Home
iDIM Family (304, 316, 403) Installation and User Guide
Contents
1. Note The corridor is wired DALI 1 or 2 to DALI 1 or 2 along the corridor Corridor loads and controls can be connected to either DALI output The contributing Dim Solo supplies must not exceed 250 mA on any DALI connection iDim Solos contain DALI power supplies and therefore must always be connected DA to DA and DA to DA 11 Helvar 304 316 403 1DIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Freedom in lighting 3 6 5 Corridor Hold Setup T Mode 5 e Mode 4 for corridor wiring Presence Detection Enabled Absence Checking Enabled Bright Out Enabled Occupancy Timeout 15 minutes Transition 60 seconds d 20 Exit delay 90 seconds A eee E d BBR Spree et SS AS Note he corridor will remain lit when any of the lights are on in single cell offices Office loads and controls must be connected to the DALI 1 output 64 mA current limit limited by Solo DALI 1 supply The DALI 2 output is only for connection from the office to the corridor iDim Solos contain DALI power supplies and therefore must always be connected DA to DA and DA to DA 6 6 Meeting Room Alternative Classroom D Mode 6 Presence Detection Disabled Absence Checking Enabled Bright Out Enabled Occupancy Timeout 19 minutes Transition 60 seconds d 20 Exit delay 90 seconds
2. Exit delay 90 seconds Note For an alternative classroom setup please refer to 6 6 Meeting Room Alternative Classroom N Sau SEERE EEEL DALI 2 i OFFSET 6 2 Single Office Setup Mode 2 C Presence Detection Enabled Absence Checking Enabled Bright Out Enabled Occupancy Timeout 19 minutes Transition 60 seconds d 20 Exit delay 90 seconds OFFSET Optional DALI 1 CL 10 Helvar 304 316 403 1DIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 6 3 Open Plan Office Setup Mode 3 freedom in lighting Presence Detection Enabled Absence Checking Enabled Bright Out Enabled Occupancy Timeout 15 minutes Transition 60 minutes Q 20 Exit delay 90 seconds ote OFFSET EEEE LL i afc ner CPE ELE LLL n Se amai 6 4 Corridor Link Setup Mode 4 e s Presence Detection Enabled Absence Checking Enabled Bright Out Enabled Occupancy Timeout 5 minutes Transition 30 minutes Q 20 Exit delay 90 seconds EEETITTTETTTETTETTTET
3. 1 O 4 2 iDim Networked Important Only available with iDim Sense 315 iDim Ballasts e The adjacent diagram shows the iDim Sense 315 Seale system connected directly to a Helvar 910 920 router aiie via the push wire DALI connectors located on the iDim Sense lt lt T 315 oe e iDim Sense 315 can also be used in conjunction with Helvar Digidim Toolbox systems iii pins reverse of the device CANES a DALI Cable e Using the iDim Sense 315 with a 910 or 920 router will cause the iDim Sense mode selector to be ignored All amp DIGIDIM configuration is done via Designer software where the melee peek iDim Sense 315 behaves like a 312 Multisensor x Panels a Control 5 Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Helvar 4 3 iDim Solo as a PSU treads in lighting e The adjacent diagram shows the iDim Solo working as a PSU e Outputs are paralleled to provide 96 mA of power Ou i Oan e RJ4P4C Connector and Switch
4. Installation and User Guide Helvar IDIM Family 304 316 403 freedom in lighting Product description C The iDim concept is a luminaire based lighting control solution comprising an intelligent sensor iDim Sense 316 an interface unit iDim Solo 403 as well as a range of ballasts EL iDim Combined together they provide a unique standalone solution for intelligent single room lighting applications iDim Sense 316 Standalone This luminaire based sensor provides 6 out of box standalone application modes It connects via Its RJ style connector to the iDim Solo interface module The iDim Sense 315 system version is available to provide additional functionality as PIR extension sensor and as network sensor on Helvar Digidim Toolbox and Router networks iDim Solo 403 The iDim Solo acts as a power supply as well as an interface module to connect Dim Sense DALI loads and a range of user Interfaces iDim Remote 304 The iDim Remote allows the user to easily modify the preset light levels Constant Light or Fixed Light recall store scenes and activate special functions such as 100 hour burn in test and PIR walk in test Another use Is to program advanced settings through use of USB interface and easy to use PC software The Dim remote can also operate as a personal desktop user interface As an alternative solution the Digidim Remote 303 can be used in conjunction with the iDim Sense to modify the preset
