Operating instructions Pressure sensor PN70xx 706136 / 00 01

image

Contents

1. ifm electronic Operating instructions Pressure sensor efectorson PN70xx C 706136 00 12 Contents 1 Nole eee a 3 1 1 Symbols WSC issaraen asia eana EEE EAEE 9 2 Safety INS TUC ONS cnsiansicnadsssneencencianseasiganendenswdsaenscesaeanssapeannuraiudicsamrsiesdedadienseundars 3 3 Functions and features 4 ae A E 0 A A E A I 5 4 1 Communication parameter setting evaluation 5 4 2 Switching eee ee I nrnna 5 43 POSING MTN WOM u u uu eae 6 s rl uuu au su aasan 6 a cll al Connec io eee u yn a u anna maa 7 7 Operating and display elements u I ara 8 9 uuu Ne ee 22 9 ot the malu uuu u l l E 10 9 Parame rS l Ne 11 9 1 General parameter setting Jl l I a 1 9 2 Configuring the display optional l 13 9 3 Seting TIE output Signals JULI I li aaa 13 9 3 1 Setting OF I output LLL Lu ua 13 9 3 2 Setting of the switching limits 13 9 4 User settings optional ULU aaa 14 9 4 1 Setting of a time delay for the switching signals 14 9 4 2 Setting of the output logic for the switching outputs 14 9 4 3 Setting of the damping for the switching 00 14 95 Oe UIC eat OINS u u ee E 14 9 5 1 Reading
2. open Hnc hysteresis function normally closed Fno window function normally open Fnc window function normally closed dESI output 2 is used as a diagnostic output 9 3 2 Setting of the switching limits gt Select SP1 SP2 and set the value at which the output switches gt Select rP1 rP2 and set the value at which the output switches off rPx is always smaller than SPx The unit only accepts values which are lower than the value for SPx 9 4 User settings optional 9 4 1 Setting of a time delay for the switching signals 051 dS2 switch on delay for OUT1 OUT2 dr1 dr2 switch off delay for OUT1 OUT2 lt Select dS1 dS2 dr1 or dr2 and set a value between 0 2 and 50 s at 0 0 the delay time is not active 9 4 2 Setting of the output logic for the switching outputs gt Select P n and set PnP or nPn Pen 9 4 3 Setting of the damping for the switching outputs gt Select dAP and seta value dAP value response time between pressure change and change of the switching status in milliseconds Damping has also an effect on the display and the IO Link process value The following fix values can be set they define the switching frequency f of the output a s em 225 ooo e s 6 6 9 5 Service functions 9 5 1 Reading the min max values for the system pressure gt Select HI or LO press Set briefly
3. the FDT service program ifm Con tainer or other parameter setting tools with IO Link capability The program library of the available DTM objects and the IO Device Descrip tion IODD are available at www ifm com Service Download 4 2 Switching function OUTx changes its switching state if it is above or below the set switching limits SPx rPx The following switching functions can be selected Hysteresis function normally open OUx Hno fig 1 Hysteresis function normally closed OUx Hnc fig 1 First the set point SPx is set then the reset point rPx with the requested differ ence Window function normally open OUx Fno fig 2 Window function normally closed OUx Fnc fig 2 The width of the window can be set by means of the difference between SPx and rPx SPx upper value rPx lower value P system pressure HY hysteresis FE window 4 3 Diagnostic function Output 2 is used as diagnostic output based on the DESINA specification if OU2 dESI f there is no fault the output is switched and carries UB if P n PnP or UB if P n nPn In case of malfunctions in the following areas the output is inactive Measuring cell defect short circuit in output 1 5 Installation Before mounting and removing the sensor make sure that no pressure is applied to the system gt Insert the unit in a G process connection gt
4. the min max values for the system pressure 14 9 5 2 Reset all parameters to factory Setting 14 jac ac 7 EEEE 15 10 1 Reading of the set parameters 15 10 2 AUPE Sencar 15 Ll a N G O E A ere E EE 16 12 JECUNIC ADA lec oredr 16 Tales u uapa aasma asa 18 13 Factory SEUNG seisoin ianei ee ee aa oi 19 1 Preliminary note 1 1 Symbols used gt Instruction gt Reaction result Designation of pushbuttons buttons or indications Cross reference 1 Important note Non compliance can result in malfunctions or interference 2 Safety instructions e Please read this document prior to set up of the unit Ensure that the product is Suitable for your application without any restrictions the operating instructions or the technical data are not adhered to personal injury and or damage to property can occur Check the compatibility of the product materials chapter 12 Technical data with the media to be measured in all applications Use in gases at pressures gt 25 bar only after contacting the manufacturer ifm 3 Functions and features The unit monitors the system pressure of machines and plants Applications Type of pressure relative pressure Order no Measuring range Permissible Bursting pressure j g rang overpressure gp x bar PS br Psi br PS PN7000 0 400 0 5800 6
