Home

Serie 90

image

Contents

1. Installation diagrams esee eese tnn teta IU rozm PRODUCT FUNCTIONS The restart function consists of automatically reclosing the differential switch if it uncouples unexpectedly due to a temporary electrical phenomenon lightning disturbances etc Before reclosing the device makes a check that there is no earthing fault in the circuit downstream if there is a fault it goes into locked status otherwise it proceeds with reclosing After a third cut in of the differential switch within three minutes of a previous automatic reset the device goes into locked status To re enable the restart function open the hatch raise the differential switch lever to position 1 and close the hatch If the differential switch will not remain in position 1 stop trying and call a specialised technician to check the system The restart function cannot be activated when the differential switch is open to activate it the differential switch lever must be raised to position 1 and the hatch closed The test key and the differential switch lever cannot be accessed when the functions are active PRODUCT DESCRIPTION Power supply m N Synoptic C e signal LED Signal LED gt Hatch in the automatic operation position Power supply um Hatch in the manual operation position System checking terminals Reset lever USER INSTRUCTIONS AUTOMATIC OPERATION CUTTIN
2. Dispositivo di riarmo non inserito nterruttore differenziale chiuso mpianto alimentato ED Dispositivo di riarmo non inserito nterruttore differenziale scattato o aperto intenzionalmente mpianto non alimentato e sezionato Funzionamento automatico xm Dispositivo di riarmo inserito nterruttore differenziale chiuso NE mpianto alimentato Dispositivo di riarmo in fase di verifica presenza guasto I po richiusura L apertura dello sportello interrompe la SET s richiusura automatica rendendo possibile la manovra TOSSO manuale Impianto non alimentato ma sezionato Dispositivo di riarmo in blocco per rilevazione guasto o T nell impianto a valle Tentare un riarmo manuale Se il ten tativo fallisce chiamare l installatore Interruttore differen TOSSO ziale scattato Impianto non alimentato ma non sezionato Legenda Q Led spento Led lampeggiante e Led acceso ISTRUZIONI PER L INSTALLAZIONE MONTAGGIO E CABLAGGIO solo per GW 90 971 INSTALLAZIONE Prima di effettuare qualsiasi operazione accertarsi che non vi sia tensione nell impianto Accoppiare RESTART sul lato destro dell interruttore differenziale SD facendo particolare attenzione all inserimento del perno nel foro della maniglia dell interruttore differenziale Fig 1 spingere per agganciarli meccanicamente fra loro Fig 2 Il perno e l
3. G IN AUTOMATIC MODE e INSERIRE CON d ion gt 1 Raise the lever Slide the hatch until a click is heard system System powered up powered up AUTOMATIC RESTART In the case of a temporary fault INSERIRE q 1 Normal operation gt El ISERIRE CON Li nw 3 The device performs a test of the system 4 Reset completed the lever rises again of approx 60sec Red indicator blinking powering up the system and cannot be operated manually for the next 3 minutes Differential switch closing can be forced manually by going into manual mode and raising the lever Call the installation technician if the differential switch trips again 18 In the case of a permanent fault IU rozm 3 The device performs a test of the system 4 Reset not successful due to system of at least 20sec Red indicator blinking problems 5 Open the hatch to section the system Note attempt a manual reset by opening the hatch and raising the lever If the reset fails stop attempt ing the reset operation and contact a specialised technician MANUAL OPERATION FROM AUTOMATIC TO MANUAL in INSERIRE CON posizione Slide the hatch until a click is heard Lower the lever if the system is to be System powered up powered down 19 LED SIGNALS LED SIGNALS DEVICE FRONT CONDITION Manual operation E Rest
