Home
UPSMON PRO Linux --
Contents
1. Ups Polling Interval default 3000 ms Would you need to reset default N root dinow System Product Name home dinow UPSMON_PRO_Linux Diagram Start Config CC UPSMON PRO Status C 1 Command upsmon pro status gt It will repeatedly poll you current ups status until Ctrl C pressing Power Status Battery Power Utility Power Input Voltage To display utility power voltage Input Frequency To display utility power frequency Output Voltage To display ups output voltage Output Power To display ups output power UPS Status Normal Bypass AVR Boost AVR Buck UPS Failed UPS Load To display total capacity of loads UPS Temperature To display ups inside temperature UPS Beeper ON OFF Battery Status Normal Charge Discharge Battery Test Low Battery Battery Failed Battery Capacity To display battery percentage level Battery Voltage To display battery its voltage Battery Backup Time To display battery estimated backup time in battery mode Battery Test Times Accumulated times that ups made battery test Battery Last Test The last time this ups made battery test Battery Test Result Normal Battery Failed Low Battery Battery Power Times Accumulated times that ups output power supply from batteries Battery Power Start The last time ups switch power from its battery Battery Power End The last time ups
2. 120 0 Volts 36 00 Volts 50 0 Hz SNMP Card 210 202 53 134 2 44 BT 506 public Upsmon Pro Polling Interval 2000 ms Linux shutdown delay seconds 120 Seconds Linux shutdown 1f battery capacity BO Percent Linux shutdown 1f battery backup minutes 5 Minutes Ups Shutdown Delay 3 Minutes Diagram UPS Information C 3 Command upsmon pro log gt To list the ups data log C 4 Command upsmon pro log erase gt To erase the ups data log gt To avoid data conflict please execute this command without upsmon pro service running C 5 Command upsmon pro event gt To list the ups event C 6 Command upsmon pro log erase gt To erase the ups event gt To avoid data conflict please execute this command without upsmon pro service running DD UPSMON PRO Config D 1 Command upsmon pro mail gt This configuration will help you to get email notification once ups events occurs a E Mail Server Enable Y n b E Mail Server Name or IP Email server address c E Mail Server Port 25 default d E Mail Account The account of this email server e E Mail Password The password of this email account f SSL Requires This mail server requires an secure connection g E Mail Sender The email address of this account h E Mail Recipient The recipient who needs to get email notification D 2 Command upsmon pro mail test gt This command will send a te
3. Connect Choose UPSMON PRO URPSMON PRO rel C USB C SNMP Card lo IRG I 254 C COM Port l UPSMON PRO 10 192 136 231 User Mame Password Scredule p J CEE Entau PP Control Password UPSMON English C EPX GG UPSMON PRO Auto Start G 1 Command path UPSMON PRO Linux upsmon pro service gt To have a daemon start every time Linux reboot please add above script into beginning procedures Typically this script locate in etc rc d or etc re d rc local or etc init d rc local However the name and path vary by the distribution HH Q and A H 1 Linux usb connect Fail Command sudo apt get install lib32bz2 1 0 Debian Command sudo apt get install lib32z1 Ubuntu Mint Command yum install glibc 1686 Fedora CentOS H 2 Linux Display Fail Command sudo apt get install default jre Command cd UPSMON PRO Linux EXT Command java Display
