1. KLUIMA Strategic Products and Services INSTALLATION MANUAL Four way Cassette Type Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference CONTENTS PAGE PRECAUTIONS INSTALLATION INFORMATION INSPECTING AND HANDLING THE UNIT lt lt 2 ATTACHED FITTINGS INDOOR UNIT INSTALLATION INSTALL THE CONNECTING PIPE REFRIGERANT PIPE CONNECTION CONNECT THE DRAIN PIPE WIRING CONTROL TROUBLE SHOOTING TEST OPERATION 1 PRECAUTIONS NW Be sure to be in conformity with the local national and international laws and regulations E Read PRECAUTIONS carefully before installation E The following precautions include important safty items Observe them and never forget NW Keep this manual with the owner s manual in a handy place for future reference The safty precautions listed here are divided into two categories In either case important safty information is listed which must be read carefully A WARNING Failure to observe a warning may result in death A CAUTION Failure to observe a caution may result in injury or damage to the equipment After completing the installation make sure that the unit operates properly during the start up operation Please instruct the customer on how to operate the unit and keep it maintained Also inform customer
2. Notices For Benable pipe The bending angle should not exceed 90 C Bending position is preferably in the bendable pipe The larger the better it is Do not bend the pipe more than three times Bend the connecting pipe of small wall thickness Cut out a desired concave at the bending part of the insulating pipe Then expose the pipe cover it with tapes after bending To prevent collapsing of deforming please bend the pipe at its biggest radius Use bender to get a small radius pipes Use the market brass pipe Be sure to use the same insulating materials when you buy the brass pipe More than 9mm thick installation manual 6 Use frozen oil Fig 6 1 Bend the pipe with thumb Fig 6 2 Make the ends straight A Fig 6 3 Locate The Pipe Drill a hole in the wall suitable just for the size of the wall conduit 90mm in general then set on the fittings such as the wall conduit and its cover Bind the connecting pipe and the cables together tightly with binding tapes Do not let air in which will cause water leakage by condensation Pass the bound connecting pipe through the wall conduit from outside Be careful of the pipe all ocation to do no damage to the tubing Connect the pipes Then openthestemofstopvalvesoftheoutdoorunittomakethere frigerant pipe connecting the indoor unit with the outdoor unit fluently flow Be sure of no leakage by checking it with leak detector
3. could be extracted out easily e There is no direct radiation from heaters 4h CAUTION Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept 5 2 Install the main body m The existing ceiling to be horizontal 1 Please cut a quadrangular hole of 600x600mm in the ceiling according to the shape of the installation paper board Refer to Fig 5 3 Fig 5 4 e The center of the hole should be at the same position of that of the air conditioner body Determine the lengths and outlets of the connecting pipe drainpipe and cables To balance the ceiling and to avoid vibration please enforce the ceiling when necessary 2 Please select the position of installation hooks according to the hook holes on the installation board e Drill four holes of 12mm 50 50mm deep at the selected positions on the ceiling Then embed the expansible hooks fittings e Face the concave side of the installation hooks toward the expansible hooks Determine the length of the installation hooks from the height of ceiling then cut off the unnecessary part e If the ceiling is extremely high please determine the length of the installation hook according to facts e Cut the insta
4. handling the unit take into account the following 5 Fragile handle the unit with care 11 Keep the unit upright in order to avoid compressor damage m There is petrolatum existing 2 Choose on before hand the path along which the unit is to be brought in There is salty air surrounding near the coast 3 Move this unit as originally package as possible There is caustic gas the sulfide for example existing in the air near a hot spring 4 When lifting the unit always use protectors to prevent belt The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existing There are inflammable materials or gas There is acid or alkaline liquid evaporating Other special conditions damage and pay attention to the position of the unit s centre of gravity installation manual 2 4 ATTACHED FITTINGS Please check whether the following fittings are of full scope If there are some spare fittings please restore them carefully Four way Four way Cassette Cassette compact 1 Expansible hook INSTALLATION FITTINGS Installation hook Installation paper board Tubing amp Fittings Soundproof insulation sheath Out let pipe pipe Out let pipe sheath Out let pipe clasp Drainpipe Fittings 9 Tightening band 00 O 00 10 Remote controller ARA RAE
