1. e Press lt 4 in this menu to enter the Pass Code Press x to put the system into Sleep 18 Menu Layout User Menu Descriptions Controller parameters System Controller System Controller Software Version Power Mode Hi A or Lo A Status Fire Delay Fire Threshold Received Signal Compensation Level Percentage Detector parameters Detector Status Temperature Distance Fault Delay Info Detector Software 8 50m or 50 100m Version Centigrade or Fahrenheit 19 Menu Layout Engineering Menu tp D si a a ADe Oue OD ehbguke Home Position Detector Settings LASER Targeting Beam Alignment Fire Threshold Controller Settings Software Utilities Fire Test Fire Fault Delay tr Ei ef d e 4D h0G6 k uf Deeoeae che fD amp holQue Ae GHGS The Pass Code must be entered to access the Engineering Menu e The menu is navigated by using lt gt keys to move the cursor Items are selected by using 74 e Pressing 3 exits this menu and returns the system to a locked state 20 Menu Layout Detector Settings Default is Non Latched BSS E a 7 fe e en mae Auto Optimise Motor Movement On Off Set Distance Set Fire Latch Reset Set Dete
2. 0 3 Deg Range 1 to 255 Indicates the level of amplification Receive Gain applied by the receiver Set automatically by Auto Align Operating Voltage Operating Current Low Power Mode 52 mA Power Mode LOA D 0 Operating Current High Power Mode Fire Threshold Range Delay to Fire Delay to Fault Operating Distance between Detector and Reflector Maximum angular misalignment of Detector Maximum angular misalignment of Reflector 5 Deg 2999 Fire Threshold Range 10 to 60 Sets the amount of obscuration 850 nm required for the Detector to signal a Fire Maximum angular movement of Detector head o Optical wavelength 35 Rapid obscuration Fault threshold 87 Range 2s to 30s Sets the time the system needs to Delay to Fire i 0 37 8 Deg C be below the Fire threshold before signalling a Fire Range 2s to 30s Sets the time the system needs to 10 55 Deg C be below the Fault threshold before a Fault is Delay to Fault i 40 85 Deg C signalled Note the signal needs to fall to lt 13 within 2s 8 50m or 50 100m Sets the distance between IP54 Distance Detector and Reflector Affects the initial transmit 8 50m 30V DC power at the start of Auto Align 100 mA Auto Optimise Disables or enables Auto Optimise the automatic On 100 On Off beam movement function m Latched non Sets if the system will latch Fire or automatically reset Non 24 14 AWG latched Faults are always non latching latching
3. English IMPORTANT PLEASE NOTE The infrared beam path MUST be kept clear of obstructions at all times Failure to comply may result in the Detector initiating a Fire or Fault signal Oo ON 12 13 14 15 16 17 18 20 21 22 23 24 Installation General Information Fitting the Product Wiring Diagrams Commissioning Apply Power and Enter Pass Code Select Power Mode and Distance LASER Targeting Auto Alignment and Set 0 100 Calibrate In Use Settings and Final Tests Cleaning Manual Fire and Fault Tests Troubleshooting Error Codes LASER Not Visible Home Position System Information LCD Icon Layout Status Indicators User Menu Layout Engineering Menu Layout Detector Settings Menu Layout System Controller Settings Menu Layout Operating Parameters and Dimensions Approvals and Territory Specific Information Installation General Information 50 100m x4 18 50m x1 50cm 8 18m x1 ia Di 8 100m 7 Use Short Range Mask Ensure clear line of sight Mount on solid surfaces structural wall or girder from Detector to Reflector Check the beam spacing against local regulations Position beam as high as possible but with a minimum ve distance of 0 5m from detector to ceiling Mount Detector and Reflector directly opposite each other Do NOT position detector where personnel or objects can enter the beam path f x Installation Fitting t
4. 0 5 1 5 mm Operating Temperature UL Approved Operating Temperature EN54 12 Approved Storage temperature Relative Humidity non condensing 93 IP Rating Relay Contact Voltage Relay Contact Current Maximum Cable Length Controller to Detector O O N n D O O J Q ok N n Cable Gauge Housing Flammability rating UL94 VO Dimensions Width in mm Height in mm Depth in mm Weight Ib kg System Controller including base 2 0 0 9 Detector including easy fit base 1 1 0 5 Universal Bracket 0 4 0 2 Reflector Single 0 2 0 1 Protective Cage 5 4 136 6 2 157 j 0 3 0 13 Approval Information 24 UL Approval Information UL File Number 83417 Distance between Fire Threshold Detector and Reflector Range 10 15m 32 8 49 2ft 22 40m 72 2 131 2ft 40 60m 131 2 196 8ft 35 50 60 100m 196 8 328 1ft All installations should comply with NFPA72 Territory Specific Information European Approval Information CE 0832 Fire Fighting Enterprises Ltd 9 Hunting Gate Hitchin SG4 OTJ UK 07 0832 CPD 0565 EN54 12 Line Detector using an Optical Beam Fire Safety Documentation See doc 0044 003 Complies with EN54 12 for sensitivity levels between 25 and 35 with a maximum delay to fire of 20 seconds Protective cage must be fitted to comply with EN54 12 Document Number 0044 003 05
