Home
Corrigo E - User Manual - Xref controls e-shop
Contents
1. 3 2 2 Inputs and outputs The list of input and output functions in section 3 2 3 is handy instrument to help you keep track of which inputs and outputs you will need to configure Analogue inputs Analogue inputs must refer to an A gnd terminal placed in the same terminal block as the input being wired Analogue inputs can depending on the configuration be used for either PT1000 temperature sensors or for 0 10 V DC analogue input signals for example from a pressure transmitter Digital inputs Digital inputs must refer to C on terminal 4 Digital inputs may only be wired to voltage free contacts Any external voltage applied to digital input may harm the unit Universal inputs universal input can be configured to act as either an analogue input or as digital input universal input configured as analogue input must refer to an A gnd terminal placed in the same terminal block as the input being wired universal inputs configured an analogue input can depending on the configuration be used for either PT 1000 temperature sensors or for 0 10 V DC analogue input signals for example from a pressure transmitter universal input configured as digital input must refer to C on terminal 4 It may only be wired to voltage free contacts Corrigo E Heating manual revision G Chapter Installation and wiring 8 Analogue outputs Analogue outputs must refer to the A gnd terminal placed in the AO
2. 0O YV Down There are seven buttons 4 arrow buttons which will be called UP DOWN RIGHT and LEFT The menus in the Corrigo E are organized in a horizontal tree structure The UP DOWN buttons are used to move between menus at the present menu level The RIGHT LEFT buttons are used to move between menu levels When changing parameters the UP DOWN buttons are used to increase decrease the value of the parameter and the RIGHT LEFT buttons to move between digits within the parameter e The OK button is used to confirm the choice of a parameter setting e The C button is used to abort an initiated parameter change and restore the original value e The ALARM button marked with a red button top is used to access the alarm list Corrigo Heating manual revision Chapter 6 Display LEDs and buttons 22 6 4 Navigating the menus The start display the display normally shown is at the root of the menu tree Pressing DOWN will move you through the menu choices at this the lowest level UP will move you back through the choices To enter higher menu level use UP or DOWN to place the display marker opposite the menu you wish to access and press RIGHT If you have sufficient log on privileges the display will change to the menu you have chosen At each level there may be several new menus through which you may move using the UP DOWN buttons Sometimes there are further submenus linked to a menu or menu item T
3. Time 1 6 17 Outdoor temp Time is limited to maximum 60 minutes 5 1 8 Night set back Lowering of the night temperature is set in room temperature degrees The corresponding lowering of the supply temperature is calculated by the controller by multiplying the value by 3 The Corrigo has individual schedules for each heating system with two comfort temperature periods per day 5 1 9 Power limitation Using a digital input the power to the heating systems can be temporarily restricted When activated the setpoints are lowered by a settable factor relative to 20 C The limitation applies to all configured heating systems The limitation is calculated as below Limited setpoint 20 Setpoint 20 Factor 100 Factor 100 gives no setpoint reduction 0 gives full reduction to 20 C 5 2 Tap hot water 5 2 0 General Corrigo E can be configured for one or two tap hot water systems HW1 and HW2 These have constant supply temperature control 5 2 1 Controllers The heating system controllers are PID controllers with settable P band I time and D time 5 2 3 Night set back The Corrigo E has individual schedules for each hot water system with two normal temperature periods per day Corrigo E Heating manual revision G Chapter 5 Functional description 18 5 2 4 Pump control HW1 only Corrigo E has a digital output signal that can be used to control the hot water circulation pump in HW1 The pump will r
4. 1 07 00 16 00 Per 2 00 00 00 00 10 4 Timer outputs 1 5 10 5 Holidays Up to 5 digital outputs can be configured as timer outputs each with separate week schedule with two activation periods per day Holiday schedules take precedence over other schedules Timer output 2 Wednesday Per 1 05 30 08 00 Per 2 17 00 23 00 Up to 24 separate holiday periods for a full year can be set holiday period can be any number of consecutive days from one and upwards The dates are in the format MM DD When the current date falls within holiday period the scheduler will use the settings for the weekday Holiday Holidays mm dd 1 01 01 02 01 2 09 04 12 04 3 01 05 01 05 Corrigo E Heating manual revision G Chapter 10 Time settings 42 Chapter 11 Actual Setpoint In this menu group all actual current values and setpoint values are displayed and providing sufficiently high log on level is used all setpoints can be changed The following menus are available providing that the corresponding input is activated 11 1 Setpoint Heating systems HS1 HS2 and HS3 Outdoortemp 18 4 C HS1 Act 19 8 C Setp gt Setp 20 0 C Submenu Setpoint In between values are calculated using straight lines between breakpoints Setpoints for temperatures lower than the lowest breakpoint and higher than the highest breakpoint are calculated by extending the li
5. Corrigo E can be configured for 1 to 3 heating systems radiator groups HS1 HS2 and HS3 5 1 1 Controllers The heating system controllers are PI controllers with settable P band and I time 5 1 2 Control curves The controllers have individual outdoor temperature supply temperature control curves Each curve has 8 fix points The default setting of the outdoor temperature values for the fix points are 20 15 10 5 0 5 10 15 These can not be changed using the Corrigo front panel but can be changed using E tool The corresponding supply temperature values are settable using the front panel or E tool 5 1 3 Adaptation of curves Room sensors can be used to correct the control curves The average room temperature error over 24 hours is calculated Values 1 hour before and 1 hour after day night or night day change over are ignored The curves are corrected once daily using the average room temperature error and settable correction factor The correction will be parallel displacement of the entire curve using the following formula Displacement Room setpoint Average temp Factor 5 1 4 Pump control Each system can have single or double pumps Double pumps are run one at a time with automatic weekly change over and automatic start of the backup pump on malfunction of the active pump Outdoor temperature dependent pump stop can be configured Pumps are exercised for 5 minutes at 3 pm daily 5 1
6. 00 C m s Corrigo E Heating manual revision G Chapter 11 Actual Setpoint 44 Chapter 12 Manual Auto General In this menu the running mode of the unit and all the configured outputs can be manually controlled This is very handy feature which simplifies the checking of individual functions in the Corrigo It is also possible to manually control each of the temperature output signals individually the configured digital outputs can be set to On Off or Auto Since leaving any of the outputs in manual control will disrupt the normal control an alarm will be generated as soon as any output is set to a manual mode Since the menus vary according to the configuration of the outputs only the most common ones will be shown here For the digital signals you can normally choose between Auto and On and Off or similar words indicating the two possible manual states of the digital output Heating systems HS1 HS2 and HS3 Manual Auto HS1 Auto Manual set 0 0 Hot water circuits HWC1 and HWC2 Manual Auto HWC1 Auto Manual set 0 0 Pressure control Pressure control Auto Manual set Minmum set 0 0 Pumps HS1 HS2 and HS3 Manual Auto HS1 P1A Auto P1B Auto Pump HWC1 Manual Auto HWC1 Auto Frequency converter start Manual Auto Frequency conv Auto Corrigo E Heating manual revision G Chapter 12 Ma
