1. FOCUS E Parameter overview 1 10 Parameter overview Note 3 Parameters can be processed as described under Parameter Settings No Meaning Adjustment range Code level DE German GB English IT Italian RU Russian Fl Finnish DK Danish P001 Languaoe selection LT Lithunian SE Swedish PL Polish all guag ES Spanish PT Portuguese FR French NL Dutch LV Latvian TR Turkish CZ Czech HU Hungarian P012 Max pressure for pressure range 1 0 bar 4 bar maximum system pressure limitation USER P013 Max pressure for pressure range 1 3 bar maximum P012 less min hysterisis USER P014 Max pressure for pressure range 2 0 bar 4 bar maximum system pressure limitation USER P015 Max pressure for pressure range 2 3 bar maximum P014 less min hysterisis USER P020 Auto restart Automatic restart after power failure 0 Off 1 On USER P021 Auto restart time time until restart after power failure 30 s 3600 s USER P022 Short stop limiting value 0 s 3600 s USER P031 After running time 0 s 600 s USER Anti freeze protection Compressor starts when final P032 compression temperature drops below 5 C and switches 0 On 1 Off USER off as soon as 20 C are reached P034 Continuous operation Compressor does not switch off 1 On 0 Off USER but stays continuously in idling operation P042 Booster pressure 0 12 bar
2. Terminals Type of Function Description Rating terminal 1 2 Tension Relay output Ready for operation 2A 30V DC 250 with ohmic load V AC with ohmic load spring Make contact 0 6A 250 V AC 50 60Hz with inductive load terminal Power factor 0 4 3 4 5 Tension Relay output Fault free 2A 30V DC 250 with ohmic load V AC with ohmic load spring Grouping terminal 3 0 6A 250 V AC 50 60Hz with inductive load terminal Break contact terminal 4 Power factor 0 4 and make contact terinal 5 6 7 Tension Relay output Operation 2A 30V DC 250 with ohmic load V AC with ohmic load spring Make contact 0 6A 250 V AC 50 60Hz with inductive load terminal Power factor 0 4 8 9 Tension Relay output Load operation 2A 30V DC 250 with ohmic load V AC with ohmic load spring Make contact 0 6A 250 V AC 50 60Hz with inductive load terminal Power factor 0 4 10 11 Tension Relay output Serviving 2A 30V DC 250 with ohmic load V AC with ohmic load spring Make contact 0 6A 250 V AC 50 60Hz with inductive load terminal Power factor 0 4 12 13 Tension Relay output Pre selection remote 2A 30V DC 250 with ohmic load V AC with ohmic load spring Make contact 0 6A 250 V AC 50 60Hz with inductive load terminal Power factor 0 4 14 15 Tension Relay output Switch clock 2A 30V DC 250 with ohmic load V AC with ohmic load spring Make contact 0 6A 250 V AC 50 60Hz with inductive load terminal Power factor 0 4 34 Tension Digital input Monitoring compresse
3. Single leakage The abbreviation LE stands for single leakage measurement measurement The displayed value shows the annual operating load times due LE to leakage Continuous leakage The abbreviation Le stands for continuous leakage measure measurement ment The displayed value shows the annual operating load Le LC times due to leakage When the abbreviation LC is displayed continuous measure ment has been carried out for more than a week In case of single leakage measurement a single measurement operation over six hours serves to determine the hourly operating load times per year due to leakage In order to obtain a precise value it is imperative that no operational com pressed air consumption take place during measurement resp production is to be shut off for at least six hours If measurement is actuated by means of the control system measurement will be deferred by six hours This allows you to activate the leakage function already in the afternoon causing the measur ing operation to start in the evening six hours later to continue over night Unlike continuous value measurement single value measurement is also pos sible if several compressors are being operated in the basic load mode at the same time Starting separate single value measurement of each compressor enables you after a six hour measurement period to read and to add up all of the single values of the compressor control units Their total v
4. ssssssssse 9 OA e ee eere et 11 ITO 352 2er bis RR add alle cocida 11 BANDI 12 Set date time sic aui d ob pt dtl lui m sen t adn 12 Display of version necem 13 1 4 Settings epe 13 Entering of codes in general ssse 13 Parameter Sta onere iit oe ew 14 Set parameters crono Lade den Ero pde i Le de dud 14 Pat tretere ete eet id a 15 1 5 Group parameters Parameter management 22 Servicing Interval 2 en eee i oed bete iet 22 Parameter factory SettiNQ oooonnncccnnnnnacccccnnnconccncnnnnannccnnnnanncccnnnna 22 Base load switch control sssssssss eene 22 Switch clock i t e t eine 23 Unplanned compressed air requirement sssssssss 24 View input Status ieia raa aat aa a a aa a A enne eere 24 BOGE FOCUS compressor control for screw compressors Page Ill Index 1 6 1 7 1 8 1 9 FUNCIONS aa na rar 24 Motor switching limitation eseen nn 24 Power failure cycle protection 24s0nnnnnnennnnnennnnnnnnnnennnn nn 25 Motor spinning time usnnneneennnnnnnnennnnnnnnennnnnnnnnnnnnn nn 25 Star phase time Control c cccecceececeeeeeeeeeeeceeeneeeaeeeeeeeeeeeeeeeees 25 Pressure range selection sess 25 Parameterization of frequency converter ssssssssss 26 TAN test a MER Dn eL ML M 26 Base lo
5. 2 Two compressors are to be involved in the base load switching mode 3 Three compressors are to be involved in the base load switching mode 4 Four compressors are to be involved in the base load switching mode After setting the required value press the ENTER key in order to confirm data entry Then use parameter 071 to determine the base load switching interval time Exception the value is set at 1 while the base load switching function is deactivated Page 20 BOGE FOCUS compressor control for screw compressors FOCUS EN Settings P071 Setting base load switching interval time Calling parameter P070 enables you to determine the time interval serving to change compressor priorities The keys gt amp allow you to set a value between 0 and 250 hour No cyclic change will take place if the value is set at 0 In such a case the priority sequences can be controlled by a switch clock Siehe Switch clock on page 23 After setting the required value press the ENTER key EL in order to confirm data entry P075 Base load switching p Pressure range 1 Pressure range 1 of the BLS is the default pressure setting for the base load switch control By parameter P075 the top pressure setpoint for pressure range 1 is set P076 Base load switching p Pressure range 1 Pressure range 1 of the BLS is the default pressure setting for the base load Switch control By parameter P076 the bottom pressure se
6. by actuating the ENTER key According to the entered code either windows for various settings or a parameter list opens When entering the second fifth digit actuating the INFO key i causes an erasing of the previous digit so that it can be entered again Actuating the INFO key i when entering the first digit the code setting is left and you return to the version display BOGE FOCUS compressor control for screw compressors Page 13 FOCUS EN Settings CODE Meaning 17391 User code parameter list 00000 Parameter display access previous code 00111 Setting Resetting servicing intervals 00988 Parameter restoring 00798 Switch clock settings 00356 View input status Note 35 If the USER code SERVICE code or BOGE code is entered it is possible to return to the previously left parameter list within 30 minutes after having left this list without having to enter the code once more by entering Code 00000 Parameter list If one of the codes for the parameter list is entered USER code SERVICE code BOGE code it depends on the entered code which of the parameters can be processed An arrow at the beginning of the line shows where the cursor is currently posi tioned and if a value under this code can be changed If only the outline of the arrow gt is displayed the value under this code cannot be changed if the arrow is completely filled gt the value can be chang
7. in the switch cabinet of the master com pressor A FOCUS control is changed into a master unit by setting its parameter 70 number of compressors at any value above 1 This means at the same time that for any other FOCUS control equipped slave compressors this number must be set at 1 Transmitter for system pressure An additional module rotary switch in position 2 for rail mounting with analogue input 7 6 signal 7 7 will be available as of version 1 18 for integration of a System pressure transmitter using two wire technology output 4 20 mA and a shielded cable it is for example to be pneumatically connected to a col lection point such as a buffer tank The module is snapped on directly next to the main circuit board As of version 1 18 parameters 075 to 078 are used as pressure setpoints for both BLS pressure ranges Addresses and output releases The addresses and output releases of the compressors equipped with serial connection Modbus RTU or relay modules have to be set according to the following table Compressor Address Relay module rotary switch Output release 1 Master 0 n a Internal 2 2 2 External 3 3 3 External 4 4 4 External As regards shut off or reduction on pressure band 2 by means of integrated real time clock please see Chapter Unplanned Air Demand BOGE FOCUS compressor control for screw compressors Page 27 FOCUS EN Functions Th
