Operating Instructions Fire Alarm System EBL512
Contents
1. 27 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 10 Disable Re enable all control extinguishing and ventilation outputs All control outputs programmed as type 0 control general 1 fire ventilation 2 extinguishing system can via menu H2 B8 be collective disabled for one more or all control units This is indicated by LED Disablements L8 They will remain disabled until they are re enabled again via menu H2 B8 See also chapter Disable Re enable all control exting and ventilation outputs H2 B8 page 91 2 Also the Extinguish equipment output on the German FBP interface board 1583 28 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 11 Evacuate This function is only valid for Belgian British Standard Hungarian and Ukrainian conventions S W version gt 2 2 3 A front with the push button Evacuate P5 is also required As from version 2 3 x one programmable input per c i e can as an alternative be used to _ turn ON the Evacuate function When the push button Evacuate P5 is pressed all outputs programmed for sounders type 3 alarm devices will be collective turned ON steady This is indicated by the following information in the alphanumeric display Evacuate i
2. 6 1 2 System information on the bottom second row A user definable 40 characters text created and downloaded via Win512 System Properties The text is valid for the system i e it is shown in all control units One example YYYY MM DD BL512 CU XX hh mm ss Panasonic Electric Works F amp STE AB al 21 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 7 Access levels The control unit has six access levels for different kind of users Access level 0 Door closed Anybody Scroll browse through the queued alarms Access level 1 Open door Fire brigade personnel Fire alarm handling key is required Access level 2 Access code for Building occupier Installation handling level 2 or 3 or 4 monthly tests is required disablements etc Access level 3 Access code for Service personnel Service maintenance level 3 or 4 is required Access level 4 Access code for Service Service commissioning level 4 is commissioning the system etc required engineer Access level 5 Access code for Service PC Win512 connection level 5 is commissioning to EBL512 required engineer The access codes can be changed To change a code you have to know the valid code or use a code for a higher access level 7 1 Access level 0 With the door closed anybody has access to the push butt
3. Fax 46 0 40 697 70 99 info fste eu pewg panasonic com www panasonic fire security com woa E es E mi ISO 9001
4. If the CU restarts in conjunction with this fault the synchronization will start automatically otherwise it has to be started via this menu 136 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Press Return to menu S10 Or press 1 and A to start the synchronisation or press A to go directly to the field Synchronization completed Scroll or press Return to menu H8 Scroll or press Return to log off 137 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 12 Change access code for maintenance H8 S11 For security reasons the default code should be changed Access According to chapter Access code for maintenance see page 125 Scroll to menu S9 Enter the old code the The digits are replaced new code and the new in the display code again The code was not correct Try again The code was correct and is now changed to the new code Scroll or press Return to menu H8 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 74 If the valid access code is unknown a back door code is available 138 Panasonic Electric Works Fir
5. Several control units connected via a TLON network co operating control units Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater Brief explanations to the words expressions to be found in connection with a network See also separate TLON Technical description TLON TeleLarm Local Operating Network a LonWorks based network for communication between several units nodes The protocol is LonTalk and the transmission works with doubly terminated bus topology Echelon FTT 10 To connect a control unit to the network a TLON connection board is plugged in the control unit Old installations Some control units not prepared for network connection could be connected via a serial interface and a Gateway A network can be one sub net FTT 10 or several sub nets connected via routers In the TLON Network a sub net a channel LonWorks A summing up name for the market of Echelon Corporation Inc technology 10 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 2 14 2 15 2 16 2 17 2 18 2 19 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Repeaters are used to increase the maximum cable length node to node in a network Router or Repeater is the same type of unit different configuration All network programming configuration are made with the PC program TLON
6. The buzzer in the control unit will sound for e pre warning 0 8 5 sec e 2 zone dependent or 2 unit dependent fire alarm When only one zone or one zone address alarm point is in alarm status 0 8 5 sec e Quiet alarm 0 8 5 sec e fire alarm 0 4 0 4 sec e fault continuous e disablements and faults 1 sec directly after the door to the C U is closed e activated interlocking input 0 8 0 8 sec if this option is selected via Win512 Press Silence buzzer P2 to silence the buzzer In case of a new alarm or if the push button Silence buzzer is pressed again the buzzer will automatically sound again NOTE This is also valid for pre warning co incidence alarm etc Silence buzzer by open door In Win512 System dialog box can the function Silence Buzzer by Door Switch be selected The buzzer will then be turned off as long as the control unit door is open This function is a violation to the EN54 2 standard Old front For the function described above the new front with the push button Silence buzzer P2 is required The old front without the push button Silence buzzer results in the following function The buzzer is silenced via the control unit door Switch i e the buzzer will be silent as long as the door is open EBLS512 c i e 1550 This unit has no front The built in buzzer is always disabled Not valid if the buzzer is silenced by the open door
7. Table showing the algorithms and the shortenings respectively 99 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 26 5 1 Operating Instructions Fire alarm system EBL512 V2 5 x Algorithm Short name nnnnnn Normal sensitivity amp Normal detection 15 s N 15 High sensitivity amp Normal detection 15 s H 15 Low sensitivity amp Normal detection 15 s L 15 Normal sensitivity amp Slow detection 35 s N 35 High sensitivity amp Slow detection 35 s H 35 Low sensitivity amp Slow detection 35 s L 35 Heat algorithm Class A1 Al Heat algorithm Class A2 S A2 Heat algorithm Class B S B Decision algorithm Dec Default is N 15 and A1 respectively Reset of a week average sensor value If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be set to the default value otherwise the new clean sensor will inherit the old sensor s value It is possible to clear the week average sensor value for each sensor individually see chapter Clear weekly average H8 S5 page 130 See also chapter Acknowledge SERVICE signal H8 S4 page 129 NOTE Authorised service personnel only must do the reset to default value Used incorrectly it can cause nuisance fire alarms 81 If some other short name is wanted it can be changed in Win512 Up to six characters can be used In
8. When the AA function is enabled indicated by the LED Fire brigade tx delay L16 the indications print outs actions etc are as for a normal fire alarm except the c i e output for routing equipment fire brigade tx will not be activated The AA alarm has to be acknowledged within an acknowledge time and reset within an investigation time otherwise the output s for routing equipment fire brigade tx will be activated See EBL512 Planning Instructions for more information regarding the AA function Acknowledgement and reset of the AA alarm can be done on a Display unit 2235 an AA unit 1735 1736 or an AA controller 1740 See also chapter Alarm reset page 43 2 zone address dependence co incidence alarm When only one zone or one zone address alarm point is in alarm status the buzzer sounds 0 8 5 sec and there is a Co incidence alarm presentation in the display Co incidence alarm detector ZZZ AA user definable text message or 4 In the Polish CNBOP and Czech conventions the push button Evacuate P5 can be used for AA Acknowledge LED Acknowledge on 2235 is indicating that the push button Acknowledge has been activated A busy system can cause a time delay up to 10 seconds before the fire alarm is acknowledged 42 Tf two or more zones or units zone addresses dependent on each other are in alarm status at the same time normal fire alarm will be activated in
9. A to accept to perform monthly test or scroll jump to the follow ing menus H2 H10 Explanations Action in the table use push button key e g signed Access Text in display in the table what is shown in the alphanumeric display in the control unit c i e Comments in the table Comments to the text in the Action and Text in display columns Use Tt and J to scroll between the main menus H1 H10 Use A to accept Some main menus have sub menus Use tT and to scroll between the sub menus e g B1 B9 Use A to accept NOTE The menus are circular i e if you scroll with 4 and the last menu is reached the first menu comes up next Quick jump can be used within each menu e g in menu H1 press 6 for a quick jump to menu H6 1 and 0 within 1 sec 10 Instead of a menu identification e g B1 the letter L can be shown which means that it is a List Use 1 and to scroll in the list Use lt and gt to move the cursor in a menu Use Return to return from a sub menu to the main menu H1 H10 Use Return to log off from a main menu H1 H10 There will be an automatic log off 60 minutes after the last action i e if the key pad or a push button has not been used for 60 min 77 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 23 Perform monthly test H1 The con
10. AN A Test of routing equipment 0 The LED Test mode is il wee 0 No ACCEPT turned OFF Some national regulations also require a routine test of the routing equipment Press A for no test and press 1 and A to start such a test The following will happen in the system e The c i e Fault tx output will be de activated indicated by the LED Fault tx activated L11 A 60 seconds count down starts e After 30 seconds also the c i e Fire brigade tx output and corresponding programmable outputs type 4 routing equipment will be activated indicated by the LED Fire brigade tx L15 e After another 30 seconds the test will be ended and the outputs and LEDs will return to normal 1 A Test of routing equipment in progress nn starts at 60 and will nn seconds left count down to 00 Monthly test is completed ACCEPT Perform monthly test Scroll or press Return ACCEPT H1 log off 74 This output is activated in normal state 79 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x NOTE_1 During the test the following information will be shown in all other c i e displays Zones in test mode 001 002 003 004 In DBI Danish convention only one zone NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will not be a fire alarm activa
11. HW A HW e g a printed circuit board has e atype number e g 1556 e an article number often the type no and sometimes is a country code added e g 1556SE e aproduct name e g Main Board 128 addr e ap c b number e g 9261 3A and can also have a configuration e g CFG 1 and a revision e g REV 2 e sometimes a S W S W A S W has e aversion number e g V2 5 x e sometimes additional information such as Convention different functions facilities Language Number of addresses etc PC S W A PC S W is a program used for programming commissioning etc It has a version number File name K PRO FIRE 512 Doc 2 5 x MEW01002 Rev doc Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 2 Operating Instructions Fire alarm system EBL512 V2 5 x Definitions Explanations 2 1 2 2 2 2 1 2 2 2 2 2 3 2 2 4 2 2 5 2 2 6 2 2 7 Definitions explanations abbreviations etc frequently used or not explained elsewhere in the document PEWF amp STE AB Panasonic Electric Works Fire amp Security Technology Europe AB Alarm points Units which can generate a fire alarm in the control unit i e analog detectors sensors conventional detectors manual call points etc Smoke detector Analog and conventional photoelectric optical smoke detectors are available Sensor Sensor Analog detector Analog detector Contains a
12. If not scroll or press Return to menu H2 Scroll or press Return to log off 87 Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 5 x MEW01002 24 6 Rev Re enable control output H2 B6 Disabled outputs are listed in menu H4 U1 from which it is also possible to get a print out When all control outputs have been re enabled The LED Disablements L8 will be turned OFF if there are no other disablements in the system Action Access Scroll to menu H2 Scroll to menu B6 AN Depending on the chosen type 0 1 2 3 resp 4 the following will be shown Text in display Disable or re enable Disable zone ACCEPT H2 ACCEPT B1 Re enable control output Re enable control output type 0 ocroopunit 12S 225R SERE 4ZES ACCEPT ACCEPT B6 4 ES not valid in Swedish SBF convention Re enable 00 0000 output 0 Re enable Control unit 00 SO Re enable Control unit 00 RO ACCEPT Re enable output 0 ACCEPT L Re enable output for extinguishing controll unit 00 relay board 0 ACCEPT L system on 1583 board CU 00 88 Comments According to chapter Access see page 77 Press 0 RU4 2265 or SU4 2262 2263 or MIO 3361 or ASI 3377 or ASB 3378 1 S0 S3 2 RO R1 3 Relay board 1581 4 1583 board output Ex
13. MEW01002 2 2 8 2 2 9 2 2 10 2 2 11 2 3 2 4 2 5 2 6 2 7 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Addressable A unit with a built in address device i e each unit is individually identified handled and indicated in the c i e The unit can be an I O unit with a zone line input to which one or more conventional alarm points can be connected Old detector Old installations Conventional detector with a closing contact i e a short circuit no alarm resistor or a detector with two breaking contacts Conventional zone line input External line Input intended for one or more conventional alarm points End of line device in the last alarm point Old installations ADB Addressable zone interface input intended for one or more conventional alarm points End of line resistor in the last alarm point ADB input Addressable zone interface Old installations Ext line conventional zone line intended for one or more conventional alarm points End of line resistor in the last alarm point Output unit Addressable unit with programmable control outputs Connected to a COM loop see below Output Control output Defined or programmable function Relay output or voltage output supervised monitored in the c i e or an output unit Short circuit isolator ISO Addressable unit for automatic disconnection of a part segment of a COM loop see below in case of a
14. Site specific data i e all the installation programming downloaded from Win512 SSI EBL512 settings downloaded from Win512 S W Software i e the control unit system program Safe shut down of control unit menu H8 S8 will save the SSW data in a Flash ROM before you power off the control unit Before the first Safe shut down this memory is empty After each Safe shut down the latest SSW data is saved When the power supply returns the control unit RAM working memory will after the restart read the SSW data saved in the Flash ROM 19 Action Data etc which Data etc which will be deleted will be not deleted Control unit power OFF a n F SSI then power ON again RESET jumper JP4 on the SSD SSI main board 1556 S W SSW Reset command from Win512 FFD SSD SSI or TLON Manager S W SSW amomanciiy due to external SSD SSI disturbance S W SSW Automatically after download SSD SSI of site specific data SSD via a S W SSW PC amp Win512 NOTE During restart the following will happen The Fault tx output will be activated Outputs S0 S3 programmed as normally high will be low for a few seconds Restart affects the control unit where it is performed and that control unit s data in a system 70 If this memory is empty when the power supply returns new week average sensor values will be calculated within two minutes During the two minutes all fire alarms from analog smoke detect
15. conventions this button is used to disable all zones in alarm 17 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x LED indicators on the Control Panel CP LED indicator Indicating General fault yellow Fault s i e not acknowledged fault s and or acknowledged but not corrected fault s Disablements yellow Something in the system is disabled disconnected NOTE Also valid for Single encapsulated reset Test mode yellow One or more zones are in test mode Door open yellow A door is open L11 Fault tx activated yellow One or more not acknowledged faults in the system and the output Fault tx routing equipment is activated i e this output must not be disabled L7 L8 L9 10 L Test of routing equipment in progress see menu H1 L12 Service yellow One or more sensors have reached the service level See menu H4 U6 Fault Disablements One or more outputs type 3 alarm device in the Alarm devices yellow system are disabled Blinking One or more supervised outputs type 3 alarm device have generated fault s L14 System fault yellow EBL512 is not running because of S W CPU memory fault Fault Disablements Output s for fire brigade tx routing equipment Fire brigade tx yellow is are disabled via menu H8 S1 or H2 B3 or via an open door Blinking Routing equ
16. to ACCEPT S6 return to menu H8 Scroll or press Return to log off 131 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 8 Test alarm devices H8 S7 The programmable outputs type Alarm device can be collectively activated via this menu H8 S7 which make it possible to test the alarm devices The test can not be started if fire alarm is activated in the system One or all control units can be selected When the test starts the alarm devices will sound for approx 5 seconds be silent for approx 25 seconds sound for approx 5 seconds and so on NOTE Also disabled and silenced alarm devices will be tested The test will continue for one hour is stopped via this menu H8 S7 or if a fire alarm is activated in the system Access According to chapter Access code for maintenance see page 125 Scroll to menu S7 Test alarm devices ACCEPT S7 Test alarm devices on CU 00 99 All Write a CU no or 99 ACCEPT for all CUs and press A to accept Test alarm devices Scroll or press Return to ACCEPT S7 return to menu H8 Scroll or press Return to log off 35 Including Addressable siren 3377 and Addressable sounder base 3378 The output activation will be continuously steady For the alarm devices 3377 and 3378 the tone with the highest priority level and type alarm device will
17. 2 1 4 14 2 1 5 14 2 1 6 Operating Instructions Fire alarm system EBL512 V2 5 x Display faults X2 Press A E g Only the fault message for the fault respectively is displayed here not date time and status information Display disablements X3 Press A E g Disable zone X4 Press A E g Write zone number and press A If more zones are to be disabled repeat the procedure Re enable zone X5 Press A E g This is a list of disabled zones Scroll to or write the wanted zone number and press A If more zones are to be re enabled repeat the procedure Disable Re enable control X6 Press A E g 38 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 14 2 1 7 14 2 2 14 2 3 Rev Operating Instructions Fire alarm system EBL512 V2 5 x To disable press 0 and A To re enable press 1 and A For more information see chapter Disable Re enable all control exting and ventilation outputs H2 B8 page 91 Disable Re enable alarm devices X7 ZONE 123 LAST 789 No 003 Disable Re enable alarm dev ACCEPT X7 Press A E g ZONE 123 ETAST 789 Nor 00B Dis 0 or re en 1 alarm dev 1 ACCEPT To disable press 0 and A To re enable press 1 and A For more information see chapter Disable Re enable alarm devices H2 B9 page 92 Alert Annunciation AA alarm
18. 4 19 Unexpected interrupt xx 20 S W monitoring fault xx 00 or 03 is normal If xx 01 02 or 04 20 appear often call for service personnel engineer yy y memory address before restart FAULT Sensor techn no xxxxxx The sensor 22xx 23xx is removed from its sensor base 2210 2312 Faulty sensor The analog detector 33xx 43xx in NORMAL mode The built in self verification function has reported a fault status Detector removed from its base generates FAULT No reply FAULT Short circuit COM loop x CU xx Short circuit on COM loop x short circuit isolator is not connected on the loop Check the loop NOTE As long as there is a short circuit the COM loop is disabled Each 10 minute is an attempt made to re enable the loop again FAULT Gh eire input x 1580 board x CU 8 zones expansion board DET8 This is indicating short circuit on input x zone line on the 1580 board The wires cable might have been damaged NOTE As long as there is a short circuit the zone is disabled Each minute is an attempt made to re enable the zone again FAULT Short eire loop x BSA CUR 1584 Autronica interface board BS4 Short circuit or current consumption gt 167mA on the BS4 loop short circuit isolator is not connected on the loop Check the loop NOTE As long as there is a short circuit the BS4 loop is disabled Each 10 minute is an attempt made to re enable the loop again 59 Panasoni
19. Instead the alarm point will be disabled and has to be re enabled again via menu H2 B5 When the Fire door closing function is used the fire door will be closed when the detectors controlling the door are tested via the test mode 124 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 Maintenance H8 30 1 Access code for maintenance Access code for access level 3 is required for menu H8 NOTE If login to level 2 was made with code for level 3 or 4 no code to access level 3 is required here Access According to chapter Access see page 77 A A When required see above enter the access code for level 3 Enter the code 4 digits i The digits are replaced in the display The access code was not correct Try again The access code was 1 correct This is menu S1 Press A to accept or scroll to the following menus S2 S8 125 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 2 Disable or re enable outputs for routing equipment H8 S1 Outputs for routing equipment fire brigade tx fault tx can be disabled via this menu They stay disabled until re enabled again via this menu Can be useful during an installation test period when only local alarms are required Disabled outputs are indicated by LEDs Disab
20. Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 6 Display current consumption in unit H5 A5 The resolution is not very high i e the displayed values give only a rough idea of the current consumption Control unit The total current consumption including the charging current at 24V for the selected control unit c i e when it is connected to the mains 230 V AC i e this function is not working by battery backup Charging The battery charging current for the selected control unit c i e This is at 24 V i e before the DC DC converter for battery charging voltage etc NOTE Control unit current gt 3800 mA is presented as gt 3800 mA Charging current lt 100 mA can not be correctly presented The displayed Charging value xxxx mA shall be multiplied by two when High current charging mode has been selected via jumper JP2 on the Charger board 1657 JP2 shunted High current charging mode Access According to chapter Access code for service H5 see page 110 Scroll to menu A5 Display current consumption in unit ACCEPT A5 A From which control unit shall current Write control unit number consumption be displayed 00 ACCEPT Press A to accept i Se le If the control unit don t exist or don t answer this message will be shown Display current consumption in unit Scroll or press Return to ACCEPT A
21. SSD only for the control units that shall be connected now Wait to download the SSD until the TLON Network installation is ready In TLON Manager do the TLON Network programming for the project i e only the control units that shall be connected now Start up the control units according to chapter Control Units in a TLON network page 64 i e turn power on and do the TLON Network installation of the control units Download the SSD Later when one or more control units shall be stated up Open the project in TLON Manager add the control unit s and install download it according to the separate TLON network documentation Open the SSD in Win512 and add the control unit s and download the SSD to all control units NOTE For highest security the function Redundancy in distributed system can be used in a system with a TLON Network One control unit is a master unit and the other control units in the system are slave units that are connected to the master unit via a separate network and a 1580 board in the master unit For more information see Planning Instructions chapter Redundancy in distributed system TLON network installation A project a system with two or more control units has to be created in the PC program TLON Manager or has been created earlier A PC is connected to the modular connector J2 in the control unit main board 1556 Open the project in TLON Manager and install download the pro
22. Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x BPOINT 1239245 No 001 User definable text message for 123 45 More than one alarm point in a zone or One conventional zone zone line input ZONE 123 NoT 00I User definable text message for zone 137 More than one zone ZONE 234 LAST 567 No 002 User definable text message for zone 234 Only one alarm point in each zone POINT 122 45 LAST 789 01 No 003 User definable text message for 123 45 LAST The most recent zone address that has activated fire alarm No The total number of zones where fire alarm is activated User definable text message alarm text For an alarm point it is the individual free text for the alarm point if programmed or the default control unit text if programmed User definable text message For a zone it is the individual free text for the zone if programmed or the text Many alarms in zone LEDs Alarms queued L2 blinking 0 4 0 4 sec More than one fire alarm is activated To scroll through the zones use the push button Scroll P1 The fire alarms are stored in a circular buffer and when scrolling from the last to the first alarm the LEDs Alarms queued will be turned off for three seconds The first alarm will be automatically displayed again 20 seconds after the latest time the Scroll button was used The printer
23. a push button P3 Silence Alarm devices If the push button Silence Alarm devices is pressed during a pre warning a fire alarm or a Co incidence alarm the following will happen e LEDs Fire L1 and Alarms queued 23 L2 changes from blinking 0 4 0 4 to steady ON e activated outputs programmed for sounders type 3 alarm devices will be turned OFF In case of a new alarm or if the push button Silence Alarm devices is pressed again the sounders will automatically sound again and the LEDs Fire and Alarms queued starts blinking NOTE This is also valid for Pre warning and Co incidence alarm Disable Re enable alarm devices The outputs programmed for sounders type 3 alarm devices can via menu H2 B9 be collective disabled for one more or all control units This is indicated by LED Disablements L8 and LED Fault Disablements Alarm devices L13 steady ON In case of a fire the sounders will remain disabled i e the alarm devices will not sound They will remain disabled until they are re enabled again via menu H2 B9 See also chapter Disable Re enable alarm devices H2 B9 page 92 23 4 When more than one fire alarm is activated Including Addressable siren 3377 and Addressable sounder base 3378 26 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 9 Silence buzzer
24. all control units can be downloaded via one control unit Start the download from Win512 The download will now be performed to the control units one at a time according to the chapter Single Control Unit above When the download to a control unit is completed that control unit will automatically restart see chapter Restart page 74 User definable text messages download When a fire alarm is activated e g an addressable alarm point the presentation number Zone amp Address will be shown on the first row in the control units and the ext FBP s alphanumeric display On the second row will be shown a user definable text message alarm text if programmed Each alarm point can have a unique text message When several alarms are activated in one or more zones and only the zone numbers are shown each zone can have a unique text message Each zone line input can have a unique text message Downloading is performed in a consecutive order i e 0 1 2 3 4 29 amongst the selected control units but the control unit where the PC is connected will automatically be the last one to get the SSD downloaded Also valid for the Ext Presentation unit 1728 and the Alert Annunciation units 1735 1736 68 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 18 5 Rev Operating Instructions Fire alarm system EBL512 V2 5 x The user definable text messages will be printed out w
25. and Win512 Access According to chapter Access code for service H5 see page 110 Scroll to menu A4 Show information about site specific data ACCEPT A4 Name XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX YY year MM month Downloaded YY MM DD hh mm ACCEPT DD day TE bel CENO below hh hour mm minute Show information about Scroll or press Return to site specific data ACCEPT A4 H5 Scroll or press Return to log off If there is no SSD downloaded to the control unit the following text message will be shown No SSD downloaded NOTE In the British Standard Marine Application convention it is possible to change the alarm algorithm for some type of analog detectors see chapter Algorithm setting via menu H4 U5 page 101 If one or more alarm algorithms are changed the following infor mation will be shown instead of the information shown above Name XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX YY year MM month Modified by CU YY MM DD hh mm ACCEPT DD day hh hour mm minute If an algorithm is set changed via menu H4 US the site specific data SSD in the c i e is not equal to the SSD file downloaded from Win512 i e a back up is required to update the SSD file XXXxxx 512 Modified by CU will be changed back to Downloaded after the next SSD download and the alarm algorithms will be according to that SSD Logical Name as written in Win512 dialog box System Properties tab System Data 114
26. be automatically selected 132 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 9 Safe shut down of control unit H8 S8 It s not recommended to power off a control unit i e no 230 V AC and no battery without first doing a safe shut down of control unit Safe shut down will save the SSW and put the CPU at rest See also chapter Restart page 74 It s recommended to do a safe shut down after commissioning the installation and after the calibration of supervised outputs change of access code etc in order to save the new values codes etc Safe shut down can be performed from any control unit and any control unit can be selected e g a control unit without a front has to be shut down from another control unit NOTE activated By restart and power off the Fault tx output s will be n a Scroll to menu S8 Write the C U number 1 yes and NA Safe shut down of control unit ACCEPT S8 Shut down control unit 00 0 lL ea wes Wo ACCEPT Please Wait In the CU that will be shut down when a front is available Ready for shut down break the power Automatic restart within nnn seconds In the CU s that will not be shut down Control unit xx ready for power off No reply from the selected CU xx i e no safe shut down No reply from control unit FAULT Restart CU xx code xx yyyyyyy Date mm dd h
27. before a fire alarm 41 14 4 2 Key cabinet opened in conjunction with a fire alarm _ 41 14 4 3 Key cabinet alarm DBI convention 41 14 5 Alarm Acknowledgement Facility AAF 42 14 6 Quiet alarm 42 15 Alarm reset 43 15 1 Pre warning reset 43 15 2 Fire alarm reset 43 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 15 2 1 Multiple reset 15 2 2 Single reset 15 2 3 Single encapsulated reset 15 2 4 Alert Annunciation 15 2 5 Co incidence alarm 15 3 Heavy smoke heat alarm reset 15 4 Key cabinet alarm reset 15 5 Quiet alarm reset 15 6 Alarm Acknowledgement Facility AAF reset 16 Fault 16 1 Fault messages 16 2 Fault acknowledge 17 Commissioning an installation 17 1 Single Control Unit 17 2 Control Units in a TLON network 17 2 1 TLON network installation 17 3 Adda Control Unit in a TLON network 17 4 Make two TLON networks one 17 5 Delete a Control Unit in a TLON network 18 Programming SSD download 18 1 Check All Loop Units 18 2 Single Control Unit 18 3 Control Units in a TLON network 18 4 User definable text messages download 18 5 Using old SSD 19 New system program S W version download __ 19 1 A single control unit c i e 19 2 Control Units in a TLON network 19 3 Earlier S W version download 20 EBLS512 settings download 20 1 Control Units in a TLON network 21 Restart 21 1 Boot menu 22 Access 23 Perform monthly tes
28. control units connected in parallel i e it is used for Redundancy in distributed system In such a case the output for routing equipment fire brigade tx in the slave unit respectively works as a detector 1584 Autronica interface board BS4 Cut off break on the BS4 loop This is indicating a single break on the loop Communication has to be performed in both directions to find all units Each 10 minute is an attempt made to comm in one direction again This is indicating a single break on the COM loop x when one or more short circuit isolators are connected on the loop Communication has to be performed in both directions to find all units The break is to be found in the specified segment e g ASF 3 lt gt CU between short circuit isolator no 3 and the control unit Each 10 minute is an attempt to comm in one direction made again 52 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x FAULT Display unit xxxxxx Display unit out of work Fault in the display unit EEPROM site specific data Download the data again or change the EEPROM and download the data again FAULT Double addresses techn no XXXXXX Two or more units connected to a BS4 loop 1584 board have been given the same address Check the units FAULT Earth fault plus CU xx FAULT Earth fault minus CU xx Earth fault is detected Syst
29. downloading the following faults might be generated FAULT CU xx has no contact with CU xx FAULT CU xx has wrong information The faults have to be acknowledged Earlier S W version download For some reason it might by required to download an earlier S W version This is done the same way as for a new S W version but with the following additions 1 The Win512 version designed for the S W version to be downloaded has to be used 2 After the download the EBL512 settings shall be read edited if required e g the no of addresses and then downloaded again 3 The dialog box Please enter your password might be displayed E g if a new control unit with the latest S W version downloaded by delivery shall be added to a system with an older S W version downloaded 71 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 4 If so the PC program Key512 is used to get a Password for the number specified in the Key field Only authorised personnel have access to Key512 5 When the password is typed click OK NOTE If a running EBL512 system shall be downgraded bear in mind that the Site Specific Data SSD created in a new Win512 version e g 2 3 1 can not be opened in an earlier Win512 version e g 2 2 5 New SSD has in this case to be created in the earlier Win512 version 72 Panasonic Ele
30. e Remove fuse F5 not F1 F4 on the connection board 1555 The following fault message is to be shown FAULT Supervised output 0 CU xx NOTE xx is depending on control unit e Put back the fuse and acknowledge the fault When output units type 2262 2263 are installed e Remove the battery fuse F3 on the rectifier p c b The following fault message is to be shown FAULT Battery output unit xxxxxx NOTE xxxxxx is depending on output unit and control unit e Put back the fuse and acknowledge the fault e Remove fuse F8 on the output p c b The following fault message is to be shown FAULT Superv output 3 tech no xxxxxx NOTE xxxxxx is depending on output unit and control unit e Check the manual call points the glass Take required measures Use the manual call point alarm test key e Check some control outputs Are they activated according to programmed control expressions 145 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 34 How to change paper in the printer When the paper roll is almost empty a red line appears on one edge of the paper Change the paper roll before it s completely empty Always have a spare paper roll on site Change the paper roll as follows e Read all instructions before changing the paper roll e Open the control unit door Unlock the metal inner door by removing the screw placed on
31. for fire brigade tx type 4 routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L15 blinking x 0 SO Short circuit break on the connected cable equipment and or blown fuse F5 or F6 on the connection board x 1 S1 Short circuit break on the connected cable equipment and or blown fuse F7 or F8 on the connection board x 2 S2 Short circuit break on the connected cable equipment x 3 S3 Short circuit break on the connected cable equipment e Connected equipment might be stolen e Resistor s missing or not correct value see dwg 512 42 FAULT Superv output x tech no xxxxxx If the output is programmed for sounders type 3 alarm devices it is also indicated by LED Fault Disablements Alarm devices L13 blinking If the output is programmed for fire brigade tx type 4 routing equipment it is also indicated by LED Fault Disablements Fire brigade tx L15 blinking e Check fuses F1 F8 on the output unit p c b Short circuit break on the connected wires Wrong no end of line resistor One or more connected units have been removed stolen FAULT Wire to exting system CU xx Short circuit cut off on the wires from the 1583 German Fire Brigade interface board in control unit No xx to the connected extinguishing system equipment FAULT Wrong type board x loop x CU xx This is valid for the I O Matrix board 4582 no x connected on COM loop x in the co
32. in menu H3 93 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 26 Present system status on display and printer H4 A printer is factory mounted in control unit 1549 Printer 1558 is an option for control unit 1548 26 1 Disablement H4 U1 A list of all disablements in the system Also alarm point s and or zones disabled via the function Single encapsulated reset see page 44 is shown in the list In this case a zone will be displayed as ZZZ 00 i e zone number and address 00 Disablements by time channels are listed in menu H4 U2 From this menu it is also possible to get a print out Action Text in display Comments Access According to chapter Access see page 77 A Press 1 for an automatic print out of all disablements in the system Press A for presentation in the display L a list in which you can scroll If there are no disablements and if Return is pressed menu U1 will be shown again a On this row can be shown adding infor mation e g Automatic re enablement HH MM or by open door in CU XX Press A and menu U1 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off 94 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 26 2 Disablement by time
33. internal resistance too high The battery might be too old Cables fuses etc for externally placed batteries might cause a voltage drop Check adjust the rectifier power supply voltage 24 V DC Check the charging voltage over the battery respectively 13 5 13 8 depending on the actual charging step Check the voltage over a disconnected battery fully charged gt 13 V FAULT Low main PWS control unit xx Mains voltage below 187 V AC Blown fuse 230 V AC or no voltage Rectifier voltage below 21 V DC Fuse F1 on the charger board 1557 1657 is blown FAULT Low voltage control unit xx Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x System voltage lt 21 V DC Check adjust so that the rectifier output voltage is 24 V DC FAULT Low voltage output unit xxxxxx The external power supply s system voltage lt 21 V DC Check adjust so that the rectifier output voltage is 24 V DC FAULT Mains control unit xx The fault is activated 1 300 minutes after Loss of mains i e no 230 V AC Blown fuse 230 V AC Blown fuse F1 on Charger board 1557 1657 Battery charging has been turned off for some security reason e g too high current consumption Valid for Charger board 1657 FAULT Mains ext power supply CU xx The fault is activated after 1 300 minutes because of e Loss of mains i e no 2
34. or external FBP connected to own control unit Door open in a C U is indicated by LED Door open in that C U and all ext FBPs connected to that C U Door open in an ext FBP is indicated by LED Door open in the C U it is connected to and all ext FBPs connected to that C U O Door in control unit Door open in a C U is indicated by LED Door open in that C U and in all ext FBPs connected to that C U Door open in an ext FBP is indicated by LED Door open in that ext FBP only Outputs for routing equipment Fire brigade tx and Fault tx Disablement of routing equipment No disablement Door open in a C U or an ext FBP will not disable the output s for routing equipment Fire brigade and fault tx O Disable by door in any control unit Door open in any C U will disable the output s for routing equipment Fire brigade and fault tx in all C U s O Disable by door in any control unit or any external FBP Door open in any C U or any ext FBP will disable the output s for routing equipment Fire brigade and fault tx in all C U s Disabled outputs for routing equipment are indicated by the LED Disablements L8 and Fault Disablements Fire brigade tx L15 and listed in menu H4 U1 2 In the ext FBP 1828 when the key is turned to the position open 30 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 13 Operating Instructions Fire alarm system EB
35. see chapter Acknowledge SERVICE signal H8 S4 page 129 It is not possible to get a print out from menu H4 U6 According to chapter Access see page 77 L a list in which you can scroll Press Return to menu U6 If there are no sensors in the list menu U6 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off 106 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 26 7 Rev Event log H4 U7 Operating Instructions Fire alarm system EBL512 V2 5 x This is a list of events Type and number of events in the list etc can be set in Win512 see Planning Instructions and Win512 help From this menu it is possible to get a print out The events can be listed Via display See Alternative A below Via a print out See Alternative 1 below NOTE open The event logging is disabled as long as menu H4 U7 is Action Access Scroll to menu H4 Scroll to menu U7 Alternative A Alternative 1 Write number of events to be printed e g 010 Text in display Present system status on display and printer ACCEPT Disablement Printout l yes Event log Printout 1l yes When A is pressed an event will be shown in the display e g FIRE ALARM zone 123 address 45 MM DD HH MM XX or FIRE ALARM zone 456 Many alarms in zone MM DD HH MM XX How many events should be printed 000 ACCEP
36. short circuit on the loop According to EN54 2 One ISO is required per 32 alarm points on the COM loop Display unit DU Addressable unit for fire alarm presentation incl user definable text messages if programmed COM loop Loop a cable with two wires to which all the addressable units can be connected Starts in the c i e and it returns back to the c i e Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 2 8 2 9 2 10 2 11 2 12 2 13 Rev Operating Instructions Fire alarm system EBL512 V2 5 x BS4 loop Loop a cable with two wires to which all the addressable Autronica BS100 units can be connected Starts in the c i e and it returns back to the c 1 e Control Unit C U C LE Control Unit Control and Indicating Equipment Unit to which the alarm points are connected via a COM loop Indicates fire alarm fault condition etc Fire Brigade Panel amp Control Panel see below included or not included Printer included or not included Fire Brigade Panel FBP Unit intended for fire alarm presentation etc for the fire brigade personnel Can be a part of the control unit front or a separate unit external FBP In the ext FBP a printer can be included or not included Control panel CP A part of the control unit front intended for the building occupier service personnel etc to communicate with the control unit system System