4. switch power to utility Battery Age The age of ups batteries have used Ambient Temperature The sense of environmental temperature Ambient Humidity The sense of environmental humidity Upsmon Pro Linux This ups monitoring software version Upsmon Pro Status Monitoring Disconnect Upsmon Pro Data Update The data update time Upsmon Pro is going to shutdown after XXX seconds Blackout and shutdown mode root dinow System Product Name home dinow UPSMON_PRO_Linux Power Status AC Utility Power Input Voltage 110 Volts Input Frequency 686 Hz Output Voltage 120 Volts Output Power gt 34 Watt Status Normal i Load 3 Percent ps Temperature sae JC Ups Beeper OFF Battery Status Normal Battery Capacity 100 Percent Battery Voltage 22 0 Volts Battery Test Times 3 Times Battery Last Test 11 43 51 2015 06 01 Battery Test Result Battery Normal Battery Power Times 3 Times Battery Power Start 11 46 16 26 Battery Power End gt 11 46 44 2 Battery Age gt 1 Month Ambient Temperature 28 C Ambient Humidity 45 Percent Upsmon Pro Linux V1 22 Upsmon Pro Status Monitoring Upsmon Pro Update 5 13 32 37 2615 66 61 Diagram UPS Status C 2 Command upsmon pro info gt To display ups service devices information and configuration Ups Company The manufacture of the ups Ups Model The ups model name Ups Firmware The ups firmware vers
5. UPSMON PRO Linux User Manual Version 1 22 Attention root authority is necessary to execute at Linux here AA UPSMON PRO Install p BB UPSMON PRO Start 3 CC UPSMON PRO Status 6 DD UPSMON PRO Config 9 EE UPSMON PRO Set 10 FF UPSMON PRO Multi Connect 12 GG UPSMON PRO Auto Start 14 HH O and A 15 AA UPSMON PRO Install A 1 Command cp UPSMON PRO Linux tar home user A 2 Command tar xvf UPSMON PRO Linux tar A 3 Command cd UPSMON PRO Linux gt These command will copy and uncompressed this ups monitoring software gt And the package contains executable files about ups monitoring configuration and control Terminal root dinow System Product Name home dinow Ls Desktop Downloads Music Public Documents examples desktop Pictures Templates Videos root dinow System Product Name home dinow tar xvf UPSMON PRO Linux V1 22 tar AAS root dinow System Product Name home dinow UPSMON_PRO_Linux UPSMON_PRO_Linux upsmon pro outLleti off UPSMON_ PRO Linux upsmon pro matl test UPSMON_PRO_Linux upsmon pro beeper on UPSMON_ PRO Linux upsmon pro log erase root dinow System Product Name home dinow cd UPSMON_PRO_Linux root dinow System Product Name home dinow UPSMON PRO Linux Ls Class upsmon pro maiLl test upsmon pro status upsmon pro beeper off upsmon pro outLeti off upsmon pro status2 upsmon pro beeper on upsmon pro outLeti on upsmon pro stop upsmon pro event upsmon pro outLlet2 off upsmon pro test
6. ion Rating Input Volt Ratting Input Voltage Rating Output Volt Ratting Output Voltage Upsmon Pro Connect RS232 USB SNMP Card UPSMON PRO Upsmon Pro RS232 Port Name and Path Serial port path ex dev ttySO Upsmon Pro Master IP The IP address of Upsmon Pro Master RS232 or USB Snmp Card IP The IP address of snmp card Snmp Card firmware The firmware version of snmp card Snmp Card Community The community of snmp card Upsmon Pro Usb VID amp PID Usb vendor ID and Usb product ID Upsmon Pro Usb Type Driver for usb hid ups equipment Polling Interval The query interval to ups Linux shutdown delay seconds When power failure occurs Linux will act shutdown after this count down seconds Linux shutdown if battery capacity Linux act shutdown at once if battery descend to this level Linux shutdown if battery backup minutes Linux act shutdown at once if ups estimated battery backup time descend to this minutes Ups shutdown delay minutes Once Linux commit shutdown ups will sustain power for these minutes dinow linux s9bl Desktop File Edit View Terminal Linux s9bL home dinow UPSMON PRO Linux Ups Company Ups Model Ups Firmware Rating Input Voltage Rating Output Voltage Rating Battery Voltage Rating Frequency Upsmon Pro Connect SNMP Card IP SNMP Card firmware SNMP Card Community POWERCOM VOS 1000 Ver 1xXP 3 120 Volts
