Home
INSTALLATION MANUAL
Contents
1. 2 Do not install the unit where a strong wind blows or where it is very dusty 3 Do not install the unit where people pass 4 Take you neighbors into consideration so that they are not disturbed by air blowing into their windows or by noise 5 Provide the space shown in figure so that the airflow is not blocked Also for efficient operation leave open three of the four directions front rear and both sides 6 Install the outdoor unit in a location which can withstand the weight of the unit and vibration and which can install horizontally 7 Provide the indicated space to ensure good airflow 8 During heating operation drain water flows from the outdoor unit Therefore install the outdoor unit in a place where the drain water flow will not be obstructed Reverse cycle model only 9 Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible 10 Install the unit where connection to the indoor unit is easy WARNING Install at a place that can withstand the weight of the outdoor units and install positively so that the units will not topple or fall CAUTION Do not install where there is the danger of combustible gas leakage Do not install near heat sources If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit 4 INSTALLATION DIAGRAM OUTDOOR UNIT Do not directly install it
2. Do not use this equipment with air or any other unspecified refrigerant in the refrigerant lines Excess pressure can cause a rupture During installation make sure that the refrigerant pipe is attached firmly before you run the compressor Do not operate the compressor under the condition of refrigerant piping not attached properly with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to rupture and even injury When installing and relocating the air conditioner do not mix gases other than the specified refrigerant R410A to enter the refrigerant cycle If air or other gas enters the refrigerant cycle the pressure inside the cycle will rise to an abnormally high value and cause rupture injury etc The rated voltage 230V 50Hz WARNING The rated voltage of this product is 230 V AC 50 Hz Before turning on the power check if the voltage is within the 220 V 10 to 240 V 10 range Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner Use a circuit breaker and receptacle matched to the capacity of the air conditioner Do not extend the power cable Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Install a leakage circuit breaker in accordance with the related laws and regulations and electric company standards The circuit
3. be measured with a conven tional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended the gauge with seals 0 1 to 5 3 MPa 1 to 53 bar for high pressure 0 1 to 3 8 MPa 1 to 38 bar for low pressure To increase pressure resistance the hose material and base Charge hose size were changed A conventional vacuum pump can be used by installing a Vacuum pump vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A Copper pipes Gauge manifold It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg 10 m Do not use copper pipes having a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion value or capillary tube may become blocked with contaminants As an air conditioner using R410A incurs pressure higher than when using R22 it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in Table1 Never use copper pipes thinner than 0 8 mm even when it is available on the market CONNECTION PIPE REQUIREMENT Nominal diameter Outer diameter 15 88 mm Do not use the existing for R22 piping and flare nuts If the existing materials are used the pressure inside the refrigerant cycle will rise and cause failure injury etc Use the special R410A materials
4. the ground otherwise it will cause failure SS d 5 cm or more 2 CAUTION In the area with heavy snowfall if the intake and outlet of outdoor unit is blocked with snow it might become difficult to get warm and it is likely to cause of the breakdown Please construct a canopy and a pedestal or place the unit on a high stand local configured En 2 When there are obstacles at the back side 10 cm or more When there are obstacles at the back and front sides 10 cm or more 60 cm or more x When there are obstacles at the back side s and top as 60 or more 10 cm or more 40 em or more 25 cm or more Ss Service space When there are obstacles at the back side with the installation of more than one unit or more 5 INSTALLATION 5 1 Installation 1 Outdoor unit to be fasten with bolts at the four places indicated by the arrows without fail 2 Fix securely with bolts on a solid block Use 4 sets of commercially available M10 bolt nut and washer Bolt Block En 3 3 Since the drain water flows out of the outdoor unit during heating operation install the drain pipe and connect it to a commercial 16 mm hose When installing the drain pipe plug all the holes other than the drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage Reverse cycle model only AIR Drain cap