5. Note iDim Solo SW1 input operates DALI 1 CL Off and SW2 input operates DALI 2 FL 100 Off As SW1 is located at the entrance of a room switching off SW1 will cause both DALI 1 and DALI 2 circuits to go off 12 Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 LED Feedback freedom in lighting The iDim Sense contains 2 LEDs red and green that provide user feedback for different functions Function JLED Flash Feedback n ee a lee T rY tou 00000 CEOGCE nnn 6066 600GEEEGECE aa PIR Walk Test Mode Sequence repeats until walk test Is complete 100 hour Burn In Mode Sequence repeats until burn in is complete DALI Errors Sequence repeats until error clears a we a i Change from unoccupied to occupied wy Typically follows a PIR detection ae ee Failed Scene Store 4 N Successful Upload from IR Remote lt 7 lt 7 ww an 8 Failed Upload from IR Remote Note iDim Sense LED feedback flashes apply to all iDim units of v5 3 and onwards To leave User Defined mode and reset iDim Sense to default settings at any time hold button 3 4 on the iDim Remote Control for 10 seconds while the remote is in Special function mode 193 Helvar 304 316 403 1DIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Helvar Ordering Information
6. CIL CL Controller Link to See notes DALI 2 Offset Offset Offset FL 100 Sceme Corridor below iDim DALI 1 Clee Cll Cle FL 70 eR Controller Link to DALI 2 Offset Offset FL 70 FL 100 scene 2 Corridor 2 iDim DARK FICO EE 100 FL 100 FL 40 FL 100 Controller Link to DALI 2 FL 100 FL 100 FL 100 FL 40 FL 0 Scene 3 Corridor 2 iDim DARK FL 40 FL 40 PL 40 FL 10 PL 40 PL 40 Controller Te Scene 4 ee FL 40 FL 40 FL40 FL IO FL 20 Table Information In this table iDim Controller refers to Remote Control Switches and Panels unless specified ss iDim Solo SW1 and SW 2 are switch control inputs In modes where DALI 2 is offset from DALI 1 and in Corridor Hold mode they control the level of both DALI 1 and DALI 2 2 In Corridor Hold Mode 5 DALI 2 is only used to connect an office to the corridor 3 In Meeting Room Mode 4 iDim Solo SW1 input operates DALI 1 CL Off and SW2 input operates DALI 2 FL 100 Off As SW1 is located at the entrance of a room switching off SW1 will cause both DALI 1 and DALI 2 circuits to go off General Information Long key presses of a controller give Up Down level control of DALI 1 and DALI 2 They operate independently except when in CL Offset scenes where they operate together Short key presses of a switch give Scene 1 Off control
7. Installation There are 3 possible ways for mounting the iDim Sense to the luminaire External Mounting 1 Cut opening In luminaire 96 5 x 26 mm 0 25 mm 2 Click Fascia to iDim Sense 3 Click iDim Sense into luminaire Th Note Opening dimensions are applicable for a luminaire with a housing thickness of 0 6 mm to 2 4 mm max Fabricate Louvre Adapter 1 Fabricate a louvre adapter to fit at either end of the luminaire Opening dimensions 56 5 x 26 mm 0 25 mm 2 Click Dim Sense into louvre adapter opening 3 Fit complete assembly to louvre Internal Mounting ce Recommended 1 Cut three holes in the luminaire Housing Thickness See adjacent diagram for dimensions 6 Gace amin 2 Insert iDim Sense from inside the luminaire 3 Fabricate a bracket to secure iDim Sense in place 6 G9smm B21mm B95 mn Note Fascia not required when mounting the iDim Sense o internally ee 17mm 17mm Mee 3 2 1Dim Solo Installation Use these screw types when mounting the iDim Solo X vV e Pan head Machine Screw M4 e e Pan head Self Tapping Screw No 8 gt Note Countersunk screws should not be used 3 3 Mounting the optional PIR Restrictor 1 Select a mode before mounting PIR restrictor He As NI www hel iDim Solo Co NIM EI Interface Cp SI Bi KI ta CPN te 2 Position PIR restrictor to cover the area to be hidden 3 Push PIR restri
