Manuel d`installation - capteur de température

image

Contents

1. FRANCE Tel 33 0 4 72 14 15 40 Fax 33 0 4 72 14 15 41 For manuals and configuration software please visit www pyrocontrole com This document is property of Pyrocontrole Duplication and reprodution are forbidden if not authorized Contents of the present documentation refers to products and technologies described in it All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision ERA crea ROLE 694087A00 ED1 ENGLISH 1 8 GENERAL SPECIFICATIONS e Voltage or current inputs with programmable range 2 Vdc 10 Vdcand 20 mA with 16 bits resolution e module auxiliary power supply can be supplied to all 4 current loops at the same time e Modbus address and Baud rate can be set through DIP switches e Sampling time for all channel at 240 ms or 480 ms e Current input with internal shunt can be imposed through DIP switch e 1500 Vac output isolation compared with other low voltage circuits e Easy connections for power supply and serial communication from PDM DIN bus system that can be mounted on standard DIN 46277 rail e Removable terminals with section of 2 5 mm e RS485 serial communication with Modbus Rtu protocol maximum 64 nodes e Module insertion or extraction from PDM DIN bus without interruption for serial communication and power supply e Connection distance up to 1200 m e RS232 communication with jack 3 5 mm connector on front
2. Meaning of LEDs PWR On Power supply presence FAIL Blinking Error settings RX Blinking Received data On Error connection TX Blinking Received data Q PYRO Bed CONTROLE 694087A00 ED1 ENGLISH 7 8 FACTORY SETTING AND ADVANCED SETTING Factory settings Tutti i DIP switch in OFF Modbus protocol Communication parameters 38400 8 N 1 Addr 1 Input channel 1 VOLTAGE 10 V Input channel 2 VOLTAGE 10 V Input channel 3 VOLTAGE 10 V Input channel 4 VOLTAGE 10 V Measure NCH representation 10000 Signal sampling time 120 ms for channel Advanced settings Input channel can be set in current or voltage Possibility to set the representation of the measure in range with value IS start scale ES end scale 10000 mV and 0 20000 pA Possibility to set the representation of the measurement with normalized value Signal sampling time can be set at 60 ms or 120 ms Possibility to set a filters for the inputs measured Modification of standard parameters is possible by using configuration software PDM Studio www pyrocontrole com For more information about a list of all registers and their functions consult the PDM General User manual Disposal of Electrical amp Electronic Equipment Applicable throughout the European Union and other European countries with separate collections programs This symbol found on your producr or on its packaging indicates ps that this product should n
3. PYRO CONTROLE CHAUVIN ARNOUX GROUP S rie PDM PDM 4AI Module 4 ENTREES ANALOGIQUES tension courant avec protocole Modbus RS485 Manuel d installation Contenus Caract ristiques g n rales Caract ristiques techniques Connexion au Modbus Installation Branchements lectriques R glage commutateurs Signalisation l aide de DELS Param tres d usine ERR PWR RX TX PYROCONTROLE Groupe Chauvin Arnoux 6bis Av Dr Schweitzer 69881 MEYZIEU Cedex FRANCE Tel 33 0 4 72 14 15 40 Fax 33 0 4 72 14 15 41 Pour les manuels et le logiciel de configuration visiter le site www pyrocontrole com Ce document est la propri t de Pyrocontrole Il est interdit de le copier ou de le reproduire sans autorisation Le contenu de la pr sente documentation correspond aux produits et aux technologies d crites Les donn es report es pourront tre modifi es ou compl t es pour des exigences techniques et ou commerciales PYRO CONTROLE CHAUVIN ARNOUX GROUP 694085A00 Ed1 FRAN AIS 1 8 CARACT RISTIQUES G N RALES Entr es en tension ou en courant dans les plages de 2 Vcc 10 Vcc et 20 mA avec r solution 16 bits l alimentation auxiliaire du module peut alimenter simultan ment les 4 boucles de courant ecommutateur pour configurer adresse et Baud Rate du module e Temps d chantillonnage pouvant tre saisi pour tous les canaux a 240 ms ou 480 ms Entr e en courant avec s
