1. EBDSPIR HB AD Product Guide lectronics intelligent energy control High bay PIR presence detector 1 10V dimming Caan The EBDSPIR HB AD PIR passive infrared presence detector provides automatic control of lighting loads with optional manual control It is specifically designed for the detection of movement in high bay lighting applications such as warehouses and factories Overview Output Channel 1 comprises a mains voltage relay capable of simple on off switching while Output Channel 2 provides dimmable control of 1 10V ballasts Functioning as a presence detector the unit can turn lights on when an area is occupied and off when the area is empty Optional settings allow lights to be turned off in response to ambient daylight or to implement a maintained illuminance daylight harvesting system All functionality is fully programmable using an IR handset Front features Mounting Bezel Lee Sensor Lens which covers PIR Sensor IR Receiver Light Level Sensor Status LEDs Back features Retaining Spring Dimmable Control Output Connector Channel 2 Power Input amp Switched Output Connector Channel 1 Switch Input Retaining Spring Connector PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level
2. To cancel the burn in function simply select a time of 0 Note that when the lamps are changed the burn in time should be set again Installation The EBDSPIR HB AD is designed to be mounted using either e Flush fixing or e Surface fixing using the optional Surface Mounting Box part no DBB Both methods are illustrated below Flush Fixing Hole 64mm Warning be careful bending springs when mounting unit Pull out spring tab and rotate spring arm as shown Wire stripping details Important lt lt _____ Ensure that the cables are formed as shown Ga 0 before affixing the cable clamp The clamp MUST clamp the outer sheath s only 6mm Bend cores as shown 35 mm Readback function UNLCDHS handset only The UNLCDHS has the ability to read back the settings stored in a device To read back individual parameters Navigate to the parameter and press the R Read button whilst pointing at the device The handset will click when the parameter has been read back the device will flash its LED and the value will be shown against the parameter in the menu To read back all of the parameters in a menu Press and hold the R Read button for more than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be
3. Note that whenever the an external switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Select No for a 30 second delay on start up If Yes is selected there will be no delay on start up and the detector will always power up detecting iia Disables detection leaving the relay output permanently off with the dimming output operational This mode is used when the unit is for maintained illuminance only The On Delay to allows the first channel to switch on after the second channel A typical application for this would be where a detector is controlling lighting and air conditioning in an area When the occupant is detected the lighting will be turned on immediately whereas the air conditioning may be turned on after 15 minutes If the area is vacated and the detector times out before the delay then the air conditioning would never go on The delay can be set only for channel 1 using the on delay parameter When the detector turns off a delay is instigated to prevent retriggering In certain circumstances this delay may not be enough This parameter allows the delay to fee scenes Ve changed Factory default se amp 4 Restores factory default settings Channel Modes Switch only r i Fe Usually used for absence detection in this mode the dimming channel is not used Switch and dim Default The detector will swi
4. e Absence The load is manually switched on When the area is no longer occupied the load will automatically switch off after the adjustable time period has elapsed In either case sensitivity to movement of the PIR sensor can be adjusted using the Sensitivity parameter HINT To assist in setting the Sensitivity turn on the Walk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Brighter Lux Off Level Ambient Light Level Lux On Level Darker Occupancy detected Maintained Illuminance daylight harvesting The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level maintained illuminance or daylight harvesting Overview It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time to guarantee lamp life refer to the manufacturer s datasheet for details As this EBDSPIR HB AD is able to dim the lamps using 1 10V the product provides a facility to disable this for a given period of time Operation By setting the Burn in parameter you can select a time during which the lamps are not allowed to deviate from maximum output The unit counts the time and even remembers how long has elapsed in the event of a power failure