8. freedom in lighting A large selection of accessories can be used In conjunction with the 1Dim family to support your individual lighting needs Sensors amp Interface Module Accessories x 312 Multisensor lt 8 PIR extension only 50630 iDim Cable Pack of 30 90cm RJ style cable 4P4C crossover C 315 iDim Sense System amp Standalone iDim Fascia Ss 4 white or grey supplied as 316 iDim Sense standard with iDim Sense Standalone other colours optional 403 iDim Solo Digidim 444 Mini Input Unit Interface Module User Interfaces E Dedicated Dim remote EUERE gt USB port for advanced settings and iDim Demonstrator PE EEROR Freeware to simulate the IDim 3 standalone system operation for al Digidim iDim Ready Panels s Mara gasses Bs 121 122 324 129 126 iDim Studio Editor Digidim 303 IR Remote Control d 1 Freeware that allows to create either Standard remote control to modify b graphical user interface applets for the target light levels scene recall i iDim Remote or modify advanced iDim store and recall test functions system settings For detailed information about all Helvar products please visit www helvar com 315 single packaged IDim Sense System amp Standalone including white and grey Be eae ai cae A fascia and PIR restrictor Single packaged iDim Sense Standalone including white and grey fascia and 316 PIR rastrictor 65 mm x 34 mm x 30 mm T
9. light levels recall store scenes as well as activate its specials functions 100 hour burn in and PIR walk test Helvar Data is subject to change without notice www helvar com I Contents Product description iDim Sense 316 Standalone iDim Solo 403 Interface Module iDim Physical Installation Connections Connection Methods Mode Selection Mode Selection Typical Mode Setup LED Feedback Ordering Information Technical Data Helvar Data is subject to change without notice NI OO fF WO gt 10 13 14 19 Helvar tyeodom in lighting www helvar com iDim Sense 316 Standalone The iDim Sense is a luminaire based sensor It combines a movement detector PIR remote control receiver IR and photocell CL in one enclosure The manual mode selector allows the user to easily select one of the 6 out of box application modes Key Features PIR photocell CL and Infrared control IR Easy to select application modes Clip on fascia in different colours Clip on PIR restrictor Mode Selector with LED feedback Installation Notes Multiple mounting options 1 Mount from outside luminaire Click fit 2 Mount from inside luminaire Bracket fit 3 Combined with louvre adapter Adapter fit Isolate the mains supply before installation All cabling must be 230 VAC mains rated when used outside luminaire Movement Detector PIR Coverage with Top Down View 3 0m 4 5 m wit
10. Inputs are not used aon Ou when iDim Solo operates as a DALI power supply a A Note For maximum number of ballasts see 3 ee On manufacturer data iDim Ballasts Daon DA OJO 230 V Not oe OIl DA O1 l DA OJO EE z Heban 1m Not K l riere Nodi Paralleled used a 19 C 50 s 2 iDim Solo eee 4 4 Device Combinations e The adjacent diagram shows all possible device combinations e See table 1 for possible system device capacities using Multisensor 312 iDim Sense the iDim Sense and Solo PIR extension 315 or 316 PIR extension e SW1 and SW 2 are switch control inputs giving scene 1 Q Oo off and level control of DALI 1 and 2 respectively i e PIR movement generates scene 1 when lights are Off or 57 extends the scene already selected when lights areon 9 oo 316 Master RJ Style DA O 1 4PAC Cable DAO p 230 V aes A iDim Ballasts Z Helvar a am Sa DALI 2 Ot SS ye 32 mA DAW O 18 DAO LOT iDim Solo Switch Control Input 1 Switch Gonto Input 2 Son Sao DIGIDIM via DIGIDIM 444 Panels 2 Table 1 iDim Sense and iDim Solo device capacity combinations iDim Sense 316 iDim ballast Ceiling multisensor iDim Sense 315 DIGIDIM Master 2 mA PIR extension or 316 button panel He iDim Solo 15 mA PIR extension 10 mA 10 mA NS om to 27 to 3 to gt up to up to up to 64 mA 10 mA 4 i 5 DALI 2 up to 2 up to 3 up to 3 32 mA The total number of devices de