4. RFACE MODBUS L alimentation et l interface Modbus peuvent tre connect s via le bus pour rail DIN a l aide du connecteur IDC10 et des accessoires PDM DIN ou encore via les borniers a vis e PYRO Bed CONTROLE 694085A00 Ed1 FRAN AIS 4 8 Connecteur arri re IDC 10 RS485 GND RS485 A Power Supply AC Pr sentation des connexions du bornier IDC10 pour une utilisation externe Power Supply AC RS485 B Peo Accessoire PDM DIN C 2S Sci peui oo 7 DIN C 2S Ground DIP SWITCH l alimentation et le Rs485 peuvent tre Power supply AC connect s sur les borniers Cf ci contre 120 Ohm terminator i Power supply AC a NE af GNDSHLD Blindage pour prot ger les c bles de connexion conseill oooogo oooogo oooogo oooogo ENTREES A Entr e tension avec alimentation du capteur provenant du MODULE 13 Vcc B Entr e tension avec alimentation du capteur Ne provenant PAS du MODULE C Entr e courant avec alimentation du capteur Ne provenant PAS du MODULE D Entr e courant avec alimentation du capteur provenant du MODULE 13 Vcc E Entr e courant avec alimentation du capteur EXTERNE l i wins OD 19 HN HINA Et I I I GND fer Uee vaux TL I Vaux Vext I is ol 7 Lo HD 1 SB EG AN alle i iN2 9 D DIRES ru Vaux G n r e par le module 13 Vdc ALIMENTATION la place de la c
5. Tx R GLAGE COMMUTATEURS La position des commutateurs d finit les param tres de communication Modbus du module Adresse et Baud Rate Les valeurs du Baud Rate et de l adresse en fonction de la configuration des commutateurs sont report es dans le tableau suivant TAT DES COMMUTATEURS POSITION BAUD RATE POSITION ADRESSE POSITION TERMINATEUR 00xxxxxxxx 9600 xx000001xx 1 XXXXXXXXXO d sactiv 01xxxxxxxx 19200 xx000010xx 2 XXXXXxxxx1 activ 1Oxxxxxxxx 38400 Foo oun 11xxxxxxxx 57600 xx111111xx 63 POSITION BAUD RATE POSITION ADRESSE xx000000 From EEprom xx000000 From EEprom g PYRO Bed CONTROLE 694085A00 Ed1 FRAN AIS 6 8 Remarque Quand les commutateurs de 3 8 sont sur OFF les param tres de communication sont pris par la programmation EEPROM Remarque 2 La terminaison de la ligne RS485 ne doit tre effectu e qu aux extr mit s de la ligne de communication PARAM TRES ENTR ES L AIDE DU COMMUTATEUR CANAL TENSION COURANT CH1 Oovoxxxx 1 O00XXXX CH2 oO coxxxx o1 OOXXXX CH3 oD oxxxx 00 OXXXX CH4 000 Oxxxx 0001 XXXX Les r glages des commutateurs devront tre compatibles avec les r glages sur les registres La description des registres est report e sur le MANUEL D UTILISATION REGISTRES MODBUS DE BASE ET SIGNALISATION A L AIDE DE DELS Holding register Registre Nom Description 40017 Valeur de la mesure du canal avec chelle 10000 normalis e plus haut plus haut Comme plus ha
6. ac 50 60 Hz tension Consommation typique 1 5 W Max 2 5 W CONDITIONS AMBIANTES Temp rature 10 65 C Humidit 30 90 a 40 C sans condensation Altitude jusqu 2 000 m au dessus du niveau de la mer Temp rature de Stockage 20 85 C Degr de protection IP20 CONNEXIONS Bornes a vis amovibles a 3 voies pas 5 08 mm Connecteur arri re IDC10 pour rail DIN 46277 connexions Jack front 3 5 mm ENCOMBREMENTS BOITIER Dimensions Largeur 100 mm hauteur 112 mm profondeur 17 5 mm Boitier PBT Couleur noir ISOLATIONS NORMES 1500 Vac L instrument est conforme aux normes suivantes aa eT EN61000 6 4 2002 10 mission lectromagn tique