KM260 Series Installation and User Guide
Contents
1. 1 LED display 9 150 PPM LED 2 Power on off key LED 10 100 PPM LED 3 Mute key LED 11 50 PPM LED 4 Testkey 12 Level key 5 star key 13 Automatic mode LED 6 Alarm LED 14 Manual mode LED 7 Ventilation LED 15 Stopped LED 8 Fault LED 16 Mode key KM260 Series Carbon Monoxide Detection System 3 2 Zone module keys Power on off Key The on off key switches the zone module ON and OFF When the zone module is OFF it is indicated in the unit LED display and in the power on off key LED indicator Mute key The mute key silences the internal buzzer and disables the alarm output relay When the mute key is active the key LED indicator is red Test key Used to verify the proper working of the LED display the zone module LED indicators and the acoustic buzzer star key The key has two functions 1 Alarm level indication and selection If the zone is quiescent pressing the key will display the pre defined CO alarm level flashing in the unit LED display This level may be changed using the Level Mode and Mute keys Mute increments of 5 Mode increments of 10 Level increments of 100 2 Fault code indication If the zone is in fault condition indicated by the fault warning indicator and the intermittent buzzer pressing the key displays the code of the fault detected The fault codes are 500 Scanning fault 501 Detector fault filament breakage 502 Low line volta
2. 4 KM260 Series Carbon Monoxide Detection System 2 INSTALLATION GUIDE 2 1 Fixing the cabinet to the wall A Fix the cabinet to the wall at an approximate height of 1 5 metres from the floor in a place with easy access The zone module LED display should be at eye level The cabinet must be installed in a clean dry place free from vibrations with a temperature between 0 and 60 C The relative humidity must not exceed 95 There should be no condensation The place of installation should be protected by the CO detection system Risk of mechanical damage must be avoided Create the cable holes you require in the metal cabinet before fixing it to the wall Do not perforate the panel in places other than those indicated Avoid dropping shavings or pieces of removed casing inside the cabinet PG 11 type cable adapters may be used 2 2 Connections There is a three terminal connector shared by all the zone modules for connecting the mains 230 VAC and earth cables The mains fuse is incorporated into the connector see Figure 3 Mains connection In addition each zone module has a nine terminal connector Figure 1 Zone module connector 0 dam dam dam J 1 Three zone line terminals positive negative and data See Figure 2 Line connection 2 Three terminals for the ventilation output relay EXTR 1 common C normally open NO normally closed NC 3 Three term
3. GE Interlogix KM260 Series Carbon Monoxide Detection System Installation and User Guide Version 2 1 April 2004 Kilsen and Aritech are GE Interlogix brands http www geindustrial com ge interlogix emea O 2003 GE Interlogix B V All rights reserved GE Interlogix B V grants the right to reprint this manual for internal use only GE Interlogix B V reserves the right to change information without notice CONTENTS 1 INTO les die RA RE EE EE EE EE N 4 1 1 GeneraldescriptiON EE eae nate Ee SE ES SR ee Ge Ge REG e dee ee eee 4 1 2 System Components EE EE RE eee ede ee als 4 2 Installation Ee OR EE OR OE OE OAR EE HO OP 5 2 1 Fixing the cabinet to the wall uses ieee es GE tienta gee 5 2 21 Connections uta idas dado ta o See 5 2 3 System Startup anoto 6 3 User GUide OR EE RE EE EE EN 7 3 1 Zone mod le keypad EER Rg carl ei A De eg Ee eer 7 3 2 LONE mod le OM EE OE OE AE N EE a ee EN 8 3 3 oek GE de OE EE Aa A aaa 9 3A Configuratio inei RE IN SE N EE N EE EE EN 9 4 Maintenance and Safety ii sere SEE ESE da ad 11 4 1 Systemimaintenanoe iii 11 4 2 Carbon monoxide safety levels ee ee AA Re AA ee ee AA ee ee ee Re ee ee ee AA ee ee Re ee ee ee 11 5 Technical Specifications seil REKE KERE KERSE RR REEKS nie nicas 12 KM260 Series Carbon Monoxide Detection System 1 INTRODUCTION 1 1 General description The GE Interlogix carbon monoxide CO detection system is the ideal solution for detection of d