7. lay seconds default 180 Linux shutdown if battery capacity default default default Ups shutdown delay minutes Would you need to reset Linux shutdown if battery backup minutes default root localhost UPSMON PRO Linux UPSMON UPSMON Start root localhost UPSMON PRO Linux UPSMON Start Monitor root Localhost UPSMON PRO Linux J Diagram SNMPCard Connection CentOS B 2 Command upsmon pro stop gt It will stop ups monitoring service B 3 Command upsmon pro service gt This command directly start ups monitoring without any information query Add this within start daemon B 4 Command upsmon pro restart gt This command will restart the ups monitoring B 5 Command upsmon pro start config gt This command will reset ups connection and shutdown condition gt Polling Interval The application query interval to ups milli second Termine File Edit View Search Terminal Help root dinow System Product Name home dinow UPSMON_PRO_Linux root dtnow System Product Name home dinow UPSMON_ PRO Linux upsmon pro start conftig UPS connection 1 RS232 2 USB 3 SNMP Cara 4 UPSMON PRO 1 Name and path of serial port ex dev ttyso0 dev ttyso Linux shutdown delay seconds default 120 60 Linux shutdown if battery capacity default 30 45 Linux shutdown if battery backup minutes default 5 Ups shutdown delay minutes default 3
8. st mail to make sure your configuration 1s success or not A dinow linux s9bl Desktop File Edit View Terminal Tabs Help Linux s9bL home dinow UPSMON PRO Linux upsmon pro mail Mail Server Enable Yn Mall Server Name or IP smtp gqmail com Mail Server Port default 25 465 Mall Account dinow46 Mail Password SSL Requires Y n E Mail Sender gt dinow46 qgmaiLl com E Mail Recipient gt dinow upspowercom com tw Would you need to reset Nyy a Ee E d e g h 1 Linux s9bL home dinow UPSMON PRO Linux Linux s9bL home dinow UPSMON_PRO Linux Linux s9bL home dinow UPSMON PRO Linux Linux s9bL home dinow UPSMON PRO Linux UPSMON Email Test Linux s9bL home dinow UPSMON PRO Linux 2 UPSMON Email Test MEAR 80 oi SPP dinow4G grnail com Aaa 2015F6A48 EF 10 54 BPA din OWwRUpSpowercorm corm tw ar B UPSMON Email Test If you received this test mal it means that your UPSMOHN mad settings are correct gt EE UPSMON PRO Set E 1 Command upsmon pro test gt To check the battery health ups will supply the power shortly from its battery E 2 Command upsmon pro test deep gt To simulate battery capability ups will supply battery power for its limits E 3 Command upsmon pro test cancel gt With this command it will cease deep battery power test 5 Applications Places System dinow localhost home dino
9. t once gt ups outlets control 1s specific for certain ups FF UPSMON PRO Multi Connect gt The UPSMON PRO can play the role as Master or Slave F 1 UPSMON PRO Master e UPSMON PRO Master The Linux who physically connects UPS via RS232 or USB e UPSMON PRO Master It can share UPS status to the other UPSMON PRO Slaves e EX UPSMON PRO Master 10 192 136 231 IP Address al USB a COM UPSMON Pro for Linux Master m IF 10 192 136 23 1 UPSMON Pro UPSMON Pro UPSMON Pro Slave Slave Slave UPSMON Pro Slave F 2 UPSMON PRO Linux Slave e UPSMON PRO Slave The Linux who connect to UPSMON PRO Master via net e UPSMON PRO Slave Execute upsmon pro start with 4 upsmon pro parameter H Applications Places System b fo E dinow localhost home dinow UPSMON PRO Linux File Edit View Search Terminal Help root localhost UPSMON PRO Linux upsmon pro start UPS connection 1 R5232 2 USB 3 SNMP Card 4 UPSMON PRO 4 UPSMON PRO IP address 186 192 136 231 Linux shutdown delay seconds default 120 Linux shutdown if battery capacity default 38 Linux shutdown if battery backup minutes default 5 Would you need to reset default N root localhost UPSMON PRO Linux UPSMON UPSMON Start root localhost UPSMON PRO Linux UPSMON Start Monitor F 3 UPSMON PRO Windows Slave e UPSMON PRO Slave The Windows who connect to UPSMON PRO Master via net e UPSMON PRO Slave