5. too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table below for the terminal screw tightening torques Strip Crimp type terminal p Screw with special washer Wi Crimp type terminal Terminal board Sleeve Terminal block Screw with special washer Camp ORe ermina Wire Tightening torque 1 2 to 1 8 N m 12 to 18 kgf cm 2 0 to 3 0 N m 20 to 30 kgf cm 1 CONNECTION DIAGRAMS Power supply EARTH 3 2 Power line 3 2 0 1 1 9 kO EARTH Indoor unit Outdoor unit side terminal side terminal 2 CONNECTION CABLE PREPARATION Keep the earth wire longer than the other wires 30 mm Power supply cable or connection cable When connecting the power supply cable make sure that the phase of the power supply matches with the phase of the terminal board If the phases do not match the compressor will rotate in reverse and will not be able to compress 1 Service cover removal Remove the two mounting screws Remove the service cover by pushing downwards Hook 3 places Direction of the service cover removal Service cover 2 Valve cover removal Remove the one mounting screw Remove the valve cover by sliding upward
6. AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Personal MANUEL D INSTALLATION Pour le personnel agr uniquement MANUAL DE INSTALACION Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato El XEIPIAIO EFKATAZTAZH2Z Ma EEQUDIOOOTNHEVO TIPOOWTTIKO OEPBIC MANUAL DE INSTALAGAO Apenas para t cnicos autorizados KURULUM KILAVUZU Yetkili servis personeli i indir PART NO 9374995202 02 T rk e Portugu s EAAnvika Italiano Espanol Frangais Deutsch English AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL 9374995202 02 Contents 4 SAFETY 1 27 EON EASAN 1 3 SELECTING THE MOUNTING POSITION AR 2 4 INSTALLATION DIAGRAM a 2 INSTALLATION E 3 6 PUMP DOWN 1 1 For authorized service personnel only 1 SAFETY PRECAUTIONS This mark indicates procedures which if improperly per formed might lead to the death o
7. Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Use the special R410A flare tool or the conventional for R22 flare tool When using the conventional flare tool always use an allowance adjustment gauge and secure the A dimension shown in table 2 Check if L is flared uniformly and is not cracked or scratched A mm Conventional R22 Flaring tool Wing nut type Pipe outside TETEG Flaring tool for R410A clutch type Clutch type 0 9 52 mm 3 8 1 0 to 1 5 1 5 to 2 0 1 5 to 2 0 15 88 mm 5 8 1 0 to 1 5 BENDING PIPES 1 When bending the pipe be careful not to crush it 2 To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 70 mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place En 4 CONNECTION PIPES Outdoor unit 1 Detach the caps and plugs from the pipes Be sure to apply the pipe against the port on the indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connect ing the connection pipe 2 Centering the pipe agains
8. R410A inside the refrigerant cycle When charging the refrigerant R410A always use an electronic balance for refrigerant charging to measure the refrigerant by weight When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Add refrigerant from the charging valve after the completion of the work If the units are further apart than the maximum pipe length correct operation cannot be guaranteed 2 7 Accessories Name and Shape Name and Shape Q ty Insulation seal Installation manual Drain cap One set of following parts are necessary in installation of this air conditioner Connection pipe assembly Connection cable Wall pipe Decorative tape Vinyl tape Wall cap Saddle Drain hose Tapping screws Sealant M10 bolt nut 3 SELECTING THE MOUNTING POSITION Decide the mounting position with the customer as follows Do not set to a place where there is oily smoke oil is used the factory the unit can contact sea breeze sulfide gases will be generated in the hot spring area corrosive gases will be generated animal may urine on the unit and ammonia will be generated and a dusty place 3 1 Outdoor unit 1 If possible do not install the unit where it will be exposed to direct sunlight If necessary Install a blind that does not interfere with the air flow
9. Valve cover Hook 4 places 3 Connect the power supply cable and the connection cable to terminal wire terminations will not receive external stress 4 Fasten the power supply cable and connection cable with cable clamp Control box Terminal blocks Mofo a a ne Tee Lt P 5 Cable clamp Cable clamp Firmly secure cable clamp so ING Use the specified wire type and connect it securely H 2 ae Connection cable U Power supply cable EARTH Indoor unit 5 Power supply cable and connection cable should be fixed with cable clip as shown in the figure Fill in a gap at the entrance of the cables with insulation seal Fix cables so that cables do not make contact with the pipes especially on high pres sure side Do not make power supply cable and connection cable come in contact with valve Gas Power supply cable and connection cable 6 Put the service cover and valve cover back after completion of the work 5 3 Connecting the piping FLARING 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare the pipe with a flaring tool
