle morsettiere con circuiti a sicurezza intrinseca Ex e ia o Ex ia oppure Ex tD iaD o Ex iaD Generalit Tipologia di morsetti ammessi Le morsettiere ammesse possono contenere sia morsetti a sicurezza intrinseca interfacciati con apparecchiature ia sia morsetti di tipo Ex e o entrambi questi devono essere dotati di propria certificazione ATEX in accordo alle norme EN 60079 0 EN 60079 7 EN 60079 11 nel caso della marcatura ATEX H 2G in accordo alle norme EN 61241 0 EN 61241 1 EN 61241 11 nel caso di marcatura ATEX II 2 D E obbligatorio verificare che la temperatura ambiente Ta indicata in targa sia superiore o uguale a alla temperatura prevista per le condizioni d uso La massima tensione Um di modo comune applicato ai terminali dei morsetti deve essere quella indicato in
26. with the following explained features The terminal blocks have been studied and manufactured following the regulations of the European rules EN 60079 0 EN 60079 7 prEN 60079 11 EN 61241 0 EN 61241 1 EN 61241 11 and in conformity to the ATEX Directive 94 9 CE These instructions have been conceived for installer and technical users who have already a background of technical experience on the use and start up of equipment and electrical machinery in areas with explosion of danger and who have been already trained and informed accordingly Instructions Manual These instructions are supplied with dimensions and engineering drawings technical data necessary to perform a correct installation and connection Refer to the drawings for complete instructions Usage Limitation The terminal blocks are manufactured in accordance to Ex e Ex ia Ex eia protection The protection level refer to every single box is indicated on the body of the box Furthermore they have a protection degree IP66 using a gasket in accordance with the features showed in the specific certificate The limit temperature of usage for gas is T6 for dust is T85 C Ambient Temperature 20 C to 40 C or 20 C to 55 C Istruzioni per Puso ATEX Generalit Le misure di sicurezza e le apparecchiature utilizzate sul posto d installazione esercizio e manutenzione delle Morsettiere serie CSA devono seguire le istruzioni specifiche contenute in questo ma
Download Pdf Manuals
Related Search
Related Contents
Manuel d`utilisation Trevi OM 3310 JVC HR-A590U User's Manual Premier Mounts Swingout Arm for 40"-61" Displays (AM3) Manual de instruções - Aparelho de pressão Modelo 3001 ST 190 ST 190 Sika MaxTack Steam Pro Compact - Pdfstream.manualsonline.com EQUIPO DE SOLDADURA OXIBUTANICA Código: FC22 Lote: 155 Guide du bilan sociétal PME Copyright © All rights reserved.