5. AUTION Never put the panel face down on floor or against the wall or on bulgy objects Never crash or strike it Remove the air in grill Slide two grill switches toward the middle at the same time and then pull them up Refer to Fig 5 9 Draw the grill up to an angle of about 45 and remove it Refer to Fig 5 10 Fig 5 9 Fig 5 10 2 Install the panel Align the swing motor on the panel to the tubing joints of the body properly Refer to Fig 5 11 E Hang the four fixed rope of the main body to the installation cover and the other three covers of the swing motor Refer to Fig 5 11 and CAUTION The installation cover of the swing motor must sink into the corresponding water receiver installation manual 9 E Install the panel on the main body with bolt M5x16 and washer Refer to Fig 5 11 E Adjust the four panel hook screws to keep the panel horizontal and screw them up to the ceiling evenly E Regulate the panel in the direction of the arrow in Fig 5 11 3 slightly to fit the panel s center to the center of the ceiling s opening Guarantee that hooks of four corners are fixed well _ Keep fastening the screws under the panel hooks until the thickness of the sponge between the body and the panel s outlet has been reduced to about 4 6mm The edge of the panel should contact with the ceiling well Refer to Fig 5 12 e Malfunction described in Fig 5 13 can be caused by inappropriate tightness th
6. CCM COMM BUS COMM BUS Please use 3 core shielded wire and j connect the shielded layer to the earth Fig 9 3 l Display l KX Wire board i wy controller l L To wire controller The reserved wire control function is indicated in broken table user can purchase the wire controller when necessary Fig 9 4 10 CONTROL m Hoursepower set Hoursepower code Base on different purposes to setting the switch cords on PC panel of indoor electrical control box Once finish the setting please cut off the main power and then input power again otherwise setting function could not work installation manual 10 ENC1 Dial switch Horsepower setting Code Capacity Horsepower Note The horsepower has been set before leaving the factory 1 which can only be modified by 2 professionals 3 4 0 2200W 0 8HP 2800W 1 0HP 3600W 1 2HP 4500W 1 5HP 5600W 2 0HP A The system together have 64units 0 63 everyone has only system addresscode f two addresses are the same in one system the abnormal operation will occur CAUTION Please switch off the power before setting otherwise the unexpected error will occur Main board Code designation SW1 definition O 1 means factory test mode 0 means add auto searching mode default setting O 1 means DC fan is chosen 0 means AC fan is chosen 00 means DC fan static pressure is 0 reserved 00 means the temperature is 15 degrees when shuttin
7. E CUA 11 Frame 12 Mounting screw ST2 9x10 C H 13 Alkaline dry batteries AM4 16 Connective pipe for 4 1 restriction assembly Cautions on remote controller installation El Never throw or beat the controller Mounting screw B ST2 9x10 C H Before installation operate the remote controller to determine its location in a reception range m Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment it is necessary to prevent image disturbances or noise interferences Al Do not install the remote controller in a place exposed to direct sunlight or close to a heating source such as a stove Remote controller holder E Note that the positive and negative poles are right positions when loading batteries Remote controller E This manual is subject to changes due to technological improvement without further notices installation manual 3 9 INDOOR UNIT INSTALLATION 5 1 Installation place Refer to Fig 5 1 Fig 5 2 Fig 5 3 for specification The indoor unit should be installed in a location that meets the following reauirements There is enough room for installation and maintenance The ceiling is horizontal and its structure can endure the weight of the indoor unit The outlet and the inlet are not impeded and the influence of external air is the least e The air flow can reach throughout the room e The connecting pipe and drainpipe
