1. 1010 2020 OPERATORS MANUAL During a walk test as each detector alarms it will not display on the LCD it s LED will activate for 5 seconds and outputs set as Walk Test will toggle on for 10 seconds then reset These outputs should be connected to sounders or bells to confirm to the testing technician that the alarm has been received at the panel The detectors will also automatically reset during walk test mode NOTE During walk test all ID s are ignored therefore and PHOD detectors will register in walk tests le If a door switch or fan airflow module etc activates it will ring bells for 10 seconds and appear in the report MMX 2 modules are not able to be walk tested SYSTEM TEST MENU The System test menu allows for manual testing of devices on the system To enter system test mode simply press the SYSTEM TEST button once The SYSTEM TEST menu provides the following options Selection Abbreviation Description 1 ALM ALARM TEST This provides for a real alarm test on a detector Enter LxxDxx then press enter The detector must then be Acknowledged and Reset as per normal 2 FLT FAULT TEST This provides for a real fault test on a detector module Enter LxxDxx or LxxMxx then enter You will be required to acknowledge faults as per normal 3 Lamp LAMP TEST Initiates a lamp test on the system 4 System SYSTEM Function is not used PERIODIC TEST To ensure c
2. 0 OPERATORS MANUAL PAGE 3 BASIC OPERATIONAL PROCEDURES ACKNOWLEDGE SILENCE ALARMS To individually acknowledge alarms The fire alarm LED will go steady and the ACK buzzer will silence once alarms have been acknowledged NEXT Press To SILENCE THE EXTERNAL BELL Press To isolate silence the external bells EXT The yellow LED labeled EXT BELL ISOLATED will illuminate to confirm BELL To de isolate the bells simply press the button a second time ISOL To ACKNOWLEDGE FAULTS Once to acknowledge all faults in the system The common fault LED will go ACK steady Subsequent faults will require further acknowledgment NEXT Press ISOLATE A DEVICE CURRENTLY ALARM Press ACK To scroll through alarms until the alarm you wish to isolate is on the display NEXT Press The device is now isolated ISOL To RESET THE PANEL SYSTEM seconds NB All alarms and faults must be acknowledged before a system reset is Press Once The LCD will read System Reset Initiated This process may take up to 30 RESET allowed To RESET THE AIR CONDITIONING LATCHING SYSTEMS Once While the system is performing it s reset locate the SCS 8 fan control module SYSTEM and press the button labeled A C TRIP RESET RESET Press SYSTEMS Press Once The air conditioning trip output will automatically reset SYSTEM RESET COPYRIGHT 2000 NOTIFIER INERTIA LTD PAGE 4 1010 2020 OPER
3. ATORS MANUAL BASIC OPERATIONAL PROCEDURES CONT ISOLATE A DETECTOR OR MODULE EG Loop 1 Detector 26 Press ALTER 1 STATUS gt gt Press 11026 ENTER m Z m 2 The LCD will then ask Do you want this point isolated YES Enter Press ENTER i If you re doing only 1 isolate press To exit otherwise continue with next BACK g device SPACE To DE ISOLATE A DETECTOR OR MODULE It is strongly recommended before you de isolate that you first check to see if the detector module you are about to de isolate is currently in alarm by doing a read status on the point See Page 10 Follow the same procedure as Isolating above except answer when the LCD asks Do you want this point isolated YES N Enter Press ENTER To exit otherwise continue with next BACK device SPACE If your doing only one isolate press CAUTION The above serves only as a quick reference guide This system should only be operated by qualified professionals Incorrect operation may result in the systems becoming inoperable Always notify your service company before making any attempt to operate the system Please refer to Page 6 for details of how to enter alphanumeric data COPYRIGHT 2000 NOTIFIER INERTIA LTD 5 1010 2020 OPERATORS MANUAL THE KEYBOARD K 2 A X ERIZE 1531 yoya gt M A n
