User Manual-EN-SG30KTL_SG30KTL-M-Ver12
Contents
1. PENR S T S noooooonnono a G 8 gt Front View of Connection Cabinet L L 11 WO P PSP 2 CP9 P i00 O r g o e de 9500 10 1 q p Bottom View of Connection C Cabinet 4 Fig 6 2 Connection Cabinet Description No Description No Description 1 DC switch 7 Second PE terminal 2 Pinth DIDE SPDS SUTE Protection 8 DC connection circuit board Devices 3 Configuration circuit board 9 PV input terminals 4 Cooling Fan 10 Communication cable glands 5 AC connection circuit board 11 AC cable gland 6 AC connection terminal block and PE terminal SUNGROW 29 6 Electrical Connection User Manual 6 3 Connecting Inverter to AC Grid 6 3 1 AC Side Requirements D Only after receiving prior approval from the local grid company as required should you connect the inverter to the grid Prior to connecting to the utility grid verify whether the grid voltage and frequency are within the range of inverter output parameters referred to Appendix Otherwise consult local
2. Item Description 1 SUNGROW logo and product type 2 Technical data of inverter 3 Marks of certification institutions of inverter 4 Company name website and origin Tab 4 1 Description of Icons on the Nameplate Icon Description P A Don t dispose of the inverter with the household waste Refer to the corresponding instructions TUV mark of conformity The inverter is in compliance with directives of TUV CE mark of conformity The inverter is in compliance with directives of CE SUNGROW 17 4 Unpacking and Storage User Manual 4 3 Delivery Contents a Fig 4 3 Delivery Contents Item Name Description A Inverter unit B Backplate It is used for mounting inverter onto the wall C Inverter cap It is for inverter s better weather proof function Documents include quality certificate packing list product D Documents test report quick installation guide and inverter user manual E Expansion Six units It is used for fastening backplate onto concrete bolts wall F Fastener set Six units It is used for fastening backplate onto metal frame G Fix screws 2 M4x 16 screws for fix the inverter to the backplate 4 DC Ten pairs PV input cables must be equipped with the connectors connector 18 SUNGROW User Manual 4 Unpacking and Storage 4 4 Storage of Inverter Where the inverter may not be installed immediately or inverter needs to be stored
3. Fault Description Troubleshootin Code p g The PV configuration 1 Disconnect inverter mode set on the display 2 Re select PV configuration mode and 0047 is not in accordance with re connect PV strings For more detailed the configuration in the information please refer to 6 4 Connecting connection cabinet Inverter to PV Arrays 0048 Phase R current sampling channel fault Bice Gen eamiclia 1 Wait a moment for inverter recovery 0049 ping 2 If the fault occurs repeatedly contact channel fault Sungrow Service Dept Phase T current sampling 0050 channel fault 1 Wait a moment for inverter recovery Hardware Overvoltage 0051 i 2 If the fault occurs repeatedly contact Overcurrent protection Sungrow Service Dept 0070 aT detective ao inverter and remove the broken 0072 Fault with DC SPD It is necessary to replace the DC SPD Contact Sungrow Service Dept 0073 pice kas klownout Disconnect inverter and replace the fuses Contact Sungrow Service Dept A fault has occurred in the internal 0074 Communication fault of communication of the inverter However the LCD inverter continues feeding into the grid Contact Sungrow Service Dept CE Wait for higher irradiation Solar irradiation is not E ae a If this recurs at medium irradiation check the 0075 sufficient for inverter i PV system design and correct the connection operation of PV inputs 0076 PV1 overload Check the PV system design and co
4. Main Screen Press ENTER Menu Press Y His record Press ENTER Press Vv Fit record Press ENTER Inverter shows fault record pages Scroll pages by pressing Vv i SUNGROW Flt record P 1 2 1 gt 12 01 31 10 16 10 0008 2 gt 12 01 31 10 16 10 0008 3 gt 12 01 31 10 16 10 0008 4 gt 12 01 31 10 16 10 0008 5 gt 12 01 31 10 16 10 0040 The inverter can only store at most 10 latest fault records 71 10 Operation of LCD Display User Manual 10 7 Start and Stop Inverter Main Screen Press ENTER Menu Press Y x2 Start Stop Press ENTER Press V to choose Start Stop Start Stop ley and press ENTER to confirm the gt Start Start choice Stop gt Stop Press ENTER to confirm Confirm start the Confirm stop the inverter inverter 10 8 Input Parameter Settings Password The parameter settings are protected by the password If you want to set the inverter s parameters you have to input the correct password 1 Press ENTER to enter into Menu screen De Press v to move the cursor to Set param menu item and confirm by pressing ENTER 3 A password confirmation screen will occur Press Set Param gt to move cursor right and Press v to input the password 111111 Password 000000 4 Press ENTER to confirm the password and enter _ Set param the Set param sub menu gt
5. IP65 Fans IP55 Night power consumption lt 1W Operating ambient temperature range 25 60 C gt 45 C derating Allowable relative humidity range 0 95 no condensing Cooling method Smart forced air cooling Max operating altitude 4000m gt 2000m derating Display Graphic LCD Communication RS485 RJ45 connector Certification VDE0126 1 1 EN62109 1 EN62109 2 G59 2 CEI 021 AS NZS 3100 AS4777 2 AS4777 3 VDE AR N 4105 BDEW CGC SOLAR Mechanical Data Dimensions WxHxD 634x820 257mm Mounting method Wall bracket Weight 65kg 11 2 Terminals and Cables i Recommended Terminal Type Conductor size conductor size PGA29L 27 AC terminal Phoenix Spring 8AWG 5AWG 7AWG terminal block 8 16mm 10 mm PLH 16 5 15 MC4 DC terminals PV KST4 6II UR Fe ill 11AWG 4 6mm 4mm PV KBT4 6ll UR RS485Comm Pre Twist pair type cable terminals lee Twist pair type shielding Ethernet cable Second PE i 10AWG 8AWG 9AWG terminal 6mm 6mm 90 SUNGROW 11 3 Exclusion of Liability The content of these documents is periodically checked and revised please contact us or check our website www sungrowpower com for the latest information Discrepancies cannot be excluded No guarantee is made for the completeness of these documents Please contact our company or distributors to get the latest version Guarant
6. Sys param Run param Pro param Com param 72 SUNGROW User Manual 10 Operation of LCD Display 10 9 System Parameters Setting 10 9 1 Language Setting The inverter supports five languages English German French Italian and Chinese Language can be configured as the following indication Main Screen Press ENTER Menu screen Press x3 Set param Press ENTER Enter password Press ENTER Sys param Press ENTER gt Language Press ENTER Press Y to select language as you prefer and confirm it Languages by pressing ENTER English O Deutsch O Francaise O Italia O WX 10 9 2 Time Setting If there is deviation between the time on inverter main screen and your local time you should perform the operation time setting Otherwise the inverter data logging will fail Clock is 24 hour format Main Screen Press ENTER Menu screen Press Y x3 Set param Press ENTER Enter password Press ENTER Sys param Press ENTER Press v Time Press ENTER On the Time screen Press gt to move the cursor Time right and Press Y to set the correct date and time Format YY MM DD Confirm settings by pressing ENTER Date 12 01 31 Time 10 30 55 10 9 3 Energy Deviation Adjustment If the accumulative value of E total in the inverter is different from the value in the external metering device you should adjust the Energy adj setting Main Screen Press ENTER Menu scree
7. 00 00s 00 00Hz 00 00s gt I Min F rete I Min F tempo II Min F rete II Min F tempo 00 00Hz 00 00s 00 00Hz 00 00s 87 10 Operation of LCD Display User Manual Tab 10 11 IT Stage II Protective Parameters Explanation Parameter Explanation Max V prote Over voltage protection I Max V rete Stage I Grid over voltage I Max V tempo Stage I Grid over voltage tripping time I Max V rete Stage II Grid over voltage I Max V tempo Stage II Grid over voltage tripping time Min V prote Under voltage protection I Min V rete Stage I Grid under voltage I Min V tempo Stage I Grid under voltage tripping time I Min V rete Stage I Grid under voltage I Min V tempo Stage II Grid under voltage tripping time Max F prote Over frequency protection I Max F rete Stage I Grid over frequency I Max F tempo Stage I Grid over frequency tripping time I Max F rete Stage II Grid over frequency I Max F tempo Stage II Grid over frequency tripping time Min F prote Under frequency protection I Min F rete Stage I Grid under frequency I Min F tempo Stage I Grid under frequency tripping time I Min F rete Stage I Grid under frequency IT Min F tempo Stage II Grid under frequency tripping time 88 SUNGROW 11 Appendix 11 1 Technical Data Parameter
8. to decrease one step value settings Q S A Italy Q P Mode The power factor changes with the output power of the Run param Q P P3 3 inverter gt PA 020 0 Select Q P mode and Press w to enter into the n Run para Q P sub menu anes j pii Press Y to navigate the cursor Press gt to enter into the Uin 108 6 editing mode then the selected parameter will be shaded iut 100 0 Press Vv to increase one step value Press gt to decrease one step value Press ENTER to confirm the setting and exit from the editing mode Tab 10 7 Italy Q P Mode Parameters Explanation Parameter Explanation Default Range Step PA Active power at point A in 20 20 100 1 PR Active power at point B in 50 20 100 1 PC Active power at point C in 100 20 100 1 Pf max Power factor at point C 0 9 0 9 1 0 01 Enter into the Q P regulation Uin mode when the grid voltage is 105 100 110 1 above Uin Exit from the Q P regulation Uout mode when the grid voltage is 100 90 100 1 below Uout PA lt PB lt PC Uin gt Uout 84 SUNGROW User Manual 10 Operation of LCD Display cos Default Curve I Deviation P Pn ZZ No adjustment cose 0 98 0 9 0 95 e That depends on the capacity of the inverter Fig 10 6 Reactive Power Regulation Curve in IT Q P Mode Italy Q U M
9. under certain condition store the unit as the following indications The unit must be packed into original carton and desiccant must be put inside If the original packaging is not available an equivalent carton which is able to support the unit weight and size can be used The packing should be sealed by adhesive tape The unit must be stored in a clean and dry place to protect against dust and moisture The storage temperature should be always between 25 C and 60 C And the storage relative humidity should be always 0 and 95 The recommended number of stack layers is not more than 4 It is very important to keep the packing away from chemicals Otherwise it will lead to corrosion During the storage time periodically check any visible damage by rats and other rodents Replace the packaging if necessary The packaging should be kept upright After long term storage local installer or service dept of Sungrow should perform a comprehensive test before connecting the inverter into PV power system SUNGROW 19 5 Installing Inverter onto Wall 5 1 Selecting Installation Location Selecting an optimal installation location for the inverter is decisive for its operating safety as well as its expected efficiency and service life Take the load capacity of the wall into account The wall such as concrete wall and metal structure should be strong enough to hold the weight of the inverter over a long period of time
10. 10 Stage I Protective Parameter Explanation Parameter Explanation Parameter Explanation Max V grid Grid over voltage value Max Fgrid Grid over frequency value Gri nder fr n Min V grid Grid under voltage value Min F grid pi uneg a IT Stage ll o Protective Parameter may differ from that in other menus Proceed as follows to perform the parameter settings Switching Mode Editing Mode The button functions for Italy Stage IL parameter setting sub menus Shortly press to navigate gt Shortly press gt Long press to turn page Long press or Select Pro stage II and Press v to enter into the sub menus Press Vv to navigate the cursor Press gt to enter into the editing mode then the selected parameter will be shaded Press wv to increase one step value Press gt to decrease one step value Press ENTER to confirm the setting and exit from the editing mode SUNGROW Shortly press to add one step value Shortly press to decrease one step value Max V prote Min V prote gt I Max V rete I Max V tempo II Max V rete II Max V tempo 000 0V 00 00s 000 0V 00 00s gt I Min V rete I Min V tempo II Min V rete II Min V tempo 000 0V 00 00s 000 0V 00 00s F prote Min F prote v I Max F rete I Max F tempo II Max F rete II Max F tempo 00 00Hz
11. FERA AORE EEEE DU 7 1 Inspection before COMMISSIONING ssse ssssesssssesssseesssseessseeeosseesssseesssseessssees 50 7 2 Commissioning Procedure se esesesssseesseesseessseesseesssessseeosseesseessseosssrossersseesss 51 Disconnecting Dismantling and Disposing the Inverter 54 8 1 DISCONNECTING the lnverte sussen EA 54 8 2 Dismantling the Inverter ss seseesesessseessseesseesssesssseesseesseessseeosseesseesseessseroseesss 55 8 3 Disposing the Inverter s ssseesesessseessseesseesssesssseesseesseessseeosseesseeoesosserossersseesss 55 Troubleshooting and Maintenance s esssscecssscccssscessseessse DO gT mroupeshogtiNg sesa a EN 56 9 1 1 Troubleshooting Of LED Indicator ssssseeesssseesesssseesssssseessssseeesnsssesosssseessssss 56 9 1 2 Troubleshooting of Faults in LCD Screen ssssesssssseesssssseesssseeesssssesesssseessssss 56 92 Maintenance oerna a EE S 61 9 2 1 Ro tine Maintenant E assess cscdecdccscsssccvsstsedscsscseseaunseusseaveustvedsestnssanssatsedsesteneseanieas 61 9 2 2 Maintenance INSU ctio Ma 62 9 3 Contact SUNgrOW SerViC Enna 65 Operation of LCD Display ssssssseccocsssssssceceosssssseccesossssssseess OO 10 1 Description of Button Function seseessessseesseessseessscesseesseessseressersseesneeesseeesss 66 10 2 Inverter Menu StruCtUure sseseesesseseeseesessesseesessosseseeseesossossessessesseseeseesessessese 67 TOS Malt SEEN aena A A L E ea tation 68 TOA Adj