8. measurement methods Start single measurement Single leakage measurement will not start but six hours after actuation of this process Your are herefore requested to make sure that after the deferred start of the measurement process no operational compressed air production will take place over a period of six hours that the compressor be set into the ready mode by means of the control unit and that the green LED of the control be lit that when using the external flow release the external flow release may not be shut off neither manually nor by the switch clock In order to start single measurement 1 Keep ENTER key pressed for three seconds The value next to LE starts blinking 2 Press ENTER key again for three seconds The number 9999 appears and single value measurement will start in six hours hours After a period of twelve hours the single measurement value will be displayed This value will be saved until a new measurement pro cess is carried out If during measurement a power failure takes place the number 9980 will be displayed In such case it is recommended to repeat the measurement pro cess at a later stage If during measurement the compressor is put out of operation the number 9990 will be displayed i e the compressor is switched off and the energy loss due to leakage could not be properly determined during said measurement In this case too the measurement process should be
9. pressure for pressure range 2 0 bar 4 bar max pressure of compressor type USER P078 Base load switching min pressure for pressure range 2 3 bar maximum P077 USER Page 38 BOGE FOCUS compressor control for screw compressors
10. 061 55 Pressure dew point dryer too low T 56 Pressure dew point dryer too high 57 Temperature compressed air outlet Parameterizable BOGE FOCUS compressor control for screw compressors Page 35 FOCUS EN Fault messages Fault Meaning Compressor no switch off 58 Control unit LEFT key does not open 59 Control unit RIGHT key does not open 60 Basic module recognizes TAN error X 61 Communication with RS485 Module faulty 62 Communication with converter module faulty X 63 Communiction with analogue outlet module faulty 64 Motor bearing temperture too high X 71 Run time memory 1 72 Run time memory 2 73 Type of parameter 74 Dryer and compressor servicing due 75 Software version of TAN and basic module not compatible 79 Operating data memory error 80 Memory error of 2nd operating data memory 81 Parameter memory error X 82 System pressure transmitter faulty 83 Communication with system pressure module defective 84 Data reconciliation error in system pressure module 91 Mainboard input 42 signals fault see circuit diagram X Fault messages for special types 90 Lack of insulation X 92 Condensate drain of microfilter X 93 Condensate drain of dryer X 94 Dryer X 95 Microfilter X 96 Supply voltage X 97 Side duct ventilation excess current X Page 36 BOGE FOCUS compressor control for screw compressors
11. 3 as withstandard bus optional bus closed not used no change of live bit non existent 2 or Master closed not used change of live bit non existent 1 or Master opened w o influence w o influence w o influence 1 closed Range 2 no change of live bit non existent 2 or not used closed Rangel not used non existent 1 or not used BOGE FOCUS compressor control for screw compressors Page 25 FOCUS EN Functions Parameterization of frequency converter TAN test Besides the selection of the pressure range via the timer the digital input of the basic module terminal 42 common inputs reference terminal 31 is availa ble to select the pressure range n case the contact for the external selection of the pressure range has never been active before an influence on the selec tion of the pressure range is not given The input is only considered if it has been closed once After that the open contact always means the selection of the first pressure range and a closed contact the selection resp release of the second pressure range In case the switch clock and the external contact if registered by the control require different pressure ranges pressure range 1 is active Pressure range 2 becomes active if selected by the external contact and the Switch clock or if the external contact is closed and no pressure range selec tion is made by the time As soon as the ON key 1 is pressed the frequency co
12. Auto Restart is activated If the value 0 is set the Auto Restart is deactivated When switching off the compressors with the Emergency Off button the Auto Restart function is not active P021 Auto Restart time The time set in seconds is the time that elapses after a power failure before the compressor starts again with activated Auto Restart or Remote On Off P022 Short stop time limiting value The time set in seconds is the time that should elapse at least after a motor stop before the switch on pressure value of the air supply network is reached or dropped below again To be able to do so the FOCUS control constantly monitors the air supply net work and learns the necessary data Thus these data are automatically kept in case of net structure changes Note The default value should only be changed in consultation with BOGE Service P031 After running time Interval during which the compressor remains at least in the idling phase after a load run before it switches to Ready or Off status This value is normally set to zero Under special circumstances increased after running times may be necessary which can be set at this place P032 Anti freeze protection Here the automatic anti freeze protection can be rendered inoperative Ifthe compressor is in Ready status and the oil temperature final compression temperature drops below 5 C the compressor starts automatically and runs in idling until the oil temperat
13. BOGE AIR THE AIR TO WORK ROG COMPRESSED AIR SYSTEMS Operating instructions FOCUS compressor control for screw compressors www boge com Operating instructions FOCUS compressor control for screw compressors BOGE KOMPRESSOREN Postfach 10 07 13 33507 Bielefeld Otto Boge Stra e 1 7 33739 Bielefeld Fon 49 5206 601 0 Fax 49 5206 601 200 Mail info boge com Net www boge com Issue 01 2012 No 596 1011 01 Nominal price 5 00 BOGE FOCUS compressor control for screw compressors Page Index Part 1 1 1 The BOGE control concept eene 1 FOCUS Installation Aue die tete do ten ern 1 Gonttrol Ult d ARDEN ERG 2 1 2 OperatiOn iere eere reed PUR RERO REA REIS HERE lios 3 Switch on the Control e a a a a T e E E 4 Switch on the compressor cooooococccccccccccnccnnonnnnnononnnnnnnnnnnnnnnannnnnnnnnnnn 4 ico m da 4 R n up phase Na a 5 Load operation sriid heer ed Ede e eei teen Lead 5 ia Na oe 5 Switch off the compressor cooccococcococcccnccoconocononnnnnononnnnnnnnnnnnnnnnnnnnnnnnnn 5 Maintenance acc oett e etnies 5 1 3 Display information uurssrnresnnnsennnnnnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnn 6 Main diSplay is nne e de E E pete do 6 Bl PE EE 7 Maintenance iui ttc daret rte ril RE ee aae erede ada 7 Operating mes 7 Leakage monitor nn ced Rn eb tita eem 8 Start leakage measurement
14. USER P044 Type of message oil filter 1 Fault 0 Warning USER 0 for Master P050 Modbus address 2 4 for additional compressors USER 1 248 for other applications P051 Modbus baud rate 1200 115200 USER P052 Modbus communication parameter te ONONE PONONGA A USER 0 for Master P053 Modbus address module 2 4 for additional compressors USER 1 248 for pure control applications P054 Modbus baud rate module 1200 115200 USER BOGE FOCUS compressor control for screw compressors Page 37 FOCUS E Parameter overview No Meaning Adjustment range Code level P055 Modbus communication parameter module a e ONOnda Seven BOUd Td USER P060 Contacttype compressed air treatment 0 Break contact 1 Make contact USER P061 Type of message for compressed air treatment 1 Fault 0 Warning USER P063 External output release 0 USER P064 Monitoring of external output release 0 USER P065 Remote Start Stop O USER P066 Key switch 0 USER P067 Function of input 42 0 Pressure range 1 Monitoring USER P070 Interval time until base load switching e USER P071 Interval time until base load switching 0 250 USER P075 Base load switching max pressure for pressure range 1 0 bar 4 bar max pressure of compressor type USER P076 Base load switching min pressure for pressure range 1 3 bar maximum P075 USER P077 Base load switching max
15. ad switch control with additional compressors 27 Warning message Fault message csseeseeses 30 Warning message Fault message sssssssssseee 30 Warning message coooooococccccccccocococononnnononnnnnnnnnnnnnnnnn nana nen nnnannnnrn nen 30 Pre acknowledgement sssssseee enne 30 Acknowledgement of message 45 Watchdog Timer Reset 30 Fault messages eiie iiit elek 30 Data of external CONNectiONS oocccccccccnnnnnnnnononccnnnnnnnnnnnnananananos 31 Basic module E 2 cc cece eee A E E E SE 31 Analogue output module ssssesee een 32 RS 485 mod le sran eet een 32 Analogue input module seem 32 Wire cross sections of external connections nn 33 Fault messages true a Rer n ran RA EIER ARES 34 List of fault messages ssssssssssseeeeenenes 34 Parameter overview eeseeseeeseseeseeeeene nennen nnn nnne nnne 37 Page IV BOGE FOCUS compressor control for screw compressors FOCUS EB The BOGE control concept Installation 1 1 The BOGE control concept FOCUS is a compressor control unit It is installed into the switch cabinet as part of the compressor and serves as a compressor control device Prior to commissioning and before accomplishing any kind of maintenance or servicing work please read the functional descriptions of both cont
16. al 3 Tension External RS485 Signal B Input differential voltage spring interface max 12 V terminal Analogue input module Terminals Type of Function Description Rating terminal 6 7 Tension Analogue input System pressure meas 4 20mA terminal 7 spring urement 24V terminal 6 terminal max 22mA DC input resistance 150 Q Separated from external supply voltage due to double insulation Page 32 BOGE FOCUS compressor control for screw compressors FOCUS Wire cross sections of external connections Data of external connections For external connections the following conductor cross sections are to be used Screw terminals Terminal Cross section Fixed flexible min 0 2 mm Fixed flexible max 25 mm Flexible with ferrule with without plastic sleeve min 0 25 mm Flexible with ferrule with without plastic sleeve max 25 mm AWG kcmil min 24 AWG kcmil max 12 2 conductors with identical cross section fixed min 0 2 mm 2 conductors with identical cross section fixed max 1 mm 2 conductors with identical cross section flexible min 0 2 mm 2 conductors with identical cross section flexible max 1 5 mm 2 conductors with identical cross section flexible w AEH ferrule without plastic sleeve min 0 25 mm 2 conductors with identical cross section flexible w AEH ferrule without plastic sleeve max 1 mm 2 conductors with identical
