Contents
1. Space for 12 V 7 Ah battery not included 3 o m O 1 Enclosure mounting points 3 Location of tamper switch 2 Board mounting points Installation guidelines Intelligent Access Controllers are designed assembled and tested to meet the requirements related to safety emission and immunity with respect to environmental electrical and electromagnetic interference as of current relevant standards In addition to the general installation guidelines installers must adhere to any country dependent requirements of local applicable standards Only a qualified electrician or other suitably trained and qualified person should attempt to wire this system to the mains e Mount the unit using screws or bolts through the four mounting holes in the base Ensure that the unit is mounted on a flat solid vertical surface so that the base will not flex or warp when the mounting screws or bolts are tightened TS0866 Four Door Controller Installation Manual Allow 50 mm clearance between the equipment enclosures mounted side by side and 25 mm between the enclosure and any side wall or ceiling Each Challenger system device that has an earth terminal must be earthed by connecting it to a Communications Ea
2. m I ON SR zi OK o 3 L 3 o lo o 2 o ka F2 BATT2 o 29 et 2 o e LJ o o F GL ea F3 AUX am i 3 o gt 6 J E F4 EXT n o 2 0 o 25 e o 28 D Saka 25 o Q o gn o Rx Rx1m 3 v 0 Ta o a LE m o 29 mlos o Tx fo o 29 7 ola gt 8 L 2 e a o ge o 20 Ez TERM an oS 6 o o ON Lee e Bogg o 25 ADDRESS o om do o 8 Di on Ol x gia o a o ABCD o Az m 7 T o 88 gt 7 3 z 9 2 o 000 00 J00000o0 J0 000 i 10C2C3 C 4C5C6C ALARM INPUTS 7C8C Figure 3 legend Item Description 1 Connect the board s earth terminal or lug via minimum 2 5mm GNYE earth cable not exceeding 1 Q to a Communications Earth Terminal CET See System earthing on page 19 for details 2 The board s ground link must remain fitted 3 The AC terminals are connected to the transformer supplied at the factory for models shipped with enclosure 4 Connect the J1 connector s earth terminal to the system LAN s RS 485 data cable shield See Figure 9 on page 21 See also RS 485 LAN cabling on page 20 Di Connect the and terminals to a 12 V sealed lead acid battery 7 0 Ah maximum not supplied 6 Optionally connect the second set of and terminals to a second 12 V sealed lead acid ba
3. an out reader and an out keypad Use 2 pair twisted shielded data cable such as Belden 8723 to connect the controller to RASs 10 TS0866 Four Door Controller Installation Manual e Connect the 12 terminal to the red wire The 12 terminal provides 12 V to LAN devices such as RASs within 100 m cabling distance e Connect the OV terminal to the black wire The OV terminal provides ve DC to LAN devices such as RASs and common 0 V for the RS 485 LAN e Connect the D terminal to the white wire The D terminal is data positive e Connect the D terminal to the green wire The D terminal is data negative e Connect the data cable shield to the LAN earth connection Figure 3 on page 8 item 14 The RS 485 LAN may be used to power devices up to 100 m cabling distance from the controller See Power supply to LAN devices on page 20 for details One set of LAN terminals is provided if you need more than one connection you can use a TS0844 Power Distribution Board to increase the number of terminals Figure 5 Connecting a Smart Card Reader to the local LAN Green Connect shield to earth terminal Terminating the RS 485 LAN All Challenger LAN devices including the panel use a 470 O LAN termination resistor where required LAN termination resistors are used to set the impedance of the LAN to around 220 Q in order to minimise noise The termination resistor may be external or onboard devices with an onboard resisto
4. 12 VDC Auxiliary power 12 VDC gt x U O m D I I l n L 8 Q siren speaker or 1KO 1 4 watt resistor System RS 485 data cable Panel tamper switches Auxiliary power terminals Connect the and auxiliary power output terminals to devices that require 12 VDC power such as detectors Three sets of auxiliary power output terminals are provided if you need more than three connections you can use a TS0844 Power Distribution Board to increase the number of terminals Note The auxiliary power output and siren speaker are supplied from one circuit The maximum current draw for all auxiliary devices local LAN J22 and the siren speaker must not exceed 700 mA RS 485 system LAN Use 2 pair twisted shielded data cable such as Belden 8723 to connect the controller to the Challenger panel e Connect the OV terminal to the black wire e Connect the D terminal to the white wire The D terminal is data positive e Connect the D terminal to the green wire The D terminal is data negative e Connect the data cable shield to the LAN earth connection Figure 3 on page 8 item 4 RS 485 local LAN TS0866 Four Door Controllers can have up to 16 RAS devices such as keypads card readers arming stations or Smart Door Controllers on the local LAN Sixteen devices might be required for four doors where each door has an in reader an in keypad