8. alves A and B are both closed e Connect the joint of the charge hose with the vacuum pump e Open the Lo lever of the manifold valve completely e Turnonthe vacuum pump At the beginning of pumping loosen the maintenance terminator nut of stop valve B a little to check whether the air comes in the sound of the pump changes and the indicator of compound meter turns below zero Then fasten the nut e When the pumping has finished close the Lo lever of the manifold valve completely and turn off the vacuum pump e When you have pumped for over 15 minutes please confirm that the indicator of multimeter is on 1 0X105Pa 76cmHg e Loosen and remove the quadrangle cover of stop valves A and B to open stop valve A and B completely then fasten them e Disassemble the charge hose from the repair mouth of stop valve A and fasten the nut Manifold valve Multi meter Pressure meter 76 cmHg Hi lever Charge hose Po pump Lo lever Fig 7 4 mM Allthe stop valves should be opened before test operation Each air conditioner has two stop valves of different sizes on the side of the outdoor unit which operate as Lo stop value respectively Refer to Fig 7 5 Flare nut Valve body Valve stem 7 2 Check The Leakage E Check all the joints with the leak detector or soap water See Fig 7 6 as a reference illustration Check point of indoor unit D C Check point of outdoor unit A Lo stop val
9. e screw e lfthe gap between the panel and ceiling still exists after fastening the screws the height of the indoor unit should be modified again Refer to Fig 5 14 left e You can modify the height of the indoor unit through the openings on the panel s four corners if the lift of the indoor unit and the drainpipe is not influenced Refer to Fig 5 14 right 3 Hang the air in grill to the panel then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively 4 Relocate the air in grid in the procedure of reversed order install the air in grid AA NE O 201 ja ir K ES Swing motor installation cover lo Swing motor side lease operate accordin Bolt washer Fig 5 1 1 pe en of En or it can not be disassembled when it is necessary Body i nigi alir Panel sealing foam Ceiling Panel foam2 7 ex S d Outlet air Airplate Panel Panel foam Fig 5 12 7 Ceiling Leakage L ike i Dew Ba Fig 5 13 gt Hexagon nut Horizontal adjust ment 6 INSTALL THE CONNECTING PIPE Check whether the height drop between the indoor unit and outdoor unit the length of refrigerant pipe and the number of the bends meet the following requirements The max height drop and The length of refrigerant pipe deponding on the ouotdoor unit If the height drop is more tha
10. engthen drainpipe apply protective tube to wrap its indoor parts for ensuring the lengthen part connected tightly 7 In case the drainpipe outlet is higher than pumping connective pipe of the main body the drainpipe must be arranged upwards vertically by using connective assembly of the water outlet for vertical bending and the height of the drainpipe shall set to the defrosting pan surface no more than 600mm otherwise too much backflow while shutdown would leads to overflow Refer to Fig 8 2 8 Base on the actual requirement to bend piping and use connective assembly of water outlet in terminal box for pipe layout A CAUTION The joints in drain system must be sealed to avoid water leakage 9 The height from floor to the end of drainpipe or the bottom of drain slot must more than 50 mm Don t immerse the end of drainpipe or the bottom of drain slot into water When drain condensate liquid to raceway please bend the drainpipe to a U sharped hydroseal for avoiding stench transmitted by drainpipe to indoor Gradient higher than 1 100 Fig 8 1 Lean over 1 100 Max 600mm Pump pipe clasp the fittings Fig 8 2 8 2 Drainage Test m Check whether the drainpipe is unhindered NW New built house should have this test done before paving the ceiling 1 Remove the test cover and stow water of about 2000ml to the water receiver through the stow tube 2 Turn on the power and operate the air conditione
11. erture of refrigerant circuit will be high please keep the interconnection cable away from the copper tube installation manual 1 Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Improper installation work may result in the equipment falling and causing accidents If the refrigerant leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into the place contacting with fire After completing the installation work check that the refrigerant does not leak Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker CAUTION Ground the air conditioner Do not connect the ground wire to gas or water pipes lightning rod or a telephone ground wire Incomplete grounding may result in electric shocks Be sure to install an earth leakage breaker 2 INSTALLATION INFORMATION To install properly please read this installation manual at first The air conditioner must be installed by qualified persons When installing the indoor unit or its tubing please follow this manual as strictly as possible If the air conditioner is installed on a metal part of the building it must be electrically insulated according to the relevant standards to electrical appliances When all the installation work is finished please tur