17. alue corres ponds to the annual number of hours of operating load times as a result of leakage in your compressed air networks Continuous leakage measurement is designed to continuously calculate operating load values at six hour intervals Page 8 BOGE FOCUS compressor control for screw compressors FOCUS Display information Start leakage measurement Unlike single leakage measurement continuous leakage measurement can also be started during current daily production with measurement starting at once The first value obtained after a six hour period will probably be distorted since any operational compressed air production will be added to any potential leakage related operating load Most probably however no operational pro duction will be in effect during any subsequent value measurement The then obtained value which is exclusively due to leakage will be smaller than the first obtained value The control system is designed to always display the smallest value of all measurements in this case however the last obtained value This means that any distorted calculation of production operating loads will be excluded In order to determine exact leakage measurement values make sure that dur ing a time frame of 12 hours there will in all probability be no operational com pressed air production After editing leakage in the control display please proceed as follows in or der to start either of the available
18. can be accomplished as described above P001 Language The following display languages are available German DE English GB Italian IT Russian RU Finnish FI Danish DK Lithuanian LT Swedish SE Polish PL Spanish ES Portuguese PT French FR Dutch NL Latvian LV Turkish TR Czech CZ Hungarian HU P012 Panax Pressure range 1 Pressure range 1 is the default pressure setting for the compressor Here the upper pressure target value for pressure range 1 is set As soon as the net pressure has reached p the compressor changes from load run to idling P013 Pain Pressure range 1 Pressure range 1 is the default pressure setting for the compressor Here the bottom pressure target value for pressure range 1 is set If the com pressor is in the Ready state and the net pressure drops below p the com pressor starts with the output Note If the pressure range selection is effectuated by a master control or the exter nal contact you have to observe when setting the pressure ranges that in case of a power failure or fault of the master control the compressor control eventually falls back on this pressure range P014 Panax Pressure range 2 Pressure range 2 offers the possibility for pressure decreases the value must not be set above that of pressure range 1 Here the upper pressure target value for pressure range 2 is set As soon as the net pressure has reached Pmax the compresso
19. cross section flexible w TWIN AEH without plastic sleeve min 0 5 mm 2 conductors with identical cross section flexible w TWIN AEH without plastic sleeve max 1 5 mm Tension spring terminals Terminal Cross section Capacity of terminal 0 5 1 5 mm Single wire 0 5 1 5 mm Stranded wire 0 5 1 5 mm with ferrule 0 5 1 5 mm AWG conductor 26 14 BOGE FOCUS compressor control for screw compressors Page 33 FOCUS EN Fault messages 1 9 Fault messages List of fault messages Fault Meaning Compressor no switch off 1 Final compression temperature too high gt 110 C X 2 Motor temperature too high X 3 Fan motor X 4 Wrong rotational direction X 5 Compressor system pressure too high X 6 Suction filter differential pressure too high 7 Oil filter differential pressure too high Parametarizabie P044 8 Oil separator differential pressure too high D toc ren 10 Motor servicing due 11 Compressor servicing due 12 System pressure decrease too slow 13 Frequency converter signals fault no release X 14 Temperature too low lt 3 C X 15 Suction regulation Proportional control 16 Net pressure transmitter faulty X 17 Sys pressure build up too fast increase too sharp X 18 Fault of an external control 19 Power up phases too short too many motor switching cycles 20 Continuous contact of an e
20. d 24 31V DC 10mA spring air treatment input resistance 3 kQ terminal Terminal 34 against terminal 31 24V 40 Tension Digital input Output release 24 31 V DC 10 mA spring Terminal 40 against input resistance 3 kQ terminal terminal 31 24 V 41 Tension Digital input Remote Start stop switch 24 31 V DC 10 mA spring Terminal 41 against input resistance 3 kQ terminal terminal 31 24 V 42 Tension Digital input Switchover pressure 24 31 V DC 10 mA spring range input resistance 3 kQ terminal Terminal 42 against terminal 31 24 V 51 Screw External RS485 Earth GND terminal interface 52 Screw External RS485 Signal A Input differential voltage terminal interface max 12 V 53 Screw External RS485 Signal B Input differential voltage terminal interface max 12 V BOGE FOCUS compressor control for screw compressors Page 31 FOCUS Analogue output module Data of external connections Terminals Type of Function Description Rating terminal 1 2 Tension Analogue Actual frequency value max 28 mA max load 400 Q spring output 4 20 mA terminal 1 terminal against terminal 2 GND RS 485 module Terminals Type of Function Description Rating terminal 1 Tension External R8485 Earth GND spring interface terminal 2 Tension External R8485 Signal A Input differential voltage spring interface max 12 V termin
21. display can be reached in the menu by pressing the keys Here the name of the control the software number and the manufacturer are displayed If the key amp gis pressed now you get to the Module Info display Here the addresses and the installed software versions of the connected mod ules are shown The first display refers to the basic module Address 0 all other connected modules can be displayed by actuating the keys e Module Address Position of rotary switch Basic module 0 TAN 1 FC frequency converter module 10 0 FC module for connection of soft starters 11 1 System pressure module 12 2 Dryer module 20 RS485 module 30 0 Analogue output module 50 0 Note 3 Relay modules are not displayed If the display of a module is flashing the communication with this module is faulty You can leave Module Info by actuating the INFO key i 1 4 Settings Entering of codes 1 Actuating the key leads from the main display 1 to the version display in general 2 If now the ENTER key is actuated a display is shown asking you to enter a 5 digit code see code list 3 The first place value of the code is blinking By means of the keys gt a digit can now be changed 4 By actuating the ENTER key or key the cursor jumps to the next value and the value can be changed accordingly 5 Oncethe last digit has been set the code is acknowledged
22. e base load switching see also Base load switch control with additional compressors page 27 As of version 1 18 parameters P075 to P078 Pmax and p of BLS pressure ranges 1 and 2 are added These parameters regulate the output release of the base load switch control via pressure measurement Page 22 BOGE FOCUS compressor control for screw compressors FOCUS E Group parameters Parameter management Switch clock By entering Code 00798 the switch clock can be adjusted 1 Having entered the code you get to the selection of the switch channels This is shown by the blinking of the first letter in the top line 26 channels from A Z are available The channel can be selected using the keys e 2 First the weekday starts blinking The desired weekday can be selected using the keys lt gt One switch clock channel is deactivated if two dashes are set instead a weekday 3 By pressing the ENTER key the input is acknowledged and the cursor jumps to the display of the hours Using the keys gt this value can now be set as well and acknowledged by means of the ENTER key The same applies to the minutes 4 Next the priority sequence of the compressors see also Base load switch control with additional compressors page 27 can be selected Each combination of the numbers 1 4 is possible The priority sequence 0000 effectuates that from the corresponding point of time
23. e base load switching control of FOCUS can be operated either at cyclic in tervals or by means of an integrated real time switch clock also see Chapter Switch Clock In case of cyclic operation use Parameter 71 to set the cycle time For this reason the switch clock must either not be used no weekday on any channel or in case of any other type of use no priority sequence must be con tained in the respective switch clock channel nor the sequence 0000 but only EE When using the switch clock for base load switching purposes parameter 7 1 has to be set at zero 26 switch clock channels switch points are available Entering a weekday causes a channel to be activated Any priority sequence is available for selection In addition shut off is possible by using the 0000 pri ority sequence Selection of the second pressure band by means of the switch clock allows temporary change to a lower pressure range Additionaly the switch clock is equipped with a potential free change over contact Speed controlled compressors with a FOCUS control system are possible to be operated in the base load switch control mode This requires Modbus RTU communication in order to ensure control of the max priority base load com pressor and unregulated mode operation at max speed of the remaining compressors As of version 1 18 the base load switching control normally uses the pressure value of parameter P075 as the upper shut off value a