5. terminate if applicable the LAN segment on each side of the module s isolation barrier Figure 11 RS 485 LAN cabling between two buildings Building A Building B Challenger a Panel T On termination link fitted T Off termination link not fitted TS0866 Four Door Controller Installation Manual 23 Figure 11 legend Item Description 1 LAN segment 1 extends from the Challenger panel to one side of the TS0893 LAN Isolation Interface Termination is ON at the panel and the panel s side of the TS0893 Maximum cabling distance for segment 1 is 1500 metres 2 LAN segment 2 extends from the TS0893 in building A to the TS0893 in building B Termination is ON at both TS0893 modules Maximum cabling distance for segment 2 is 1500 metres 3 Earth point on device 4 Each device s earth point must be connected via minimum 2 5mm GNYE earth cable not exceeding 1 Q to a Communications Earth Terminal CET 5 Minimum 6mm GNYE earth conductor not exceeding 0 5 0 See System earthing on page 19 for details 6 Plastic body LAN device See Figure 9 on page 21 for details of joining the data cable shield to extend the LAN past such a device 24 TS0866 Four Door Controller Installation Manual
6. A UTC Fire amp Security nited Technologies Company TS0866 Four Door Controller Installation Manual P N MAINST TS0866 REV 3 0 ISS 24SEP10 Copyright Trademarks and patents Manufacturer ACMA compliance Contact information 2010 UTC Fire amp Security All rights reserved The Challenger name and logo are trademarks of UTC Fire amp Security Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective producis UTC Fire amp Security Americas Corporation Inc 1275 Red Fox Rd Arden Hills MN 55112 6943 USA Authorized Australia and New Zealand manufacturing representative UTC Fire amp Security Australia Pty Ltd Unit 3 310 Ferntree Gully Road Notting Hill VIC 3168 Australia Cr Notice This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures For contact information see www utcfs com au Content Important information ii Limitation of liability ii Agency compliance ii Product overview 1 Mechanical and environmental specifications 1 Product contents 1 Related documentation 2 Before you begin 3 Installing the Intelligent Access Controller 5 Installation guidelines 5 Installation procedures 6 DIP switch settings 7 Connections 7 Connecting expansion modules 15 LED indications 15 Over current pro
7. AN TERM link on TS0866 Four Door Controller Installation Manual gt EARTH gt 2 I Y CET Figure 9 legend Item Description 1 Each device s earth point must be connected via minimum 2 5 mm GNYE earth cable not exceeding 1 Q to a Communications Earth Terminal CET If the device has a GND link it must remain fitted 2 The CET must be labelled CET and installed adjacent to the electrical switchboard 3 Minimum 6 mm GNYE earth cable not exceeding 0 5 Q to building earth or electrical switchboard 4 RS 485 LAN cable GE recommends the use of 2 pair twisted shielded data cable such as Belden 8723 for optimal performance 5 Join data cable shields where cable extends past a device that doesn t have a LAN earth connection 6 In each segment of LAN cabling connect one end only of the data cable shield to a device s LAN earth terminal 7 External 12 VDC power supply if needed 8 Do not connect the from the external 12 VDC power supply to the of the LAN 9 Terminate the control panel and the most distant device or the devices at the ends of the two longest LAN cable runs as applicable System configurations A Challenger panel s system LAN or an Intelligent Access Controller s local LAN may be configured in a variety of ways Straight LAN where the Challenger panel or controller is at one end of a LAN cable run e Star
8. LAN where multiple LAN cable runs are used in a branched configuration e Multi building where the LAN extends to more than one building Straight LAN In a straight configuration Figure 9 on page 21 the panel or controller is at one end of the LAN cable run and all other devices are connected to the LAN cable In a straight LAN configuration the TERM links would be on for the panel or controller and for the last device on the system or local LAN Star LAN In a star configuration the LAN has at least two branches Figure 10 on page 23 optionally connected via a TS0844 Power Distribution Board In a star LAN configuration the TERM links would be on for the two devices at the ends of the two longest cable runs 22 TS0866 Four Door Controller Installation Manual Figure 10 Star LAN configuration Challenger panel T On termination link fitted T Off termination link not fitted T Off Multi building or long distance LAN cabling If the RS 485 LAN extends to more than one building each building must have its own earth system LAN isolation devices such as TS0893 are used to isolate the system LAN between buildings to protect the system against differences in earth potential Figure 11 below shows the use of two TS0893 Isolated RS 485 to RS 485 Interface modules to extend the RS 485 LAN across two electrical installations Each TS0893 module has a pair of termination links used to
