Home
Supply air hood JSI-UV Installation
Contents
1. H 500 mm B 500 mm 25 30 40 i 100 50 60 80 100 120 160 200 240 dm s 200 300 P Pa Measured pressure difference Pa H Height of the supply air unit mm B Width of the supply air unit mm 500 700 1000 mh K coefficient supply air Hood height Supply air unit 540 330 540 Width mm 200 500 500 Height mm 500 290 500 K1 m3 h 77 0 96 0 192 K2 I s 21 4 26 7 53 3 Q Kx Pm Pm Q K Pa WWW JEVEN COM All rights reserved Top ventilation for top chefs VAES JEVEN Kitchen ventilation Supply Air Hood JSI UV CLEANING OF THE HOOD SURFACES Hood surfaces should be cleaned during normal kitchen cleaning Normal washing detergent of the stainless steel may be used CLEANING OF THE FASCIAS Fascias should be cleaned during normal kitchen cleaning About twice a year it is advisable to detach the fascias and wash them in a commercial dishwasher These fascias are easily removed by lifting them up tilting the lower edge towards you and then lowering the fascia out of the canopy 25 8 2015 J even Top ventilation for top chefs All rights reserved WWW JEVEN COM
2. JEVEN Kitchen ventilation WAC K Supply Air Hood JSI UV ADJUSTMENT OF THE EXHAUST AIR Dampers with locking screws Hoods are supplied with exhaust dampers Dampers are situated behind the filters inside the filter box All dampers should be open before when starting the adjustment work These dampers are only for balancing the hoods Use other dampers and fan adjustment when adjusting the total airflows K COEFFICIENT EXHAUST AIR 120 1 2 3 4 56 7 8 Number of filter units 100 Pm Pa A o 2530405060 80100 160 240320 500600 1000 l s ias nun 3M 800 100 200 300 500 700 1000 2000 3000 m h 1400 Q Kx Pm Pm Q Kf Pa Recommended pressure difference 40 60 Pa WWW JEVEN COM All rights reserved J even Top ventilation for top chefs NG JEVEN Kitchen ventilation Supply Air Hood JSI UV INSTALLATION OF THE FASCIAS Attention There should be min 15 mm free place between the ceiling and the upper point of the fascia Attention Min 15mm The fascias are easily installed by lifting them up so that the upper lip of the fascia goes inside the hood opening Tilting the lower edge towards the hood and then lowering the fascia until its lower edge is on the same level as the hoods lower edge J even Top ventilation for top chefs All rights reserved WWW JEVEN COM JEVEN Kitchen ventilation MACE E Supply Air Hood JSI UV AIRFLOW MEASURING POINT K COEFFICIENT A Pm Supply air
3. Pm Supply air acd Exhaust air Exhaust air ADJUSTMENT OF THE SUPPLY AIR Hoods are supplied from factory with suitable air flow rates for pressure loss 25 35 Pa When fine adjustment is needed detach the supply air fascia and adjustment units All supply air fascias should be placed on when the measuring of the air flows is in operation Adjustment units in the canopies are only for balancing the air flows of the supply air units The dampers should be placed on the main and branch ducts for adjustment of the total air flows Adjustment unit WWW JEVEN COM All rights reserved J even Top ventilation for top chefs VAE JEVEN Kitchen ventilation Supply Air Hood JSI UV ADJUSTMENT OF THE SUPPLY AIR PATTERN By turning the vertical guide profiles inside the fascia pattern of the air flow can be changed O 1 way throw 2 Displacement throw 9 2 way throw M Ao ERE LII ARE Throw upside Factory setup Throw downside By turning the horizontal guide profiles inside the fascia can throw direction be changed The fascias are supplied with adjustable personal supply air nozzles The kitchen staff can personally adjust the air flow pattern with the help of these nozzles WWW nmi MW WN TY J even Top ventilation for top chefs All rights reserved WWW JEVEN COM Supply Air Hood JSI UV SUPPLY AIR MEASUREMENT CHART AND K COEFFICIENT H 500 mm B 200 mm H 290 mm B 500 mm
4. Power unit is plugged to 230v 16A AC outlet with the included cable Commissioning Make sure all the cables are correctly fitted and that they are intact Check that the pressure hoses are in good condition are not pinched or become detached from the transport The power unit has access to control start and stop of the fan through relay connection Fan Connect the power unit with the supplied plug into a 230V outlet which is secured to 10A and turn on the power unit with the switch mounted on the chassis of the power unit When the device is switched on the display panel starts Make sure that the exhaust fan is on and is operating at the right air flow Wiring diagram Display panel Pressure sensor x 5 components marked with broken line are not included in the delivery x QC y A ppliancelsocket 16A 230V 16A 230V 12V l l 230VAC 16A eee l Safety switch f Power unit UV frame WWW JEVEN COM All rights reserved J even Top ventilation for top chefs zelum JEVEN Kitchen ventilation Supply Air Hood JSI UV UV UNIT MAINTENANCE UV frame UV lamps are mounted in a stainless steel frame The frame includes two special transformers Each frame has its own electrical power cable connection which must be removed for maintenance Only an electrician may open the electricial components of the frame UV lamps UV lamps must be clean to provide full effect If they aren t clea