5. Sensor Measures the overall light level in the detection area Status LEDs The LED flashes Red to indicate the following 17 Walk Test LED active Gy when movement is detected 41S I x lo Valid setting received Q Power Input amp Switched Output Connector Channel 1 Used to connect mains power to the unit and to connect a switched load Dimmable Control Output Connector Channel 2 Used to connect 1 10V controllable ballasts and transformers for dimmable loads Switch Input Connector Two input terminals can be used to manually override the dimming levels and override the lights on or off Detection diagram 15m Aisle mounting Align indents with aisle ee go te o 2 Ps S E q Detection pattern Installation Choosing a Suitable Location The EBDSPIR HB AD is designed to be ceiling mounted and must satisfy the following criteria Avoid positioning the unit where direct sunlight may enter the sensor element Do not site the sensor within 1m of any lighting forced air heating or ventilation Do not fix the sensor to an unstable or vibrating surface Sensor functionality Detection Mode The Detection Mode for both output Channels 1 and 2 can be set to behave in Presence or Absence mode e Presence When movement is detected the load will automatically turn on When the area is no longer occupied the load will automatically switch off after an adjustable time period
6. On Level value Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Pf eo Returns the unit to the default settings DEFAULTS Pe Determines how long the output will be at 100 1 50 0 so that lamps burn in The burn in time is not affected by power supply interruptions o Presence mode allows the output to turn on when movement is detected and off when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Advanced programming Detector Parameters Once the detector is turned on this value sets how long the lights will stay on once movement has ceased Select 0 for 10 second delay use for commissioning only Walk Test LED Off On or Off When set to On this causes a red LED to flash on the sensor when it detects VA Y movement Use this feature to check for adequate sensitivity levels Time Out 20 minutes 0 99 minutes Time adjustment Manual Time Out 0 99 minutes lights may turn on inadvertently during the presentation if the occupants are still for the manual timeout period so adjust the timing carefully When a manual operation occurs either via the switch input or the infrared it x Y invokes the timeout period Example 1 a detector in presence mode has a detector timeout of 15 m
7. commands will be indicated by a red LED flash See page 1 for details of other LED responses Note other functions on the UHS5 which are not shown below are not applicable to this product t Number of Shift key presses SHIFT UHS5 Handset Graphics Description Parameter Default Name Value Off Lower Time Out Time adjustment Turn lights on or to raise lights Turn lights off or to lower lights O When set to On this causes a red LED to flash on the sensor when it detects movement Use this feature to check for adequate sensitivity levels Once the detector is turned on this value sets how long the lights will stay on once movement has ceased 20 mins seconds Lux on level Switch level on Lux level setting to prevent the luminaires being switched on if the ambient light level is sufficient adjustable between 1 and 9 The luminaires will always be switched on at level 9 Light Level 6 600 2 200 Sets a target light level to be maintained by the 5 500 lighting system T as 9 999 disabled Lux off level Switch level off Sensitivity Presence Absence Lux level setting to switch the luminaires off during occupancy if the ambient light level goes above the setting adjustable between 1 and 9 Level 9 will always keep the lights on This setting can be used for window row switching Note the Lux Off Level value must always be greater than the Lux
8. e Presence Presence or Presence mode allows the output to turn on when movement is detected and off Absence when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Lux on level 1to9 Sets a minimum light level below which the PIR sensor is enabled allowing lights Switch level on For a higher resolution to be turned on by movement a scale of 101 199 is Note the Lux Level Off value must always be greater than the Lux Level On value available Lux off level 1to9 Sets a maximum light level above which the PIR sensor is disabled preventing Switch level off For a higher resolution lights from being turned on by movement a scale of 101 199 is available Light Level 1 to 998 999 Sets a target light level to be maintained by the lighting system J maintained illuminance Iaa Memorise Yes or No eee eee this is set to Yes the last manual lux level set will be memorised and used as BES new switch on level Off value 0 to 99 Dimming output level when switched off 0 99 If a non zero off value is set then the output will toggle between this value and Lae off depending on the switch level on and off values For example if it is light outside the fittings will be off if there is no occupancy If it is dark outside they will adopt the preset off value This feature is only enabled if Min value is set to 99 Burn in O disabled or Determines how long the output w