milieu industriel EN61000 6 2 2006 10 immunit lectromagn tique milieu industriel EN61010 1 2001 s curit Tous les circuits doivent tre isol s avec une double isolation des circuits sous tension dangereuse Le transformateur d alimentation doit satisfaire la norme EN60742 Transformateurs d isolation et transformateurs de s curit RS232 se RS485 11 10 9 POWER 8 SUPPLY 234 O 7 REMARQUES SUPPL MENTAIRES SUR L UTILISATION utiliser dans des milieux avec degr de pollution 2 PYRO CONTROLE CHAUVIN ARNOUX GROUP 694085A00 Ed1 FRAN AIS 3 8 CONNEXION AU MODBUS 1 Installer les modules dans le guide DIN max 120 2 Brancher les modules distance en utilisant des c bles ayant une longue
7. al TECHNICAL FEATURES Inputs Bipolar with programmable FS at 2 Vdc or Voltage inputs 10 Vdc input impedance gt 100 kQ Bipolar with programmable FS at 20 mA The 50 Q internal shunts are selected through DIP switches Available power supply 13V 90 mA Current inputs Number of input channel 4 30 Vdc or 25 mA 15 bit 1 bit sign Protection inputs Inputs resolution Initial 0 1 of full scale Linearity 0 03 of range Zero 0 02 of range TC 100 ppm EMI 0 02 Voltage and current accuracy Sampling Time 120 ms channel o 60 ms channel A PYRO meat CONTROLE 694087A00 ED1 ENGLISH 2 8 Power supply 10 40 Voc 19 28 Vac 50 60 Hz Voltage Consumption Typical 1 5 W Maximum 2 5 W Environmental condition Temperature 10 65 C Humidity 30 90 a 40 C not condensing Storage E Temperature 20 85 C Degree protection IP20 Connections Removable 3 way screw terminals 5 08 pitch Connections Rear IDC10 connector for DIN 46277 rail Frontal jack 3 5 mm Box Dimensions Dimensions L 100 mm H 112 mm W 17 5 mm Box PBT Black Isolations Standards 1500 V he module is conforming to the following regulations EN61000 6 4 2002 electromagnetic emission industrial environment EN61000 6 2 2006 electromagnetic immunity industrial environment EN61010 1 2001 safety All circuits must be isolated from the other circuits under dangerous voltage with doub
8. hunt interne pouvant tre s lectionn l aide du commutateur Isolation des entr es de 1 500 Vca par rapport aux circuits restants en basse tension eC blage facilit de l alimentation et de la communication s rie l aide d un bus log dans le rail DIN Bornes extractibles section 2 5 mm Communication s rie RS485 avec protocole Modbus Rtu maximum 64 n uds Insertion et extraction du slot sans interruption de la communication ou de l alimentation du bus Distance de branchement jusqu 1 200 m Connexion RS232 sur la partie frontale avec commutation automatique de la communication Commutateur pour configurer adresse et Baud Rate du module CARACT RISTIQUES TECHNIQUES ENTR ES Bipolaire avec F S chelle programmable Entr e en tension 2 Vou 10 Vdc Imp dance entr e gt 100 KQ Bipolaire avec F S chelle programmable 20 mA avec shunt de 50 Q interne pouvant tre s lectionn l aide du commutateur Alimentation auxiliaire disponible 13 V 90mA Entr e en courant Nombre de voies 4 30 Vcc ou 25 mA 15 bits signe Protection entr es R solution entr es Pr cision tension et courant Initial 0 1 de l chelle Z ro 0 02 de l chelle Lin arit 0 03 de l chelle Stabilit Thermique 100 ppm C EMI 0 02 Temps d chantillonnage 120 ms canal ou 60 ms canal PYRO D ROLE 694085A00 Ed1 FRAN AIS 2 8 cH ALIMENTATION 10 40 Voc 19 28 V
