Home

KSA700 Series User Guide

image

Contents

1. Sounder Fault Disabled One or more of the sounder outputs has a problem or is disabled System fault System CPU Fault There is a malfunction in the fire panel Sounders Disabled A sounder output has been disabled The fire panel is not able to warn of a potential risk situation Relays disabled Relays disabled A relay output has been disabled The fire panel is not able to release any safety device in the event of a potential risk situation Sounder Delay The fire panel has detected a fire but has not activated the sounders or relays as a time delay has been programmed Earth Fault Earth Fault There is a current leakage Cable runs must be checked Silence Buzzer Mute The internal buzzer has been silenced Out of Service The fire panel does not work 2 3 Access levels and passwords Following EN54 standard part 2 the fire panels have different access levels as a security measure The configuration and control menus can be accessed only if the appropriate password is entered Level 1 All the panel indications are operational but only visual control of the fire panel is allowed to verify that everything is working properly The controls are blocked No password is required to access this level Level 2 This level is reserved for the person or persons responsible for controlling the proper operation of the fire system Up to 10 different passwords can b
2. 4 Delayed Mode 5 Relay Sounders Exit The following procedures apply to both enabling and disabling features of the system Choose Enable or Disable from the Main Menu as required KSA700 Series User Guide 3 2 4 1 Zone Select Zone from the Disable Menu The system will ask which zone is to be disabled Enter the zone to be modified Disable zone number 001 The fire panel will activate the internal buzzer to confirm a zone has been disabled Press Enter or to silence the buzzer A message will confirm the details of the event and the time it was performed Incidence 1 of 1 at 00 00 ZONE DISABLED Panel 1 Zone 1 A disabled zone will be highlighted with the corresponding Disabled LED indicator on the panel Devices assigned to a disabled zone will not be controlled by the fire panel but output signals sounders relays will remain active 3 2 4 2 Devices Every element of the installation can be enabled or disabled independently Select Devices from the Disable Menu The system will ask for the loop number and the device address Loop 01 Address 001 Enter the loop number and the device address and press Enter or The Disabled LED will be activated The device may be enabled again following the same procedure in the Enable Menu Signals from a disabled device will not be processed by the fire panel but output signals sounders relays will
3. e Devices Print the status of devices connected to a loop and the text assigned to each e History The system records a history of events It is possible to print all of these events or only part of them e g the events of the last week e Mode The printer may be in one of three modes e Auto This is the default and recommended mode A short report is printed for every system event e Manual Prints only when the user decides to print e OFF The printer is switched off e Disabled Print a list of all disabled devices e Options To select the port used by the printer The View option in the Main Menu allows the operator to check the current status of selected devices in the installation VIEW Exit 1 Devices 4 Outputs 2 History 5 Disabled 3 Faults 6 Events Device This displays the status of a single device on a loop The loop number and device address must be entered to view the device details KSA700 Series User Guide Loop 01 Zone 01 Address 001 Type Analogue value Zone Point History Allows the operator to view the list of events that the system has recorded Navigate using the left right keys on the keyboard Faults View current faults in the system Outputs View the status of sounders and relays Use Enter or to jump from one output to the next Details available e Ifan output is enabled or disabled ON OFF e Ifan alarm event event 1 has
4. GE Interlogix KSA700 Series Analogue Addressable Fire Panels User Guide Version 2 1 September 2003 Kilsen is a GE Interlogix brand http Awww geindustrial com ge interlogix emea 2003 GE Interlogix B V All rights reserved GE Interlogix B V grants the right to reprint this manual for internal use only GE Interlogix B V reserves the right to change information without notice KSA700 Series User Guide CONTENTS 1 Introd CtiOn 2288 A TTE dre E EEE sens ap ie 4 1 1 General description and product range 4 1 2 Safety precautions and warnings ttt EAEn e teert EAEEren eree Eren 4 2 The Control Panel E E A A E Le E 5 2 1 General view of the control panel ss iissssieieseeeeeeererre 5 2 1 1 KSATO sms nan area r et eed ian a ea e Eea lianas 5 2 1 2 KSA702 700 nent ee deel ia ed eed 6 2 2 Keyboard fUNCONS 51s sec cece ev cece tise eh reader retenir Steves ces daa th ete a a destin 7 2 2 1 KOS nee idee codecs tie att ttes tube tie ethic teeth ed E Ls ne Ls teed tate be 7 2 2 2 Keypad sis E E ecb eeteeiveseseaceesvetee tev ete ee 7 2 2 3 L D INdICAtOrS sr sta vssadace cnc E ss DER e AT PNA Len NCA EEE casauoaavetete 7 2 3 Access levels and passwords c cccceeeeeeeeeeeeeeneeeeeeeeeeeeeeceeaaaeeeeeeeeeeeeeeneaaaeeeeeeeeeeeeseeenaaeeeeeeess 8 3 The User Menu cctecdeedastadsbacteddes odes caducceccatedscuiedex AVAE ASen serah A AESA ETRA tses Renien
