1. CA M1000735 I E ENGLISH 4 8 Rear connector IDC10 RS485 GND RS485 A Power Supply AC In the figure the meaning of the IDC10 connector pins is showed This connector can be used in alternative to the screw terminals blocks Power Supply AC RS485 B Utilizzo Accessorio Z PC DINAL2 17 5 oe DIP SWITCH Power supply AC B Power supply AC 120 Ohm terminator 7 NZE If Z PC DINAL2 17 5 accessory is used the power supply signals and communication signals may be provided by the terminals block into the DIN rail support In the figure are shown the meaning and the position of the terminal blocks The DIP switch set the 120 Q terminator is used only for CAN communication GNDSHLD Shield to protect the connection cables recommended om0000 ooo0o00 Digital Outputs Z 10 D OUT Z 10 D OUT 7 H oap 6 8 0m 7 9 048 10 LOAD 9 11 E se 1 OUTPUT gt gt SENECA Warnings OUTPUT gt gt MI000735 1 E ENGLISH 5 8 e The power supply for these loads MUST be provided directly from terminal 1 maximum 30 Vdc The return currents of the loads MUST be connected together and to the terminal 12 e The total current the sum of the maximum peak currents of all the loads that can enter from terminal 1 MUST BE LIMITED TO 5 A with quick break fuse or equivalent protection e In order to obtain recognition of the o
2. SENECA mm Serie Z PC i Z 10 D OUT LI Modulo 10 USCITE DIGITALI a MOSFET con protocollo Modbus Manuale di Installazione Contenuti Caratteristiche Generali Specifiche Tecniche Norme di connessione al Modbus Norme di installaizone Collegamenti Elettrici Impostazione DIP switch Registri Modbus di base e segnalazione tramite LED Parametri di fabbrica e impostazioni avanzate SENECA s r l Via Germania 34 35127 Z l CAMIN PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 Per i manuali e i software di configurazione visitare il sito www seneca it Questo documento di propriet SENECA srl La duplicazione e la riproduzione sono vietate se non autorizzate Il contenuto della presente documentazione corrisponde ai prodotti e alle tecnologie descritte dati riportati potranno essere modificati o integrati per esigenze tecniche e o commerciali SENECA MI000735 1 E ITALIANO 1 8 CARATTERISTICHE GENERALI e 10 uscite a MOSFET con negativo in comune da alimentare collettivamente con una tensione massima di 30 Vdc e minima di 6 Vdc e Portata massima uscita digitale 0 5 A carico resistivo e 0 5 A carico induttivo con massima frequenza di ciclo accensione spegnimento di due cicli al secondo e Morsetti estraibili sezione 2 5 mm e Uscite protette contro il cortocircuito e Impostazione di uno stato di sicurezza delle uscite all avvio o nel caso di mancata comun
3. TALIANO 4 8 Connettore Posteriore IDC10 RS485 GND Power Supply AC RS485 A Power Supply AC In figura si riporta il significato dei vari a a pin del connettore IDC10 nel caso in i cui si desideri fornire i segnali direttamente tramite esso RS485 B eo Utilizzo Accessorio Z PC DINAL2 17 5 round DIP SWITCH Nel caso di utilizzo dell accessorio Z Power supply AC Power supply AC 120 Ohm kap PC DINAL2 17 5 i segnali possono i essere forniti tramite morsettiere TEE In figura si riporta il significato dei vari NO morsetti e la posizione del DIP switch presente in tutti i supporti per guida DIN elencati in Accessori per la terminazione della rete CAN non usata nel caso di rete Modbus GNDSHLD Schermo per proteggere i cavi di connessione consigliato Uscite Digitali Z 10 D OUT Z 10 D OUT 1 25 5A _ 12 OUTPUT gt cm o gt SENECA MI000735 1 E ITALIANO 5 8 Avvertenze e L alimentazione per questi carichi DEVE essere fornita direttamente dal morsetto 1 massimo 30 Vdc ritorni dei carichi DEVONO essere collegati insieme e al morsetto 12 e La corrente complessiva somma della corrente massima di picco di ciascun carico che pu entrare dal morsetto 1 DEVE ESSERE LIMITATA a 5A con fusibile rapido o con protezione equivalente Per ottenere il riconoscimento del cortocircuito in uscita l alimentazione dei carichi deve supportare la corrente di co