24. ed In the parameter setting actuating the keys amp makes the cursor move one parameter forwards or backwards Use keys amp lt gt to scroll to the previ ous next page To leave the parameter list actuate INFO key i and you get back to the main display If you are in the adjustment range of a parameter it can be left again by actu ating the INFO key i You have to actuate the INFO key i once more to close the list Einstellungen 1c m P4 O m wnr he m m te CTS m mo Qu c a e xe a Uc oi ENSE FAR Pal Pal Pal Pal i tu B C P3 O it B c J c E a gt Set parameters 1 Opening of the parameter list by means of the desired code USER code SERVICE code BOGE Code 2 If the cursor points at the parameter which is to be changed e g maximum pressure in the pressure range 1 P012 this selection is acknowledged by actuating the ENTER key 3 If a digit e g 9 bar is blinking on the right side of the parameter the de sired value can be set e g 10 bar by actuating the keys m 4 By actuating the ENTER key this input is acknowledged and stored Actuating the INFO key i at this place causes a leaving of the setting without accepting the changes You can proceed with every parameter in the same way Page 14 BOGE FOCUS compressor control for screw compressors FOCUS EN Settings Parameters The setting of the parameters
25. ed on Emergency Stop button The Emergency Stop button interrupts the power supply for the con tactor coil The controlis still energized and generates a correspond ing display 1 2 Operation CAUTION Risk of injury If the compressor is not closed there is a risk of injury due to rotating or pro jecting parts resp a crushing hazard because of flaps or doors standing open The compressor may only be operated with all flaps and doors closed Prerequisite The compressor must be electrically and pneumatically connected the power supply voltage must be turned on and the ball valves and or balanced disc stop valves between compressor and compressed air receiver must be opened BOGE FOCUS compressor control for screw compressors Page 3 FOCUS E Operation Switch on the control Switch on the compressor Having connected the compressor to the power supply and having switched on the main switch if applicable the version is displayed if neither Auto Restart nor Remote control are parameterized on which the name of the con trol the name of the manufacturer and the version number are shown First a parameter adjustment between basic module and TAN is performed resp and if applicable the registration of connected and not yet registered ad ditional modules When this procedure has been finished the symbol for the OFF key 9 is flash ing Press OFF key 0 to acknow
26. eek This allows after expiry of another week a higher value compared to the one of the pre vious week to be displayed if the measured minimum value has increased during that period Any potential increase of leakages in the compressed air network will therefore also be possible to be determined Any power failures during measurement will not be indicated by a sequence of digits because new values will be calculated every six hours and because any such power failure during measurement will not prevent the values of the sub sequent measurement to be displayed If the value next to Lc is blinking and no measurement is intended to be carried out Press INFO key i The value will stop blinking and the measurement process is not started Pressing the key amp enables you to access the operating hours display Page 10 BOGE FOCUS compressor control for screw compressors FOCUS Display information Info 1 Pressing the key in the operating times display causes the control display to show Info 1 This display serves to show information on the compressor set up D K Vorort Aus intern Status RS485 1 19200 8N1 The RS485 interface is parameterized as a slave Address baud rate data bits parity stop bits no communication has taken place as yet O K The last communication has taken place less than 1 minute ago Time This serves to indicate when the last valid communi cat
27. en the LEDs are activated and deactivated in a variable sequence As an additional control the symbols of the three LEDs are displayed and shown with a black background when activated so that itis clear which off the LEDs should be illuminated You leave the LED Test by pressing the INFO key i Page 26 BOGE FOCUS compressor control for screw compressors FOCUS EN Functions Base load switch control with additional compressors The control contains a master control function for a total of up to four compres Sors This means that a maximum of three additional compressor controls can be connected either by means of the integrated or optional serial RS485 in terface Modbus RTU or also by means of optional relay modules one relay module per compressor to the master parameterized FOCUS control The serial connection is only suitable for compressors with FOCUS or RATIO control The relay modules are suited for machines equipped with BASIC control all other BOGE compressor controls or controls with single pole control pressure Switch using two terminals only As regards any other compressor makes e g with electronic controls BOGE is unable to warrant proper connection which may prove to be extremely ex pensive too It is recommended not to use a star shaped connection for the serial RS485 module but to make sure to use separate connections from compressor to compressor All relay modules must be installed
28. ency operation function Four compressors 10 bar all of which are equipped with a FOCUS control and a frequency converter are connected by means of RS485 interfaces The pressure at user s facility is to be completely released over the weekend and over night and in addition be able to be reduced Providing sufficient receiver network volume the pressure values can be set according to the following table allowing pressure reduction by 1 5 bar which can be actuated by an ex ternal contact or by means of a switch clock as regards switch clock actuated pressure reduction also see chapter Unplanned compressed air require ment Compressor Parameter setting in bar Control target pressure in bar No P075 P076 P077 P078 P012 P013 P014 P015 P016 P064 Pressure range 1 Pressure range 2 1 Master 9 5 75 8 0 6 0 10 89 85 74 13 0 8 7 7 2 2 3 4 no function 99 88 84 73 98 87 83 72 97 86 82 71 1 2 0 8 7 7 2 1 1 0 8 7 7 2 1 0 0 8 7 72 Parameter P016 has to be set in such a way that the control target pressures of the frequency converters are identical for all compressors BOGE FOCUS compressor control for screw compressors Page 29 FOCUS Warning message Fault message Warning message Fault message Warning message Pre acknowledgement Acknowledgement of m
29. essage 45 Watchdog Timer Reset Fault messages 1 7 Warning message Fault message As far as pending messages are concerned there is a difference between warning and fault messages Depending whether an input is defined as fault or warning either only the warning is displayed ort he compressor is switched off at once via a fault mes sage All warning and fault messages are saved by the control in the LogBook to gether with operating states and time In case of a pending warning or servicing message the compressor remains in operation and this status is visible by means of an orange coloured blinking LED on the control By actuating th INFO key i the message is displayed and by means of the message code list it can be identified By actuating the INFO key i once more the compressor states are displayed at the time of the warning This warning can be acknowledged by pressing the ENTER key In case you are in the status display the acknowledgement can be effectuated by ac tuating the ENTER key two times If various warnings are pending at the same time they can only be displayed and acknowledged when the reason for the first warning has been eliminated If a warning is pending when the control is powered up this is signalled at once by means of the flashing yellow coloured LED In this case the boot display can be left by pressing the OFF key 0 or you can get to the main menu by displaying and acknowledging the warn
30. f 1 x output and 1 x no output each BOGE FOCUS compressor control for screw compressors Page 7 FOCUS Display information Leakage monitor Pressing the key din the operating hours display causes the control display to show leakage The display serves to enable you to determine the energy loss resulting from any potential leaks in your compressed air network To this purpose the control unit measures the time period duration of the operating loads during which under normal circumstances no production of compressed air takes place as for example over night or operation down times This however is conditioned on the fact that operational compressed air pro duction be discontinued for a protracted period of time and that the compres Sor be set into the ready mode by means of the control system In case of a potential pressure reduction below the preset minimum pressure value result ing from leaks in the compressed air network this compressor automatically Switches into the operating mode in order to recover the set pressure range The leakage measurement serves to record the duration of the operating load times and to extrapolate them for the whole year This allows you to quantify any leakages and to easily determine their portion of additional costs due to any energy losses A potential leakage is either measured by a single LE or continuous Lc value measurement e re Lc 173 hea
31. g a master control ES Note For all units within the Bus system this value must be the same BOGE FOCUS compressor control for screw compressors Page 17 FOCUS EN Settings P052 Modbus frame The protocol frame of the RS485 interface is determined here 8 data bits are transmitted and the parity can be selected O Odd E Even N None as well as the number of stop bits 1 or 2 Note For all units within the Bus system this value must be the same P053 Modbus address module The set value 0 248 indicates the Bus address of the RS485 interface on the basic module for the communication with an external Bus system e g a mas ter control 0 stands for master additionally connected compressors have to be specified with the values 2 4 Note The address must be unique in the Bus system P054 Modbus baud rate module The value shown here indicates the data signalling rate Bits s of the RS485 interface of the module for the communication with additional compressors Note For all units within the Bus system this value must be the same P055 Modbus frame module The protocol frame is determined here 8 data bits are transmitted and the par ity can be selected O Odd E Even N None as well as the number of stop bits 1 or 2 Note For all units within the Bus system this value must be the same P060 Contact type for compressed air treatment B