5. ct Section Name Indication 8 3 Points breakdown signals 8 4 Total loss of power supply Controls 7 12 Coincidence detection 7 11 Output delay 95 Disconnection of an i addressable point 10 Test status Outputs 7 8 Fire alarm device output Auxiliary functions not required in the EN54 2 4 In addition to the compulsory and optional functions defined by EN54 2 4 this control panel incorporates the following functions not required by the standard e Auto search options e Allocation of 10 access level 2 passwords e Ability to configure by zone logical events general events etc e RS485 outputs e RS232 outputs e Auto search serial ports e Edition of points from the control unit e Edition of zones from the control unit e Edition of manoeuvre from the control unit e Storage of events in a history file e Language selection 17 KSA700 Series User Guide CE 55370008
6. e defined by the installer The user can access the panel controls and switch on and off zones and adjust the time and the date but cannot make changes in the configuration There are two additional access level reversed for the installation specialist and the manufacturer KSA700 Series User Guide 3 THE USER MENU 3 1 Introduction and menu access Instructions in this section refer to access level 2 See section 2 3 Access EES levels and passwords The LCD has 4 lines of information of 40 characters each The menu is structured in the following way MAIN MENU Exit 1 Configure 4 Enable 7 View 2 Test 5 Disable 3 Time 6 Print 1 Menu title 2 Menu options 3 Use the key to exit the current menu When set up of the system is complete and all devices configured the control panel displays the following message kkk kkk ALL CONNECTED DEVICES ARE AT NORMAL STATUS 00 00 0000 00 00 To access the user menu press Enter or and enter your password Once the password has been entered the Main Menu is displayed 3 2 The main menu MAIN MENU Exit 1 Configure 4 Enable 7 View 2 Test 5 Disable 3 Time 6 Print 3 2 1 Configure The Configure option is not available to standard users Configuration may only be performed by qualified personnel 3 2 2 Test Allows tests on the panel LED indicators and display From the Main Menu sel
7. e free contact relays an auxiliary 24 VDC output A PC printer modem GSM modem or Ethernet network connection module can be connected to the fire panel via the RS232 port This supports short distance communications up to 15 metres The RS485 port supports communications up to 1 2 Km and allows for the creation of connected fire and repeater panels networks Specifications vary depending on the model The fire panel is available in the following versions KSA701 2 One loop KSA701 2 Two loops KSA702 One or two loops expandable by the installer KSA705 One to five loops expandable by the installer KSA702P and KSA705P As per KSA702 705 but with built in printer 1 2 Safety precautions and warnings The proper way of supplying current to the panel is e First connect the mains 110 VAC or 230 VAC e Then connect the batteries Not following this recommendation may damage the system 4 KSA700 Series User Guide 2 THE CONTROL PANEL 2 1 General view of the control panel 2 1 1 KSA701 _ C_ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 TPS a e Cao D Co D DDD ES So GOO Ce Daa T Coo a RD SOP mo MODO a ss 2 G LCD Navigation and enter Alphanumeric keypad Exit menu key Change key Language card slots Earth Fault LED Relays Disabled LED Sounder Delay LED Sounder Fault Disabled LED System Fault LED S
8. eE sarii 9 3 1 Introduction and menu access 9 3 2 Thema Mensa n a ennemie tn eee eee 9 3 2 1 COMPIQU Re EEE M eet hs eee ch cet rt a Danes ah a ea a kara 9 3 2 2 IMOSTAL IEEE oe tae bathe A ae en O fe Ee sc Na ss ae ek 9 3 2 3 TIM seen retenir ere delenit dined E 10 3 2 4 Enable Disable 2 241 208nux ni einen intimement ile areia 10 3 2 5 ad aa EA EE REP Go E RU E EERS 13 3 2 6 AE E E EEE A E E EE E A E A A res 13 4 What to do in case of alarm or fault iiiissiiisssissscaneeereseeeresneenennres 15 5 Maintenance nn nn ne T E on d nn tes ere ae TERT 16 S 1 Bythe USer cnatan ro naie a a aa aa a a e a see dead reader ee ee ts 16 5 2 By the maintenance company ses 16 6 Ne POMGIGES R AET TET ATTA ate 2 Ses T E ATT 17 6 1 Appendix 1 Applicable standards 17 3 KSA700 Series User Guide 1 INTRODUCTION This fire panel has been designed and manufactured in compliance with EN54 2 and EN54 4 1997 standards This is a detailed manual for the proper use of the system To avoid potential problems and accidents it is advised that manual is studied before using this equipment 1 1 General description and product range This fire panel has been designed to guarantee high reliability and ease of use Its loop structure allows for flexible system configuration and expansion options In addition to the standard loop outputs the fire panel includes two serial ports RS232 and or RS485 two monitored sounder outputs two voltag
