Home
IO User Manual
Contents
1. 8DIO 2 5 gt Set internal jumper O412 24Vdc or o0Vdc oo occ oooooooc0ooooooooooQo 412 24Vdc O412 24Vdc o0Vdc The following diagram shows the wiring for the power and RS485 communications Gredian 1 12veb angore 2E OINA a 4F amp Gt5 Note If power communication connections are reversed module may become faulty 3 2 5 Switch Settings SWITCH FUNCTION DESCRIPTION 1 NODEID 1 Node ID s from 0 to 127 are set up using switches 1 to 7 2 NODEID 2 3 NODEID 4 i 4 NODEID 8 5 NODEID 16 6 ID 32 7 NODE ID 64 li 8 INVERT When switched ON the status of the inputs is inverted in the Modbus status register 30002 9 MODE Off Slave 10 BAUD RATE Selects 9600 off or Programmed Baud Rate on 15 3 2 6 Jumper Settings The Digital inputs can be configured as NPN inputs This means that the inputs can be operated by switching to OV Open the IO Module Change the link LK1 to the NPN position as shown below PNP NPN x The Digital inputs can be configured as PNP inputs This means that the inputs can be operated by switching to 12V to 24V Open the IO Module Change the link LK1 to the PNP position as
2. Logic Supply Current 38mA 9 12V 19mA 24V Field Supply Voltage 12 24 Vdc Field Supply Current 6mA 12V 6mA 24V Digital Inputs Input Points 8 Input Voltage Range 12 24 Vdc Input Current per input 5mA 12Vdc 11mA 24Vdc Isolation 1500Vrms between field and logic Digital Outputs Output Points 8 Maximum Voltage 36 Vdc Maximum Current 100 mA per output Vceon 1 1V Max Isolation 1500Vrms between field and logic Counters Inputs 1to8 Resolution 32 Bits Frequency 1KHz max Pulse Width 500us min Temperature Operating Temperature 10 C to 50 C Storage Temperature 40 C to 85 C Connectors Logic Power and Comms 4 Pin Connector on underside of unit Outputs 18 Way screw connector on front Note Inputs 1 to 8 are used as both digital inputs and counter inputs 3 2 3 Status Power RS485 Rx RS485 Tx Input Status Output Status Indicators Flashes to indicate the CPU is running Flashes to indicate the unit has received a valid Modbus message Flashes to indicate the unit has sent a Modbus message OFF when the input is off ON when the input is on OFF when the output is off ON when the output is on Input Status RS485 Tx 1 8 P R T 5 16 17 18 O1 02 O3 04 Output Status O5 O6 O7 O8 1 8 8DIO 3 2 4 Wiring The following diagram shows how the digital inputs and outputs are connected P 1 15 01 05 R T 2 16 17 18 02 O3 O4 O6 O8
3. 30005 RTD Input 4 XXX X R 30006 RTD Input 5 R 30007 RTD Input 6 XXX X yyyy y R i 30008 Input Status 0 65535 R bit 0 OK bit1 1 error or open circuit 30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel 40101 RTD Type 1 7 R W See RTD Tables 40102 Line Frequency 50 60 R W Line Frequency 40103 Units Type 1 2 R W 1 2 F 40121 Baud Rate 2400 11520 R W 2400 4800 9600 19200 38400 57600 115200 40122 Parity 0 2 R W 0 none 1 even 2 odd 40123 Stop Bits 1 2 R W 1 1 stop bit 2 2 stop bits 40124 Reply Delay 0 65535 R W 0 Disable gt 0 Enable x10ms MSB 3 3 6 1 RTD Input Status There is one status bits associated with each RTD input These bits are used to indicate if the input is open circuit or over range If the input is open circuit or over range then the error bit will be set Bit 1 Error 0 1 Bit 2 Not Used 0 0 Condition Status LED Input working OK LED OFF Open circuit Over range LED ON The analog input status can be read in a single register as follows IOX 6RTD ANALOG INPUT STATUS LSB FS T u TED 32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30008 22 P1 Error IP2 Error IP3 Error IP4 Error IP5 Error IP6 Error 3 4 IOX DAIO DIGITAL ANALOG INPUTS AND OUTPUTS 3 4 1 Description The IOX DAIO module is a multipurpose combination of inputs and