9. edited and then saved as a Macro Notes If a parameter s has been missed because of a communication error the missing value s is replaced by dashes When reading back the Channel 1 relay where fitted will temporarily be switched off and will return to it s normal state 2 seconds after the read back has been completed Wiring diagrams Multiple luminaires may be connected in parallel to Channel 1 via the N and L Out terminals as long as the maximum total load is not exceeded Channel 2 dimmable output of the EBDHS AD can be used to control the light output of luminaires that are fitted with dimming ballasts transformers The ballasts transformers can be connected in parallel to Channel 2 via the DIM and DIM terminals Refer to the specification on page 12 for ballast quantities The wiring examples below show common methods of connecting the output channels for a single detector unit Single channel dimming Functions Switches the luminaire with occupancy and maintains illuminance Dims and switches using optional centre biased retractive switch MK K4900 or similar Configured to presence detection Turns on automatically with occupancy Maintains illuminance Press and release down switch to turn off Press and release up switch to turn back on Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Configured to absence detection Press and release up s
10. erminal Capacity See diagrams opposite 0 15kg 230VAC 10 50Hz Channel 1 switching 10A of lighting and or ventilation including incandescent fluorescent compact fluorescent low voltage by switching the primary of transformer Channel 2 dimming Maximum number of 1 10V ballasts is 10 On 724mW Off 260mW Basic insulation only Although low voltage this is not an SELV output and should be treated as if mains potential Use mains rated wiring 2 5mm EBDSPIR HB AD Temperature 10 C to 35 C Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Type Class 2 IP rating IP40 Compliance EMC 2004 108 EC LVD 2006 95 EC Part numbers Part number Description Detector EBDSPIR HB AD High bay PIR presence detector 1 10V dimming Accessories DBB Surface mounting box UHS5 Programming IR handset UNLCDHS Universal LCD IR handset IMPORTANT NOTICE This device should be installed by a qualified electrician in accordance with the latest edition of the IEE Wiring Regulations and any applicable Building Regulations ESTA energy systems trade associatior FM 45789 EMS 534520 Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice 12 lectronics intelligent energy control C P Electronics Ltd Brent Crescent London NW 10 7XR United Kin
11. gdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Ref WD490 Issue 1
12. ill be at 100 so that lamps burn in The burn 4 to 999 hours in time is not affected by power supply interruptions Fade value 0 to 99 After occupancy ceases this dimming output level is loaded for the fade time adjustable between 0 and 99 Fade mins 0 to 99 This is the time period adjustable between 0 and 99 minutes that the luminaire will be held at the fade value before turning off A value of 0 ae the fade function Speed On Measured in 0 1 Determines the dimming response speed after the setup time has finished x sec intervals Speed Set 5 Measured in 0 1 Determines the dimming response speed during the set up time Measured in 0 1 x sec intervals sec intervals If set to 0 will disable dimming for Set seconds below used if fittings are required to warm up before dimming Set Seconds 120 1 to 999 seconds Determines how long the dimming response set up period lasts on power up or on setting change This enables the desired lux level to be achieved rapidly when the x v4 lights come on or during setup Switch Modes 2 position switch Default A single centre biased retractive switch will be used to control both channels x VA together together 1 position switch A single position retractive switch controls both channels together x z together 10 This page intentionally left blank 11 Technical data Dimensions Weight Supply Voltage Frequency Maximum Load Power consumption Dimming output T