4. GEWISS Serie 90 RESTART RD RESTART d u t En C iss GW 90 971 CARATTERISTICHE TECNICHE Tensione nominale Vn 230Vac fase neutro TT e TN Tensione di funzionamento da 0 85 a 1 1 Vn Durata massima del riarmo 2 minuti Intervallo minimo tra due chiusure consecutive 3 minuti Tensione di isolamento verso massa 2500V Potenza assorbita con interruttore differenziale chiuso 0 VA Potenza assorbita con RESTART in blocco 3 VA Temperatura d impiego da 5 C a 40 C Le caratteristiche tecniche ed elettriche sono le medesime dell interruttore associato AVVERTENZE LA SICUREZZA N B Leggere attentamente prima dell installazione e dell utilizzo del dispositivo Intervenire solo ad impianto sezionato e quindi con dispositivo non inserito Non accedere ai collegamenti elettrici senza aver tolto tensione all im pianto Il prodotto non idoneo all installazione in reti fase fase Quando il dispositivo amp in modalit manuale l interruttore associato svolge la funzione di protezione di un interruttore differenziale tradi zionale Quando il dispositivo in modalit automatica svolge un controllo dell impianto in seguito ad apertura dell interruttore differenziale per verificare la possibilit di ripristino automatico in sicurezza Eventuali posizioni intermedie della leva dell interruttore associato non costituiscono malfunzionamenti se temporanee e Se occorre disalimentare
5. Only intervene with the system sectioned and so with the device not inserted Do not access the electrical connections without having powered down the system The product is not suitable for installation in phase to phase networks When the device is in manual mode the associated switch performs the function of a traditional differential switch When the device is in automatic mode it makes a check of the system following the opening of the differential switch to verify the possibility of restarting automatically in safety Possible intermediate positions of the lever of the associated switch are not malfunctions if they are temporary e f the system is to be powered down manually within 3 minutes of a previous automatic restart use the test button of the differential switch after opening the hatch or use the switches connected downstream INDEX Product functions rette tete Product description iii o User instructions Automatic operation Cutting in automatic mode Automatic restart ssssssssseseeeenennenennnennnneees Manual operation 2 0 escecesessceseceseeseseceeeeesesecesseseseetenseseseeseseaee From automatic to manual L d Signals toon eit Hd de P ER Installation instructions s Assembly and cabling only for GW 90 971 Installation seen Aaa Technicali data tn
6. a maniglia devono essere gi Fig 2 Installare gli apparecchi sulla rotaia e collegare i cavi di linea e carico prima di serrare i morsetti collegare i fili d ingresso del RESTART lato linea e quelli di x controllo lato carico inserendo i DI capicorda sotto le teste delle viti Fig 3 Serrare a fondo i morsetti verifi cando che entrambi i collega menti siano bloccati Fig 3 OZz gt r ISTRUZIONI PER L INSTALLAZIONE _ A questo punto l interruttore installato correttamente possibile ora chiudere comple tamente lo sportello solo dopo aver alzato la leva in posizione Fig 4 Alla prima messa in servizio far scattare l interruttore differenziale con le apposite strumentazioni di verifica impianto ed il dispositivo in funzionamento automatico Nel caso il ciclo di riarmo non venga concluso correttamente verificare l isolamento verso terra dell impianto che deve superare i 500kQ CARATTERISTICHE TECNICHE SCHEMI D INSTALLAZIONE RD kWh Alimentazione dall alto pi mv ou ese ah Impianto utente RD Alimentazione dal basso Impianto utente kWh OZ P mr 4 GEWISS ENGLISH RESTART RD Series 90 SAFETY WARNINGS N B Read carefully before installing and using the device
7. art device not cut in Differential switch closed System powered up ED Restart device not cut in Differential switch tripped or opened intentionally System disconnected and sectioned Automatic operation be dns Restart device cut in Differential switch closed System powered up Restart device in the check for presence of a fault or E du reclosing phase Opening the hatch interrupts automatic iy reclosing making the manual manoeuvre possible red System disconnected but not sectioned Restart device blocked due to a fault in the system down Q vos stream Attempt a manual restart Call the installation tech nician if the attempt fails Differential switch tripped red System disconnected but not sectioned Key Q LED off E LED blinking LED on 20 INSTALLATION INSTRUCTIONS ASSEMBLY AND CABLING only for GW 90 971 INSTALLATION Ensure that the system is powered down before performing any operation Connect RESTART to the right hand side of differential switch SD taking particular care over inserting the pin into the hole in the differential switch handle Fig 1 push to couple them together mechanically Fig 2 The pin and the handle must be down ro rozm Fig 1 Fig 2 Install the appliances on the rail and connect the line and load cables before tightening the terminals connect
