Modelo 8500 - Chauvin Arnoux Group

image

Contents

1. 12V 5 x 2 NiCd packs 1300mAH Panasonic P 130SCR or equivalent Battery Life Up to 10 hrs continuous operation May be used while recharging Low battery LCD indication Charging Time 14 hrs typical C 10 rate Line Fuse 115V 1 0A 5 x 20mm slow acting 230V 0 5A 5 x 20mm slow acting 23 C 5 C 50 to 70 RH full battery charge no external fields or noise Digital Transformer Ratiometer DTR Model 8500 7 3 2 Mechanical Connections Cannon XLR connectors amp large color coded industrial clips Leads 15 ft H amp X color coded in carrying bag Display Dual line alpha numeric 3 875 x 875 with contrast adjustment and backlight Operating Temperature 0 to 50 C 32 to 122 F 0 to 90 RH without condensation Case Heavy duty structural polypropylene yellow Dimensions 13 x 12 x 6 330 x 305 x 152mm Weight 14 Ib 6 4kg All specifications are subject to change without notice 3 3 Cable Identification RED BOOT H IDENTIFIER CONNECTOR CABLE SET H IDENTIFIER BLACK BOOT RED BOOT X IDENTIFIER A e S 3 PIN CONNECTOR X CABLE SET W E E X IDENTIFIER BLACK BOOT 8 Digital Transformer Ratiometer DTR Model 8500 CHAPTER 4 OPERATION A WARNING The Digital Transformer Ratiometer DTR Model 8500 is designed for use on non energized dead transformers only Make sure the test sample is completely disconnected from AC power and is fully discharged 4 1 Co
2. CHAPTER 5 MAINTENANCE Use only factory specified replacement parts AEMC will not be held responsible for any accident incident or malfunction following a repair done other than by its service center or by an approved repair center WARNING To avoid electrical shock do not perform any service other than the operating instructions contained in this manual unless you are qualified to do so Do not allow water or other foreign substances into the case Disconnect the unit from all circuits and test cables before opening the case Use caution with metallic tools that may short battery packs power supplies etc Digital Transformer Ratiometer DTR2 Model 8500 21 Repair and Calibration North South America Australia New Zealand To ensure that your instrument meets factory specifications we recommend that it be submitted to our factory Service Center at one year intervals for reca libration or as required by other standards or internal procedures For instrument repair and calibration You must contact our Service Center for a Customer Service Authorization Number CSA This will ensure that when your instrument arrives it will be tracked and processed promptly Please write the CSA on the outside of the shipping container If the instrument is returned for calibration we need to know if you want a standard calibration or a calibration traceable to N I S T Includes calibration certificate plus reco
3. transformers only Make sure the test sample is completely disconnected from AC power and is fully discharged Only qualified personnel should use the Model 8500 The DTR must not be used in a manner in which any of its com ponents including test cables are relied upon to provide protec tion from electric shock No high voltage insulation protection is provided by any component of the DTR Always make sure the circuit is fully discharged before attaching any test cables Do not touch adjust or reposition test cables while the DTR is conducting a test Use caution on any apparatus potentially high voltages and cur rents may be present and pose a shock hazard Safety is the responsibility of the user Never open the instrument while it is connected to AC power or when test cables are connected to transformers equipment circuits etc 1 1 International Electrical Symbols This symbol signifies that the instrument is protected by double or reinforced insulation Use only specified replacement parts when servicing the instrument the operator must refer to the user manual for instructions before operating the instrument Risk of electric shock The voltage at the parts marked with this 4 This symbol on the instrument indicates a WARNING that A symbol may be dangerous Digital Transformer Ratiometer DTR Model 8500 3 1 2 Receiving Your Shipment Upon receiving your shipment make sure that the contents ar
4. 4 3 CT Test Mode Flow 15 4 5 Displayed 16 4 6 Power Supply er ep bee e eid 17 4 7 Changing Power Supply Setting from 115V to 230V or 230V to 115 18 4 8 Tips for Making Precise Ratio Measurements 19 49 Ratio Tests 11 Rete ect ee oce te dece ee ez EE 19 4 10 Polyphase Connections 20 MAINTENANCE eee eernn eere nnne nnn nnn nnn nnns 21 Repair and Calibration North South America Australia New Zealand 22 Technical and Sales Assistance North South America Australia New Zealand 22 Repair and Calibration Europe Asia Africa mem te eee tera 23 Technical and Sales Assistance Europe Asia Africa ei nate ttt e e rad ei dit 23 Limited Warranty etes ettet er ead iee ii ios 24 Warranty RepallS tae aa Ee aces 24 Digital Transformer Ratiometer DTR Model 8500 CHAPTER 1 INTRODUCTION A WARNING N These safety warnings are provided to ensure the safety of personnel and proper operation of the instrument Read the instruction manual completely and follow all safety infor mation before attempting to use or service this instrument The Digital Transformer Ratiometer DTR Model 8500 is designed for use on non energized dead
5. The DTR uses a maximum 44V excitation signal for testing thus the displayed excitation current value will almost always be a small fraction of the tested transformer s no load excitation at full rated voltage Most transformers will require 100mA or less some will require less than 1mA Note If you are presently using a ratiometer that employs X side step up excitation e g common hand cranked instrument exci tation currents displayed by the DTR will in most cases be signifi cantly lower This is normal and results directly from the fact that in most step down transformers the H winding exhibits much higher impedance than its associated X winding 4 3 5 VT PT Continuity Test The Continuity Test function of the DTR Model 8500 serves as a useful means of identifying open primary and secondary windings open circuit breakers and blown fuses When selected the DTR alternately checks for continuity between its X cables and between its H cables The Continuity Test is selected when the user depresses the TEST button at the Press TEST to Check Continuity prompt The DTR will display the results of continuity checking then enter a brief degaussing period During this time the message Pre Test Checks will be displayed The DTR will indicate OPEN for tested circuits greater than 4kQ and CONT for those less than 4kO A small percentage of transformers e g those with extremely high inductance or high winding resista