32. g phase with flashing green LED is completed beforehand as already described in the chapter Idling last passage When operating the control the battery voltage has to be checked from time to time If the voltage drops too far a warning message is created In this case the battery has to be replaced he display of the TAN has to be cleaned with a damped yet not wet cloth from time to time As cleaning agents customary household detergents for greasy surfaces can be used No further maintenance is required for the control BOGE FOCUS compressor control for screw compressors Page 5 FOCUS Display information Main display 1 3 Display information This is the main display in the control menu Here the net pressure the final compression temperature and the compressor status are displayed display CD By pressing the key lt gt the system pressure is displayed instead of the final compression temperature display 2 Py T 9 bar Net pressure p Shows the current net pressure System pressure ps Shows the current system pressure Final compression temperature C Shows the current final compression temperature Compressor status Meaning Off Compressor is switched off Ready Compressor is Ready and starts automatically as soon as the conditions are fulfilled Run up Compressor is in star phase Load operation Compressor runs in delta phase the sole
33. he current system pressure value is registered during motor start up and fitted with an adjustable offset With regard to the system pressure relief monitoring switch off and restart lock functions a 1 3 bar pressure threshold along with the booster pressure max value is provided P044 Message type for oil filter By this parameter it can be declared whether a pending message of the oil fil ter monitoring is defined as a warning or as a fault This adjustment has effects on the properties of the control Whereas for a warning only a message is cre ated the compressor is additionally cut off at once as soon as the parameter is defined as a fault For this parameter setting 1 means Fault and setting 0 Warning P050 Modbus address The set value 0 248indicates the Bus address of the RS485 interface on the basic module for the communication with an external Bus system e g a mas ter control For the settings of the integrated base load switch control the value 0 is avail able for the master Additionally connected compressors have to be specified with the values 2 4 For other applications the address can be matched with the requirements All addresses from 1 248 are possible Note The address must be unique in the Bus system P051 Modbus baud rate The value shown here indicates the data signalling rate Bits s of the RS485 interface of the main board for the communication with an external Bus system e
34. ing Even if you leave the boot display via displaying the warning nevertheless the OFF key 9 has to be actuated once before the control resumes its normal function If a message is acknowledges and the reason for it is not yet eliminated the corresponding LED remains continuously illuminated As long as a fault or warning is signalled by the LED the fault message can be displayed by press ing the INFO key i again This message must be pre acknowledged first For a complete acknowledgement of the message switch off of the yellow coloured LED the control must be de energized for a short time In case of a fault message the compressor is switched off at once without idling phase A red blinking LED signals a pending fault message and the display shows the corresponding message number at once By actuating the INFO key i the operating states at the time of the fault are displayed Actuating of the ENTER key leads to the leaving of the operating states dis play and pressing the key once more acknowledges the fault The red LED is continuously illuminated after the acknowledgement of the fault and the compressor status display shows Fault until the fault has been recti fied Only then the compressor can be started again Page 30 BOGE FOCUS compressor control for screw compressors FOCUS Basic module Data of external connections 1 8 Data of external connections
35. ion has taken place up to 7 days C2 C3 C4 When parameterized as a master and master control this serves to display which of the compressors are in communication Blinking of the combination indicates defective communication On Off Local via keyboard Remote via contact and or Bus On Compressor is switched on Off Compressor is switched off Output release Internal via internal pressure sensor External Output release via contact and or Bus Yes Output release enabled No Output lock is active Auto Restart n a No Auto Restart after control power failure Time Auto Restart active Auto Restart time Note Changes to the displayed settings have to be accomplished by means of the parameter settings if applicable see also section 1 4 Settings page 13 or by changing the automatically registered configuration Info 2 The information to the control settings as master control resp the current sta tus of the integrated switch clock are displayed here Infostz Pressure range Activated pressure range System pres Shows the current system pressure net pressure sure net pres sure Switch clock A Z active switch clock channel n ano channel active Priority se Set priority sequence active compressors and time in h and min until quence time next change of priority until change of priority The priority sequence is only disp
36. is ready for operation and the pres sure control is active as long as no Timer Off is due or an external pressure control was parameterized If the compressor status Ready is displayed the compressor is in the ready for operation status That means that the compressor automatically re starts pressure and or time controlled as long as the conditions to do so are ful filled Page 4 BOGE FOCUS compressor control for screw compressors FOCUS E Operation Run up phase Load operation Idling Switch off the compressor Maintenance The compressor motor is started and run up as already described under Ready The status display changes from Ready to Run up To be able to do so the system pressure at the compressor must be decreased and the motor spinning time finished Furthermore no limitation of the motor switching cycles is allowed Otherwise the display Ready is shown in the motor status display For the star delta contactor combination applies First the star contactor and 20 ms later the mains contactor is switched on The display Run up signals the corresponding status of the control The Run up resp Star phase is finished after termination of the run up time by switching of the control into the Load run status When changing into the Load run the control switches on the delivery valve Compressors which are controlled accordingly now change into the delta switching Frequency con
37. isplay BOGE FOCUS compressor control for screw compressors Page 23 FOCUS EN Functions Unplanned compressed air requirement If compressed air is needed when the priority sequence 0000 is active 1 The compressor can be started by actuating the ON key 1 in case of multiple systems the complete plant at the Master control Parameter P070 must be set to more than one compressor The control accesses the priority sequence of channel A and pressure range 1 For this reason the priority sequences 0000 and must not be saved under channel A This status will be canceled by actuating the OFF key 0 or the next switch clock channel by means of an active priority sequence Pressing the 1 key once causes the operating readiness of the master to be restored The green LED is lit 2 Alternatively the switch clock channel A and the saved kind of remote con trol contact or data bus can be selected by the corresponding setting of parameter P063 In case of an external control the priority sequence of channel A stays active until the external signal is cancelled In case of ac tive base load switch control only the master must receive this signal see also Base load switch control with additional compressors page 27 Ry Note This function is valid even if channel A weekday is not activated ES Note If the function Remote On Off is used only the second varian
38. layed if the number of compressors in the base load switch control is set to a value above 1 In case the number of com pressors is set to 1 n a is displayed here BOGE FOCUS compressor control for screw compressors Page 11 FOCUS Display information The display of the priority sequence shows the currently effective sequence for selecting the compressors Depending on the setting the priority sequence is changed cyclically base load switch control or selected by means of the switch clock For each parameterized compressor the current output signal status the cur rent priority level and the time until the next priority change with switched on base load switch control is displayed If only the switch clock is active cyclic changing time set to 0 no time is displayed Meaning C1 C2 C3 means that the compressors 1 3 are connected and the sequence 1 2 3 is chosen in this case none of the compressors receives an output signal C1 C3 C2 means as in the first example that the compressors 1 3 are param eterized although they are selected in the sequence 1 3 und 2 and further more compressor 1 receives an output signal in this case The output signal status is shown by means of a black background in the graph ical presentation of the compressors in the display ES Note Changes to the displayed data have to be accomplished by means of the Basic Load Switching Control see also chapter 1 4 Set