7. 47 Heating systems 17 Holidays 42 HS Heating System supply 28 HS_ Night Set back 41 HWC_ Night set back 42 Inputs and outputs 8 26 Analogue inputs 8 Analogue outputs 9 Digital inputs 8 Digital outputs 9 Input and output lists 9 Universal inputs 8 L Leakage monitoring 31 48 LEDs 22 Log off 24 Log on 24 Menus 23 Modbus 36 N Navigating the menus 23 O Outputs See Inputs and outputs P Password 24 Power limitation 34 Pressure control 19 Settings 38 Pulse inputs 31 Pump stop 29 R Remote control 36 Return water temperature 29 Revision number 49 Run indication Motor protection 30 Running time 3 pos actuators 30 5 SMS 37 Split of output signal 34 Start screen 35 Storage tank 19 Summer time adjustment 36 T Tap hot water 18 Temperature control Settings 38 Time Date 41 Timer channel outputs 21 Timer outputs 42 U Universal inputs 8 AB Regin Phone 46 31 720 02 00 REGIN Box 116 SE 428 22 K llered Sweden Fax 46 31 9401 46 Visiting address Bang rdsv gen 35 www regin se info regin se THE CHALLENGER IN BUILDING AUTOMATION
8. 5 Frost protection If a controller is set to Off or Man ual control and the outdoor temperature is below a settable value a minimum settable supply temperature will be maintained and the pump will run 5 1 6 Wind compensation To compensate for wind chilling it is possible to connect a wind sensor and generate a setpoint displacement according to a settable factor C per m s Corrigo E Heating manual revision G Chapter 5 Functional description 17 5 1 7 Building inertia and boost The building inertia is settable to one of three levels None Medium High The set inertia dictates the influence of outdoor temperature With no inertia the outdoor temperature is used directly with medium inertia one hour average 15 used and with high inertia 12 hour average is used Boost is used to speed up the raising of the indoor temperature when switching from night set back temperature to normal comfort temperature This is done by temporarily displacing the supply temperature set point curve The following conditions must be met e Average outdoor temperature lower than 17 C e Supply set point value higher than 25 C e Night set back more than 2 C room temperature The displacement is calculated as follows Displacem Factor 17 outdoor temp night set back Where Factor is settable 0 10 where 0 gives no boost and 10 gives high boost The time in minutes that boost will be active is calculated as follows
9. DC Reference for digital inputs DI 53 10 G Reference for digital outputs DO 57 Net 11 DOI 58 Net LON connection LON versions only 12 DO2 59 Egnd 30 Agnd Reference pole for analogue inputs 71 Dil 31 AH 72 32 AD 73 DI3 90 Agnd Reference for analogue outputs 91 AOI Corrigo E Heating manual revision G Chapter 1 14 Chapter 4 Commissioning General Before the Corrigo can be used it must be configured inputs and outputs must be assigned and all relevant parameters must be set All commissioning can be done using the Corrigo front panel display and buttons or using the display unit E DSP Corrigo E tool The best way however is to configure the Corrigo E by using Corrigo E tool Corrigo E tool is PC based configuration program specially developed to simplify the commissioning of the Corrigo E series When using E tool the whole configuration and all settings can be done on the computer and then downloaded to the Corrigo An infinite number of different configurations can be saved in computer memory for later use 4 1 How to do it For configuration using E tool see the E tool manual For configuration using the front panel there are two ways to go depending on how much help you need Option 1 e Jump straight to chapter 6 and 7 Display buttons and LEDs and Access rights e After mastering the button and menu system connect power to your Corrigo log
10. IEC60068 2 6 Test FC vibration Sinusoidal Shock 5 aee RS Sepa pb RIPE IEC60068 2 27 Test Ea Free falli eR o en REPE IEC60068 2 27 Test Ed Storage Climatic conditions according to IEC 721 3 1 sese Class 1k3 Ambient temperature 20 70 C Ait humidity tenk Max 95 RH Battery jb Pp ales Replaceable Lithium cell Battery au DRUSI nU Re e gibt Better than 5 years NANG NANA Low battery warning Battery backup ette ee ere eR deu en Memory and real time clock Communication EXOline Port 1 insulated via a built in RS485 contact The basic version of Corrigo E can communicate with Modbus You do not need an activation code Corrigo E can be ordered with a communication port for TCP IP or LON Corrigo E Heating manual revision G Chapter 2 About Corrigo E 6 CE marking Conforms with the EMC standards CENELEC EN61000 6 3 2001 CENELEC EN61000 6 1 2001 Inputs Analogue inputs AL sees Settable 0 10 V DC or PT1000 12 bit A D Digital inputs DE ree er intere Harden Potential free closure Universal inputs UI eee Can be set to act as either an analogue input or a digital input with specifications as above Outputs Analogue outputs AO sss Settable 0 10 V DC 2 10 V DC 10 0 V DC or 10 2 V DC 8 bit D A short circuit protected Digital outputs DO eee Triac ou
11. this menu to change the display language Choose language English Note This menu is also directly accessible by holding the OK button depressed during power up 8 14 2 Choose start screen the text normally shown on the display There are 4 different to choose from Type 1 The second line shows date and time The third line shows the text HS1 The fourth line shows the present temperature setpoint and actual values for HS1 Heating Regulator 04 03 15 11 28 HS1 Sp 32 89C Act 33 19C Type 2 The second line shows date and time The third line shows the text HWC1 The fourth line shows the present temperature setpoint and actual values for HWC1 Heating Regulator 04 03 15 11 28 HWC1 Sp 55 09C Act 54 8 C Type 3 The second line shows the text HS1 HWC1 The third line shows the present temperature setpoint and actual values for HS1 The fourth line shows the present temperature setpoint and actual values for HWC1 Heating Regulator HS1 HWC1 Sp 32 89C Act 33 1 C Sp 55 09C Act 54 8 C Corrigo E Heating manual revision G Chapter 8 Configuration 35 Type 4 The second line shows the outdoor temperature The third line shows the text HS1 The fourth line shows the present temperature setpoint and actual values for HS1 Heating Regulator Outdoor temp 8 2 C HS1 Sp 32 89C Act 33 19C 8 14 3 Automatic summer time adjustment The internal
12. when the start up display is shown until the arrow marker to the left of the text list points to Access rights Press right arrow Log on Log off Change password Log on Enter password Actual level In this menu it is possible to log on to any level by entering the appropriate 4 digit code The log on menu will also be displayed should you try to gain access to menu or try to do an operation requiring higher authority than you have Press the OK button and cursor marker will appear at the first digit position Repeatedly press the up arrow until the correct digit is displayed Press the right arrow to move to the next position Repeat the procedure until all four digits are displayed Then press OK to confirm After short while the text on the line Present level will change to display the new log on level Press left arrow to leave the menu Use this menu to log off from the present level to the basic no log on level Log off No Actual level System Logoff is also initiated automatically 5 minutes after the last time button is pressed 7 3 Change password As default Corrigo comes with the following passwords for the different levels System 1111 Operator 3333 Basic 5555 You can only change the password for log on levels lower or equal to the presently active level 1 if you are logged in as System you can change all passwords but as Operator you can only c