4. Abbreviation Description 1 SYS SYSTEM STATUS Provides information on currently programmed System Parameters Refer programming manual for details 2 PTREAD READ Provides an instant snap shot of the current status of any device in the system including obscuration levels verification count options etc See Point Read heading below for more information 3 ALM ALARM LIST Provides a list of devices currently in alarm Select to display zones or devices and then use the Previous and Next keys to scroll through the list Press Backspace when finished 4 FLT FAULT LIST Provides a list of devices currently in fault Select to display zones or devices and then use the Previous and Next keys to scroll through the list Press Backspace when finished 5 ISO ISOLATED DEVICE LIST Provides a list of devices currently isolated Select to display zones or devices and then use the Previous and Next keys to scroll through the list Press Backspace when finished 6 MONON MONITOR ON Provides a list of monitors loop inputs currently activated Use the Previous and Next keys to scroll through the list Press Backspace when finished 7 CTLON CONTROL ON Provides a list of control modules loop outputs currently activated Use the Previous and Next keys to scroll through the list Press Backspace when finished Note Press BackSpace at any time to exit POINT READ SCREEN DISPLAY Once you hav
5. Q NOTIFIER INERTIA IRE SYSTEMS OPERATORS MANUAL 1010 2020 INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 3 0 REVISION AUS1 NSW Head Office QLD VIC 7 Columbia Court 16 Lucy St Unit 2 297 Ingles St Norwest Business Park Moorooka Port Melbourne Baulkham Hills NSW 2153 Qld 4104 Vic 3207 Ph 02 9899 4155 Ph 07 3892 6444 Ph 03 9681 9929 Fax 02 9899 4156 07 3892 6455 Fax 03 9681 9930 Notifier Inertia Pty Ltd 002 692 962 PITTWAY COMPANY www inertia com au PAGE 2 1010 2020 OPERATORS MANUAL TABLE OF CONTENTS TABLE OF CONTENT 5 1 eceesaetsecceiusubetsuntsccensaestee 2 BASIC OPERATIONAL PROCEDURES lt 2 cc2s cu ceccchccecdecetecsneneccenseed encescus seceestaraceruceeesieesnedenedeties 3 TO ACKNOWLEDGE SILENCE ALARMS 3 SILENCE THE EXTERNAL TO ACKNOWLEDGE To ISOLATE A DEVICE CURRENTLY IN ALARM TO RESET THE TO RESET THE AIR CONDITIONING To ISOLATE A DETECTOR OR MODULE DE ISOLATE A DETECTOR OR MODULE 2 ccss ecceseeeeeeeeeeeeseneeeessaeeeeneeeeensneesessaeeeessnee
6. YS EXPLAINED ALL SYSTEMS NORMAL DISPLAY When the system is in normal mode ie No faults alarms or isolates it will display the ALL SYSTEMS NORMAL message The insert building name here is a 20 character area which can be customised INSERT BUILDING NAME HERE ALL SYSTEMS NORMAL 13 20 31 12 00 ALARM DISPLAY PHOT Photo Optical Detector ALARM Unacknowledged Alarm ION IONISATION DETECTOR ACKALM Acknowledged alarm THER Thermal Detector CMBO Combination Heat Smoke and lon Detector MON Monitor input ie Break glass pressure switch Alarm of total alarms SUPV Supervisory AX Device Descriptor ALARM 010 06 PHOT APPARTMENT 212 Z010 LEVEL 2 WEST 06 00 1 00 499 Zone and Descriptor Alarm Fault amp Isolate Counters Loop Device FAULT DISPLAY FAULT Unacknowledged Fault ACKFLT Acknowledged Fault FAULT SMOKE PHOTO APPARTMENT 212 Z010 INVALID REPLY 00 F 01 00 499 ISOLATE DISPLAY ISOLAT Isolated device ISOALM Isolated device which is also in Alarm ISOLAT SMOKE PHOTO APPARTMENT 212 7010 ISOLATED DEVICE A 00 F 00 01 499 COPYRIGHT 2000 NOTIFIER INERTIA LTD PAGE 8 1010 2020 OPERATORS MANUAL OPERATING THE PANEL ACKNOWLEDGING Each and every alarm event that takes place on the system is required to be individually Acknowledged This acknowledgment process confirms to the system that an operator is aware of the situation and as such the internal buzzers no
7. all faults Isolated devices however will remain isolated To perform a system reset press the SYSTEM RESET key once BELL ISOLATE The EXT BELL ISOL button will isolate all outputs flagged with Bell Isolate This is to prevent the main bells from ringing during routine testing Also once an alarm has been acknowledged you can press the EXT BELL 1501 button and the bells will silence and remain silenced Note If automatic bell cut off is set once the cut off is initiated the EXT BELL ISOL will remain isolated until a system reset If bell cut off is not set the EXT BELL ISOL can be toggled on off at any time by pressing the button COPYRIGHT 2000 NOTIFIER INERTIA PTY LTD 1010 2020 OPERATORS MANUAL PAGE 9 OPERATING ANNUNCIATORS SCS 8 SMOKE CONTROLLER Each Notifier SCS 8 Smoke Control Annunciator can control up to 8 individual fans as per the requirements of AS1668 Each fan has a 3 position switch and 3 LED indications The 3 positions on the switch are ON Force fan to RUN overriding all other signals AUTO Fan controlled by others but in fire mode follows programmed logic sequence OFF Force fan to STOP overriding all other signals The 3 indicators are Airflow is detected upstream from the fan STOP Airflow is NOT detected upstream from the fan FAULT The fan is not responding to signals given e If the Stop LED is flashing this means the fan has been shut down due to sm