8. manualmente l impianto entro tre minuti da un precedente riarmo automatico agire sul pulsante di test dell inter ruttore differenziale previa apertura dello sportello o sugli interruttori collegati a valle INDICE e Funzioni di prodotto tttm 4 Descrizioni del 0110 5 Istruzioni per l uso coccion ninia cinco 6 Funzionamento automatico 6 Inserimento modalit 1 6 Riarmo automatico 6 Funzionamento Manuale i 7 Da automatico a manuale 7 Segnalazione dei 8 Istruzioni per l installazione 9 Montaggio e cablaggio solo per GW 90 971 9 cocci e imr 9 Caratteristiche tecniche 11 Schemi d installaziONe in 11 OZz gt r FUNZIONI DI PRODOTTO La funzione di riarmo consiste nella richiusura automatica dell interruttore differenziale in caso di sgancio intempestivo per fenomeno elettrico temporaneo fulmini perturbazioni ecc Prima di procedere all azione di richiusura il dispositivo effettua un controllo d assenza di guast
9. ne RIARMO AUTOMATICO In caso di guasto temporaneo INSERIRE dan q 1 Funzionamento normale o gt El ISERIRE CON Lig nw posizione 3 L apparecchio esegue un test dell im 4 Riarmo eseguito la leva si rialza ridando pianto di circa 60sec Spia rossa lam tensione all impianto e nei 3 minuti suc peggiante cessivi non azionabile manualmente possibile forzare manualmente la chiusura dell interruttore differenziale passando in modalit manuale ed alzando la leva Nel caso l interruttore differenziale scatti nuova mente chiamare l installatore In caso di guasto permanente OZz gt r 3 L apparecchio esegue un test dell impianto 4 Riarmo non eseguito per problemi all im di almeno 20sec Spia rossa lampeggiante pianto n 5 Per sezionare l impianto aprire lo sportello Nota procedere ad un tentativo di riarmo manuale aprendo lo sportello ed alzando la leva In caso di mancata riattivazione desistere dal continuare l opera zione di riarmo e contattare un tecnico specializzato FUNZIONAMENTO MANUALE DA AUTOMATICO A MANUALE Far scorrere lo sportello fino a sentire lo Nel caso si desideri togliere tensione scatto Impianto sotto tensione all impianto abbassare la leva INSERIRE CON posizione SEGNALAZIONE DEI LED SEGNALAZIONI LED FRONTALE DISPOSITIVO CONDIZIONE Funzionamento manuale O E
10. o a terra sul circuito a valle se viene rilevato un guasto si porta in stato di blocco altrimenti procede alla richiusura Dopo un terzo intervento dell interruttore differenziale entro tre minuti da un precedente riarmo automatico il dispositivo si porta in stato di blocco Per riabilitare la funzione di riarmo aprire lo sportello alzare la leva del l interruttore differenziale in posizione e chiudere lo sportello Se l interruttore differenziale non rimane in posizione sospendere i tentativi e chiamare un tecnico specializzato per verificare l impianto Non possibile attivare la funzione di riarmo ad interruttore differenziale aperto Per attivarla necessario alzare la leva dell interruttore differenziale in posizione e chiudere lo sportello A funzioni attivate il tasto di test e la leva dell interruttore differenziale non sono accessibili DESCRIZIONE DEL PRODOTTO Alimentazione Sinottico Led di segnalazione Led di segnalazione Sportello in posizione di funzionamento automatico x Alimentazione Sportello in posizione di funzionamento manuale Terminali di AR verifica impianto Leva di riarmo ISTRUZIONI L USO FUNZIONAMENTO AUTOMATICO INSERIMENTO MODALIT AUTOMATICA INSERIRE CON d ion gt Sn 1 Alzare la leva Far scorrere lo sportello fino a sentire lo Impianto sotto tensione scatto impianto sotto tensio
11. the RESTART line side and load side control x input wires fitting the wire DI terminals under the heads of the screws Fig 3 Fully tighten the terminals checking that both connections are locked Fig 3 21 INSTALLATION INSTRUCTIONS The switch is correctly installed at this point It is now only possible to close the hatch completely after having raised the lever to position I Fig 4 At the first start up trip the differential switch with the special system checking instrumentation and the device in automatic mode If the reset cycle is not concluded correctly check the earth insulation of the system which must be more than 500kQ 22 TECHNICAL DATA INSTALLATION DIAGRAMS RD kWh Power supply from above n User s system RD User s system Power supply from below 7 xod wa r ld LOAD kWh 23 OA