13. yesterday e 24 hour usage in kWh day before yesterday e Total usage in kWh or MWh The value is resettable 5 7 2 Power values Heating power is calculated by measuring the time between the energy pulses The following power values are calculated e Instantaneous value for a certain time or after a certain number of pulses e Average of the above instantaneous value for the last hour e Maximum value for the above instantaneous value 5 7 3 Leakage monitoring Once a week the control valves will be closed and the energy usage measured for a preset time An alarm is generated if the energy leakage is larger than a settable value default 3000 W The time for and duration of the leakage monitoring is settable Default is Sundays at 2 00 am for 30 minutes 5 7 4 Alarms Pulse error If no pulses are detected within a settable time an alarm is activated Setting the time to 0 inhibits the alarm function High usage If the daily usage is higher than a settable value an alarm is activated 5 8 Electricity meter One digital pulse function can be configured for electricity energy monitoring The pulse constant is settable 5 8 1 Usage values Total usage in MWh The value is resettable Corrigo E Heating manual revision G Chapter 5 Functional description 20 5 9 Timer channel outputs 5 10 Alarms Up to 5 digital outputs can be used as timer controlled outputs These can be used for controlling for example door locks lightin
14. AI 34 Supply temp hot water sequence 1 HW 1 90 Agnd Reference for analogue outputs AO 35 AI4 Return temp heating sequence 1 HS1 91 Actuator Heating sequencel 1 92 AO2 Actuator Heating sequence2 HS2 40 Agnd Reference pole for universal inputs UI 93 Actuator Heating sequence3 HS3 41 UII Supply temp heating sequence 2 HS2 94 A04 42 UD Return temp heating sequence 2 HS2 95 5 43 Agnd Reference pole for universal inputs 44 UB Room sensor heating sequence 1 HS1 45 94 Room sensor heating sequence 2 HS2 Wiring diagram Corrigo E15H factory configuration 1 G 50 B Supply voltage 24 V AC 15 50 60 Hz Ee 65485 EXOline Modbus 3 Protective earth 52 4 C 24 V DC Reference for digital inputs DI 53 10 G Reference for digital outputs DO 57 Net 11 Start stop pump PLA HS1 58 Net LON connection LON versions only 12 DO2 Start stop pump PIB HS1 59 Egnd 13 Start stop pump PI HWI 14 DO4 Sum alarm 71 DH Run indication alarm pump PLA HS1 72 DI2 Run indication alarm pump P1B HS1 30 Agnd Reference pole for analogue inputs AI 73 DB Run indication alarm pump P1 HW1 31 Outdoor temperature sensor 74 DI4 Pressure switch expansion vessel 32 AD Supply temp heating sequence 1 HS1 33 Agnd Reference pole for analogue inputs AI 90 Agnd Reference for analogue outputs AO 34 AB Supply temp hot w
15. High HWCI HWC I temperature too high 20 HghHWC2 HWC2 temperature too high 21 Boilerhigh Boiler temperature too high 22 Boilerlow Boiler temperature too low 23 Pulse error volume No pulses from water volume meter 24 Pulse error energy No pulses from energy meter 25 High cold water 24 hour cold water usage higher than limit 26 Highenergy 24 hour energy usage higher than limit OTN fr Corrigo Heating manual revision G Chapter 8 Configuration 32 Alarm text Description 27 High cold water hour B water usage hour higher than min limit 28 High leakage Leakage higher than set value 29 Malf PLA amp B HSI Malfunction both circulation pumps and PIB HS1 30 Malf amp 52 Malfunction both circulation pumps and PIB in HS2 31 Malf PLA amp B HS3 Malfunction both circulation pumps P1A and PIB in HS3 32 Pulse error CW1 No pulses from cold water meter 1 33 Pulse error CW2 No pulses from cold water meter 2 34 HS1 in manual mode 35 HS2 in manual mode 36 HS3 in manual mode 37 HWC 1 in manual mode 38 HWC2 in manual mode 39 Pressure control in manual mode 40 Boiler in manual mode 41 1 1 in manual mode 42 P1B HSI in manual mode 43 P1A HS2 in manual mode 44 P1B HS2 in manual mode 45 P1A HS3 in manual mode 46 P1B HS3 in manual mode 47 P1 HWC1 in manual mod
16. These outputs can be used to control lighting doorlocks etc Time Date HS1 Night setback HS2 Night setback HS3 Night setback HWC1 Night setback HWC2 Night setback Timer outputl Timer output2 Timer output3 Timer output4 Timer output5 Holidays This menu shows and permits the setting of time and date Time is shown in 24 hour format Date is shown in the format YY MM DD Time 18 21 Date 04 02 23 Weekday Monday 10 2 HS Night Set back HS1 Night Setback On 5 0 room degrees Setting comfort temperature periods For each control system there are 8 separate setting menus one for each weekday and one extra for holidays Holiday schedules take precedence over other schedules For 24 hour running set a period to 00 00 24 00 To disable a period set it to 00 00 00 00 HS1 Comfort time Monday Per 1 07 00 16 00 Per 2 00 00 00 00 Corrigo E Heating manual revision G Chapter 10 Time settings 41 10 3 HWC Night set back HWC1 Night setback On 2 5 0 OC Pump stop Off Setting comfort temperature periods For each control system there are 8 separate setting menus one for each weekday and one extra for holidays Holiday schedules take precedence over other schedules For 24 hour running set period to 00 00 24 00 To disable a period set it to 00 00 0 00 1 Comfort time Monday
17. analogue and digital inputs and outputs As you read mark in the list the inputs and outputs you will be using for the application you are building Note that the universal inputs in Corrigo E28 can individually be configured as either analogue or digital inputs Display buttons and LEDs Read chapter 6 on how to use the front panel buttons to navigate the Corrigo E menu system Access rights Chapter 7 Learn how to log in on the Corrigo E Configuration Chapter 8 Configuration Connect power to the Corrigo Using the buttons and menu system go through the configuration menus covering the functions you wish to use On delivery the units already have the inputs and outputs assigned to various functions These can of course be changed In chapter 3 Installation and wiring there are two sets of wiring diagrams one set showing the pre configured input output configuration and one set where you can fill your own configuration choices Settings Set the control parameters P band I time for the temperature control loops in use Set the alarm parameters alarm levels and delay times Timer settings Set the clock and calendar functions Setpoints Set all the setpoints for all active control loops Hand Auto Learn to use manual control Very useful for testing out your system Corrigo E Heating manual revision G Chapter 4 Commissioning 16 Chapter 5 Functional description 5 1 Heating systems 5 1 0 General
18. art 1 will be activated Should the temperature fall below Start temperature 2 the digital output Start 2 will be activated Any active outputs will be deactivated when the boiler temperature rises above the set Stop temperature 5 6 Cold water monitoring One or two circuits monitoring the cold water usage can be configured each using a digital pulse input from water meter The pulse constant is settable Maximum pulse rate is 2 Hz 5 6 1 Values The following values are calculated e 24 hour usage in litres today e 24 hour usage in litres yesterday e 24 hour usage in litres day before yesterday e Lowest hourly usage in litres today e Lowest hourly usage in litres yesterday e Usage total in m The value is resettable e Water flow litres min Corrigo E Heating manual revision G Chapter 5 Functional description 19 5 6 2 Alarms Pulse error If no pulses are detected within a settable time an alarm is activated Setting the time to 0 inhibits the alarm function High usage If the daily usage is higher than settable value an alarm is activated Leakage control If the lowest hourly usage during the previous day is higher than settable value an alarm is activated 5 7 Energy monitoring One digital pulse function can be configured for heating energy monitoring The pulse constant is settable 5 7 1 Usage values The following usage values are calculated e 24 hour usage in kWh today e 24 hour usage in kWh
19. ater sequence 1 HW 1 91 AOI Actuator Heating sequencel HS1 35 AI4 Return temp heating sequence 1 HS1 92 AO2 Actuator Heating sequence2 HS2 93 Actuator Heating sequence3 HS3 Corrigo E Heating manual revision G Chapter I 12 Wiring diagram Corrigo E8H factory configuration 1 G 50 B Supply voltage 24 V AC 15 50 60 Hz SM ila RS485 EXOline Modbus 3 Protective earth 52 N 4 C 24 V DC Reference for digital inputs DI 53 E 10 G Reference for digital outputs DO 57 Net 11 Start stop pump 1 11 58 Net LON connection LON versions only 12 DO2 Start stop pump PIB HS11 59 Egnd 30 Agnd Reference pole for analogue inputs AI 71 Dil Run indication alarm pump PLA HS1 31 Outdoor temperature sensor 72 DD Run indication alarm pump P1B HS1 32 AD Supply temp heating sequence 1 HS1 73 DB Pressure switch expansion vessel 90 Agnd Reference for analogue output AO 91 AOL Actuator Heating sequencel HS1 Empty wiring diagram Corrigo E28H 1 G 50 B Supply voltage 24 V AC 15 50 60 Hz zaa RS485 EXOline Modbus 3 Protective earth 52 N 4 C 24 V DC Reference for digital inputs DI 53 E 10 G Reference for digital outputs DO 57 Net 11 DOI 58 Net LON connect