37. the alert annunciation function can be used e Pre warning can be used 150 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 38 Information regarding radioactive radiation source The installation might contain old smoke sensors detectors of the ionization type They contain a small radioactive radiation source Americium 241 When the sensor detector gets dirty and when service signal has been activated in the system contact your local dealer for cleaning replacement of the sensors detectors Metal objects must absolutely not be stuck into the sensor detector Static electricity might destroy the detector Defective faulty discarded and replaced sensors detectors shall be taken care of as radioactive waste They shall be packed in chock absorbing material to make a stable parcel PLEASE NOTE Damaged sensors detectors shall also be packed in a sealed packet whose surface must not be contaminated that is not be soiled with loose radioactive dust 151 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 39 Revision history 152 This page has deliberately been left blank Panasonic Panasonic Electric Works Fire amp Security Technology Europe AB Citadellsvagen 23 SE 211 18 Malm Sweden Tel 46 0 40 697 70 00
38. the DBI Danish convention up to five characters 82 Low sensitivity and or slow detection 35 s might not fulfil the EN54 7 specifications 8 Analog multi detector 3316 only 100 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 26 5 2 Algorithm setting via menu H4 U5 NOTE Algorithm setting via menu H4 US is only valid for the _ British Standard Marine Application convention The alarm algorithm can be set changed via menu H4 U5 for the following detectors 3304 in NORMAL mode 3308 3309 in NORMAL mode 3316 in NORMAL mode the Decision algorithm is not possible to use No alternative algorithm can be used No values offset level etc can be set via menu H4 U5 i e these values have to be set via Win512 The Short name set in Win512 can be lt 5 characters When scrolling the message Please Wait might be shown for a second and No more sensors found in the system before the lowest and after the highest possible technical number in the system NOTE If an algorithm is set changed via menu H4 U5 the site specific data SSD in the c i e is not equal to the SSD file downloaded from Win512 i e a back up is required to update the SSD file xxxxxx 512 If an algorithm is set changed via menu H4 U5 the information in menu H5 A4 will be changed from Downloaded xxxx to Modified by CU
39. the trigger conditions no 42 Quiet Alarm Zone or no 43 Quiet Alarm Zone Address 7 The AAF Control is available on the Australian market only 42 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 15 Operating Instructions Fire alarm system EBL512 V2 5 x Alarm reset 15 1 15 2 15 2 1 15 2 2 Pre warning reset Pre warning is automatically reset Fire alarm reset NOTE The detectors having activated fire alarm shall after reset be inspected tested and replaced when required One of the following alarm reset alternatives is valid This is selected via Win512 Multiple reset is default NOTE In Belgian British Standard and British Standard Marine Application conventions the alarm devices have to be silenced P3 before the reset button P4 can be used Multiple reset All the fire alarms will be reset by pressing Reset P3 According to the EN54 2 standard NOTE The push button has to be pressed in for min 0 5 sec When all fire alarms are reset LEDs Fire L1 and Alarms queued L2 are turned OFF and the display is empty All outputs for fire alarm have also been reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be shown in the display see chapter Key cabinet alarm reset page 45 Single re
40. to accept A Re connect COM Loop 0 Write the required numbers Press A to Depending on the accept chosen type 0 1 2 or 3 the following will be shown Re connect input technical no 000000 ACCEPT A Re connect type 0 0 COM 1 BS4 Continue to re connect or 2 DET8 3 Loop Unit ACCEPT press Return to menu S2 LED Disablements will be turned off if there are no other disablements in the system Return Re connect loop Scroll or press Return to ACCEPT S3 return to menu H8 Scroll or press Return to log off 128 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 5 Acknowledge SERVICE signal H8 S4 See chapter Sensors activating SERVICE signal H4 U6 page 106 When service signal from a sensor is acknowledged the sensor is given a default sensor value for a new clean sensor i e first replace the sensor then acknowledge the service signal as soon as possible The first week average sensor value after acknowledge will be calculated within one hour and after that each week NOTE If a sensor is replaced without activating service signal it has to be reset to the default sensor value see chapter Clear weekly average H8 S5 page 130 Access According to chapter Access code for maintenance see page 125 Scroll to menu S4 A If there are no sensors to acknowled
41. top to the left of the inner door Open the inner door e Remove the old paper roll carefully cut the paper so that the paper within the printer remains there e Take the new paper roll tape the new paper to the old paper and place the paper roll on the printer e Press the Paper feed button P7 until the new paper comes out of the printer Cut off the paper and lock the inner door Close the control unit door 146 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 35 Replacing a TLON connection board and or a main board By the TLON network programming some unique data will be stored in a memory on the 1590 TLON connection board and some unique data will be stored in a memory on the 1556 main board After replacing a TLON connection board to another or replacing both a TLON connection board and a main board do Replace Update and Save in TLON Manager After replacing a main board to another not the TLON connection board do Update and Save in TLON Manager 147 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 36 Battery maintenance The batteries 2 x 12 V 24 Ah are normally placed in the control unit Larger batteries lt 60 Ah are placed outside the control unit The control unit supervises the batteries and a f
42. will print each fire alarm e g xxx Fire Alarm Point 123 45 Time HH MM Date MM DD User programmable text message if progr or Zone 123 Time HH MM Date MM DD User programmable text message if progr Reset of the fire alarms see chapter Alarm reset page 43 7 More than one alarm point in the same zone If no user definable text message is programmed the text Many alarms in zone will be shown 38 Up to 512 alarms can be presented in the display Alarm ZONE and or ZONE ADDRESS depending on zone or point alarm presentation but all possible alarms 15360 can be stored When printer is available e g control unit 1549 The alarms will be printed like they are presented in the display i e as point alarms or zone alarms 36 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 14 2 1 14 2 1 1 Rev Operating Instructions Fire alarm system EBL512 V2 5 x NOTE NOTE NOTE NOTE NOTE NOTE NOTE POINT 999 nn and POINT 999 99 Zone number 999 could indicate that the alarm is activated by one or more control units in the system In this case nn 00 29 is indicating a single slave unit and nn 99 is indicating several control units connected in parallel Normally the user definable text message alarm text on the second row will indicate if it is a normal alarm point or a slave unit units For more information see Planning Instructions chapter Red
43. xx FAULT Fan xx control unit xx The LED Fault is lit on a fan control module connected to control unit xx Fan no xx has been activated but the corresponding I O unit 3361 input has not been activated within 30 seconds e Check the fan and the cables connections PAURE TEBE Sex ISS Polo succl ox GU xox FBP 1826 1828 The unit is programmed as another type of unit than the SSD says or fault in the unit FAULT Fuse 1580 8 zones board x CU xx DET8 1580 8 zones expansion board Check for blown fuse on the 1580 board FAULT Fuse 1582 FBP board x CU xx External Fire Brigade Panel interface board 1582 Check for blown fuses on the 1582 board FAULT Fuse 1584 Autron board x CU xx 54 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x BS4 1584 Autronica interface board Blown fuse on the 1584 board The fuse is not replaceable The board has to be replaced FAULT Fuse 1587 board x CU xx External Fire Brigade Panel DU interface board 1587 Check for blown fuses on the 1587 board FAULT Fuse on COM loop x CU xx The fuse is not replaceable More components might also be broken The main board 1556 has to be replaced FAULT Fuse output unit techn no xxxxxx Fuse F9 on the output unit p c b is blown FAULT High Current loop x 1584 x CU xx Autronica interface board BS4 The current consum
44. 0 Write the required ACCEPT numbers Press A to Depending on the ul chosen type 0 1 2 or BS4 Loop 0 Board 0 CU 3 the following will be ACCEPT shown J accept DET8 input 0 Board 0 ACCEPT Disconnect input technical no 000000 ACCEPT A Disconnect type 0 0 COM 1 BS4 LED Disablements 2 DEMS as Loop UNIE ACCEPT indicates disconnected loops etc Continue to disconnect or press Return to menu S2 Return Disconnect loop Scroll or press Return to ACCEPT S2 return to menu H8 Scroll or press Return to log off 4 Only valid for input 0 as a zone line input Z i e trigger cond no 19 127 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Don t forget to re connect the loop zone line again via menu H8 S3 30 4 Re connect loop H8 S3 Disconnected disabled loops zone lines via menu H8 S2 are indicated by LED Disablements and listed in menu H4 U1 NOTE When you re connect a COM loop all the statistics shown in menu H5 A7 will be erased and set to 0 Access According to chapter Access code for maintenance see page 125 Scroll to menu S3 Re connect loop ACCEPT S3 Re connect type 0 0 COM 1 BS4 Press 22DET8S S WOO On Unie ACCEPT 0 COM loop 1 BS4 loop 2 Expansion board 1580 3 Addr zone interface 2226 2335 3361 MIO Press A
45. 001 Current N 15 Use gt or L 15 L 35 N 15 N 35 H 15 H 35 nym Change algorithm 000001 Current N 15 MESIE SS NAIS INI SNS gts St ENS 102 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x See chapter Restart page 74 NOTE Write the sensor s techn number and or press A to accept or press Return to carry out the change of algorithm s Menu U5 will be shown for a few seconds and then the affected control unit s will restart The new algorithm will not be in use until after the restart In case of an automatic log off and one or more algorithms are changed the affected control unit s will restart Perf Factor Performance factor Low min 0 The detector is mounted in a stable environment High max 2 55 The detector is mounted in an unstable environment See also Planning Instructions chapter Performance factor 103 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Sensor values and setting alarm algorithm for the Analog heat detector 3308 3309 Access According to chapter Access see page 77 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1l yes U1 Scroll to menu US Sensor values To make a p
46. 125 Scroll to menu S9 Activate address in alarm mode ACCEPT Select zone 000 address 00 ACCEPT Write the zone and Select zone 123 address 45 Press A to accept start address ACCEPT the fire alarm POINT 123 45 NOR Normal fire alarm User definable text if programmed presentation in the control unit s FBPs display If more alarm points have to be set in alarm status press Return to select another zone address and continue as above Select zone 000 address 00 ACCEPT Write the zone and Select zone 012 address 34 Press A to accept start address ACCEPT the fire alarm POTN 122 45 T TAST 012534 No 002 User definable text if programmed What happens by reset of the fire alarm s is depending on a if you still are in menu H8 S9 and single reset is used b if you still are in menu H8 S9 and multiple reset is used or if you are logged out by pressing Return two times or automatically after 10 minutes 134 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Alternative a Scroll or press Return to menu H8 Scroll or press Return to log off Reset Alternative b Reset NOTE Multiple reset is default By Single reset each point has to be reset individually 8 Alarm reset is selected in the Win512 System dialog box 135 Panas
47. 1826 1828 units connected to an Ext FBP DU interface board 1587 can also on site be downloaded via Win512 See the Win512 help chapter help topic Display unit menu and the Technical Description for the unit respectively A single control unit c i e A single c i e must not have a TLON connection board 1590 mounted To download a new software system program version a PC and Win512 are used Before download the PC has to be connected to the D connector J1 in the control unit main board 1556 in question 1 Start Win512 In the Tools menu open the Download software dialog box and do the required settings e g the path for the S W BIN file and or the language SST file Do not forget to mark the checkbox respectively 2 Set the c i e in Bootstrap mode i e set jumper JP1 BOOT in position on the main board 1556 3 Do a reset restart i e set jumper JP4 RESET in position momentarily approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinking indicating that the control unit is in Bootstrap mode 5 Start the downloading click Download The buzzer will now be silenced and LED LD101 is turned on continuously Tt is recommended that the two first digits in the EBL512 S W version and the Win512 version are the same e g for EBL version 2 3 1 shall Win512 version 2 3 x be used When a c i e has a TLON connection board 1590 mounted it i
48. 200 outputs can be individually disabled via menu H2 B3 Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs via menu H2 B8 and menu H2 B9 are not limited and must not be counted Up to 200 Interlocking outputs can be individually disabled via menu H9 C4 All interlocking outputs disabled via 000 00 are not limited and must not be counted It is not possible to exceed the limits A warning will be shown Max disablements reached Disablement not performed ACCEPT Don t forget to re enable via menus H2 B4 B6 B8 or B9 H8 S3 H9 C5 or use automatic re enablement for zones and alarm points Disablements are indicated by LED Disablements L8 and are also shown in the display An example Zone 001 is disabled Morera More is indicating two or more disablements Disablements and faults are indicated by a 2 sec beep when an open control unit door is being closed 75 NOTE See chapter Alphanumeric display LCD in the control unit page 20 regarding priority order 81 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 1 Disable zone H2 B1 When a whole zone is disabled all alarm points within the zone are disabled except the addressable manual call points Disabled zones are listed in menu H4 U1 from which it is also possible to get a prin
49. 3 3 Documents 3 4 Applications 3 5 PC S W OCDODOCODOOCOCOCCOCADBDNADABDAHADAHOHO SF N O O O oO 10 11 11 11 11 11 11 12 12 12 12 12 13 13 13 13 Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 5 x MEWO01002 Rev 4 Control Unit 14 5 LED indicators and push buttons 16 6 Normal operation 20 6 1 Alphanumeric display LCD in the control unit 20 6 1 1 System information on the top first row 20 6 1 2 System information on the bottom second row 21 7 Access levels _ 22 TA Access level 0 22 7 2 Access level 1 22 7 3 Access level 2 23 74 Access level 3 24 7 5 Access level 4 25 7 6 Access level 5 25 8 Silence Alarm devices 26 8 1 Disable Re enable alarm devices 26 9 Silence buzzer 27 10 Disable Re enable all control extinguishing and ventilation outputs 28 11 Evacuate 29 12 Door open 30 12 1 LED Door open 30 12 2 Outputs for routing equipment Fire brigade tx and Fault tx 30 13 Technical number Presentation number 31 13 1 Technical number for COM loop units 31 13 2 Technical number for BS4 loop units 32 13 3 Presentation number 33 14 Alarm types 34 14 1 Pre warning 34 14 2 Fire alarm 35 14 2 1 Fire alarm menu X1 X7 37 14 2 2 Alert Annunciation AA alarm 39 14 2 3 2 zone address dependence co incidence alarm ___ 39 14 3 Heavy smoke alarm Heavy heat alarm 40 14 4 Key cabinet alarm 41 14 4 1 Key cabinet opened
50. 30 V AC to the ext power supply equipment e Blown fuse 230 V AC FAULT Mains output unit xxxxxx The fault is activated after 1 300 minutes because of Loss of mains i e no 230 V AC Blown fuse 230 V AC Blown fuse F1 or F5 on the output unit rectifier p c b Battery charging is turned off i e the total current consumption incl the battery charging current is too high gt 4 5 A Valid for the Ext power supply unit 3366 Mains OK output in 3366 is high Mains OK input in 3364 is high 5 The time is programmable in Win512 Max 30 min according to the ENS54 2 standard Default value depending convention 57 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x FAULT No reply board x loop x CU xx This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx e Check the board s address i e the I O Matrix board no Jumpers JP1 and JP2 on the board e Check if the board is disconnected from the loop FAULT No reply techn no xxxxxx In spite of the control unit is communicating in both directions one or more units can not be found Check the unit s address DIL Switch in some unit or with programming tool 3314 in some units Faulty unit Detector removed from its base Double break on the COM BS4 loop Note Single break gives the fault message FAUL
51. 5 H5 Scroll or press Return to log off Current consumption control unit 00 Control unit xxxx mA Charging xxxx mA o 115 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 7 Display current consumption COM BS4 loop H5 A6 The resolution is not very high i e the displayed values give only a rough idea of the current consumption The current consumption an average value for each COM loop and BS4 loop can be displayed NOTE No or very small current consumption can not be presented correctly precisely Access According to chapter Access code for service H5 see page 110 A Select type of loop Press A to accept Write loop number board number 0 3 and control or unit number Press A to W 1 Ta wA S i a accept If the control unit don t exist or don t answer this message will be shown The current consumption accuracy is 5 mA Scroll or press Return to H5 Scroll or press Return to log off l An Autronica interface board 1584 is required in the control unit 116 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 8 Display statistics for COM loop H5 A7 The statistics can be used during commissioning service etc Pollings are the number of pollings questions sent ou
52. 92 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 25 Set calendar and clock H3 The RTC component has a capacitor as a backup power supply Normally date day of the week and time only have to be set when the power is turned on the control unit for the first time If required the clock might be corrected so that the time stamps for fire alarms faults etc will be correct In this menu is also the S W system program version shown The calendar and clock can be set in any c i e for the whole system Every day at midnight the calendar and clock will be synchronised NOTE If you don t want to change anything e g if you only want to see the S W version press Return instead of A to return to menu H3 Action Text in display Comments Access According to chapter Access see page 77 A j 1 i Here is the S W version shown e g VER 2 4 The time shown is the time when A was pressed in menu H3 Change the date time and or weekday The clock starts again from the date time etc shown in the display NOTE Press Return instead of A if no changes are to be done A or ndar and cloc Scroll or press Return to Return log off The capacitor can supply the RTC for a couple of days When the power has been turned off it is recommended to check set the date and time
53. All faults i e not acknowledged faults acknowledged faults and corrected faults are stored in the event log and can be listed see chapter Event log H4 U7 page 107 In menu H6 are up to 200 faults listed not_acknowledged and acknowledged but not corrected faults Access According to chapter Access see page 77 A This is a list in which you can scroll The first fault in the list is the most recent fault If a fault is corrected the text Serviced is shown To acknowledge the fault shown in the display press Fault acknowledge Fault acknowledge The fault is now Acknowledged If when the fault is corrected it is no longer shown in this list Scroll in the list e g to acknowledge more faults or press Return to menu H6 Scroll or press Return to log off When the list is empty i e when all faults are acknowledged and corrected you will automatically return to menu H6 122 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 29 Perform ZONE TEST test mode H7 Normally zones are tested during the monthly test via menu H1 Via this menu H7 it is possible to perform the zone test solely In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S7 If a real fire alarm is acti
54. Comments According to chapter Access see page 77 Press A or 1 to accept Here follows the alternative A no printout The alternative 1 printout follows below wat E g 000001 A Start Sensor 000000 Type 3304 Sensor 000001 Momentary XX X m Weekly XX X m Depending on gt the type the following will 3 be shown Sensor 000001 Min Perf Factor X XX m Max XX X m XX X m Sensor 000001 Current algorithm nnnnnn A Type 23xx 22xx amp AUT Sensor 000002 Momentary XXX Weekly XXX AN Type 3308 3309 Sensor 000003 Mare SE Momentary XX C Max XX C gt HAN Sensor 000003 Current algorithm nnnnnn Type 3316 Sensor OOOOON Momentary XX X m Weekly XX X m 3 Sensor 00000N Min XX X m Perf Factor X XX m Max XX X m 98 Write the sensor s techn number and or press A to accept This is a list in which you can scroll or use gt to see the next information window for the selected sensor Press Return to the Start Sensor Scroll or write a new techn number or press Return to menu US NOTE XX X 3 m XX X obscuration per meter XXX sensor value Perf Factor see below this table nnnnnn algorithm short name see separate table page 99 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire al