9. le Manuel d Utilisation G n ral S rie PDM limination des d chets lectriques et lectroniques applicable dans l Union europ enne et dans les autres pays qui pratiquent la collecte s lective Le symbole report sur le produit ou sur l emballage indique que le produit ne doit pas tre jet avec les ordures m nag res Il doit au contraire tre remis a une station de collecte s lective autoris e pour le recyclage des d chets lectriques et lectroniques Le fait de veiller ce que le produit soit limin de fa on ad quate permet d viter l impact n gatif potentiel sur l environnement et la sant humaine pouvant tre d l limination non conforme de ce dernier Les recyclage des mat riaux contribue la conservation des ressources naturelles Pour avoir des informations plus d taill es pri re de contacter le bureau pr pos de la ville int ress e le service de ramassage des d chets ou le revendeur du produit 694085A00 Ed1 FRAN AIS 8 8 PYRO CONTROLE CHAUVIN ARNOUX GROUP PDM Line R PDM 4AI 4ANALOG INPUT voltage current with Modbus RS485 Installation Manual Contents General specifications Technical features Modbus connections Installation Electrical connections DIP switches settings Modbus registers and LEDs signaling Factory settings and advanced settings PYROCONTROLE Groupe Chauvin Arnoux 6bis Av Dr Schweitzer 69881 MEYZIEU Cedex
10. le isolation The power supply transformer must comply with EN60742 Isolated transformers and safety transformers SUPPLEMENTARY NOTE FOR USE Use in environment with 2 or less pollution degree Pyro crn els 694087A00 ED1 ENGLISH 3 8 MODBUS CONNECTIONS 1 Install the modules on the DIN rail max 120 2 Connect the remote modules using cables of proper length On the table the following data about the cables length are provided Bus Length Modbus network maximum length as a function of the Baud rate It is the lenght of the cables which connect the two bus terminators modules see Scheme 1 Drop Length maximum length of a drop line see Scheme 1 Bus lenght Drop Nodes Node 4 lenght i inator Ld erminator 1200 m 2m ermina HH Node 1 Node 2 Node 5 f Bus Length Scheme 1 Ld Drop Length For the maximum performances it s recommended to use a Shielded cable INSTALLATION The module is designed to be installed in vertical position on DIN 46277 rail For the best performance and long life cycle the cables raceways and other objects in the control panel must be placed not to obstruct the slits of the module that must be ventilated Never install the modules near heat sources It s advised to install the module in the lower part of the control panel Inserting on the DIN rail Inserting in the DIN rail Module How the picture shows 1 Insert the mod
11. nt input with external power supply for sensor gt wns ol 10 ni i Sn a HINA Et I La r NPA Mae P E aux I I Vaux Vext eet el 7 IN1 JO LL N2 219 A BE D Bo ye Vaux supplied from module 13 Vdc Power supply Screw terminal 2 and 3 are the alternative to PDM DIN rail bus system to provide the power supply at the module The upper 19 28 V 2 limits must not be exceeded otherwise the module can be 10 40 V 3 damaged If the power supply source is not protected against overload a safety fuse with a maximum acceptable value of 2 5A must be installed in the power supply line PYRO Error 694087A00 ED1 ENGLISH 5 8 RS485 GND QJ 4 Connection for RS485 communication using the Modbus master B ojs systemasan alternative to the PDM DIN rail bus system A Note the indication of the RS485 connection polarity is not O6 standardised and in some masters may be inverted RS232 The RS232 port can be used to communicate and also to program the module PDM Studio is the configuration software The RS232 communication use the following parameter of communications 2400 8 N 1 RS232 and RS485 port use the same Modbus protocol When RS232 communication is active the serial RS485 bus network will be stopped The RS485 will return automatically active a few seconds after the last data packed received from Rs232 The 3 5 mm DB9 jack stereo c