11. ard ballast style enclosure making it easy to assemble Key Features e Power capability 64 mA DALI 1 32 mA DALI 2 or 96 mA when operating in parallel e 2x DALI outputs e 2x Switch control inputs e jDim Sense connection RJ style 4P4C e Mains connection Installation Notes e All cabling must be 230 VAC mains rated and considered live when operating outside luminaire e solate the mains supply before installation e The external mains supply to the unit must be protected e Install in a restricted access location only e g luminaire housing Helvar Freedom in lighting iDim Solo as Interface Module iDim Sense Master RJ Style Cable oY iDim Solo 4P4C l ahs inte ace Module asa ne a Up te 75 C Switch 10 Control a DALI 2 O O 10O 32 mA DAGO DA 0 0O iDim Ballasts 10O 10 DALI 1 10 64 mA DA O DA IO iDim Solo as a Power Supply Unit PSU Oa Ou Ou li olo iDim Ballasts Helvar 304 316 403 iDIM Sense Solo Installation and User Guide iDim Solo Doc D004735 issue 06_062014Update 12 06 2014 iDim Physical Installation freedom in lighting Below you will find the recommended methods for installing the 1Dim Sense and Solo into your luminaire 3 1 1Dim Sense
12. ctor over the mode selector Caution Do NOT adjust PIR restrictor while it is attached to Ut S the iDim Sense e gt Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Connections freedom in lighting Cable Requirements Note 1 DALI cable must be mains rated and the maximum voltage drop along the length of the cable must not exceed 2 V Note 2 RJ cabling used outside of luminaire fitting must be mains rated Use Alpha 1174C or 6642 Connection Cable Type Cable Length iDim Solo DALI 1 0 mm to 1 5 mm recommended max 300 m a 1 5 mm iDim Sense 316 RJ style 4P4C connector crossover max 3 m between iDim Solo and 1Dim Sense Standalone Switch Control 0 5mm to 1 5 mm recommended ma OU mim Mains Supply Cable 0 5 mm to 1 5 mm Connection Methods Important iDim Solos contain DALI power supplies and therefore must always be connected DA to DA and DA to DA RJ Style 4 1 iDim Standalone iDim Sense 316 oroo is l l _ _ Master Om 1 The adjacent diagram shows the iDim Sense 316 iDim Solo and iDim ballasts connected as a basic standalone 230 V iDim Solo system a Helvar iDim Solo E amp W Interface Module 100 240 V 50 60 Hz EH 40ma ta 10 C 50 C DAIMO DA 1 O iDim Ballasts DA O DA
13. e the upper level threshold for more than 10 minutes If the light level goes below the lower level threshold then the lights revert to Constant Light Power Up Procedure When lights are powered up they will go to 100 for 5 minutes If there is no PIR movement within this time they will go off 0 If movement is detected anytime during this period then the system will start to operate as normal As this is a standard safety feature it is NOT configurable in iDim Studio User Defined Mode iDim Sense enters User Defined Mode as soon as scenes and Settings are stored via the iDim Remote Control When in User Defined Mode the iDim Sense Mode Selector ring will be ignored To leave User Defined Mode and reset to default settings at any time hold button 3 4 on the Remote for 10 seconds Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Typical Mode Setup freedom in lighting Please see below for suggested installation methods for each of the six modes Note The following modes show DALI 1 and DALI 2 when scene 1 Is selected See table 2 for further information Key iDim Sense BOSSI Panels U Switch or E 7 button panel A R iDim Solo _ iDim Ballasts mummu iDim Remote Control 6 1 Classroom Setup Mode 1 s Presence Detection Disabled Absence Checking Enabled Bright Out Enabled Occupancy Timeout 19 minutes Transition 60 seconds d 20