12. g down the unit for cold wind proof 01 means the temperature is 20 degrees when shutting down the unit for cold wind proof 10 means the temperature is 24 degrees when shutting down the unit for cold wind proof 11 means the temperature is 26 degrees when shutting down the unit for cold wind proof 00 means temperature compensation is 6 degrees under heating mode O 01 means temperature compensation is 2 degrees under heating mode Network address set e Network address is set by communication of indoor and outdoor unit the address is the same as indoor address there is no need to set separately e The central control of indoor units can be done on outdoor unit there is no need to control indoor unit separately for details please refer to V4 outdoor unit manual e For previous control of indoor units the network can be set by connecting X Y E terminals there is no need to set network address The network can also be set by outer network module and main board CN20 01 means DC fan static pressure is 1 reserved O 10 means DC fan static pressure is 2 reserved O 11 means DC fan static pressure is 3 reserved 00 means the time of stopping TERMAL fan is 4 minutes 01 means the time of stopping TERMAL fan is 8 minutes 10 means the time of stopping TERMAL fan is 12 minutes 11 means the time of stopping TERMAL fan is 16 minutes O 10 means temperature compensation is 4 degrees unde
13. larm when first time run LED flash disappear it restores power on togather automatically installation manual 12 12 TEST OPERATION A The test operation must be carried out after the entire installation has been completed Please confirm the following points before the test operation The indoor unit and outdoor unit are installed properly Tubing and wiring are correctly completed The refrigerant pipe system is leakage checked The drainage is unimpeded The heating insulation works well The ground wiring is connected correctly The length of the tubing and the added stow capacity of the refrigerant have been recorded The power voltage fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the outdoor and indoor and indoor units The gas side and liquid side stop values are both opened The air conditioner is pre heated by turning on the power Test operation Set the air conditioner under the mode of COOLING with the remote controller and check the following points perthe Owner s Manual lf there is any malfunction please resolve it as per chapter Troubles And Causes The indoor unit Whether the switch on the remote controller works well Whether the buttons on the remote controller works well Whether the air flow louver moves normally Whether the room temperature is adjusted well Whether the indicator lights normally Whether the temp
14. llation hook open in the middle position then use apropriate length of reinforcing rod 12 to weld together The length could be calculated from Refer to Fig 5 5 Length 210 L in general L is half of the whole length of the installation hook 1 A Please adjust the hexangular nuts on the four installation hooks evenly to ensure the balance of the body e If the drainpipe is awry leakage will be caused by the malfunction of the water level switch Adjust the position to ensure the gaps between the body and the four sides of ceiling are even The body s lower part should sink into the ceiling for 10 12 mm Refer to Fig 5 5 e Use the transparent hose filled with water to check the lever of the main body from the four sides or diagonal line direction the lever indicator also can check the lever from four sides of the main body Refer to Fig 5 6 e Locate the air conditioner firmly by wrenching the nuts after having adjusted the body s position well New built houses and ceilings In the case of new built house the hook can be embedded in advance refer to the A b mentioned above But it should be strong enough to bear the indoor unit and will not become loose because of concrete shrinking After installing the body please fasten the installation paper board onto the air conditioner with bolts M6X16 to determine in advance the sizes and positions of the hole opening on ceiling Refer to Fig 5 8 Please fir
15. mbols with the direction of the fluid flow For electrical work follow the local national wiring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect in electrical work it will cause electrical shock and fire Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal If connection or fixing is not perfect it will cause heat up or fire at the connection Wiring routing must be properly arranged so that control board cover is fixed properly If control board cover is not fixed perfectly it will cause heat up at connection point of terminal fire or electrical shock If the supply cord is damaged it must be replaced by the manufacture or its sevice agent or a similarly qualified person in order to avoid a hazard An all pole disconnection swith having a contact separation of at least 3mm in all poles should be connected in fixed wiring When carrying out piping connection take care not to let air substances go into refrigeration cycle Otherwise it will cause lower capacity abnormal high pressure in the refrigeration cycle explosion and injury Do not modify the length of the power supply cord or use of extension cord and do not share the single outlet with other electrical appliances Otherwise it will cause fire or electrical shock The temp