20. clock is normally configured for automatic summertime wintertime adjustment The function can be disabled in this menu When enabled the clock will be advanced one hour at 02 00 am the last Sunday of March and retarded one hour at 03 00 am the last Sunday of October Automatic summer winter time change over Yes 8 14 4 Address Corrigo uses the addresses below when connecting to Corrigo E tool and when multiple controllers are connected in a network E tool normally uses the addresses below so if an address is changed the new address must also be entered in E tool If several Corrigo are connected in network all the units must have the same ELA address but each unit must have unique PLA address Address PLA 254 ELA 254 8 14 5 Display anywhere Remote control If multiple Corrigo units are connected in network it is possible to remote control unit in the network from a unit with display You do this by entering the address of the unit you wish to remote control in the unit with display The function is aborted by pressing the buttons UP OK and DOWN simultaneously Address for remote communication PLA ELA 00 00 8 14 6 Communication code Modbus If Corrigo is to be wired to network for Modbus communication special code must be purchased from Regin Entering the code unlocks the unit so the addresses can be changed The code is unique for each Corrigo and is serial
21. d lt P gt Corrigo E User Manual Heating THE CHALLENGER IN BUILDING AUTOMATION DISCLAIMER The information in this manual has been carefully checked and is believed to be correct Regin however makes no warranties as regards the contents of this manual and users are requested to report errors discrepancies or ambiguities to Regin so that corrections may be made in future editions The information in this document is subject to change without prior notification The software described in this document is supplied under licence by Regin and may be used or copied only in accordance with the terms of the licence No part of this document may be reproduced or transmitted in any form in any fashion electronically or mechanically without the express written permission of Regin COPYRIGHT O AB Regin All rights reserved TRADEMARKS Corrigo E tool EXOdesigner EXOreal EXO4 EXOline EXO4 Web Server Optigo Regio and Regio Tool are registered trademarks of AB Regin Windows Windows 2000 Windows XP and Windows Server 2003 are registered trademarks of Microsoft Corporation Some product names mentioned in this document are used for identification purposes only and may be the registered trademarks of their respective companies Revision G Dec 2007 Document Revision 1 7 1 01 Table of contents Chapter I About the manual Chapter 2 About Corrigo E Chapter 3 Installation and wiring Chapter 4 Commissioning Chap
22. e 48 P1 HWC2 in manual mode 49 P1 frequency controlled in manual 50 HSI Supply max HS1 supply temp maximum limit activated 51 HS2 Supply max HS2 supply temp maximum limit activated 52 HS3 Supply HS3 supply temp maximum limit activated 53 HSI Supply min HS1 supply temp minimum limit activated 54 HS2 Supply min HS2 supply temp minimum limit activated 55 HS3 Supply min HS3 supply temp minimum limit activated 56 HSI Returnmax 1 return temp maximum limit activated 57 HS2Retunmax HS2 return temp maximum limit activated 58 HS3Retummax HS3 return temp maximum limit activated 59 HSI Retummin 1 return temp minimum limit activated 60 HS2Retummin HS2 return temp minimum limit activated 61 HS3Retummin HS3 return temp minimum limit activated 62 HSI Frost 1 frost protection active 63 HS2Frost HS2 frost protection active 64 HS3 Frot HS3 frost protection active 65 Battery error Malfunction of the internal memory backup battery Corrigo E Heating manual revision G Chapter 8 Configuration 8 13 Other parameters A collection of different parameters that did not fit into any of the other menus 8 13 1 Building inertia and boost For detailed information see 5 1 7 Building inertia and boost The building inertia is settable to one of three levels None Medium or High The displacement is calculated as follows Disp
23. g laundry room equipment etc Each timer has its own scheduler with two activation periods for each day of the week and year based holiday calendar 5 10 1 Alarm handling Alarms are indicated by the alarm LED on the front All alarms can be monitored acknowledged and blocked using the display and buttons 5 10 2 Alarm priorities Alarms can be given different priority levels Digital outputs can be bound to act as alarm outputs for different priority levels Using the front panel it is possible to change the alarm priority level A B C alarm Not active of any alarm Corrigo E Heating manual revision G Chapter 5 Functional description 21 Chapter 6 Display LEDs and buttons 6 1 Display 6 2 LEDs 6 3 Buttons This section is applicable to Corrigo E units with display and buttons but also to the hand terminal E DSP which can be connected to Corrigo E units without display and buttons The display has 4 rows of 20 characters It has background illumination The illumination will normally be off but will activated as soon as any button is pressed The illumination will be turned off again after period of inactivity There are two LEDs on the front The alarm LED marked with the amp symbol The write enable LED marked with the symbol The four LEDs placed next to the upper terminal strip will be described later Alarm LED 4 Write LED Alarm O Up Left lt OK Right OK
24. hange the Operator and Basic passwords There is no point in changing the Basic password since access to that level is granted automatically to all users Corrigo E Heating manual revision G Chapter 7 Access rights 24 Change password for level Operator New password 7 4 Forgotten your password If the password for System has been changed and then lost a temporary password can be obtained from Regin This code is date dependent and only valid for one day Corrigo E Heating manual revision G Chapter 7 Access rights 25 Chapter 8 Configuration Start by logging on at System level See section Access rights above Using DOWN set the display marker opposite the menu title Configuration and press RIGHT The main configuration menu will be shown Inputs Outputs HS Supply Return temp Pump stop Twin Single pump Run ind Motor prot Actuator type Actuator run time Actuator exercise Leakage monitoring Pulse inputs Alarm config Other params System 8 1 In and Outputs Analogue inputs Digital inputs Universal inputs Analogue outputs Digital outputs General Free configuration Any control signal can be bound to any input output the only restriction being that digital signals cannot be bound to analogue inputs and vice versa It is up to the user doing the binding to make sure that activated functions are bound to appropriate signals Delivery setting On delivery all
25. his is indicated by an arrow symbol at the right hand edge of the display To choose one use RIGHT again To back down to a lower menu level use LEFT Change parameter In some menus there are parameters that can be set This will be indicated by the LED flashing To change a parameter first press the OK button A cursor will appear at the first settable value If you wish to change the value do so by pressing the UP DOWN buttons In numbers containing several digits you can move between the digits using the LEFT RIGHT buttons When the desired value is displayed press OK If there are further settable values displayed the cursor will automatically move to the next one To pass a value without changing it press RIGHT To abort a change and return to the initial setting press and hold the C button until the cursor disappears Corrigo E Heating manual revision G Chapter 6 Display LEDs and buttons 23 Chapter 7 Access rights 7 1 Log on 7 2 Log off There are 3 different log on levels System level which has the highest authority Operator level and the basic no log on level System level gives full read write access to all settings and parameters in all menus Operator level gives read only access to all settings and parameters and write access to all settings and parameters in all menus except Configuration The basic level permits read only access to all settings and parameters Repeatedly press down arrow