4. 5 Setlirigs uiii teet bp teca ht nito Pers acer xac 21 3 3 6 IOX 6RTD Data Registers MODULE TYPE 109 22 3 4 IOX DAIO DIGITAL ANALOG INPUTS AND OUTPUTS een 23 3 4 1 IBI egi m 23 3 4 2 Technical Specification of IOX DAIO ssssssssseeeeeen nens 25 2 49 Status INGICAtONS een rt rtt dete Ede e ed Diete bas 27 3 44 catre tee tenete et s tee epe E puce tae eco tee ve en 28 3 45 Switch Settings eed adero edd atid cia rd e E 28 239 46 Jumper Settings n cie ener fae ta e eec a de EX 29 3 4 4 IOX DAIO Data Registers MODULE TYPE 112 30 4 SPECIFICATIONS Rad v sk Rada E 31 AT ENVIRONMENTAL iiber fae ete teh Leer e Hee Deren o RE 31 4 2 EMC INSTALLATION INSTRUCTIONS sesenta 31 1 AN OVERVIEW OF THE IO SYSTEM 1 1 Introduction The NetBiter I O Extender series provides a solution for distributed I O requirements The IO system consists of stand alone Digital and Analog Input Output modules which are connected together on a RS485 two wire multi drop network The modules communicate using the MODBUS RTU protocol A 32bit ARM CPU is used in the modules to provide high speed data processing and fast communications turnaround times Multiple baud rates are selectable from 2400 to 115200 baud All IO modules plug directly on
5. Counter Registers The counters are stored in two 16 bit registers The first register is the High Register and the second register is the Low Register To get the actual 32 bit count value the registers must be combined as follows Counter High Value Register 40003 Counter Low Value Register 40004 Counter Value Counter High Value X 65535 Counter Low Value 3 2 7 4 Output Watchdog Timer The watchdog timer is used to switch off all of the outputs in the event of a communications failure When set to zero register 40101 the watchdog timer is disabled 3 3 IOX 6RTD RTD INPUTS 3 3 1 Description The IOX 6RTD module is a 6 RTD input module The module can accommodate either 2 or 3 wire RTD sensors The RTD inputs are isolated from the logic The RTD resistance is read by the module circuitry linearised and converted to degrees Centigrade No ranging is required as the module covers the full range of the RTD as indicated in the RTD table The value that is read from the Modbus register is the actual temperature in degrees centigrade to 0 1 C resolution ie a value of 3451 corresponds to a temperature of 345 1 C The RTD type is setup by writing a value to the RTD Type register The value is obtained from the table below For example to select a PT100 RTD the value 1 must be written to the RTD Type register All 6 RTD inputs adopt the same RTD type The DIP switch 9 is used to select upscale or downscale burnout
6. ID 32 7 NODEID 64 8 Not used 9 Not used 10 BAUD RATE Selects 9600 off or Programmed Baud Rate on 28 3 4 6 Jumper Settings 3 4 6 1 Current Input and Output The Analog inputs can be configured as a current 0 4 20mA input by placing the jumper on J7 for Al1 and J8 for Al2 The Analog output can be configured as a current 0 4 20mA output by placing the jumpers J9 J10 and J11 on the I position as shown below 3 4 6 2 Voltage Input and Output The Analog inputs can be configured as a voltage 0 10V input by removing the jumper from J7 for Al1 and J8 for Al2 The Analog output can be configured as a voltage 0 10V output by placing the jumpers J9 J10 and J11 on the V position as shown below 29 3 4 7 IOX DAIO Data Registers MODULE TYPE 112 Modbus Register Name Low High Access Comments Address Limit Limit 10001 Digital Input 1 0 1 R Status of Digital Inputs 10002 Digital Input 2 0 1 H i 10003 Digital Input 3 0 1 R 10004 Digital Input 4 0 1 R B 00017 Digital Output 1 0 1 R W Status of Digital Outputs 00018 Digital Output 2 0 1 R W 30001 S W Version N A N A R High Byte Software Version Module Type Low Byte 112 30002 Digital Inputs N A N A R Digital Inputs in lower 8 bits 8 1 40003 Digital Outputs N A N A R W Digital Out
7. Output 2 0 1 R W 00003 Relay Output 3 0 1 R W i 00004 Relay Output 4 0 1 R W 30001 S W Version N A N A R High Byte Software Version Module Type Low Byte 113 40002 Digital Outputs N A N A R W Digital Outputs in bits 4 msb 1 Isb 30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel 40101 Watchdog Timer 0 255 R W Timer in seconds 0 disabled 1 255 enabled 40121 Baud Rate 2400 11520 R W 2400 4800 9600 19200 38400 57600 115200 40122 Parity 0 2 R W 0 1 even 2 odd 40123 Stop Bits 1 2 R W 1 1 stop bit 2 2 stop bits 40124 Reply Delay 0 65535 R W 0 Disable gt 0 Enable x10ms 3 1 6 1 Relay Output Register The relay outputs can be read written in a single register as follows MSB IOX 4RO DIGITAL OUTPUTS LSB CE esaa T 32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 40002 3 1 6 2 Output Watchdog Timer Relay Output The watchdog timer is used to switch off all of the outputs in the event of a communications failure When set to zero register 40101 the watchdog timer is disabled 3 2 IOX 8DIO DIGITAL INPUTS OUTPUTS 3 2 1 Description The IOX 8DIO module is an 8 channel digital input and 8 channel digital output module The inputs are isolated from the logic by bi directional opto couplers The common is connected internally to either the volts
