1. Enable DHCP Change the way to get IP address for PDU SD nat ATS Status ATS A Active ATS B Standby Information IP Address Host Name ServerLink rElaN IP Address 192 168 0 37 Power ee ee ee SE Subnet Mask 255 255 255 0 Configuration ateway 192 163 0 254 ATS ba Enable DHCP Threshold DONS Server IP User Primary ONS IP 192 168 0 254 Network Secondary ONS IP Marl SNMP ATS User Manual Ver 1 0 Configuration Mail When event occurs PDU can send out email message to pre defined account Email Server The Email Server only support to be input domain name not IP address Sender s Email Input the sender email address Email Address Input the recipient email address The message in the email Indicate OutletA H XXXXXXXX status in order X 0 means the power off X 1 means the power on Note Make sure DNS server can resolve the Email Server s domain name J 4a ATS Status ATS A Active ATS B Standby Information Email Setting ATS E Email Server mail vour Com System Power Sender s Email sender yourcom com Configuration Recipient s Email Address ges Email Address o Threshold User Network Mail SNMP SSL ATS User Manual Ver 1 0 17 Configuration SNMP When event occurs PDU can send out trap message to pre defined IP address Trap Notification Set receiver IP for trap Community Set SNMP community Read Community is public and
2. Air Flow Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised C Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading D Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on over current protection and supply wiring Appropriate consideration of equipment nameplate ratings should be used when addressing this concern E Reliable Earthing Reliable earthing of rack mounted equipment should be maintained Particular attention should be given to supply connections other than direct connections to the branch circuit e g use of power strips Diagram ee PDU Install In the Rack PDU Install In the Rack e PDU Install In the Rack Remote Monitor The multiple PDU power PDU Install In the Rack O Local Monitor a PDU Install In the Rack lt PDU Install In the Rack ATS User Manual Ver 1 0 Hardware 1 Install mounting brackets 2 The ATS comes with brackets for mounting in a rack To mount the ATS into a rack performs the following procedure 3 Attach the mounting brackets to the unit using the four retaining screws provided for each of the brackets 4 Choose a location for the b
3. Input Input A Current Voltage Frequency Power Factor Active Power Apparent Power Main Energy Accumulating Energy Carbon Emission Data Co2 Electricity Emission Rate Standby OA 112 27 W 59 98 Hz 1 OW 0 VA 57472 559 kWh 0 kWh 0 000 Kg 12 Configuration ATS ATS Selection Manually select one of inputs as the primary power source Input Identification Rename input power identification 2a ATS Status ATS A Active ATS B Standby Information ATS Selection ALS Primary Input A System Ip Power Configuration Apply ATS Threshold Input Identification User Input A Input B Mail SNMP SSL ATS User Manual Ver 1 0 13 Configuration Threshold Set the warning and overload threshold for each circuit Set lower and upper threshold for temperature and humidity ia ATS Status ATS A Active ATS B Standby en Sein Threshold Amp ATS Warning Overload system Output 10 16 Power Lower Upper Configuration ATS Temperature Threshold Humidity Network al z Lf Es Kl Of Fi ATS User Manual Ver 1 0 14 Configuration User Change ID and password Default ID is snmp and password is 1234 aa ATS Status ATS A Active ATS B Standby Information Original ATS System Configuration New ATS Threshold User Password sd Network ATS User Manual Ver 1 0 15 Configuration Network PDU network information
4. and the current is lower than the threshold to 0 5 amps Press and hold the key after 1 beeping it can let the meter to show up the current information and temperature humidity in sequence Press and hold the key after 2 beeping it can let the meter to show up the IP address Press and hold the key after A beeping it can change the way to get IP by DHCP or Fixed IP Press and hold the key after 6 beeping it can reset PDU back to default setting 3 digits to display current and IP Address Information indication SSL yellow Light on means that web access Is protected by SSL DHCP green Light on means that PDU gets IP address through DHCP Input green Indicate input power status Output green Indicate which input power source is active to provide output power ENV RJ 11 for option probe attached to detect temperature and humidity Circuit Breaker Overload power protection Only 30 Amp above is available ATS User Manual Ver 1 0 4 Installation This section will provide a quick instruction to install the PDU Rack Mount Instructions A Elevated Operating Ambient If installed in a closed or multi unit rack assembly the operating ambient temperature of the rack environment may be greater than room ambient Therefore consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature specified by the manufacturer B Reduced
5. fixed Default Write Community is public and can be modified by user g ATS Status ATS A Active ATS B Standby Information ATS System Power Apply Trap Notification Receiver IP 192 168 0 1 Configuration Community ATS Read public Threshold Write User Network Mail SNMP SSL ATS User Manual Ver 1 0 18 Configuration SSL Enable SSL for web communication User must input the correct ID and password to enable SSL function The ID and password must be the same with the setting in User Change port User can change network port number for web access az ATS Status ATS A Active ATS B Standby Information Enable SSL E ATS System Der Confirmation Configuration ID o ATS Threshold User Network ATS User Manual Ver 1 0 19