9. ally closed tamper contact tamper contact Normally closed Normally open alarm contact alarm contact When four state monitoring is used the panel uses the circuit s resistance to determine the state of the zone input e 10 KQ indicates sealed e 5kQ or 20KQ indicates unsealed e Open circuit indicates input tamper e Short circuit indicates input tamper To use four state monitoring for all zone inputs input tamper monitoring must be set to Yes Install menu option 7 System Options for the Challenger panel and tamper monitoring must be set to Yes controller menu option 1 Controller Options for the controller Alternatively the Challenger system can be configured to monitor zone inputs for two states sealed and unsealed This is accomplished by using one 10 kO resistor in each circuit as shown in Figure 8 on page 14 TS0866 Four Door Controller Installation Manual 13 Figure 8 Two state monitored zone input circuits Normally open tamper contact Normally closed tamper contact Normally closed Normally open alarm contact alarm contact The panel uses the circuit s resistance to determine the state of the zone input e 10 kO indicates sealed e Open circuit or short circuit indicates unsealed To use two state monitoring for all zone inputs input tamper monitoring must be set to No Install menu option 7 System Options for the Challenger panel and tamper monitoring must be set to No controller menu option 1 Con
10. d to add remove join repair connections within the electrical switchboard Install LAN isolation devices between multiple buildings and maintain independent earthing systems For example use TS0893 TS0894 or TS0896 Isolation Interface modules to provide electrical isolation and or to extend distance e Do not install multiple main earth electrodes stakes in the same building or electrical installation Earthing of one cabinet containing several devices All devices designed for the system have earth connections via metal studs to the metal housing Take care that these metal studs have a good connection to bare metal no paint Earthing of panels in a single building In a single building several cabinets or devices are earthed A licensed electrical contractor must check the integrity of the building main earth Earthing of panels in more than one building If the wiring extends to separate buildings use more than one common earth system Install LAN isolation devices such as TS0893 to isolate the system LAN between buildings to protect the system against differences in earth potential See Figure 11 on page 23 TS0866 Four Door Controller Installation Manual 19 RS 485 LAN cabling The cabling recommendations for the system LAN or local LAN are Use 2 pair twisted shielded data cable such as Belden 8723 e n each segment of LAN cabling connect one end only of the data cable shield to a device s LAN earth terminal Joi
11. emperature 0 to 50 C Relative humidity 0 to 95 noncondensing Product contents Inspect the package and contents for visible damage If any components are damaged or missing do not use the unit contact the supplier immediately If you need to return the unit you must ship it in the original box Table 1 below lists the items that are shipped with a TS0866 Four Door Controller without Wiegand interfaces Table 1 TS0866 shipping list Quantity Item 1 TS0866 board 1 Intelligent Access Controller Installation Manual Universal Enclosure with four spring standoffs fitted Universal Enclosure Installation Instructions Mains transformer 2A with mains power cord Tamper switch AA AHA Tamper switch metal bracket TS0866 Four Door Controller Installation Manual 1 Quantity Item 1 Ring terminal 1 M4 x 12 Allen head cap screw 6 M3 x 10 pan head screws 12 3 way plug on screw terminal connectors 12 2 way plug on screw terminal connectors 2 Red battery lead with QC terminal 2 Black battery lead with QC terminal 4 Link jumpers 1 1K 1 4 watt resistor 29 10K 1 4 watt resistors Related documentation The Four Door amp Four Lift Controller Programming Manual provides detailed information about configuring and programming Four Door and Four Lift Controller models TS0866 TS0867 and TS0869 The Challenger V8 amp V9 Installation and Quick Programming Manual provides detailed information about config