26. ion LON versions only 12 DO2 59 Egnd 13 DO3 14 DO4 71 DH 15 DO5 72 DD 16 DO6 73 DI3 17 DO7 74 DI4 75 DI5 30 Agnd Reference pole for analogue inputs 76 DI6 31 All 77 DI7 32 AD 78 DI8 33 Agnd Reference pole for analogue inputs 34 90 Agnd Reference for analogue outputs AO 35 AI4 91 AOL 92 2 40 Agnd Reference pole for analogue inputs 93 41 UH 94 4 42 UD 95 AOS 43 Agnd Reference pole for analogue inputs 44 45 UM Corrigo E Heating manual revision G Chapter 1 13 Empty wiring diagram Corrigo E15H 1 G 50 B Supply voltage 24 V AC 15 50 60 Hz 99 RS485 EXOline Modbus 3 Protective earth 52 N 4 C 24 V DC Reference for digital inputs DI 53 E 10 G Reference for digital outputs DO 57 Net 11 DOI 58 Net LON connection LON versions only 12 DO2 59 Egnd 13 DO3 14 DO4 71 DH 72 DD 30 Agnd Reference pole for analogue inputs 73 DB 31 All 74 DI4 32 AD 33 Agnd Reference pole for analogue inputs 90 Agnd Reference for analogue outputs AO 34 AB 91 AOI 35 AI4 92 AO2 93 AO3 Empty wiring diagram Corrigo E8H 1 G 50 B Supply voltage 24 V AC 1596 50 60 Hz lt o Hila RS485 EXOline Modbus 3 Protective earth 52 N 4 C 24 V
27. ion G Chapter Installation and wiring 9 Digital inputs Digital input signal Run indication alarm circulation pump P1 A HS1 Run indication alarm circulation pump P1 B HS1 Run indication alarm circulation pump PI A HS2 Run indication alarm circulation pump P1B HS2 Run indication alarm circulation pump P1 HW I Volume pulses heating usage Volume pulses cold water usage 1 Energy pulses heating usage Pressure switch expansion vessel pressure External alarm Boiler alarm Run indication alarm circulation pump P1A HS3 Run indication alarm circulation pump P1B HS3 Run indication alarm frequency converter for pressure control Run indication alarm storage tank charge pump 1 External power limitation Volume pulses cold water usage 2 Energy pulses electricity meter Note The universal inputs on Corrigo E28 can individually be configured as either analogue inputs using any of the analogue input signals above or as digital inputs using any of the digital input signals above Analogue outputs Analogue output signal Valve actuator Heating sequencel HS 1 Valve actuator hot water circuit 1 HW 1 Valve actuator Heating sequence2 HS2 Valve actuator hot water circuit 2 HW2 Frequency converter pressure control Split of any one of the above circuits Valve actuator Heating sequence3 HS3 Corrigo E Heating manual revision G Chapter Installation and wiring 10 Digital out
28. iversal input 1 gt Choose AI or DI sign AI sign HS2 Supply DI sign Not active After choosing AI or DI signal the unused alternative must be set to Not active there is sub menu with settings used when the input is configured as an Al input This menu is accessed by pressing RIGHT Universal AI1 Sign HS2 Supply Raw value 38 5 Compensation 0 09C Input signals can be compensated for example for wiring resistance The Raw value will show the actual uncompensated input value If an input has been assigned to pressure control the following submenu will be available UAI1 Pressure at Ov 0 0 kPa 10 10 0 kPa Filter factor 0 2 Universal 011 NO NC NO Signal HS1 PumpA Status Off To simplify adaptation to external functions all universal inputs configured as digital inputs can be set as either normally open NO or normally closed NC The inputs are as standard normally open 1 e if the input 1 closed the function connected to the input in Corrigo 15 activated 8 1 4 Analogue outputs Analogue outputs are 0 10 V DC Analogue output 1 Sign HS1 Actuator Auto Value 2 3 V Corrigo E Heating manual revision G Chapter 8 Configuration 27 8 1 5 Digital outputs Digital output 1 Signal HS1 PumpA Auto Status On 8 2 HS Heating System supply 8 2 1 Parallel displacement To each of the set control curves can be added paralle
29. l displacement Parallel displacemnt HS1 0 0 9c HS2 0 0 HS3 0 0 9c 8 2 2 Maximum limit A maximum supply temperature can be set individually for each heating system Maximum limit HS1 98 HS2 98 ec HS3 98 ec 8 2 3 Minimum limit A minimum supply temperature can be set individually for each heating system Minimum limit HS1 0 ec HS2 0 ec HS3 0 2C 8 2 4 Auto correction of setpoint Room sensors can be used to correct the control curves The average room temperature error over 24 hours is calculated Values 1 hour before and 1 hour after a day night or night day change over are ignored The curves are corrected once daily using the average room temperature error and a settable correction factor The correction will be a parallel displacement of the entire curve using the following formula Displacement Room setpoint Average temp Factor Auto correction Setpoint HS1 On gt Corr factor HS1 2 0 Present correction 0 6 C Corrigo E Heating manual revision G Chapter 8 Configuration 28 8 3 Return water temperature Individual maximum and minimum return water temperatures can be set for the heating systems Should the water temperature go outside the set limits the supply water temperature will be adjusted to correct The adjustment will be the temperature offset multiplied by the set limiting factor 8 3 1 Maximum temperat
30. lacem Factor 17 outd temp night set back Where Factor is a settable factor 0 10 where 0 gives no boost and 10 gives maximum boost Boost duration time is calculated as below Time 1 6 17 outdoor temp Building inertia None Boost factor 0 10 1 8 13 2 Power limitation Using a digital input the power to the heating systems can be temporarily restricted When activated the setpoints are lowered by a settable factor relative to 20 C The limitation applies to all configured heating systems The limitation is calculated as below Limited setpoint 20 Setpoint 20 Factor 100 Power limitation 100 rel 20 C Factor 100 gives no setpoint lowering 0 gives full lowering to 20 C 8 13 3 Frost protection If the controller is in mode Off or Manual and the outdoor temperature falls below a settable value a settable minimum supply temperature will be maintained Circulation pumps will be activated Frost protect Off Outdoor temp activ Frost prot 0 0 C Min sup temp 10 0 C 8 13 4 Split of output signal Any one of the temperature control output signals HS1 HS2 HS3 HWC1 or HWC2 can be split in two Split of any temp sequence No split Corrigo E Heating manual revision G Chapter 8 Configuration 34 8 14 System 8 13 5 Periodical heating Periodical heating HW1 No HP1 No 8 14 1 Change language Use
31. ming and normal handling can be done using the display and buttons or from connected computer running Corrigo E tool The temperature controllers are PI controllers for heating control and tap hot water control with a pre programmed set of control modes To the controllers can be bound a number of different control functions and analogue and digital input and output functions The choice of which functions are to be used is free the only restriction lying in the physical number of inputs and outputs that the different models have The Corrigo is designed for DIN rail mounting The program for a heating unit contains apart from other things the following functions Heating sequence control Control of 1 3 individual heating circuits Tap hot water control 1 or 2 tap hot water circuits and I storage tank charger circuit Differential pressure control One constant differential pressure control circuit Boiler control Basic two step boiler control Timer outputs Up to 5 individually settable timer outputs for control of for example lighting door locks etc Timer control Year base clock individual schedulers holiday scheduler Water consumption Energy consumption Corrigo E Heating manual revision G Chapter 2 About Corrigo E 5 Corrigo E hardware overview Model 8 8D 15 15D 28 28D Analogue Inputs 2 2 4 4 4 4 Digital Inputs 3 3 4 8 8 Universal I