6. de transporte y avise inmediatamente a su distribuidor dando una descrip ci n detallada de cualquier da o 1 3 Embalaje El instrumento puede ser embalado en dos formas dependiendo de si Ud compr una unidad con entrada para 115V 50 60Hz Cat 2111 80 o una unidad con entrada para 230V 50 60Hz Cat 2116 21 El Medidor de Raz n de Transformador Digital DTR 8500 ajustado en f brica para 115V 50 60Hz Cat 2111 80 incluye bater as NiCd ins taladas cable de alimentaci n para 115V conjunto de cables de prueba de 15 pies en un estuche de transporte tarjeta de garant a amp manual de usuario El Medidor de Raz n de Transformador Digital DTR9 8500 ajustado en f brica para 230V 50 60Hz Cat 2116 21 incluye bater as NiCd instaladas cable de alimentaci n con extremos desnudos sin enchufe conjunto de cables de prueba de 15 pies en un estuche de transporte tarjeta de garant a amp manual de usuario 28 Medidor de Raz n de Transformador Digital DTR Modelo 8500 1 3 1 Accesorios Cables de prueba 9m 30 pies en estuche de transporte Cat 2118 47 Repuesto de cables de prueba 4 5m 15 pies Cat 2118 48 Bater as de repuesto 12V NiCd conjunto de dos Cat 2118 57 Fusible conjunto de 5 0 5A 2250V 5 x 20mm acci n lenta para entrada de 230V y placa principal Cat 2118 53 Fusible conjunto de 5 1A 2125V 5 x 20mm acci n lenta
7. el circuito est totalmente descargado antes de conectar ning n cable de prueba No toque ajuste o mueva los cables de prueba mientras se est realizando una prueba con el DTR Sea precavido ante cualquier equipo puede haber altos vol tajes y corrientes que representen un peligro de choque el c trico La seguridad es responsabilidad del usuario Nunca abra el instrumento mientras est conectado a una fuente de alimentaci n AC o mientras los cables de prueba est n conectados a transformadores equipos circuitos etc Siempre inspeccione el instrumento y los cables de prueba antes de usarlos Reemplace las partes defectuosas inmedia tamente con repuestos de f brica solamente Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 27 1 1 S mbolos El ctricos Internacionales E Este s mbolo sefiala que el instrumento est protegido mediante una aislaci n doble o reforzada Al reparar el instrumento use s lo los repuestos especificados A Este s mbolo se ala CUIDADO y pide al usuario que consulte el manual de usuario antes de usar el instrumento Riesgo de choque el ctrico Los voltajes en las partes marcadas con este s mbolo pueden ser peligrosos 1 2 Recepci n De Su Embarque Al recibir su embarque aseg rese que el contenido corresponde a la gu a de despacho Avise a su distribuidor de cualquier tem faltante Si el equipo llega dafiado presente inmediatamente un reclamo a la empresa
8. s lo para unidades de 115V Cat 2118 54 Fusible conjunto de 5 4A gt 125V Cat 42118 55 5 x 20mm acci n lenta Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 29 CAPITULO 2 PRESENTACI N 2 1 Descripci n El DTR Modelo 8500 es un medidor de raz n de transformador digital port til robusto y liviano dise ado para la prueba en terreno de transformadores de potencia de voltaje y de corriente La operaci n del DTR Modelo 8500 es totalmente autom tica No requiere calibraci n selecci n de rango uso de manivela o un balanceo tedioso por parte del usuario Durante cada ciclo de prueba el DTR autom ticamente comprueba Inversi n de los cables H X e Continuidad de los circuitos espiras bajo prueba Condiciones de cortocircuito alta corriente Al completar un ciclo de prueba el DTR presenta Raz n de Espiras la raz n entre voltaje primario y secundario en los terminales del transformador producida por la excitaci n de prueba Corriente de Excitaci n La corriente de excitaci n RMS en el bobinado H producida por la excitaci n de prueba durante una carga despreciable del bobinado X asociado Polaridad Indica la polaridad fase de X relativa a H La Raz n de Espiras Corriente de Excitaci n y Polaridad son par metros tiles para diagnosticar y predecir una variedad de fallas que se presentan en los transformadores de potencia de volt
9. 3 742 2346 or 603 749 6309 repair aemc com Contacte su distribuidor autorizado El coste por reparaci n calibraci n est ndar y calibraci n N I S T est n disponibles NOTA Todos los clientes deber n obtener el CSA antes de devolver el instrumento Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 47 5 2 Asistencia t cnica y venta Si tiene cualquier problema t cnico o requiere de ayuda para una ope raci n o aplicaci n determinada con el instrumento por favor ll menos correos fax o e mail a nuestro servicio t cnico Chauvin Arnoux Inc d b a AEMC Instruments 200 Foxborough Boulevard Foxborough MA 02035 USA Phone 508 698 2115 Fax 508 698 2118 E mail techsupport aemc com NOTA No mande el instrumento a nuestra direcci n de Foxborough MA 5 3 Garant a Limitada El Modelo DTR 8500 esta garantizado por el periodo de un a o desde la fecha de su adquisici n y solamente por defectos de fabricaci n Esta garant a limitada es dada por AEMC Instruments no por el distribuidor al cual fue comprado el instrumento Esta garant a puede ser cancelada si la unidad a sido mal tratada o defectuosa por uso indebido o por reparacio nes no efectuadas por nuestro servicio t cnico de AEMC Instruments Para un mayor detalle de la cobertura de la garant a y registracion vaya a www aemc com Que puede hacer AEMC Si el mal funcionamiento ocurre durante el periodo del afio deber devolver la unid
10. Accessories and Replacement Parts Directly Online Check our Storefront at www aemc com for availability 4 Digital Transformer Ratiometer DTR Model 8500 CHAPTER 2 PRODUCT FEATURES 2 4 Description The DTR Model 8500 is a lightweight rugged portable digital transformer ratiometer designed for onsite testing of power potential and current trans formers Operation of the Model 8500 is fully automatic No user calibra tion range selection hand cranking or tedious balancing is required During each test cycle the DTR automatically checks for lead reversal Continuity of tested circuits windings Short circuit conditions high current Upon completion of a test cycle the DTR displays Turns Ratio the ratio of the primary to secondary voltage at the transformer terminals due to test excitation Excitation Current the RMS excitation current in the H winding due to test excitation during negligible loading of the associated X winding Polarity indicates the polarity phase of X relative to H Turns Ratio Excitation Current and Polarity are useful parameters in diag nosing and predicting a variety of faults that occur in power potential and current transformers The Model 8500 will display the following messages Incorrect Lead Connections H XReversal accidental step up misconnection Short excess excitation current Open Circuits Circuit Continuity Low Battery A The DTR utiliz
11. El DIGITAL TRANSFORMER RATIOMETER El MEDIDOR DE RAZ N DE TRANSFORMADOR DIGITAL User Manual Manual de Instrucciones INSTRUMENTS Statement of Compliance Chauvin Arnoux Inc d b a AEMCS Instruments certifies that this instrument has been calibrated using standards and instruments traceable to international standards We guarantee that at the time of shipping your instrument has met its published specifications An NIST traceable certificate may be requested at the time of purchase or obtained by returning the instrument to our repair and calibration facility for a nominal charge The recommended calibration interval for this instrument is 12 months and begins on the date of receipt by the customer For recalibration please use our calibration services Refer to our repair and calibration section at www aemc com Serial Catalog 2111 80 2116 21 Model 8500 115V 8500 230V Please fill in the appropriate date as indicated Date Received Date Calibration Due Chauvin Arnoux Inc d b a AEMC Instruments INSTRUMENTS www aemc com Lee oa a e o gt Table of Contents Digital Transformer Ratiometer DTR Model 8500 ENGLISA cok epe de ep ee UE tas 1 ESPA OL costat oe bo tutatus t LAINE DO EE 25 1 INTRODUCTION 3 1 1 International El