12. ly Door lock power to lock gt O000O Notes e Use a suppression diode such as 1N4004 in door lock circuits e Lock fault monitoring is not available on TS0866 Zone inputs Zone inputs are also known as alarm inputs A Challenger system can receive alarm signals from up to 256 zone inputs including the Challenger panel s 16 onboard inputs Each pair of zone input terminals may be connected to an alarm system device such as a detector or reed switch Additional zone inputs numbered in the range 17 to 256 are provided via Data Gathering Panels DGPs Wireless Data Gathering Panels WDGPs and Intelligent Access Controllers on the system LAN 12 TS0866 Four Door Controller Installation Manual By default the Challenger system can monitor zone inputs for four states sealed unsealed open circuit and short circuit This is accomplished by using two 10 kQ end of line EOL resistors in each zone input circuit as shown in Figure 7 below Install EOL resistors in zone input circuits at the end of the circuit If an alarm device is connected place the EOL resistors at the device s connections If a zone input is not used you don t need to connect an EOL resistor if you program the corresponding input number as type 10 spare Tip Use sleeves on the resistor leads to prevent accidental shorting Figure 7 Four state monitored zone input circuits Normally open Norm
13. n data cable shields where cable extends past a device that doesn t have a LAN earth connection The length of the LAN cable run must not exceed 1 5 km unless LAN isolation devices are used to extend the distance Power supply to LAN devices Devices on the controller s local LAN may be supplied from the controller s 12 VDC LAN output Use an external 12 V power supply such as TS0073 2 A Power Supply when the device is more than 100 m data cable length from the panel e electrical isolation is required more power is needed than can be provided by the LAN When powering a LAN device from an external 12 V power supply e Connect the external power supply s terminal to the device s terminal Do not connect the power supply to the LAN e Connect the external power supply s terminal to the device terminal e Connect the LAN cable black wire to the device terminal 20 TS0866 Four Door Controller Installation Manual Figure 9 RS 485 LAN and earth system block diagram Ce EARTH Challenger panel first device on LAN S8 E d a TERM link on d 0 Plastic bodied RAS TERM link off gt External power supply if needed 9 HH d q Plastic bodied RAS ai J I TERM link off Data gathering panel last device on L
14. nsert the bracket with tamper switch into the 1 cm slot on top right hand side of the enclosure 3 in Figure 1 on page 5 To mount the printed circuit board to the enclosure 1 2 Remove the board from its antistatic bag Use four M3 x 10 pan head screws to fix the board to the enclosure s standoffs Slide the board s terminal connectors together and mount them to the board TS0866 Four Door Controller Installation Manual To set the LAN address Configure the DGP address in the range 1 to 12 using the Address DIP switch Refer to DIP switch settings below DIP switch settings Intelligent Access Controllers must be addressed as a DGP in the range 1 to 12 Use the four segment Address DIP switch to set the address the four segment ABCD DIP switch is not used Set all switches to OFF to disable the controller Figure 2 Address DIP switch 1234 ADDRESS Table 2 DIP switch settings Address S1 1 S1 2 S1 3 S1 4 01 l O O O 02 O l O O 03 l l O O 04 O O l O 05 l O l O 06 O l l O 07 I I I O 08 O O O l 09 l O O 10 O l O l 11 O I 12 O O I I Legend ON O OFF Connections See on page 8 for the locations of connectors and other items See Cabling requirements on page 19 for recommendations for the application and wiring of Challenger equipment TS0866 Four Door Controller Installation Manual Figure 3 TS0866 board details NE gi
15. ontact your local supplier or visit us online at www utcfs com au Agency compliance This product conforms to the standards set by Standards Australia on behalf of the Australian Communications and Media Authority ACMA UTC Fire amp Security recommend enclosure covers remain fitted to maintain C Tick compliance Notice This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures ii TS0866 Four Door Controller Installation Manual Product overview This manual applies to TS0866 Four Door Controller without Wiegand interfaces The TS0866 is also known as Intelligent Access Controller controller or DGP Up to 12 Intelligent Access Controllers can be connected to a Challenger panel s RS 485 system LAN Intelligent Access Controllers also have a local LAN to connect readers for doors Intelligent Access Controllers provide enhanced access control functionality to the Challenger system This manual describes How to install the Intelligent Access Controller e How to connect other equipment to the Intelligent Access Controller e Programming required for basic system setup This manual is intended for use only by trained Challenger installation and configuration technicians Mechanical and environmental specifications Enclosure dimensions WxHxD 345 x 450 x 73 mm Storage temperature 20 to 80 C Operating environment T