8. Vdc or 0 10 Vdc Input Resistance 190kohms Input Type Range Resolution 4 0 4095 12 bits 5 0 10 000 V 1mV 6 10 000 V 1mV 7 0 1 0000 V 0 1mV 8 1 0000 V 0 1mV Drift 100ppm C Accuracy 0 2 of span Isolation 1000Vrms between field and logic Current Output Output Points 1 Output Current 0 4 20 mA Output Type Range Resolution 1 0 4095 12 bits Drift 100ppm C Accuracy 0 05 of span Compliance 1000 ohms max 24Vdc 500 ohms max 12Vdc 25 Voltage Output Output Points 1 Output Voltage 0 2 10 V Output Type Range Resolution 2 0 4095 12 bits Drift 100ppm C Accuracy 0 05 of span Compliance 2000 ohms min load Digital Inputs Input Points 4 Input Voltage Range 10 26 Vdc Input Current per input 4mA 12Vdc 8mA 24Vdc Counters Inputs 1104 Resolution 32 Bits Frequency 50 Hz max Pulse Width 20 ms min Digital Outputs Output Points 2 Maximum Voltage 36 Vdc Maximum Current 100 mA per output Vceon 1 1V Max Isolation Between field and logic 1500Vrms between field and logic Temperature Operating Temperature 10 C to 50 C Storage Temperature 40 C to 85 Connectors Logic Power and Comms 4 Pin Connector on underside of unit Inputs 18 Way screw connecior on front 26 3 4 3 Status Indicators Power ON when module has power RS485 Rx Flashes to indicate the unit has recei
9. etc This electromagnetic radiation can induce electrical noise into both power and signal lines as well as direct radiation into the module causing negative effects on the system Appropriate grounding shielding and other protective steps should be taken at the installation stage to prevent these effects These protective steps include control cabinet grounding module grounding cable shield grounding protective elements for electromagnetic switching devices correct wiring as well as consideration of cable types and their cross sections 2 3 Network Termination Transmission line effects often present a problem on data communication networks These problems include reflections and signal attenuation To eliminate the presence of reflections from the end of the cable the cable must be terminated at both ends with a resistor across the line equal to its characteristic impedance Both ends must be terminated since the direction of propagation is bi directional In the case of an RS485 twisted pair cable this termination is typically 120 ohms 2 4 Setting the Modbus Node ID 2 4 4 Node ID Table The following table assists with the setting up of DIP switches for the required NODE ID 1234567 1213415167 0 96 2 2 98 oo 4 mati 5 n 101 ELLE 6 m 9 ast 105 BALA 10 au 11 107 MILL 12 LS 108 ag
10. outputs The module can accommodate either 2 or 3 wire RTD sensors current 0 20mA and voltage 0 10V inputs current 0 20mA or voltage 0 10V output and digital inputs and outputs RTD INPUTS There are 2 RTD inputs on the module The RTD resistance is read by the module circuitry linearised and converted to degrees Centigrade No ranging is required as the module covers the full range of the RTD as indicated in the RTD table The value that is read from the Modbus register is the actual temperature in degrees centigrade to 0 1 resolution ie a value of 3451 corresponds to a temperature of 345 1 The RTD type is setup by writing a value to the RTD Type register The value is obtained from the table below For example to select a PT 100 RTD the value 1 must be written to the RTD Type register A value of 32767 is used to indicate downscale burnout Note As there is no inter channel isolation isolated RTD s must be used in order to prevent ground loops and reading errors ANALOG INPUTS The Analog Inputs 2 can be configured by internal jumpers as either a current input 0 20mA or a voltage input 0 10V An input of 0 20mA input current or 0 10V input voltage represents an output value of 0 4095 12 bits in the corresponding Modbus register ANALOG OUTPUT There is a single analog output which can be configured with internal jumpers for a current output 0 20mA or voltage output 0 10V The resol