12. ITULO 5 MANTENIMIENTO Para su mantenimiento use s lo repuestos especificados de f brica Evite choque el ctrico no intente realizar ning n servicio si no est calificado para hacerlo Evite choque el ctrico y o da o al instrumento no permita que entre agua u otras sustancias extrafias a la carcasa Desconecte la unidad de todos los circuitos y cables de prueba antes de abrir la carcasa Tenga cuidado con las herramientas met licas que pueden corto cir cuitar las bater as fuentes de poder etc 5 1 Reparaci n y Calibraci n Para asegurar que su instrumento cumple las especificaciones de la empresa recomendamos que se mande a nuestro Servicio T cnico en intervalos de un afio para recalibrarlos o por requerimientos de otro est ndar o procesos internos Para reparaci n o calibraci n de instrumentos Deber contactar con nuestro Centro de Servicios para obtener el Numero de Autorizaci n del Servicio al Cliente CSA Este asegurara que cuando recibamos el instrumento ser procesado r pidamente Por favor escriba el CSA por fuera del embalaje Si el instrumento es mandado para calibraci n necesitamos saber el modelo de calibraci n que desea calibraci n est ndar o calibraci n para N I S T Incluye certificado de calibraci n mas la informa ci n recogida al ser calibrado Chauvin Arnoux Inc d b a AEMC Instruments 15 Faraday Drive Dover NH 03820 USA Tel 603 749 6434 Ext 360 Fax 60
13. SECONDARY 7200 240CT e NR H RED H BLACK H BLACK H I X BLACK Note Unlike other instruments the DTR Model 8500 does not impose polarity restrictions or forced auto connections thus there are several valid hookups and virtually all transformer configu rations can be tested In all tests a negative sign preceding the displayed ratio indicates phase reversal inverted polarity of the sensed X signal relative to the excitation signal at H In using the DTRS always note the color code of test cable boots 10 Digital Transformer Ratiometer DTR Model 8500 4 3 2 VT PT Testing 1 When the instrument is set for VT PT testing the DTR will display the VT PT Test Mode Ready message after the initial power up sequence This message indicates that the DTR is now ready to execute a test 2 Press the TEST button once WARNING The test should not be performed while personnel are handling transformer connections 3 Press TEST to Check Continuity is now displayed for three 3 seconds If a continuity test is desired the TEST button should be pressed once at this time The results of continuity testing will be displayed as CONT or OPEN for both X and H connections Refer to VT PT Continuity Test page 12 for more information 4 The next message displayed is Ratio Testing TEST to Cancel The asterisk will blink as testing proceeds Testing may be cancelled at this time
14. a prueba de Continuidad queda seleccionada cuando el usuario pulsa el bot n TEST ante el mensaje Press TEST to Check Continuity El DTR mostrar los resultados de la prueba de continuidad entrando luego en un breve periodo de desgaussiado desmagnetizaci n Durante este tiempo se mostrar el mensaje Pre Test Checks EIDTR indicar OPEN abierto para los circuitos probados con m s de 4KO y CONT continuo para aquellos con menos de 4KO Un pequefio porcentaje de transformadores por ejemplo aquellos con inductancia extremadamente alta o bobinados de alta resistencia pueden aparecer como un circuito abierto para el DTR La indicaci n OPEN no cancelar el ciclo de la prueba en curso y se mostrar n los resultados de la prueba de raz n de todos modos e Transformadores cuya disposici n de los bobinados contiene caminos paralelos m ltiples por ejemplo tipos con conexi n Delta pueden dar la lectura CONT cuando en realidad uno o m s de los bobinados pueden estar abiertos 38 Medidor de Raz n de Transformador Digital DTR Modelo 8500 44 CT 4 4 1 Ejemplo de Conexi n CT La prueba de raz n en Transformadores de Corriente CT se realiza conectando el conjunto de cables de prueba H al bobinado X y uniendo en corto el conjunto de cables de prueba X a trav s de la abertura CT como se ilustra abajo Esto crea una configuraci n de baja de voltaje en que el bobinado X sirve de circuito primario y el conjunto de cabl
15. aci n Caja Polipropileno estructural amarillo para trabajo pesado Dimensiones 13 x 12 x 6 330 x 305 x 152 mm Peso 14 Ibs 6 4kg Todas las especificaciones y precios pueden variar sin previo aviso 3 3 Identificaci n de Cables Capuch n Rojo Identificador H Conector de 5 Patas conn de Cables H t Identificador H Capuch n Negro Capuch n Rojo Identificador X Mie Conector de 3 Patas E A Conjunto de Cables X 3 BR El Identificador X Capuch n Negro Medidor de Raz n de Transformador Digital DTR Modelo 8500 33 CAPITULO 4 UTILIZACI N ADVERTENCIA El Medidor de Raz n de Transformador Digital DTR Modelo 8500 est dise ado para ser usado en transformado res no energizados solamente Aseg rese que el equipo a probar est completamente desconectado de la fuente de alimentaci n AC y est totalmente descargado 4 1 Para realizar una prueba 1 Conecte los cables de prueba del DTR a un transformador no ener gizado de manera adecuada Refi rase a Ejemplos de Conexi n 84 3 1 and 84 4 1 2 Encienda el DTR y seleccione el modo de prueba adecuado Refi rase a Selecci n de Modo m s abajo 3 Cuando aparezca Ready pulse el bot n de prueba TEST para comenzar Luego de un breve ciclo de comprobaci n se mostrar n Raz n Polaridad y Corriente de Excitaci n Para informaci n completa de la operaci n
16. ad a nosotros para reparaci n sin costo alguno aseg rese de mandarnos la Tarjeta de Registro AEMC Instruments podr decidir reparar la unidad o reemplazarla 5 4 Garant a de Reparaci n Que debe hacer para devolver el instrumento para ser reparado bajo la garant a Primero adquiera el Numero de Autorizaci n del Servicio al Cliente CSA por tel fono o por fax desde nuestro Departamento de Servicios ver direcci n adjunta despu s devuelva el instrumento con la autorizaci n CSA firmada Por favor escriba el CSA en el exterior del embalaje Devuelva el instru mento con los portes y seguros prepagados a Chauvin Arnoux Inc d b a AEMC Instruments Service Department 15 Faraday Drive Dover NH 03820 USA Tel 603 749 6434 Ext 360 Fax 603 742 2346 or 603 749 6309 E mail repairQaemc com Advertencia Para protegerse usted mismo por perdida del instrumento en transito le recomendamos que lo asegure NOTA Todos los clientes deber n obtener el CSA antes de devolver el instrumento 48 Medidor de Raz n de Transformador Digital DTR Modelo 8500 E AEMC INSTRUMENTS 08 08 99 MAN 100150 v8 Chauvin Arnoux Inc d b a AEMC Instruments 15 Faraday Drive Dover NH 03820 USA Phone 603 749 6434 Fax 603 742 2346 www aemc com
17. aje y de corriente EI DTR Modelo 8500 presentar los siguientes mensajes Conexi n Incorrecta de los Cables de Prueba Inversi n H X malconexi n accidental de elevaci n de voltaje Corto exceso de corriente de excitaci n Circuitos Abiertos Continuidad de Circuito Bater a Baja EI DTR utiliza una avanzada t cnica de medici n de bajo voltaje por disminuci n de voltaje en que el bobinado de alto voltaje H se somete a la excitaci n de prueba Esto se traduce en una mayor seguridad para el operador y en una habilidad para probar una gama m s amplia de tipos y tama os de transformadores 30 Medidor de Raz n de Transformador Digital DTR Modelo 8500 2 2 Descripci n del Aparato c TRANSFORMER RATIO MODEL 8500 Display Indicador de Carga de la Bater a Entrada de Alimentaci n AC Porta Fusible de Alimentaci n Ajuste de Contraste del Display Bot n Pulsador de PRUEBA Interruptor de Alimentaci n Conector de Cable X lado bajo secundario Rom Conector de Cable lado alto primario Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 31 CAPITULO 3 ESPECIFICACIONES 3 1 Electricas C Rango de Razones Autorango 0 8000 a 1500 0 1 Exactitud Raz n 10 a 1 0 2 de Lectura Raz n x 10 a 1000 a 1 0 196 de Lectura Raz n 1000 a 1 0 296 de Lectura Sefial de Excitaci n Modo PT VT 44Vrms m ximo Modo CT Nivel Autom