16. n is indicated in broken line table users can select it when necessary 3 core shielded wire Fig 9 1 Y NOTE E Please remember the surroundings environmental temperature direct sunlight rain etc m We consider the minimal size of the metal core as the wire size So itis recommended you adopt a thicker one as the power conducting wire so as to avoid power decrease E Connect the grounded wire to both indoor and outdoor units E This chart is just an on site wire connecting example For details please refer to relative National criteria A B 20m Distance between outdoor unit and the farthest indoor unit lt 1200m Note The length of signal wire depends I I l l l l IA on actual wiring condition not longer than 1200m IB l l l l Indoor Outdoor Unit O Unit l l l Entrance Entrance I of the Indoor Unit of the outdoor Unit E Terminal board diagram Please refer to the indoor unit wiring diagram for the wiring NOTE The air conditioners can connect with Central Control Monitor CCM Before operation please wiring correctly and set system address and network address of indoor om units XT1 e els ele TO INDOOR POWER 220 240V 50Hz 208 230V 60Hz Fig 9 2 gt gt 1 lt I wW ml A gt x12 X Y E P Qa ONOI ANNIN OOE N RR XK OR RRA To Central Control Monitor TO OUTDOOR
17. n 10m you had better put the outdoor unit over above the indoor unit The number bends fewer than 15 Do not let air dust or other impurities fall in the pipe system during the time of installation The connecting pipe should not be installed until the indoor and outdoor units have been fixed already Keep the connecting pipe dry and do not let moisture in during installation The Procedure of Connecting Pipes Measure the necessary length of the connecting pipe and make it by the following way Connect the indoor unit at first then the outdoor unit Bend the tubing in proper way Dont harm them Daub the surfaces of the flare pipe and the joint nuts with frozen oil and wrench it for 3 4rounds with hands before fasten the flare nuts Refer to Fig 6 1 Be sure to use two wrenches simultaneously when you connect or disconnect the pipes The stop valve of the outdoor unit should be closed absolutely as original state Every time you connect it first loosen the nuts at the part of stop valve then connect the flare pipe immediately in 5 minutes If the nuts have been loosened for a long time dusts and other impurities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection Expel the air refer to the Expel The Air after connecting the refrigerant pipe with the indoor unit and the outdoor unit Then fasten the nuts at the repair points
18. n on the power only after a thorough check Regret for no further announcement if there is any change of this manual caused by product improvement INSTALLATION ORDER l l l NH Select the location Failure to install an earth leakage breaker may result in electric shocks E Install the indoor unit Connect the outdoor unit wires then connect the indoor E install the outdoor unit unit wires You are not allow to connect the air conditioner with the Install the connecting pipe power source until wiring and piping the air conditioner is done m Connect the drain pipe While following the instructions in this installation Wiring manual install drain piping in order to ensure proper drainage and insulate piping in order to prevent E condensation Improper drain piping may result in water leakage and property damage Install the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locations 3 Test operation INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the service agent When