39. ledge and exit the display Otherwise Auto restart and or Remote On Off is activated After the recurrence of the power supply net power failure the display shows a countdown starting with the set Auto Restart time s When this time is ex pired the compressor switches to Ready status and starts automatically as soon as the prerequisites are fulfilled In case faults occur when the compressor is powered up they are displayed immediately after the parameter reconciliation The fault has to be acknowl edged to get to the main display see also section 1 7 Warning message Fault message page 30 CAUTION Risk of injury If the compressor is not closed there is a risk of injury due to rotating or pro jecting parts resp a crushing hazard because of flaps or doors standing open The compressor may only be operated with all flaps and doors closed Ready At first OFF should be displayed in the bottom frame the status display of the compressor If EMERGENCY STOP is displayed for the compressor status the Emergency Stop button has to be unlocked first If the status display shows Fault the control is faulty and the malfunction has to be corrected first see also section 1 7 Warning message Fault message page 30 Once this has been accomplished and the display shows the OFF status the compressor can be put into the Ready status by pressing the ON key 1 A green LED signals that the compressor
40. nd of parameter P076 as the lower switch on value All other necessary shut off and switch on pres sure values are automatically calculated All other necessary shut off and Switch on pressure values are automatically calculated The proper internal pressure switch points of the connected compressors are to be selected such as to prevent such compressors from switching them selves off within the pressure band as set at the master unit In this conjunc tion possible pressure pipe losses are to be taken into account In case of in stallations with system pressure transmitter this applies also for compressor 1 Master If pressure reduction parameter 77 is used as upper nominal pressure value parameter 78 as lower value as of version 1 18 is applied all other FOCUS controls using the RS485 interface for connection to the master unit will au tomatically be switched to their second pressure band This is primarily of advantage for speed controlled compressors because their control target pressure is reduced at the same time enabling controlled operation also in pressure range 2 In this conjunction make sure not to use the digital input Pressure Band of the slave compressors and that their switch clocks do not impact on their pressure band The control target pressure is to be set using the correct algebraic sign rela tive to the current upper pressure target value P012 or P014 in parameter P016 of the respective compressor In other w
41. noid valve is closed Converter workload Display of the workload of frequency controlled compressors The solenoid valve is closed Idling Compressor runs in delta phase the solenoid valve is opened Fault A fault has occurred on the compressor compressed air treat ment the compressor is switched off The fault has to be rectified prior to a restart Emergency Stop The Emergency Stop button has been actuated If a dryer module is connected the actuation of the keys in display 1 or display 2 of the main display effectuates that instead of the compressor status the tendency display of the dryer is displayed With a relative humidity of 25 the display is exactly in the centre If the cool ing temperature drops to lt 0 C it is entered into the calculation The display then moves to the left with decreasing temperatures into direction LO If the key lt gt is pressed the compressor status is displayed again Pressing the keys amp gt leads to the next display Page 6 BOGE FOCUS compressor control for screw compressors FOCUS Dryer Display information When connecting the dryer module to the control an additional page with the headline Dryer is displayed in the menu sequence On this page the operat ing data of the dryer are displayed Trockner Room temperature Current ambient temperature Dryer efficiency display Ratio between l
42. nverter is energized and the compressor motor starts If the frequency converter is to be parameterized during an absolute motor standstill the ENTER key has to be actuated for three secondes when the compressor is in the OFF status with view of the main display The converter supply contactor picks up but the motor remains switched off the green LED is off This status is illustrated as FC frequency converter Parameter in the status display By actuating the OFF key oO the converter supply contactor drops out If the key is pressed for three seconds during the display of the boot image you get to the display TAN test A test is selected by means of the keys gt and by actuating the ENTER key The TAN test can be left by pressing back or by actuating the INFO key i The TAN test offers a selection of three tests Screen The screen becomes dark and is continuously set up again by means of dark vertical stripes so that all pixels are activated and deacti vated Leave the Screen Test by pressing the INFO key i Keys A display is shown where all keys of the TAN are displayed If a key is actuated it gets a dark background After all keys have been pressed the display goes back to the selection display In case one of the keys is defective a count down of 30 seconds is started When this time is elapsed he display changes automatically back to the selection display LED If this option is chos
43. oad time and total running time in Operating hours Shows the operating hours of the dryer Service interval counter Shows the operating hours until the next servicing Maintenance With the next actuation of the key lt gt you getto the maintenance display Here the information concerning the maintenance times are displayed Wartung Saa enah 3 825 Next motor servicing h Shows the operating hours until the next motor servicing Next compressor servicing h Shows the operating hours until the next compressor servicing Next receiver servicing Shows the number of load changes until the next receiver ser vicing Current battery voltage Shows the current voltage of the battery for the real time clock in the main module Operating times With the next actuation of the key gt you get to the operating times display on this menu page the operating times of the compressor are displayed Motor running time Shows the total operating time ofthe compressor motor in hours minutes and seconds Idling Shows the share of time in which the compressor was idling in hours minutes and seconds Efficiency display Shows the ratio of load energy compared to total operating time energy since the preceding Reset Load cycles of internal receiver Counts the effected load cycles of the internal combination receiver One cycle consists o
44. ords Control pressure setpoint current top pressure setpoint Parameter 16 Page 28 BOGE FOCUS compressor control for screw compressors FOCUS Functions Example with monitoring and emergency operation function Four compressors 10 bar all of which are equipped with a FOCUS control and a frequency converter are connected by means of RS485 interfaces Pressure at user s facility must not completely be shut off should however be able to be reduced Providing sufficient receiver network volume the pres sure values can be set according to the following table allowing pressure re duction by 1 5 bar which can be actuated by an external contact or by means of a switch clock as regards switch clock actuated pressure reduction also see chapter Unplanned compressed air requirement Compressor Parameter setting in bar Control target pressure in bar No P075 P076 P077 P078 P012 P013 P014 P015 P016 P064 Pressure range 1 Pressure range 2 1 Master 9 5 7 5 8 0 6 0 10 74 85 59 13 1 8 7 12 2 3 4 no function 99 73 84 58 98 72 83 57 9 7 71 8 2 56 1 2 1 8 7 7 2 1 1 1 8 7 7 2 1 0 1 8 7 7 2 Parameter P016 has to be set in such a way that the control target pressures of the frequency converters are identical for all compressors Example without monitoring and emerg
45. r changes from load run to idling Pressure range 2 is only active if corresponding adjustments of the switch clock have been made and or the external contact for the pressure range selection is active P015 Pahin Pressure range 2 Pressure range 2 offers the possibility for pressure decreases the value must not be set above that of pressure range 1 Here the lower pressure target value for pressure range 2 is set As soon as the net pressure drops below p the compressor starts with the output Pressure range 2 is only active if corresponding adjustments of the switch clock have been made and or the external contact for the pressure range selection is active P020 Auto Restart Switching On Off of the Auto Restart function network independent on off memory Normally the version display is shown after a power failure which must be acknowledged by actuating the OFF key 0 before the control displays the Off status and the alarm relay returns to the status no fault BOGE FOCUS compressor control for screw compressors Page 15 FOCUS EN Settings If the Auto Restart function is active and the compressor was previously switched on an adjustable count down is started after power recovery Auto Restart time P021 When this time is elapsed the compressor automatically returns to the Ready status The pressure control is active and on demand the compressor resumes the output If PO20 is set to the value 1 and