5. 0 8700 1000 14500 1 5214 11600 MPa bar 10 kPa bar x 100 Avoid static and dynamic overpressure exceeding the given overload pres sure by taking appropriate measures The indicated bursting pressure must not be exceeded Even if the bursting pressure is exceeded only for a short time the unit may be destroyed NOTE Risk of injury Use in gases at pressures gt 25 bar only after contacting the manufacturer ifm High pressure units 400 bar 600 bar are supplied with an integrated damping device to comply with the regulations for UL approval and to avoid any risk of injury in case of bursting when bursting pressure is exceeded When the damping device is removed the damping device can become unus able When the damping device is removed the unit can no longer be used under UL conditions If you have any questions please contact ifm electronic s sales specialists 4 Function 4 1 Communication parameter setting evaluation The unit displays the current process value t generates 2 output signals according to the parameter setting OUT1 Switching signal for process value IO Link 2 options OUT2 Switching signal for process value e Diagnostic signal output 2 is inactive in case of a fault The following function is available via IO Link OUT Reading the current process value changing the parameters and transferring them to other units of the same type using
6. C 20 80 UB gt 32 V 20 60 UB gt 32 V Medium temperature C 80 Storage temperature C 100 EMC EN 610004 2 ESD reiorciines inire arianen ara NEONA aE KEDE NAER 4 18 KV EN 61000 4 3 HF radiated IL a s a aasan vaisiniai 10 V m 0 anka aiins 2 KV EN G1000 4 5 DUGE uuu u l eR EE 0 5 1KV EN 61000 4 6 HF conducted 1 l I n 10 V to EN50178 SELV PELV in addition PTFE for PN7003 PN7009 for PN7000 PN7002 PN7060 4 for PN7003 PN7009 BFSL Best Fit Straight Line LS Limit Value Setting 7 18 increments AP LO LO LO pa Oo A cio eee Bees CPN j2 lt ojo RN Sl 5 gt SF ee c o gt 4 St I i Sr c lt cu cN 3l2 8 2 3 2 5 5 sie z Be s E2 000ZNd LOOZNd 3 6002 4 6002 VOOLNd 0 9002 Z00ZNd 600ZNd 12 1 Setting ranges SP1 SP2 rP1 rP2 8700 50 06 o os 57 03 AP increments 13 Factory setting Factory setting 25 VMR 23 VMR 75 VMR 73 VMR bAr mbAr the indicated percentage of the final value of the measuring range VMR of the corresponding sensor in bar mbar is set More information at www ifm com 19
7. HI maximum value LO minimum value Delete memory gt Select Hl or LO gt Press Set until is displayed gt Press Mode Enter briefly LO is available only for PN7004 and PN7009 9 5 2 Reset all parameters to factory setting gt Select rES gt Press Set and keep it pressed until is displayed gt Press Mode Enter briefly It is recommended to take down your own settings in the table before carry ing out a reset 13 Factory setting 10 Operation After power on the unit is in the Run mode normal operating mode It carries out its measurement and evaluation functions and provides output signals accord ing to the set parameters Operating indications chapter 7 Operating and display elements 10 1 Reading of the set parameters gt Press Mode Enter until the requested parameter is displayed gt Press Set briefly gt The unit displays the corresponding parameter value for about 15 s After UK another 15 5 the unit returns to the Run mode 10 2 Fault indication OL Overload pressure measuring range exceeded UL Underload pressure below measuring range SC1 j Short circuit in OUT1 SC2 j Short circuit in OUT2 Short circuit in both outputs Flashing internal fault The output concerned is switched off as long as the short circuit exists The messages SC1 SC2 SC and Err are shown even if the display is switched off 15 11 Scale drawin
8. Tighten firmly 6 Electrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to Voltage supply to EN50178 SELV PELV gt Disconnect power gt Connect the unit as follows 2 x p switching 2 x n switching 4 OUT 1 IO Link 2 OUT 2 Ub Pin 4 OUT1 binary switching output pressure monitoring IO Link i binary switching output if OU2 Hno Hnc Fno or Fnc Pee diagnostic output OU2 dESI Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black 7 Operating and display elements 09 IO O O Ore 1 to 8 Indicator LEDs LED 1 to LED 4 system pressure in unit of measurement as indicated on the label LED 4 not used for units with 3 adjustable units of measurement LEDs 5 and 6 not used LED 7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 digits Indication of the current system pressure Indication of the parameters and parameter values 10 Set pushbutton Setting of the parameter values scrolling by holding pressed incremental by pressing briefly 11 Mode Enter pushbutton Selection of the parameters and acknowledgement of the parameter values Q k C CJ CJ 8 1 Menu structure 8 Menu 8 2 Explanation of the menu SP1 rP1 Upper lower li