14. f adequate natural light By default bright out settings for all preset Dim modes are enabled Bright out settings can be either enabled or disabled in iDim Studio Bright Out When Off If lights are off and there is enough natural light the lights will go to power save level default 10 when switched on Bright Out When On If lights are on and there is enough natural light the lights will reduce to power save level after 10 mins Bright out Upper threshold Specific threshold above the target light level Configurable using iDim Studio software Bright out Lower threshold Specific threshold below the target light level Configurable using iDim Studio software For example Note f the light level is ever less than the power save level then it will stay at Bright Out When On 10 mins the lower level and not go to A l O eel Natural light Upper threshold qv A the power save level Target Level Lower threshold If necessary the power save level can be set to off 0 via iDim Studio Editor Power Save Level Light Level gt Entry Bright out Constant Light Bright out When scene is selected triggered Lights go to power save level 10 by default if natural light is above the upper level threshold If light level goes below the lower level threshold then the lights revert to Constant Light When scene is already selected Lights reduce to power save level if natural light is abov
15. hout restrictor Egam ggn JEO m die Eaa m aa E nH 4 5m iin i 1m E E Ee DE 2m E l ee 3m 2m 1m Om Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Freedom in lighting Photocell CL Pa Movement detector PIR Remote control t receiver IR Fascia Mode selector Mounting Considerations 7 O A Do not mount sensor in direct line of artificial light sources e g lamps uplighters B Do not mount sensor in direct sunlight Photocell Coverage CL eee F alll eee eee ere NU A gt L 60 3m Doc D004735 issue 06_062014Update 12 06 2014 iDim Sense 316 Standalone Connections 316 DA and DA are for PIR extension use only u ee ee Dimensions mm iDim Sense without fascia Helvar Freedom in lighting Detector locations PIR IR remote control receiver IR and light sensor for constant light CL O95 B21 O95 iDim Sense with fascia 2 Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 3 iDim Solo 403 Interface Module The iDim Solo is used as an interface module to connect the iDim Sense 316 Standalone and iDim ballasts as well as user Interfaces Additionally the iDim Solo can be used as a DALI power supply unit PSU The unit is housed in a stand
16. mm Material housing Non flammable polycarbonate halogen free ee Colour housing Traffic White RAL 9016 gt 3 o 3 Bracket screws 2x Nob y 3 5 mm x 20 mm lt BEAR pan pozi head screws 3 es Operating conditions ae a gas Yon een 3 Ambient temperature 0 C to 40 C l C Relative humidity Max 90 non condensing T k 19mm Storage temperature 10 C to 0 C x E Conformity and standards EMC emission EN 61000 6 3 oa An EMC immunity EN 61006 1 Safety EN 60950 1 Environment Complies with WEEE and RoHs Dimensions directives 2da Helvar 30 mm C NI Em trace Modiji 14 2 mm Cc 100 240 V 50 60 Hz Cp Ni Em om Te 102 mm 112 mm al SS 121 mm 15 Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014
17. of DALI 1 and DALI 2 together except in Meeting Room Mode 4 Refer to point 3 above Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Freedom in lighting The following settings can be modified using the Helvar iDim Studio software Occupancy Timeout Time when PIR detects no movement and maintains level before moving to transition timeout e g 15 mins Transition Timeout Lights are lowered to energy saving level for a specific time before switching off e g 60 secs For example Relative light level e g 15 mins e g 60 secs Presence Presence Detection enables PIR movement to switch on lights This function can be either enabled or disabled Absence Absence Detection enables automatic switch off of lights This function can be either enabled or disabled iDim Remote Controller Scenes 1 4 DALI 1 and DALI 2 outputs operate as a combination of Constant Light CL Fixed Light FL and Offset These terms are discussed in greater detail below The Constant Light and Fixed Light level settings can be modified using the 1Dim Remote Control or a DIGIDIM button panel For further information on these settings see iDim Remote User Manual D004744 Constant Light Constant Light CL is a method of automatically controlling the level of the system s lights by utilising the natural light of an area and adapting the light level accordingly This setting i