18. anumesure Reux 14130 Pont l Ev que France Tel 33 2 31 64 51 43 Fax 33 2 31 64 51 09 www chauvin arnoux com Or contact your authorized distributor Technical and Sales Assistance Europe Asia Africa If you are experiencing any technical problems or require any assistance with the proper use or application of this instrument please contact CHAUVIN ARNOUX SCA 190 rue Championnet 75876 Paris Cedex 18 France Tel 33 1 44 85 44 57 Fax 33 1 46 27 95 59 www chauvin arnoux com Digital Transformer Ratiometer DTR Model 8500 23 Limited Warranty The Model 8500 is warranted to the owner for a period of one year from the date of original purchase against defects in manufacture This limited warranty is given by AEMC Instruments not by the distributor from whom it was purchased This warranty is void if the unit has been tampered with abused or if the defect is related to service not performed by AEMC Instruments For full and detailed warranty coverage please read the Warranty Cov erage Information which is attached to the Warranty Registration Card if enclosed or is available at www aemc com Please keep the War ranty Coverage Information with your records What AEMC Instruments will do If a malfunction occurs within the one year period you may return the instrument to us for repair provided we have your warranty registration information on file or a proof of purchase AEMC I
19. by pressing the TEST button once If the test continues Ratio and Excitation current will be displayed 5 Once test results are recorded press the TEST button to reset for the next test This routine may be repeated as many times as needed without powering down the unit Digital Transformer Ratiometer DTR Model 8500 11 4 3 3 VT Test Mode Flow Chart Display Indication Operator for Mode Action Version XXX 1999 Turn Unit On Indicates version of Chauvin Arnoux Internal Firmware AEMC Instruments e N A DTR Model 8500 m N A soa Model Identification Replaces Above Indication B N A xx when Batteries Need ow i ery Recharging PT VT Test Mode no N A mem Indication of Selected Mode Calibrating m NA m Internal Calibraiton Please Wait in Progress VTIPT Test Mode Push TEST Now System Ready to Ss Ready to Initiate Testing Begin Testing Comments Test Cancel Option Push TEST Now er to Check Continuity m DC t BE Inuity or do nothing to skip pion ogs Ratio Testing Pushi TEST Now Ratio Testing to Cancel TEST to Cancel in Progress with Test in Progress Push TEST Now to Reset for Next Test Ratio 60 00 1 Current 11 mA 12 Digital Transformer Ratiometer Model 8500 4 3 4 VT PT Excitation Current Excitation Current displayed in milliamperes is the RMS current in the H winding due to test excitation during negligible loading of the associated X winding
20. che Cada vez que el DTR se conecta a la energ a AC comienza un ciclo de recarga de 14 horas Repetidas recargas de bater as parcialmente descargadas no produce 42 Medidor de Raz n de Transformador Digital DTR Modelo 8500 dafio a las bater as Durante el ciclo de 14 horas el indicador CHARGING estar encendido permanentemente luego de este periodo se entra en un modo de carga de mantenci n pulsada y el indicador se encender y apagar pulsadamente 4 7 Cambiar el Voltaje de la Fuente de Poder de Cuerpo Negro Interruptor Rojo Posici n de Ajuste a 115V 115V a 230V o de 230V a 115V Alimentaci n Fusible Selector de Voltaje de Alimentaci n Etiqueta del Voltaje de Entrada coincidente con el ajuste del Voltaje de alimentaci n Interruptor Encendido Apagado Paquete de Bater as Posici n de Ajuste a 230V El voltaje de la fuente de poder del instrumento puede ser cambiado de 115 a 230 volts mediante el siguiente procedimiento 1 ov d com Apague el instrumento Desconecte el instrumento de la l nea y de todas sus entradas Suelte los cuatro tornillos en su base Extraiga el instrumento de la carcasa Localice el interruptor cerca del transformador vea el dibujo Coloque el interruptor rojo en 115V o en 230V seg n corresponda La posici n del interruptor indica el voltaje de l nea seleccionado Reemplace el fusible por uno del valor de corriente apropiado vea la entrada de a
21. dor omentarios Encienda la Unidad Indica versi n Version 1997 pm con el Bot n del Programa de Chauvin TEST Presionado Instrucciones Interno AEMC Instruments Mantenga el Bot n Identificaci n DTR Model 8500 TEST Presionado del Modelo Y Reemplaza el Mensaje de A AEMC Instruments Mantenga el Bot n Arriba cuando las Low Battery TEST Presionado Bater as Necesitan Y ser Recargadas CT Test Mode m Suelte el Bot n TEST s Indicaci n del Modo Seleccionado Calibrating NA H Calibraci n Interna Please Wait en Curso Y Sistema Listo CT para eaey a Comenzar la Prueba r Pulse TEST Ahora Prueba de Raz n en Ratio Testing TEST to Cancel para Cancelar la Curso con la Opci n i Prueba en Curso de Cancelar la Prueba Pulse TEST Ahora para Ratio 40 00 1 Current 35 mA Reiniciar para la Pr xima Prueba 40 Medidor de Raz n de Transformador Digital DTR Modelo 8500 4 5 Mensajes Mostrados Check for H lt gt X Cable Reversal Compruebe Inversi n de los Cables H lt gt X El DTR puede haber detectado una condici n de elevaci n de voltaje potencialmente peligrosa al intentar probar el transformador tal como est conectado Compruebe las conexiones HRoJo amp deber an estar conectados al bobinado de alto voltaje 8 XNEGRO deber an estar conectados al bobinado de bajo voltaje High Excitation Current Alta Corriente de Excitac
22. e la secuencia de encendido CT Test Mode Ready Modo de Prueba CT Listo Indica que el sistema est listo para la prueba CT X Circuit OPEN or CONT Circuito X ABIERTO CONTINUO Refi rase a la secci n Prueba de Continuidad VT PT H Circuit OPEN or CONT Circuito H ABIERTO o CONTINUO Refi rase a la secci n Prueba de Continuidad VT PT Low X Signal Sefial X Baja Revise los cables X por posibles cortocircuitos inadvertidos El bobinado X puede estar en corto o el desconectador del transformador puede estar abierto Low H Signal Se al H Baja Revise los cables H por posibles cortocircuitos inadvertidos Revise los conectores de cables H en el panel frontal del DTR 4 6 Alimentaci n El DTR Modelo 8500 puede ser usado hasta 10 horas con bater as NiCd totalmente cargadas El DTR tambi n puede ser alimentado desde la l nea durante las mediciones En este modo el DTR tambi n recarga las bater as NiCd LOW BATTERY BATERIA BAJA se presenta cuando las bater as inter nas se aproximan a un voltaje bajo Cuando se presenta todav a se puede realizar un n mero limitado de mediciones aunque recomendamos recar gar el DTR lo antes posible Si el voltaje de la bater a cae muy bajo el DTR bloquea cualquier operaci n ulterior En este modo bloqueado el DTR apaga todas las funciones hasta que se conecta a la energ a AC y se recarga la bater a Recomendamos recargar el DTR durante la no