16. polling on the local LAN e 1x1 rapid flashing if a RAS is connected to the local LAN e 1x1 off if no RAS is connected to the local LAN TS0866 Four Door Controller Installation Manual 15 Over current protection F1 3A fuse for battery 1 to limit current when unit is running on the battery F2 3A fuse for battery 2 to limit current when unit is running on the battery F3 1A fuse to limit auxiliary output current and siren F4 2A fuse to limit external output current local LAN J22 TS0866 Four Door Controller Installation Manual Powering up the controller Before applying power check the following The DGP address is correctly set Address DIP switch The memory configuration of the controller matches the Challenger panel same type of memory modules The DGP type is correctly programmed as a Door Controller in the Challenger Install menu option 4 DGP Database The controller is connected to the Challenger system LAN at J3 After power up check the Rx Tx Rx1 and Tx1 LEDs See LED indications on page 15 After initial power up before programming the controller use an LCD RAS on the Challenger system LAN to initialise the controller s database This ensures that the programming is in the default state To initialise the controller s database 1 3 4 Use the Install menu option 28 Remote Controllers to connect to the controller Select option 3 Initialise Database When selected the di
17. r use a link to set the LAN termination to ON A Challenger LAN should have only two devices with the LAN termination set to ON or the LAN termination resistor fitted e In a straight LAN configuration Figure 9 on page 21 the TERM links are ON at the Challenger panel and the most distant device e In a star LAN configuration Figure 10 on page 23 the TERM links are ON at the two devices that are the furthest apart and OFF at the Challenger panel In a completely connected but powered down system you can check for correct LAN termination by measuring the resistance across the D and D terminals e 0Q indicates a short circuit in the cabling e 160 Q or less indicates that three or more devices are terminated TS0866 Four Door Controller Installation Manual 11 e 220 Q is good two devices are terminated e 470 Q or more indicates that less than two devices are terminated Door lock relay wiring Figure 6 below details the wiring for terminal blocks J4 to J7 Figure 6 Door lock wiring options relay shown deenergised 8 G Door lock A Door lock power to lock A power to unlock 0 0 20 29 Lock powered by controller Lock powered by controller 250 mA maximum per lock 250 mA maximum per lock External External 12V power supply Door lock power to unlock A Lock powered externally Lock powered externally power supp
18. rth Terminal CET See System earthing on page 19 for details The Intelligent Access Controller has an internal transformer that is powered from 240 V mains cable supplied A power outlet GPO must be in proximity to the panel Only qualified Electricians should provide a GPO If the upper and or lower cabinet entry cable holes are used to route wiring into the control panel always use a proper pipe fitting system by means of an appropriate conduit and junction box For this purpose use only materials of suitable flammability class Avoid loops of wire inside the enclosure and route cables so that they do not lie on top or underneath the printed circuit board The use of cable ties is recommended and improves neatness of the wiring within the box The batteries used with this unit must be made of materials of suitable flammability class HB or better Only use units in a clean environment and not in humid air installation procedures To mount the enclosure 1 Fix the enclosure to the wall via the enclosure s four mounting holes 1 in Figure 1 on page 5 Make sure the enclosure is level and the rear tamper switch 3 location isn t sitting over a line of mortar if you re installing the enclosure on a brick wall To mount the tamper switch The two way tamper switch detects removal of the cover from the enclosure and removal of the enclosure from the wall Insert the tamper switch into its metal bracket I