12. Grid over voltage value Min V grid Grid under voltage value Max Fgrid Grid over frequency value Min F grid Grid under frequency value 80 SUNGROW User Manual 10 Operation of LCD Display Multi stage Protective Parameter when the country selection is not IT If the selected protective Max V prot Min v prot parameter type is Multi stage gt I Max V grid 000 0V gt I Min V grid 000 0V the following sub menus will I Max V time 00 00s pl I Min V time 00 00s come up II Max V grid 000 0V II Min V grid 000 0V Press V to select parameter TI Max V time 00 00s II Min V time 00 00s Press gt to move cursor right and Press v to set the maxF prot Min F prot appropriate value Confirm i SE sane settings by Pressing ENTER ar ore iin i I Max F time 00 00s 4 I Min F time 00 00s II Max F grid 00 00Hz qT Man Fegrid bl II Max F time 00 00s teers 09 093 Tab 10 6 Multi stage Protective Parameter Explanation Parameter Explanation Max V prot Over voltage protection I Max V grid Stage I Grid over voltage I Max V time Stage I Grid over voltage tripping time IT Max V grid Stage II Grid over voltage I Max V time Stage II Grid over voltage tripping time Min V prot Under voltage protection I Min V grid Stage I Grid under voltage I Min V time Stage I Grid under voltage tripping time IT Min V grid Sta
13. Inverter 8 1 Disconnecting the Inverter For maintenance work or any service work inverter must be switched off In normal operation switching off is not necessary In order to disconnect the inverter from the AC and DC power sources you should proceed with the following procedures Otherwise you will be exposed to lethal voltages or the inverter will be damaged 1 2 Disconnect the external AC circuit breaker and prevent it from connecting again Turn off the upstream DC circuit break or cover the PV arrays with opaque materials Rotate DC switch at the side of inverter to the OFF position NOTICE Please strictly follow the sequence of the above procedures Otherwise it will lead to unrecoverable inverter damage 3 54 Wait about ten minutes until the capacitors inside the inverter have discharged Loose the six screws on the lower connection cabinet and then remove the lid Measure AC voltage to ground at the AC terminal to confirm AC output of inverter at the AC circuit breaker is voltage free Loose screws to remove AC cables Disconnect DC cables from the inverters SUNGROW User Manual 8 Disconnecting Dismantling and Disposing the Inverter 8 2 Dismantling the Inverter Refer to Chapter 5 and Chapter 6 to dismantle the inverter in reverse steps NOTICE If the inverter will be reinstalled in the future please refer to 4 4 Storage of Inverter for a proper conse
14. Limit for Current Limit for p Each Input Each Input 32000W 16000W 1000V 33A Considering the negative voltage temperature coefficient of PV module more attention should be paid to the open circuit voltage of PV strings when designing at the lowest ambient temperature Take an example for explanation The parameters of PV module STP230S 24 Vb are listed below Item Value PV module type STP230S 24 Vb Power 230W Open circuit voltage STC 42 4V Short circuit current STC 7 60A Open circuit voltage temperature coefficient p 0 3656 C Number of PV module in a PV string 21 Under the STC condition where ambient temperature is 25 C the open circuit voltage of PV string 42 4V x 21 890 4V lt 1000V Supposed that the lowest temperature is 25 C the open circuit voltage of PV string 21 x42 4Vx 1 B x min ambient temperature STC temperature 21x 42 4V x 1 0 3656 C x 25 C 25 C 1053V gt 1000V Therefore PV string should be designed again to meet the open circuit voltage requirement even under the lowest ambient temperature PV Configuration Mode Parallel Mode For parallel mode the PV inputs can be configured in parallel inside the connection cabinet All PV strings connected to the SG30KTL M have a homogenous structure including the same type the same number identical tilt and identical orientation As shown in the following diagram the SG30KTL M may choose parallel mode due to no differ
15. MPP tracker The two PV inputs can be configured in independent mode or parallel mode NOTICE There is a risk of inverter damage The following requirements should be met otherwise they will lead to loss of any and all warranty rights e Make sure that the maximum short circuit current of each DC input is less than inverter allowable limit e Make sure that the maximum open voltage of each string is less than 1000V Voltage over 1000V can damage the inverter PV Configuration Mode Independent Mode For independent mode the two PV inputs work independently each with its own MPPT Therefore the two PV inputs can be different with each other including different PV module types different numbers of connected in PV string different tilt angles or orientation angle of PV modules As shown in the following diagram SG30KTL M should choose independent mode due to different orientation angle between the two PV inputs H ae CH a SHE To make sure maximum DC power can be utilized PV strings connected to individual input area should have a homogenous structure including the same type the same number identical tilt and identical orientation t Inverter Inside lddW 36 SUNGROW User Manual 6 Electrical Connection Prior to connecting the SG30KTL M to PV inputs the following electrical specifications must be met simultaneously THe De Garr we Dace Ua Sees SAT Limit for cach Inoue Voltage
16. adjust it until it is in a horizontal position Step 3 Mark the positions to drill holes using the backplate as the template Step 4 Drill holes according to the marks made before In order to avoid electrical shock or other injury inspect existing electronic or plumbing installations before drilling holes Mark positions Drill holes Step 5 Attach the backplate to the wall firmly with the supplied expansion bolt set The torque for fastening the nut is 35 Nm 24 SUNGROW User Manual 5 Installing Inverter onto Wall Install backplate Step 6 Assemble the cap onto the inverter for better weatherproof function Step 7 Lift up inverter above the backplate and then slide down to make sure that the recesses on the back of the inverter fit perfectly together with the backplate Step 8 After fit the inverter to the backplate fasten the inverter to the backplate with two M4x16 screws Assemble cap _ Hang inverter SUNGROW 25 5 Installing Inverter onto Wall User Manual 5 3 3 Installing on Metal Frame Step 1 Remove backplate and fasteners from the packaging Step 2 Choose the best installation site according to above requirements Place the backplate onto the chosen metal frame and adjust it until it is in a horizontal position Step 3 Mark the positions to drill holes by using the backplate as the template Step 4 Drill 6 holes at the marks you have made If the shape of th
17. checked that range of inverter protective parameters ask 0013 yn a the grid is abnormal utility grid company for solution 3 If the grid frequency is within the permissible range contact Sungrow Service Dept The aca gng vortage 1 Wait a moment for inverter recovery over 10 minutes is not 0014 oe are 2 If the fault occurs repeatedly contact within the permissible Sungrow Service Dept range 1 Check AC cables for appropriate size 0015 Grid impedance has 2 Wait amoment for inverter recovery exceeded inverter s limit 3 If the fault occurs repeatedly contact Sungrow Service Dept 1 Wait a moment for inverter recovery 0016 The AC output overloads 2 If the fault occurs repeatedly contact Sungrow Service Dept The inverter has checked 1 Wait a moment for inverter recovery that there is unbalance 0017 2 If the fault occurs repeatedly contact between the three phase Sungrow Service Dept voltages The bus voltae E 1 Wait a moment for inverter recovery 0019 iemodiaii hah g 2 If the fault occurs repeatedly contact p Pa Sungrow Service Dept 1 Wait a moment for inverter recovery 0020 The bus voltage is high 2 If the fault occurs repeatedly contact Sungrow Service Dept Inverter has checked that 0021 there is overcurrent of Check the layout and the wiring of PV1 input PV1 input Inverter has checked that 0022 there is overcurrent of Check the layout and the wiring of PV2 input PV2 input PY eongureton m
18. connect cables to RJ45 plug according to TIA EIA 568B ce RJ45 plug d RJ45 Port Corresponding Relationship Between Cables and Pins Pin 1 White orange Pin 2 Orange Pin 3 White green Pin 4 Blue Pin 5 White blue Pin 6 Green Pin 7 White brown Pin 8 Brown HEE i 8 I I I 7 I I I I il 23456 12345678 Pin 3 and Pin 6 are used for communication Pin 3 to R8485 B Pin 6 to RS485 A RS485 A Step 3 Connect the RJ45 plug into the RS485 in RS485 out terminal on the configuration circuit board Step 4 According to the position of the inverter refer to the prior section repeat step1 3 to connect the other RS 485 Ethernet cables to the RS485 out RS485 in terminal on the configuration circuit board Step 5 Pull cables outwards to confirm whether they are fastened firmly Step 6 Tighten the tread lock sealing lock Block off the vacant terminals to protect the inverter s internal from dust and moisture Step 7 According to the position of the inverter refer to the prior section switch ON or OFF the terminating resistor Step 8 If there is no other connection procedure recover and fix the front cover of the connection cabinet Step 9 As for the wires which connect to the logging devices use the Ethernet wire stripper to strip the insulation layer and connect the RS485 A and B cables 3 and 6 to data logging device or RS 485 232 converter Com
19. diameter ranges from 22mm to 27mm Length of insulation to be stripped off 18mm Insulation layer z A 3 D Crosssectonrof AC cables Recommendation value 10mm 7 AWG Max value 16mm The maximum accepted cable external diameter ranges from 22 to 27 mm whereas each individual terminal of the terminal board accepts a cable with cross section of up to 16 mm SUNGROW 33 6 Electrical Connection User Manual Step 4 Insert AC cables through cable gland from outside Step 5 Pull the cables through and fix L1 L2 L3 N PE cables ends to the corresponding terminals according to markings b NOTICE e Observe the pin assignment of AC terminal block If a phase wire is connected to the PE terminal it may permanently destroy the inverter e Please avoid squeezing the cable insulation layer into the AC terminal Improper connection may damage the inverter Step 6 Screw cap nut tightly onto the cable 34 SUNGROW User Manual 6 Electrical Connection 6 4 Connecting Inverter to PV Arrays 7 DANGER Lethal voltage exists PV arrays produce electrical energy when exposed to light and thus can create an electrical shock hazard Cover the PV arrays with opaque materials and then perform the wiring Wiring should only be performed by qualified personnel NOTICE Make sure that the maximum input ground capacity of
20. lt sezo aut Aqpueys lt Z Id weued uny do3s 4e1S UOTSJ9A JEMWJT A nejap peo 1LNeJap peol p4sod04 314 YaLNa pe A6saug ge u o oo UWTL U3LNI puodeu uny lt s en ue lt lt weued sAs p40394 STH wesed 3aS do3S 34e3S piodeu STH OjuT uny nuay JLN os4 u 19S UIEN OE OT TE T0 ZIOZ HD 0 ri 8 OT m 000 EZ we ld aN Fig 10 1 Menu Tree English 67 SUNGROW 10 Operation of LCD Display User Manual 10 3 Main Screen If the inverter succeeds in commissioning LCD display will enter into the main screen as shown in Fig 10 2 E Se du 90 1 2012 01 31 10 30 17 Fig 10 2 Main Screen Description No Description Power curve x axis time in hours y axis output power yield P in Icons refer to the Tab 10 3 and the Inverter active power limits P W limits Current output power Energy generation during this day until now Total energy generation since initial commissioning Inverter state NYO BR WlN Date year month date and time Tab 10 2 Inverter State Description Inverter State Description After being energized the inverter tracks the PV arrays maximum Run power point MPP and feeds AC power to grid This mode is the normal mode Standby Inverter will enter into Standby mode for insufficient input powe
21. power is always three phase via the AC terminal AC Cable Requirements Consider the following facts when select AC cables specifications and types The grid impedance of the AC cable must correspond to the specification to avoid unintended disconnection from the grid or derating of the output power Voltage drop and other consideration may use the larger size cables Avoid power loss in cables of more than 1 of nominal inverter rating e Withstand ambient temperature Layout type inside wall underground free air etc e UV resistance and so on 32 SUNGROW User Manual 6 Electrical Connection Connecting Inverter to AC Grid Danger to human life due to high voltage existing inside the inverter Make sure that all the DC and AC cables to the inverter are not live before you start the electrical work Do not turn on the AC side circuit breaker until all inverter electrical connections have completed Connect the inverter exclusively to TN or TT mains as the following procedures Step 1 Disconnect AC circuit breaker and prevent Aia it from reconnection inadvertently Step 2 Loose the six screws on the lower connection cabinet Step 3 Strip off AC cables as the following indication For flexible cables stranded wires use cold pressing terminal lugs plastic sleeves C D PE L1 L2 L3 N m B No Description Remark A Protective layer Accepted cable external
22. 0 i a P 5 Q Var limits Inverter reactive power limits 0 0 0 100 Over frequency power derating slope oe vue 83 33 40 100 Slope Only available when the Countries is selected to IT SUNGROW 75 10 Operation of LCD Display User Manual 10 10 2 Reactive Power Regulation The inverter provides reactive power regulation function Use the Q Var switch parameter to activate this function and select proper regulation mode Mode Explanation Pf The reactive power can be regulated by the parameter PF Power Factor Qt The reactive power can be regulated by the parameter Q Var limits in Off The PF is limited to 1 000 and the Q Var limits is limited to 0 0 Q P The PF changes with the output power of the inverter Q U The reactive power changes with the grid voltage Pf Mode The reactive power can be regulated by the parameter PF on the Run param screen Qt Mode The reactive power can be regulated by the parameter Q Var limits in on the Run param screen Off Mode The PF is limited to 1 000 and the Q Var limit is limited to 0 0 Q P Mode when the country selection is not IT The PF changes with the inverter output power Run param Q P If the country selection is not IT Italy after selecting Q P gt Upper PF Cap 1 000 Mode Press Y to enter the Run param Q P sub menu Lower Power 050 0 For each item s