55. L512 V2 5 x Technical number Presentation number 13 1 Technical number for COM loop units The technical number NNNNNN is used when programming all units connected to the COM loops Technical number is also used to identify which unit has generated a fault 000 127 The address on the COM loop Avoid address 000 Start at 001 Don t have to be in sequence The connections on the COM loop don t have to be in sequence The address is set on a DIL switch in some units and with a programming tool 3314 in some units 0 3 COM loop number 00 29 The control unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager Regarding DIL Switch address setting see dwg 512 71 Regarding the address 000 Address 000 can not be set with the Address setting tool 3314 i e only addresses 001 127 can be used A brand new detector has address 000 factory set Connected on the COM loop the LED will start blinking every second as information that an address has to be set before the detector will work 31 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 13 2 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Technical number for BS4 loop units Autronica interface board 1584 four BS4 loops is required in the control unit The technical number NNNNNN is u
56. Manager LED LED Light Emitting Diode Yellow green or red optical indicator lamp External Indicator LED A unit with an LED Connected to an ASB CDB or a detector with a built in LED Old installations Also connected to an ADB Lit when the built in LED is lit Display LCD LCD Liquid Crystal Display Display in the c i e or Display unit for presentation of fire alarms fault messages etc Normally 40 alphanumeric characters and backlight Door open Door Key switch In EBL512 there is a door switch which is activated when the control unit door is open In some other units this door switch is replaced with a key switch The LED Door open is indicating door open key switch in position open Site Specific Data SSD The SSD is unique for each installation All alarm points presentation numbers user definable text messages programmable outputs etc are created in the PC program Win512 and also downloaded in EBL512 with Win512 Software S W System program The S W makes the control unit the microprocessor work It is factory downloaded but a new version can be downloaded in EBL512 on site 11 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 3 Operating Instructions Fire alarm system EBL512 V2 5 x Overview 3 1 3 1 2 The EBL512 system EBL512 is a microprocessor controlled intelligent fire alarm system intended for analog addressab
57. Panasonic Operating Instructions MEW01002 Revision Fire Alarm System EBL512 V2 5 X Author Jan Pettersson Date of issue 2007 10 31 Date of rev This page has deliberately been left blank Panasonic Electric Works Fire amp Security Technology Europe AB Operating Instructions Fire alarm system EBL512 V2 5 x MEW01002 Rev Table of contents 1 Introduction 2 Definitions Explanations 2 1 PEWF amp STE AB 2 2 Alarm points 2 2 1 2 2 2 2 2 3 2 2 4 229 2 2 6 2 2 7 2 2 8 2 2 9 2 2 10 2 2 11 Smoke detector Sensor Analog detector Analog Sensor Base ASB Conventional detector Conventional Detector Base CDB Addressable Detector Base ADB Addressable Old detector Conventional zone line input External line ADB input Addressable zone interface 2 3 Output unit 2 4 Output Control output 2 5 Short circuit isolator ISO 2 6 Display unit DU 2J COM loop 2 8 BS4 loop 2 9 Control Unit C U C LE 2 10 Fire Brigade Panel FBP 2 11 Control panel CP 2 12 System 2 13 Network TLON LonWorks Echelon Node TLON Conn board Gateway Sub net Backbone net Router Repeater 10 2 14 LED 2 15 External Indicator LED 2 16 Display LCD 2 17 Door open Door Key switch 2 18 Site Specific Data SSD 2 19 Software S W System program 3 Overview 3 1 The EBL512 system 3 1 1 3 1 2 3 1 3 Expansion boards Printer Power supply 3 2 S W versions
58. Regarding the ASI Disable RO 3377 amp ASB 3378 ACCEPT units Control output Disable relay board 0 output 0 O high priority ACCEPT 1 medium priority 2 low priority Disable output for extinguishing system Write the data on 1583 board CU 00 ACCEPT Press A to accept LED Disablements L8 will light up 84 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x A If more disablements shall be done continue like above If not press Return to menu B3 Scroll or press Return to menu H2 Scroll or press Return to log off 85 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 4 Re enable zone H2 B4 Disabled zones are listed in menu H4 U1 from which it is also possible to get a print out Re enabling via this menu has higher priority than automatic re enabling When all zones have been re enabled The LED Disablements L8 will be turned OFF if there are no other disablements in the system NOTE It is not possible to collectively re enable a number of alarm points zone address that are individually disabled via menu H2 B2 Text in display Comments Access According to chapter Access see page 77 Scroll to menu H2 If there are no zones to re enable menu B4 will be sh
59. Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Zones are set in test mode LED Test mode L9 wait will light up Zone in TEST MODE Perform the tests 001 002 003 004 End test ACCEPT The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press Return two times you will be logged out from menu H1 Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabled also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the c i e will light up about ten seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM A sensor in test mode will not be able to activate fault After 60 minutes or Zones in test mode 001 002 003 You are no longer in menu Return H1 but still in test mode Return NOTE See chapter Alphanumeric display LCD in the control unit page 20 regarding priority order When required Zone in TEST MODE Press A to end the test Access code 001 002 003 004 End test ACCEPT mode
60. Show information about Site Specific Data H5 A4 ___ 114 27 6 Display current consumption in unit H5 A5 115 27 7 Display current consumption COM BS4 loop H5 A6 __ 116 27 8 Display statistics for COM loop H5 A7 117 27 9 Select unit on COM loop to use for trigging H5 A8 __ s i1 18 27 10 Activate address setting mode for DU H5 A9 119 27 11 Change access code for PC communication H5 A10 _ 120 27 12 Change access code for service H5 A11 121 28 Acknowledge FAULTS H6 122 29 Perform ZONE TEST test mode H7 123 30 Maintenance H8 125 30 1 Access code for maintenance 123 30 2 Disable or re enable outputs for routing equipment H8 S1 126 30 3 Disconnect loop H8 S2 127 30 4 Re connect loop H8 S3 128 30 5 Acknowledge SERVICE signal H8 S4 129 30 6 Clear weekly average H8 S5 130 30 7 De activate alert annunciation function H8 S6 131 30 8 Test alarm devices H8 S7 132 30 9 Safe shut down of control unit H8 S8 133 30 10 Activate address in alarm mode H8 S9 134 30 11 Synchronize the control units H8 S10 136 30 12 Change access code for maintenance H8 S11 138 31 Interlocking outputs and inputs H9 139 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 31 1 Activated interlocking outputs inputs H9 C1 139 31 2 Activate interlocking output H9 C2 140 31 3 Reset interlocking output H9 C3 141 31 4 Disable interlocking outpu
61. T How many events should be printed 010 ACCEPT Comments According to chapter Access see page 77 Press A for display presentation or Press 1 for print out The most recent event will be shown i e use AX to scroll upwards in the list Press Return to menu U7 XX in the example control unit number XX 99 Win512 Press A to start print out AN Printing started To stop printing press C and 0 simultaneously ACCEPT Show event log Printout l yes Scroll or press Return to menu H4 Scroll or press Return to log off More than one alarm point in zone 456 have activated fire alarm 107 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 26 8 Configuration H4 U8 In a control unit the menu H4 U8 can be used to see the following settings made in Win512 Tools menu for that specific control unit Number of addresses that can be used i e xxx 128 256 or 512 set in EBL512 settings dialog box Language The language for texts presented in the alphanumeric display print outs Language file nnnn SST to be downloaded is selected in Download software dialog box Convention Different countries have different conventions i e country specific functions etc Convention is set changed in Win512 menu Tools Settings Win512 Settings dialog box It is no
62. T Cut off FAULT Output unit techn no xxxxxx e Fault in the output unit RAM e Fault in the output unit EPROM e Fault in the output unit EEPROM site specific data Replace the output unit output unit p c b FAULT Read write site data SSW CU xx SSW data that is changed during operation i e sensor values access codes etc e If the C U was made powerless i e no mains and no the battery without first doing a Safe shut down of control unit via menu H8 S8 see page 133 this fault might be generated when the C U is powered again After fault acknowledge the SSW will get default values and the fault will be corrected serviced e Some external influence has caused a fault in the SSW This is very serious Call for service personnel engineer FAULT Restart CU nn code xx yyyyyyyyyy Control unit restart has occurred See also page 74 nn Control unit number 00 29 NOTE nn 55 TLON conn board 1590 not programmed e g after it has been replaced See TLON Manager Operating Instr 58 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x xx 00 Power On Restart Power supply connected xx 01 Watchdog Restart xx 02 Accidental jump to reset vector xx 03 External restart caused by external watchdog user e g after SSD download or jumper JP4 RESET on the main board 1556 has been used xx
63. TLON network In a TLON network there is two or more control units connected A TLON connection board 1590 is required in each control unit connected to the network When the 1590 board is on place and the cables are connected for each control unit do as follows 1 Take away the rectifier fuse F1 and a battery fuse F2 or F3 on the charger board 1557 1657 Connect the batteries to the charger board 1557 1657 Connect the rectifier to the mains 230 V AC Replace the rectifier fuse F1 and the battery fuse F2 or F3 on the charger board 1557 1657 LED Operation L6 indicate that the 24 V DC power supply rectifier and or battery is okay An automatic reset restart will now take place see chapter Restart page 74 5 The TLON connection board is mounted on the main board 1556 Network cable connections are made on the connection board 1555 T B P1 64 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 17 2 1 17 3 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 7 When all control units are power supplied the TLON network installation have to be done before the site specific data SSD can be downloaded see chapter Programming SSD download page 67 8 See also chapter Calibration of supervised outputs H5 A1 page 111 If you know that one or more of the control units are to be started up later do as follow Create in Win512 the
64. The EBL512 system is intended for small medium and large installations The intelligent control units offer the system designer and end user a technically sophisticated range of facilities and functions Programming PC S W Win512 and commissioning of the control unit system is very easy Start with one control unit and then when required add more units The TLON network makes it possible to install the control units in one building or in many buildings PC S W Win512 is used for programming and commissioning of one or more control units e create download backup upload of site specific data SSD e download of S W settings conventions configurations C U amp system data etc e create download the user definable text messages shown in the alphanumeric display in the C U ext FBP Display units Win512 shall have the same or higher version number as the EBL512 S W version number e g 2 5 x and 2 5 x respectively Backup require the same version number in Win512 and EBL512 Old files can be opened and saved in a higher version of Win512 and thereafter downloaded TLON Manager is used for network programming The former Charger board for EBL512 had the type no 1557 13 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 4 Control Unit Figure 1 The EBL512 Control Unit 1548 1549 The look
65. Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 9 Disable Re enable alarm devices H2 B9 Outputs programmed as type 3 alarm device sounder can be disabled all at the same time Disabled alarm devices means that even if the control expression trigger condition for output respectively is fulfilled the output will not be activated Disabled alarm devices are indicated by LED Fault Disablements Alarm devices L13 and LED Disablements L8 and is also shown in menu H4 U1 The outputs in one or more control units can be disabled or the outputs in all control units The outputs will be disabled until re enabled again via this menu NOTE This function is not the same as push button Silence alarm devices P3 see chapter Silence Alarm devices page 26 This function has higher priority than Silence alarm devices Action Text in display Comments Access According to chapter Access see page 77 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B9 Disable Re enable alarm devices ACCEPT B9 A Disable 0 or Re enable 1 alarm Press 1 or 0 write the devices 1 CU 99 99 lt ALI ACCEPT CU number or 99 for all CUs and press A to accept A Disable Re enable alarm devices Scroll or press Return to ACCEPT B9 menu H2 Scroll or press Return to log off
66. address setting 1587 board the ext FBP SW mode setting etc If there is a program memory fault in the ext FBP there will be a fault message in the ext FBP display Memory fault in program area n n l or 2 The ext FBP will not work 50 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x FAULT Configuration control unit xx Fault in the SSI EBL512 settings downloaded from Win512 FAULT CU xx has no contact with CU xx Can be shown in conjunction with new S W download e Check the TLON network cable connections e Faulty TLON connection board 1590 e No power supply to the control unit FAULT CU xx has wrong information Can be shown in conjunction with new S W download and or when commissioning a system One or more control units might have data stored that is not the same in all control units If a control unit restarts in conjunction with this fault a synchronization will start automatically otherwise a synchronization has to be started via menu H8 S10 or via Win512 NOTE It is important that all control units that are supposed to exist SSD downloaded via Win512 are running and are connected to the TLON network The TLON network programming has to be done FAULT CU xx high current consumption The control unit current consumption is gt 2 5A gt 3 6A in alarm state and because of this the battery charg
67. al type 1 fire ventilation and or type 2 extinguishing system can be disabled all at the same time Disabled control output means that even if the control expression trigger condition for the output respectively is fulfilled the output will not be activated Disabled control outputs are indicated by LED Disablements L8 and is shown in menu H4 U1 The outputs in one or more control units can be disabled or the outputs in all control units The outputs will be disabled until re enabled again via this menu Access According to chapter Access see page 77 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT B1 Scroll to menu B8 Disable Re enable all control exting and ventilation outputs ACCEPT B8 A Disable 0 or Re enable 1 outputs 1 Press 1 or 0 write the CURIS MCS Se A ACCEPT CU number or 99 for all CUs and press A to accept A Disable Re enable all control exting Scroll or press Return to and ventilation outputs ACCEPT B8 menu H2 Scroll or press Return to log off 76 Including Addressable siren 3377 and Addressable sounder base 3378 Also the Extinguish equipment output on the German FBP interface board 1583 738 NOTE Outputs disabled for a specific control unit e g CU 03 can not be collectively re enabled via CU 99 You have to re enable the outputs for the specific control unit s e g CU 03 91 Panasonic Electric
68. alarm It is also used to disable re enable fire alarm points zones and in control conditions expressions to activate the programmable outputs Together with the presentation number a user definable 40 characters text message alarm text can be displayed if programmed 00 99 01 99 The address within the zone 00 Zone number only will be displayed e g for one or more conventional detectors connected to a zone interface ADB MIO or 8 zones expansion board input 001 999 Zone number NOTE 1 Zone numbers 001 999 can be used but more than 512 alarm points or zones per c i e is a violation to the EN54 2 standard NOTE 2 When the function Redundancy in distributed system is used it is presented as 999 xx The zone number 999 is indicating that it is an alarm from a Control Unit and the address xx is indicating from which CU xx xx could be an individual CU xx 00 29 or several CU s xx 99 Also in the Alert Annunciation Units and Presentation Units Display Units The presentation number or a user definable 40 characters text message can also be shown in the old type of display units connected to the COM loops 33 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 14 Operating Instructions Fire alarm system EBL512 V2 5 x Alarm types 14 1 In case of a fire analog detectors sensors conventional smoke and or heat detectors manual call points and pr
69. arm system EBL512 V2 5 x Sensor 00000N Current algorithm nnnnnn 3 Sensor OOOOO0ON Min OCC Momentary XX C Mane sea 3 Sensor 00000N Current algorithm nnnnnn Return Start Sensor 000000 Write the sensor s techn number and or press A to accept or press Return to menu U5 Sensor values Scroll or press Return Printout l yes to menu H4 Scroll or press Return to log off When scrolling the message Please Wait might be shown for a second and No more sensors found in the system before the lowest and after the highest possible technical number in the system Here follows the alternative 1 printout Scroll to menu US Sensor values Press 1 to accept Printout l yes U5 Start Sensor 000000 Write the techn numbers End Sensor and or press A to accept Printing started To stop printing press Press A and menu U5 C and 0 simultaneously ACCEPT will be shown again Start Sensor 000000 Write the sensor s techn number and or press A to accept or press Return to menu US Sensor values Scroll or press Return Printout l yes to menu H4 Scroll or press Return to log off Perf Factor Performance factor Low min 0 The detector is mounted in a stable environment High max 2 55 The detector is mounted in an unstable environment See also Planning Instructions chapter Performance factor
70. ault will be generated if something goes wrong They are rechargeable sealed lead acid batteries and normally maintenance free The producer s instructions shall always be followed The ambient temperature affects the battery capacity self discharge and life span It should not be higher than normal room temperature approx 20 22 C For highest safety batteries used in a fire alarm installation should never be older than four years 148 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 37 How to avoid unnecessary nuisance fire alarms We all realise when life buildings production facilities etc shall be saved it is of utmost importance that an initial fire is detected as soon as possible That s why more and more automatic fire alarm systems are installed In an automatic fire alarm installation especially if smoke detectors sensors are used everybody in the building needs to be informed how to avoid so called unnecessary nuisance fire alarms To avoid trouble and unnecessary expenses there are a couple of things to bear in mind Here are some advice and tips Tobacco smoke The detectors sensors can not sense the difference between smoke and smoke They can not separate tobacco smoke from smoke from a fire Intensive tobacco smoking in connection with bad ventilation can cause a fire alarm Welding grinding cut
71. board Check programming Win512 FAULT 24 V for ext equipment CU xx Check the fuses F2 and F4 on the connection board 1555 Supervised output S2 is also supplied via F2 and F4 FAULT 24 V for routing equipment CU xx Check the fuses F1 and F3 on the connection board 1555 Supervised output S3 is in some conventions configurations supplied via F1 and F3 Indicated by LED L15 blinking FAULT 24 V out output unit xxxxxx The output current is gt 4A The output might also be turned off PFAUCT AAU xx 1587 board x CU xx AAU 1735 1736 The unit is programmed as another type of unit than the SSD says or fault in the unit Uline s Alarm input Iba boari x CU xox The zone line input x on the 1580 board placed in control unit xx master is used for a single slave unit control unit or several control units connected in parallel i e the board is used for Redundancy in distributed system The input x is in fire alarm state but there is no activated fire alarm 48 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x in any control unit and no fault on the TLON Network Check the connections e g of the alarm resistor in the slave unit units FAULT Alarm input tech no xxxxxx The zone line input Input 0 on the 3361 unit with technical number XXXXxx is used for a single slave unit control unit o
72. c Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Short circuit on the COM loop x one or more short circuit isolators are connected on the loop Check the specified and isolated segment on the loop e g CU lt gt ASFO between the control unit and short circuit isolator no 0 Each 10 minute is an attempt made to re enable the isolated segment again Some external influence or after download has caused a checksum fault in the from Win5 2 downloaded Site Specific Data SSD An SSD download is required This is very serious Call for service personnel engineer immediately AAU 1735 1736 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD EPU 1728 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD 60 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x PAURE SSID TBP Sox 1587 ponard x GU Fox BP 1826 1828 There is no SSD Site Specific Data downloaded to the unit or something is wrong in the downloaded SSD FAULT Supervised output x CU xx If the output is programmed for sounders type 3 alarm devices it is also indicated by LED Fault Disablements Alarm devices L13 blinking If the output is programmed