32. ndication of the motor running or for monitoring of motor protection contacts Run indication input should be normally closed Open contact when the motor is running i e motor control output is activated will generate an alarm Motor protection should be normally open Closed contact when the motor is running i e motor control output is active will generate an alarm Run ind Motor prot HS1 Motor prot HS2 Motor prot HS3 Motor prot Run ind Motor prot HW1 Motor prot HP1 Motor prot Freq Con Motor prot 8 7 Actuator type Choose output signals to the actuators connected to the analogue control outputs 0 10 V DC 2 10 V DC 10 0 V DC or 10 2 V DC Actuator type HS1 0 10V HS2 0 10V HS3 0 10V Actuator type HW1 0 10V HW2 0 10V Freq 0 10V Note that although many manufacturers state 0 10 V DC as control signal for many actuators the actual control signal is more often than not 2 10V DC Check the actuator documentation carefully If uncertain choose 0 10V DC Although control might be less accurate it will ensure that the valve always can be driven to its fully opened and fully closed positions 8 8 Running time 3 pos actuators These parameters have no function if analogue actuators are configured The values are used to determine the control parameters for 3 position actuators It is important to set correct values since incorrect values lead to
33. ne between the two last breakpoints at either end Example At the lower end the setpoint is increasing by 14 C for every 5 C lowering of the outdoor temperature So the setpoint at 23 C would be 77 3 5 14 C 85 4 C Outd comp setp HS1 i Ye NIC 15 OCE 163 2C 10 59 Outdoor comp setp c Ao Gf He 0 OC 53 OC Outdoor comp setp 10 C 35 C I5 CCNE2 582G 11 2 Room sensor HS1 HS2 and HS3 Room sensor HS1 Actual 20 8 C Setpoint 21 0 C Return temp 20 0 C 11 3 Return water temperature Return temp HS1 20 0 C HS2 24 0 C HS3 23 0 C Corrigo E Heating manual revision G Chapter 11 Actual Setpoint 43 11 4 Supply temp HWC1 and HWC2 Supply temp HWC1 Actual 54 8 Setpoint 55 0 C 11 5 Storage tank Supply temp 1 45 8 C gt Return temp HP1 38 32C 11 6 Boiler temp Loading HP1 Start temp 46 0 OC Stop temp 55 0 Diff temp 2 0 C Boiler temp 68 6 Start templ 65 0 C Start temp2 60 0 C Stop temp 70 0 C 11 7 Return temp boiler Return temp Boiler 28 7 C 11 8 Pressure control Pressure control Actual 48 8 kPa Setp 50 0 kPa 11 9 Wind speed Wind speed Actual 4 6 m s Scale factor 1 0 m s V Compensation HS1 0 00 C m s HS2 0 00 C m s HS3 0
34. nputs 4 4 Analogue Outputs 1 1 3 3 5 5 Digital Outputs 2 2 4 4 7 7 RS485 Yes Yes Yes Yes Yes Yes LON Option Option Option Option Option Option TCP IP Option Option Option Option Option Option Display No Yes No Yes No Yes Ext display Option No Option No Option No Technical data Protection AA IP20 a NAKAKA aani 4 rows of 20 characters Background illumination LEDs Yellow sitom Settable parameter item trae De BANI RU Year base 24 hour clock with battery backup Automatic summer winter time changeover Operating System 2 pane bhai Rr Dee iad coisa meas EXOreal Supply voltage n oe He ERR REED UTR 24 V AC 6 VA eene 148x123x60 WxHxD incl terminals argu dS Standard Euronorm Mounting On DIN rail Operation Climatic conditions according to IEC 721 3 3 sse Class 3k5 Ambient temperature diee cerno et a rc TP ETUR E 0 50 C Ambient oeste ebrei te RESET Pe Max 9596 RH Mechanical requirements according to IEC721 3 3 sess Class 3M3 IEC60068 2 6 Test FC vibration Sinusoidal Shocks ES IEC60068 2 27 Test Ea Transport Climatic conditions according to IEC 721 3 2 sese Class 2k3 Ambient temperature 5 re veter eee ere a etae eere e ete see 20 70 C Ait c E Max 9596 RH Mechanical requirements according to IEC721 3 2 Class 2M2 Vibra sarte
35. nual Auto 45 Boiler start Manual Auto Boiler Auto Corrigo E Heating manual revision G Chapter 12 Manual Auto 46 Chapter 13 Energy Cold water In this menu the pulse counter input results are administered The pulse constants pulses unit are set in the menu Configuration Pulse constants Heating meter Cold water meter 1 Cold water meter 2 Electricity meter Leakage monitoring 13 1 Heating meter Energy total 1532 MWh Hot water total 387 m3 These values can be reset Energy Today 28 15 kWh Yesterday 123 45 kWh D B Y day 132 11 kWh Usage Today 28 15 lit Yesterday 123 45 lit D B Y day 132 11 lit Power usage Instant 2 1kW Average h 3 2kW Max aver 5 3 13 2 Cold water meters CW1 and CW2 CW1 Usage total 276 2 m3 CW1 Flow 6 4 1 min CW1 Usage Today 88 1 lit Yesterday 4123 4 lit D B Y day 5012 1 lit Lowest CW1 usage Today 0 1 lit h Yest 0 2 lit h Corrigo E Heating manual revision G Chapter 13 Energy Cold water 47 13 3 Electricity meter Energy total 1866 54 mWh The value can be reset 13 4 Leakage monitoring Leakage power 1 31 kw Corrigo E Heating manual revision G Chapter 13 Energy Cold water 48 Chapter 14 Other functions 14 1 Alarm handling If an alarm condition occurs the Alarm LED on the front panel on units with display
36. number dependent Communication code for modbus 0 Modbus Not Active Modbus Address 1 Speed 9600 bps Two stop bits Yes Parity No Corrigo E Heating manual revision G Chapter 8 Configuration 36 8 14 7 Dial up modem With the help of a dial up modem Corrigo can be connected to a supervisor Exo system We recommend the modem Westermo TD 32 B The default password is exo DialUpModem No Number Password exo 8 14 8 Alarm forwarding via SMS Via a connected GSM modem Corrigo can send an alarm message to up to 3 different recipients To use this function you first have to purchase a lock up code from Regin When there is an alarm Corrigo sends an alarm message to the first number on the list The message consists of an alarm text the unit name the same text that is shown in the first row of the start display and the time when the alarm occurred If the recipient does not send an SMS within 5 minutes to confirm that the message has been received Corrigo will send the message to the next number on the list Code to enable SMS function 0 SMS Not Active Nbrl Nbr2 Nbr3 Corrigo E Heating manual revision G Chapter 8 Configuration 37 Chapter 9 Settings In this menu group all settings for all activated functions should be available Depending on what choices have been made during configuration some of the alternatives in this menu group may not be sh
37. on at System level and go to the menu Configuration e For the time being skip the configuration menu nputs Outputs and start by configuring Control functions e Run through the configuration menus in order and set whatever functions and parameters you wish to include Use chapter 4 of this manual for reference Keep track of which inputs and outputs you will need To help you there is a list of input and output functions provided in chapter 3 3 2 3 Input Output list e Finally configure Inputs Outputs e Exit Configuration and go to Settings e Set the control values in Settings e Set the clock and scheduler functions in Timers e Set the control setpoints in Actual Setpoint Your Corrigo should now be ready to run Option 2 Read this manual in the order given below The manual has been designed to act as a guide through the commissioning The last chapters of the manual not listed below cover menus and functions that are not used during commissioning Corrigo E Heating manual revision G Chapter 4 Commissioning 15 Functional description Start by reading the chapter 5 Functional description below Some functions are essential to the working of the unit and must be included Others are more of the nature of optional extras which can be excluded At the end of each function description there is a table of the necessary inputs and outputs to implement the function At the end of the manual there is a list of all the
38. own Settings Control temp gt Control pressure gt Alarm settings 9 1 Control temp 9 1 1 HS1 HS2 and HS3 Control parameters for the three heating system controllers HS1 P band 100 0 C I time 100 0 sec 9 1 2 HWC1 and HWC2 Control parameters for the two hot water controllers HWC1 P band 100 0 C I time 150 0 sec D time 1 0 sec 9 2 Control pressure 9 2 1 Control pressure Control parameters for pressure control Only accessible if pressure control has been configured Pressure control P band 25 0 kPa I time 100 0 sec Min output 0 9 3 Alarm settings Alarm settings Alarm limits Alarm delay vv Corrigo E Heating manual revision G Chapter 9 Settings 38 9 3 1 Alarm limits Control deviation HS1 HS2 and HS3 Control deviation HS1 20 0 C HS2 20 0 C HS3 20 0 C Control deviation HWC1 and HWC2 Control deviation HWC1 20 0 C HWC2 20 0 C Scalding limit Scalding HWC1 65 0 C HWC2 65 0 OC Boiler limits High boiler temp 70 0 OG Low boiler temp 30 0 Sc High water usage High 24h water usage 10000 0 liters High 1h water usage 10000 0 liters High energy usage High 24h energy usage 10000 0 kWh Maximum time between pulses Max between Vpulse 0 min Max between Epulse 0 min Max between CWlpulse 0 min Max bet