23. e consis tent with the packing list Notify your distributor of any missing items If the equipment appears to be damaged file a claim immediately with the carrier and notify your distributor at once giving a detailed description of any damage Save the damaged packing container to substantiate your claim 1 3 Ordering Information Digital Transformer Ratiometer Model 8500 115 Cat 2111 80 Includes ratiometer factory preset 115V 50 60Hz input NiCd batteries installed 115V power cord set of 15 ft cables in a carrying bag warranty card and user manual Digital Transformer Ratiometer Model 8500 230V Cat 2116 21 Includes ratiometer factory preset 230V 50 60Hz input NiCd batteries installed power cord with stripped end no receptacle plug set of 15 ft cables in a carrying bag warranty card and user manual 1 3 1 Accessories and Replacement Parts Test lead set 30 ft in carrying bag Cat 2118 47 Replacement set of test leads 15 Cat 2118 48 Replacement 12V NiCd batteries set of two Cat 42118 57 Fuse set of 5 5 2250 Cat 42118 53 5 x 20mm slow acting for 230V power input and main board F se set of 5 4A72425W 2 Dau Cat 42118 54 5 x 20mm slow acting for 115V unit only Fuse set of 5 4A 7125V iit ee ie te Cat 42118 55 5 x 20mm slow acting Order
24. e high voltage winding XRED XBLACR should be attached to the low voltage winding High Excitation Current Check test cable connections for inadvertent short circuits Check for shorted transformer windings Check Cables amp Connections Verify that all test cable connections have been made correctly and are firmly attached to the transformer terminals Inspect transformer terminals for dielectric coatings fungus and corrosion Low Battery Low battery indication Recharge the batteries immediately Note The DTR can be operated during battery charging Calibrating Please Wait The DTR always self calibrates upon power up The DTR will also automatically self calibrate atperiodic intervals after 32 sequential test cycles have been performed following the detection of any error in which the DTR automati cally cancels the test in progress VT PT Test Mode Operation mode used in VT PT testing power up default mode VT PT Test Mode Ready Indicates system ready for VT PT testing CT Test Mode Selected Indicates user selection of CT Test Mode Mode selected by depressing and holding TEST button during power up sequence 16 Digital Transformer Ratiometer Model 8500 CT Test Mode Ready Indicates system ready for CT testing X Circuit OPEN or CONT Refer to the VT PT Continuity Test section H Circuit OPEN or CONT Refer to the VT PT Continuity Test section Low X Signal Check X cables for inadverten
25. ectrical 3 1 2 Receiving Your 4 1 3 Ordering 4 1 3 1 Accessories and Replacement Parts 4 2 PRODUCT FEATURES 5 2 4 Description ona teret dte tete yE a dee eee eR ua ss 5 2 2 Control 5 6 3 SPECIFICATIONS 7 3 1 Electrical a te eed tite 7 3 2 Mechanical Ginnie Debe ge 8 3 3 Cable Identification 8 4 OPERATION aa a A 9 4 1 Conducting a Test aee 9 4 2 Mode 9 43 NT PR E PEN 10 4 3 1 VT PT Example Connections 10 43 2 VTPT Testing eet etel 11 4 3 3 Test Mode Flow 12 4 3 4 VT PT Excitation Current 13 4 3 5 VT PT Continuity Test 13 A A A 14 4 4 1 CT Example Connections 14 442 CT Testing ee C ER data 14 4
26. es an advanced low voltage step down measurement technique in which the high voltage H winding is subjected to test excitation This results in greater operator safety and the ability to test a much wider array of transformer types and sizes Digital Transformer Ratiometer DTR Model 8500 5 2 2 oN Oa Rom Control Features c TRANSFORMER RATIO MODEL 8500 Display Battery Charge Indicator AC Power Inlet Line Fuse Tray Display Contrast Adjustment TEST Push button Main Power Switch Low side X cable connector secondary High side H cable connector primary Digital Transformer Ratiometer DTR Model 8500 CHAPTER 3 SPECIFICATIONS 3 1 Electrical Ratio Range C Autoranging 0 8000 to 1500 0 1 Accuracy Ratio 10 to 1 0 296 of Reading Ratio lt 10 to 1000 to 1 0 1 of Reading Ratio 2 1000 to 1 0 296 of Reading Excitation Signal PT VT Mode 44Vrms maximum CT Mode Auto Level 0 to 1A 0 1 to 5Vrms Excitation Current Display Range 0 to 1000mA Accuracy 2 2mA Excitation Frequency 70Hz Display LCD Character 20 x 2 large format LED backlight day night visible Measurement Method In accordance with ANSI IEEE C57 12 90 Power Supply Dual operation rechargeable NiCd battery amp 115 230V 50 60Hz line supply DTR may be changed from 115 230V by internal switch at any time Units available with factory presetting of 115V or 230V Batteries
27. es de prueba X hace de bobinado secundario de una vuelta TRANSFORMADOR DE CORRIENTE X NEGRO 4 4 2 Prueba CT 1 Cuando el instrumento est ajustado para una prueba CT el DTR mostrar el mensaje CT Test Mode Selected despu s de la secuen cia de encendido inicial Este mensaje indica que el DTR est listo para realizar una prueba 2 Pulse una vez el bot n TEST para comenzar el ciclo de prueba 3 El siguiente mensaje que se presenta es Ratio Testing TEST to Cancel Prueba de Raz n TEST para Cancelar El asterisco va a parpadear mientras dura la prueba La prueba puede ser cance lada en este momento pulsando una vez el bot n TEST Si la prueba contin a se mostrar la Raz n y la Corriente de Excitaci n 4 Una vez que los resultados de la prueba han sido registrados pulse el bot n TEST para reiniciar para la pr xima prueba A NOTA Hay CTs de baja masa de baja raz n donde el DTR puede no ser capaz de proporcionar la raz n correcta El mensaje de error ser High Excitation Current alta corriente de excitaci n Al igual que en el Modo de Prueba VT PT esta rutina puede ser repe tida tantas veces como sea necesario sin apagar la unidad El Modo de Prueba CT permanece activo hasta que se apaga la unidad Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 39 4 4 3 Diagrama de Flujo del Mode de Prueba CT Mensaje del Display Acci n del Para el Modo PT CT Opera
28. i n Revise las conexiones de los cables de prueba por posibles cortocircuitos inadvertidos Revise cortocircuitos en los bobinados del transformador Check Cables amp Connections Revise Cables amp Conexiones Revise que todas las conexiones de los cables de la prueba han sido hechas correctamente y est n unidas firmemente al transformador Inspeccione los terminales del transformador por posibles recubrimientos con diel ctricos hongos y corrosi n Low Battery Bater a Baja Indicaci n de bater a baja Recargue las bater as inmediatamente Nota El DTR puede ser operado durante la recarga de las bater as Calibrating Please Wait Calibrando Por Favor Espere EI DTR siempre se autocalibra luego de encendido El DTR tambi n se autocalibra e aintervalos peri dicos e despu s que se han completado 32 ciclos de prueba secuenciales e luego de detectar cualquier error en que el DTR autom ticamente cancela la prueba en curso VT PT Test Mode Modo de Prueba VT PT Modo de operaci n utilizado en las pruebas VT PT modo preestablecido al encender VT PT Test Mode Ready Modo de Prueba VT PT Listo Indica que el sistema est listo para la prueba VT PT Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 41 CT Test Mode Selected Modo de Prueba CT Seleccionado Indica la selecci n del Modo de Prueba CT por el usuario Este modo se selecciona presionando y manteniendo presionado el bot n TEST durant