11. shown below x NPN PNP 16 3 2 7 IOX 8DIO Data Registers MODULE TYPE 102 Modbus Register Name Low High Access Comments Address Limit Limit 10001 Digital Input 1 0 1 R Status of Digital Inputs 10002 Digital Input 2 0 1 R i 10003 Digital Input 3 0 1 R t 10004 Digital Input 4 0 1 R i 10005 Digital Input 5 0 1 R 10006 Digital Input 6 0 1 R 10007 Digital Input 7 0 1 R 10008 Digital Input 8 0 1 R i 00017 Digital Output 1 0 1 R W Status of Digital Outputs 00018 Digital Output 2 0 1 R W 00019 Digital Output 3 0 1 R W 00020 Digital Output 4 0 1 R W 00021 Digital Output 5 0 1 R W 00022 Digital Output 6 0 1 R W 00023 Digital Output 7 0 1 R W 00024 Digital Output 8 0 1 R W 30001 S W Version N A N A R High Byte Software Version Module Type Low Byte 102 30002 Digital Inputs N A N A R Digital Inputs in lower 8 bits 8 1 40003 Digital Outputs N A N A R W Digital Outputs in lower 8 bits 8 1 40004 Counter 1 MSB 0 65535 R W Counter MSB and LSB combine to give a 32 bit 40005 Counter 1 LSB 0 65535 R W Counter with range 0 to 4294967295 40006 Counter 2 MSB 0 65535 R W 40007 Counter 2 LSB 0 65535 R W i 40008 Counter 3 MSB 0 65535 R W 40009 Counter 3 LSB 0 65535 R W d 40010 Counter 4 LSB 0 65535 R W 40011 Counter 4 LSB 0 65535 R W i 40012 Counter
12. the output is off ON when the output is on Power RS485 Rx Output Status RS485 Tx P R T 1 2 3 4 M Switch 10 3 1 4 Wiring The following diagram shows how the digital outputs are connected to the coil of a relay The coil is connected to positive and switched to negative T 2 2 5 lwin 000000 0000000 Relay 2 Normally Open Relay 2 Normally Closed Relay 3 Normally Open Relay 1 Common Relay 1 Normally Open Relay 1 Normally Closed Relay 2 Common 24V dc 220Vac RELAY R Common o0Vdc 220Vac Relay 3 Normally Closed Relay 4 Common Relay 4 Normally Open Relay 4 Normally Closed Note If power communication connections are reversed module may become faulty 3 1 5 Switch Setting SWITCH FUNCTION DESCRIPTION 1 NODEID i Node ID s from to 127 are set up using switches 1 to 7 2 NODEID 2 3 NODE ID 4 4 8 5 __ 16 6 NODEID 32 7 NODEID 64 8 Not Used 9 MODE Slave Off 10 BAUD RATE Selects 9600 off or Programmed Baud Rate on 3 1 6 IOX 4RO Data Registers MODULE TYPE 113 Modbus Register Name Low High Access Comments Address Limit Limit 00001 Relay Output 1 0 1 R W Status of Digital Outputs 00002 Relay
13. 11520 R W 2400 4800 9600 19200 38400 57600 11520 40122 Parity 0 2 R W 0 none 1 even 2 odd 40123 Stop Bits 1 2 1 1 stop bit 2 2 stop bits 40124 Reply Delay 0 65535 R W x10ms The baud rate value is programmed directly into the baud rate register The only exception is the 115200 baud rate where the value 11520 is used The reply delay is a time delay between the Modbus message received to the reply being sent In some applications where a modem or radio is used in the RS485 network it may be necessary to add a reply delay due to turn around delays in the equipment Reply Delay Bx Reauest Time x10ms 2 5 4 Modbus Register Types There are 4 types of variables which can be accessed from the module Each module has one or more of these data variables Type Start Address Variable Access 1 00001 Digital Outputs Read amp Write 2 10001 Digital Inputs Read Only 3 30001 Input registers Analog Read Only 4 40001 Output registers Analog Read amp Write Holding type Note The Modbus message length must be limited to 100 consecutive read or write registers If more registers are required then a new poll group must be added for the next xxx registers 3 MODULES 3 1 IOX 4RO RELAY OUTPUTS 3 1 1 Description The IOX A4RO module has 4 normally open normally closed relay outputs These modules may be used when a higher drive capabi