5. Top ventilation for top chefs Supply air hood JSI UV Installation adjustment and guide Leste ALL Mel JEVEN Kitchen ventilation Table of Contents Installation of hanging brackets 3 Fixture points and connecting the hood modules 4 Installation of glasses 5 Light fittings 6 rei I m m Installation of covering boards 7 pmi TM EN Installation of UV unit 8 9 m rag Maintenance of UV unit 10 11 Installation of grease filters 12 Adjustment of exhaust air 13 Installation of the fascias 14 Air flow measuring points and location of k coefficient sticker 15 Adjustment of supply air pattern 16 Supply air measurement chart and k coefficient 17 Cleaning 18 Contact us jevenGjeven fi 010 231 2030 J even Top ventilation for top chefs All rights reserved WWW JEVEN COM JEVEN Kitchen ventilation WAC Supply Air Hood JSI UV INSTALLATION OF HANGING BRACKETS 1 Hanging bracket 2 Bolt 3 Corner profile 4 Hanging bar not included in the delivery Hanging brackets should be mounted in the corner profiles with help of the bolts ALTERNATIVE 1 Hanging bracket 2 Bolt 3 Corner profile 4 Hanging bar not included in the delivery Hanging bracket can be also mounted inside the corner profile close to the lower edge of the hood Holes for this installation should be drilled to the profile on the site This alternative installation is advisable when the hood should be mounted on the cor
6. n fat will burn onto the tube which reduces air purification Spray tubes with a tergent with high pH 13 Since this is aggressive protective gloves and goggles are required Then rub the pipes gently with a damp cloth The frequency of cleaning should be done depending on the production in the kitchen Normally once a month Replacement of UV lamps Contact retailer for more information System should be resetted after replacing the lamps Only qualified service person shall reset the system Always switch off UV lights before starting maintenance Blue light is harmful to the eyes Switch off the lamps by pressing Stop button in display panel Open the filter unit cleaning door by lifting it up and pulling it out Remove cyclone filters by dragging them out and wash them in dishwasher Dry filters before installing them back Install cleaning door back to its place Press Start button to start up the system Cleaning interval for different parts of the UV filter unit is kitchen specific On the next page there are some examples of maintenance intervals J even Top ventilation for top chefs All rights reserved WWW JEVEN COM JEVEN Kitchen ventilation WAC Supply Air Hood JSI UV UV UNIT MAINTENANCE Mesh filter School kitchen every other month Restaurant kitchen once a month Wok Asian cuisine once a week Open cleaning door and pull mesh filter out of the chamber Wash the filter in dishwasher Let the filter d
7. ner of the kitchen WWW JEVEN COM All rights reserved J even Top ventilation for top chefs NG JEVEN Kitchen ventilation Supply Air Hood JSI UV FIXTURE POINTS AND CONNECTING THE HOOD MODULES 1 Hanging bar not included in the delivery 2 Hanging bracket 3 Nut 4 Bolt 5 Corner profile 6 Hexagonal tool The hood shall be installed by hanging bars f ex M8 These bars are not included in the delivery Holes for the hanging bars should be drilled to the ceiling of the kitchen by using the shown fixture points Recommended height position of the hood is 2100 2200 mm Install plastic protective corner profiles on the lower end J even Top ventilation for top chefs All rights reserved WWW JEVEN COM JEVEN Kitchen ventilation MENCE Supply Air Hood JSI UV INSTALLATION OF GLASSES Lift up the glass into upper moulding and let it down into lower moulding Stroke silicon on the corners of the glass Stroke silicon by using a wet finger WWW JEVEN COM All rights reserved J even Top ventilation for top chefs Nixes JEVEN Kitchen ventilation Supply Air Hood JSI UV LIGHT FITTING 1 Light fitting 2 Cable 2 0m Every hood module incorporates as standard a recessed fluorescent light fitting Light fitting IP 65 67 is supplied with cable which should be connected to brach box not included in the delivery and light tubes All tubes are standard white fittings Wiring diag