29. i n td AS 30 2 2 Descripci n del 31 3 ESPECIFICACIONES 32 331 DENS CUNGAS d usse tette ert 32 3 2 tub edge b cue vua 33 3 3 Identificaci n de Cables sss 33 4 UTIIZAGI N ia 34 4 1 Para realizar una prueba 34 4 2 Selecci n de 34 43 NTP A EE ESA 35 4 3 1 Ejemplos de Conexiones VT PT 35 43 2 Prueba VT PT iiie tate tt ctt eee tees 36 4 3 3 Diagrama de Flujo del Modo de Prueba VT PT 37 4 3 4 Corriente de Excitaci n VT PT 38 4 3 5 Prueba de Continuidad VT PT 38 AA UO Tui ttai eb Niel o e e O 39 4 4 1 Ejemplo de Conexi n CT 39 442 Prueba eet e ed debes 39 4 4 3 Diagrama de Flujo del Mode de Prueba CT 40 4 5 Mensajes 5 41 4 6 Alimentaci n i ra pe de nd 42 4 7 Cambiar el Voltaje de la Fuente de Poder de 115V a 230V o de 230V a 115 43 4 8 Consejos para Hacer Mediciones de Raz n Precisas 44 Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 25 26 4 9 Prueba de Raz n 1 1 esses 45 4 10 Po
30. idor de Raz n de Transformador Digital DTR2 Modelo 8500 37 4 3 4 Corriente de Excitaci n VT PT La Corriente de Excitaci n mostrada en miliamperes es la corriente RMS en el bobinado H causada por la excitaci n de prueba durante una carga despreciable del bobinado X asociado El DTR usa para las pruebas una sefial de excitaci n de 44V m ximo luego el valor de la corriente de excitaci n mostrado ser casi siempre una peque a fracci n de la excitaci n sin carga del transformador bajo prueba a un voltaje nominal total La mayor a de los transformadores requerir n 100mA o menos algunos requerir n menos de 1mA Nota Si Usted actualmente est usando un medidor de raz n que emplea una excitaci n por elevaci n de voltaje en el lado X ejem plo instrumentos de manivela corrientes la corriente de excitaci n mostrada por el DTR ser en la mayor a de los casos significati vamente menor Esto es normal y se produce directamente por el hecho que en la mayor a de los transformadores que bajan voltaje el bobinado H presenta una impedancia mucho m s alta que su bobinado X asociado 4 3 5 Prueba de Continuidad VT PT La funci n de Prueba de Continuidad del DTR Modelo 8500 sirve como un medio til para identificar bobinados primarios y secundarios abiertos desconectadores abiertos y fusibles quemados Cuando se lo selecciona el DTR comprueba alternativamente la continuidad de sus cables X y de sus cables H L
31. la On Off Switch Battery Pack Power Supply Voltage Selector Black Body Red Switch 115 V Setting Position 230 V Setting Position Ea Switch Position for Power Su i 15V 20 3909 The instrument s power supply setting can be changed from 115 to 230V by following the procedure below 1 Turn the power OFF and unplug instrument from all inputs and power Unscrew all four bottom screws Remove instrument from case Locate switch next to transformer see drawing gu Re seo OMS Set red switch 115V or 230V as appropriate Switch setting indicates the selected supply voltage 6 Replace the fuse see power inlet with appropriate current rating 115V 1A 230V 0 5A 7 Carefully reinstall instrument into the case and fasten bottom screws 8 Remove old voltage label Affix input voltage label 115V or 230V under the AC power inlet 18 Digital Transformer Ratiometer Model 8500 4 8 Tips for Making Precise Ratio Measurements NOTE The DTR is designed to test step down transformers It works with low voltage on the primary limited to 40V max If the secondary reaches 40V before the primary a safety feature stops the mea surement The recommended procedure to test step up transform ers is to reverse the low and high leads and read the reverse ratio Always verify the integrity of test cable connections and reposition test clips as necessary Inspect transformer terminals for dielect
32. lado primario extremadamente alta No se requiere en la mayor a de los transformadores de derivaci n variable ni en los reguladores Al probar transformadores polif sicos tenga en mente que en algunos casos las razones medidas deben ser multiplicadas o divididas por 13 Refi rase al 4 10 para los diagramas de conexiones polif sicas y las ecuaciones de raz n asociadas Medidor de Raz n de Transformador Digital Modelo 8500 4 9 Prueba de Raz n 1 1 Se puede hacer una prueba sencilla para ensayar el funcionamiento del DTR Al conectar HRoJo a XroJo y separadamente HNEGRO a XNEGRO se simula un transformador 1 1 Al operar el DTR con esta configuraci n se deber a obtener una raz n casi igual a 1 000 Si no se obtiene el DTR puede necesitar reparaci n o calibraci n H ROJO X ROJO 1 1 H NEGRO X NEGRO CONEXIONES EQUIVALENTE Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 45 4 10 Polyphase Connections TRANSFORMADOR BOBINADO BOBINADO TIPO BOBINADO DE BOBINADO DE VOLTAJE VOLTAJE VOLTAJE ALTO VOLTAJE BAJO ALTO BAJO 12 AA X X A A STD X A A REV X A Y STD A Y REV H Y Y POH STD I Y Y REV Y A STD A cH H X YN N Hl x H X a AM H A H Xo H B 4 N H A H H B C H X B H H Y REV B 2 3 46 Medidor de Raz n de Transformador Digital DTR Modelo 8500 CAP
33. limentaci n 115V 1 A 230V 0 5A Reinstale cuidadosamente el instrumento en la carcasa y asegure los tornillos de su base Remueva la etiqueta con el antiguo voltaje Coloque una etiqueta con el nuevo voltaje de entrada 115V o 230V debajo de la entrada de alimentaci n AC Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 43 4 8 Consejos para Hacer Mediciones de Raz n Precisas NOTE El DTR est dise ado para probar transformadores que bajan voltaje Opera con bajo voltaje en el primario limitado a 40V m ximo Si el secundario alcanza 40V antes que el primario un dispositivo de seguridad detiene la medici n El procedimiento recomendado para probar transformadores que elevan voltaje es invertir los terminales de baja y de alta y leer la raz n inversa 44 Siempre verifique la integridad de las conexiones de los cables de prueba y reubique las pinzas de prueba si es necesario Inspeccione los terminales del transformador por posibles recubrimientos diel ctri cos hongos y corrosi n Durante el Modo de operaci n VT PT seleccione Continuity Test Prueba de Continuidad cuando sea posible Adem s de ser una manera til de probar bobinados y conexiones esta prueba tiene el beneficio adicional de disminuir el magnetismo remanente en el trans formador bajo ensayo Esto es importante primeramente en transfor madores con una alta resistencia en serie y en transformadores de bajo KVA con una inductancia del
34. lyphase 46 MANTENIMIENTO 47 5 1 Reparaci n Calibraci n 47 5 2 Asistencia t cnica y venta 48 5 3 Garant a Limitada ieri ii 48 5 4 Garant a de Reparaci n 48 Medidor de Raz n de Transformador Digital Modelo 8500 CAPITULO 1 INTRODUCCI N ZN ADVERTENCIA N Estas advertencias de seguridad se entregan para garantizar la seguridad del personal y la operaci n adecuada del instrumento Lea el manual de instrucciones completamente y siga toda su informaci n de seguridad antes de intentar usar o reparar este instrumento El Medidor de Raz n de Transformador Digital DTR Modelo 8500 est dise ado para ser usado en transformadores no energizados solamente Aseg rese que el equipo a probar est completamente desconectado de la fuente de alimenta ci n AC y est totalmente descargado S lo personal calificado deber a usar el Modelo 8500 El DTR no debe ser usado confiando en que cualquiera de sus componentes incluyendo los cables de prueba proporciona protecci n contra un choque el ctrico Ninguno de los compo nentes del DTR proporciona protecci n aislaci n contra alto voltaje Siempre aseg rese que