19. or soap water Cover the joint of the connecting pipe to the indoor unit with the sound proof insulating sheath fittings and bind it well with the tapes to prevent leakage REFRIGERANT PIPE CONNECTION Expel The Air Flaring Cut a pipe with a pipe cutter Insert a flare nut into a pipe and flare the pipe x X crude burr Sal 12 7mm 15 9mm 61 8 75 4N m Fig 7 2 Table 7 1 Outside diameter Fasten the nut Put the connecting tubing at the proper position wrench the nuts with hands then fasten it with a wrench Refer to Fig 7 3 Too large torque will harm the bellmouthing and too small will cause leakage Please determine the torque according to Table 7 2 Fig 7 3 Table 7 2 Tubing size 14 2 17 2N m 32 7 39 9N m 49 5 60 3N m 19 1mm 97 2 118 6N m installation manual m The necessary filling amount of refrigerant e Refrigerant volume to be added is calculated according to outdoor unit installation manual Be sure to add refrigerant measuring by a scale L The length of the pipe e Please record the quantity added and store it carefully for future maintenance NW Expel the air with a vacuum pump Refer to Fig 7 4 Please refer to its manual for the way of using manifold valve e Loosen and remove the maintenance nuts of stop valves A and B and connect the charge hose of the manifold valve with the maintenance terminator of stop valve A Be sure that stop v
20. orary buttons works well Whether the drainage is normal Whether there is vibration or abnormal noise during operation Whether the air conditioner heats well in the case of the HEATING COOLING type The outdoor unit Whether there is vibration or abnormal noise during operation Whether the generated wind noise or condensed of by the air conditioner have influenced your neighborhood Whether any of the refrigerant is leaked CAUTION Protection function will delay the startup of compressor for 3 minutes in case the unit is turned on immediately after power on or restarted after shutdown MDV10I 029AW 202000171572
21. r under the COOLING mode Listen to the sound of the drain pump Check whether the water is discharged well a lag of 1min is allowed before discharging according to the length of the drain pipe and check whether water leaksfrom the joints CAUTIONS If there is any malfunction please resolve it immediately 3 Stop the air conditioner for there minutes check if everything is ok If the drain hose is located unreasonable water overflow will cause the Alarm indicator lamp flashing For both cooling and heating type or cooling only type even the water leak out from the water receiver 4 Check the drain pump whether drain water immediately when alarm sound for the high water lever If the water lever can t come down below to the limited water lever the air conditioner will stop Restart it until turn off the power and drain off all the water 5 Turn off the power drain the water away NW The drain plug is used to empty the water receiver for maintenance of the air conditioner Please stuff it imposition at all times during operation to avoid leakage 9 WIRING Caution o The air conditioner should use separate power supply with rated voltage the voltage of power supply must be within90 110 of rated value The external power supply to the air conditioner should have ground wiring which is linked to the ground wiring of the indoor and outdoor unit s The wiring work should be done by qualified persons according
22. r heating mode O 11 means temperature compensation is 8 degrees under heating mode installation manual 11 SW6 definition 1 means auto wind under auto mode O 0 means auto wind under non auto mode reserved J1 J2 definition J1 no Jumpers means power off memory function J1 Jumpers means no power off memory function reserved 11 TROUBLE SHOOTING Table 12 1 noe conan eii romare The evaporator The run lamp After the malfunctions sensor check flashes fast disappear it restores Malfun point is abnomal automatically ction orroom temp sensor is abnormal Malfun Indoor outdoor unit The timer lamp After the malfunctions ation communication flashes fast disappear it restores is abnormal automatically Outdoor unit The alarm lamp After the malfunctions Malfun js abnormal flashes slowly disappear it restores ction automatically After the malfunctions disappear it restores automatically When the indoor unit The defrost lamp t a A Mode conflict flashes fast He Alarm or is turned off the alarm will disappear When the indoor unit is Alarm M_Home rd replaced with a correct mismatching 9 one the alarm will Malfun Water level switch The alarm lamp ction is abnormal flashes fast disappear ends After the malfunctions Malfun eirost asn disappear it restores ction EEPROM error slowly automatically No address Timer LED and After the malfunctions A