23. 2 Inverter n AUDITY EE Ln PV Arrays 1 He l ere eLde SUNGROW suNGROW suncrow bey E i a hasa PV Arrays 2 KY Mounting Frame of PV arrays i i Copper Busbar O ogooodo0oo0o0000 000000000000 Grounding Electrode Grounding of PV Power System A LIL2L3N AC Circuit Breaker Inventors moop ee ee aur ae 25K E AC Grounding Electrode Grounding of Inverter AC Side Fig 6 3 Grounding for Inverter 42 SUNGROW User Manual 6 Electrical Connection 6 5 2 Second Protective Earth Terminal The inverter is equipped with second protective earth terminal as specified in EN 50178 Second PE Terminals There is a second PE terminal on one side of the inverter Users may choose to connect PE connection Fig 6 4 Second PE Terminals Second PE Connection Item Description Remark A Screw M4x 12mm B Lock washer C Washer D Cable socket E Yellow green cable 6mm 9AWG Fig 6 5 Connection of the Second PE Connection The connection parts are not included in the delivery scope SUNGROW 43 6 Electrical Connection User Manual 6 6 Communication Connection 6 6 1 Communication Overview The inverter operation information can be transferred via its integrated RS485 in
24. CO2 emission reduction C02 reduce 00000kg due to the inverter E month 0000KWh E month is the energy generation in this month h Total 0000h h Total is the total running hours of the inverter T today 0000min T today is today running time of the inverter Temp 000 0 C Temp is the internal temperature of the inverter 70 SUNGROW User Manual 10 6 History Records 10 6 1 Running Information Records 10 Operation of LCD Display Main Screen Press ENTER Menu Press VY His record Press ENTER Run record Press ENTER On the display press Y to select the date you want to view pressing Confirm by ENTER Inverter running pages Scroll pressing Y Change to the next record by pressing gt 10 6 2 Fault Records Run record shows historical information pages by P 1 2 Run reocrd T 2 gt 2012 01 21 30 2012 01 22 30 2012 01 23 30 2012 01 24 30 2012 01 25 30 2012 01 26 30 P 3 10 2012 01 21 10 16 PV1 PV2 Vdc V 0000 0 0000 0 Idc A 000 0 000 0 Pdc W 00000 00000 Paral mode El P 3 30 2012 01 31 10 16 P W 00000W S Va 00000VA Country GB Grid code LV P 3 10 2012 01 21 10 16 Temp 000 0 C State Run P 3 30 2012 01 31 10 16 L1 L2 L3 Vac V 000 0 000 0 000 0 Tac A 000 0 000 0 000 0 Pac W 0000 0000 0000 F Hz 00 00 00 00 00 00
25. LCD RS485 Fans 4 Power Circuit Fig 2 5 Main Circuit Diagram of SG30KTL DC Switch S r g i DC EMC MPPT1 Relay D Filter Boost E E O re A DC Bus Inversion r 7 i Circuit A AC re Ss L Reactor ai L3 z Ca R i i lt T CY treated N o x Dt EMG MPPT2 pel 2 ilter Boost I i l i A ny Serra Fig 2 6 Main Circuit Diagram of SG30KTL M 10 SUNGROW User Manual 2 Product Introduction 2 3 2 Functions Description Inverter functions can be grouped as the following Conversion function Inverter converts the direct current power into alternating current power which conforms to the grid requirement of its installation country Data storage and display Inverter stores essential data including running information and fault records and displays them on integrated LCD display Parameters configuration Inverter provides various parameters configuration for optimal operation Communication interface Standard RS485 interface for connecting other monitoring devices into the PV system is included Protection functions Reverse polarity protection Short circuit protection Insulation resistance to ground surveillance Inverter output voltage surveillance Inverter output frequency surveillance Residual current protection DC component of AC output current surveillance Anti islanding phenomena protection Ambient temperature surveilla
26. Order Description Reference Chapter 1 Unpacking and inspection Section 4 1 gt Read this Monta especially the section on safety Chapter 1 instruction 3 Store the inverter unit if not install immediately Section 4 4 4 Choose the best installation site Section 5 1 5 Moving the inverter to installation site Section 5 2 6 Install the inverter against the chosen wall Section 5 3 4 Electrical connections include DC AC ground and Section 6 3 6 7 communication optional connection 8 Examine before commissioning Section 7 1 9 Start up inverter and configure corresponding Section 7 2 parameters 10 Troubleshooting Section 9 1 SUNGROW 15 4 Unpacking and Storage 4 1 Unpacking and Inspection The unit is thoroughly tested and strictly inspected before delivery Damage may still occur during shipping e Check the packing for any visible damage upon receiving e Check the inner contents for damage after unpacking e Check the completeness of delivery contents according to the inner packing list If there is visible damage to the packaging or the inner contents or if there is something missing contact the unit dealer Do not dispose of the original packaging It will be the best choice to store the inverter by re using the original packaging Fig 4 1 Paper Packaging of Inverter 16 SUNGROW User Manual 4 2 Identifying Inverter 4 Unpacking and Storage A nameplate is attached to one side of the inverter and the cart
27. RS 485 A B bus or RJ 45 Terminating Resistor RS 485 A B bus RJ 45 esis Only out Only out RS485in RS4850u Yes 1200hM Single one For Multiple Inverters Where there is more than one inverter all inverters can be connected to data logging device in daisy chain The first and last inverters in the chain must be terminated with a resistor of 1200 The shielding layer of RS485 cable should be single point grounded The maximum number that inverters are connected in the daisy chain depends on converter data logging device and other factors Please refer to converter s or data logging device s manual to obtain the limit SUNGROW 45 6 Electrical Connection User Manual Inverter n Inverter 2 Inverter 1 Solarlnfo Logger PC RS485 RS232 Shielding layer is grounded Communication Connection Inverter _ RS 485 A B bus or RJ 45 zerminaung Resistor RS 485 A B bus RJ 45 Only out Only out RS485in RS485out Yes 1200hM Inverter 1 In and Out No Inverter PA 2 n 1 In and Out In and Out RS485in RS485out Yes 1200hM Inverter n 46 SUNGROW User Manual 6 Electrical Connection 6 6 3 RS485 Communication Connection RS485A B Bus Connection Step 1 Lead shielding RS485 twist pair type cable through communication cable gland to the configuration circuit board Step 2 Trip off the insulating layer of the communication cables Connect the cables to the RS 485 bu
28. RT function regardless of the country selected Step 9 After configuring the Grid Code there will be a Pro param type selection screen and then corresponding sub menu will come up For detailed information please refer to 10 11 Protective Parameters Setting 52 Pro param Single stage Multi stage IT Italy Pro param gt Pro Stage 11 Fmax recover 50 10Hz Fmin recover 49 90Hz Vmax recover 253 00V Vmin recover 195 5V SUNGROW User Manual 7 Commissioning Setting confirmation Step 10 After configuring all parameters there will be a setting confirmation screen Check Country Other whether all above mentioned parameters are Grid code LV correct Confirm by Pressing ENTER Cancel LVRT OFF by Pressing ESC and reset Date 2012 01 31 Confirm above settings Step 11 Inverter will enter into startup process Observe status of LED indicators and the LCD main screen If inverters commissioning succeeds the RUN indicator will be lit and RUN will be displayed on the State area amp AL 90 15 2012 01 31 10 30 If inverter s commissioning fails the FAULT indicator will be lit and fault will occur on the display Press V to view current fault information Remove the existing malfunction and then repeat starting up inverter as the above procedures SUNGROW 53 8 Disconnecting Dismantling and Disposing the
29. SUNGROW User Manual SG30KTL SG3OKTL M PV Grid Connected Inverter SG30KTL_SG30KTL M UEN Ver12 201304 Version 1 2 About This Manual This manual is for the inverters SG3OKTL and SG30KTL M These inverter are grid connected transformer less robust and of high conversion efficiency The device will bring you profit from PV power system Aim The manual contains information about the inverter which will provide you guidelines to connect the inverter into the PV power system and operate the inverter Related Documents The manual cannot include complete information about the PV system You will get the additional information about other devices at www sungrowpower com or via webpage of device manufacturer Target Group The manual is targeted to technical personnel who is responsible for inverter installation and commissioning in the PV power system and inverter owner who will perform daily LCD operation How to Use This Manual Read the manual and other related documents before any work with the inverter Documents must be stored carefully and available at all times The contents of the manual will be periodically updated or revised due to the product development It is probably that there are changes of manual in subsequent inverter edition The latest manual can be acquired via visiting the web page www sungrowpower com Symbols Explanation Important instructions contained in this manual should be followed d
30. allinG on Metal Frane mainesana AAE RORA 26 Electrical Connection eessssscessssscccsossscccsssscccossssseessssssessssss LO 6 1 Simplified Electrical Connection Diagram ssss ssesseessseessseessssecsssserssseeesss 28 62 lermi als Descriptio N neesan AN 29 10 6 3 Connecting Inverter to AC Grid es sssessseessseessecsseessseesseessseosseeosseesseesssessss 30 OS TAC Side Requirements ass acca lescts cs aecvssiyssccsiutevscoutavoosseeasiosapwisetenoer ears 30 63 2 Gnid CONNECTION erari etait nein E 32 6 4 Connecting Inverter to PV ArrayS esessessesssesscssesserseossesserseossesecseesesseeseee 35 6 4 1 PV Inputs Configuration Of SG30KTL ssssseeesssseeesssssesessssecsssssseesssseeessssee 35 6 4 2 PV Inputs Configuration Of SG3OKTL M ccssssssssssssssscsessssssssssessesseesseessees 36 6 4 3 PV Connection Procedures ensai a R 39 65 GrouUNnGING THE INVENTEN nsession a E a 42 6 5 1 GrOUNCING System Overview enosn anato E aa OE 42 6 5 2 Second Protective Earth Terminal esssseessssserssssseeessssseeessssecoossseerossseersssssee 43 660 COMMUNICATION Connecti easain ak asai 44 6 6 1 Communication OvervieW sssessserssseeessseeossscosssscssescroseeeesssecsssecossseossescossscess 44 6 6 2 COMMUNICATION Sy STEM ae lat naa aceite cnit ten eieanie 45 6 6 3 RS485 COMMUNICATION CONNECTION cessscesecsecessecsccecsecscssesesteseeneseeneesees 47 Commissioning EEE aclo setae EPE E EF EAE
31. alls below the protective value a 2 If the fault still exists please contact protective limit Sungrow Service Dept 0007 Inverter has checked AC The inverter will self recover after several overcurrent temporarily seconds The grid frequency has 1 Check the frequency of the grid 0008 exceeded inverter 2 If the grid frequency exceeds the permissible allowable upper limit range of inverter protective parameters ask The grid frequency has utility grid company for solution 0009 fallen below inverter 3 Ifthe grid frequency is within the permissible allowable lower limit range contact Sungrow Service Dept 1 Check whether AC circuit breaker is triggered 2 Check whether AC cables are all firmly connected Ka hanang 3 Check whether grid is not on service 4 If all conditions are OK and this malfunction still occurs in the LCD screen contact Sungrow Service Dept The DC component of AC 1 Wait a moment for inverter recovery 0011 current has exceeded 2 If the fault occurs repeatedly contact inverter limit Sungrow Service Dept Inverter has detected 1 Check the PV strings for ground fault 0012 that there is a failure 2 If the fault occurs repeatedly contact current Sungrow Service Dept SUNGROW 57 9 Troubleshooting and Maintenance User Manual Fault Description Troubleshootin Code p g 1 Wait a moment for grid recovery 2 If the grid parameters exceed the permissible Inverter has
32. are designed for the limit value that can trigger the protective functions of the inverter Main Screen Press ENTER Menu screen Press Y x3 Set param Press ENTER Enter password Press ENTER Press Y x2 Pro param Press ENTER A password confirmation screen will occur Press gt to Pro param move cursor right and Press Y to input the password Please enquire Sungrow or your dealer for this Password password 000000 To make protective parameters setting convenient Countries Inverter provides country code selection The protective O B O DE O FR OTT parameters have been configured before delivery O ESO AT O AU OZ according to different countries utility grid O BE O DK O GRLO GRIS requirements Choose the correct country code by Press v and Press ENTER to confirm O NL O PT O CHN O SE Other The description of country code is illustrated below Country Code Full Name Country Code Full Name GB Great Britain DE Germany FR France IT Italy ES Spain AT Austria AU Australia CZ Czech BE Belgium DK Denmark GR_L Greece Land GR_IS Greece Island NL Netherlands PT Portugal CHN China SE Sweden Other Country not included above SUNGROW 79 10 Operation of LCD Display Confirm by pressing ENTER after country code selection Choose grid code according to actual grid condition Note LV represents Low Voltage Grid Code and MV represents Middle Voltage G