12. onnector for RS232 communication Jack stereo 3 5 mm Rx GND Tx DIP SWITCHES SETTING The DIP switches positions defines the Modbus communication parameter Address and Baud rate In the following table the Baud rate and address value are listed as a function of the DIP switches position DIP switches table POSITION BAUD RATE POSITION ADDRESS POSITION TERMINATOR OOxxxxxxxx 9600 01xxxxxxxx 19200 10xxxxxxxx 38400 11xxxxxxxx 57600 xx000001xx 1 xx000010xx 2 XXXxxxxxx0 Disable XXXXXXXxXX1 Enable xx111111xx 63 POSITION BAUD RATE POSITION ADDRESS xx000000 From EEprom xx000000 From EEprom CB PYRO Bead CONTROLE 694087A00 ED1 ENGLISH 6 8 Note when DIP switches from 3 to 8 are OFF comunication settings are retrieved from EEprom Nota 2 The termination of RS485 communication must be enabled only to the end of the communication line DIP switches for inputs setting CHANNEL VOLTAGE CURRENT CH1 Oovoxxxx 1 000XXXX CH2 oDooxxxx o1 OOXXXX CH3 ooDoxxxx 001 OXXXX CH4 0000 xxx 000 XXXX The DIP switches inputs setting must be compatible with the Modbus register setting The description of Modbus registers are available in the USER MANUAL MODBUS REGISTER AND LED SIGNALING Holding register Register Name Description 40017 NCH 1 Measured value of channel with scale 10000 normalized 40018 See before 40019 See before 40020 NCH 4 See before LEDs signallings LED STATE
13. onnexion du syst me de bus PDM DIN il est Q possible d utiliser les bornes 2 et 3 pour fournir l alimentation au 19 28V lof 2 10 40V lof module Les limites sup rieures ne doivent pas tre d pass es sous peine d endommager le module Si la source d alimentation n est pas prot g e contre la surcharge il est n cessaire de monter un fusible dans la ligne d alimentation valeur maximale 2 5 A PYRO ana ROLE 694085A00 Ed1 FRAN AIS 5 8 RS485 GND Ql 4 Branchement pour la communication Rs485 avec le systeme master B O5 Modbus ala place du syst me de bus PDM DIN A all 6 N B L indication de la polarit de la connexion Rs485 n est pas 2 standardis e elle peut tre invers e sur certains masters RS232 Ce port de communication peut tre utilis pour communiquer et pour programmer le module via par exemple le logiciel de configuration PDM Studio Le port s rie RS232 utilise les param tres de communication suivants 2 400 8 N 1 Le port de communication COM se comporte exactement comme celui du bus RS485 sauf pour les param tres de communication Durant l utilisation du port RS232 le bus sera inactif il se r activera automatiquement au bout de quelques secondes apr s le dernier message chang sur le port COM Le c ble de connexion DB9 Jack st r o 3 5 mm peut tre assembl comme indiqu sur la figure ci dessous ou achet comme accessoire Jack stereo 3 5 mm Rx GND
14. ot be treated as household waste when you wish to dispose of it Instead it should be handed over to an applicable collection point for the recycling of electrical amp electronic equipment By ensuring this product is didposed of correctly you will help prevent potential negative consequences to the environment and human health which could otherwise be caused by inappropriate disposal of this product The recycling of materials will help to conserve natural resources For more detailed information about the recycling of the product please contact your local city office waste disposal service of the retail store where you purchased this product 694087A00 ED1 ENGLISH 8 8