39. put s Class C alarms are removed from the alarm list when the alarm input resets even if the alarm has not been acknowledged 14 2 Revision numbers If RIGHT is pressed once when the start display is shown see section 8 14 2 a menu showing the program revision number and id number will be displayed 14 3 Free text If RIGHT is pressed twice when the start display is shown see section 8 14 2 a menu showing text of your choice is displayed The text can be used to show information concerning the commissioning company name and phone number to service personnel etc Text is entered using E tool Up to 4 lines of 20 characters can be entered Corrigo E Heating manual revision G Chapter 14 Other functions 49 Chapter 15 Index Access rights 24 Actual Setpoint 43 Address 36 Alarm configuration 32 Alarm list 32 Alarm settings 38 Alarms 21 Alarm handling 49 Alarm list 32 Analogue inputs 8 Analogue outputs 9 Boiler control 19 Boost 34 Building inertia 34 Buttons 22 C Change language 35 Cold water meters 47 Cold water monitoring 19 Configuration 26 Inputs and outputs 26 Running time 3 pos actuators 30 D Dial up modem 37 Digital inputs 8 Digital outputs 9 Display 22 Display LEDs and buttons 22 E Electricity meter 20 48 Energy Cold water 47 Energy monitoring 20 Exercising 31 F Free text 49 Frost protection 34 H Hand Auto 45 Heating meter
40. puts Digital output signal Start stop pump PLA HS1 Corrigo E Heating manual revision G Chapter Installation and wiring 11 Wiring diagram Corrigo E28 factory configuration See also picture of the position of the terminals on page 7 1 G 50 B Supply voltage 24 V AC 15 50 60 Hz 2 GO 51 RS485 EXOline Modbus 3 Protective earth 52 4 C 24 V DC Reference for digital inputs DI 53 E 10 G Reference for digital outputs DO 57 Net 11 DOI Start stop pump P1A HS1 58 Net LON connection LON versions only 12 DO2 Start stop pump 1 1 59 Egnd 13 DO3 Actuator HS1 increase 14 DO4 Actuator HS1 decrease 71 Dil Run indication alarm pump PLA HS1 15 DOS Start stop pump PI HW1 72 Run indication alarm pump P1B HS1 16 DOG Start stop pump PLA HS2 73 DB Run indication alarm pump P1 A HS2 17 DO7 Sum alarm 74 DI4 Run indication alarm pump P1 HW1 75 DIS Volume pulse heating usage meter 30 Agnd Reference pole for analogue inputs AI 76 DI6 Energy pulse heating usage meter 31 Outdoor temperature sensor TI DI7 Volume pulse cold water usage I 32 AD Supply temp heating sequence 1 HS1 78 DI8 Pressure switch expansion vessel 33 Agnd Reference pole for analogue inputs
41. sloppy control Corrigo E Heating manual revision G Chapter 8 Configuration 30 Actuator run time HS1 255 sec HS2 255 sec HS3 255 sec Actuator run time HW1 80 sec HW2 80 sec 8 9 Valve exercising The valves can be exercised once daily Default time is 3 00 pm but can be set to any time The actuators will be forced to either endpoint for the set actuator running time The pumps will run and the temperature offset alarm will be blocked for the duration of the exercising Actuator exercise HS1 Off Hour for exerc 15 Minute for ex 00 8 10 Leakage monitoring Once a week the control valves will be closed and the energy usage measured for a preset time An alarm is generated should the energy leakage be larger than a settable value default 3 0 kW The time for and duration of the leakage monitoring is settable Default is Sundays at 2 00 am for 30 minutes Leakage mon Off Weekday Sunday Hour 2 Duration 30 min Permitted leakage 3 00 kw Start monitoring now No 8 11 Pulse inputs Energy pulse heating 100 0 kWh Pulse Volume pulse heating 10 0 liters Pulse Cold water 1 10 0 liters Pulse Cold water 2 10 0 liters Pulse Electric meter 100 0 kWh Pulse Corrigo E Heating manual revision G Chapter 8 Configuration 31 8 12 Alarm configuration Permits configuration of all alarms Select the appropria
42. te alarm number from the alarm list The alarm text for the alarm will be displayed and the alarm priority can be set A alarm B alarm C alarm or not active Alarm no 1 65 1 Malfunction P1A HS1 gt Malfunction P1A HS1 Priority B alarm Alarm list Values in the Priority column show the factory set values Alarm text Pri Description PIA HS 1 Malfunction pump P1A HS1 Malf PIB HS1 Malfunction pump P1B HS1 Malf PIA HS2 Malfunction pump P1A HS2 PIB HS2 Malfunction pump P1B HS2 PIA HS3 Malfunction pump P1A HS3 PIB HS3 Malfunction pump P1B HS3 Malf Frequence fB Malfunction frequency converter Malf PI HWC Malfunction pump P1 HWC Malfunction pump P1 VVB 10 Exp vessel Expansion vessel alarm 11 External alarm External alarm 12 Boiler alarm Bekrdam la Boiler alarm 13 Deviation HS1 Supply temp HS1 deviates too much from the setpoint for too long 14 Deviation HS2 Supply temp HS2 deviates too much from the setpoint for too long 15 Deviation HS3 Supply temp HS3 deviates too much from the setpoint for too long 16 Deviation HWC1 A Supply temp HWCI deviates too much from the setpoint for too long 17 Deviation HWC2 Supply temp HWC2 deviates too much from the setpoint for too long 18 Sensor error Sensor errr Malfunction of a connected sensor 19
43. ter 5 Functional description Chapter 6 Display LEDs and buttons Chapter 7 Access rights Chapter 8 Configuration Chapter 9 Settings Chapter 10 Time settings Chapter 11 Actual Setpoint Chapter 12 Manual Auto Chapter 13 Energy Cold water Chapter 14 Other functions Chapter 15 Index 15 17 22 24 26 38 41 43 45 47 49 50 Chapter 1 About the manual This manual covers all the models in the Corrigo E series of heating controllers This revision covers program revision 1 7 1 01 More information More information about Corrigo E can be found in e Manual E tool Manual of how to configure the controllers e Lon interface variable list Variable list for the Corrigo E series e Network variables for EXOline and Modbus Variable list for EXOline and Modbus communication e CE Declaration of conformity Corrigo E The information is available for download from Regin s homepage www regin se Corrigo E Heating manual revision G Chapter I About the manual 4 Chapter2 About Corrigo E Corrigo for heating is complete new range of programmable controllers for control of building heating systems Corrigo E series for heating comprises three model sizes 8 15 or 28 in outputs Available with or without front panel display and buttons For units without front panel display and buttons a separate cable connected terminal E DSP with display and buttons is available All program
44. terminal block All analogue outputs can be individually set to any one of the following signals 0 10 V DC 2 10 V DC 10 0 V DC 10 2 V DC If the Corrigo E and the actuators connected to it share the same transformer it is essential that the same transformer pole is used as reference for all the equipment Failure to do so will prevent the equipment from functioning as intended and may also lead to damages Digital outputs Digital outputs must refer to G on terminal 10 the digital outputs are triac controlled The outputs will deliver 24 V AC 0 5 A continuous The outputs cannot be used to drive DC relays 10 1 11 ge Om 12104 i 3 2 3 Input and output lists Use these lists during commissioning to help you keep track of which input and output functions you wish to use Analogue inputs v Analogue input signal Outdoor temperature sensor Supply temperature Heating sequence Tap hot water circuit 1 supply temperature Return temperature Heating sequence Tap hot water circuit 2 supply temperature Storage tank supply temperature Storage tank return temperature Return temperature Heating sequence2 Room temperature Heating sequence2 Retur temperature Heating sequenced Room temperrue Heng sequence MT ET Supply temperature Heating sequence IET i Corrigo E Heating manual revis