4. e that will be enabled in case of lost communication for a time equal to setted safety timer Variations of standard parameters are possible by using configuration softwares Z NET and EASY Z PC www seneca it For more information about a list of all register and their function consult the USER manual Disposal of Electrical amp Electronic Equipment Applicable throughout the European Union and other European countries with separate collections programs This symbol found on your producr or on its packaging indicates X that this product should not be treated as household waste when you wish to dispose of it Instead it should be handed over to an applicable collection point for the recycling of electrical amp electronic equipment By ensuring this product is didposed of correctly you will help prevent potential negative consequences to the environment and human health which could otherwise be caused by inappropriate disposal of this product The recycling of materials fn will help to conserve natural resources For more detailed information about the recycling of the product please contact your local city office waste disposal service of the retail store where you purchased this product SENECA MI000735 1 E ENGLISH 8 8
5. gistri Nome Descrizione 10001 OUTPUT1 Come bit 0 del registro 40003 10002 OUTPUT2 Come bit 1 del registro 40003 10003 OUTPUT3 Come bit 2 del registro 40003 10004 OUTPUT4 Come bit 3 del registro 40003 10005 OUTPUT5 Come bit 4 del registro 40003 10006 OUTPUT6 Come bit 5 del registro 40003 10007 OUTPUT7 Come bit 6 del registro 40003 10008 OUTPUTS Come bit 7 del registro 40003 10009 OUTPUT9 Come bit 8 del registro 40003 10010 OUTPUT10 Come bit 9 del registro 40003 Segnalazione tramite LED LED STATO Significato dei LED PWR Acceso fisso Il dispositivo alimentato correttamente FAIL Lampeggiante Vedere impostazioni avanzate RX Lampeggiante Ricezione pacchetto avvenuta Verifica connessione Ricezione pacchetto avvenuta Acceso fisso Lampeggiante TX SENECA PARAMETRI DI FABBRICA E IMPOSTAZIONI AVANZATE Parametri di fabbrica MI000735 1 E ITALIANO 7 8 Tutti i DIP switch in OFF Protocollo Modbus Parametri di comunicazione 38400 8 N 1 Addr 1 Uscite digitali NORMALMENTE APERTE Stato di sicurezza ABILITATO Tempo di sicurezza DISABILITATO Inversione stato relay DISABILITATO Ritardo riconoscimento corto circuito fino 1s Controllo tensione di alimentazione uscite ABILITATO Impostazioni avanzate e Possibilit di mantenere costantemente monitorato il cortocircuito delle uscite previa impostazione del registro di diagnostica e Possibilit di gestione del cortocircuito tramite l uso di un timer impo
6. i stoccaggio 20 85 C Grado di Protezione P20 Connessioni Morsetti a vite sfilabili a 3 vie passo 5 08 mm Connessioni Connettore posteriore IDC10 per barra DIN 46277 Ingombri contenitore Dimensioni L 100 mm H 112 mm W 17 5 mm Contenitore PBT colore nero Isolamenti 1500 V Normative Lo strumento conforme alle seguenti normative EN61000 6 4 2002 10 emissione elettromagnetica in ambiente industriale EN61000 6 2 2006 10 immunit Digitali EN61010 1 2001 sicurezza Tutti i circuiti devono essere isolati con doppio isolamento dai circuiti sotto tensione pericolosa Il trasformatore di alimentazione deve essere a norma EN60742 Trasformatori di isolamento e trasformatori di sicurezza NOTE SUPPLEMENTARI SULL UTILIZZO Usare in ambienti con grado di inquinamento 2 L alimentatore deve essere di classe 2 Se alimentato da un alimentatore isolato limitato in tensione limitato in corrente un fusibile di portata max di 2 5 A deve essre installato in campo SENECA NORME DI CONNESSIONE AL MODBUS 1 Installare i moduli nella guida DIN max 120 2 Connettere i moduli remoti usando cavi di lunghezza appropriata Nella seguente tabella si riportano i seguenti dati relativi alla lunghezza dei cavi Lunghezza bus lunghezza massima della rete Modbus in funzione del Baud Rate Essa la lunghezza della rete che ha due moduli su cui stata inserita la terminazione del bus
7. icazione e Tempo di sicurezza impostabile da 33 ms a 2184 s e Diagnostica dei cortocircuiti e Misura della tensione di alimentazione dei carichi e Possibilit di configurazione ON LINE e Comunicazione seriale RS485 con protocollo Modbus Rtu massimo 64 nodi e Isolamento 1500 Vac delle uscite rispetto ai restanti circuiti in bassa tensione e Cablaggio facilitato dell alimentazione e del collegamento seriale per mezzo di un bus alloggiabile nella guida DIN 46277 e Inserimento ed estrazione dal bus senza interruzione della comunicazione o dell alimentazione del sistema e Tempi di comunicazione inferiori a 10 ms 38400 Baud e Distanza di collegamento fino a 1200 m e DIP Switch per settare indirizzo