13. inutes and a manual timeout of 3 minutes When the user leaves the room they press the off button The sensor will revert to automatic after 3 minutes and then walking back in the room will turn the lights on Example 2 using the settings above the user turns the lights off say for a presentation but stays in the room Every time a movement is detected the manual timeout period is re triggered but when it doesn t pick up for the short timeout period the sensor will timeout and revert to automatic This means the Sensitivity On 1 min to 9 max Sensitivity level for detecting movement when the detector is already on UHS5 V VA sets Sensitivity On and Off to the same value Sensitivity Off 1 min to 9 max Sensitivity level for detecting movement when the detector is off UHS5 sets s Sensitivity On and Off to the same value Lux time 0 disabled 1 99 minutes Power Up State ee On or Off On Delay 0 99 minutes Inhibit i to 999 seconds If the detector measures the lux level and decides that the output needs switching on or off as a consequence the lux time must elapse first If at any time during the timed delay the lux change reverses then the process is cancelled Lux Time enables absence detection to be implemented with a lux off level set When the button is pressed the lights will go on regardless of ambient light level However if there is sufficient ambient light they will turn off again after the Lux Time
14. mediately Set the timeout to 10 seconds vacate the room or remain very still and wait for the load to switch off Check that the load switches on when movement is detected The unit is now ready for programming Fault finding What if the load does not turn ON e Check that the live supply to the circuit is good e Check that the load is functioning by bypassing the sensor e g link terminals L and L Out on Channel If the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range HINT The Walk Test LED function can be used to check that the unit is detecting movement in the required area What if the load does not turn OFF e Ensure that the area is left unoccupied for longer than the Time Out Period e Ensure that the sensor is not adjacent to circulating air heaters or lamps Basic programming The functionality of the EBDSPIR HB AD is controlled by a number of parameters which can ff gt be changed or programmed by any of the following devices e UHS5 Infrared Handset See below for programmable functions e UNLCDHS Infrared Handset with LCD See user guide for full programming details For most basic programming operations the UHS5 handset can be used and the following procedures are based on using this device Point the handset at the Sensor and send the required programming commands to the unit as shown below Valid
15. tch and dim the lighting together x y together User Modes Scene Override Off Select the individual scene between 0 and 6 1 min output 2 10 3 25 4 50 5 75 6 100 If the lights are on sending the IR command will turn them off immediately After the manual timeout period described above the sensor will revert to automatic Override On If the lights are off sending the IR command will turn them on immediately and revert to automatic operation using the manual timeout period cancel Pe Cancels the on or off override returning the detector to normal operation CEA Advanced programming Channel 1 Switching Channel Detection Mode Presence Presence or Presence mode allows the output to turn on when movement is detected and off Absence when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Lux on level 1to9 Sets a minimum light level below which the PIR sensor is enabled allowing lights Switch level on For a higher resolution to be turned on by movement a scale of 101 199 is Note the Lux Level Off value must always be greater than the Lux Level On value available Lux off level 1to9 Sets a maximum light level above which the PIR sensor is disabled preventing Switch level off For a higher resolution lights from being turned on by movement a scale of 101 199 is available Channel 2 Dimming Channel Detection Mod
16. witch to turn on Maintains illuminance Press and release down switch to turn off Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Channel mode Set to Switch and dim together E DIMMING KS BaLLasT X DIMMING LUMINAIRE 1 10V NEUTRAL LIVE Oo gt lt 0 CIRCUIT PROTECTION IF REQUIRED CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection Single channel switching Functions Switches channel 1 only with occupancy optional override switch No dimming output Configured to presence detection Turns on automatically with occupancy Press and release down switch to turn off Press and release up switch to turn back on Turns off after occupancy Configured to absence detection Press and release up switch to turn on Press and release down switch to turn off Turns off after occupancy Channel mode Set to Switch only Switch mode Set to 2 position switch together Note a single position switch can be used instead to toggle the output set to 1 position switch separate NEUTRAL LIVE Oo gt lt 0D CIRCUIT PROTECTION IF REQUIRED oF wg LUMINAIRE NON DIMMING CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection Power up test procedure When power is applied to the unit the load will turn on im
Download Pdf Manuals
Related Search
Related Contents
"user manual" 平成27年度 国民宿舎もちづき荘新館客室内トイレ改修工事 Diseño e Implementación de un Sistema de Control para la gGE Druck - Test Equipment Depot Samsung 19 collu HD monitors ar īpaši asu attēlu Lietotāja rokasgrāmata 取扱説明書 - キヤノン Smeg PV630N hob 1PH813/1PH816 Duplex AES GCM 10G for OTN Data Sheet, Xilinx Edition Copyright © All rights reserved.