73. ccording to chapter Access see page 77 Scroll to menu H10 Enter the old code the A The digits are replaced new code and the new jo in the display code again The code was not correct Try again The code was correct and is now changed to the new code Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 74 If the valid access code is unknown a back door code is available 144 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 33 Annual control The building occupier is highly recommended once a year to do some tests beside the monthly tests To avoid the Fault tx output s to be activated they can be disabled via menu H8 S1 or via an open door se chapter Door open page 30 Regarding the fault condition see chapters Fault page 46 and Fault messages page 47 NOTE Most of the faults have a delay Each control unit should be tested as follows e Perform monthly test menu H1 e Remove one battery fuse F2 or F3 on the charger board 1557 1657 The following fault message is to be shown FAULT Battery not connected CU xx NOTE xx is depending on control unit e Put back the fuse and acknowledge the fault Menu H6
74. channel H4 U2 A list of all disablements by time channel s in the system From this menu it is also possible to get a print out NOTE Other disablements are listed in menu H4 U1 Text in display Access According to chapter Access see page 77 ae Scroll to menu U2 n Press 1 for an automatic print out of all disablements in the system Press A for presentation in the display L a list in which you can scroll If there are no disablements and if Return is pressed menu U2 will be shown again Press A and menu U2 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off When scrolling in the list the message No more zone addresses disabled by time channel found in the system can be shown 95 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 26 3 Doors open H4 U3 The LED Door open L10 is lit to indicate that one or more doors are open See chapter Door open page 30 This menu is a list of all open doors and it is also possible to get a print out Access According to chapter Access see page 77 Scroll to menu U3 Press 1 for an automatic print out of all open doors Press A for presentation in the display L a list in which you can scroll If there are no open doors and if Return is pressed menu U3 will be shown again Pre
75. ctric Works Fire amp Security Technology Europe AB MEWO01002 20 Operating Instructions Fire alarm system EBL512 V2 5 x EBL512 settings download 20 1 EBLS512 settings are normally factory downloaded before the delivery It is however possible to download the following on site e The number of addresses max loop units e Serial number normally not changed e Date normally not changed e Adhesive type Type 1 old Type 2 new acc to EN54 If you wish to download new EBLS12 settings a PC and Win512 are used Before download the PC has to be connected to the D connector J1 in the control unit main board 1556 in question 1 Start Win512 In the Tools menu open the EBL512 settings dialog box 2 Set the c i e in Bootstrap mode i e set jumper JP1 BOOT in position on the main board 1556 3 Do a reset restart i e set jumper JP4 RESET in position momentarily approx 1 second 4 The buzzer will now sound intermittent and LED LD101 starts blinking indicating that the control unit is in Bootstrap mode 5 In the Win512 settings dialog box click Read The buzzer will be silenced the actual settings shown and in the Win512 log view will be shown System information has been uploaded Write the new settings in the fields respectively Do like 3 amp 4 above Click Download The buzzer will be silenced and a Win512 box will be displayed Click OK NOTE If Max loop u
76. e amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 31 Interlocking outputs and inputs H9 31 1 Activated interlocking outputs inputs H9 C1 Access According to chapter Access see page 77 Scroll to menu H9 A C IH MM This is a list in which you can scroll Depending on activated output and or input the AAA interlocking comb following will be l r l area shown ble me PP interlocking comb point within the area Press Return to menu Cl Scroll or press Return to menu H9 Scroll or press Return to log off 139 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 31 2 Activate interlocking output H9 C2 The output in each interlocking combination area point can be manually activated via this menu The corresponding interlocking input will be monitored in the same way as if the output was activated by its control expression Reset has to be performed via menu H9 C3 Access According to chapter Access see page 77 Scroll to menu H9 Scroll to menu C2 Write the area and point Press A to accept and or Return to menu C2 Scroll or press Return to menu H9 Scroll or press Return to log off 140 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alar
77. e new code Scroll or press Return to H5 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 74 120 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 12 Change access code for service H5 A11 For security reasons the default code should be changed Access According to chapter Access code for service H5 see page 110 Scroll to menu A11 Enter the old code the The digits are replaced new code and the new in the display code again The code was not correct Try again e The code was correct and N N is now changed to the new code Scroll or press Return to H5 Scroll or press Return to log off NOTE After change of access code it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the new code in a Flash ROM see page 74 If the valid access code is unknown a back door code is available 121 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 28 Acknowledge FAULTS H6 Regarding fault indication etc see chapter Fault page 46 See also chapter Fault acknowledge page 63
78. ed also the parts of the zones in test mode not visible for the test personnel are disabled In order to shorten the testing time any time delay for the detectors zones in test mode will be disabled i e fire alarm will be detected faster than normally In the tested alarm point the LED will light up and the LEDs Fire L1 in the C U will light up about ten seconds then the alarm point will be automatically reset The printer if available will print out every tested alarm point Zone xxx Address xx Time HH MM A sensor in test mode will not be able to activate fault After 60 minutes or Zones in test mode 001 002 003 004 You are no longer in menu Return H7 but still in test mode Return NOTE See chapter Alphanumeric display LCD in the control unit page 20 regarding priority order When required Zone in TEST MODE Press A to end the test Access code 001 002 003 004 End test ACCEPT mode Scroll to menu H7 AN Perform ZONE TEST The LED Test mode is ACCEPT H7 turned OFF If more zones are to be tested continue as above If not scroll or press Return to log off NOTE During the test the following information will be shown in all other c i e displays Zones in test mode 001 002 003 004 In DBI Danish convention only one zone NOTE_2 If an alarm point e g a manual call point is in alarm state when the test mode is ended there will not be a fire alarm activated
79. ed by service personnel Same menus as in access level 2 plus the following S1 Disable or re enable outputs for routing equipment Fire brigade tx amp Fault tx S2 Disconnect loop S3 Re connect loop S4 Acknowledge service signal I If code for access level 3 or 4 has been used to logon to access level 2 new logon to access level 3 is not required 24 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 7 5 Access level 4 From access level 2 the user can logon to access level 4 which gives access to the following menus normally used by Service Commissioning Engineers Same menus as in access level 2 and 3 plus the following A7 Display statistics for COM loop A11 Change access code for service access level 4 7 6 Access level 5 Used by Service Commissioning Engineers when a PC is to be connected to the control unit i e when Win512 is to be used for backup download of Site Specific Data S W settings configurations C U and system data on line status checking etc If code for access level 4 has been used to logon to access level 2 new logon to access level 4 is not required 25 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 8 Operating Instructions Fire alarm system EBL512 V2 5 x Silence Alarm devices 8 1 In the control unit on the FBP there is
80. ed to the Charger board Max two 1582 1587 boards together per control unit 1582 will be replaced by 1587 4 Max one 1583 board per control unit 1583 board is not possible to use in Swedish SBF convention 5 Max four 1584 boards per control unit 1584 board is only possible to use in Swedish SBF convention 12 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 3 2 3 3 3 4 3 5 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 1657 which handles the charging of the batteries etc Low or High current charging mode is selected depending on the wanted backup battery capacity backup time and or the EBL512 current consumption See the EBL512 Planning Instructions chapter Power supply for more information S W versions Due to continual development and improvement different S W versions can be found When installing a new control unit in a system with older control units you might have to update the S W in the old control units It is highly recommended to have the same S W version in all control units but as from S W version 2 X x the same S W version is required in all control units Documents The following documents except this document are available e Planning instructions e Drawings Normally information that is found in one document is not to be found in another document i e the documents complement each other Applications
81. em voltage is normally 24 V DC 24 V to earth is normally 12 5 V O V to earth is normally 11 5 V Voltage to earth lt 3 4 V Earth fault minus Voltage to earth gt 18 3 V Earth fault plus Check all cables for damage etc The function of the control unit can not be guaranteed Call for service personnel engineer FAULT Earth fault o tput nit XXXXXX Check all cables connected to the output unit FAUS T EBRU sox 50r boardi CU EPU 1728 The unit is programmed as another type of unit than the SSD says or fault in the unit PAULL Expansion boardi x loop x CUR This is valid for the I O Matrix board 4582 no x connected on COM loop x in the control unit no xx There is some internal fault on the board FAULT External FBP x board x CU xx The control unit i e the 1582 board can not communicate with the ext FBP or data converter 53 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Check the connections Check the cable break Check the address DIL Switch in the ext FBP Is correct address set Several ext FBPs have the same address Faulty ext FBP FAULT External fuses control unit xx The fault is to be found in the external power supply blown fuses etc FAULT External power supply CU xx The fault is to be found in the external power supply connected to input in control unit
82. ents L8 is also indicating one or more disabled interlocking outputs Access According to chapter Access see page 77 Scroll to menu H9 Press A to accept and or Return to menu C3 Scroll or press Return to menu H9 Scroll or press Return to log off 142 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 31 5 Re enable interlocking output H9 C5 Disabled interlocking outputs are listed in menu H4 U1 from which it is also possible to get a print out Interlocking outputs Type Interlocking can be re enabled via this menu but not via menu H2 B6 If 000 00 is entered all interlocking outputs disabled via menu H9 C4 and 000 00 will be re enabled at the same time Text in display Access According to chapter Access see page 77 Scroll to menu H9 Scroll to menu C5 This is a list in which you can scroll If there are no disabled outputs menu C5 will be shown again Press A for re enable or Return not re enable to menu C5 Scroll or press Return to menu H9 Scroll or press Return to log off 143 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 32 Change access code for daily duties H10 For security reasons the default code should be changed Access A
83. er sounds steady The Fault tx output is activated A new download of S W system program is required NOTE After the SSD download see chapter Programming SSD download page 67 the following might be shown in the display Checksum fault in downloaded data Control unit will now restart After the restart see above and the text message FAULT Restart CU nn code xx yyyyyyyyyy Date MM DD Time HH MM Serviced Another text message will be shown in the display FAULT Site specific data SSD CU nn Date MM DD Time HH MM This text message means that the SSD have not been downloaded A new download has to be performed 75 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 21 1 Operating Instructions Fire alarm system EBL512 V2 5 x Boot menu The Boot menu should be used by authorised personnel only NOTE Vital data can be erased via this menu The Boot menu is opened as follows Perform a reset restart e Power off power on or e Jumper JP4 on the main board The following text messages will be show in the alphanumeric display Checking program memory And after that Bootimngn 4 4 When the text Booting appears press Access and 0 1 sec later also press 1 and the Boot menu will be shown 1 Reset 2 Clear mem 4 Read AD 5 MSClo ck 6 Checksum 7 Cursor 8 Texts Press 1 to perf
84. ge menu S4 will be shown again L a list in which you can scroll If it is the correct i sensor to acknowledge press Fault acknowledge po If not scroll or write the wanted sensor and press Fault acknowledge or press Return to S4 Fault acknowledge f If more service signal acknowledgements shall be done continue like above If not press Return to menu S4 Scroll or press Return to menu H8 Scroll or press Return to log off LED Service L12 will be turned off when all sensors have been acknowledged 129 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 6 Clear weekly average H8 S5 If a sensor analog smoke detector is replaced without having generated SERVICE signal its week average sensor value has to be set to the default value otherwise the new clean sensor will inherit the old sensor s value It is possible to clear the week average sensor value for each sensor individually NOTE First replace the sensor then clear the week average value as soon as possible Authorised service personnel only must do this Used incorrectly it can cause nuisance fire alarms The first week average sensor value after clearing will be calculated within one hour and after that each week Action Text in display Comments Access According to chapter Access code for maintenance see page 125 Scr
85. get access to the menu tree via an access code to carry out disablements etc In conjunction with fire alarm some information is available and some actions are possible to perform via the Fire alarm menu X1 X9 without log on see chapter Fire alarm page 35 gg Return white Used to stop input of data leave a menu one step up and to log off 1 9 and 0 Numeric keys for the figures 0 9 Used to clear delete just written data N T Used to accept a menu and accept input of data Left right keys are used to move the cursor in a menu Jp down keys are used to scroll between the menus 19 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 6 Operating Instructions Fire alarm system EBL512 V2 5 x Normal operation 6 1 When the control unit system is in normal operation quiescent state i e no fire alarms no faults no disablements no service signals no zones in test mode no activated interlocking in outputs no open doors and or Alert Annunciation function not enabled only the LED Operation L6 should be lit Alphanumeric display LCD in the control unit In normal operation quiescent state some system information is shown in the LCD in the control unit The system information has the lowest priority The priority order is Fire alarms Co incidence alarms Pre warnings Quiet alarm Used e g for fan control AAF alarm Evacuate info
86. h mm NOTE The date is in the Ukrainian convention S W version gt 2 2 3 and the Australian convention shown as DD MM Time Serviced According to chapter Access code for maintenance see page 125 Shown for 3 sec then one of the three alternatives Count down starts from nnn 300 seconds Disconnect the power supply mains and battery When the power supply is connected again or after 300 seconds if powered all time there will be an automatic reset restart After restart power on see page 74 there will be a fault activated This fault has to be acknowledged see chapter Acknowledge FAULTS H6 page 122 7 Tf not a fault FAULT Read write site data SSW CU xx might be generated when you power up the control unit again 133 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 10 Activate address in alarm mode H8 S9 One alarm point address not a whole zone can be set in alarm status The built in LED in the alarm point detector will be turned on to indicate the alarm Among other applications this function is used for installations on ships NOTE All outputs standard and programmable which would have been activated by a real fire alarm from the same alarm point will be activated by this manual alarm as well Access According to chapter Access code for maintenance see page
87. hen a printer is available See also chapter Fire alarm page 35 Unique user definable text messages for each alarm point and each zone line input can also be shown in Display units 2235 2236 connected on the COM loops All user definable text messages up to 40 alphanumeric characters each are created and downloaded via Win512 See Planning Instructions chapter User definable text messages See also the Win512 help chapters help topics Download and Display unit menu An older DOS based PC program NEWTEXT can also be used see Planning Instructions chapter Display units addressable See also Win512 help Using old SSD Site Specific Data SSD created in an earlier Win512 version can be opened in e g the latest Win512 version edited if required saved and downloaded to an EBL512 with the latest version 69 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 19 Operating Instructions Fire alarm system EBL512 V2 5 x New system program S W version download 19 1 The latest software S W version of the EBL512 system program is factory downloaded before the delivery Due to continual development and improvement different S W versions can be found The valid S W version can be read in menu H3 or via Win512 New S W can on site be downloaded via Win512 See also the Win512 help chapter help topic Download Software New S W for the 1728 1735 1736 amp
88. his fault is acknowledged see chapter Acknowledge FAULTS H6 page 122 there is a 5 minutes delay before a new key cabinet fault can be generated again Alarm Acknowledgement Facility AAF One or more Alarm Acknowledgement Facility Controls are used in the system During the Acknowledgement Period 10 60 sec there is an indication in the control unit display AAF zone zz activated During the Investigation Period 0 3 min there is an indication in the c i e display AAF zone zz investigation in progress See EBL512 Planning Instructions chapter Alarm Acknowledgement Facility AAF for more information regarding the AAF function Quiet alarm One or more smoke detectors programmed for quiet alarm e g used for fan control stop start depending on the type of fan have passed the fire alarm level Quiet alarm is e g used in conjunction with the I O Matrix board 4582 an application board for fan control and an I O unit 3361 for fan control NOTE These units are available on the Australian market only Indications and actions LEDs Fire L1 are blinking 0 4 0 4 sec the buzzer sounds 0 8 5 sec and there is a Quiet alarm presentation in the display Quiet alarm detector ZZZ AA user definable text message Programmable outputs for quiet alarm e g 3361 outputs controlling supply air fans and standard fans i e any output with a control expression containing
89. hown in the display see chapter Key cabinet alarm reset page 45 Single encapsulated reset Like Single reset but with an encapsulation function as well Normally when an alarm point or zone having activated fire alarm is reset when still in alarm status it will activate a new fire alarm within 20 seconds According to the EN54 2 standard When Single encapsulated reset is performed an alarm point or zone still in alarm status will not only be reset but also disconnected i e it will not activate a new fire alarm within 20 seconds It has to be re enabled via menu H2 B5 before it can activate a new fire alarm This function set in Win512 is a violation to the EN54 2 standard LED Disablements L8 is indicating one or more disablements in the system NOTE When Multi reset or Single reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press Alarms queued P1 and hold them pressed for gt 0 5 sec By Single reset The fire alarm displayed in the LCD first row to the left will be reset and disabled By Multiple reset The fire alarm displayed in the LCD first row to the left will be reset and disabled or the points in alarm status within one zone will be reset and disabled or the whole zone conventional will be reset and disabled Alert Annunciation Regarding the function see chapter Alert Annunciation AA alarm page 39 and EBLS512 Planning Instruction