35. nce may appear as open circuits to the DTR An OPEN indication will not cancel the test cycle in progress and the results of ratio testing will still be displayed Transformers whose winding arrangement involves multiple parallel paths e g Delta connected types may read CONT when in fact one or more windings may be open Digital Transformer Ratiometer DTR Model 8500 13 44 CT 4 4 1 CT Example Connections Current Transformer CT ratio testing is performed by connecting the H cable set to the X winding and by shorting the X cable set through the CT aperture as depicted below This creates a step down configuration in which the X winding serves as the primary circuit and the X cable set serves as a one turn secondary winding CURRENT TRANSFORMER X BLACK 4 4 2 CT Testing 1 When the instrument is set for CT testing the DTR will display the CT Test Mode Selected message after the initial power up sequence This message indicates that the DTR is now ready to execute a test 2 Press the TEST button once to begin the test cycle 3 The next message displayed is Ratio Testing TEST to Cancel The asterisk will blink as testing proceeds Testing may be cancelled at this time by pressing the TEST button once If the test continues Ratio and Excitation current will be displayed 4 Oncetest results are recorded press the TEST button to reset for the next test NOTE There are certain low mass low ra
36. nducting a Test 1 Connectthe DTRS test cables in the proper manner to a non energized transformer Refer to Connection Examples 84 3 1 and 84 4 1 2 Turn the DTR ON and select the proper test mode Refer to Mode Selection below 3 At Ready press the test button to begin Following a brief test cycle Ratio Polarity and Excitation Current will be displayed Please refer to VT PT Testing and CT Testing sections of this manual for complete operating information 84 3 2 and 84 4 2 4 2 Mode Selection The operating mode of the DTR is configured at power up of the instru ment The default test mode is VT PT To enter the CT Test Mode depress the TEST button while turning the instrument on and hold until CT Test Mode Selected is displayed Use the VT PT Test Mode for testing voltage and potential transformers maximum 44V test excitation Use the CT Test Mode for testing current transformers maximum 5V test excitation The DTR automatically reverts to the VT PT Test Mode when power is turned off Digital Transformer Ratiometer DTR Model 8500 9 4 3 VT PT 4 3 1 Example Connections Here is an example of connections to an ordinary 7200 120 240 distribution transformer with center tapped secondary winding Typical Connection RATIO 60 00 1 PRIMARY SECONDARY 7200 240CT lt X RED H RED QZ X BLACK 1 X BLACK Alternate Connection RATIO 30 00 1 PRIMARY
37. nstruments will at its option repair or replace the faulty material REGISTER ONLINE AT www aemc com Warranty Repairs What you must do to return an Instrument for Warranty Repair First request a Customer Service Authorization Number CSA by phone or by fax from our Service Department see address below then return the instrument along with the signed CSA Form Please write the CSA on the outside of the shipping container Return the instrument postage or shipment pre paid to Chauvin Arnoux Inc d b a AEMC Instruments Service Department 15 Faraday Drive Dover NH 03820 USA Tel 800 945 2362 Ext 360 603 749 6434 Ext 360 Fax 603 742 2346 or 603 749 6309 repair aemc com Caution To protect yourself against in transit loss we recommend you insure your returned material NOTE All customers must obtain a CSA before returning any instrument 24 Digital Transformer Ratiometer DTR2 Model 8500 Tabla de Contenidos ENGLISH cenar Dep eee 02 De eta ER 1 ESPA OL a EE EA 25 T INTR0ODUCCI N 27 1 1 S mbolos El ctricos Internacionales 28 1 2 Recepci n De Su Embarque 28 1 9 EMBAT eee rette Renee 28 1 3 1 ACCOSOMOS nin eene ot ba aa to eo e Lee e 29 2 PRESENTACI N nd 30 2 1 Descripc
38. omento pulsando el bot n TEST una vez Si la prueba contin a se mostrar la Raz n y la Corriente de Excitaci n Una vez que los resultados de la prueba han sido registrados pulse el bot n TEST para reiniciar para la pr xima prueba Esta rutina puede ser repetida tantas veces como sea necesario sin apagar el instrumento 36 Medidor de Raz n de Transformador Digital Modelo 8500 4 3 3 Diagrama de Flujo del Modo de Prueba VT PT Mensaje del Display Acci n del Para el Modo VT PT Operador 3 Indica version 1999 me Encienda la Unidad zm del Programa de SE Instrucciones Interno AEMC Instruments alli N A DTR Model 8500 m N A sas dentificaci n del Modelo Comentarios Y Reemplaza el Mensaje e AERC sree YI m i ser Recargadas PT VT Test Mode N A Indicaci n del Modo Seleccionado Calibrating N A Calibraci n Interna Please Wait en Curso VT PT Test Mode Pulse TEST Ahora Sistema Listo para Exi A Ready para Iniciar la Prueba Comenzar la Prueba Y Pulse TEST Ahora Press TEST to para Comprobar me Selecci n de la Opci n Check Continuity Continuidad o no haga Prueba de Continuidad nada para salt rselo Y Pulse TEST Ahora Prueba de Raz n en Ri T WEIT Mesi para Cancelar Curso con la Opci n i la Prueba en Curso de Cancelar la Prueba Pulse TEST Ahora para Reiniciar para la Pr xima Prueba Ratio 60 00 1 Current 11 mA Med
39. por favor refi rase a las sec ciones Prueba VT PT y Prueba CT de este manual 84 3 2 and 84 4 2 4 2 Selecci n de Modo El modo de operaci n del DTR se configura al encender el instrumento El modo de prueba preestablecido es VT PT Para entrar al modo de prueba CT presione el bot n TEST mientras enciende el instrumento y mant ngalo presionado hasta que aparezca CT Test Mode Selected Use el Modo de Prueba VT PT para probar transformadores de voltaje y de potencia excitaci n de prueba de 44V m ximo Use el Modo de Prueba CT para probar transformadores de corriente excitaci n de prueba de 5V m ximo El DTR autom ticamente vuelve al Modo de Prueba VT PT al ser apagado 34 Medidor de Raz n de Transformador Digital DTR Modelo 8500 4 3 VT PT 4 3 1 Ejemplos de Conexiones VT PT He aqu un ejemplo de conexiones a un transformador de distribuci n corriente 7200 120 240 con un bobinado secundario con derivaci n cen tral Conexi n T pica Raz n 60 00 1 H ROJO PRIMARIO SECUNDARIO 7200 240CT De gt gt cupo ROJO H ROJO H NEGRO u X NEGRO H NEGRO X NEGRO du Conexi n Alternativa Raz n 30 00 1 PRIMARIO SECUNDARIO 7200 240CT HROJO DS lt ALE xRoJo H NEGRO lt NEGRO Nota A diferencia de otros instrumentos el DTR Modelo 8500 no impone restricciones de polaridad o auto conexiones obligadas luego hay varios tipos de conexiones
40. rded calibration data Chauvin Arnoux Inc d b a AEMC Instruments 15 Faraday Drive Dover NH 03820 USA Tel 800 945 2362 Ext 360 603 749 6434 Ext 360 Fax 603 742 2346 or 603 749 6309 repair aemc com Or contact your authorized distributor Costs for repair standard calibration and calibration traceable to N I S T are available NOTE All customers must obtain a CSA before returning any instrument LIr Technical and Sales Assistance North South America Australia New Zealand If you are experiencing any technical problems or require any assistance with the proper operation or application of your instrument please call mail fax or e mail our technical support hotline Chauvin Arnoux Inc d b a AEMC Instruments 200 Foxborough Boulevard Foxborough MA 02035 USA Phone 800 343 1391 508 698 2115 Fax 508 698 2118 techsupport aemc com www aemc com NOTE Do not ship Instruments to our Foxborough MA address 22 Digital Transformer Ratiometer Model 8500 Repair and Calibration Europe Asia Africa To ensure that your instrument meets factory specifications we recommend that it be submitted to our factory Service Center at one year intervals for reca libration or as required by other standards or internal procedures For instrument repair and calibration For instrument repair and or calibration please call our European Repair Center M