46. r lamp Warning yellow 4 Indicator lamp Ready green 5 Navigation keys 6 INFO key 1 7 ENTER key 8 ON key 1 9 OFF key o Operating control element Designation Function Navigation keys Navigation in the menu scrolling the displays scrolling of pages in a the parameter display Navigation keys Navigation in the menu displays dryer status navigation in the the a m parameter display setting of values INFO key Display of faults warnings or maintenance messages log book i quitting of settings Page 2 BOGE FOCUS compressor control for screw compressors FOCUS Operation Operating control element Designation Function ENTER key Confirmation of inputs selection of parameters forced idling setting J of FC frequency converter parameters OFF key Acknowledging when switching on the control switching off the compressor switching off forced idling n ON key Switching on the compressor forced idling Warning Flashing Pending warning compressor is working as yet e Y Maintenance Lit Warning already acknowledged compressor is LED yellow working as yet Fault Flashing Upcoming fault compressor is switched off e LED red Lit Fault already acknowledged compressor remains switched off and cannot be restarted until the fault has been rectified Operation Flashing Compressor in idling operation 1 LED green Lit Compressor is switch
47. repeated at a later stage while making sure that the compressor be switched off during measurement If the value next to LE starts blinking and no measurement is to carried out Press INFO key i The value will stop blinking and the measurement process is not started Pressing the key amp enables you to access the operating hours display BOGE FOCUS compressor control for screw compressors Page 9 FOCUS Display information Starting continuous measurement Continuous leakage measurement will start immediately Make sure that during the following days at least for once during a time frame of 12 hours no operational compressed air production takes place thatthe compressor be set into the ready mode by means of the control unit and that the green LED of the control be lit In order to start continuous measurement 1 Press the ENTER key for three seconds The value next to LE starts blinking 2 Press the key The value next to Lc starts blinking 3 Press the ENTER key for three seconds The number 9999 appears next to Lc Continuous measurement will start immediately and keep being carried out After the twelve hour time frame during which no operational production has taken place has been excee ded a sound measurement value is obtained The control system will always save the lowest value A search for the lowest value as a background process will be restarted once a w
48. rnal output release is deactivated if the value 1 is set the monitoring is active In case of activated monitoring the FOCUS automatically switches to internal pressure control and outputs an appropriate warning message as soon as a fault of the external control is registered P065 Remote Start Stop This parameter determines the ON Off switching function of the control via TAN a potential free contact or the Bus In case the parameter is selected unequal 0 a switching On or Off via TAN of the FOCUS is no longer possible Setting Meaning 0 The On Off switching is effectuated solely by the control keyboard local The On Off switching is effectuated solely by the input Remote Start Stop switch continuous contact 2 The On Off switching is effectuated solely by the BUS interface The On Off switching is effectuated solely by the continuous contact re 3 lease function and via the BUS interface however not via the control keyboard In case of Remote On Off the Auto Restart time P021 after a power failure is used for an automatic start delay BOGE FOCUS compressor control for screw compressors Page 19 FOCUS EN Settings P066 Key switch The function of the key switch is set here Setting Meaning 0 The key switch has no function it is deactivated 1 When actuating the key switch the function Remote Start Stop is acti vated 2 When actuating the key swi
49. rol and com pressor carefully First and foremost observe the Safety notes in Chapter 1 of the functional description of the compressor Power input Terminals A1 and A2 for 24 V AC DC Rating 24 V 10 50 60Hz 15 W 24 V DC 10 0 4 A An interruption of the power supply is effected by means of the mains discon nector of the compressor Modules The basic equipment of the FOCUS consists of a basic module and a keypad display unit TAN Amongst others the following modules are optionally available for frequency regulated compressors with a 4 20 mA output for master controls suitable for frequency regu lated compressors with a second RS485 interface for the connection of additional compres sors if the first interface is used otherwise for compressors with built in dryers with changeover contact relay function can be selected by rotary switch system pressure module for a system pressure transmitter on the master compressor Interconnection of the modules may only be completed using the provided leads supplied with the equipment BOGE FOCUS compressor control for screw compressors Page 1 FOCUS EN The BOGE control concept Control unit The display unit comprises a graphic display and 3 indicator lamps LEDs for an additional illustration of the operating modes Fig 1 1 FOCUS operating panel 1 LC display 2 Indicator lamp Fault red 3 Indicato
50. short power failure control volt age if the motor start number would be too high after another start at the cur rent moment and a possible start would probably be delayed For the calcu lation the power failure times provided the real time clock is connected via plug in jumper of the basic module and its voltage see also chapter mainte nance is sufficient are considered This is shown in the Countdown display by means of a once increased Auto Restart time For motors with less than 15 switching cycles per hour the control unit reserves a spinning time of 20 s during contactor operation after switching off the motor contactors A switching on of the motor is disabled within this period of time To reduce starting current when starting the motor by contactors it is first oper ated load free in star phase control and after a short time in delta control The star time is fixed for each compressor type and stored in the control unit It can be changed using parameter P033 The following table refers to links see also section Switch clock page 23 selection Contact Switch clock Standard bus Optional bus Pressure range not used not used determines pressure range non existent acc to Bit 3 0 switches to range 1 or Master more than 1 compres standard bus Bit 3 1 switches to range 2 sor parameterized live bit not necessary not used not used w o influence determines pressure range acc to Bit
51. t is possible View input status Motor switching limitation Entering Code 00356 enables the display of the various digital inputs of the control in the form of boxes As regards allocation the respective terminal numbers of the basic module are shown underneath The inputs having closed contacts are marked with a check in the respective boxes Thus the boxes without a check stand for opened contacts Press the INFO key i to quit the display 1 6 Functions Motor switching limitation is only active when the air requirement makes it nec essary i e after the Motor start count per time base is reached before time Only then does it switch from intermittent to a limited continuous operation or an automatic or remote restart after a power failure is delayed correspond ingly The control unit calculates the through time so that on the one hand the maximum allowed switch count per hour can not be exceeded and unneces sary idling times can be saved as well The minimum time base is 12 minutes It is created automatically by the con trol unit according to the given maximum switch cycle rate per hour Page 24 BOGE FOCUS compressor control for screw compressors FOCUS EN Functions Power failure cycle protection Motor spinning time Star phase time control Pressure range If the function Auto Restart or Remote On Off is activated it is registered after an automatic motor restart following a
52. tch the external output release is activated When actuating the key switch both the external output release as well as the Remote Start Stop function are enabled The settings for external output release P064 and Remote Start Stop P065 have to be effectuated separately under the corresponding parameter num bers P067 Function of input 42 Normally there are three possibilities for a pressure range switch 1 via integrated switch clock 2 via data Bus and 3 via external switch contact at input 42 if P067 shows the value 0 If P067 is set to1 point 3 is no longer valid Input 42 serves as compressor switch off by means of an optional monitoring device when its contact is opened fault message 91 is shown P070 Base load switching determine number of involved compressors The base load switch control see Base load switch control with additional compressors page 27 allows several linked compressors in turns to produce the required quantity of compressed air This parameter serves to determine the number of compressors which are to be controlled by a master FOCUS in the base load switching mode The base load switch control is designed for compressors of the same size Calling parameter P070 enables you to set a value between 1 and 4 by means of the keys gt Setting Meaning The basic load mode function is deactivated because only one compres 1 ps sor is involved
53. the load cycles of the internal receiver are counted One cycle consists of 1 x output and 1 x no output each With the keys lt gt the corresponding servicing interval is selected and acknowledged by means of the ENTER key Now the digit starts blinking and can be changed using the keys gt gt Only after having acknowledged and entered the value by means of the ENTER keys the new servicing interval is accepted and the corresponding down counter restarted By means of the INFO key i this setting can be left without saving the chang es or the counter reading The display of the servicing intervals can also be left by means of the INFO key i With the setting of 2 000 000 receiver load cycles this down counter is deactivated In case somebody has changed any parameters and wants to recover a func tionally safe status the factory setting resp commissioning setting can be re stored To do this the compressor must be in the OFF status Only then Code 00988 can be entered In the displayed window you can read Restore and you can select either Yes or No Should the saved parameters be restored you can use the keys gt to se lect Yes and acknowledge by means of the ENTER key Now the current data on the basic module are overwritten with the factory set values As of version 1 11 setting of the base load switch control BLS is effected by Parameter P070 Number of compressors and P071 Interval tim