14. 13 ML M 109 ML NN m 14 15 Mis 111 MANN 16 mmt 112 888 17 18 MELLE 114 LE 19 MN an 115 ALL m 20 116 21 MM 22 118 EL 24 itn 120 25 NN 26 ELEM 122 uL 27 m 123 MIL m 28 mg 124 29 My 125 ML ME 3o Qm 126 _ 31 127 All modules will respond to a default Node ID of 254 2 4 2 DIP Switch Status Register Each module uses register 30100 to store the status of the DIP switches MSB DIP SWITCH REGISTER LSB D Ds Pe LTTSTETETSTETTIS ee 32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30100 D SW 1 SW2 SW SW 4 SW 5 SW 6 SW 7 SW 8 SW 9 SW 10 2 5 Communications Settings The data in the modules is stored in 16 bit registers These registers are accessed over the network using the MODBUS RTU communication protocol 2 5 1 Communications Settings with DIP Switch 10 OFF Default BAUD RATE 9600 DATA BITS 8 PARITY NONE STOP BITS 1 2 5 2 Communications Settings with DIP Switch 10 ON Programmed Baud Rate BAUD RATE 2400 4800 9600 19200 38400 57600 115200 DATA BITS 8 PARITY None Even Odd STOP BITS 1 2 Note These settings are changed from a Modbus Master device During these changes DIP switch10 should be OFF such that the Master device can communicate with IO module on default communication settings 2 5 3 Communications Settings Registers 40121 Baud Rate 2400
15. 5 MSB 0 65535 R W i 40013 Counter 5 LSB 0 65535 R W 40014 Counter 6 MSB 0 65535 R W d 40015 Counter 6 LSB 0 65535 R W 40016 Counter 7 MSB 0 65535 R W 40017 Counter 7 LSB 0 65535 R W 40018 Counter 8 MSB 0 65535 R W 40019 Counter 8 LSB 0 65535 R W 30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel 40101 Watchdog Timer 0 255 R W Timer in seconds 0 disabled 1 255 enabled 40105 Counter Mode 0 2 R W 0 Disable 1 Up Counting 2 Up Down Count 40106 Input Filter 0 65535 R W 0 Disable gt 0 Enable x10ms 40121 Baud Rate 2400 11520 R W 2400 4800 9600 19200 38400 57600 115200 40122 Parity 0 2 R W 0 1 even 2 odd 40123 Stop Bits 1 2 R W 1 1 stop bit 2 2 stop bits 40124 Reply Delay 0 65535 R W 0 Disable gt 0 Enable x10ms 3 2 7 1 Digital Input Register The digital inputs can be read in a single register as follows MSB IOX 8DIO DIGITAL INPUTS LSB E T H T TET Dus De Jo 32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30002 0 0 0 0 0 0 0 8 7 6 5 4 3 2 1 Digital Input Number 3 2 7 2 Digital Output Register The digital outputs can be read written in a single register as follows MSB IOX 8DIO DIGITAL OUTPUTS LSB DW pepe 32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 40003 0 oOo 0 0 0 0 0 7 6 5 4 3 2 1 Digital Output Number 3 2 7 3
16. NetBiter I O Extender 4RO 6RTD 8DIO DAIO User Manual Revision 1 00 IntelliCom Innovation AB Phone 46 35 1821 70 INTELLICOM Linjegatan 3D Fax 44635 18 2199 innovation SE 302 50 Halmstad email infoGintellicom se SWEDEN www www ntellicom se 1 OVERVIEW OF THE IO SYSTEM eene 3 Tel INTRODUCTION eterne tes etus e erf eee ee 3 1 2 DATAACQUISITION i ct ee dede tee haee Y epe e eee a ERR E dee nits tae ede cov ru ge cda 3 1 9 MODULE SELECTION TABLE ninu iirin lee eL acere dg 3 2 IO GENERAL INFORMATION ecce ecce esee 4 2 1 PHYSICAE DIMENSIONS Leda Eee EE Reed ee HERD ead ee papas 4 2 2 GROUNDING SHIELDING eese nennen nnne enne nein rennen ense nr 4 2 9 NETWORK TERMINATION 52 deed Eee e eere dee ER let rrr Das 4 2 4 SETTING THE MODBUS NODE ID sse nennen nennen enn nnne nnns 5 2 4 1 Node ID Table sce tabe aet beer 5 2 4 2 DIP Switch Status Register sssssssssssssseeseneeeeneen enne 6 2 5 COMMUNICATIONS SETTINGS s ipee erint ER ap ERES ES 7 2 5 1 Communications Settings with DIP Switch 10 OFF Default 7 2 5 2 Communications Settings with DIP Switch 10 ON Programmed Baud Rate 7 2 5 8 Co
17. cuit OFF when the RTD is connected RS485 Rx RS485 Tx Switch 10 Input Status 1 6 Switch 1 20 3 3 4 Wiring The following diagram shows how the inputs are connected to a 2 and 3 wire RTD 1 RTD 3 Wire RTD Input 4c 2 Wire Note If power communication connections are reversed module may become faulty 3 3 5 Switch Settings SWITCH FUNCTION DESCRIPTION 1 NODEID 1 Node ID s from 0 to 127 are set up using switches 1 to 7 2 NODEID 2 ij 3 NODEID 4 4 NODEID 8 i 5 NODE ID 16 6 ID 32 7 NODEID 64 8 Not used 9 BREAK RTD break When switched off the RTD value will loaded with 32767 when the RTD is faulty When switched on the RTD value will be loaded with 32768 10 BAUD RATE Selects 9600 off or Programmed Baud Rate on 21 3 3 6 IOX 6RTD Data Registers MODULE TYPE 109 Modbus Register Name Low High Access Description Address Limit Limit 30001 S W Version N A N A R High Byte Software Version Module Type Low Byte 109 30002 RTD Input 1 XXX X R RTD Inputs See table for range 30003 RTD Input 2 XXX X yyyy y H Resolution in 0 1 30004 RTD Input 3 XXX X R l