33. ccccccccccccccccccccccccccccseseoO 2 1 tended Usad Cin cacitentnnaitrecenncsnsaeavineniea E EA 6 22 Product Desiptio Mear a NAA 7 22 1 Product AppearaNCE aei a A S 7 22 2 Dimensions Of Inverter E 8 223 FCD Display Panel sundonin a A 8 224 DE SWI hensii a a a en dada AA A 9 23 Technical DESCH STON eater acssincecuteiiesinascadacusatccne ance O 10 2 3 Principle Descriptio Miciauwascassmiaincamancenuwaanuieeaaunnees 10 2 3 2 Functions DOS CHIOTIOMN serons R ase abec sssdersceevanasaseaanenes 11 2 3 3 Derti ea a sb sts tench tess vaccavguen de eatteeee ab vce tented a deandeutd diate ied eeu ved tetas 12 Installation FIOW cccccccccccccccscsccccccccsccccccccsccccccccccscccccccccccs 1 4 Unpacking and Storage sssccccsssscccssssccccssssccccssssccssssee 16 4 1 Unpacking ANd Inspections 16 A2 NASITITYVIAG Verte ssri O 17 43 Delivery Content nA 18 4 4 Storage of lnverter sssesesseesssseesssseesssseesssecosseeossseesssserssseresseeeossecosssersssseesssee 19 Installing Inverter onto Wall cccccsssssccssssccccsssscccssesee2O 5 1 Selecting Installation Location es esssessseessseesseesssessseessseesscessseossseossersseesss 20 5 2 Moving Inverter to Installation Site seseesssessssessseesseesssessseeosseesseessseeses 23 53 MStAINNE the MVEN E ereo A ES 23 5 3 2 Installing on Concrete Wall seseessseessssesssssesssseesssseesssseessseeesssesosseesssseeossseess 24 532 INSt
34. ce broken fan in necessary 0037 eet temperature is too high 3 Clean air grills of outlet 4 If the fault still exists please contact with Sungrow The inverter has checked 1 Wait a moment for inverter recovery 0038 that there is a fault of 2 If the fault occurs repeatedly contact relay Sungrow Service Dept 1 Wait a moment for inverter recovery The insulation resistance 0039 2 If the fault occurs repeatedly contact is low ISO fIt Sungrow Service Dept 1 Wait a moment for inverter recovery 0040 IGBT saturation 2 If the fault occurs repeatedly contact Sungrow Service Dept There is a fault with 1 Wait a moment for inverter recovery 0041 2 If the fault occurs repeatedly contact sampling channel Sungrow Service Dept 0042 Caenin bane If the fault occurs repeatedly contact Sungrow Service Dept The ambient Disconnect inverter to stop Wait for ambient 0043 temperature falls below temperature to rise above 25 C and then 25 C start inverter again Theres i a tult with 1 Wait a moment for inverter recovery 0044 ae 2 If the fault occurs repeatedly contact DC AC inversion circuit Sungrow Service Dept i ith PV1 0045 Toere aa rau 1 Wait a moment for inverter recovery poostelreult 2 If the fault occurs repeatedly contact There is a fault with PV2 p u 0046 am Sungrow Service Dept boost circuit SUNGROW 59 9 Troubleshooting and Maintenance User Manual
35. cececesasssssssssseseseeseasares 79 10 12 Communication Parameters Setting ssessessssssessessesssessessesssessessesseessessesse 82 10 13 Special Settings forta y uensrisssononasen nin en 83 10 13 1 Over frequency Derating Setting for Italy essssssosessssssseesessssssceeessss 83 10 13 2 Reactive Power Regulation for Italy uu c sssssssssssssessessessssscssesesseesseneesees 84 10 13 3 Protective Parameters Setting for Italy 0 esssssssseesessssscseesesseesseseeeees 86 MD App ndiX 6 cscscnsscscvcedssecocenssesseeasasdvatecdsiwssasacdecsessenveesseulecessedesees Oo Tele Technical Dataoanies ai AA R sa atece terion 89 IGA Terminas anda Gables i E T N 90 11 3 Excl siomof Lia BIY vcesscsssissvessorssncceseencessessncseiosorenstedutanantentonsansonnneivans 91 IA ADDUTUS eukin nie N N NNa 92 VI 1 Safety Instructions IMPORTANT SAFETY INSTRUCTIONS The SG30KTL and the SG30KTL M have been designed and tested strictly according to the international safety regulations As electrical and electronic equipment safety instructions related to them must be complied with during installation commissioning operation and maintenance Incorrect operation or work may result in damage to e The life and well being of the operator or a third party The inverter and other properties that belong to the operator or a third party Therefore the following safety instructions must be read and always kept in mind prior to any work All
36. ddress 001 SUNGROW User Manual 10 Operation of LCD Display 10 13 Special Settings for Italy If the Countries selection is IT Italy several LCD menus and operation methods are different from other countries The differences focus on Run param and Pro param as shown below 10 13 1 Over frequency Derating Setting for Italy If the Countries selection is IT Italy the Derating Slope will display in the Run param screen When the grid frequency is between 50 3Hz and 51 5Hz inverter will decrease power according to the Derating Slope Default derating slope Pm Hz Pm is the power before derating 83 33 Range 40 100 Note Derating Slope is the power derating slope Power derating slope 100 Grid frequency x Frequency derating slope Frequency derating slope range 2 5 Fig 10 5 IT Over frequency Derating Curve SUNGROW 83 10 Operation of LCD Display 10 13 2 Reactive Power Regulation for Italy Button Operation User Manual The button functions for Italy parameter setting sub menus may differ from that in other menus Proceed as follows to perform the parameter settings Switching Mode Editing Mode N Shortly press y Shortly press Oto navigate gt A 4 d Long press or Long press to confirm all the Shortly press to add one step value Shortly press
37. detailed work related safety warnings and notes will be specified at the critical points in corresponding chapter A WARNING All installation and electrical work must only be performed by qualified personnel They have e been trained specially e already completely read through and understood the manual and other related documents e been familiar with safety requirements for electrical system Technical personnel mentioned above may perform the following work Install the inverter onto the wall e Connect the inverter into the PV power system Connect other devices into the PV power system e Commission the inverter e Maintain and service the inverter SUNGROW 1 1 Safety Instructions User Manual Before Installation There is a risk of injury due to improperly handling the device Always follow the instructions contained in the manual when moving and positioning the inverter e The weight of the equipment can cause injuries serious wounds or bruise if improperly handled During Installation Prior to installing the inverter onto the wall it is crucial to make certain that the inverter is not electrically connected System performance loss due to bad ventilation The equipment requires good quality ventilation during operation It is essential to keep the unit upright and nothing covering the heat sink in order to ensure that the equipment interior is well cooled down During Electrical Conn
38. e Install the unit where is accessible to install electrical connect or service e Do not install the unit on the wall of flammable materials material Do not install the inverter where contains flammable WN AS materials or flammable gas in the vicinity of the unit Y A installation off N S Ie YX RS S h JO N S Flammable material or gas near the installation 20 SUNGROW User Manual 5 Installing Inverter onto Wall Install the unit at eye level for easily buttons operation and display read It is suggested that the inverter be installed vertically with upside up for good heat dissipation e Never install the inverter horizontally nor with a forward tilt nor with a backward tilt nor even with upside down Forward tilt Backward tilt Horizontally Upside down mm z mm wru A W A rw A The inverter unit with IP65 can be installed gt ee temperature PO indoors or outdoors also l i e The ambient temperature should range from Min ambient temperature 25 C 25 C to 60 C Max relative humidity 95 No condensing The relative humidity at the installation must not Q exceed 95 Moisture may result in corrosion and damage to the int
39. e metal frame doesn t fit the holes on the backplate re drill holes on the backplate of appropriate position according to the chosen frame In order to avoid electrical shock or other injury inspect existing electronic or plumbing installations before drilling holes Mark positions Drill holes Step 5 Fasten the backplate against the metal frame with bolts and nuts The dimensions of fasteners used in the following diagram are recommended The torque for fastening the nut is 35 Nm mete ae Item Description Remark A Hexagonal socket nut M10 Spring washer Washer Hexagonal bolt M10 45 Metallic wall Backplate nanim oLa 26 SUNGROW User Manual 5 Installing Inverter onto Wall Step 6 Assemble the cap onto the inverter for better weatherproof function Step 7 Lift up the inverter above the backplate and then slide down to make sure that the recesses on the back of the inverter fit perfectly together with the backplate Step 8 After fit the inverter to the backplate fasten the inverter to the backplate with two M4x16 screws Assemble cap _ Hang inverter SUNGROW 27 6 Electrical Connection Once the inverter is firmly attached to the appropriate location it can be connected to the PV power system Installation shall comply with local regulations and technical rules Installation shall comply with the relevant instr
40. ear fan turning Clean or replace the fans Check the fuses and the DC SPD Devices eek Replace the fuse Every 6 months Contact Sungrow to order new DC SPDs Check the LCD stop and emergency stop circuit of the system Safety Simulate shutdown and check stop signal Once or twice a function communication year Check the warning labels and replace them if necessary Software optimization Once or twice a Software Check the setting of every parameter year SUNGROW 61 9 Troubleshooting and Maintenance User Manual 9 2 2 Maintenance Instruction Fans Maintenance There are four fans at the side of the inverter for active cooling during running operation If the fans are dirty or out of work the inverter may not be cooled down well and its efficiency may accordingly decrease Therefore it is necessary to clean the dirty fans or replace the broken fans as the following indications 44 DANGER e Disconnect the inverter from the grid first and then PV arrays before any maintenance work e Lethal voltage still exists in the inverter Please wait for at least ten minutes and then perform maintenance work e Fans maintenance work may only be performed by qualified electricians 1 Disconnect the AC circuit breaker 2 Turn off the upstream DC circuit break or cover the PV arrays with opaque materials Rotate DC switch at the side of inverter to the OFF position 3 Wait for at least ten minutes Disconnect all elec
41. ection Lethal voltage exists PV arrays will produce electrical energy when exposed to sunlight and thus can create an electrical shock hazard e Wiring of the PV arrays should only be performed by qualified personnel PV modules should be covered by opaque materials during wiring WARNING All cables must be firmly attached undamaged properly insulated and adequately dimensioned 2 SUNGROW User Manual 1 Safety Instructions During Inverter Operation Do not open the enclosure when the inverter is under voltage There is an unlikely but possible risk of explosion in very specific cases of malfunction The housing will protect persons and property from such an explosion only if it is correctly sealed There is a risk of inverter damage or personal injury Do not disconnect DC connectors while the inverter is under AC load First de energize the equipment from dual power sources and then verify that there is no voltage present There is a risk of burn Prevent from touching device hot parts such as heat sink during operation Only LCD display panel and DC switch can be touched during inverter operation Maintenance and Service There is a risk of inverter damage or personnel injury due to incorrect service work Always keep in mind that the inverter is power supplied by dual power source PV arrays and utility grid Before any service work you should obey the following procedures e Disconnect invert
42. ee or liability claims for damages of any kind are excluded if they are caused by one or more of the followings Inappropriate use or install of the product e Installing or operating the product in an unintended environment Ignoring relevant safety regulations in the deployment location when installing or operating the product e Ignoring safety warnings and instructions contained in all documents relevant to the product Installing or operating the product under incorrect safety or protection conditions e Altering the product or supplied software without authority The product malfunctions due to operating attached or neighboring devices beyond allowed limit values e Damages caused by irresistible natural environment The use of supplied software produced by Sungrow Power Supply Co Ltd is subject to the following conditions e Sungrow Power Supply Co Ltd rejects any liability for direct or indirect damages arising from the use of the Solarlnfo software This also applies to the provision or non provision of support activities e Using the Solarlnfo software for commercial purposes is prohibited Decompiling decoding or destroying the original program including SolarInfo software and the embedded software is prohibited SUNGROW 91 11 4 AboutUs Sungrow power supply is a China leading manufacturer of various power electronics products for renewable energy generation systems Our products include converter
43. en the modules temperature exceeds an upper limit the inverter start to gradually derating until the temperature decreases to normal range e When the inner temperature exceeds an upper limit the inverter start to gradually derating until the temperature decreases to normal range The deration lower limitation is about 33 If the modules temperature and the inner temperature are both exceed the limit the actual derating power value will be the less one Grid Under voltage Derating Once the grid voltage is in the defined range of Vgrid Vmin 215V the inverter will decrease the power output Pivmin 215 Pn x Vgrid 230V Ph Working area gt Vinit 215V Vmax Fig 2 8 Grid Under voltage Derating SUNGROW 13 3 Installation Flow Fig 3 1 shows the installation flow of inverter for installer Please follow these procedures Unpacking and Inspection Read User Manual Install Immediately Yes i Storage Mounting Location Selection Moving Inverter Mounting the Inverter Electrical Connection Check before Commissioning l 10 Commissioning ee Troubleshooting a Ne Yes Cu D Fig 3 1 Installation Flow Chart 14 SUNGROW User Manual Tab 3 1 Description of Installation Flow 3 Installation Flow