8. e entered point read from the read status menu and entered LxxDxx Zxxx then Enter the following display wil appear Status Type Description _ NORMAL SMOKE PHOT COMPUTER ROOM SMOKE AFT V 000 034 5 226 Isolated Alarm Fault Tracking AVF AVF Sensitivity of Alarm Address Count Silenceable Bell 150 Lxx Dxx Note A detector may be in periodic test during a read status In this case the detector status will be normal but the percentage of alarm threshold will be greater than 100 If this happens wait one minute and then perform read status again COPYRIGHT 2000 NOTIFIER INERTIA PTY LTD 1010 2020 OPERATORS MANUAL PAGE 11 ALTER STATUS MENU The ALTER STATUS menu provides the following options Selection Abbreviation Description 1 ISO ISOLATE FUNCTION Provided the ability to isolate de isolate individual points on the system Enter the detector module or zone number and then select Y to isolate or N to de isolate Press backspace to exit 2 CTL CONTROL MODULE ACTIVATE DEACTIVATE This provides the ability to manually activate de activate any control point CMX output on the System Enter the LxxMxx then select Y N 3 DSEN DETECTOR SENSITIVITY Provides the ability to change each detectors sensitivity level Sensitivity set to L Low M Medium H High 4 TIME TIME CHANGE Provides the ability to change the system clock time 5 DIA SYSTEM DIAGNOSTICS Invokes a s
9. easaaesessaneeeseneasesaaeseesaeeeessnaeseseaesesseneeeeseeeseseaeeeeees SYSTEM OVERVIEW 2 se A E E E ABOUT PASSWORDS USING THE ALPHANUMERIC 6 LCD DISPLAYS EXPLAINED ALE SYSTEMS NORMAL ALARM DISPLAY FAULT DISPLAY ISOLATE DISPLAY OPERATING THE PANEL 2525 dense ACKNOWLEDGING pero SCROLLING anssen rannan DISPLAYING CURRENT ALARMS AND FAULTS A BEUL ISOLATE erinin E E IET O ENOO EEIN OIO POINT READ SCREEN DISPLAY ALTER STATUS MENU 55 anerhtuescers tase ae Oaa a a a aaaea aa Eaa ISOLATE FUNCTION ae Eeoa 11 ENABLE DISABLE THE HISTORY 1062 HOW SET THE DATE AND 15 COPYRIGHT 2000 NOTIFIER INERTIA PTY LTD 1010 202
10. elf diagnostic systems check 6 WALK WALK TEST Invokes walk test mode for 1 man detector testing Walk test will automatically exit after 15 minutes of no alarms Please refer to walk test heading below for further information WALK TEST PROCEDURE Walk test is a feature used for 1 man detector testing Menu options are as follows Selection Abbreviation Description 1 SEL Select Loops for Walk Test Select the loops to perform walk test on 2 UNP Unprogrammed Device Report Print a report to the printer showing a list of all unprogrammed devices on the loop s 3 UNI Uninstalled Devices Print a report to the printer showing a list of all uninstalled devices on the loop 5 4 TEST Tested Device Report Print a report to the printer showing a list of all tested devices on the loop s 5 UNTST Untested Device Report Print a report to the printer showing a list of all untested devices on the loop s 6 EXIT Exit Walk Test Mode It is important that walk test be correctly exited to return the system back to it s normal condition The panel will automatically exit walk test mode after 15 minutes of no alarms The procedure for walk test is as follows Enter walk test mode Select one or more loops for walk testing Test detectors amp input modules Print reports Exit walk test mode returning panel to normal COPYRIGHT 2000 NOTIFIER INERTIA PTY LTD PAGE 12
11. essor based system used for the detection and warning of fire alarm conditions for commercial residential and industrial buildings Unlike conventional fire control panels the 1010 2020 intelligently communicates with each detector and Input Output module on the entire system Thus providing accurate information as to the exact point of alarm and the ability to operate specific outputs using programmable logic functions The method of communication with field devices is a high speed proprietary protocol capable of supporting up to 99 detectors and 99 modules per two wire loop The 1010 panel is capable of 4 loops and the 2020 is capable of 10 loops Each or these panels may then be networked together on our customised network protocol known as Notifier Net which provides peer to peer or master slave networking allowing may thousands of detectors and Input Output I O points to be monitored and controlled The system can also be connected into our proprietary Network Control Station NCS which is a windows based graphical control centre for controlling the entire fire alarm network Each of the panels can also accommodate up to 32 Annunciator cards each can provide 32 x fully programmable LED indications 16 x single pushbutton isolate functions 8 x AS1668 fire fan control modules 8 x relay outputs remote LCD displays etc These will be discussed later in the manual These systems due to their immense flexibility require a firm understanding o