5. System Controller to test the wiring to the Fire Confirm screen Fire screen Control Panel Detector will signal Fire System Controller signals System Controller will Fire to Fire Control Panel stay Normal Press Yor X to Press X to exit ayit without performing the test 11 Cleaning the System Performing Manual Fire and Fault Tests Cleaning the System The system will automatically compensate for dust build up by changing the Compensation Level However it is recommended that the Detector lenses and the Reflector are cleaned periodically with a soft lint free cloth If the Compensation Level remains above 130 for several days this indicates that cleaning should take place The system should be isolated from the Fire Control Panel before cleaning takes place After cleaning verify that the system is operating normally If the Signal Strength is between 90 and 110 leave the system to compensate back to 100 this should take no more than 12 hours If the Signal Strength is above 110 reduce Compensation Level until Signal Strength is 90 110 and wait for system to compensate back to 100 If the Signal Strength is below 90 perform LASER Targeting Auto Align and Set 12 How to change Compensation Level Manual Fire and Fault Tests After installation or cleaning it is recommended that a manual Fire and Fault test i
6. and Distance 3 Select Power Mode 4 Select Distance between Detector and Reflector e All functions can be performed in Lo A 10mA e Select 8 50m default or 100m mode default e Select Hi A 50mA to enable faster beam movement during Auto Align and Laser Targeting e After installation set the system back to Lo A 4 1 Use VO to move between 4 Use AY to icons in the Engineering Menu change selection to highlight the icon shown 5 Press V to accept 2 Press v to select Press K to cancel 3 Use to move to required item Menu Navigation Commissioning LASER Targeting 5 LASER Targeting The system will signal Fault while in this mode The LASER is used to align the Detector with the Reflector It is an approximate alignment tool only After Auto Align the LASER may not be aimed directly at the Reflector Use K gt v to move the LASER as close to the Reflector as possible One press of an arrow key results in one movement of the Detector head Press or X to turn off the LASER and return to the Settings menu Refer to User Guide page 14 for troubleshooting if LASER is not visible Commissioning LASER RADIATION AVOID DIRECT EYE EXPOSURE POWER OUTPUT lt 5mW CLASS Illa LASER Wavelength 630 680 nm Commissioni
7. ctor Number Set TX Power Set Compensation Level Set RX Gain Set Zero 100 Info ONLY AVAILABLE ON MULTI DETECTOR UNIT WARNING ENGINEERING USE ONLY ALTERING MAY CAUSE MALFUNCTION 21 Menu Layout System Controller Settings Power Mode Units of Measurement Change Pass Code MANSINI e Units of Measurement Changes between Metric and Imperial Care must be taken when changing the Pass Code e Change Pass Code If the code is lost the unit Use lt gt to access each digit cannot be unlocked and E must be returned to the Use wv A to change the digit manufacturer This is not covered by the warranty Press Y to save the new Pass Code and return to the settings menu Press X to cancel the change and return to the Engineering menu System Information Operating Parameters and Dimensions Parameter Value Parameter Description Default 14 28V DC Pass code User Code required to access Engineering Menu 1234 8 12 mA Hi A System will operate at 50mA constant current consumption Lo A System will operate at 10mA constant current 0 45 3 98 dB consumption 10 60 Range 50 to 205 Level of amplification applied to SI compensate for dust build up and building movement sani At 75 Auto Optimise is started 2 30 s T 1 Range 50 to 4095 Indicates the optical power output ransmit power 8 100 m Set automatically by Auto Align
8. he Product Installation Options for Detector wiring orientation LED indicator must face downward Installation Wiring Diagrams TO THE TO THE DETECTOR DETECTOR CON C ZONE ZONE SUPPLY _ SUPPLY P EARTH SCREEN Fire Resistor Contact Fire Control Panel manufacturer e ALWAYS use a separate screened 2 core cable for for values of Fire Resistor each detector head Some Zone and Switch Interface Modules do not need a End Of Line EOL component is Fire Resistor replace Resistor with a short circuit Refer to supplied by Fire Control Panel manufacturer supplied CD IE reer information l e CAUTION For system monitoring Do not use looped e Check operation of Fire and Fault connection on wire under any terminals Break wire run to provide 6 Fire Panel monitoring of connections Commissioning Apply Power and Enter Pass Code 1 Apply power 2 Enter Pass Code to Access Engineering Menu EZ T H 0 ADOOS g Press for Pass Code screen LILILIAI EME Commissioning e Default Pass Code 1 2 3 4 e AN vV Change digit e lt gt Move between digits e lt Accept e An incorrect Pass Code will return the display to the Pass Code entry screen e Three incorrect attempts will lock access for three minutes Note a commissioned system will display Commissioning Select Power Mode