10. breaker is installed in the permanent wiring Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3 mm between the contacts of each pole The power source capacity must be the sum of the air conditioner current and the cur rent of other electrical appliances When the current contracted capacity is insufficient change the contracted capacity When the voltage is low and the air conditioner is difficult to start contact the power company the voltage raised 2 4 Electric requirement Electric wire size and fuse capacity Power supply cable Connection cable Fuse capacity A Use conformed cable with Type245 IEC57 Install all electrical works in accordance to the national standard Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units Both indoor unit and outdoor unit Install the circuit breaker nearby the units 2 5 Operating range Cooling Dry Mode Heating Mode About 10 to 46 C About 15 to 24 2 6 Additional charge Refrigerant suitable for a piping length of 20 m is charged in the outdoor unit at the factory When the piping is longer than 20 m additional charging is necessary For the additional amount see the table below Piping length 20m 30m 40m 50 m Model type ELT When moving and installing the air conditioner do not mix gas other than the specified refrigerant
11. es and fit the cap to the charging valve to the specified torque 5 Remove the blank caps and fully open the spindles of the 2 way and 3 way valves with a hexagon wrench Torque 6 7 N m 60 to 70 kgf cm 6 Tighten the blank caps of the 2 way valve and 3 way valve to the specified torque 9 52 mm 3 8 in Elaphe 15 88 mm 5 8 in Charging port cap Tightening torque 20 to 25 N m 200 to 250 kgf cm 30 to 35 N m 300 to 350 12 5 to 16 125 to 160 kgf cm En 5 Connection pipe Q Blank cap Outdoor unit Hexagon wrench Use a 4 mm hexagon wrench Service hose 3 way valve with valve core Charging port Z N caution Use a clean gauge manifold and charging hose for R410A exclu sively Vacuum pump Service hose Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation There is no extra refrigerant in the outdoor unit for air purging Use a vacuum pump and gauge manifold and charging hose for R410A exclusively Using the same vacuum for different refrigerants may damage the vacuum pump or the unit GAS LEAKAGE INSPECTION CAUTION After connecting the piping check the all joints for gas leakage with gas leak detector When inspecting gas leakage always use the vacuum pump for pressure Do not use nitrogen gas Z CAUTION Install insulation around both the gas and liquid pipes Failure to do
12. l noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage 5 6 Customer guidance Explain the followings to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer airflow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the airflow direction louvers 3 Give the operating and installation manuals to the customer 6 PUMP DOWN 6 1 Pump down PUMP DOWN OPERATION FORCED COOLING OPERATION To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the cooling operation or forced cooling operation according to the following procedure When the cooling operation cannot start in winter and so on start the forced cooling operation 1 Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the low pressure valve slightly 2 Close the valve stem of 2 way valve completely 3 Start the cooling operation or following forced cooling operation Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing f
13. mounting holes 370 mm 4 912 hole Drain pipe mounting hole WS gt Base es Drain pipe When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in extremely cold weather Reverse cycle model only 5 2 Outdoor unit wiring Use crimp type terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause heavy damage inside the unit Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts cause a fire If the insulator is chafed electric leakage may occur Do not use the earth screw for an external connector Only use for interconnection between two units HOW TO CONNECT THE WIRE TO THE TERMINALS 1 Use crimp type terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely crimp the crimp type terminals to the wires using an appropriate tool so that the wires do not come loose 3 Use the specified wires connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is
14. or more than 10 seconds 4 Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0 05 0 Mpa 0 5 0 kg cm 5 Stop the operation Press the START STOP button of the remote control unit to stop the operation Press the MANUAL AUTO button when stopping the operation from indoor unit side It is not necessary to press on keeping for more than 10 seconds During the pump down operation make sure that the compressor is turned off before you remove the refrigerant piping Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to rupture and even injury En 6