9. g Dimensions are in millimeters dimensions for PN7000 and PN7060 1 display 2 LED s 3 programming button 12 Technical data Operating voltage V Current consumption mA Current rating per switching output mA Reverse polarity protection overload protection Short circuit protection Integrated watchdog Voltage drop V Power on delay time s l l a 0 0 3 Switching frequency Hz max 170 16 Communication interface Baud rate KBAUD Accuracy deviations in of the span Set point accuracy Deviation of the characteristics gt 0 25 BFSL lt 0 5 LS Hysteresis lt 0 25 1 0 for PN7060 Repeatability in case of temperature fluctuations lt 10 K lt 0 1 Long term stability in of the span per 6 months Temperature coefficients TEMPCO in the compensated temperature range 0 80 C in of the span per 10 K Greatest TEMPCO of the zero point of the span lt 0 2 lt 02 Materials wetted parts stainless steel 303S22 ceramics FPM Viton Housing material stainless steel 304515 stainless steel 316L 1 4404 PBTP Pocan PEI FPM Viton 2 Protection Protection Insulation resistance MQ gt 100 500 V DC Shock resistance g 50 DIN IEC 68 2 27 11ms Vibration resistance g 20 DIN IEC 68 2 6 10 2000 Hz Switching cycles MIN 100 million 50 million for PN7060 Operating temperature
10. imum setting value Then the cycle starts again at the minimum setting value Acknowledgement of the parameter value gt Press Mode Enter briefly gt The parameter is displayed again The new setting value is stored Setting of other parameters gt Start again with step 1 Finishing the parameter setting gt Press Mode Enter several times until the current measured value is displayed or wait for 15 s gt The unit returns to the operating mode SLoc is displayed when attempting a modification of a parameter value the sensor is locked via software This locking can only be removed via a param eter setting software Change from menu level 1 to menu level 2 gt Press Mode Enter until EF is displayed If the submenu is protected with an ac cess code Cod1 flashes in the display lslslslsl gt Press Set and keep it pressed until Modis Set WEF the valid code no is displayed gt Press Mode Enter briefly On delivery by ifm electronic no access restriction gt Press Set briefly gt The first parameter of the sub menu GEE Dinas J is displayed here Uni oe With the user interface of the ifm Container program gt Activate the EF button menu level 2 is protected by an access code the input field for the code no is activated gt Enter valid code no Locking unlocking The unit can be locked electronically to prevent unintentional sett
11. ings gt Make sure that the unit is in the normal operating mode BEGG lt Press Mode Enter Set for 10 s Q gt Loc is displayed 10s During operation Loc is briefly displayed if you try to change parameter values For unlocking gt Press Mode Enter Set for 10 s bul oc gt uLoc is displayed o On delivery unlocked Timeout no button is pressed for 15 s during parameter setting the unit returns to the operat ing mode with unchanged values 12 13 9 2 Configuring the display optional gt Select Uni and set the unit of of measurement bar mbar MPa kPa PSI for PN7007 and PN7009 in addition inHg gt Select diS and set update rate and orientation of the display d1 Update of the measured value every 50 ms d2 Update of the measured value every 200 ms d3 Update of the measured value every 600 ms rd1 rd2 rd3 Display like 01 d2 d3 rotated by 180 OFF The display is deactivated in the operating mode 9 3 Setting the output signals 9 3 1 Setting of the output function gt Select OU1 and set the function Hno hysteresis function normally open Hnc hysteresis function normally closed Fno window function normally open Fnc window function normally closed gt Select OU2 and set the function Hno hysteresis function normally
12. mit value for system pressure at which OUT1 switches SP2 rP2 Upper lower limit value for system pressure at which OUT2 switches 001 Output function for OUT1 Switching signal for the pressure limit values hysteresis function H or window function F either normally open no or normally closed nc 002 Output function for OUT2 Switching signal for the pressure limit values hysteresis function H or window function F either normally open no or normally closed nc Diagnostic signal OU2 dESI Extended functions opening of menu level 2 Standard unit of measurement for system pressure Update rate and orientation of the display Restore factory settings 10 9 Parameter setting During parameter setting the unit remains in the operating mode It continues its monitoring function with the existing parameters until the parameter setting has been completed 9 1 General parameter setting 3 steps must be taken for each parameter setting Parameter selection gt Press Mode Enter until the re quested parameter is displayed Setting of the parameter value 4 Press Set and keep it pressed Current setting value of the param eter flashes for 5 s After 5 s setting value is changed incrementally by pressing the button once or continuously by keeping the button pressed Numerical values are incremented continuously To reduce the value let the display move to the max