10. ult 120 Linux shutdown 7 attery capacity default 30 Linux shutdown if bD ery backu LI default 5 default 3 Would you need to reset default N root dinow System Product Name home dainow UPSMON PRO Linux UPSMON UPSMON Start root dtnow System Product Name home datnow UPSMON_PRO_ Linux UPSMON Start Monitor root ditnow System Product Name home datnow UPSMON_ PRO_Linux i Diagram USB Connection dinow linux s9bl Desktop File Edit View Terminal Tabs Help Linux s9bL f home dinow UPSMON PRO Linux upsmon pro start UPS connection 1 R5232 2 USB 3 5NMP Card 4 UPSMON PRO Name and path of serial port lex dev ttySo dev ttyso Linux shutdown delay seconds default 120 90 Linux shutdown 1f battery capacity default 30 Linux shutdown 1f battery backup minutes default 5 Ups shutdown delay minutes default 3 Would you need to reset default N Linux s9bL home dinow UPSMON PRO Linux UPFSMON UPSMON Start Llinux s9bL home dinow UPSMON PRO Linux UPSMON Start Monitor Diagram RS232 Connection SuSe Applications Places 5 Places System ystem amp amp E dinow localhost home dinow UPSMON PRO Linux File Edit View Search Terminal Help root localhost UPSMON PRO Linux upsmon pro start a UPS connection 1 RS 232 2 USB 3 SNMP Card 4 UPSMON PRO 3 SNMP Card IP address 180 192 136 236 Linux shutdown de
11. upsmon pro event erase wupsmon pro outLlet2 on upsmon pro test cancelL upsmon pro info upsmon pro restart upsmon pro test deep upsmon pro Log upsmon pro service upsmon pro ups reboot upsmon pro Log erase upsmon pro start upsmon pro maiLl upsmon pro start config root dinow System Product Name home dinow UPSMON PRO Linux Diagram UPSMON PRO Install Ubuntu BB UPSMON PRO Start B 1 Command upsmon pro start gt It will ask you the basic information and then auto start ups monitoring service a UPS Connection 1 RS232 2 USB 3 SNMP Card 4 UPSMON PRO b Linux shutdown delay seconds When power failure occurs Linux will act shutdown after this count down seconds c Linux shutdown if battery capacity Linux act shutdown at once if battery descend to this level d Linux shutdown if battery backup minutes Linux act shutdown at once if battery estimated backup time descend to this minutes e Ups shutdown delay minutes Once Linux commit shutdown ups will sustain power for these minutes gt UPSMON UPSMON Start gt It means the program successfully execute gt UPSMON Start Monitor gt It means the program successfully get ups connection Terminal root dinow System Product Name home dinow UPSMON_PRO_Linux root dtnow System Product Name home atnow UPSMON PRO _Linux upsmon pro start UPS connection 1 R523 2 U5B 3 5NMP Card 4 UPSMON PRO 2 Linux shutdown delay seco defa
12. w UPSMON PRO Linux File Edit View Search Terminal Help root localhost UPSMON PRO Linux root localhost UPSMON PRO Linux UPSMON Battery Test dinow localhost home dinow UPSMON PRO Linux File Edit View Search Terminal Help Power Status AC Utility Power Input Voltage 111 Volts Input Frequency 59 Hz Output Voltage 120 Volts Normal Percent Ups Temperature t JIL Ups Beeper ON Status Discharge Battery Test Capacity 99 Percent Voltage 2 19 Volts y Backup Time 199 Minutes Estimate Test Times 3 Times Last Test 10 16 42 2015 06 03 Test Result Battery Normal Battery Age 2 Days Upsmon Pro Linux V1 22 Upsmon Pro Status Monitoring Upsmon Pro Update 10 16 42 2015 06 03 Diagram UPS Batter Test E 4 Command upsmon pro beeper on gt Ups alarm for ups warning condition E 5 Command upsmon pro beeper off gt Ups silence for ups warning condition E 6 Command upsmon pro ups reboot Description Shutdown Linux and reboot ups after XX minutes a Ups reboot after minutes defaut 2 Ups reboot its power after this minutes b Commit ups reboot Y n E 7 Command upsmon pro outlet off gt It will turn ups outlet OFF at once E 8 Command upsmon pro outletl on gt It will turn ups outlet ON at once E 9 Command upsmon pro outlet2 off gt It will turn ups outlet2 OFF at once E 10 Command upsmon pro outlet2 on gt It will turn ups outlet2 ON a
Download Pdf Manuals