90. ht be turned ON as well Output s for routing equipment Fault tx is are activated Output s for general fault is are activated Output s for general charge fault might be activated A fault message date and time are shown in the control unit s display After the time might be shown More faults more than one fault is generated in the system If Fault latching is selected in Win512 default after the time might be shown Serviced the fault is already serviced corrected e Login according to chapter Access page 77 e Use menu H6 access level 2 for fault acknowledge see chapter Acknowledge FAULTS H6 page 122 Menu H6 is a list showing a maximum of 200 faults not acknow ledged faults and or acknowledged but not corrected faults The first fault in the list is the most recent fault When a fault is acknowledged and corrected it will be removed from the list and a new fault can be shown Corrected faults are shown in the event log menu H4 U7 e All faults have to be individually acknowledged one by one push button Fault acknowledge P6 Use or keys to scroll e Ifa fault has been corrected before it has been acknowledged the text Serviced is added after the time It still has to be acknowledged e When a fault is corrected and acknowledged it will disappear from the list H6 e When all faults have been acknowledged output s for routing equipment Fault tx is are reset
91. i e the LED Fault tx activated L11 will be turned off e As long as there are faults i e not acknowledged faults and or acknowledged but not corrected faults the LED General fault L7 will be lit and general fault and maybe general charge fault output s are activated 54 Indicating that output for routing equipment Fault tx is activated 63 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 17 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Commissioning an installation 17 1 17 2 Before you connect the power supply to a control unit all other cable connections shall be made Check once more that they are correct Single Control Unit 1 Take away the rectifier fuse F1 and a battery fuse F2 or F3 on the charger board 1557 1657 Connect the batteries to the charger board 1557 1657 Connect the rectifier to the mains 230 V AC Replace the rectifier fuse F1 and the battery fuse F2 or F3 on the charger board 1557 1657 LED Operation L6 indicate that the 24 V DC power supply rectifier and or battery is okay An automatic restart will now take place see chapter Restart page 74 The site specific data SSD can now be downloaded see chapter Programming SSD download page 67 The SSD is created via the PC program Win512 See also chapter Calibration of supervised outputs H5 A1 page 111 Control Units ina
92. ies to detect faults during the commissioning it is possible to use the Sensitive fault detection mode The time delay for each fault will be reduced NOTE Don t forget to turn off this mode after the commissioning Access According to chapter Access code for service H5 see page 110 Scroll to menu A2 A Press A or 1 and A to accept ON is indicated by LED Fault tx activated L11 and the Fault output for routing equipment This mode is ON until turned OFF in this menu A2 Scroll or press Return to H5 Scroll or press or Return to log off m 1 ue WAN 112 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 4 Direction for communication on COM BS4 loop H5 A3 The communication direction is normally automatically changed every minute to ensure that the wires are okay all the way To make trouble shooting easier e g during the commissioning it is possible to lock the communication on a COM or BS4 loop in one direction FAULT No reply techn no xxxxxx will be generated with a reduced delay time This function can be used to list all technical numbers behind a loop cut off NOTE since they require communication in both directions at the same time The locking only works as long as you see the text Loop cut off and short circuit faults can not be generated COM loop is currently comm
93. ing is turned off and will be so until the current consumption has decreased to lt 2 5A lt 3 6 A again PAUL CUE Ori COMS IOOP X This is indicating a single break on the loop Communication has to be performed in both directions to find all the units It might also be shown after a short circuit on the loop when short circuit isolators are used communication in both directions A double break will give the message FAULT No reply It can also be indicating a too long COM loop cable i e all units are not found until the communication is performed in both directions NOTE Communication in both directions lasts for about ten minutes before a new attempt to communicate in one direction is performed If the break remains a new ten minutes period starts and so on If the fault is acknowledged and the break is corrected during a ten minutes period it will not disappear from the list until the end of the ten minutes period 51 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 8 zones expansion board DET8 This is indicating a break cut off or a missing end of line resistor on input x zone line on the 1580 board placed in control unit xx It can also be a detector that have been removed stolen from its base NOTE The input can as an alternative be used for a single slave unit control unit or several
94. ing mode in the following Display Units connected to an Ext FBP DU interface board 1587 in the c i e e Ext Presentation unit 1728 e Alert Annunciation unit 1735 1736 e Ext FBP 1826 1828 A specific unit or all units connected to one 1587 board can be activated for address setting NOTE The units have to be in operation and in quiescent condition i e the units have to have an address already Scroll to menu A9 A According to chapter Access code for service H5 see page 110 Write control unit number the board number 0 1 and the unit s address 99 All units on the selected 1587 board Press A to accept Scroll or press Return to H5 Scroll or press Return to log off The address is thereafter edited in the unit respectively 119 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 11 Change access code for PC communication H5 A10 As a protection against unauthorised personnel programming the system via Win512 an access code level 5 for PC connection is required For security reasons the default code should be changed NOTE This code requires eight 8 digits Access According to chapter Access code for service HS5 see page 110 The digits are replaced in the display The code was not correct Try again The code was correct and is now changed to th
95. ipment power supply output or one or more supervised outputs type 4 routing equipment have generated fault s L16 Fire brigade tx delay The alert annunciation function is enabled i e time yellow channel controlling this function is on S See also chapter Door open page 30 14 This is also valid when the c i e has no contact with a unit with such an output e g a 3377 3378 3361 etc 15 Connection board 1555 terminal block P1 37 38 fuses F1 and F3 This is also valid when the c i e has no contact with a unit with such an output e g a 3361 etc 17 The Alert Annunciation function is described in the EBL512 Planning Instructions chapter Alert annunciation The LED L16 will be on if the AA function is enabled for at least one alarm point zone Normally is only one time channel used for this function but two or more channels can be used The AA function can as an alternative be continuously on 18 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Push buttons Keypad on the Control Panel CP Key push button Operation function Fault acknowledge Used to acknowledge the faults shown in menu H6 Also used yellow to acknowledge SERVICE signal see menu H8 S4 Paper feed white Used for paper feed when a built in printer is available in the C 1 e Access white Used to log on i e to
96. ject see separate TLON network documentation Add a Control Unit in a TLON network When adding a control unit to a running installation you have to have the same software S W version in all control units Often the new control unit has a newer version than the existing control units Normally the latest version is the best to use i e the control units in the running installation have to be upgraded As an alternative it is possible to download an earlier S W version in the new control unit 65 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 17 4 17 5 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Both alternatives are described in chapter New system program S W version download page 70 Open the current project in TLON Manager add one control unit and install download it according to the separate TLON network documentation Open the SSD for the current system via Win512 Add one control unit and the units connected to it and download the new SSD according to chapter Programming SSD download page 67 Make two TLON networks one It is very important that two or more presentation numbers Zone Address in the systems are not the same The system properties have to be the same Use one of the systems and add to it the control units etc from the other system If it is known from the beginning that two systems shall be one in the future it is
97. larm ZZZ zone number AA address According to chapter Access see page 77 Press 1 for an automatic print out Press A for presentation in the display This is a list in which you can scroll If there are no alarms and if Return is pressed menu U4 will be shown again Press A and menu U4 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off 8 When two or more zones or units zone addresses dependent on each other are in alarm status at the same time normal fire alarm will be activated in the system 97 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 26 5 Access Scroll to menu H4 A Disablement Printout l yes Scroll to menu US Rev Sensor values H4 U5 Operating Instructions Fire alarm system EBL512 V2 5 x The very first week average sensor value is calculated within 2 minutes after SSD download amp restart During these 2 minutes can no fire alarm be activated and the sensor value 000 will be shown The Performance factor and Min Max values are updated each night 00 00 i e the values shown are from the previous day Regarding the British Standard Marine Application convention see chapter Algorithm setting via menu H4 U5 page 101 Text in display Present system status on display and printer ACCEPT H4 Sensor values Printout l yes
98. le smoke detectors as well as conventional detectors and manual call points Programmable control outputs and output units are available Up to 512 addresses can be connected to each control unit c i e EBL512 is available in several types versions and configurations It can be connected to a TLON network a system with up to 30 control units Each control unit has access to all information EBL512 is designed according to the European standard EN54 part 2 and 4 The front conforms to S3654 Expansion boards In the control unit c i e it is possible to mount up to six expansion boards The following types are available 1580 8 zones expansion board 1581 8 relays expansion board 1582 External FBP interface board 1583 German FBP interface board 1584 Autronica interface board four BS4 loops 1587 External FBP DU interface board Regarding the expansion boards see also the EBL512 Planning Instructions and drawings Printer Control unit 1549 is equipped with a printer In control unit 1548 it is possible to mount a Printer 1558 In Ext Fire Brigade Panel 1826 it is possible to mount a Printer 1535 Power supply The main power source is a built in rectifier 1537 230 V AC 24 V DC 4 5 A The second power source is a backup battery 2 x 12 V In the c i e is space for two 24 27 Ah batteries Larger batteries up to 60 Ah has to be placed outside the c i e The batteries and the rectifier are connect
99. lements L8 and Fault Disablements Fire brigade tx L15 Disabled outputs are listed in menu H4 U1 Access According to chapter Access code for maintenance see page 4 ia or re enable outputs for ia equipment ACCEPT S1 Routing equipment for FIRE 1 FAULT 1 To move the cursor press l enabled 0 disabled ACCEPT 5 Edit and or press A to accept Disable or re enable outputs for Scroll or press Return to routing equipment ACCEPT S1 return to H8 Scroll or press Return to log off 126 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 30 3 Disconnect loop H8 S2 Before physical connection disconnection of loop units etc the loop or zone line shall be disconnected disabled i e there will be no voltage on the loop to avoid damage on the units and the c i e BS4 loop require an Autronica interface board 1584 in the control unit DET8 loop zone line requires an 8 zones expansion board 1580 in the control unit Text in display Comments Access According to chapter Access code for maintenance see page 125 Scroll to menu S2 Disconnect loop ACCEPT S2 Disconnect type 0 0 COM 1 BS4 Press 2 DES 3 L00p Unit ACCEPT 0 COM loop 1 BS4 loop 2 Expansion board 1580 3 Addr zone interface 2226 2335 2821 or 3361 MIO Press A to accept A Disconnect COM Loop
100. m system EBL512 V2 5 x 31 3 Reset interlocking output H9 C3 All activated interlocking outputs are listed in this menu Interlocking output activated via its control expression and with latching output selected in Win512 The output has to be reset via this menu Interlocking output activated via its control expression and with latching output not selected The output can be reset via this menu Interlocking output activated via menu H9 C2 The output has to be reset via this menu Action Text in display Comments Access bane to chapter bane see page 77 This is a list in which you can scroll If there are no activated outputs menu C3 will be shown again Press A for reset or Return no reset to menu C3 Scroll or press Return to menu H9 Scroll or press Return to log off 141 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 31 4 Disable interlocking output H9 C4 Interlocking outputs Type Interlocking can be disabled via this menu but not via menu H2 B3 The Interlocking Combination Area Point is to be entered to disable the output If 000 00 is entered all interlocking outputs will be disabled at the same time Up to 200 interlocking outputs can be disabled Disabled interlocking outputs are listed in menu H4 U1 from which it is also possible to get a print out The LED Disablem
101. might vary according to configuration country etc The control unit c i e is housed in a grey metal cabinet The door has a Plexiglas ahead of the FBP part see Figure 1 To open the door access level 1 a key is required supplied When the door is open you fully see the front the Fire Brigade Panel FBP and Control Panel CP see Figure 2 page 15 To open the inner door for the purpose of maintenance or servicing a screwdriver is required 14 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 2 eee eeee Extinguishing e e Silence buzzer Silence Ventilation Alarms queued alarm devices Fire brigade tx Reset Operation Evacuate _ Figure 2 The EBL512 front FBP upper black part and CP lower grey part The look might vary according to configuration convention etc An English front is shown in the figure See also chapter LED indicators and push buttons The fire brigade personnel use the FBP to take required operational control of the system and to see which alarm point zone s having generated fire alarm In the alphanumeric display LCD 2x40 alphanumeric characters the information displayed on the first row is depending on how many alarm points zones having generated fire alarm and also convention On the second row is a user definable text message shown if programmed for an alarm p
102. n Normal alarm devices routing equipment etc will not be activated In case of a pre warning the following will happen e The buzzer in the control unit sounds 0 8 sec each 5 sec 0 8 5 sec e LEDs Fire L1 are blinking 0 4 0 4 sec e Outputs programmed for pre warning are activated See EBL512 Planning Instructions Any programmable input can also be used to activate a pre warning Regarding the BS4 exp board 1584 for Autronica devices BS4 loops pre warning can also be generated by detector s connected to address units 3 Outputs programmed for General pre warning and outputs programmed for the activated pre warning s 34 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 14 2 Operating Instructions Fire alarm system EBL512 V2 5 x e On the first row in the c i e display the presentation number zone address is shown for the first pre warning e On the second row a user definable text message that for fire alarm will be shown if programmed Example pre warning zone 123 address 45 within zone 123 Pre warning detector 123 45 user definable text message Example pre warning zone 123 Pre warning zone 123 user definable text message If more than one pre warning is generated the LEDs Alarms queued L2 are blinking and the pre warnings will be automatically scrolled each five seconds Pre warning is automaticall
103. n A D converter The Control Unit pick up the digital values sensor values for each detector individually All evaluations and decisions are then made in the c ie Analog detectors are addressable an address setting tool is used for detector types 33xx 430x Old installations A DIL switch in the ASB see below is used for address setting for detectors 2xxx An analog detector has to be plugged in an analog sensor base ASB Analog Sensor Base ASB A sensor is plugged in an ASB which is connected to a COM loop see below Old installations Analog sensor base types 2xxx have a DIL switch for the COM loop address setting Conventional detector Detector with only two statuses i e normal and fire alarm The detector contains a closing contact and a series alarm resistor Normally plugged in a conventional detector base CDB see below connected to a conventional zone line input with an end of line device Some types are connected directly on zone line Old installations An addressable detector base ADB for conventional detectors see below could be connected directly to a COM loop Conventional Detector Base CDB A conventional detector is plugged in a CDB connected to a conventional zone line input Addressable Detector Base ADB Old installations An ADB for conventional detectors see above could be connected directly to a COM loop Panasonic Electric Works Fire amp Security Technology Europe AB
104. n progress The sounders will remain turned ON until they are turned OFF by pressing the push button Evacuate P5 again NOTE The alarm devices sounders will always be activated steady sound continuously irrespective of the fact that the outputs can be set to anything else for fire alarm e g intermittent 7 Alt when a programmable input is activated 8 Alt when the programmable input is de activated 29 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 12 Operating Instructions Fire alarm system EBL512 V2 5 x Door open 12 1 12 2 A special key is used to open the control unit door to get access to the front system see chapter Access levels page 22 The same type of key is also used to open the ext FBP door Door open is indicated by LED Door open L10 In Win512 System dialog box Door open tab the following can be programmed default settings shown LED Door open Indication door open affected by Door in any control unit or any external FBP Door open ina C U is indicated by LED Door open in all C U s and in all ext FBPs Door open in an ext FBP is indicated by LED Door open in all C U s and in all ext FBPs O Door in any control unit Door open in a C U is indicated by LED Door open in all C U s and in all ext FBPs Door open in an ext FBP is indicated by LED Door open in that ext FBP only O Door in control unit
105. nits are changed a Please enter your password dialog box will be shown 8 When the download is ready in the Win512 log view it will be shown System information has been downloaded 9 Read see 3 4 amp 5 above to verify the new settings 10 Remove jumper JP1 BOOT Do a reset restart see 3 above Regarding the reset restart see chapter Restart page 74 Follow the same procedure in each control unit Control Units ina TLON network All control units connected to a TLON network have the same convention via the SSD download but the number of addresses max loop units and the language can vary if required 6 To change the Max loop units a separate password for download is required This password is in conjunction with a Key eight digits and is available from the producer if you are authorized The Key is shown in Win512 and the procedure is described in the Win512 help 73 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 21 Restart A restart will delete or not delete the data in the control unit Here follow an explanation of the different data abbreviations and a table showing how the data respectively is affected FFD Fire alarms faults and disablements SSW Week average sensor values access codes supervised output calibration values and log buffers Alarm counter when applicable SSD
106. normal fire alarm when printer is available see chapter Fire alarm page 35 Key cabinet alarm is reset like a normal fire alarm see chapter Fire alarm reset page 43 This alarm will also generate a fault message see chapter Key cabinet alarm reset page 45 It is indicated by LED Fault L8 NOTE The Fault tx output s will not be activated by this fault Key cabinet opened in conjunction with a fire alarm The fire brigade personnel can open the key cabinet if a fire alarm already is activated in the c i e In this case there will be no key cabinet alarm or fault generated when the key cabinet is opened Restoring the key after a fire alarm When all fire alarms in the system are reset see chapter Alarm reset page 43 the key has to be restored in the key cabinet within 5 minutes If not a fault will be generated see chapter Key cabinet alarm reset page 45 Key cabinet alarm DBI convention NOTE Valid for the DBI Danish convention only When the key cabinet is opened the Fault tx output s will be activated and a key cabinet fault will be generated Input I0 I3 or COM loop input unit can be used 41 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 14 5 14 6 Rev Operating Instructions Fire alarm system EBL512 V2 5 x PAUND Key cabinet control unit xx Date MM DD Time HH MM In Danish FEJL N gleskab central xx When t
107. nt 123 45 Time HH MM Date MM DD User programmable text message if progr or zone 123 Time HH MM Date MM DD User programmable text message if progr xxx Heavy heat Point 123 45 Time HH MM Date MM DD User programmable text message if progr or 4 See EBL512 Planning Instructions General heavy smoke heat alarm and individual alarm points zones 4 When printer is available e g control unit 1549 40 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 14 4 14 4 1 14 4 2 14 4 2 1 14 4 3 Rev Operating Instructions Fire alarm system EBL512 V2 5 x zone 123 Time HH MM Date MM DD User programmable text message if progr Heavy smoke heat alarm will be reset when the fire alarm respectively is reset see chapter Alarm reset page 43 Key cabinet alarm One programmable input per c i e can be used to connect a key cabinet The fire brigade uses a key cabinet to store a key to the building NOTE In the DBI Danish convention the key cabinet alarm function is a little different see below Key cabinet opened before a fire alarm If the key cabinet is opened before a fire alarm e g if somebody illegally breaks into the key cabinet a key cabinet alarm i e a fire alarm will be generated Example Key cabinet alarm xx control unit number POINT KEY xx Nor 00M Alarm from key cabinet It will be printed like a