18. for break detection A value of 32768 is used to indicate upscale burnout and a value of 32767 is used to indicate downscale burnout Note As there is no inter channel isolation isolated RTD s must be used in order to prevent ground loops and reading errors 3 3 2 Technical Specification of IOX 6RTD Power Supply Logic Supply Voltage 12 24 Vdc Logic Supply Current 87mA 12V 45mA 24V RTD Inputs Input Points 6 RTD Configuration 2 or 3 Wire Resolution 0 1 C Drift 100ppm C Typ Line resistance effect lt 0 1 C balanced Max line resistance 100ohms Isolation 1500Vrms between field and logic RTD Type Number Type Range Accuracy 1 PT100 200 to 850 C 0 3 C IEC 751 1983 2 Ni120 80 to 320 0 3 C 3 PT1000 200 to 850 C 0 3 C 4 Ni1000 DIN 200to 850 C 0 3 C 5 Ni1000 200 to 850 C 0 3 C Landys amp Gyr 6 Ohms 10 400 ohms 0 0596 7 Ohms 100 40000hms 0 05 Temperature Operating Temperature 10 C to 50 C Storage Temperature 40 C to 85 Connectors Logic Power and Comms 4 Pin Connector on underside of unit Inputs 18 Way screw connector on front 3 3 3 Status Indicators Power Flashes to indicate the CPU is running RS485 Rx Flashes to indicate the unit has received a valid Modbus message RS485 Tx Flashes to indicate the unit has sent a Modbus message Input Status when the RTD is open cir
19. le x10ms 30 4 SPECIFICATIONS 4 1 ENVIRONMENTAL Operating Temperature 10 C to 50 C Storage Temperature 40 C to 85 C Humidity Up to 95 non condensing 4 2 EMC INSTALLATION INSTRUCTIONS 1 Screened twisted pair RS485 cable must be used with the screen grounded at one point only 2 The RS485 cable must be terminated at both ends using a 120ohm resistor 3 Use should be made of screened I O T C RTD cable with the screens grounded at one point as close to the IO module as possible 31
20. lity is required or when isolation between outputs are required When switch 9 is off the module is configured as a slave module for the Modbus master device such as a PC PLC HMI When used as a slave module the outputs are written to by the Modbus master device such as a PC PLC HMI Each output can be individually switched on or off or all outputs can be set up at the same time by writing a single number to the output register which represents the status of all outputs An output watchdog timer can be configured to switch off all the outputs if there has been no communications with the module for up to 255 seconds A value of 0 seconds will disable this timer and the outputs will remain in the last programmed state 3 1 2 Technical Specification of IOX ARO Power Supply Logic Supply Voltage 24 Vdc Logic Supply Current 42 mA Relay Outputs Output Points 4 Maximum Current 0 5A 220VAC 1A 28VDC Isolation 1000Vrms between field and logic 1000Vrms between outputs Temperature Operating Temperature 10 C to 50 C Storage Temperature 40 C to 85 C Connectors Logic Power and Comms 4 Pin Connector on underside of unit Outputs 18 Way screw connector on front 3 1 3 Status Indicators Power Flashes to indicate the CPU is running RS485 Rx Flashes to indicate the unit has received a valid Modbus message RS485 Tx Flashes to indicate the unit has sent a Modbus message Output Status OFF when
21. mmunications Settings Registers sse 7 2 5 4 Modbus Register Types ie Eee ene e ev pP Eee lanes 8 3 TO MODULES 9 3 1 IOX 4RO RELAY OUTPUTS Saini naa iaa entan eaaa entente rris nennen ns 9 3 1 1 Description coire Donde edite eR Core ren eme HER Ceo uas 9 3 1 2 Technical Specification of 1 4 9 3133 Status Indicators avis ceri Eee I e P Uer ia apes 10 334 eie ien eter OD eMe Dec an deae 11 24 5 SWITCH Setting ier REDE E CR i bu DRE 11 3 1 6 IOX 4RO Data Registers MODULE TYPE 113 12 3 2 IOX 8DIO DIGITAL INPUTS OUTPUTS sees 13 3 2 1 IBI ege RC 13 3 2 2 Technical Specification of IOX DIO sssssssseseeeeeen nnns 14 3 2 3 Status IndiCators Ri n pet e pi tette erdt 14 E MEE II T EH 15 3 2 b _ SSwitCh dip esee pet RE etae 15 3 267 Jumper Setting Ske ee eedem es 16 3 2 7 IOX 8DIO Data Registers MODULE TYPE 102 17 3 3 IOX 6RTD RTD INPUTS 19 3 3 1 DOSSCIiPtlON CL 19 3 3 2 Technical Specification of 1 6 19 23 3 Status Indicators s eo tei tirar 20 3 9 4 us eei reet Pee PETERE I p ertet 21 23 9