15. r serious injury of the user ZN WARNING For the room air conditioner to operate satisfactory install it as outlined in this installa tion manual Connect the indoor unit and outdoor unit with the air conditioner piping and cables available standards parts This installation manual describes the correct connections using the standard accessories and the parts specified in this installation manual Have installation work done by authorized service personnel only Do not use an extension cable Do not turn on the power until all installation work is complete This mark indicates procedures which if improperly performed might possibly result in personal harm to the user or damage to property CAUTION When installing pipes shorter than 3 m sound of the outdoor unit will be transferred to the indoor unit which will cause large operating sound or some abnormal sound This installation manual describes how to install the outdoor unit only To install the indoor unit refer to the installation manual included with the indoor unit Be careful not to scratch the air conditioner when handling it After installation explain correct operation to the customer using the operating manual Let the customer keep this installation manual because it is used when the air condi tioner is serviced or moved The maximum lengths of this product are shown in the following table If the units are fur
16. so may cause water leaks Use insulation with heat resistance above 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install insulation around the refrigerant piping If the expected humidity level is 70 80 use insulation that is 15 mm or thicker and if the expected humidity level exceeds 80 use insulation that is 20 mm or thicker If insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use insulation with heat conductivity of 0 045 W m k or less at 20 5 5 Test run Perform test operation and check items For the test operation method refer to the operating manual The outdoor unit may not operate depending the room temperature In this case press the test run button on the remote controller while the air conditioner is running Point the transmitter section of the remote controller toward the air conditioner and press the test run button with the tip of a ball point pen etc end test operation press the remote controller START STOP button When the air conditioner is run by pressing the test run button the OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly Transmitter section Test run button OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Wil
17. t port on the outdoor unit turn the flare nut with your hand To prevent gas leakage coat the flare surface with alkylbenzene oil HAB Do not use mineral oil 3 Tighten the flare nut of the connection pipe at the outdoor unit valve connector 3 way valve Liquid Connection pipe Liquid 3 way valve Gas Flare nut Connection pipe Gas 4 When the flare nut is tightened properly by your hand use a torque wrench to finally tighten it Holding spanner Body side Torque wrench Hold the torque wrench at its grip keeping it in the right angle with the pipe in order to tighten the flare nut correctly 9 52 mm 3 8 in dia 15 88 mm 5 8 in dia Fasten a flare nut with a torque wrench as instructed in this manual If fastened too tight the flare nut may be broken after a long period of time and cause a leakage of refrigerant 5 4 Air purge Always use a vacuum pump to purge the air Refrigerant for purging the air is not charged in the outdoor unit at the factory Tightening torque 32 to 42 N m 320 to 420 kgf cm 63 to 75 N m 630 to 750 kgf cm 1 Remove the cap and connect the gauge manifold and the vacuum pump to the charging valve by the service hoses 2 Vacuum the indoor unit and the connection pipes until the pressure gauge indicates 0 1 MPa 76 cmHg 3 When 0 1 MPa 76 cmHg is reached operate the vacuum pump for at least 60 minutes 4 Disconnect the service hos
18. ther apart than this correct operation cannot be guaranteed Model Pipe diameter Piping length Max height difference type Indoor unit to outdoor unit 30m IN 9 52 15 88 mm sem sm The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are special See the table below Especially when replacing a conventional refrigerant R22 model with a new refrigerant R410A model always replace the conventional piping and flare nuts with the R410A piping and flare nuts Models that use refrigerant R410A have a different charging port thread diameter to pre vent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 inch Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases And always charge from the liquid phase where refrigerant composition is stable En 1 2 2 Special tools for R Pressure is high and cannot
Download Pdf Manuals
Related Search
Related Contents
永井豪記念館 Инструкция по эксплуатации Actionneur rotatif à piston pneumatique 1061 de Fisherr avec Manual de instalação SOLUTIONS 取扱説明書 OPERATOR`S MANUAL 650554 Belkin Bluetooth GPS Navigation System Copyright © All rights reserved.
Failed to retrieve file