Operating instructions Switching amplifiers N00
Contents
1. CE 02 2014 80009130 00 ifm electronic Operating instructions Switching amplifiers efectoring N00 A N05 A Qo O Qo Quo Qa Ss eee eg ood O Instructions for the safe use in hazardous areas 1 Use e Units which contain intrinsically safe circuits are used to operate intrinsically safe field units within hazardous areas e The manufacturer s data sheets must be observed e The units are not suitable for the separation of signals in power measurement technology e The laws and regulations applicable to the use or intended application must be adhered to 2 Mounting In principle two different types of mounting are possible le 2 Mounting on 35mm rail the units are clipped onto the rail Wall mounting pull out 2 tabs at the bottom of the unit then fix the unit with 4mm screws 3 Setup installation The units have the protection rating IP20 in accordance with EN 60529 and must therefore be protected accordingly when exposed to adverse environmen tal conditions such as water splashes or dirt exceeding the soiling degree 2 The units must be mounted outside the hazardous area For units with intrinsically safe circuits the protected circuit light blue marking on the unit may be connected into hazardous areas Special care must be ta ken for a safe separation from all non intrinsically safe circuits The intrinsically safe circuits must be installed in accordance with the applicable
2. e corresponding output is not active transistor blocked relay de energised 3 LED green Lights when supply voltage is applied 4 Selector switch Programming of the output function S1 S1 S2 1 direct operation 5 Selector switch output switches like input signal IN ON OUT ON S2 S1 S2 2 inverted operation output switches opposed to the input signal IN ON gt OUT OFF For single channel units S2 has no function 6 Selector switch Setting for short circuit wire monitoring S3 e When proximity switches are connected monitoring is always active S3 must be in position l e When mechanical switches are connected the following applies Monitoring active for input circuit no 1 S3 must be in position I Without short circuit monitoring for input circuit no 2 and S3 in position Without short circuit and wire monitoring for input circuit no 3 and S3 in position Il 6 Wiring Mechanical switches input circuit no 7 Type test certificate Electrical values Article no Type test Max permissible values of the control circuits in type certificate of protection intrinsic safety Ex ia IIC IIB Ex ib IIC IIB N0030A PTB 02 Voltage 10 6 V N0031A ATEX 2035 Current 19 1 mA N0032A Power 51 mW N0033A External inductance 97 mH IIC 390 mH IIB External capacitance 2 32 uF IIC 16 2 uF IIB N0530A PTB 02 Voltage 10 5 V N0533A ATEX 2036 Current 13 mA Power 34 mW E
3. installation regulations For the connection of the intrinsically safe field units to the intrinsically safe circuits of the switching amplifiers the relevant maximum values of the field unit and the switching amplifier according to the explosion protection must be observed proof of intrinsic safety When the intrinsically safe circuits are used in hazardous dust areas D only certified field units are allowed to be connected The EC certificates of conformity and EC type test certificates must be adhered to Compliance with the Special Conditions which may be included therein is especially important 4 Maintenance repair The transmission characteristics of the units are stable over long periods regular adjustment or such like is therefore not necessary No maintenance is required 5 Rectification of faults Units that are operated in combination with hazardous areas must not be modified Uday Only specially qualified and authorised personnel are allowed to repair the unit Insulation coordination for units with Ex certificate in accordance with EN 60079 11 The units are rated for use in soiling degree 2 in accordance with DIN EN 50178 1 LEDs yellow Indication of the switching status output 1 output 2 lights when the corresponding output is switched the relay is energised 2 LEDs red Fault indication for input circuit 1 input circuit 2 lights in case of wire break or short circuit in the respective input circuit Th
4. xternal inductance 210 mH IIC 840 mH IIB External capacitance 2 41 uF IIC 16 8 uF IIB N0531A PTB 02 Voltage 10 5 V N0532A ATEX 2037 Current 13 mA N0534A Power 34 mW External inductance 200 mH IIC 740 mH IIB External capacitance 2 4 uF IIC 16 8 uF IIB Marking II 1 G Ex ia IIC i 1 D Ex ia IIIC
Download Pdf Manuals
Related Search
Related Contents
MANUAL DE INSTRUCCIONES INSTRUCCIONES 「学習指導と評価の改善・充実」 Westinghouse One-Light Adjustable Mini Pendant 6100700 Specification Sheet Hands Free Telephone System Whirlpool 19760268A User's Manual AD822 Planos y Presupuesto (PAPEL OFICIAL) Copyright © All rights reserved.
Failed to retrieve file