44. ence between the two PV inputs SUNGROW 37 6 Electrical Connection User Manual Ha Ee A Ea HA E PV input 2 Fanka _ Prior to connecting the SG30KTL M to PV inputs the following electrical specifications must be met simultaneously T Total DC Power Limit Open circuit Voltage Short circuit Current for the SG30KTL M Limit for Each Input Limit for Total Input 32000W 1000V 66A You should also take the negative open circuit voltage temperature coefficient into consideration when designing the PV string Configuration of PV Connection Mode PV configuration mode of the SG30KTL M can be performed by a switch on the configuration circuit board Independence mode turn the switch ON Parallel mode turn the switch OFF Configuration circuitboard PV configuration mode Independence Independence ale Default NOTICE For SG30KTL the switch must be set in parallel mode 38 SUNGROW User Manual 6 Electrical Connection 6 4 3 PV Connection Procedures DC cables from PV strings should be equipped with DC connectors Sungrow provides corresponding plug connectors in the scope of delivery for quick connection of PV inputs Pairs of MC4 DC connectors are supplied in the scope of delivery To maintain IP65 weatherproof function of inverter only the supplied DC connectors or the connectors of the same protection class can be used DC Cable Requirements Cross section Oute
45. er from the utility grid side first and then PV arrays e Wait at least ten minutes until the inner capacitors discharge completely e Verify that no voltage or current present with appropriate testing device Keep unrelated person away A temporary warning sign and barrier must be posted to keep non related person away for any period while performing electrical connection and service work SUNGROW 3 1 Safety Instructions User Manual NOTICE e Any malfunction that may impair the inverter safety functions must be repaired immediately before the inverter is restarted again e Inverter contains no owner serviceable parts inside Please contact local authorized personnel if any service work is required Servicing of the device in accordance with the manual should never be undertaken in the absence of proper tools test equipment or more recent revision of the manual which is clearly and thoroughly understood NOTICE There is a risk of inverter damage if it is improperly serviced Use only accessories and spare parts approved by the inverter manufacturer Never modify the inverter or other components of the inverter Otherwise it will cause loss of any or all warranty rights NOTICE There is a risk of inverter damage due to electrostatic discharge The printed circuit boards contain components sensitive to electrostatic discharge Wear a grounding wrist band when handling the boards Avoid unnecessary touch with the board
46. erminal to DC2 with a cable of cross section not less than 6mm 10 AWG and connect DC1 to DC2 on the DC connection circuit board as the following diagram shown The existing cable connections are not displayed in the below diagram 40 SUNGROW User Manual 6 Electrical Connection THT wenn o HH AR HR DC connection circuit board LILIO Step 9 Plug the positive and negative DC connectors into PV terminals underneath the connection cabinet until there is an audible sound Step10 Connect other PV strings following the above mentioned procedures Step 11 Seal the unused DC terminals with the terminal caps SUNGROW 41 6 Electrical Connection User Manual 6 5 Grounding the Inverter WARNING Because of the transformer less design of the inverter neither the DC positive pole nor the DC negative pole of the PV string is permitted to be grounded 6 5 1 Grounding System Overview All non current carrying exposed metal parts of the equipment and other enclosures in the PV power system should be grounded e g PV arrays frame and inverter enclosure Where there is only one inverter in the PV power system connect PE cable to the installation ground Where there are multiple inverters in the PV power system connect PE cables of all inverters and mounting frame of PV arrays to the same copper bus bar In this way it will establish equipotential connection Inverter 1 Inverter
47. ernal device components SUNGROW 21 5 Installing Inverter onto Wall User Manual e Avoid exposing inverter to direct sunlight or rain or snow to extend its service life despite the IP65 protection degree Exposure to the sun may cause additional internal heating which will cause power reducing Shaded site of the building is preferred O Z AN AN E F 7 oN i y SS i i l Snow Direct sunlight Direct rain fall accumulation e Take enough space for convection into consideration during installing multiple inverters It is suggested that position the multiple inverters in a staggered way if necessary n Coolair SS Hot air J g Y en beans E pane E EA XIa Y 600mm 1000mm 1000mm 600mm yy N gn Z O i a N Siasi n 5 Y 600mm ag 1000mm 600mm Do not install the inverter in a closed cabinet Lo a Otherwise the inverter will not operate an normally It is necessary to make sure that hot air will be discharged by forced ventilation J Ie U e Do not install the inverter where children can i Do not install the inverter in living area Noise can be produced during running of inverter which may affect your daily life 22 SUNGROW User Manual 5 Installing Inverter onto Wall 5 2 Moving Inverter to Installation Site If the inv
48. erter is to be installed remove the unit from the packaging and move it to the chosen installation site During the moving process the following instructions should be obeyed Always remember the weight of the inverters e Grasp the equipment handles by both hands by means of handles e Move the unit with the help of others or the lifting device Do not release the equipment unless it has been secured to the wall firmly 5 3 Installing the Inverter Inverter is installed onto the wall by means of backplate enclosed in the packaging If you don t use the supplied backplate you may drill holes refer to its dimension below 544 514 60 216 5 216 5 100 pomm a 70 22 440 524 544 Fig 5 1 Dimensions of Backplate unit mm SUNGROW 23 5 Installing Inverter onto Wall User Manual There are two sets of stainless fasteners supplied for attaching the backplate to concrete wall and metal frame a 65 Fig 5 3 Dimensions of Fastener Set for Metal Frame unit mm 5 3 2 Installing on Concrete Wall Step 1 Remove backplate and fasteners from the packaging Step 2 Place the backplate onto the chosen concrete wall and
49. etting Press gt to move cursor right and Lower PF Ind 0 900 Press Vv to set the appropriate value Confirm settings by Upper Power 100 0 Press ENTER Parameter Explanation Default Range Upper PF Cap Power factor of point P1 in the Q P mode 1 09 1 curve Lower Output power of point P1 in the Q P mode 50 0 50 Power curve in Lower PF Ind Power factor of point P2 in the Q P mode 0 9 0 9 1 curve Upper Output power of point P2 in the Q P mode 100 50 10 Power curve in i 0 Lower Power lt Upper Power 76 SUNGROW User Manual 10 Operation of LCD Display General Q P Curve Default Q P Curve P1 COS COS Upper PF Cap Lower Power Upper Power 50 100 P Pn _ gt P Pn Upper PF Cap Powe 1 Lower Power Upper Power Inductive Lower Lower PF Ind PF Ind 0 9 P2 Fig 10 3 Reactive Power Regulation Curve in Q P Mode Q U Mode when the country selection is not IT The reactive power ratio changes with the grid voltage If the country selection is not IT Italy after selecting Q U Lower Q Sn Ind 050 0 mode Press Y to enter the Run param Q U sub menu Upper Q Sn Cap 050 0 For each item setting Press gt to move cursor right and Lower U Limit 095 0 Press VY to set the appropriate value Upper U Limit 115 0 Confirm settings by Pressing ENTER Run param Q U gt Ul Limit U2 Limit Hysteresis Parameter Explanation Default Ra
50. ge I Grid under voltage I Min V time Stage II Grid under voltage tripping time Max F prot Over frequency protection I Max F grid Stage I Grid over frequency I Max F time Stage I Grid over frequency tripping time I Max F grid Stage II Grid over frequency I Max F time Stage II Grid over frequency tripping time Min F prot Under frequency protection I Min F grid Stage I Grid under frequency I Min F time Stage I Grid under frequency tripping time IT Min F grid Stage II Grid under frequency I Min F time Stage II Grid under frequency tripping time SUNGROW 81 10 Operation of LCD Display Confirm settings by pressing ENTER and enter the Setting confirmation screen Check all above mentioned parameter settings Confirm them by pressing ENTER Cancel by pressing ESC and reset User Manual Setting confirmation Country Other Grid code LV LVRT OFF Confirm above settings i When the Country or the Grid code or LVRT switch mode is changed the protective settings will be unavailable unless the inverter is re energized 10 12 Communication Parameters Setting Main Screen Press ENTER Menu screen Press Y x3 Set param Press ENTER gt Enter password Press ENTER Press Y x3 Com param Press ENTER Press gt to move cursor right and Press Y to set the appropriate value Confirm settings by Pressing ENTER The range of communication address is 1 247 82 Com param A
51. grid company for solution AC Side Circuit Breaker An independent three or four pole circuit breaker minimum size value 50A for each inverter must be installed at the output side to ensure that the inverter can be securely disconnected NOTICE There are some points that are not allowed for the inverter It is not allowed for several inverters to use the same circuit breaker e It is not allowed to connect loads between inverter and circuit breaker Residual Current Device With an integrated universal current sensitive residual current monitoring unit inside the inverter is able to distinguish the fault currents from normal capacitive leakage currents The inverter will disconnect from mains as soon as a fault current of more than limit value has been detected However if an external RCD or residual current breaker is mandatory the switch must trigger at a failure current of 300mA or higher Requirements of Multiple Inverters in Parallel Grid Connection If several inverters are operated in parallel connection to grid different requirements should be obeyed L1 Scenario 1 L2 gt L3 Several inverters are operated N in parallel connection to the PE three phase Low Voltage grid Inverter 1 Inverter2 eee Invertern 30 SUNGROW User Manual 6 Electrical Connection Requirements The sum of all inverters in parallel connection is limited t
52. h Francaise Italia HC Time Format Date Time YY MM DD 12 01 31 10 30 55 Warning Only qualified personnel are allowed to adjust following parameters Improper settings may cause damage to the inverter Countries O GB O O ES O BE O O NL O Other DE O FR O IT AT O AU O CZ DK O GR_LO GR_IS PT CHN SE 51 7 Commissioning User Manual Refer to 10 11 Protective Parameters Setting for country code explanation If the inverter is installed where the country code is not included please choose item Other and manually set the protective parameters If the country code is not set correctly during commissioning reset the protective parameters as dictated in 10 11 Protective Parameters Setting There may be faults if otherwise Step 7 Configure grid code on the display Press v to select grid code Confirm the selection by Pressing ENTER Where LV indicates Low Voltage Grid Code MV indicates Middle Voltage Grid Code Step 8 When choose MV Press gt to enter the LVRT function selection Press v to switch on or off the LVRT function and Press ENTER to confirm the selection Grid codes O LV MV LVRT ON If the Country selected does not have the Grid codes directives this i configuration will not affect the following procedures However you may select the MV to enable disable the LV
53. ing The contrast value ranges from 0 to 100 The recommended value is 50 or 60 SUNGROW 69 10 Operation of LCD Display User Manual 10 5 Detailed Running Information On the main screen there is some basic information about the inverter For more detailed running information please operate as follows Main Screen Press ENTER Menu Run info Press ENTER LCD screen will show four detailed running information pages Scroll pages by pressing gt V DC power input represents the total input power of DC power input 00000W PV1 and PV2 PV1 PV2 Vdc indicates the DC voltage of each input Vde V 0000 0 9000 0 Idc indicates the DC current of each input Idc A 000 0 000 0 Pdc indicates the DC power of each input Pdc W 00000 00000 Indep Paral mode is the PV configuration mode of Indep mode the two PV inputs indicates the corresponding input is at work P W is inverter output active power P W 00000W S Va is inverter output apparent power Country is inverter selected country code Grid code is inverter selected grid code sounmery ap S Va 00000VA Grid code LV Vac is phase voltage aaa lac is phase current Pac is AC output of each phase ee ee ee F is frequency of each phase poe Soe ee ee 0000 0000 F Hz 00 00 00 00 00 00 CO2 reduce indicates total
54. ly affixed and durable 50 SUNGROW User Manual 7 2 Commissioning Procedure 7 Commissioning If all checking items mentioned above meet the requirements precede the following procedures to start up the inverter for the first time Step 1 Close external AC circuit breaker Step 2 Rotate DC switch to ON position Step 3 Language Suppose there are sufficient sunlight and enough DC power PV arrays initialize and supply DC power to inverter The LCD display is activated to check the validity first If there is a defect on the display contact Sungrow selection screen will prompt Perform language settings with the right two buttons Detailed button functions can be referred to 10 1 Description of Button Function Press v to choose language as you prefer Confirm the settings by Pressing ENTER Step 4 Configure time according to the local time Step 5 Step 6 Time setting is very important which directly affects data logging Press gt to move cursor and Press y to scroll up time value Confirm the settings by Pressing ENTER Select the country code according to the inverter s installation country Each country code represents corresponding local protective parameters that have been preset before delivery Before country setting there is warning screen Press v to choose country code Confirm the settings by Pressing ENTER SUNGROW Languages O00 0 English Deutsc