23. s that they should store this installation manual along with the owner s manual for future reference A WARNING Be sure only trained and qualified service personnel to install repair or service the equipment Improper installation repair and maintenance may result in electric shocks short circuit leaks fire or other damage to the equipment Install according to this installation instructions strictly If installation is defective it will cause water leakage electrical shock and fire When installing the unit in a small room take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage Contact the place of purchase for information Excessive refrigerant in a closed ambient can lead to oxygen deficiency Use the attached accessories parts and specified parts for installation otherwise it will cause the set to fall water leakage electrical shock fire Install at a strong and firm location which is able to withstand the set s weight If the strength is not enough or installation is not properly done the set will drop to cause injury The appliance must be installed 2 3m above floor The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is accessible The enclosure of the appliance shall be marked by word or by sy
24. st guarantee the flatness and horizontal of ceiling when installing it Refer to the A a mentioned above for others Refer to the A c mentioned above for installation Remove the installation paper board CAUTION After installing the body the four bolts M6x12 must be fastened to the air conditioner onto ensure the body is grounded well Necessary room 144 N N Outlet Inlet Outlet AA Fig 5 1 Fig 5 2 installation manual 4 Drain side g 3 5 WS EE a UY y EI il 570 Body 647 Panel 523 Hook location 9 545 Hook location 570 Body 647 Panel Unit mm Fig 5 3 A ESA Sa PIS E EA ae LLALL LLL LLULL RLL RRL RLE Body j Hook 1 m raaa 1 TE QT Ir le jl AL i a Nut a jij S L Hau ne o a aaa a Ceiling 5 Panel nn 600 J Fig 5 4 z gt 2 E D I Fig 5 5 OSO i ey ET weer CERES Colourless _ ee zontal trans parent pipe indicator Fig 5 6 Fig 5 7 Body Central hole Fixing hole installation paper board Hook hole Screw M5x16 N Accessory Installation paper board Fig 5 8 u 3 A A NOTE All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail Install The Panel C
25. to circuit drawing o A disconnection device having an air gap contact separation in all active conductors should in corporated in the fixed wiring according to the National wiring regulation o Be sure to locate the power wiring and the signal wiring well to avoid cross disturbance and their contact with connecting pipe or stop valve body o The wiring attached to this air conditioner is 6m long Be sure toprolongitwithwiringofthesametypeandproperlengthifneces sary Generally do not twist two wiring together unless the joint is soldered well and covered with insulator tape o Do not turn on the power until you have checked carefully after wiring o The yellow and green wire can only be used to link to the ground wiring E The Specification of Power installation manual 9 Table 9 1 Model W 2200 5600 Phase Power 220 240 50Hz Frequency and volt 208 230 60Hz Circuit breaker fuse A Indoor unit power wiring mm2 Indoor outdoor connecting wiring mm 3 core shielded wire weak electric signal 3x0 5 A CAUTION m Adisconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation m Ground the air conditioner properly to obtain a good anti interference effect E Wiring chart Power 220 240V 50Hz 208 230V 60Hz CENTRAL CONTROL MONITOR CCM OUTDOOR UNIT The reserved functio
26. ve B Hi stop valve C D Joints of the connecting pipe to the indoor unit Fig 7 6 7 3 Insulation WN Be sure to with insulating materials cover all the exposed parts of the flare pipe joints and refrigerant pipe on the liquid side and the gas side Ensure that there is no gap between them NW Incomplete insulation may cause water condensation 8 CONNECT THE DRAIN PIPE 8 1 Install The Drainpipe Of The Indoor Unit 1 The drainpipe can use PVC pipe external diameter about 37 39mm inner diameter is 32mm 2 Joint drainpipe connector to the end side of water pumping pipe and fix drainpipe together with water outflow pipe and thermal insulation tube by clasp of water outflow pipe attached A CAUTION Don t use forcing strength to crack the water pumping pipe 3 Water pumping pipe and drainpipe from main body must be wrapped by insulation tube evenly and bound by tighten band for obstructing air getting in and coagulation 4 Prevent from water backflow into unit inside during shutdown the drain pipe shall place down side and drain water to outdoor drain side the gradient of the drain pipe should be higher than 1 100 without salient and water remain Refer to Fig 8 1 a installation manual 8 5 When connecting drainpipe don t drag the pipe that would pull the main unit For this please arrange bearing points every 0 8 to 1 0 meter to avoid pipe be bended See Fig 8 1 b 6 When connect a l

Download Pdf Manuals

image

Related Search

Related Contents

InstallatIon · Manual 5.0670.01.72 1/2  User Manual  Ver ficha técnica - Artículos para el jardín, piscina, SPA. Todo para  Olympus BLS-5  IShowV3 User Manual  Gravador de Vídeo Digital Divar MR  le tapis de plantes instantané de covergreen® covergreen  Introducing the perfect choice for mobile presenters  Oscilloscope Measurement Labs  