12. f the total operation of the system for their correct operation Please ensure that the following document is read in its entirety before making any attempt to operate the system ABOUT PASSWORDS As the program in the system is critical to the correct operation during fire alarm conditions it is protected from modification by a five digit password All other features are available without password protection Please ensure the password is recorded and stored in a safe place as it remains unique and your key to future system modification USING THE ALPHANUMERIC KEYBOARD As the system requires alphanumeric entry each key on the main keypad is designed to serve multiple purposes For instance pressing the 3 key when in data entry mode will display the letter 3 on the LCD pressing it a second time will display the letter D and so on The alphabet letter s relating to each key is printed directly above the corresponding numerical key By pressing a different key you will automatically accept your previous letter and move on two of the characters contained on a particular key for instance the letter D and the number 3 are need to be entered in succession then press the NEXT CHAR key to accept the current letter and move on For example E g To enter 1034 loop 1 detector 34 Keystrokes Result COPYRIGHT 2000 NOTIFIER INERTIA LTD 1010 2020 OPERATORS MANUAL PAGE 7 LCD DISPLA
13. ill now display Enter Number entries to clear 1 400 Select number and press ENTER To ENABLE DISABLE THE HISTORY LOG Enter programming mode by pressing PROG Enter 5 digit password KK KKK Select 8 HIS To Enable Start the history log Select 1 START To Disable Stop the history log Select 2 STOP COPYRIGHT 2000 NOTIFIER INERTIA LTD 1010 2020 OPERATORS MANUAL PAGE 15 HOW TO SET THE DATE AND TIME Enter Alter Status menu by pressing STATUS Select 4 TIME Ly You will then be prompted to enter the following Valid Reponses Enter the month 1 12 Enter the day of month 1 31 Enter the year 0 99 Enter the day of week 1 5 SAT Enter the hours in military time 0 23 Enter the minutes 0 59 Do you want daylight savings enabled Y N COPYRIGHT 2000 NOTIFIER INERTIA PTY LTD
14. l WALSAS a d N Snivis FETI H 9 SNLYLS Vv 9101081 71138 NO SNIVIN 709 1531 W3LSAS ee C ALIMNOV4A 6 831 91 3 INSLSAS NOILOSLIG LNSDITISLNI 0202 0 0 ved ve Jopajep Be Jaquinu AA ynes ues W 0 Jequinu 9001 AK 4 Bulssauppy 8980 498 20850 enuey ONY pod uny 055 ofdginuu 555444 sse eqejostep N 16303 won 0 amp 5 389118372 4501 ssaud JES OL 7 juano E 1081 Sseud 94 2 joued suoljonujsuy 5 SWALSAS 38481 COPYRIGHT 2000 NOTIFIER INERTIA LTD PAGE 6 1010 2020 OPERATORS MANUAL SYSTEM OVERVIEW The Notifier Inertia fire systems 1010 2020 intelligent fire detection and alarm system is a microproc
15. longer require sounding Any subsequent alarm will re activate the internal buzzer and require re acknowledgment When multiple faults come into the system simultaneously due to broken cables missing devices system faults etc only one acknowledge function is required This acknowledgment performs a block acknowledge of all faults in the system A monitor device or detector which is set as tracking Non Latching will also require acknowledgment when it clears it s alarm state All events on the system must be acknowledged before a system reset can be performed SCROLLING As the LCD is only 2 lines to scroll from one event to the next simply press the ACK NEXT key DISPLAYING CURRENT ALARMS AND FAULTS Once all alarms and faults have been acknowledged the system maintains a list of all current alarms and faults in the system which can be scrolled through individually This can be done by simply pressing ACK NEXT to step through the list The list priority is Alarms in chronological order then Faults amp Isolates in Loop Device order Continual scrolling will wrap around back to the beginning Once a new alarm occurs the scrolling process is cleared and the cursor position is set back to the first event alarm in the list RESETTING As alarms on the system are generally latching a System Reset is then required to return the panel back to its normal condition A system reset will clear all alarms from the system and