55. munication 48 SUNGROW User Manual 6 Electrical Connection terminal definition is referred to the device manual Step10 Verify the communication connection and configure the communication parameters If there is more than one inverter to communicate with a PC or a data i logger it is crucial to configure the communication parameters of each inverter See 10 12 Communication Parameters Setting Solarlnfo logger and RS485 232 converter are optional parts and can be ordered from Sungrow Pin3 aTh z RS485 a RS 232 RS 485 RS422 RS232 PINGS 7 OR SUNGROW 49 7 Commissioning Commissioning is a critical part for a well installed PV system which can protect against fires injury and electrical shock 7 1 Inspection before Commissioning Before starting the inverter you should check the following items should be checked for requirements 1 Inverter unit is accessible for operation maintenance and service 2 Re check that the inverter is firmly installed onto the wall 3 Space for ventilation well is provided for one inverter or more than one inverter Nothing is left on the top of the inverter unit Inverter and accessories are correctly connected Cables are routed in safe place or protected against mechanical damage Specification of AC circuit breaker is reasonable Terminals not used underneath the inverter are sealed o po oe SS Warning signs amp labels are suitab
56. n including LCD version and DSP version The firmware version information is read only 74 Firmware version LCD LCD_SG30KTL_V1 X M DSP DSP_SG30KTL_V11_X SUNGROW User Manual 10 Operation of LCD Display 10 10 Running Parameters Setting 10 10 1 Main Menu of Run param Main Screen Press ENTER Menu screen Press Y x 3 Set param Press ENTER Enter password Press ENTER Press VY Run param Press ENTER On the Run param screen Press Y to move arrow to one item and Press ENTER to start this item setting For each item setting Press gt to move cursor right and Press Y to set the appropriate value Confirm by Pressing ENTER Run param P1 2 gt Standby time 020s Recovery time 030s P W limits Derating Slope 100 00 100 0 y Run param P2 2 gt Q Var switch 0FF PF 1 000 Q Var limits 100 0 Tab 10 4 Specification of Running Parameters Parameter Explanation Default Range Standby The time from inverter initialization to 30s 30 255s time inverter feeding power to grid Recover The time from the fault is cleared to 30s 0 900s time inverter feeding power to grid IT 300s a P W limits Inverter active power limits 100 0 0 100 Q Var Whether to start inverter reactive Pf Pf Qt Off switch power adjustment function Q P Q U 1 000 0 900 PF Power factor 1 000 40 900 1 000 0 10
57. n Press Vv X3 Set param Press ENTER Enter password Press ENTER Sys param Press ENTER Press wx2 gt Energy adj Press ENTER SUNGROW 73 10 Operation of LCD Display On the Energy adj screen Press gt to move cursor right and Press Y to set the correct offset value Confirm settings by pressing ENTER The positive symbol can be changed to the negative symbol The adjustment range is from 9999 to 9999 kWh Energy adj value Real measured value E tot reading value 10 9 4 Load Default NOTICE User Manual Energy adj 0000kWh All history accumulated information will be unrecoverable cleared and all parameters will return to the default value except the protective parameters and time once the load default operation is performed Main Screen Press ENTER Menu screen Press Y X3 Set param Press ENTER Enter password Press ENTER Sys param Press ENTER Press x3 Load default Press ENTER A password confirmation screen will occur Press gt to move cursor right and Press Vv to input the password 111111 Press ENTER to confirm load default 10 9 5 Firmware Version Load default Password 000000 Main Screen Press ENTER Menu screen Press Y X3 Set param Press ENTER Enter password Press ENTER Sys param Press ENTER Press Y x4 Firmware version Press ENTER Inverter shows detailed firmware informatio
58. nce DC over voltage protection Over current protection Power module over temperature protection SUNGROW 11 2 Product Introduction User Manual 2 3 3 Derating Derating the output power is a way to protect the inverter from overload and potential malfunctions Inverter s derating function can be activated in the following scenarios PV input overload Grid voltage too low e Temperature too high Inner temperature and power modules temperature e Power limit setting on the inverter LCD display or remote dispatch Grid frequency too high when the Country selection is DE or IT PV Overload Derating When the PV input power exceeds the defined Max DC Input Power 32 kW the inverter will reduce the power evenly to the maximum limit and keep the output power at nominal value PV out put Max DC Input Power Max DC Input DC input Power power Fig 2 7 PV Overload Derating Power Limit Setting User may allocate output power value of the inverter via LCD control panel or the remote dispatch from the grid company Under this kind of power derating the operating states will display on the LCD screen 12 SUNGROW User Manual 2 Product Introduction Over temperature Derating Power modules over temperature may result from high ambient temperature poor ventilation or fault of fans Over temperature derating may protect the inverter as well as the power modules against damage e Wh
59. nge Lower Q Sn Inductive Q Sn value of point P4 in the Q U 25 0 50 Ind mode curve Upper Q Sn Capacitive Q Sn value of point P1 in the 25 0 50 Cap Q U mode curve Grid voltage limit in of point P1 in the Lower U Limit 80 80 90 Q U mode curve A ay ar f Upper limit Grid voltage limit in of point P4 in the 115 110 115 Q U mode curve on U1 Limit Grid voltage limit in of point P2 in the 95 95 100 Q U mode curve TETE U2 Limit Grid voltage limit in of point P3 in the 105 100 105 Q U mode curve Hysteresis Hysteresis voltage width in 3 0 5 U1 Limit Hysteresis lt U2 Limit Hysteresis SUNGROW 77 10 Operation of LCD Display User Manual Q Sn Upper Q Sn U2 Limit Upper U limit m Grid voltage Lower U limit U1 Limit Lower Q Sn Fig 10 4 Reactive Power Regulation Curve in Q U Mode 10 10 3 Save P Q set On the Save P Q set screen Press Y to move arrow Save P Q set to one item Press gt to move cursor right and Press Y to set Confirm by Pressing ENTER Save Q Var set Y N gt Save P W limits Y N Select Y to save up the values set when power down Select N to restore default values when power down 78 SUNGROW User Manual 10 Operation of LCD Display 10 11 Protective Parameters Setting Protective parameters
60. nverter offers two buttons for the user to look up the running information and configure parameters settings The two buttons have multiple functions Please refer to Tab 10 1before any operation onto inverter Tab 10 1 Button Function Button Operation Description Press less than Move upwards or downwards or increase setting value Hereafter it is referred to as Press Y two seconds V Esc Press more than two seconds Return to the previous menu or cancel the command Hereafter it is referred to as Press ESC Press less than Move left or right or turn pages Hereafter it is referred to as Press gt two seconds gt ENTER Press more than two seconds Enter into the sub screen or confirm the command Hereafter it is referred to as Press ENTER The background illumination of the LCD screen will go out to save power if there is no button operation after one minute You can activate it by pressing any button 66 SUNGROW 10 Operation of LCD Display User Manual Inverter Menu Structure 10 2 YaLNa T00 SS Jppy e wesed wo7 Ja u0 Y3LNI JS O NH O ld O WN O 5 weged w0 ee SI yO1 Y9 O WG O 3A O ja SIN w eJed OJd 720 fv O lv OS O wesed uny lI O Ws O 30d O 99 O wesed sAs lt s q uno wesed jas 00 0OT dols BuT e1aq 0 OOT S1TWT1 M d dois UaLNa f SOEO aWT J A02 Y Y31LN3 A yes
61. o 34 Scenario 2 Several inverters are operated in parallel connection to low voltage side of MV transformer The high voltage side of MV transformer is connected to the Middle Voltage Grid Requirements The sum of all inverters in parallel grid connection is limited to 34 The rate voltage on the low voltage side of transformer must meet the inverter output electrical specification A neutral point is necessary and must lead outwards as neutral conductor Low voltage U2 P Side NNNNA U1 V2 e Mm s V1 w2 f A 1 i N I High voltage Sid i MV Transformer S Inverter 1 Inverter 2 eeee Inverter n The low voltage side of the transformer must be Y type 1MW transformer with a short circuit impedance less than 6 is recommended WARNING As mentioned in the scenarios above the total number of inverters is always less than or equal to 34 If there are inverters more than the limited value inverters may not operate normally See technical information Technical notes for multiple paralleled i grid connected inverters in the download area www sungrowpower com for more detailed information SUNGROW 31 6 Electrical Connection User Manual 6 3 2 Grid Connection An AC terminal block inside the connection cabinet is used for the five wire grid connection L1 L2 L3 N PE of the inverter And feed in
62. ode The reactive power ratio changes with the grid voltage a we Select Q U mode and Press Vv to enter into the ee Run para Q U sub menu vis 108 0 Press V to navigate the cursor Press gt to enter into the eae editing mode then the selected parameter will be shaded Seip Press Vv to increase one step value Press gt to decrease one step value Run param Q U P474 Press ENTER to confirm the setting and exit from the Bout 009 0 editing mode Curve a 4 Tab 10 8 Italy Q U Mode Parameters Explanation Param Explanation Default Range Step V2i Grid voltage at point D in 90 90 110 1 V1i Grid voltage at point C in 92 90 110 1 V2s Grid voltage at point A in 108 90 110 1 V1s Grid voltage at point B in 110 90 110 1 Qmax The max ratio of reactive power in 90 50 100 1 Pin Enter into the Q U regulation mode 20 20 100 1 when the power is above Pin Pout Exit from the Q U regulation mode 9 1 20 1 when the power is below Pout Curve Curve type A A B SUNGROW 85 10 Operation of LCD Display User Manual V2i lt V1i lt V1s lt V2s Pin gt Pout Capacitive Qna a A Default B Fig 10 7 Reactive Power Regulation Curve in IT Q U Mode 10 13 3 Protective Parameters Setting for Italy If the Countries selection is IT Italy the protective parameters settings procedures are shown below After Grid code
63. oge Check the PV input configuration mode and 0023 has changed during i restart the inverter when necessary inverter running muera ee ceed E 1 Inverter will recover if the deviation value E i falls below the protective limit 0024 deviation of neutral point 2 If the fault occurs repeatedly contact voltage i Sungrow Service Dept Inverter has checked out 1 Inverter will recover if the deviation value 0025 the unbalance of neutral falls below the protective limit point voltage 2 If the fault occurs repeatedly contact temporarily Sungrow Service Dept 58 SUNGROW User Manual 9 Troubleshooting and Maintenance Fault Description Troubleshootin Code p g 1 This is a short term fault Wait a moment for 0026 There is high Bus inverter recovery fluctuation voltage 2 If the fault still exists please contact Sungrow Service Dept The DC current is not balanced between the 1 Wait a moment for inverter recovery 0027 2 If the fault occurs repeatedly contact two PV inputs for parallel Sunaroi Sanice Dent PV configuration mode g pi Inverter has checked the 0028 reverse polarity of py Disconnectinverter p 2 Reconnect PV strings connection The temperature of 1 Check whether AC output power exceeds 0036 i module is too high norminal power too much 2 Check whether fans work normally and whether there are some abnormal fans Please The ambient repla
64. on 3 Wait for at least ten minutes Open the inverter as described in section 8 Disconnecting Dismantling and Disposing the Inverter 5 Observe the string fuse assignment and check the fuse conductivity using the multimeter A non conductive fuse indicates a fault in the affected string 6 Have the installer of the PV generator check the affected string and order the fuse for the defective string fuse of the same specification from Sungrow Ts Remove the blown string fuse 8 Insert the new fuse into the fuse holder 9 Close the inverter and startup the inverter again Clean Air Inlet and Outlet A huge amount of heat is generated in the process of running the inverter The inverter adopts a controlled forced air cooling method In order to maintain good ventilation please check whether there is anything blocking the air inlet and outlet Clean the air inlet and outlet with soft brush or vacuum cleaner if necessary 64 SUNGROW User Manual 9 Troubleshooting and Maintenance 9 3 Contact Sungrow Service Should you have any problems in operating on the inverter please contact us Service hotline 86 551 65327817 Email service sungrow cn We need the following information to provide you the best assistance Type of the inverter e Serial number of the inverter e Fault code name Brief description of the problem SUNGROW 65 10 Operation of LCD Display 10 1 Description of Button Function I