e Baud Rate del modulo SPECIFICHE TECNICHE Uscite Tipo di uscita a MOSFET con negativo in comune Portata uscita digitale 0 5 A carico resistivo Alimentazione esterna 30 Vdc Numero di canali 10 Massima portata corrente 0 5A sul mosfet Massima portata tensione 30 Vdc sul mosfet Massima capacit di energia h i 40 mJ con carico induttivo supportata in uscita del mosfet Tempo di risposta del mosfet SENECA 5 2 ms MI000735 1 E ITALIANO 2 8 Alimentazione 10 40 Voc 19 28 Vac 50 60 Hz Tensione Assorbimento Tipico 1 5 W Massimo 2 5 W Condizioni ambientali Temperatura 10 65 C 10 55 C UL Umidit 30 90 a 40 C non condensante Altitudine Fino a 2000 m s l m Temperatura d
8. it 0 of register 40003 10002 OUTPUT2 as bit 1 of register 40003 10003 OUTPUT3 as bit 2 of register 40003 10004 OUTPUT4 as bit 3 of register 40003 10005 OUTPUT5 as bit 4 of register 40003 10006 OUTPUT6 as bit 5 of register 40003 10007 OUTPUT7 as bit 6 of register 40003 10008 OUTPUTS as bit 7 of register 40003 10009 OUTPUT9 as bit 8 of register 40003 10010 OUTPUT10 as bit 9 of register 40003 LEDs signallings LED STATE Meaning of LEDs PWR On Power supply presence FAIL Blinking See advanced settings RX Blinking Recived data On Error connection Blinking Recived data SENECA M1000735 E FACTORY SETTING AND ADVANCED SETTING Factory settings ENGLISH 7 8 Tutti i DIP switch in OFF Modbus protocol Communication parameters 38400 8 N 1 Addr 1 Digital Outputs NORMAL OPEN Safety state ENABLE Safety timer DISABLE Reversal of status relay DISABLE Dealy short circuit recognition up to 1s Control supply voltage output ENABLE Advanced settings e Constant control of the outputs short circuit with a settable diagnostic modbus register e Control the outputs short circuit with a settable timer in the modbus register e Control and set the blinking of fail LED with a settable modbus resgister e Seta timer to regulate the time after that the output will be set in the short circuite state Seta safety timer to regulate the time that the outputs will be setin the safety state e Set the outputs safety stat
9. les who has been switched on the bus terminator see scheme 1 Drop lenght Maximum lenght of branch see scheme 1 MI000735 1 E ENGLISH 3 8 e lenght Drop mn lenght 1200 m 2m Termenator Ld i n Noce 1 Node 2 oe Bus Length Scheme 1 Lit Drop Length For the maximum performances it s recommended to use a specific schielded cable as an example BELDEN 9841 INSTALLATION RULES The module is designed to be installed in vertical position on DIN 46277 rail For the best performance and long life cycle the cables raceways and other objects in the control panel must be placed not to obstruct the slits of the module that must be ventilated Never install the modules near heat sources it s adviced the installation of the module in the lower part of the control panel Inserting on the DIN rail Inserting in the DIN rail Module As itis illustrated in the next figure 1 Insert the module IDC10 rear connnector on the DIN rail free slot the inserting is unequivocal because the connectors are polarized 2 The module can be fixed on the DIN rail through the clench of the two hooks in the lower part of it PTET DIN rail L_ ELECTRICAL CONNECTIONS Power supply and Modbus interface From IDC10 rear connector of the module or Z PC DINAL2 17 5 optional are avaiable power supply and Modbus interface In the next page are shown the use specifications of IDC10 and Z PC DINAL2 17 5 SENE
10. mum 2 5 W Environmental condition Temperature 10 65 C 10 55 C UL Humidity 30 90 a 40 C not condensing Altitude Up to 2000 m a s l Storage Temperature 20 85 C Degree protection IP20 Connections Removable 3 way screw terminals 5 08 pitch Connections Rear IDC10 connector for DIN 46277 rail Box Dimensions Dimensions L 100 mm H 112 mm W 17 5 mm Box PBT Black Isolations 1500 V Standards The module complies with the following standards EN61000 6 4 2002 10 electromagnetic emission industrial environment EN61000 6 2 2006 10 electromagnetic Output Power supply EN61010 1 2001 safety All circuits must be isolated from the other circuits under dangerous voltage with double isolation The power supply transformer must comply with EN60742 Isolated transformers and safety transformers ADDITIONAL NOTES Use in Pollution Degree 2 Environment Power Supply must be Class 2 When supplied by an Isolated Limited Voltage Limited Current power supply a fuse rated max 2 5Ashallbe installed in the field SENECA MODBUS CONNECTIONS RULES 1 Connect the module into the DIN rail max 120 2 Use a suitable lenght cable to connect the remote modules In the table below the relative data to the lenght of the bus and lenght of the cable are reported Bus lenght Maximum lenght of the Modbus network The bus lenght is determined from the lenght of network that has the two modu