6. limit for the ATS in your system See the Earth Leakage Current section later in this document for limits Earth Leakage Current To reduce the risk of electrical shock due to high leakage current a reliable grounded earth connection is essential before connecting ATS to AC power Observe the following limits when connecting the product to AC power distribution devices For products that have attached AC power cords directly connected to the building power the total combined leakage current should not exceed 5 percent of the rated input current for the device For products that have detachable AC power cords the total combined leakage current should not exceed 3 5mA ATS User Manual Ver 1 0 2 ATS Package The standard ATS package contains ATS Rack mount Brackets CD ROM it contains User Manual H Monitoring Software MIB Management Information Base for Network m Adobe Acrobat Reader ATS User Manual Ver 1 0 Interface n ET f a ane Se ATS series interface Functions Description Ethernet RJ 45 port for network communication port Audible Alarm Warning 1 beeps in 1 second Function Button Meter ID LED Indicator ATS User Manual Ver 1 0 Overload 3 beeps in 1 second Note The audible alarm will keep beeping until the current gets back to normal
7. SERVERUINK ATS Automatic Transfer Switch User Manual Table of Contents 1 Introduction 2 ATS Package 3 Function 4 Installation 5 Configuration 6 Web Interface 1 Introduction The ServerLink Automatic Transfer Switch ATS is a Single Phase Dual Input Power Distribution Unit PDU When Input A falls below normal voltage and Input B is valid the output is automatically transferred to Input B The output is transferred back to Input A when Input A is valid and rises above normal This high speed transfer rate ensures that the transfer is transparent to the sensitive equipment The two sources are not required to be in the same phase This is an effective solution that builds in redundancy and increases the AC power availability of connected equipment If the dual input power is fed through two independent AC sources then the system availability is increased and the dual input advantages are fully used The ATS is an Internet ready device designed and is equipped with an intelligent current meter True RMS that will indicate the total power consumption of ATS The ATS offers an easy set up and user friendly communication software This software provides the function that assistant manager to remotely monitor the multiple PDU power consumption Features Dual input powers provide automatically redundant power protection Built in web server manager can real time to monitoring the curr
8. ate the status of ATS input power Status Description Active Standby Backup power source n a No power input or power is out of range Indicate the temperature and humidity ia ATS Status ATS A Active ATS B Standby Information ATS Status ATS ATS A Active System ATS B Standby Power Configuration Option Device BIS Temperature 16 6 C Threshold Humidity 64 User Network Mail SNMP SA ATS User Manual Ver 1 0 10 Information System Indicate ATS system information including Model No Firmware Version MAC Address System Name System Contact Location 4a ATS Status ATS A Active ATS B Standby Information Model No ATS 15204 08N1 ATS Firmware Version s34 82 100450 ats System MAC Address 00 16 18 77 08 38 Power System Name Configuration sees Caan ieee Threshold Location User Network Mail SNMP SSL ATS User Manual Ver 1 0 Ll Information Power Provide ATS power information including Voltage Frequency Power Factor Active Power Apparent Power and Main Energy Accumulated Energy Subtotal for energy User can reset to 0 and restart calculating Carbon Emission Data Reference data CO2 Electricity Emission Rate Users can check this parameter through their power plant Status ATS A Active ATS B Information ATS System Power Configuration ATS Threshold User Network 7 i LI Es Kl LI LI ATS User Manual Ver 1 0 BR ATS
9. ent consumption of the ATS Built in true RMS current meter Setup easily meter can read the IP address directly Security web access by SSL Provide voltage frequency power factor active power apparent power and kWh information through web interface and SNMP Provide audible alarm when the power consumption over the threshold of warning and overload Send the email and traps when the power consumption exceed the trigger value of warning or overload to the PDU Provide utility it can monitor a large mount of PDU at the same time Support the SNMP and provide MIB for ATS Indicate input and output status with LED Support to monitor temperature and humidity Need to purchase option accessory WARNING There is a risk of personal injury from electrical shock and hazardous energy levels The installation of options and routine maintenance and service of the product must be performed by individuals who are knowledgeable about the procedures ATS User Manual Ver 1 0 precautions and hazards associated with AC power products trained service technician To reduce the risk of electrical shock and or equipment damage when installing or servicing the ATS e The ATS must be disconnected from the product and unplugged from the AC electrical outlet before servicing or repairing product e Do not overload the output of the ATS The total connected load should not exceed rated input power e Do not exceed the leakage current
10. rackets 5 Align the mounting holes of brackets with the notched hole on the vertical rail and attach with the retaining screws D Connect input and output power 7 Connect Ethernet cable to the ATS H Switch on the ATS Note The default setting for the way to get IP address is DHCP If ATS can not get the IP from DHCP server its IP address will stay at 192 168 0 216 ATS User Manual Ver 1 0 5 Configuration The ATS can be configured to fit several power distribution requirements Two supported configurations for Redundant Switch are shown below Minimum acceptable configuration Redundant Switch with two UPS units connected to the same facility power source Power Plant Y Remote Administrator O Best configuration Redundant Switch with two Smart UPS units connected to two separate AC lines each UPS receiving power from a separate facility power source Power Sou Remote Administrator ATS User Manual Ver 1 0 6 Web I nterface Login Input the ATS IP address in web browser Default ID is snmp Password is 1234 Connect to 1927 168 0 59 The server 192 168 0 59 at Protected requires a username and password Warning This server is requesting that your username and password be sentin an insecure manner basic authentication without a secure connection User name Password Remember my password ATS User Manual Ver 1 0 Information ATS Indic