65. on respectively It provides information on type of inverter along with the most important specifications marks of certification institutions website and serial number which is available and identified by Sungrow SG30KTL DC Input min MPP voltage max MPP voltage max Input voltage SG30KTL M DC Input min MPP voltage max MPP voltage max Input voltage max Input current Isc PV 2 40A AC Output max Input current Isc PV 80A AC Output Rated output power 30000W Rated output voltage S N PE 230V 400V Rated output frequency 50Hz Max Output current 48A Rated output power 30000W Rated output voltage 3 N PE 230V 400V Rated output frequency 50Hz Max Output current 48A Safety Class I Enclosure IP55 Fans IP65 Other Ambient temperature 25 C 60 C Safety Class I Enclosure IP55 Fans IP65 Other Ambient temperature 25 C 60 C Overvoltage Category HI MAINS HPV Overvoltage Category II MAINS HPV SUNGROW POWER SUPPLY CO LTD WWW SUNGROWPOWER COM ___MADE IN CHINA SUNGROW POWER SUPPLY CO LTD WWW SUNGROWPOWER COM MADE IN CHINA Fig 4 2 Nameplate of Inverters without serial number Image shown here is indicative only Actual product you receive may differ
66. panel configuration can be performed via the LCD display panel gt Connection They are DC input terminals AC output terminal and RS485 terminals communication terminal 3 Handles The handles are designed for holding the unit when transporting installing or servicing cond PE ae are 4 a Second protective earth terminals as specified in EN 50178 Terminals 5 Air outlet Exit of hot air during the inverter operation 6 Mounting ear Itis used for hanging inverter onto the backplate 7 Fans There are four fans to perform controlled forced air cooling During normal operation it is in ON state It can shut down 8 DC switch J p STORE B the inverter immediately in OFF position 9 Air inlet Entrance of cool air SUNGROW 2 Product Introduction User Manual 2 2 2 Dimensions of Inverter 634 620 POT ALL 819 2 E Ji Fig 2 3 Outline Dimensions of Inverter unit mm 2 2 3 LCD Display Panel As a human computer interaction interface LCD display panel comprises LED indicators buttons and LCD display screen on the front panel of the inverter LEDs indicate the working status of the inverter The current running information shown on the LCD display Malfunction records shown on the LCD display Inverter configuration by pressing the bu
67. r In this mode the inverter will wait until the DC voltage recovers Stop The inverter is shut down Key siop The inverter will stop operation by manual Stop through LCD menu Start The inverter is initializing and synchronizing with the grid Upd fail IAP In Application Programming update fails If a fault occurs the inverter will automatically stop operation trigger the AC relay and show Fault on the LCD with the FAULT Fauli indicator lit Once the fault is removed in recovery time set by user see 10 10 Running Parameters Setting the inverter will automatically resume running Warning Inverter has checked out some warning information 68 SUNGROW User Manual 10 Operation of LCD Display If inverter is in Fault state Press gt V to view multiple Current fault information pages To know the meaning of the fault code please refer to 9 1 2 Troubleshooting of Faults in LCD Screen Current fault P 1 2 Fault pages Fault Fault code Fault Fault Fault Warning Tab 10 3 Icon Description Icon Description O Inverter is in IAP update process DI Inverter in power reduction state of Fans inside are working kA Inverter is warning the running state 10 4 Adjust Contrast 1 Press ESC to enter into the contrast adjustment screen Press Y to increase the setting value and press gt to decrease the value Press ENTER to confirm the contrast sett
68. r cable Max Withstand Max input current Area Range diameters Voltage for each PV string 2 aon 6 9mm 1000V 10A 12AWG 10AWG NOTICE The input current of each input channel should be less than 10A otherwise the fuse may blow out DC Cable Connection Procedures 7 DANGER Make sure that all the DC and AC cables to the inverter are not live before you start the electrical work Step 1 Strip off 7mm insulation layer from all DC cables Step 2 Assemble cable ends with crimp Positive Crimp Contact contacts by crimping pliers wv N a egative Crimp Contact SUNGROW 39 6 Electrical Connection User Manual Step 3 Lead cable through cable gland Positive Insulator Step 4 Insert the crimp contact into the insulator until it snaps into place Then pull gently to check if it is correctly engaged Step5 Screw the cable gland to front insulator with tightening torque 2 5 3 N em i For further assembly and connection instruction please visit the webpage of the device manufacturer Step 6 Make sure the connection cable of PV string for the correct polarity NOTICE The inverter will not function properly if the DC polarities are reversed Step 7 Disconnect the DC switch Step 8 For SG30KTL M configure PV configuration mode via a jumper according to actual PV conditions Please refer to 6 4 2 PV Inputs Configuration of SG30KTL M If inverter selects parallel PV configuration mode connect DC1 t
69. r less and grid connected inverters SG30KTL and SG30KTL M are illustrated in Fig 2 5 and Fig 2 6 PV strings input voltage is transmitted to DC BUS via Boost circuit e The SG30KTL is equipped with one MPPT for DC inputs to ensure that the maximum power can be utilized e The SG30KTL M is equipped with MPPTs for two DC inputs to ensure that the maximum power can be utilized even in different PV modules installation conditions Inversion circuit converts DC power into AC power which will be fed into the utility grid via five core terminals Protective circuits are designed to guarantee inverter safe operation and human safety A DC switch is integrated for safe disconnection of DC current The inverter provides standard interface RS485 for communication Inverters are also provided running records display and parameters configuration via human computer interface LCD display panel DC Switch a co y SS DC Bus Inversion E ee ee ga Py DCEMC MPPT L ias ac H ae ala Pm Ea md Filter Boost Reactor j i L315 oe T J A Filter L NIO J 57 H E E e Ha I i 4 PE DC SPD 6 Auxiliary cle
70. rid Code When choose MV Press gt to enter the LVRT function selection Press Y to switch on or off the LVRT function and Press ENTER to confirm the selection Note If the Country selected does not have the Grid codes directives this configuration will not affect the following procedures However you may select the MV to enable disable the LVRT function regardless of the country selected Press Y to select protective parameter type Press ENTER to confirm the selection If the country selection is IT Italy the Pro param menu right will show refer to the 10 13 3 Protective Parameters Setting for Italy for detailed settings User Manual Grid codes O LV A MV LVRT ON y Pro param Single stage Multi stage Pro param gt Pro Stage I Fmax recover 50 10Hz Fmin recover 49 90Hz Vmax recover 253 00QV Vmin recover 195 5V Single stage Protective Parameter when the country selection is not IT If the selected protective parameter type is Single stage the following sub menu will come up Press Y to select parameter Press gt to move cursor right and Press Y to set the appropriate value Confirm settings by Pressing ENTER Tab 10 5 Single stage Protective Parameter Explanation Pro param single gt Max V grid 276 0V Min V grid 184 0V Max F grid 51 50Hz Min F grid 49 80Hz Parameter Explanation Max V grid
71. rrect the connection of PV1 inputs 0077 PV2 overload Check the PV system design and correct the connection of PV2 inputs 60 SUNGROW User Manual 9 Troubleshooting and Maintenance 9 2 Maintenance 9 2 1 Routine Maintenance Items Methods Period Save the running data parameters and log to a Save data disk or a file Once a month Refer to the manuals of the data logging devices Visual check any damage or deformation of the inverter General Check any abnormal noise during the running of state of the inverter Every 6 months system Check each parameter of inverter operation Check if the temperature of the housing is normal Monitor the system using the thermal imager Check the temperature and dust of the inverter Clean the inverter enclosure Six months to a System Check the humidity and dust of the environment year it depends clean Meanwhile check whether the filter function of on the dust the air inlet is ok Clean the air inlet and outlet contents in air when necessary Check whether cable connections are loose Tighten the loose connections Six months after Electrical Check whether there is injury in the cables commissioning connection especially the surface in contact with metal and then once or Check whether the wrap belt of the connection twice a year terminals is strip off Check whether there is crack of the fan blade Check whether there is any abnormal noise of the Fans Once a y
72. rvation 8 3 Disposing the Inverter Users should take the responsibility for the disposal of the inverter NOTICE Some parts and devices in the inverter such as LCD displayer batteries capacitors may cause environment pollution Users must comply with the related local regulations to avoid causing pollution SUNGROW 55 9 Troubleshooting and Maintenance 9 1 Troubleshooting 9 1 1 Troubleshooting of LED Indicator See Tab 2 2 Description of LED Indicator Status for definition of LED s states Type of fault Troubleshooting LED indicators and LCD screen cannot be lit 1 Disconnect AC side circuit breaker 2 Rotate DC switch to the OFF position 3 Check the polarity of DC input RUN indicator 1 Disconnect AC side circuit breaker 2 Rotate DC switch to the OFF position 3 Check the correctness of electrical connection of inverter See 6 Electrical Connection Se 4 Check whether DC input voltage exceeds the inverter start voltage of inverter 5 If all above conditions are OK please contact with Sungrow 1 A fault is not removed yet Fault 2 Perform troubleshooting in according to fault type in LCD indicator is lit screen See 9 1 2 Troubleshooting of Faults in LCD Screen 3 If it cannot be solved please contact Sungrow 9 1 2 Troubleshooting of Faults in LCD Screen When faults occur Fault state will be shown on the main screen Pres
73. s selection you may enter into the ITi Italy Pro param sub menu Pro param Press Vv to select parameter Press gt to move cursor right gt Pro Stage nis and Press Y to set the appropriate value Confirm settings Fmax recover 50 10Hz by Pressing ENTER Fmin recover 49 90Hz Vmax recover 253 00V Vmin recover 195 5V Tab 10 9 Italy Grid protection Recovery Value Parameter Explanation re Inverter can start operating only when the grid frequency is below evan Fmax recovery The fault recovery value when the grid over frequency occurs Emin Inverter can start operating only when the grid frequency is above em Fmin recovery The fault recovery value when the grid under frequency occurs Vmax Inverter can start operating only when the grid voltage is below Vmax Eo recover The fault recovery value when the grid over voltage occurs Vmin Inverter can start operating only when the grid voltage is above Vmin Ea recover The fault recovery value when the grid under voltage occurs 86 SUNGROW User Manual IT Stage Protective Parameter 10 Operation of LCD Display If the selected protective parameter is Pro stage I the 7 Peremsingte following sub menu will come up a Peano Press V to select parameter Press gt to move cursor right Aa aeeyen and Press Y to set the appropriate value Confirm settings Max F grid 51 50Hz by Pressing ENTER Min F grid 47 50Hz Tab 10
74. s inverters battery chargers and other power supplies for distributable generation system in both grid connected and stand alone applications The power rating of Sungrow products covers from hundred watt to mega watt systems The vision of Sungrow is to help our customers acquire stable and clean power with minimum cost maximum reliability and enhanced safety Contact Information Should you have any question about this product please contact us Company Sungrow Power Supply Co Ltd Website www sungrowpower com Email info sungrow cn service sungrow cn No 2 Tianhu Rd New amp High Technology Industrial Development Address Zone Hefei P R China Zip 230088 Telephone 86 551 6532 7834 86 551 6532 7845 Fax 86 551 6532 7856 92 SUNGROW SUNGROW Green and Effective Specifications are subject to changes without advance notice
75. s SG30KTL SG30KTL M Input Side Data Max PV input power 32000W Max PV input voltage 1000V Startup voltage 300V Nominal input voltage 650V MPP voltage range 280 950V MPP voltage range for nominal power 480 800V No of MPPT s 1 2 Max number of PV strings per MPPT 10 5 Max PV input current DC1 DC2 66A 66A 33A 33A Max input current for input connector 10A Short circuit current of PV input DC1 DC2 80A 80A 40A 40A Output Side Data Nominal AC output power 30000W Max AC output apparent power 33120VA Max AC output current 48A Nominal AC voltage 3 N PE 230 400Vac AC voltage range 310 480Vac May vary as per corresponding country s grid standard Nominal grid frequency 50Hz Grid frequency range 45 55Hz May vary as per corresponding country s grid standard THD lt 3 at nominal power DC current injection lt 0 5 ln Power factor gt 0 99 default value at nominal power adj 0 9 overexcited 0 9 underexcited Protection Anti islanding protection Yes LVRT Yes DC reverse connection protection Yes SUNGROW 89 Parameters SG30KTL SG30KTL M AC short circuit protection Yes Leakage current protection Yes DC switch Integrated DC fuse Integrated Overvoltage protection Type II DIN rail surge arrester System data Max efficiency 98 3 Max European efficiency 98 0 Isolation method Transformerless Ingress protection rating
76. s Y to view multiple current fault information pages Fault Code Description Troubleshooting The grid voltage has 0002 exceeded inverter allowable upper limit 1 Check the voltage of the grid 2 If the grid voltage exceeds the permissible range of inverter protective parameters ask utility grid company for solution 3 If the grid voltage is within the permissible range contact Sungrow Service Dept 56 SUNGROW User Manual Fault Code Description 9 Troubleshooting and Maintenance Troubleshooting Inverter has checked that the instantaneous 1 This is a short term fault due to grid 0003 sample value of the grid condition Wait a moment for inverter recovery voltage exceeds the 2 If the fault still exists please contact allowable limit for some Sungrow Service Dept time 1 Check the voltage of the grid The arid Voltage has 2 If the grid voltage exceeds the permissible 0004 fallen below inverters Oe of inverter protective parameters ask allowable lower limit utility grid company for solution 3 If the grid voltage is within the permissible range contact Sungrow Service Dept 1 This is a short term fault due to grid 0005 The grid voltage is too condition Wait a moment for inverter recovery low 2 If the fault still exists please contact Sungrow Service Dept The AC output cutrent 1 The inverter will resume if the output current 0006 beed TEBE f