19. splay shows what doors or lifts will be initialised Press or MENU to start the initialisation process Refer to the Four Door amp Four Lift Controller Programming Manual for details Note Menu option 3 Initialise Database defaults the Intelligent Access Controller database resetting all programming options to the factory defaults TS0866 Four Door Controller Installation Manual 17 18 TS0866 Four Door Controller Installation Manual Appendix A Reference Cabling requirements This section contains recommendations for installers and electricians for the application and wiring of Challenger equipment with respect to e System earthing e RS 485 data cable LAN cabling e Power supply from LAN or from external 12 V supply System earthing The following recommendations are based upon Australian wiring regulations ACMA AS ACIF S009 Section 5 and AS NZS 3000 2000 Section 5 Each device s GND link must remain fitted if applicable e Challenger system equipment with earth terminals must be earthed via minimum 2 5 mm GNYE earth cable not exceeding 1 Q toa Communications Earth Terminal CET Daisy chain connections are not permitted e The CET must be labelled Communications Earth Terminal and installed adjacent to the electrical switchboard e Each CET must be connected via minimum 6 mm GNYE earth cable not exceeding 0 5 Q to the electrical switchboard Only licensed electrical workers are permitte
20. ta cable 17 J4 to J7 relay connections for four doors Refer to Door lock relay wiring on page 12 A suppression diode such as 1N4004 must be fitted across door locks 18 Socket for TS0882 TS0883 or TS0884 memory expansion modules 19 Address selection DIP switch Configure the DGP address in the range 1 to 12 using the four segment DIP switch Refer to DIP switch settings on page 7 20 TERM link for the system LAN See Terminating the RS 485 LAN on page 11 21 TERM link for the local LAN See Terminating the RS 485 LAN on page 11 22 Lock supply voltage links one set for each relay Link to C to supply 12 V to the relay s C common contact Link to C to ground the relay s C common contact 23 D1 to D4 LEDs indicate that the associated lock relay is active 24 Rx and Tx LEDs to indicate system LAN activity See LED indications on page 15 25 Rx1 and Tx1 LEDs to indicate local LAN activity See LED indications on page 15 26 F1 F2 F3 F4 over current protection See Over current protection on page 16 Figure 4 on page 10 details the wiring for terminal blocks J1 to J3 TS0866 Four Door Controller Installation Manual Figure 4 Connection details for terminal blocks J1 to J3 18 V AC power from mains transformer RS 485 data cable shield 12 V battery 12 V battery iiva Liva OV Auxiliary power
21. tection 16 Powering up the controller 17 Appendix A Reference 19 Cabling requirements 19 System configurations 22 TS0866 Four Door Controller Installation Manual Important information Limitation of liability The customer is responsible for testing and determining the suitability of this product for specific applications In no event is UTC Fire amp Security responsible or liable for any damages incurred by the buyer or any third party arising from its use or their inability to use the product Disclaimer The information in this document is subject to change without notice UTC Fire amp Security Americas Corporation Inc UTC Fire amp Security assumes no responsibility for inaccuracies or omissions and specifically disclaims any liabilities losses or risks personal or otherwise incurred as a consequence directly or indirectly of the use or application of any of the contents of this document For the latest documentation contact your local supplier or visit us online at www utcfs com au This publication may contain examples of screen captures and reports used in daily operations Examples may include fictitious names of individuals and companies Any similarity to names and addresses of actual businesses or persons is entirely coincidental Intended use Use this product only for the purpose it was designed for refer to the data sheet and user documentation for details For the latest product information c
22. troller Options for the controller Note Two state monitoring is not compatible with input types 33 or 40 See the Challenger V8 amp V9 Programming Manual for details Default zone inputs and relays Door contacts and egress buttons associated with each door are wired to the Four Door Controller s zone inputs Spare zone inputs are provided for alarm devices such as PIRs DOTL inputs must not have any wiring connected to them Table 3 Four Door Controller zone input and relay defaults First door Second door Third door Fourth door Door contact 1 4 7 10 Spare input 2 5 8 11 Egress input 3 6 9 12 DOTL input 16 15 14 13 Door relay First Second Third Fourth Physical connection of zone input numbers 9 to 16 require the use of a TS0021 8 Input Expansion Module see Input expansion on page 15 Refer to the Four Door amp Four Lift Controller Programming Manual for the system zone input numbers relating to these functions 14 TS0866 Four Door Controller Installation Manual Connecting expansion modules Relay and output expansion The Intelligent Access Controller has four onboard relays that are assigned the first four relay numbers for the DGP address For DGP 1 these would be relays 17 18 19 and 20 If relay expansion cards are used additional relays are numbered according to their physical address starting at 5 A DGP macro logic program would be used to map the Challenger system s DGP relay n