8. notified immediately UV light frames should be unpacked and carefully placed on a flat surface since the UV lights are very sensitive Make sure all the lights are intact Keep the UV light framework in a dust free environment Contents of the package 1 Pressure sensor J Used to make sure unit is running with proper pressure and flow D i Should there be something wrong with the fan or for example a hatch is opened on the filter unit the specific UV framework will shutdown to prevent injuries 2 UV frame is made from stainless steel and contains 6 UV lamps Connector for 230v is mounted on the right side 3 Control panel 3 5 touch panel with Windows CE 6 0 OS integrated to hood 4 Power unit Power supply In 230V AC Out Control panel display 12V Pressure sensors pressure 1 5 12V UV frame filter 1 5 230V 8A relay controlled Fan control fan 230V 8A NO relay for external connections Alarm alarm 230V 8A NO relay for external connections Connections In Schuko connector 230V Out UV frame filter Mini Fit Jr 3 pol230V Control panel display Micro Fit 5 pol feed RJ45 communication 1 C to the display unit Pressure sensors pressure 1 5 Micro Fit 3 pol 12V 4 Fan fan Mini Fit Jr 2 pol 1x2 Alarm alarm Mini Fit Jr 2 pol 1x2 feet 1 2 2 4 S 1 E A afeafe ais aisah J even Top ventilation for top chefs All rights reserved WWW JEVEN COM JEVEN Kitchen ventilation WAC Su
9. pply Air Hood JSI UV UV UNIT INSTALLATION 5 Mesh filter for air equalization steady air speed improves UV light s power eo 6 Cyclone filters Used as first filter before the wire net and UV frame Warning Ultraviolet light is harmful to the eyes UV light can not be watched without approved safety goggles UV unit must always be switched off during maintenance Installation Open the filter unit cleaning door by lifting it up and pulling it out Install UV connection with external connector outward and to the right side connect the power cable which is in the filter unit to the connector on the UV part Push the UV frame inside the filter unit on the top of upper L lists Install mesh filter below the UV frame on top of the lower L lists Close cleaning door Pressure sensors are mounted from the factory in each filter the distance between pressure sensors and power unit can be extended with the splice cables that are enclosed Each cable is numbered so that the no 1 is connected to the no 1 etc Power unit and control panel are pre installed on the hood at the factory Electric cables between the power unit and the UV frame will be included in the package and the cables are numbered and the numbering corresponds to the UV frame numbering Power unit is designed such that it must be installed indoors where the ambient temperature is below 30 C The display panel is mounted on the right side of the hood
10. ram ET Light L H I N O Ql L1 9O branch box not included in the delivery REMOVING TUBES 1 Cover 2 Lath 3 Screw 4 Tube Loose both screws 3 of the lath 2 Remove the lath Turn the cover 1 to other side Remove the tubes J even Top ventilation for top chefs All rights reserved WWW JEVEN COM JEVEN Kitchen ventilation WACA Supply Air Hood JSI UV INSTALLATION OF COVERING BOARDS Boards shall be placed to right height and the holes shall Il be ri d be drilled and the board shall be rivete WWW JEVEN COM All rights reserved J even Top ventilation for top chefs MES JEVEN Kitchen ventilation Supply Air Hood JSI UV UV UNIT INSTALLATION Delivery UV filtering system consist of power unit integrated into the display cover pressure sensors for monitoring the pressure and flow the filter with cyclone filter wire net and UV light frame Filter units are supplied either separately or mounted on the roof of a kitchen hood Cycloe filter fine filter and UV light frame is packed separately for mounting and wiring in the workplace The system consist of one or more filter units an UV light frame for each filter unit apressure sensor for each filter unit and a single power unit to control up to five filter units and it s controlled with a touch panel Unpacking At delivery check the wrapping for any damage during transport Any damages must be
11. ry before installing it back UV frame UV lamps The annual need for maintenance School kitchen 1 2 times a year Restaurant kitchen 3 4 times a year Wok Asian cuisine 8 12times a year Clean the frame and lamps with dishwashing liquid and damp w DO NOT put the frame in dishwasher If the frame is particularly dirty use a cleaning agent with a high PH value PH 13 Cyclone filters School kitchen once every two weeks Restaurant kitchen once a week Wok Asian cuisine every day Filters cleaning interval depends on the kitchen utilization In general filters should be cleaned on the basis of appearance Wear protective gloves when handling the filters The filters are removed one by one by pulling them out gently along the rails Grasp the filters as shown Do not touch the top or bottom edges of the filters Low viscosity grease is poured into a grease collection container Filters are washed in the dishwasher turned upside down Clean filters are pushed along the rails back in place WWW JEVEN COM All rights reserved J even Top ventilation for top chefs Nee JEVEN Kitchen ventilation Supply Air Hood JSI UV INSTALLATION OF THE GREASE FILTERS Grease filters should be mounted by sliding them in the filter housing carefully one after one The blind filters should be mounted as same as normal filters bh a 2 J even Top ventilation for top chefs All rights reserved WWW JEVEN COM