9. ect Test The following options appear 9 KSA700 Series User Guide 3 2 3 Time LED If selected the message Checking LEDs is displayed and the fire panel switches the panel LED indicators on one by one to verify all work properly LCD If selected the system tests the panel LCD Zone This option tests outputs alarms without requiring a manual reset of the system When selected the system asks if outputs should be released If yes the outputs will be activated briefly and then silenced automatically It is also possible to select which zones to test To check the outputs from zone 1 to zone 10 enter the following From Zone To Zone Release Outputs Zone test 001 010 YES The Test LED indicator will be lit and a test screen displayed in the LCD until the test is completed To cancel all tests and or return to the previous menu press the key Updates the system time setting The default time format is 24 hour 3 2 4 Enable Disable Zones devices the keyboard the delay mode and relays sounders may all be enabled ES 10 or disabled To Enable an item select Enable from the Main Menu The following menu is displayed ENABLE 1 Zone 2 Devices 3 Keyboard 4 Delayed Mode 5 Relay Sounders Exit To Disable an item select Disable from the Main Menu The following menu is displayed DISABLE 1 Zone 2 Devices 3 Keyboard
10. occurred e Ifan alarm event has occurred after a delay event 2 Relay Status Event 1 Event 2 1 ON 000 000 If the Silence Alarms or Sounders Silence key has been pressed before EES checking outputs all sounders will be shown as OFF Disabled Allows the operator to view zones and devices that have been disabled There are two options e Zones to check disabled zones either partially or completely Devices to check disabled detectors across the installation Events View all events recorded by the system Each event is identified with a number from 1 to 999 KSA700 Series User Guide 4 WHAT TO DO IN CASE OF ALARM OR FAULT Read the following steps carefully The operator must be familiar with the fire system and control panel LED indicators to react effectively to an alarm situation 1 KEEP CALM In an alarm situation the fire panel activates the sounders It is critical to remain calm at this time so that the correct decisions may be taken and procedures followed 2 PRESS ANY KEY AND ENTER THE USER PASSWORD Any key enables the keyboard in an alarm situation An access level password is required 3 SILENCE THE INTERNAL BUZZER Use the Silence Buzzer or Mute key to silence the internal buzzer Silencing sounders may also help create better conditions to assess the situation in case of a possible fire the sounders are automatically reactivated after a few moments if the fire condition has not been re
11. remain active 3 2 4 3 Keyboard The control panel keyboard may also be disabled by selecting Keyboard from the Disable Menu 11 KSA700 Series User Guide To re activate the keyboard a level 2 access password must be entered see section 2 3 Access levels and passwords 3 2 4 4 Delayed mode A time delay can be programmed in any zone for daylight hours or for a specified period of the day It may only be programmed in access level 3 i e by the installer but can be disabled and enabled as required from access level 2 Delay modes allow the user to verify the cause of the alarm before outputs relays and sounders are activated When this option is enabled the corresponding LEDs of the front panel are switched on When the fire panel detects a fire and a delay has been programmed only the fire panel internal buzzer is activated Through the LCD display and corresponding LEDs the system informs the operator about the device that originated the alarm and that the system is in the first phase of a delayed alarm By pressing the Silence Buzzer or Mute key the system moves into the second delayed alarm phase normally programmed to be long enough to allow confirmation of the cause of the alarm and apply the appropriate corrective actions If the Silence Buzzer key is NOT pressed the system moves into the confirmed alarm mode The fire panel must be Reset before the programmed delay for phase 2 has expired else the confirmed alarm
12. s Sounders Silence Silence Alarms Silences all sounders Silence Buzzer Mute Silences the internal buzzer while an incident or fault is investigated Reset Reset Resets the system Evacuation Sets the system to alarm status releasing all sounders and any other programmed events through the relay outputs 2 2 2 Keypad Use the alphanumeric keypad to e Enter text and numbers e Select menu options using the Change or keys e Cancel an operation and exit the current menu using the key e Confirm an entry using the Enter or keys e Navigate alarm faults in the display using the up down arrow keys e Navigate numeric fields using the left right arrow keys 2 2 3 LED indicators The main LED indicators in the control panel are KSA701 KSA702 705 Description Supply On Power Mains power is ON Fire Alarm An alarm has been detected and is indicated in the corresponding zone LED Fault Fault A general fault has been detected Disabled Disabled An output or device has been disconnected making the installation incomplete Full protection cannot be 7 KSA700 Series User Guide guaranteed Test Test Highlights that a test is being performed at a certain part of the installation Supply Fault Supply Fault The fire panel is not properly powered due to either a mains shutdown or a battery problem Sounder Fault One or more of the sounder outputs has a problem