18. pends on the overall combination 10 mA is consumed by one iDim Sense Master unit iDim Solos contain power supplies Always ensure you do not exceed a current of 250 mA on any DALI connection lvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Helvar Mode Selection freedom in lighting There are 6 default modes which can be set by turning the mode selector located on the sensor unit 1 To locate mode 1 Classroom mode rotate the mode selector counterclockwise until it stops 2 If changing modes during power on the red LED will blink 1 to 6 times to indicate mode selected Note Ensure that the PIR restrictor is not attached to the iDim Sense during mode selection i S 4 CLASS SINGLE OPEN PLAN CORRIDOR CORRIDOR MEETING ROOM OFFICE OFFICE LINK HOLD ROOM Occupancy l 15 min Sannin 15 min 5 min 15 MIn 15 MIR Timeout TIMING SB e ele Table 2 Default iDim configuration Transition 1 min 1 min 60 min 30 min 1 min 1 min Timeout level 20 20 20 20 20 20 BRIGHT OUD When Off sf sf VW sf sf Enabled Disabled Enabled Enabled Enabled Enabled Disabled PRESENCE Disabled Manual On Auto On Auto On Auto On Auto On Manual On Enabled Enabled Enabled Enabled Enabled Enabled Enabled ABSENCE Disabled Auto Off Auto Off Auto Off Auto Off Auto Off Auto Off iDim DALI 1 Cli Cie Clee FL 100
19. ray of 30 pieces non packaged iDim Sense Standalone including 30 pieces 31630W white fascia and PIR restrictor 379 MM x 232 mm x 32 mm 316306 Tray of 30 pleces non packaged iDim Sense Standalone including 30 pieces 395 mm x 232 mmx 52mm grey fascia and PIR restrictor 403 Single packaged iDim Solo Interface Module 123 mm x 32 mm x 22 mm 40330 Tray of 30 pieces non packaged iDim Solo Interface Modules 367 mm x 309 mm x 30 mm or Set of 30 pieces iDim Cable RJ style connectors 4P4C each 500mm length RO 14 Helvar 304 316 403 1DIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Technical Data freedom in lighting Connections Connections PC to remote USB 2 0 A Cable to Mini B Cable Power ae tae Power supply 2 x AAA LRO3 1 5 V batteries RJ Style 4P4C a i Connector iDim Sense 7 05 1 5mm Range ose as 316 ee Operating range Approx 10 m Ox Lomm Operating frequency 36 kHz Remote control functions Infrared remote control Modify preset light levels Constant light or fixed light Scene store and recall Activate special test functions Na Ine N N DALI 64 mA _ CE DALI 2 32 mA _ Mechanical data G Dimensions 99 mm x 21 mm x 110
20. s configurable using the iDim Remote however It Is important to remember constant light should always be configured in a darkended room or at dusk to avoid natural light affecting the configuration of the target level Fixed Light Fixed Light is where the load output is NOT adjusted by the Light Sensor Lights will remain at at a certain level unless altered Offset The Offset figure is the difference between DALI 1 and DALI 2 When working with CL the offset amount will maintain the level difference no matter how lighting condtions change Constant Light CL amp Fixed Light FL The adjacent example shows DALI 2 operating with Fixed Light settings Only DALI 1 Constant Light levels increase decrease subject to natural light Relative changes Light Level DALI1 DALI2 DALI 1 DALI 2 DALI 1 DALI 2 Helvar 304 316 403 iDIM Sense Solo Installation and User Guide Doc D004735 issue 06_062014Update 12 06 2014 Mode Selection freedom in lighting Constant Light CL amp Offset The adjacent example shows the default Offset of 20 When more natural light is detected by the Constant Light sensor DALI 2 Offset will lower the light level at the same rate as DALI 1 CL while maintaining the 20 gap aoe Light Level DALI 1 DALI 2 DALI1 DALI 2 DALI1 DALI2 Bright Out Bright out is an optional feature of constant light operation that allows further energy saving by reducing light level during times o