4. angerous levels of CO gas in car parks and other enclosed spaces where levels of CO gas must be monitored and controlled effectively The detection system is based on the analysis of polyatomic gas molecules in the air and uses a rapid acting under ten seconds SnO2 doped semiconductor housed in the head of the detector CO levels are sent to and displayed in the control panel and ventilation and alarm relays triggered automatically when user defined CO levels are detected System features Easy to use modular design that provides flexible CO protection for 1 to 5 zones Detection response of less than 10 seconds using GE Interlogix KM170 CO detectors Use of up to 15 detectors per zone Coverage from 300m single zone up to 22 500m five zones using a single cabinet Two relay outputs ventilation alarm triggered by user defined CO levels Advanced system testing and self testing functions to ensure reliable detection at all times The CO detection system is available in the following versions Model Zones Cabinet size Extra zones installable KM260 1 1 275 mm x 335 mm x 130 mm 1 KM260 3 3 470 mm x 335 mm x 130 mm 2 1 2 System components 1x cabinet available in two sizes 275 mm x 335 mm x 130 mm for 1 or 2 zone modules 470 mm x 335 mm x 130 mm for 3 to 5 zone modules 1x voltage transformer 1 x mains source connecting header KM170 CO detectors sold seperately
5. e ee ee Re 230 VAC 410 95W Maximum Consumption 2 cccccceceeeeeeeeeeeeeeeeeeeeseeeueaeeeeeeeeeeeees 100 mA per zone module Mains IS SE OR DE N EE OR EE OR eee 500 mA 5x20 mm Zone module input Voltage esse ees ee ee ke ee ee ee ke ee ee ee Re ee ee tees ee ee ke ee naar ke ee ee ee ke ee ee 9 23 VAC Number of relays ie ees EED ee Se ee Ee Ee ER DA ge Se ee Ee Do Se ee Ge Ge De Ee E 3 C NO NC Maximum line lengt EE EES A AET TA EAE ONEA 350 m Maximum number of detectors per ZONE ii se ee ee RR RA ee ee ee GR RA tennet ee ee Ge nenene 15 Measurement ss AR RE EERS E Gee sisi Bes Reg nese 0 to 300 PPM Programmable alarm level ees ee ee ee ee ee ee nro cnn ee ee ee ee ee ee ee ee ee 0 to 295 PPM Selectable ventilation relay levels se ee ee ee ee ee ee ee Ge ee ee ee ee ee ee Re ee ee 50 100 150 PPM LED DIS Play ER tt EE te EERS A EE mates ee N Ee 3 digits Ventilation level indication ee ee ee ee ee Re ee Ge Re ee ee Re ee ee Re ee ee ke ee LED indicator Ventilation modeS ee see ee ee ee ee EE a ee ee ee ee ee ee ee automatic manual stopped Ventilation mode indicatiON ee ee ee ee AR AR Re AR Re AR ee ee ee ee LED indicator Alarm indication EER EE EE ER EE ER GE Ee EO acoustic and LED indicator Fault warning indication sisirin ee Ge RA ee ke ee ee acoustic and LED indicator Operating temperature sis eie Ese RE be ee eddie 0 to 60 C Storage temperature se a ade ciate de ee eed Ee Ge GR ee ie 10
6. ge level 503 Detector missing 504 Excessive power consumption Exit alarm or fault indication by pressing the key Indication will exit automatically if no key is pressed for 15 seconds Level key Used to set the CO concentration level that will trigger the ventilation relay output 8 KM260 Series Carbon Monoxide Detection System Mode key Used to select the different operating modes for ventilation Stopped Manual Automatic Stopped mode disables the ventilation system Manual mode manually activates the ventilation relay output Automatic mode triggers the ventilation output when one of the detectors in the zone reaches the pre defined alarm level Ventilation is preceded by a short user defined waiting period in which the ventilation LED indicator flashes This LED indicator is constant during ventilation Ventilation continues for a short period after CO levels have decreased 3 3 Operating states The CO detection system operates in the following states Quiescent Alarm Ventilation Fault An alarm ventilation or fault state is indicated by the red green or yellow LED indicators on the zone module keypad see section 3 1 Zone module keypad Quiescent This is the normal operating state where no event is indicated The module displays the highest CO concentration level in the zone covered by the module in the display LED Alarm There is an alarm When the alarm level is reached and afte
7. inals for the alarm output relay common C normally open NO normally closed NC KM260 Series Carbon Monoxide Detection System Figure 2 Line connection 1 Positive line 2 Data 3 Negative line Figure 3 Mains connection 1 Fuse pre installed 2 Live AC fused 3 Earth 4 Neutral AC 2 3 System startup Once all connections have been completed and zone detectors installed the zone module may be switched on and a system test performed To do this 1 Press the on off key When the zone module is first switched ON the LED display indicates On until an initial CO reading is provided by the zone module detectors During this initial period the power on off key LED indicator will flash green It will remain lit once the initial CO reading is confirmed Press the Test key This will verify the proper working of the LED display the zone module LED indicators and the acoustic buzzer The number of detectors installed in the zone will also be assessed Any fault discovered will be indicated KM260 Series Carbon Monoxide Detection System Each zone in the CO detection system is controlled and configured by an independent Zone module Zone CO levels are passed to the zone module from the detectors and the highest CO level detected is displayed on the LED display as Parts Per Million PPM of the sampled air 3 1 Zone module keypad OD