22. mp Ohms NetBiter I O Extender DAIO 2 RTD I P 2 ANALOG INPUT 0 4 20mA 0 2 10V 1 ANALOG OUTPUT 0 4 20mA 0 2 10V 4 DIGITAL INPUTS 2 DIGITAL OUTPUTS 2 lO GENERAL INFORMATION 2 1 Physical Dimensions The IO enclosure is shown below The module clips directly onto an industry standard DIN rail Field wiring is on the front of the module via a separate plug in connector The module power and RS485 communications wiring is on a separate plug in connector on the bottom side of the housing Allow at least 2bmm on front and below the module to accommodate the wiring Ensure that enough space is available above and below the module for good ventilation 97 5 86 5 1 225 Ll DICER xtender DAIO 109 0 99 5 2 5 555555 amp amp 8 DODDI 2 2 Grounding Shielding In most cases IO modules will be installed an enclosure along with other devices which generate electromagnetic radiation Examples of these devices are relays and contactors transformers motor controllers
23. or volts field power supply terminals using a jumper link which is situated inside the housing The inputs have internal counters associated with them These counters are 32 bit counters allowing a count value from 0 to 4294967295 The count value can be cleared by writing a zero to the associated registers or preset to any other value using the same method The counters can also be reset automatically when read This is done by setting on DIP switch 9 on the front panel Note The count values are not battery backed up and will be lost if power is turned off The format of the registers allows the status of the inputs to be read as either single bits or all at once as a single register on the Modbus network The 8 digital outputs are open collector NPN The outputs may be used to drive lamps or external relays when more drive capability is required The outputs are isolated from the logic and they share a common negative terminal The module may be configured as slave where PC PLC HMI acting as master on the Modbus network Dip switch 9 should be switched off to make this module as slave Each output on the module can be individually switched on or off or all outputs can be set up at the same time by writing a single number to the output register which represents the status of all outputs 3 2 2 Technical Specification of IOX DIO Power Supply Logic Supply Voltage 12 24
24. puts in lower 8 bits 8 1 40004 RTD Input 1 XXX X R RTD Inputs See table for range 40005 RTD Input 2 XXX X R Resolution in 0 1 C 40006 Analog Input 1 0 4095 R Analog Input lower 12 Bits 40007 Analog Input 2 0 4095 R Analog Input lower 12 Bits 40008 Analog Output 1 0 4095 R W Analog Output lower 12 Bits 40009 Counter 1 MSB 0 65535 R W Counter MSB and LSB combine to give a 32 bit 40010 Counter 1 LSB 0 65535 R W Counter with range 0 to 4294967295 40011 Counter 2 MSB 0 65535 R W 40012 Counter 2 LSB 0 65535 R W 40013 Counter 3 MSB 0 65535 R W 40014 Counter 3 LSB 0 65535 R W 40015 Counter 4 MSB 0 65535 R W 40016 Counter 4 LSB 0 65535 R W 30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel 40101 Watchdog Timer 0 255 R W Timer in seconds 0 disabled 1 255 enabled 40102 Counter Mode 0 2 R W 0 Disable 1 Up Counting 2 Up Down Count 40103 Input Filter 0 65535 R W 0 Disable gt 0 Enable x10ms 40104 RTD 1 Type 1 7 R W See RTD Tables 40105 RTD 2 Type 1 7 R W See RTD Tables 40106 1 Type 1 2 R W 120 20mA 2 0 10V 40107 Al 2 Type 1 2 R W i 40108 AO Type 1 2 R W 40109 Line Frequency 50 60 R W Line Frequency 40110 Units Type 1 2 R W 1 2 F 40121 Baud Rate 2400 11520 R W 2400 4800 9600 19200 38400 57600 115200 40122 Parity 0 2 R W 0 none 1 even 2 odd 40123 Stop Bits 1 2 R W 1 1 stop bit 2 2 stop bits 40124 Reply Delay 0 65535 R W 0 Disable gt 0 Enab
25. to an industry standard DIN rail All modules have a minimum isolation of 1000VAC rms between the field and logic The modules have been equipped with status led s which are used to indicate the status of the Inputs or outputs This visual indication assists with fault finding and diagnostics 1 2 Data Acquisition The primary use of the NetBiter I O Extender Modules is for Data Acquisition together with a NetBiter WebSCADA The NetBiter WebSCADA is a MODBUS Master and can retrieve and send data from NetBiter I O Extender Modules NetBiter webSCADA RS485 Network 120 Ohm Termiration Modbus sow low i Master 99 __ Requests Dro Modbus Slaves 1 3 Module Selection Table MODEL MODULE TYPE NetBiter I O Extender 4RO 4 RELAY OUTPUT MODULE NetBiter I O Extender 8DIO 8 DIGITAL INPUT 8 DIGITAL OUTPUT MODULE NetBiter I O Extender 6RTD 6 RTD INPUT MODULE PT100 Ni120 PT1000 Ni1000 Ni1000LG a