41. ric coat ings fungus and corrosion During VT PT Mode operation select Continuity Test when possible Besides being a useful way to check windings and connections this test has the added benefit of reducing magnetic remnants in the trans former under test This is important primarily in transformers with high series resistance and in low KVA transformers with extremely high pri mary side inductance It is not required in most tap change and regula tor transformers Whentesting polyphase transformers keep in mind that in some cases measured ratios must be multiplied or divided by V3 Refer to 4 10 for polyphase connections diagrams and associated ratio equations 4 9 Ratio Test 1 1 A simple test can be conducted to test functionality of the DTR9 By connecting HRED to XRED and separately HBLACR to XaLack a 1 1 transformer is simulated Operation of the DTR in this configuration should yield a ratio very nearly equal to 1 000 If it does not the DTR may require repair or calibration H RED X RED H BLACK X BLACK CONNECTIONS EQUIVALENT Digital Transformer Ratiometer DTR Model 8500 19 4 10 Polyphase Connections VOLTAGE VOLTAGE WINDING WINDING TRANSFORMER TYPE HIGH VOLTAGE LOW VOLTAGE WINDING WINDING XFM 19 STD A A A A Y Y REV R A STD Y Y STD Y Y REV Y A STD Y A REV z 7 8 20 Digital Transformer Ratiometer Model 8500
42. t short circuits X winding may be shorted or transformer circuit breaker may be open Low H Signal Check H cables for inadvertent short circuits Check H cable connector at DTR front panel 4 6 Power Supply The DTR Model 8500 may be used for up to 10 hours on fully charged NiCd batteries The DTR may also be line supplied during measurements In this mode the DTR also recharges the NiCd batteries LOW BATTERY is displayed when the internal batteries approach low voltage When displayed a limited number of measurements may still be conducted though we recommend recharging the DTR as soon as possible If the battery voltage drops too low the DTR will lock out further operation In the lock out mode the DTR shuts down all functions until AC power is applied and the battery recharged We recommend recharging the DTR overnight Each time the DTR is connected to AC power a 14 hour recharge cycle begins Repeat charging of partially discharged batteries will not result in battery damage During the 14 hr cycle the CHARGING indicator will glow continuously following this period a pulse trickle charge mode is entered and the indicator will pulse on and off Digital Transformer Ratiometer DTR Model 8500 17 4 7 Changing Power Supply Setting from 115V to 230V or 230V to 115V LIAME TRANSFORMER FA aa MODEL 8500 Power Input Fuse Input Voltage Label to match power supply voltage switch setting
43. tico O 1A 0 1 5Vrms Presentaci n de Corriente de Excitaci n Rango 0 1000mA Exactitud 2 2mA Frecuencia de Excitaci n 70Hz Display Caracteres LCD 20 x 2 formato grande LED con iluminaci n posterior visibles de d a noche M todo de Medici n de acuerdo con ANSI IEEE C57 12 90 Alimentaci n Doble operaci n bater a NiCd recargable amp l nea de 115 230V 50 60Hz Se puede cambiar el DTR entre 115 230V mediante un interruptor interno en cualquier momento Unidades disponibles preajustadas en f brica a 115V o 230V Bater as Paquetes de 5 x 2 NiCd 12V 1300mAH Panasonic P 130SCR o equivalente Vida de la Bater a Hasta 10 hrs en operaci n continua Puede utilizarse mientras se recarga Indicador LCD de bater a baja Tiempo de Carga 14 hrs t picas a velocidad C 10 Fusible de la Alimentaci n 115V 1 0A 5 x 20mm acci n lenta 230V 0 5A 5 x 20mm acci n lenta 23 C 5 C 50 a 70 HR bater a cargada totalmente sin campos externos o ruido 32 Medidor de Raz n de Transformador Digital DTR Modelo 8500 3 2 Mecanicas Conexiones Conectores Cannon XLR amp pinzas industriales grandes con c digo de color Cables de Prueba 15 pies H amp X con c digo de color en un estuche de transporte Display Alfa num rico de doble l nea 3 875 x 875 con ajuste de contraste e iluminaci n posterior Temperatura de Operaci n 0 a 50 C 32 a 122 F O a 90 HR sin condens
44. tio CT s where the DTR may not be able to provide the correct ratio The error message will be High Excitation Current As in VT PT Test Mode this routine may be repeated as many times as needed without powering down the unit The CT Test Mode remains active until the unit is powered down 14 Digital Transformer Ratiometer DTR2 Model 8500 4 4 3 CT Test Mode Flow Chart Display Indication Operator for CT Test Mode Action Turn Unit ith en A 1997 Tem Pls le bul of C rnoux Depressed nternal Firmware AEMC Instruments Hold TEST Butt DTR Model 8500 mum HO utton s Model Identification Y e Replaces Above Indication dels ments mem Hold TEST Button s when Batteries Need i Recharging CTTestMode Release TEST Button Selected Mode Calibrating Internal Calibraiton Please Wait in Progress CT Test Mode Push TEST Now System Ready to Ready to Initiate Testing Begin Testing Ratio Testing EU TES MON TEST to Cancel to Cancel E Test in Progress Ratio 40 00 1 Current 35 mA Comments Ratio Testing in Progress with Test Cancel Option Push TEST Now to Reset for Next Test Digital Transformer Ratiometer DTR Model 8500 15 4 5 Displayed Messages Check for H X Cable Reversal The DTR may have detected a potentially hazardous step up condition while attempting to test the transformer as connected Verify connections HRED 8 HBLACR should be attached to th
45. v lidas y se puede probar vir tualmente todas las configuraciones de transformadores En todas las pruebas un signo negativo que precede la raz n mostrada indica una inversi n de fases polaridad invertida de la se al detectada en X respecto de la se al de excitaci n en H Al usar el DTR fijese siempre en el c digo de color de los capuchones de los cables de prueba Medidor de Raz n de Transformador Digital DTR2 Modelo 8500 35 4 3 2 Prueba VT PT 1 Cuando el instrumento est ajustado para una prueba VT PT el DTR mostrar el mensaje VT PT Test Mode Ready despu s de la secuen cia inicial de encendido Este mensaje indica que el DTR est listo para realizar una prueba Pulse el bot n TEST una vez CUIDADO No se debe realizar la prueba mientras haya personal manejando las conexiones del trans formador Se mostrar durante 3 segundos Press TEST to Check Continuity pulse TEST para comprobar la continuidad Si se desea una prueba de continuidad se debe pulsar en ese momento el bot n TEST una vez Los resultados de la prueba de continuidad se mostrar n como CONT continuo o OPEN abierto para ambas conexiones X y H Para m s informaci n refi rase a Prueba de Continuidad VT PT p gina 12 El siguiente mensaje que se muestra es Testing TEST to Cancel Prueba de Raz n TEST para cancelar El asterisco va a parpadear mientras dura la prueba La prueba se puede cancelar en este m