8. r a set period for verification the module activates the red alarm LED indicator the alarm output relay and the acoustic signal Ventilation Ventilation is active The green ventilation LED indicator is lit Fault There is a fault Once a fault is detected the module will activate an intermittent acoustic signal and the yellow fault LED indicator The fault code is displayed by pressing the key There is a user defined delay before any fault is indicated by the system Once a fault has been fixed press the Power on off key to reset the system 3 4 Configuration To enter Configuration Mode press the key and the Test key at the same time There are 17 numbered options that may be configured On entering Configuration Mode option 1 Ventilation level 1 is displayed Use the Level Mode and Mute keys to modify numeric values Use the Mute key to modify on off values The key confirms the entry and displays the next option KM260 Series Carbon Monoxide Detection System To exit Configuration Mode use the key to cycle through all options Configuration Mode will exit after the final option Configuration Mode will exit automatically if no key is pressed for 15 seconds Configuration options and their default values can be seen in Table 1 Configuration options and default values Table 1 Configuration options and default values Option Description Default value 1 Ven
9. tilation level 1 50 2 Ventilation level 2 100 3 Ventilation level 3 150 4 Relay alarm activated with alarm ON 5 Relay alarm activated with fault OFF 6 Relay alarm activated with ventilation OFF 7 Relay alarm deactivated with mute ON 8 Missing detector detection OFF 9 Number of alarms detected 0 10 Number of ventilations performed 0 11 Delay time for Mode key in seconds 20 12 Confirmation delay to activate ventilation 60 in seconds 13 Confirmation delay to deactivate ventilation 120 in seconds 14 Idle time to exit mode in seconds 15 15 Confirmation time to alarm activation 20 in seconds 16 Confirmation time to fault activation 120 in seconds 17 Number of detectors in loop Calculated automatically during test procedure after system setup Use the Mute key to reset alarm and ventilation values 10 KM260 Series Carbon Monoxide Detection System 4 MAINTENANCE AND SAFETY 4 1 System maintenance A Do not tamper with zone module circuit board or electronics In the event of a fault only qualified personel should attempt fault repair The built in system and self testing functions ensure that your CO detection system is always in perfect working order For increased safety we recommend Regular inspection and calibration of the system The frequency of such inspections will be decided by environmental factors such as relative humidity excessive dirt or dust and concentration of any other contamina
10. ting gases A log book of all faults reported by the system or the result of an inspection should be kept and the resolution date recorded The log book should be referred to regularly to ensure all faults have been repaired The useful lifespan of GE Interlogix CO detectors is 4 years Detectors and or sensing elements must be serviced or replaced within this time frame 4 2 Carbon monoxide safety levels A Maximum recommended CO levels and exposure guidelines vary from country to country Your detection system should be calibrated to comply with local safety levels and regulations The following table of CO levels and health effects is provided as a guide only PPM 2 minutes 5 minutes 15 minutes 40 minutes 120 minutes Headache 400 PPM Headache Dizziness 800 PPM Headache Dizziness Unconsciousness 1600 PPM Headache Dizziness Unconsciousness Death 3200 PPM Headache Dizziness Unconsciousness Death 6400 PPM Dizziness Unconsciousness Death 12800 PPM Unconsciousness Death KM260 Series Carbon Monoxide Detection System 5 TECHNICAL SPECIFICATIONS Cabinet size 1 or 2 ZONES ee ee ee ee Re ee ee 275 mm x 335 mm x 130 mm Cabinet size 3 to 5 ZONES ee ee ee RA nano RA ee ee 470 mm x 335 mm x 130 mm Mains power supply 0ooooocccccccccoconononccnncconnnononcnnncnnnnnnnnnnn nono ee ee ee e
11. to 70 C MAXIMUM UNI cit 95 12 KM260 Series Carbon Monoxide Detection System ES 1049370