108. ntrol unit no xx 61 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x e Check the board type set with jumpers JP4 and JP5 on the I O Matrix board The type should be the same as programmed via Win512 FAULT Wrong type of unit tech no xxxxxx The unit is not the same type as programmed Change the programming or the unit FAULT Zone line input tech no xxxxxx Detector mounted in an ADB 2330 faulty removed detector or Ext line input to an ADB 2330 break on a wire or wrong no end of line resistor or Zone interface 2335 2226 input break on a wire or wrong no end of line resistor or Zone interface 2226 No ext power supply or Multi purpose I O unit 3361 monitored zone line input Z break on a wire or wrong no end of line capacitor short circuit if not programmed for fire alarm at short circuit User programmable text External fault Programmable input is used for an external fault see fault message 62 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 16 2 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Fault acknowledge The LEDs Fault tx activated L11 and General fault L7 are turned ON LEDs Fault Disablements Alarm devices L13 System fault L14 and or Fault Disablements Fire brigade tx L15 mig
109. o be done Function If the actual value differs from the calibrated value a small tolerance or if the calibrated value is outside the calibration range a fault will be generated NOTE Each output s logic is programmable via Win512 i e normally low default or normally high 24V but during the calibration the outputs will automatically be low i e a normally high output will be low during the calibration a few seconds Access According to chapter Access code for service H5 see page 110 Calibration of supervised outputs ACCEPT Al A Calibration in progress Please wait Calibration of supervised outputs Calibration is ready ACCEPT A1 Scroll or press Return to H5 Scroll or press Return to log off NOTE After the calibration it is recommended do a Safe shutdown of the control unit see menu H8 S8 This will save the SSW data e g the calibration values in a Flash ROM see page 74 837 Control unit and 2262 2262 outputs One end of line resistor 33K in the last unit or one resistor 33K in up to five units 3364 outputs One end of line capacitor 470 nF in the last unit or one capacitor 470 nF in up to five units 88 4K7 50K and 470 5x470 nF respectively 111 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 3 Sensitive fault detection mode H5 A2 To increase the possibilit
110. ogrammable inputs can generate fire alarm If somebody illegally breaks into a key cabinet this will also generate a fire alarm a key cabinet alarm A fire alarm could be an Alert Annunciation alarm i e the activation of the routing equipment fire brigade tx is delayed during an acknowledgement time and an investigation time respectively The analog detectors can also generate two other types of alarm i e Pre warning and Heavy smoke alarm Heavy heat alarm Two unit dependent addressable alarm points normally only smoke detectors and 2 zone dependent zones can generate a Co incidence alarm In the Australian convention only an Alarm Acknowledgement Facility function can be used During the Acknowledgement Period and the Investigation Period respectively there will be an indication in the c i e display Regarding the different alarm types etc see the following chapters Pre warning Activation of Pre warning is an option that has to be enabled via Win512 for the c i e respectively Note Pre warnings activated in any control unit in the system will be presented in all control units and all programmable outputs in the system with trigger condition pre warning will be activated if not disabled An analog detector will generate a pre warning for a lower alarm level than the fire alarm level Pre warning can be used when an early alarm and or an early action is required e g a soft computer shut dow
111. oint or a zone The CP is to communicate with the system i e for commissioning monthly tests maintenance etc Access codes for different access levels are required A keypad is used to get access to the system a menu tree with main and sub menus and for different manoeuvres The CP has several system status LEDs 15 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 5 LED indicators and push buttons LEDs and push buttons can vary according to type and configuration convention country language See also Figure 2 page 15 LED indicators on the Fire Brigade Panel FBP LED indicator Indicating Fire 5 red Fire alarm also Pre warning Heavy smoke heat alarm Alert Annunciation alarm Quiet alarm amp Key cabinet alarm Alarms queued 2 red More than one unit zone have generated fire alarm Use push button Alarms queued P1 to scroll Extinguishing red Output s for extinguishing equipment activated Fire brigade tx red Output for fire brigade tx routing equipment and or corresponding programmable output s i e type 4 routing equipment activated Test of routing equipment in progress see menu H1 Operation green Power on i e the power supply rectifier and or battery are connected and working properly FBP push buttons on next page Ventilation yellow Output s for fire smoke ven
112. oll to menu S5 A num Write the wanted techn A no and or press A to accept A i i Scroll or press Return to EPT return to menu H8 Scroll or press Return to log off 130 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 30 7 Rev Operating Instructions Fire alarm system EBL512 V2 5 x De activate alert annunciation function H8 S6 Normal function 1 For alarm points zones programmed for Alert Annunciation via Win512 is normally this function enabled via a time channel e g enabled daytime during working hours and disabled night time As an alternative for alarm points zones programmed for Alert Annunciation can this function be continuously enabled Off 0 Via this menu H8 S6 it is possible to de activate disable the AA function i e the AA function will be disabled for the alarm points zones programmed for Alert Annunciation in spite of the time channel is on or if they are programmed to be continuously enabled The AA function will stay de activated disabled until re activated re enabled again via this menu Access According to chapter Access code for maintenance see page 125 Scroll to menu S6 De activate alert annunciation function ACCEPT S6 Alert annunciation function 1 Write 0 or 1 and press ENornma l nnn O mean teta ACCEPT A to accept De activate alert annunciation function Scroll or press Return
113. on Alarms queued P1 to scroll browse through the queued alarms 7 2 Access level 1 After the door has been opened LED Door open is lit the user fire brigade personnel has access to the push buttons keypad to P8 Get access after logon to level 2 4 i e menus functions in the system NOTE In conjunction with a fire alarm the fire brigade personnel can use P8 without any access code to get access to the menu X1 to scroll through all the fire alarms e g see all point alarms 22 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 7 3 Access level 2 From access level 1 the user can logon to access level 2 which gives access to the following menus H1 Perform monthly test H2 Disable or re enable B1 Disable zone B2 Disable zone address C1 Activated interlocking outputs inputs C2 Activate interlocking output C3 Reset interlocking output C4 Disable interlocking output 2 A door is open See chapter Door open page 30 23 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x C5 Re enable interlocking output H10 Change access code for daily duties access level 2 7 4 Access level 3 From access level 2 the user can logon to access level 3 which gives access to the following menus normally us
114. one via menu H6 see page 122 This menu is a list of all not acknowledged and acknowledged but not corrected faults 50 Some units may also have an internal delay time which makes the delay time even longer e g the Multipurpose I O unit 3361 has an internal delay time of 30 seconds which results in 45 30 75 seconds delay time in total 51 For faults generated in other control units the buzzer can be suppressed Suppressed not suppressed is set via Win512 Control Unit Properties 52 In Win512 fault latching or not fault latching can be selected Fault latching default the faults always have to be acknowledged Not fault latching corrected faults will automatically be removed from the fault list menu H6 46 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x If a fault can not be corrected it is important to contact service personnel engineer immediately Note As a warning faults and disablements are also indicated by a 2 sec beep when an open c i e door is being closed 16 1 Fault messages Below follows a list of all fault messages in alphabetical order FAULT 1580 8 zones board x CU xx 8 zones expansion board DET8 Fault on no communication to 1580 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1581 Relay board x CU x
115. onic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev 30 11 m 1 z A Operating Instructions Fire alarm system EBL512 V2 5 x Synchronize the control units H8 S10 Synchronization can also be done via Win5 12 The control units have to be synchronized when e The following fault message is shown FAULT CU xx has wrong information e See chapter help topic View Faults in the Win512 help During the synchronization there will be displayed information for the control unit respectively The information is shown on the second row in positions 1 to 30 i e one position for each control unit 00 29 Synchronization not started X and alternating Synchronization in progress for CU X X is the last digit in the control unit number e g 8 for CU no 18 and 28 Synchronization completed lt Blank gt There is no control unit with that number in the system Access Scroll to menu S10 According to chapter Access code for maintenance see page 125 Press 1 and A to start the synchronisation or press A to go directly to the field Synchronization completed or press Return to menu S10 During the synchronization the information on each position on row 2 is changing all the time 28 CUs are shown in the example i e 15 amp 16 are not programmed Press A to continue Month MM day DD and time for the latest completed synchronization
116. or 1728 1735 1736 amp 1826 1828 units connected to an Ext FBP DU interface board 1587 When the units are running i e the power is turned on and the TLON network is running the SSD download can take place The PC has to be connected to the D connector J1 in a control unit main board 1556 Start Win512 Now you have to log on to the control unit In Win512 menu Tools Download you select the unit s to which the SSD is be downloaded For security reasons the SSD i e the installation will be automatically saved after the download Check All Loop Units In the Win512 COM loop icon pop up menu select Check All Loop Units This function can be used after or before the download of SSD The function is as follows The control unit will find all units that are connected on the COM loop The addresses 0 127 will be reported to Win512 For all 430x 33xx units and some of the other units the type of unit will also be reported All differences compared to the Win512 SSD will be listed in the Win512 log view and can be saved and or printed out NOTE During this check the COM loop will be disconnected disabled and no alarms or faults can be activated Disconnected COM loop is indicated by the LED Disablements L8 Single Control Unit Start the downloading from Win512 A text message will be shown in the alphanumeric display in the control unit Download in progress Block nnnn ou
117. orm a reset restart i e you will also leave the Boot menu Press 2 to open the Clear memory menu see below The other alternatives are for R amp D use only The Clear memory menu lea Sso 26 SS 3 Svslinto 4 Echel ominfto 5 Wieder Press 1 to clear the SSD memory Press 2 to clear the SSW memory The other alternatives are for R amp D use only Erasing SSD and Erasing SSW respectively will be shown and then will the Clear memory menu be shown again Press Return go back to the Boot menu NOTE After clearing the SSW perform a Power off power on reset restart directly 73 Can also be done in Win512 EBL512 settings dialog box Clear SSD 76 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 22 Access To use the key pad in the control unit to get access to the menu tree it is necessary to logon with an access code for level 2 3 or 4 See also chapter Access levels page 22 Open the door in the control unit level 1 press the Access button P8 and continue as follows YYYY MM DD EBL512 CU XX hh mm ss A user definable text C Enter the code 4 digits Access code The digits are replaced in the display NO ACCESS The access code was not correct Try again Perform monthly test The access code was ACCEPT H1 correct This is menu H1 Press
118. ors will be suppressed 7 See Safe shut down of control unit above 72 Tf this happens often call for service personnel engineer 74 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x The restart begins and will last for up to 2 minutes During this 2 minutes period no fire alarm can be activated and the following text messages will be show in the alphanumeric display Checking program memory And after that if everything is all right else see Memory fault below IBXCYONESLING 4 aree A fault is now generated in the system and the following text message will be shown in the display FAULT Restart CU nn code xx yyyyyyyyyy Date MM DD Time HH MM Regarding code xx and yy y see page 58 This fault is also indicated by LEDs Fault tx activated L11 and General fault L7 After fault acknowledge menu H6 the LEDs will be turned OFF if there are no other faults After reset a synchronization of the control units starts automatically See also chapter Synchronize the control units H8 S10 page 136 After reset required disablements have to be done Memory fault In case of a fault in the S W system program the following text message will be shown in the display Memory fault in program area xxx This is also indicated by LED System fault L14 and the buzz
119. own again L a list in which you can scroll If it s the correct zone to re enable press A to accept If not scroll or write the wanted zone and press A to accept If more re enablements shall be done continue like above If not scroll or press Return to menu H2 Scroll or press Return to log off 86 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 5 Re enable zone address H2 B5 Disabled alarm points zone addresses are listed in menu H4 U1 from which it is also possible to get a print out Alarm point s and or zones disabled via the function Single encapsulated reset see page 44 have to be re enabled via this menu A zone will be displayed as ZZZ 00 i e zone number and address 00 Re enabling via this menu has higher priority than automatic re enabling When all alarm points have been re enabled The LED Disablements L8 will be turned OFF if there are no other disablements in the system Access According to chapter Access see page 77 an If there are no zone Scroll to menu B5 addresses to re enable menu B4 will be shown again L a list in which you can scroll If it s the correct zone address to re enable press A to accept If not scroll or write the wanted zone address and press A to accept If more re enablements shall be done continue like above
120. possible to give the control units in the system respectively the final control unit numbers right from the beginning in order to get the correct technical numbers in the system documents NOTE Two or more presentation numbers Zone Address in the systems must not be the same Delete a Control Unit in a TLON network Physically disconnect the control unit which will generate faults in the other control units Acknowledge the faults Open the current project in TLON Manager delete one control unit according to the separate TLON network documentation Open the SSD for the current system via Win512 Delete one control unit and the units connected to it and download the new SSD according to chapter Programming SSD download page 67 If you after S W download get FAULT Configuration control unit xx read the EBL512 settings menu Tools EBL512 settings and download them again They will then be downloaded with the same Win512 version as the S W and the fault will normally be corrected 5 It is not possible to merge two TLON Networks into one or copy one system and paste into another system 66 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 18 Operating Instructions Fire alarm system EBL512 V2 5 x Programming SSD download 18 1 18 2 The PC program Win512 is used for programming of the site specific data SSD and to download it into the EBL512 control unit s and
121. ption is gt 60 mA on the BS4 loop FAULT High Voltage 1584 board x CU xx Autronica interface board BS4 The BS4 loop voltage is gt 16V normally it is 14V 0 1V FAULT ID fault display unit xxxxxx The display unit is not the same type as programmed Change the programming or the unit FAULT Interlocking input AAA PP An interlocking input is not activated within the time set for fault activation 5 255 seconds The time is counted from the activation of the output in the interlocking combination area point FAULT Key cabinet control unit xx 55 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x The key cabinet has been opened without a prior fire alarm i e if somebody has opened the key cabinet illegally or The key cabinet has not been closed within 5 minutes after reset of all fire alarms in the system FAULT L C mixed COM loop x CU xx The two wires L SA and C SB have been mixed alternated Check so that the wire connections are correct according to drawing 512 41 FAULT LON board 1590 control unit xx TLON connection board 1590 No communication connection with the TLON network The board has to be changed FAULT Loop unit technical number xxxxxx The communication with the unit is not all right i e the unit is out of order faulty FAULT Low battery capacity CU xx Battery
122. r several slave units connected in parallel i e the unit is used for Redundancy in distributed system The Input 0 is in fire alarm state but there is no activated fire alarm in any control unit and no fault on the TLON Network Check the connections e g of the alarm resistor in the slave unit units FAULT ASF COM loop x control unit xx ASF 2370 Addressable short circuit isolator This message is only shown when the control unit works in Sensitive fault detection mode menu H5 A2 A short circuit shorter faster than the time delay for an ordinary fault has occurred on the COM loop Can be used for commissioning maintenance purposes FAULT Battery not connected CU xx Batteries 2 x 12 V are missing or not connected correctly Fuse es F2 F3 on the charger board 1557 1657 is are blown Other battery fuse is blown e g when the batteries are placed outside the control unit This check is done every 14 minute i e after correcting the fault it might take up to 14 min until it disappears from the fault list FAULT Battery output unit xxxxxx Check the output unit battery connections fuse F3 on the power supply board in the output unit FAULT Charging ext power supply CU xx The fault is to be found in the external power supply equipment FAULT Charging output unit xxxxxx 49 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instruction
123. re delayed e g for COM loop and zone line input faults the delay time is approx 45 seconds In case of a fault condition the following has happened will happen in the control unit e The buzzer in the c i e sounds continuously steady ON e Output for routing equipment Fault tx is activated e Programmable output s for general fault is are activated and output s for general charge fault might be activated e LED Fault tx activated L11 is turned ON indicating that the output for routing equipment Fault tx is activated e LED General fault L7 is turned ON e LEDs Fault Disablements Alarm devices L13 System fault L14 and or Fault Disablements Fire brigade tx L15 might be turned ON as well e A fault message incl date and time is shown in the display Example fault message FAULT No reply techn no xxxxxx Date MM DD Time HH MM NOTE The date is in the Ukrainian convention S W version gt 2 2 3 and the Australian convention shown as DD MM e If more than one fault is activated the text More faults is added after the time e Ifa fault has been corrected before it has been acknowledged the status text Serviced is added after the time e Fire alarm presentation has higher priority than the fault messages During fire alarm presentation the faults can be shown via the special fire alarm menu X1 see page 38 Faults have to be acknowledged which is d
124. rent time 3 hours Disable zone 000 Address 00 If more disablements shall be done continue ACCEPT j like above If not press Return to menu B2 Scroll or press Return to menu H2 Scroll or press Return to log off 83 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 3 Disable control output H2 B3 Control outputs can be individually disabled Disabled output will stay in or return to the normal condition for the output respectively Disabled outputs are listed in menu H4 U1 from which it is also possible to get a print out Access According to chapter Access see page 77 Scroll to menu H2 Disable or re enable ACCEPT H2 A Disable zone ACCEPT BI Scroll to menu B3 Disable control output ACCEPT BS Disable output control unit 00 Type 0 Write C U No and Cle optnmatte SER EREA bom AC CH ram press 0 RU4 2265 or SU4 2262 2263 or MIO 3361 or AOU 3364 or 4 ES not valid in Swedish SBF convention ASI 3377 or ASB 3378 1 S0 S3 2 RO R1 3 Relay board 1581 4 1583 board output Extinguishing system Press A to accept A Disable 00 0000 control output 0 Regarding the AOU Depending on the ACCEPT 3364 unit s output 2 chosen type 0 1 2 3 Digable s is fire door functions resp 4 the following will not be disabled will be shown