15. ule IDC10 rear connnector on the DIN rail free slot inserting is univocal because connectors are polarized 2 The module can be fixed on the DIN rail through the clench of the two hooks in the bottom DIN rail ELECTRICAL CONNECTIONS Power supply and Modbus interface Power Supply and MODBUS interface are available by using the bus for the DIN rail by the rear DC10 connector and PDM DIN accessories or by auxiliary screw terminals 694087A00 ED1 ENGLISH 4 8 Rear connector IDC10 RS485 GND RS485 A Power Supply AC The picture shows the meaning of the IDC10 connector pins This connector can be used in alternative to the screw terminals Power Supply AC blocks RS485 B De e PDM DIN C 2S Accessory Use Ground DIP SWITCH In case of PDM DIN accessories use Power supply AG the signals may be provided by terminal blocks The figure shows the meaning of the terminals and the position of the DIP switch for network termination not used in case of Modbus network GNDSHLD Shield to protect the connection cables recommended Power supply AC i 120 Ohm terminator il fre oooogo ooo000 00000 oooogo Input A Voltage input with sensor s power supply from MODULE 13 Vdc B Voltage input with sensor s power supply NOT from MODULE C Current input with sensor s power supply NOT from MODULE D Current input with sensor s power supply from MODULE 13 Vdc E Curre
16. ur appropri e Le tableau ci dessous reporte les donn es suivantes relatives la longueur des c bles Longueur bus longueur maximale du r seau Modbus en fonction du Baud Rate C est la longueur des c bles qui relient les deux modules sur lesquels est ins r e la terminaison du bus voir Sch ma 1 Longueur d rivation longueur maximale d une d rivation 2 m voir Sch ma 1 n ud 3 n ud Longueur bus Longueur n ud n ud E n ud d rivation 1 2 5 4 5 1200 m 2m Te gE 5 T FAN LES Sch ma 1 Longueur bus Pour obtenir le maximum de performances il est conseill d utiliser des c bles blind s INSTALLATION Le module a t con u pour tre mont la verticale sur un rail DIN 46277 Pour que l instrument fonctionne correctement s assurer que la ventilation est ad quate en veillant ce qu aucun chemin de c ble ou autre objet ne bouche les fentes d a ration viter de monter les modules sur des appareils qui d gagent de la chaleur il est conseill de les monter en bas de l armoire Insertion dans le rail DIN ComComme illustr sur la figure 1 Ins rer le connecteur arri re IDC10 du module sur un slot libre du rail DIN les connecteurs sont polaris s 2 Pour fixer le module dans le rail DIN serrer les deux clips situ s de chaque c t du connecteur or arri re IDC10 SSS Rail Bese DIN BRANCHEMENTS ELECTRIQUES ALIMENTATION ET INTE
17. ut SIGNALISATION L AIDE DE DELS LED ETAT Signification PWR Fixe le dispositif est aliment correctement FAIL Clignote anomalie ou panne RX Clignote r ception paquet de donn es Fixe v rification connexion TX Clignote transmission paquet de donn es PYRO Beal CONTROLE 694085A00 Ed1 FRAN AIS 7 8 PARAMETRES D USINE ET PARAMETRES AVANCES PARAMETRES D USINE Tous les commutateurs sur OFF Protocole Modbus Param tres de communication 38400 8 N 1 Addr 1 Entr e canal 1 TENSION 10 V Entr e canal 2 TENSION 10 V Entr e canal 3 TENSION 10 V Entr e canal 4 TENSION 10 V Repr sentation mesure entr e NCH 10000 Temps d chantillonnage du signal 120 ms par canal PARAMETRES AVANCES Possibilit de saisir l entr e en courant ou en tension Possibilit de saisir les valeurs de repr sentation de la mesure en r glant ISM d but chelle de mesure FSM bas chelle de mesure 10 000 mV ou 0 20 000 pA Possibilit de saisir les valeurs de repr sentation de la mesure normalis es Possibilit de saisir le temps d chantillonnage du signal 60 ms ou 120 ms Possibilit de pr voir un filtre sur la mesure l entr e Pour toute modification des param tres le logiciel PDM Studio est disponible dans la zone t l chargement du site Web www pyrocontrole com Pour de plus amples informations sur la liste des registres et leurs fonctions consulter