26. ution is 12 bits so writing a value to the Modbus register for each output of 0 4095 would give an output current of 0 20mA A value of 819 1LSB will give a current output of 4mA 23 DIGITAL INPUTS There are 4 digital inputs on the module The inputs share a common terminal and can be configured for common positive or common negative The inputs have got counters associated with them The counters operate in three modes In mode 0 all the counters are disabled In mode 1 all counters are 32 bit counters allowing a count value from 0 to 4294967295 The count value can be cleared by writing a zero to the associated registers or preset to any other value using the same method In mode 2 the inputs are connected as up down counters Input 1 will increment counter 1 while input 2 decrements counter1 Note The count values are not battery backed up and will be lost if power is turned off The format of the registers allows the status of the inputs to be read as either single bits or all at once as a single register on the Modbus network DIGITAL OUTPUTS The module has 2 open collector NPN digital outputs The outputs may be used to drive lamps or external relays when more drive capability is required The outputs are written to by the Modbus master device such as a PC PLC HMI Each output can be individually switched on or off or all outputs can be set up at the same time by writing a single number to the output register
27. ved a valid Modbus message RS485 Tx Flashes to indicate the unit has sent a Modbus message Please note that LED status is not available for Digital and Analog IO s in IOX DAIO Module Power Rx Rx RS485 Tx Tx Switch 1 Switch 10 27 3 4 4 Wiring The following diagram shows how the inputs and outputs are connected to the DAIO module 424Vdc 1 RTD Input 1a 1 2 91 RTD Input 1b RTD Input 2a RID Two Wire Transmitter 3 Qu 3 Wire 4 NT RTD Input 2c 0 4 20mA 5 91 Common 0V 6 Analog Input 1 91 Analog Input 2 T Qu Analog Output 1 8 9 Common 0V 9 0 10 Digital Input 1 s E ie Digital Input 2 24Vde j 12 0 Digi Input o eaVde OVde o Analog Load 0 20mA 13 S Digital Input 4 OVdc 24Vdc o or 14 5 n Bigital Input Common RELAY od 1 Digital Output 1 5 Sir 16 S Digital Output 2 leer OVdc V 4 Go E a o 24Vdc m 18 Gn o0Vdc The following diagram shows the wiring for the power and RS485 communications Note If power communication 3 4 5 Switch Settings connections are reversed module may become faulty SWITCH FUNCTION DESCRIPTION 1 NODEID 1 Node ID s from 0 to 127 are set up using switches 1 to 7 2 NODEID 2 i 3 NODEID 4 4 NODEID 8 5 NODEID 16 i 6 NODE
28. which represents the status of all outputs An output watchdog timer can be configured to switch off all the outputs if there has been no communications with the module for up to 255 seconds A value of 0 seconds will disable this timer and the outputs will remain in the last programmed state 24 3 4 2 Technical Specification of IOX DAIO Power Supply Logic Supply Voltage 12 24 Vdc Logic Supply Current 115mA 12V 58mA 24V Field Supply Voltage 24 Vdc Field Supply Current 25mA RTD Inputs Input Points 2 RTD Configuration 2 or 3 Wire Resolution 0 1 C Drift 100ppm C Typ Line resistance effect lt 0 1 C balanced Max line resistance 100ohms Isolation 1500Vrms between field and logic RTD Type Number Type Range Accuracy 1 PT100 200 to 850 C 0 3 CIEC 751 1983 2 Ni120 80 to 320 C 0 3 C 3 PT1000 200 to 850 C 0 3 C 4 Ni1000 DIN 200 to 850 C 0 3 C 5 Ni1000 200 to 850 C 0 3 C Landys amp Gyr 6 Ohms 10 400 ohms 0 05 7 Ohms 100 4000o0hms 0 05 Current Inputs Input Points 2 Input Current 0 4 20 mA Input Resistance 250ohms Input Type Range Resolution 1 0 4095 12 bits 2 0 20 000mA 1uA 3 20 000 1uA Drift 100ppm C Accuracy 0 296 of span Isolation 1000Vrms between field and logic Voltage Inputs Input Points 2 Input Voltage 0 1
Download Pdf Manuals
Related Search
Related Contents
UMR ADEF Théorie Anthropologique du - Yves Chevallard Tout le monde peut sauver une vie ! Étiquette air operated grease pump 65:1 tryckluftsdriven SmaRT 18 Button Manual Kodak 82-184-00170 User's Manual Copyright © All rights reserved.
Failed to retrieve file