13. s of the control panel implementing the appropriate corrective actions as required e Check all the battery connections and the voltage In each zone check the fire alarms faults and auxiliary functions of the control and signalling equipment e Check the control and signalling equipment to determine a possible increase in humidity or any other type of deterioration e Check if there has been any structural alteration that may affect the functioning of the detectors manual call points or sounders e Any defect must be noted down in the on site register and the corrective actions taken as soon as possible Annually e Put the control panel in Test and check the configuration of the system Verify that all the detectors and manual call points work according to the manufacturer s recommendations and programmed configuration e Visually inspect all the equipment connections and make sure they are safely fastened that they have not been damaged and that they are appropriately protected Examine and test all batteries e Any defect must be noted down in the on site register and corrective action taken as soon as possible KSA700 Series User Guide 6 APPENDICES 6 1 Appendix 1 Applicable standards This fire panel has been designed in compliance with EN54 2 and EN54 4 1997 standards EN54 2 includes basic and optional requirements The optional requirements included in this fire panel are Subje
14. set The cause of the alarm has still not been determined 4 IDENTIFY THE CAUSE The control panel LED indicators help identify the cause of the event that has triggered the current alarm e g fire fault etc 5 ACT If an alarm situation is confirmed follow the emergency procedures defined for your site 6 SYSTEM RESET Reset the system when all incidents have been solved 15 KSA700 Series User Guide 5 MAINTENANCE Maintenance measures recommended in EN54 14 and any other applicable local authority laws must be followed 5 1 Bythe user Daily The control panel must indicate normal functioning Any faults must be noted down in the register and the maintenance company called Check that any previously registered faults have been fixed Monthly As a minimum a manual call point or detector must be activated to test the control panel and the alarm devices connected to it It is recommended to test a different zone every month Any malfunction should be written down in the register taking corrective measures as soon as possible Batteries The batteries must be replaced periodically as recommended by the manufacturer The useful life of the battery is 4 years Avoid the total discharge of the batteries Cleaning The exterior of the control panel should be cleaned with a damp cloth Do not use solvents or liquids 5 2 By the maintenance company 16 Quarterly e Check the entries in the on site register and the record
15. upply Fault LED Out of Service LED keys Oo NOUSUNA N Silence Buzzer key LED Sounders Silence key LED Evacuation key LED Reset key Sounders On key LED Test LED Disabled LED Fault LED Fire LED Supply On LED Fault Disabled Test zone LED Fire zone LED KSA700 Series User Guide 2 1 2 KSA702 705 NU BY N gt oS 11 o z O O O O O O 0O 0 6 0 O e 0s 0 0 D 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 9 00000000000000000000 00000000000000000000 5 a L8e OS a LCD 13 Reset key Power LED 14 Sound Alarms Key Alarm LED 15 Silence Alarms key LED Test LED 16 Mute key LED Fault LED 17 Zone number System CPU Fault LED 18 Alarm zone LED Earth Fault LED 19 Fault Test Disabled zone LED Supply Fault LED 20 Alphanumeric keypad Sounder Fault LED 21 Change key Disabled LED 22 Exit Menu key Sounders Disabled LED 23 Navigation and Enter keys 12 Relays Disabled LED The KSA702 control panel includes 20 zone LEDs and the KSA705 includes 40 zone LEDs Both control panels are identical in all other respects KSA700 Series User Guide 2 2 Keyboard functions 2 2 1 Keys The main keys in the control panel are KSA701 KSA702 705 Description Sounders On Sound Alarms Activates all sounder
16. will be triggered Manual call points always trigger a confirmed alarm situation as no delay is ZS allowed When Delayed Mode is selected the system asks for the number of days that this delay mode should be active Using the Change or keys enter the required number Once activated the Delayed Mode LED is switched on LR To enable the delay mode permanently enter 200 days 3 2 4 5 Relay Sounders 12 This option is useful to check the system without releasing the sounders and outputs Select Relay Sounders from the Disable Menu and select the item to be disabled from the following screen 1 Sounders Enabled 2 Relays Enabled An access level password is requested to complete this option and a confirmation screen details the event KSA700 Series User Guide 3 2 5 Print 3 2 6 View 13 Event 1 of 1 at 00 00 RELAYS DISABLED Panel 1 If sounders or relays are disabled the fire panel will activate its internal buzzer to warn that outputs have been disconnected The internal buzzer can be silenced using the Silence Buzzer or Mute key Outputs may be enabled again following the same procedure in the Enable Menu The Print option in the Main Menu allows the operator to print system information using the built in printer KSA702P and KSA705P only or an external printer connected to the panel PRINT Exit 1 Devices 4 Disabled 2 History 5 Options 3 Mode