45. the physical inputs and outputs have already been bound to a signal The delivery settings are suggestions only and can easily be changed 8 1 1 Analogue inputs Al Analogue input 1 Sign Outdoortemp Raw value 18 3 Compensation 0 0 C All analogue inputs are for PT1000 or 0 10 Volts Input signals can be compensated for example for wiring resistance The Raw value will show the actual uncompensated input value If an input has been assigned to pressure control the following submenu will be available AI2 Pressure at Ov 0 0 kPa 10V 10 0 kPa Filter factor 0 2 Corrigo E Heating manual revision G Chapter 8 Configuration 26 8 1 2 Digital inputs DI Digital input 1 NO NC NO Signal HS1 PumpA Status Off To simplify adaptation to external functions all digital inputs can be configured to be either normally open NO or normally closed NC The inputs are as standard normally open 1 e if the input is closed the function connected to the input in Corrigo 15 activated 8 1 3 Universal inputs Ul On the largest hardware version E28 there are universal inputs These can individually be configured as either analogue inputs or as digital inputs When configured as analogue inputs they can be bound to any of the analogue signals described under Analogue signals When configured as digital inputs they can be bound to any of the digital signals described under Digital signals Un
46. tputs 24 V AC 0 5 A continuous Options EON caa eei FT3150 gives a second communication route io teria Replaces RS485 for EXOline Port 1 communication External hand terminal E DSP For use with Corrigo E units without display Corrigo E Heating manual revision G Chapter 2 About Corrigo E 7 Chapter 3 Installation and wiring 3 1 Installation 3 2 Wiring Corrigo can be mounted in DIN standard casing minimum 9 modules DIN rail in cabinet or using suitable front mounting kit in cabinet door or other control panel Ambient temperature 0 50 Ambient humidity Max 95 RH non condensing At the end of this chapter there are wiring diagrams showing the factory set configuration We have also included blank diagrams Since the function of most of the inputs and outputs depends on the programming of the unit the final wiring diagram cannot be filled in until the installer has decided how to use the inputs outputs It is important to make sure that the wiring is correctly done and in accordance with the instructions given in this manual 3 2 1 Supply voltage 24 V AC 15 50 60 Hz 6 VA If the Corrigo E and the actuators connected to it share the same transformer it is essential that the same transformer pole is used as reference for all the equipment Failure to do so will prevent the equipment from functioning as intended and may also lead to damages
47. un according to the settings of the night set back schedule running during normal temperature periods and standing still during periods with reduced temperature 5 2 5 Periodic overheating Once daily at 02 00 am the temperature set point can be increased to 62 to prevent growth of Legionella bacteria The raised set point is maintained until the supply temperature reaches 60 C but not shorter than I minute and not longer than 5 minutes If the pump is stopped it will start and run for the duration of the overheating period plus 2 minutes 5 3 Storage tank storage tank function can be enabled The storage tank load pump PI HPI is started depending on the storage tank supply water and return water temperatures Loading is started if the return water temperature is lower than the set start temperature Loading is stopped when the supply temperature is higher than the set stop temperature and the return temperature is higher than the set start temperature the set differential 5 4 Pressure control Corrigo can using an analogue output signal control variable speed pump to maintain constant settable pressure digital output signal is available to give a start signal to the frequency converter This output is enabled as soon as the converter control signal rises above 0 1 V 5 5 Boiler control simple boiler control can be enabled When the boiler temperature falls below Start temperature 1 the digital signal St
48. ure Max return temp HS1 Active gt Hs2 Inactive HS3 Inactive Max return temp HS1 509C HS2 50 C HS3 50 C 8 3 2 Minimum temperature Min return temp HS1 Active HS2 Inactive HS3 Inactive Min return temp HS1 0 C HS2 0 C HS3 0 C 8 3 3 Limiting factor Return limit factor HS1 1 00 HS2 1 00 HS3 1 00 8 4 Pump stop Each heating system has individual day and night stop temperatures An active circulation pump will stop if the outdoor temperature is higher than the set value and there is no heating demand The pump will start if the temperature falls below the set stop temperature less the set hysteresis Night is between 00 00 am and 05 00 am All pumps even resting twin pumps are exercised once daily for 5 minutes at 3 pm Pump stop HS1 0n Temp stop day 17 C Temp stop night 179C Hysteresis 2 0 C Corrigo E Heating manual revision G Chapter 8 Configuration 29 8 5 Twin pump Single pump Each heating system can be configured for either single pump or twin pumps When twin pumps are configured the pumps are alternated weekly on Tuesdays at 10 00 am On activation of the pump alarm for the active pump the Corrigo will automatically switch to the other pump Twin Single pump HS1 Twin pumps HS2 Single pump HS3 Single pump 8 6 Run indication Motor protection Inputs are used either for i
49. ween CW2pulse 0 min Permitted leakage Permitted leakage 3 00 kW Corrigo E Heating manual revision G Chapter 9 Settings 39 9 3 2 Alarm delays Control deviation HS1 HS2 and HS3 Control deviation HS1 60 min HS2 60 min HS3 60 min Control deviation HWC1 and HWC2 Control deviation HWC1 60 min HWC2 60 min Scalding limit Scalding 1 300 sec 2 300 sec Boiler limits High boiler temp 0 boiler temp 0 Expansion vessel External alarm Expansion vessel 60 sec External alarm 60 sec Corrigo E Heating manual revision G Chapter 9 Settings 40 Chapter 1 0 Time settings 10 1 Time Date General Corrigo has year base clock function This means that week schedule with holiday periods for full year can be set The clock has an automatic summer winter time changeover Individual schedules for each week day plus separate holiday setting Up to 24 individual holiday periods can be configured Holiday schedules take precedence over other schedules Each day has up to two individual running periods For two speed fans and pressure controlled fans there are daily individual schedules for normal speed and reduced speed each with up to two running periods Up to five separate digital timer outputs can be configured Each with individual week schedules with two activation periods per day
50. will start flashing The LED will continue to flash as long as there are unacknowledged alarms Alarms are logged in the alarm list The list shows type of alarm date and time for the alarm and the alarm class A B or C alarm To access the alarm list press the alarm button the front panel button with the red button top Sensor error 24 Feb 10 43 Class B Reset v If there are multiple alarms this is indicated by up down arrow symbols at the right hand edge of the display Use the UP and DOWN buttons to access the other alarms At the left end of the bottom display line the alarm status is shown For active unacknowledged alarms the space is blank For alarms that have reset the text Reset is shown Acknowledged still active or blocked alarms are indicated by Acknowledged or Blocked Alarms are acknowledged by pressing the OK button You are then given the choice of acknowledging the alarm or blocking the alarm Acknowledged alarms will remain on the alarm list until the alarm input signal resets Blocked alarms remain on the alarm list until the alarm has reset and the block has been removed New alarms of the same type will not be activated as long as the block remains Since blocking alarms can be potentially hazardous you need a high log on authority to block alarms Class A and B alarms will activate alarm output s if these have been configured Class C alarms do not activate the alarm out
Download Pdf Manuals
Related Search
Related Contents
Media Core 200 User Guide Dell OpenManage Server Administrator Version 6.1 User's Manual Intermec SR31T 1D Harbor Freight Tools 1100 lb. Electric Hoist with Remote Control Product manual Sélection des meilleurs oracles et tarots MA200 Manual 9-2153-5.indd Centella Multi Surface TG-10STX _Manual Manual as PDF Samsung S24A450MWR Copyright © All rights reserved.
Failed to retrieve file