54. the output signal is cancelled for all compressors until a new pri ority sequence is generated by another switch clock channel The display effectuates that the switch clock with this channel does not influence the priority sequence but only accomplishes other func tions see below Thus it can be used with other cyclic changes according to the section Base load switch control with additional compressors page 27 5 By actuating the ENTER key the cursor now jumps to the selection of the pressure range 1 2 or ranges are available and the selection can be acknowledges pressing the ENTER key The pressure ranges 1 and 2 can be set by means of the parameter P012 15 means that no pressure range is changed by this switch clock channel Either the pressure range of the previously active channel is kept or a new channel is selected via an external contact 6 Lastthe potential free contact of the basic module terminals 14 15 can be switched Available are 1 contact closed or 0 contact open By actuating the ENTER key the display for the channel starts blinking again and by using the keys lt gt another channel can be selected and adjusted as described above If during the setting of a channel the INFO key i is actuated this setting is left without accepting the changes In the mode Selection of the switching channel the actuation of the INFO key i brings you back to the main d
55. tings page 13 or switch clock settings Date Time Set date time This menu page shows the current setting of the real time clock The time is displayed in hours minutes and seconds and the date with day of the week day month and year In case of a switched off power supply the real time clock is operated by its battery provided the plug in jumper contacts arranged next to it are con nected and their voltage is sufficient see also chapter maintenance In order to set both time and date keep the ENTER key on the menu page date time for three seconds The cursor jumps to the time display and the digits of the hour display start blinking Use keys amp to set digits With the ENTER key the input is acknowledged and the cursor moves to the next field Proceed the same way with all other place values until all values are correctly adjusted In case a value has to remain unchanged just actuate the ENTER key to jump to the next value To leave the time adjustment actuate the ENTER key until none of the place values is blinking any longer Actuate key to reach the previous page or actuate key lt gt to go to the next page If the INFO key i is actuated while adjustments are made to the real time clock this setting is left without accepting the effectuated changes Page 12 BOGE FOCUS compressor control for screw compressors FOCUS EN Settings Display of version The version
56. tpoint for pressure range 1 is set P077 Base load switching p Pressure range 2 Pressure range 2 of the BLS offers the possibility for pressure decreases the value must not be set above that of pressure range 1 By parameter P077 the top pressure setpoint for pressure range 2 is set Note 3 Pressure range 2 of the BLS is only active if corresponding adjustments of the switch clock have been made and or the external contact for the pressure range selection is active P078 Base load switching p Pressure range 2 By parameter P078 the bottom pressure setpoint for pressure range 2 is set Note 35 Pressure range 2 of the BLS is only active if corresponding adjustments of the switch clock have been made and or the external contact for the pressure range selection is active BOGE FOCUS compressor control for screw compressors Page 21 FOCUS EB Group parameters Parameter management Servicing interval Wlartungs interval le Parameter factory setting Base load switch control 1 5 Group parameters Parameter management If the Code 00111 is entered a display for the servicing intervals is opened The servicing intervals fort he compressor the motor and the receiver are set here If a dryer module is connected the servicing interval fort he dryer can be set here as well The servicing intervals for compressor motor and dryer are specified in hours fort he receiver
57. trolled machines display the percentage workload of the fre quency converter as a bar diagram If the set maximum pressure of the compressor is reached in the load run the control switches to Idling Accordingly Idling is shown in the status display As a result an automatic system pressure decrease is effectuated If no after run ning time is set default 0 sec the Idling phase is finished as soon as the sys tem pressure value drops below 1 3 bar if applicable parameterized max booster pressure provided the automatic limitation of start numbers allows it and the compressor changes into the Ready status If the compressor is switched off via the maximum pressure and the net pres sure drops below the set minimum pressure Pin during the idling time the compressor control automatically switches from Idling to Load run and the compressor continues with the output If the compressor is switched off however during a load run or idling phase by means of the OFF key O resp Remote Off it waits with a flashing green LED in the idling phase as described above until the system pressure is decreased before it changes into the Off status With the OFF key O or via Remote Off the compressor is switched off The pressure control is deactivated If this happens when the motor stands still or is just operating in the Run up phase Off is displayed at once in the compres Sor status display and the green LED goes out Otherwise an idlin
58. ure reaches 20 C again If P032 is set to the value 1 the automatic anti freeze protection is deactivated if the value 0 is set the anti freeze operation is active The value 0 is given as default value P034 Continuous operation If pressure losses have to be avoided at any cost in case of relatively small receivers or compressed air net volumes a continuous operation can be acti vated here In case of an activated continuous operation the control never switches back to the Ready status The compressor constantly runs in Idling if it is not deliv ering compressed air The value 1 means that the continuous operation is ac tive O means that the continuous operation is deactivated Page 16 BOGE FOCUS compressor control for screw compressors FOCUS EN Settings P042 Maximum booster pressure This parameter serves to adjust the booster pressure fed to the compressor In case of any potential fluctuations the peak value of the fluctuations is to be set As for compressors that do not additionally compress any pre compressed air supplied from an existing compressed air network the atmospheric pressure 1 bar absolute is to be set as booster pressure For compressors using booster pressure from a compressed air network the existing booster pres sure from the control is to be added to the pressure limit values of the rotation direction and ventilation monitoring systems As regards rotation direction monitoring t
59. xternal control 21 Receiver servicing due 25 Data reconciliation error delat 26 Control unit OFF key does not opent X 27 Control unit ON key does not open X 28 Control unit INFO key does not open 29 Control unit ENTER key does not open Page 34 BOGE FOCUS compressor control for screw compressors FOCUS Fault messages Fault Meaning Compressor no switch off 30 Control unit UP key does not open 31 Control unit DOWN key does not open 32 Net pressure transmitter wire breakage X 33 Compressor system pressure transmitter wire breakage X 34 Compressor system pressure transmitter faulty X 36 Bus live bit faulty 38 Excessive current compressor motor X 39 Fault compressed air treatment PU able 40 FC frequency converter module fault X 41 Battery voltage too low 42 FC frequency converter module not calibrated X 43 FC frequency converter module overflow 44 FC frequency converter module underflow 45 Watchdog timer Reset 46 Watchdog not active 47 f clock resp f CPU discrepant clock frequency 48 TAN identifies internal BUS fault X 49 TAN misses data from basic module X 50 Dryer module Fault dicic 51 Pressure transmitter faulty at dryer Parametenzanie viaP061 52 Cooling temperature sensor Fault De 53 Ambient temperature sensor faulty Fate totale via P061 54 Pressure at dryer too high coolant aratra via P
60. y this parameter it can be declared whether the signalling contact for the compressed air treatment is a break contact or a make contact 0 Break contact 1 Make contact Page 18 BOGE FOCUS compressor control for screw compressors FOCUS EN Settings P061 Message type for compressed air processing With this parameter it is determined whether the pending message of the com pressed air processing is defined as a warning or as a fault This setting has an influence on the performance of the control Whereas in case of a warning only a message is released the compressor is additionally switched off at once when this parameter is defined as a fault In this case setting 1 means fault and setting O warning P063 External release The kind of external release is set by this parameter Setting Meaning 0 Internal release 1 Release via contact 2 Release via contact and an external BUS If a RS485 module is used and parameterized to an address above 0 its ro tary switch must point to zero in any case it serves automatically as an ex ternal output release P064 Monitoring of an external release appliance The parameter P064 is relevant if the pressure control is effectuated externally via the digital input and compressed air has to be available continuously i e no switch off during the night or on weekends seems to be sensible If the parameter P064 is set to the value 0 the monitoring of exte