9. ligned to the Reflector so repeat Step 3 Perform Auto alignment followed by Set Troubleshooting Home Position If it is not Known where the beam is pointing use Home Position to automatically steer the infrared beam to approximately the centre of its range of movement e Press Yor X to exit this function e This will take up to 15 minutes to complete e When complete the display will return to the Engineering Menu Troubleshooting 15 Display and Indicators LCD icon Layout Seconds User Prompt Feet Latched Reset Signal Strength Compensation Level Detector Number Metres Degrees Fire Not Used bp liansmit Lee Shee Strength Received Ap 1000 tai IO N Bar Graph Set Home LASER Fire System Controller Position Targeting Threshold Fire Test Settings Detector Settings Beam Fire Fault Software Alignment Delay Utilities 16 Display and Indicators Detector and System Controller Status Indicators Detector Indicator flashes every 10 seconds NORMAL GREEN FAULT YELLOW FIRE RED System Controller Indicators 1 to 4 show status for Detectors 1 to 4 NORMAL No flash FAULT YELLOW FIRE RED Indicator 5 flashes GREEN to indicate NORMAL System Controller status All indicators flash every 10 seconds DETECTORS 2 TO 4 ONLY AVAILABLE ON MULTI HEAD SYSTEM Info 17 Menu Layout User Menu Controller parameters
10. ng Auto Alignment and Set 0 100 Calibrate 6 Auto Alignment e Select Auto to automatically align the infrared beam e Signal Strength will be shown LOA 18 minutes during Alignment HiA 15 minutes d Al OR GRE amp 10 7 Set 0 100 Calibrate When Set is displayed press Y When S 00 is displayed cover the Reflector with a non reflective material and leave covered then press lt When S 01 is displayed uncover the Reflector and leave uncovered then press 8 System is Aligned It is recommended to set the system back to Lo A mode Green LED on Detector will flash every 10 seconds and Signal Strength should be between 99 and 101 Default values 35 Fire Threshold 10 second delay to Fire and Fault Non Latching mode Refer to User Guide page 11 12 to change settings and for Fire and Fault Test In Use Settings and Final Tests Fire Threshold How to change the threshold at which the Detector will detect a Fire Fire Fault Delay How to change the delay the System Controller uses before signalling a Fire or Fault to the Fire Control Panel F Delay 1 Fire Delay 2 Fault In Use Fire Test How to perform a Fire Test from the
11. s not uncovered during S 01 e Ensure Reflector was uncovered when S 01 was selected Reflector Not Found Detector could not align with Reflector e Ensure correct distance has been set e Ensure correct Reflector type has been used Ensure clear line of sight to Reflector e Re align beam using LASER and Auto Align Centre Stage of Alignment Failed Detector is too far from the centre of the Reflector Troubleshooting Ensure clear line of sight to Reflector e Ensure correct distance between beam path and roof structures 13 Troubleshooting LASER Not Visible 14 If it is not possible to see the LASER because of the installation environment for example if you cannot see the Reflector from the System Controller or there is high ambient light then use Hand Alignment This option displays the signal strength value returned by the Detector and allows the user to move the beam al Start Auto Alignment and press X after two seconds to exit this will maximise infrared power Select Hand alignment Use lt gt A v to steer the beam until the signal strength is above 800 There is no auto repeat function on any key To move the motor in any given direction more than once press the key multiple times Cover the Reflector If the Signal Strength does not drop by more than half the beam is not a
12. s performed Fire Test Cover the Reflector slowly so that it takes longer than 2 seconds to cover The System Controller will signal Fire to the Fire Control Panel Fault Test Cover the reflector completely within 2 seconds The System Controller will signal Fault back to the Fire Control Panel Troubleshooting Error Codes Detector Not Found System Controller could not find Detector Also displayed during power up e Wait 45 seconds for system to power up e Check wiring between System Controller and Detector Voltage to Detector should be 11 13V Auto Align Failed e Ensure correct distance between Reflector and roof structures Ensure clear line of sight to Reflector e Re align Detector using Auto Align Compensation Level Not Zero Compensation must equal zero when Set is selected e Re align beam using Auto Align Cannot Zero During S 00 in Set The Reflector was not covered or the Detector was not aligned onto the Reflector e Ensure Reflector was completely covered with a non reflective material e Re align Detector using Auto Align Signal Strength Out of Range Signal Strength is too low or too high after Auto Align e Ensure correct distance has been set e Ensure correct Reflector type has been used Ensure clear line of sight to Reflector e Re align beam using LASER and Auto Align No Signal During S 01 in Set The Reflector wa