23. ttery 7 0 Ah maximum not supplied 7 Connect the and auxiliary power output terminals to devices that require 12 Volt DC power such as detectors See Auxiliary power terminals on page 10 8 Connect the S and S terminals to an 8 Q siren speaker Alternatively connect a 1k Q resistor across S and S terminals if a siren is not connected If a siren is used consider the current draw as part of the auxiliary power output See Auxiliary power terminals on page 10 9 Connect the OV D and D terminals to the system RS 485 LAN 8 TS0866 Four Door Controller Installation Manual Item Description 10 Connect the T and C terminals to the panel tamper switch supplied Short circuit for sealed open circuit for unsealed Must be sealed if not used Can only be used with normally closed contacts such as the panel tamper switches 11 Zone input terminals See Zone inputs on page 12 12 Connector for optional TS0021 8 input expansion module to increase the number of inputs from 8 to 16 13 10 way cable socket for TS0840 TS0841 or TS0842 relay or output expansion modules 14 Connect the earth terminal or lug near J14 to the local LAN s RS 485 data cable shield 15 12 V link This link enables the panel to power a relay card connected to J14 CLKOUT Remove this link if the relay card is powered from an external 12 V supply 16 Connect the 12 OV D and D terminals to the local LAN s RS 485 da
24. umber e g 21 to the Intelligent Access Controller s physical relay number e g 5 There are 48 DGP macro logic programs available One TS0840 Four Way Relay Expansion Board may be connected to J21 to add four relays Alternatively TS0841 Eight Way Clocked Relay Expansion Boards or TS0842 16 Way Clocked Open Collector Expansion Boards may be connected to J21 individually or daisy chained to add eight relays per card for TS0841 or 16 open collector outputs per card for TS0842 Note If TS0841 and or TS0842 boards are used then a Relay Controllers value must be programmed in Controller Options where 1 represents each eight relays or open collector outputs Refer to the Four Door amp Four Lift Controller Programming Manual for details Input expansion TS0866 Four Door Controllers have eight zone input circuits One TS0021 Eight Input Expansion Module may be connected at J11 to expand the capacity to 16 zone inputs LED indications LEDs on the PCB indicate the state of the system LAN the local LAN and relay activity e Rx flashing indicates polling data being received from the Challenger panel on the system LAN e Tx flashing indicates the controller is replying to polling from the Challenger panel on the system LAN Tx off indicates that the controller is not correctly addressed and or that the Challenger panel is not programmed to poll the DGP address e Rx1 flashing indicates remote units such as readers replying to
25. uring a Challenger system Details provided about a Challenger panel s system LAN apply also to an Intelligent Access Controller s local LAN The Challenger V8 amp V9 Programming Manual provides detailed information about Challenger system configuration and programming The Challenger system is modular Refer also to the documentation that is shipped with each module that you intend to use 2 TS0866 Four Door Controller Installation Manual Before you begin When installing an Intelligent Access Controller or any other parts of the system you need to be aware of requirements for cabling and earthing and plan accordingly Refer to Cabling requirements on page 19 Notice A qualified service person complying with all applicable codes should perform all required hardware installation Disclaimer This manual contains recommendations based on Australia and New Zealand codes It is not an authoritative reference regarding codes and has not been reviewed by the responsible authorities The codes may change and may not be reflected in this document TS0866 Four Door Controller Installation Manual 3 TS0866 Four Door Controller Installation Manual Installing the Intelligent Access Controller See Figure 1 below for overall details of a TS0866 Four Door Controller installed in a TS0307 Universal Enclosure supplied Figure 1 TS0866 board mounted in enclosure