11. r alla conservazione delle risorse naturali Per amm icevere ulteriori informazioni pi dettagliate Vi invitiamo a contattare l ufficio preposto nella Vostra citt il servizio per lo smaltimento dei rifiuti o il fornitore da cui avete acquistato il prodotto SENECA MI000735 1 E ITALIANO 8 8 SENECA mm Z PC Line Z 10 D OUT Modbus module with 10 MOSFET digital outputs Installation Manual Contents General specifications Technical specifications Modbus connections rules Installation rules Electrical connections DIP switches settings Modbus basic register and LEDs signallings Factory settings and advanced settings SENECA s r l Via Germania 34 35127 Z I CAMIN PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals and configuration software see www seneca it This document is property of SENECA srl Duplication and reprodution are forbidden if not authorized Contents of the present documentation refers to products and technologies described in it All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision SENECA MI000735 1 E ENGLISH 1 8 GENERAL SPECIFICATIONS e 10 MOSFET outputs with shared negative pole the outputs can be collectively connected an external supply with maximum 30 Vdc and minimum 6 Vdc e Digital output carrying capacity 0 5 A induc
12. rtocircuito senza che la tensione scenda sotto i 6 V e Le uscite digitali possono essere attivate solo se la tensione di alimentazione esterna applicata ai morsetti 1 e 12 superiore a 6 Vdc IMPOSTAZIONE DIP SWITCH La posizione dei DIP switch definisce i parametri di comunicazione Modbus del modulo Indirizzo e Baud Rate Nella tabella seguente si riportano i valori del Baud Rate e dell Indirizzo in funzione dell impostazione dei DIP switch Tabella dei dip switch POSIZIONE BAUD RATE POSIZIONE INDIRIZZO POSIZIONE TERMINATORE 00xxxxxxxx 9600 01xxxxxxxx 19200 10xxxxxxxx 38400 11xxxxxxxx 57600 xx000001xx 1 xx000010xx 2 XXXXXXXXX0_ Disabilitato XXXXXXXXX1_ Abilitato xx111111xx 63 POSIZIONE BAUD RATE POSIZIONE INDIRIZZO xx000000 Da EEprom xx000000 Da EEprom Nota Quando i DIP switch da 3 a 8 sono in OFF le impostazioni di comunicazione sono prese da programmazione EEPROM Nota 2 La terminazione della linea RS485 deve essere effettuata solamente agli estremi della linea di comunicazione SENECA MI000735 1 E ITALIANO 6 8 REGISTRI MODBUS DI BASE E SEGNALAZIONE TRAMITE LED Holding register Registro Nome Descrizione 40003 OUTPUT Lo stato dei bit di questo registro controllano le uscite Uscita 1 40003 0 Uscita 2 40003 1 Uscita 3 40003 2 Uscita 4 40003 3 Uscita 5 40003 4 Uscita 6 40003 5 Uscita 7 40003 6 Uscita 8 40003 7 Uscita 9 40003 8 Uscita 10 40003 9 Coil registers Re
13. stabile tramite il registro modbus Possibilit di impostare la modalit di lampeggio del LED fail nel registro modbus pertinente e Possibilit di impostare un timer che indica dopo quanto tempo viene riconosciuta l uscita in cortocircuito Possibilit di impostare un timer di sicurezza che imposta dopo quanto tempo le uscite vengono impostate in uno stato di sicurezza predefinito Possibilit di impostare lo stato di sicurezza delle uscite questo verr usato nel caso di mancanza di comunicazione per un tempo uguale a quello impostato nel timer di sicurezza Per qualsiasi variazione dei parametri sono disponibili nell area download del sito internet www seneca it i software di comunicazione Z NET e EASY Z PC Per maggiori informazioni riguardo la lista di tutti i registri e le loro funzioni consultare il manuale UTENTE Smaltimento dei rifiuti elettrici ed elettronici applicabile nell Unione Europea e negli altri paesi con raccolta differenziata Il simbolo presente sul prodotto o sulla confezione indica che il prodotto non verr trattato come rifiuto ye Sar invece consegnato al centro di raccolta autorizzato per il riciclo dei rifiuti elettrici ed elettronici Assicurandovi che il prodotto venga smaltito in modo adeguato eviterete un potenziale impatto negativosull ambiente e la salute umana che potrebbe essere causato da una gestione non conforme dello smaltimento del prodotto Il riciclaggio dei materiali contribui