16. lt report 5 ISO All isolated devices report 6 MONON All monitor modules active report 7 CTLON All control modules active report Select desired option and then press ENTER the screen will than ask PRESS 1 REQUEST 2 ABORT The report will then be sent directly to the system printer Note If you do not have a system printer a laptop computer can be used in terminal mode to receive the information EXTRACTING THE HISTORY LOG Select 2 HIS from special functions menu The following screen will now appear PRESS 1 PRINT 2 DISPLAY 3 STEP 4 RANGE STATUS COPYRIGHT 2000 NOTIFIER INERTIA LTD PAGE 14 1010 2020 OPERATORS MANUAL 1 PRINT Print history log directly to system printer 2 DISPLAY Displays the History log on the LCD and scrolls automatically STEP Displays the history log on the LCD and scrolls one event each time the ENTER button is pressed 4 RANGE STATUS Displays the number of events in the system Note If selecting items 1 2 or 3 you will be prompted to enter the first event and last event Event 1 is the oldest and event 400 will be the most recent To CLEAR THE History LOG Please note that clearing and enabling disabling the history log requires knowledge of system password and should only be performed by the Service Company responsible for the system Enter programming mode by pressing PROG Enter 5 digit password Select 8 HIS Select 3 CLEAR The screen w
17. oke being detected in the supply air duct to the fan Auto mode only e Each fan can be individually controlled in fire mode or in normal mode The operation of the fan in auto mode is programmed specific for each project e The A C trip reset button on the top of the module doubles as the lamp test button when not in fire mode ACM 16AT The Notifier ACM 16AT 16 way pushbutton Annunciator is used for single press operation of system functions Dependent on the configuration Each push button also has one RED and one Amber LED Each button can be programmed for a different function ie Function of Button RED LED AMBER LED Output activate deactivate Output Activated Output In Fault Zone isolate de isolate Zone in alarm Zone is isolated or in Fault Module isolate de isolate Module In Alarm Module Isolated or in Fault ACM 32R The Notifier ACM 32R Annunciator has 32 x LED indications which are fully programmable Each LED can represent 1 x detector module or zone and will illuminate red when in fire mode or when operated LCD 80 The Notifier LCD 80 Mimic is a remote LCD mimic which has a 4 x 20 LCD displaying text messages as per the main system LCD From this point you can acknowledge scroll and reset the panel as per the main panel control COPYRIGHT 2000 NOTIFIER INERTIA PTY LTD PAGE 10 1010 2020 OPERATORS MANUAL READ STATUS MENU The READ STATUS menu provides the following options Selection
18. orrect operation the panel continually performs a series of automatic chamber tests on all intelligent detectors installed in the system If a detector fails one of these automatic chamber tests it will generate a Fault message eg DET FAILED TEST DRIFT COMPENSATION OUT OF TOLERANCE etc These messages signify either the detector may be incapable of generating an alarm or has become contaminated and may cause a false alarm Either way it is important that your service company be contacted immediately to repair or replace the indicated device Please note While the fire panel carries out this test a detector the LED s on the detector stop blinking for 10 seconds COPYRIGHT 2000 NOTIFIER INERTIA PTY LTD 1010 2020 OPERATORS MANUAL PAGE 13 SYSTEM HISTORY EVENT LOG The panel has the option to store a history buffer of the last 400 events on the system These events can then be displayed or printed in event order or grouped in reports If this feature has been enabled it can be accessed as follows To enter system history menu ress the Special Function key FUNCT once The following screen will then appear PRESS 1 RPT 2 HIS PRINTING REPORTS Select 1 RPT from special functions menu The following screen will then appear 1 SYS 2 POINT 3 ALM 4 FLTS 5 150 6 7 CTLON 1 SYS Total system report 2 POINT Full device report 3 ALM All devices in alarm report 4 FLTS All devices in fau
Download Pdf Manuals
Related Search
Related Contents
取扱説明書 サンワ*完格サィン 取扱説明書 Bedienungsanleitung EMX2 User Manual - AuCom Electronics Samsung 54kg Diamond Drum Lavarropas WF8508 Manual de Usuario Comment le faire en LaTeX - Cahiers GUTenberg User`s Guide Urban Cultivator Commercial Manual IRIS LLNR User's Manual DVR autónomo serie 1U Manual de Usuario Copyright © All rights reserved.