77. s during replacement Others NOTICE The selected country settings can be changed by qualified personnel only Unauthorized modification to country settings should be prohibited Alternation of the country settings may cause a breach of the type certificate marking WARNING All safety instructions warning labels and nameplate on the inverter body e Must be clearly visible Must not be removed covered and pasted 4 SUNGROW User Manual 1 Safety Instructions WARNING These regulations should also be followed The regulations related to the electricity fed into grid e The safety instructions related to PV arrays e The safety instructions related to other electrical device SUNGROW 2 Product Introduction 2 1 Intended Usage SG30KTL and SG30KTL M They will be referred to as inverter hereinafter unless otherwise specified which are a 3 phase string inverter without transformer are crucial unit between the PV strings and utility grid in the PV power system Inverter is dedicated to converting direct current power generated by the PV modules into alternating current which conforms to parameters of local utility grid and feeds it into the utility grid The intended usage of the inverter is illustrated in Fig 2 1 WARNING Inverter CANNOT be connected to the PV modules the positive or negative terminal of which needs to be grounded A
78. s terminal blocks Step 3 According to the position of the inverter refer to the prior section repeat step 1 2 to connect the other RS 485 cables Step 4 Pull cables outwards to confirm whether they are fastened firmly Step 5 According to the position of the inverter refer to the prior section switch ON or OFF the terminating resistor Step 6 Tighten the tread lock sealing lock Block off the vacant terminals to protect the inverter s internal from dust and moisture Step 7 If there is no other connection procedure recover and fix the front cover of the connection cabinet Step 8 Now perform RS485 communication connection as the diagram shown above Connect the other end of cable to other devices Communication terminal definition is referred to device manual Step 9 Verify the communication connection and configure the communication parameters If there is more than one inverter to communicate with a PC or a data i logger it is crucial to configure the communication parameters of each inverter See 10 12 Communication Parameters Setting SolarInfo logger and RS485 232 converter are optional parts and can be ordered from Sungrow RS232 i RS485 SUNGROW 47 6 Electrical Connection User Manual RJ45 Connection Step 1 Lead shielding Ethernet cable through communication cable gland to the configuration circuit board Step 2 Use the Ethernet crimper to crimp the cables and
79. ss Fig 2 1 Application of the inverter of the PV Power System Item Description Note Monocrystalline silicon polycrystalline silicon and i pune thin film without grounding of protection class II B Inverter SG30KTL SG30KTL M C Metering device meter cupboard with power distribution system D Utility grid TT TN C TN S TN C S If the PV system exceeds the capacity of one inverter it is possible to make a multiple connection of several inverters into the PV system with each one connected to an appropriate section of PV inputs and on the AC side they connected in parallel to the grid 6 SUNGROW User Manual NOTICE Any other or additional usage is not permitted except the intended usage 2 Product Introduction Inverter may only accept PV modules with Protection Class Il as its input Inverter may only be connected to utility grid via distribution board Local loads home appliance lights motor loads etc cannot be connected between inverter and AC circuit breaker on the distribution board Additionally the unit is intended for fixed installation Located on a part that is not removable without impairing the operation of the unit 2 2 Product Description 2 2 1 Product Appearance Yi 6 By 7 F 8 Fig 2 2 Product Components Description Item Name Description 1 LCD display Inverter operation data viewing and parameters
80. terface to a PC with monitoring software such as Solarlnfo Insight or to data logging device such as Solarlnfo Logger RS485 is the standard communication choice for inverter There are communication terminals RS485 at the bottom of the inverter And there apply two optional connection terminals on the configuration circuit board RS485 A B terminal blocks and RJ45 plug in terminals In the case of a need of terminating resistor switch on the 1200 terminating resistor switch a terminating resistor will be connected between the communication cables of the inverter Configuration circuitboard 1200 terminating resistor switch fi 1200hM ey RS485 bus RS485 RJ45 terminals terminals Fig 6 6 Communication related devices on the Configuration Circuit Board Ze Before communication connection prepare communication cable and RJ45 plug NOTICE RS485 cable s requirements to ensure quality of communication e Twist pair type cable e Twist pair type shielding Ethernet cable O A converter such as RS485 232 converter or Solarlnfo Logger which converts 485 to 232 signal is needed between inverter and PC 44 SUNGROW User Manual 6 Electrical Connection 6 6 2 Communication System For Single Inverter Where there is only one inverter a RS485 cable enables connection between inverter and data logging device Inverter Communication Connection Inverter
81. the inverter is less than 0 12uf kW 30kW otherwise the inverter will not function properly WARNING Before connecting the PV arrays to the inverter make sure that the impedances between the positive terminal of the PV string and Earth and the impedances between the negative terminal of the PV string and Earth are larger than 1Mohm 6 4 1 PV Inputs Configuration of SG30KTL All PV strings connected to the SG30KTL should have a homogenous structure including the same type the same number identical tilt and identical orientation The following electrical specifications must be met simultaneously Total DC Power Limit Open circuit Voltage Short circuit Current for the SG30KTL Limit for Each Input Limit for Total Input 32kW 1000V 66A You should also take the negative open circuit voltage temperature coefficient into consideration when designing the PV string NOTICE There is a risk of inverter damage The following requirements should be met otherwise they will lead to loss of any and all warranty rights e Make sure that the maximum short circuit current of each DC input is less than inverter allowable limit e Make sure that the maximum open voltage of each string is less than 1000V Voltage over 1000V can damage the inverter SUNGROW 35 6 Electrical Connection User Manual 6 4 2 PV Inputs Configuration of SG30KTL M The SG30KTL M inverter has two PV input areas DC1 input and DC2 input each owning its
82. trical connection in the reverse procedures in the 6 Electrical Connection 5 Lift up the inverter over the backplate with the help of others and then remove it from the wall Place the inverter onto the platform Loosen the screws as the right diagram shown 62 SUNGROW User Manual 9 Troubleshooting and Maintenance 8 9 10 11 12 13 14 15 Disassemble the metal plate slightly Release the locking part of four connectors by pressing on the ribbing of the locking hooks and pull outwards Remove fans from the inverter You can clean the dirty fans with soft brush or vacuum cleaner Or replace the broken fans Re assemble the fans onto the inverter Connect the four connectors and fasten them with cable ties Assemble the plate by fastening the four screws The inverter can be put into the application again SUNGROW 63 9 Troubleshooting and Maintenance User Manual Replacing the String Fuses For optional version inverter it is necessary to replace the blown string fuses due to overcurrent To do so proceed as follows 1 Disconnect AC circuit breaker 2 Turn off the upstream DC circuit break or cover the PV arrays with opaque materials Rotate DC switch at the side of inverter to the OFF positi
83. ttons 1 2 RUN Ox 1 2 io yo Fig 2 4 LCD Display Panel Tab 2 1 LCD Display Panel Description No Name Description 1 LED RUN and FAULT Inverter current state can be known from the indicators two indicators Detailed definition is shown in Tab 2 2 Navigate in the LCD menu set values and so on Detailed 2 B n aa ia function is shown in Tab 10 1 3 LCD LCD screen can display current state of inverter current running screen information history information and parameters to be set SUNGROW User Manual 2 Product Introduction Tab 2 2 Description of LED Indicator Status LED Status Description EAL Inverter is feeding AC power to the utility grid RUN off A malfunction happens FAULT on or protection function triggers RUN off Inverter is not energized FAULT off or there is a communication error between DSP and LCD 2 2 4 DC Switch DC switch is designed for safely disconnecting the DC input current if required The inverter works automatically when input and output meet the requirements Rotating DC switch to the OFF position will immediately cut off the flow of DC current Rotate the DC switch to the ON position before restarting the inverter SUNGROW 2 Product Introduction User Manual 2 3 Technical Description 2 3 1 Principle Description The principle design of transforme
84. uctions of AS 4777 1 WARNING Improper operation during the wiring process can cause fatal injury to the operator or unrecoverable damage to the inverter Only qualified personnel can perform the wiring work Prior to any electrical connection keep in mind that inverter has dual power supplies It is mandatory for technical personnel to wear personal protective equipment helmet footwear and gloves during the electrical work 6 1 Simplified Electrical Connection Diagram Connecting inverter to the existing PV system includes connecting inverter to local grid and connecting inverter to PV arrays There may be communication connection for monitoring inverter operation if necessary All electrical connection should follow the National Wiring Rules of Standard AS NZS 3000 Inverter Connection cabinet SUNGROW gt l Q g 5 i is gt E A lt F RS483__ To communication device Fig 6 1 Simplified Electrical Connection Diagram 28 SUNGROW User Manual 6 2 Terminals Description All electrical terminals and cable openings connection cabinet as Fig 6 2 6 Electrical Connection of the inverter are located at the r i
85. uring installation operation and maintenance of the inverter And they will be highlighted by the following symbols DANGER indicates a hazard with a high level of risk which if not avoided will result in death or serious injury A WARNING WARNING indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury CAUTION indicates a hazard with a low level of risk which if not avoided could result in minor or moderate injury NOTICE NOTICE indicates a situation which if not avoided could result in equipment or property damage NOTE indicates additional information emphasized contents or tips to help you solve problems or save time Symbols on the Inverter Body AC This symbol indicates that you should wait at least 10 minutes after disconnecting the inverter from the utility grid and from the PV input before touching any inner live parts A Hot surface In order to reduce the risk of burns do not touch the hot surface when the device is running Look over the user manual before any operation on the inverter A The installation and service of the inverter unit can only be performed by qualified personnel STOP 1 ee ety Do not disconnect DC connectors from the unit under load Contents Safety Instructions iscescsssscsvssnnscessscddaavessvcteossaccessonssecsosovedessansevel Product Introduction ccccccccccccccccccccc
86. ust COMUCASE cases coc cedcuseerealecscvinstacorecserctlidesac exude icreleen cote neneieosarans 69 10 5 Detailed RUNNING Information sss sesseessseessssesssseesssseessseresseesosseessssersssseesss 70 106 History RECOTO S sonh E A A 71 10 6 1 Running Information RecordS sessessssseeesssssesessssecsosssseesssseeeessseeresssseesssss 71 10 02 Faut RECO S aaa E A aN 71 107 Start and Stop INVeNter csc wsiucessarasteuuautcunmsienamicatione 72 10 8 Input Parameter Settings Password ss esesessssessseesssessseessseesseesnsessseeossees 72 10 9 System Parameters Setting cscscsssssesessssesesssscseasssasessssssessssssescacacecesaees 73 TOO Language Setting merene EA 73 1992 Time SERINO uaea edeee scales nears temncaeien ers 73 10 9 3 Energy Deviation AdjUStMEeNL cccccsssscssssessecsssessecssscsssssscsssesseeesseesssees 73 1094 Load DCT AUN sao sciessttes teeta iaceeet ich avin ion tiene chtiatae ancients 74 10 9 SAR IRIIWATEV CrSlOls acta ed iene E R ean lide aed 74 10 10 Running Parameters Setting essessesssesscssesseserosesseoseossessoeeoseeseroseoseeseessesse 75 10 10 1 Main Menu of Run paramM s sssseessseessssesesseesesseesosseessssceosseeesseeeesseeeosseesssserssss 75 10 10 2 Reactive Power REQulation ccscsssssssssssssesssssssecsssscssssssscassessssessssessecessees 76 10103 SAVE P O Sat erie ce ss eat teal A ie dk cee eat 78 10 11 Protective Parameters Setting ssssssssssssssssssssscace
Download Pdf Manuals
Related Search
Related Contents
DrawPlus X8 Guide d`utilisation Sistema de Administración del Servicio Social para la Salud Manual Service Manual Marine Kommunikation mit den Handmeßgeräten der GMH3000 Package - Proline XP-8000-Atom-CE6 Series User Manual TROY Group Bluetooth Print Adapter User's Manual Philips 190B5CS 19INCH TFT MONITOR COMPACT BASE Copyright © All rights reserved.