14. tive load and 0 5 A resistive load with maximum switch on switch off cycle frequency of 2 cycles second e Removable terminals with section of 2 5 mm e Outputs protected against short circuit e Outputs safety status setting at power on and in case of lacking communication e Safety time can be set from 33 ms to 2184 s e Diagnostic for short circuits e Measurement of the load power supply voltage e Possibility of ON LINE configuration e RS485 serial communication with Modbus Rtu protocol maximum 64 nodes e 1500 Vac output isolation compared with other low voltage circuits e Easy connections for power supply and serial communication from seneca bus for standards DIN 46277 rail e Module insertion or extraction from seneca bus without interruptions for communication and power supply e Communication time below 10 ms 38400 Baud e Connection distance up to 1200 m e Set the Modbus address and the Baud rate with DIP Switch TECHNICAL SPECIFICATIONS Outputs Type output MOSFET with shared negative pole Digital output carrying capacity 0 5 A resistive load External power supply 30 Vdc Number of channel 10 Maximum rated current of 05A Mosfet i Maximum rated voltage of Mosfet 30 VDC Maximum output clamp energy 40 mJ with inductive load capability Time delay mosfet 5 2 ms GS SENECA M1000735 I E ENGLISH 2 8 Power supply 10 40 Voc 19 28 Vac 50 60 Hz Voltage Consumption Typical 1 5 W Maxi
15. utput short circuit the power supply to the loads must withstand the short circuit current without permitting the voltage to fall below 6 V e The digital outputs can be activated only for a external voltage supply higher than 6 V in the screw terminals 1 and 12 DIP SWITCHES SETTING The DIP switches positions defines the Modbus communication parameter Address and Baud rate In the following table the Baud rate and address value are listed as a function of the DIP switches position DIP switches table POSITION BAUD RATE POSITION ADDRESS POSITION TERMINATOR 00xxxxxxxx 9600 xx000001xx 1 XXXXXXXXX0 Disable 01xxxxxxxx 19200 xx000010xx 2 XXXXXXXXX1 Enable 10xxxxxxxx 38400 57600 11 XXXXXXXX xx111111xx 63 POSIZION BAUD RATE POSIZION ADDRESS xx000000 From EEprom xx000000 From EEprom Note when DIP switches from 3 to 8 are in OFF comunication settings are retrieved from EEprom Nota 2 The termination of RS485 communication must be enabled only to the ends of the communication line SENECA M1000735 I E ENGLISH 6 8 MODBUS BASIC REGISTER AND LED SIGNALLINGS Holding register Register Name Description 40003 OUTPUT Set the bit in the register to control the relative output Output 1 40003 0 Output 2 40003 1 Output 3 40003 2 Output 4 40003 3 Output 5 40003 4 Output 6 40003 5 Output 7 40003 6 Output 8 40003 7 Output 9 40003 8 Output 10 40003 9 Coil registers Registers Name Description 10001 OUTPUT1 as b
16. vedere Schema 1 Lunghezza derivazione lunghezza massima di una derivazione vedere Schema 1 MI000735 1 E ITALIANO 3 8 ona bus Lunghezza derivazione 1200 m 2m glie Linger bu Schema 1 Le Lutgharra deerme Per le massime prestazioni si raccomanda l utilizzo di cavi schermati speciali quali ad esempio il BELDEN 9841 NORME DI INSTALLAZIONE Il modulo progettato per essere montato su guida DIN 46277 in posizione verticale Per un funzionamento ed una durata ottimali assicurare un adeguata ventilazione evitando di posizionare canaline o altri oggetti che occludano le feritoie di ventilazione Evitare il montaggio dei moduli sopra ad apparecchiature che generano calore consigliabile il montaggio nella parte bassa del quadro Inserimento nella guida DIN i t II ida DIN nserimento nella guida Modulo Come illustrato in figura 1 Inserire il connettore posteriore IDC10 del modulo su uno slot libero della guida DIN l inserimento univoco essendo i connettori polarizzati 2 Per fissare il modulo nella guida DIN stringere i due ganci posti ai lati del connettore posteriore IDC10 555 Guida DIN COLLEGAMENTI ELETTRICI Alimentazione ed interfaccia Modbus Alimentazione ed interfaccia Modbus sono disponibili utilizzando il bus per guida DIN Seneca tramite il connettore posteriore IDC10 o l accessorio Z PC DINAL2 17 5 SENECA MI000735 1 E I