125. rintout press Printout 1 else press A to accept Enter technical number 000000 Write the sensor s techn number and or press A to accept Sensor 000003 in This is a list in which Momentary XX C you can scroll or use gt to see the next information window for the selected sensor Press Return to Enter technical number Sensor 000003 A1 short name see Current algorithm Al separate table page 99 Press Return to Enter technical number or press Access to change the algorithm Access Access code _ If login was made with code for level 3 no code is needed Enter code for level 3 4 Access code The digits are replaced in the display B oo ata 000003 Current A1 Use gt or Change algorithm 000003 Current A1 Al A2 B A Algorithm for sensor 000003 is changed from Al TOB 104 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Return Enter technical number 000000 Write the sensor s techn number and or press A to accept or press Return to carry out the change of algorithm s Return Alarm algorithms have been changed The affected CU s will now restart ACCEPT A Sensor values Menu U5 will be shown Printout 1l yes for a few seconds and then the affected control unit s will restart See chapter Restart page 74 NOTE The ne
126. rmation Valid in Belgian British Standard Hungarian and Ukrainian conventions only S W version gt 2 2 3 7 Faults not acknowledged ON Os oe ee 8 Disablements 9 Zones in Test mode 10 Interlocking inputs outputs active 11 System information NOTE The different type of alarms faults etc are described in other parts of this document Regarding System information see below System information on the top first row The date EBL512 control unit number and time are displayed The exact look is convention language dependent One example S Fire alarm have a log off function i e if a menu window is open when a fire alarm is activated an automatic menu log off will take place and the fire alarm will be presented in the alphanumeric display instead Some information is available and some actions are possible to perform via the Fire alarm menu see chapter Fire alarm page 35 The AAF function is used in conjunction with an AAF Control which is available on the Australian market only 20 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x YYYY MM DD T BL512 CU XX hh mm ss YYYY MM DD Date Year Month Day CU XX Control Unit XX 00 29 hh mm ss Time hour minute second NOTE The date is in the Ukrainian and the Australian conventions shown as DD MM YYYY
127. s chapter Alert annunciation Reset of the AA alarm s can be done via push button Reset on an AA unit 1735 1736 or an AA controller 1740 or in the c 1 e If more than one AA alarm is activated they will be reset all at a time NOTE Reset via an external unit is only possible to do during the investigation time and AA alarm s only not normal fire alarms Co incidence alarm A Co incidence alarm can be manually reset with the Reset button P4 on the c i e front or automatically reset after 5 minutes i e if the 44 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 15 3 15 4 15 5 15 6 Rev Operating Instructions Fire alarm system EBL512 V2 5 x zone alarm point is no longer in alarm status See also chapter 2 zone address dependence co incidence alarm page 39 Heavy smoke heat alarm reset If a heavy smoke heat alarm has been activated it will be reset at the same time as the corresponding fire alarm is reset Also the output s will be reset i e de activated Key cabinet alarm reset Not valid for the DBI Danish convention see chapter Key cabinet alarm DBI convention page 41 After reset of the key cabinet alarm fire alarm a fault message is shown in the display to inform the user that the key cabinet has been opened PAUND Key cabinet Control Umit sx Date MM DD Time HH MM NOTE The date is in the Ukrainian and the A
128. s Fire alarm system EBL512 V2 5 x The charging function in the external power supply unit is not OK The p c b has to be replaced FAULT Checksum system program CU xx A fault in the control unit xx S W The main board 1556 might have to be replaced This is a very serious fault Call for service personnel engineer immediately NOI Ss Com AAU sox BeF boardi x CU sex AAU 1735 1736 e The contact with the AAU is interrupted Check the cable all connections and the 1587 board Is correct complete SSD downloaded via Win512 Check the address setting 1587 board the AAU SW mode setting etc If there is a program memory fault in the AAU there will be a fault message in the AAU display Memory fault in program area n n or 2 The AAU will not work FAULT Comm EEU x ml Sici board x CU EPU 1728 e The contact with the EPU is interrupted Check the cable all connections and the 1587 board Is correct complete SSD downloaded via Win512 Check the address setting 1587 board the EPU SW mode setting etc If there is a program memory fault in the EPU there will be a fault message in the EPU display Memory fault in program area n n 1 or 2 The EPU will not work PAVUT Commi WEP sex BEI E poar dia CU sox FBP 1826 1828 e The contact with the ext FBP is interrupted Check the cable all connections and the 1587 board Is correct complete SSD downloaded via Win512 Check the
129. s expected to be one c i e in a TLON network and TLON network programming is required 65 If the new S W file comes together with a text file download it as well Also the LED System fault L14 starts blinking 70 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 19 2 19 3 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 6 During the download of the S W and or text file some information will be shown in the Win512 log view and when the download is ready Downloading completed successfully will be shown for the S W and text file respectively Close the dialog box 7 Open the Tools menu and open the EBL512 settings dialog box See 3 amp 4 above Click Read In the log view will be shown System information has been uploaded Check the settings change when required See 3 amp 4 above Click Download In the log view will be shown System information has been downloaded Close the dialog box 8 Remove jumper JP1 BOOT Do a reset restart see 3 above Regarding the reset restart see chapter Restart page 74 Follow the same procedure in each control unit Control Units in a TLON network All control units connected to a TLON network shall have the same S W version For download of new S W in each control unit follow the procedure described above Since some control units do not have contact with some control units during the
130. s generated LEDs Alarms queued are lit each fire alarm has to be individually reset Single encapsulated reset Fire alarm reset is like Single reset Encapsulation function is described in EBL512 Planning Instructions chapter System properties settings Encapsulated unit zone disabled unit zone NOTE 1 When Multiple reset or Single reset is used encapsulated reset can be done by pressing Reset P4 and 0 1 sec later also press Alarms queued P1 and hold them pressed for gt 0 5 sec By Single reset The fire alarm displayed in the LCD first row to the left will be encapsulated By Multiple reset The fire alarm displayed in the LCD first row to the left will be encapsulated or the points in alarm status within one zone will be encapsulated or the whole zone conventional will be encapsulated NOTE 2 When Single reset or Single encapsulated reset is used you can make a Multiple reset by pressing Reset P4 and 0 1 sec later also press A in the keypad and hold them pressed for gt 0 5 sec 1l Co incidence alarm One unit zone in a 2 unit zone dependence is activated 12 Tn some conventions this button is not used no designation text In Belgian British Standard Hungarian and Ukrainian conventions this button is used for the Evacuate function In Polish CNBOP and Czech conventions this button is used for Alert Annunciation Acknowledge In Australian and New Zealand
131. sed when programming all units connected to the BS4 loops Technical number is also used to identify which unit has generated a fault NN NNN 01 99 The address on the BS4 loop Don t have to be in sequence The connections on the BS4 loop don t have to be in sequence The address is set on DIL switches in each unit 0 3 BS4 loop number 4 7 Board number 00 29 The control unit address number Don t have to be in sequence The connections to the TLON network don t have to be in sequence The address is set with a PC SW TLON Manager NOTE In the technical number for unit connected to a BS4 loop the board number 4 Autronica interface board 0 the board number 5 Autronica interface board 1 the board number 6 Autronica interface board 2 and the board number 7 Autronica interface board 3 in the control unit In fault messages for Autronica interface boards the following information is shown Control unit 00 29 BS4 board 0 3 and if required BS4 loop 0 3 3 Can only be used in Swedish SBF convention 32 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Operating Instructions Fire alarm system EBL512 V2 5 x 13 3 Presentation number For each fire alarm point input zone a presentation number NNN NN has to be programmed The presentation number is shown in the c ie and ext FBP display s to identify the point zone generating fire
132. set Each fire alarm has to be reset one by one This function set in Win5 12 is a violation to the EN54 2 standard Press Reset P3 to reset the fire alarm shown in the display on the first row to the left NOTE The push button has to be pressed in for min 0 5 sec Output s programmed for this fire alarm will also be reset i e de activated If more than one fire alarm is activated i e LEDs Alarms queued L2 are lit the next fire alarm in the queue is now shown in the 48 Tf there is a fault condition e g caused by the fire a fault message will now be shown in the display When Single reset or Single encapsulated reset is used you can make a Multiple reset by pressing Reset P4 and 0 1 sec later also press A in the keypad and hold them pressed for gt 0 5 sec 43 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 15 2 3 15 2 4 15 2 5 Rev Operating Instructions Fire alarm system EBL512 V2 5 x display on the first row to the left It has to be reset the same way as the first one When all fire alarms are reset LEDs Fire L1 and Alarms queued L2 are turned OFF and the display is empty All outputs for fire alarm are now also reset i e de activated If a key cabinet is installed the key to the building has to be put back into the key cabinet within 5 minutes If not a fault will be generated and a fault message will be s
133. ss A and menu U3 will be shown again Scroll or press Return to menu H4 Scroll or press Return to log off 96 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 26 4 Scroll to menu H4 Scroll to menu U4 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Activated 2 zone address dependent zone address H4 U4 Two unit dependent in Win512 When only one zone or one zone address alarm point is in alarm status the buzzer in the c i e sounds 0 8 5 sec and there is a Co incidence alarm presentation in the c i e display The unit s or zone s in Co incidence alarm status is are shown in this menu from which it is also possible to get a print out ZAARA IE Proge Co incidence alarm detector User definable text message or Co incidence alarm zone ZZZ User definable text message if progr Present system status on display and printer ACCEPT H4 Disablement Printout l yes Activated 2 zone address dependent zone address Printout 1l yes When A is pressed the active zone amp address or zone will be shown in the display e g Co incidence alarm detector ZZZ AA L or Co incidence alarm zone ZZZ L Printing started To stop printing press C and 0 simultaneously ACCEPT Activated 2 zone address dependent zone address Printout 1l yes One alarm point or zone has activated a Co incidence a
134. t H1 24 Disable or re enable H2 24 1 Disable zone H2 B1 24 2 Disable zone address H2 B2 24 3 Disable control output H2 B3 24 4 Re enable zone H2 B4 24 5 Re enable zone address H2 B5 24 6 Re enable control output H2 B6 24 7 Re enable non reset zone address H2 B7 43 43 44 44 44 45 45 45 45 46 47 63 64 64 64 65 65 66 66 67 67 67 68 68 69 70 70 71 71 73 73 74 76 77 78 81 82 83 84 86 87 88 90 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 8 Disable Re enable all control exting and ventilation outputs H2 B8 91 24 9 Disable Re enable alarm devices H2 B9 92 25 Set calendar and clock H3 93 26 Present system status on display and printer H4 94 26 1 Disablement H4 U1 94 26 2 Disablement by time channel H4 U2 95 26 3 Doors open H4 U3 96 26 4 Activated 2 zone address dependent zone address H4 U4 _ 97 26 5 Sensor values H4 US5 98 26 5 1 Reset of a week average sensor value 100 26 5 2 Algorithm setting via menu H4 U5 101 26 6 Sensors activating SERVICE signal H4 U6 106 26 7 Event log H4 U7 107 26 8 Configuration H4 U8 108 27 Service H5 109 27 1 Access code for service H5 110 27 2 Calibration of supervised outputs H5 A1 111 27 3 Sensitive fault detection mode H5 A2 112 27 4 Direction for communication on COM BS4 loop H5 A3 113 27 5
135. t H9 C4 142 31 5 Re enable interlocking output H9 C5 143 32 Change access code for daily duties H10 144 33 Annual control 145 34 How to change paper in the printer _ 146 35 Replacing a TLON connection board and or a main board 147 36 Battery maintenance 148 37 How to avoid unnecessary nuisance fire alarms 149 38 Information regarding radioactive radiation source151 39 Revision history 152 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 1 Introduction EBL512 Operating Instructions is a document intended to be used by the end user and the fire brigade personnel as well as service commissioning engineers Due to continual development and improvement different S W versions are to be found This document is valid for S W version 2 5 x On the date rev date of the document x 0 Since the EBL512 control unit c i e is produced for many countries the look the texts the functions etc might vary Products Consists of one or more parts HW according to a Product Parts List A product has e atype number e g 1548 e an article number often the type no and sometimes is a country code added e g 1548SE e a product name e g EBL512 control unit 128 addresses without printer
136. t by the control unit to the units connected on the COM loop Parity are the received number of parity faults and faults in relation to pollings Bit are the received number of bit faults and faults in relation to pollings Answer are the received number of answer faults no answers and faults in relation to pollings The Parity Bit and Answer values shall normally be 0 or as close to 0 as possible If not there are some communication problems that have to be investigated Check the COM loop connections and the loop units All values are set to 0 after restart and or after re connection of COM loop menu H8 S3 Access According to chapter Access code for service H5 see page 110 Scroll to menu A7 Display statistics for COM loop ACCEPT A7 For which CU 00 and COM loop 0 shall Write control unit and loop statistics be displayed ACCEPT number Press A to accept If the control unit don t exist or don t answer this message will be shown Pollings 1234567 Parity 000000 00 0 i Bit 000000 00 0 Answer 000000 00 0 Press A to menu A7 Display statistics for COM loop Scroll or press Return to ACCEPT A7 H5 Scroll or press Return to log off 2 Note The values are not live updated i e the shown values were valid when A was pressed in menu A7 To see the actual values press A to menu A7 press A and write control unit and loop number again and press A Normally is only the
137. t of xxxx When the download is completed the following text message will be shown 58 It is very important that the two first digits in the EBL512 S W version and the Win512 version are the same e g for EBL version 2 3 1 shall Win512 version 2 3 x be used Access code for level 5 shall be entered via the PC Win512 6 After the download to a control unit an automatic reset restart will take place A number of faults might then be generated e g due to not connected units This will cause heavy traffic on the network which might affect delay the SSD download to the other units 67 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 18 3 18 4 Operating Instructions Fire alarm system EBL512 V2 5 x Download completed successfully Control unit will now restart Now an automatic reset restart will take place see chapter Restart page 74 If the download was not okay the following text message will be shown Checksum fault in downloaded data Control unit will now restart Now an automatic reset restart will take place see chapter Restart page 74 After the reset restart another text message will be shown in the display FAULT Site specific data SSD CU nn Date MM DD Time HH MM This text message means that the SSD have not been downloaded i e a new download has to be performed Control Units ina TLON network The SSD for
138. t out Access According to chapter Access see page 77 oe Write zone number e g Press A to accept 001 Press 1 for aut re enabling and accept or change the time max 24 hours Press A to accept LED Disablements L8 will light up If more disablements shall be done continue like above If not press Return to menu B1 Scroll or press Return to menu H2 Scroll or press Return to log off 82 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 2 Disable zone address H2 B2 Addressable alarm points also addressable manual call points connected to the COM loop can be individually disabled Disabled alarm points zone addresses are listed in menu H4 U1 from which it is also possible to get a print out Disabled alarm points zone addresses have to be re enabled via menu H4 B2 Access According to chapter Scroll to menu H2 Disable or re enable ACCEPT Disable ACCEPT Scroll to menu B2 address ACCEPT Disable zone 000 Address ACCEPT Write zone number and Disable zone 001 Address Press A to accept address e g 001 01 ACCEPT Automatic re enabling 0 0 No 1 Yes Press 1 for aut re enabling and accept or Time HH MM ACCEPT change the time max 24 hours Press A to accept LED Disablements L8 will light up Default is cur
139. t possible to get a print out from this menu Action Text in display Comments Access According to chapter Access see page 77 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout a l vesp wale Scroll to menu U8 Show configuration Press A to accept U8 A Max number of allowed loop units xxx Press Return to menu Language nnnnnnnnnn Conv ccecceccecce U8 Return Show configuration Scroll or press Return to menu H4 Scroll or press Return to log off 84 To set change the convention in Win512 Level 2 has to be selected and a password is required 108 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 Service H5 When commissioning an installation and by maintenance power on and programming a control unit a system menu H5 is used to get certain information and help Only authorised personnel have access to level 4 menus Access code for level 4 is required Via a PC and Win512 access code for level 5 you can e download backup site specific data SSD e download of S W settings configurations C U amp system data e create and download the user definable text messages shown in the alphanumeric display in the C U ext FBP and in the Display units Via a PC and TLON Manager you can do the TLON network programming config
140. ted Instead the alarm point will be disabled and has to be re enabled again via menu H2 B5 When the Fire door closing function is used the fire door will be closed when the detectors controlling the door are tested via the test mode 80 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 Disable or re enable H2 A whole zone one or more alarm points within a zone and or control outputs can be disabled via menus H2 B1 B3 This possibility can be used when a temporary disablement is wanted e g craftsmen working in the premises etc The function Enhanced disablement is enabled as default i e disabled alarm points will not activate Pre warning fire alarm or fault If this function is not enabled via Win512 fault can be activated but not pre warning or fire alarm This is a violation to the EN54 2 standard Addressable manual call points can be disabled but shall normally not be disabled However when a whole zone is disabled the addressable manual call points will not be disabled for safety reasons Up to 512 whole zones can be disabled via menu H2 B1 Up to 200 alarm points zones address can be individually disabled via menu H2 B2 and or COM BS4 loops zone interface inputs and or MIO inputs can be disabled via menu H8 S2 Alarm points disabled via time channels are not limited and must not be counted Up to
141. the system See also EBL512 Planning Instructions 39 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 14 3 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Co incidence alarm zone ZZZ user definable text message See also chapter Activated 2 zone address dependent zone address H4 U4 page 97 If more than one Co incidence alarm are generated the LEDs Alarms queued L2 are blinking and the Co incidence alarms will be automatically scrolled each 5 second A Co incidence alarm can be manually reset with the Reset button P4 on the c i e front or automatically reset after 5 minutes i e if the zone alarm point is no longer in alarm status see chapter Alarm reset page 43 The function 2 zone address dependence can be turned on off via a time channel Heavy smoke alarm Heavy heat alarm An analog detector generates heavy smoke heat alarm for a higher 1 than the fire alarm level i e fire alarm is already activated by the same detector alarm leve Heavy smoke heat alarm is a confirmation on that the smoke or heat is increasing and can be used for special actions e g activation of smoke ventilation etc In case of a heavy smoke heat alarm the following will happen e Outputs programmed for heavy smoke heat alarm are activated e Each heavy smoke heat alarm is printed e g xxx Heavy smoke Poi
142. tilation equipment activated 7 See chapter Alarm types page 34 8 L3 L5 can be individually programmed to indicate when its normal trigger condition is met or when a programmable input is activated e g L5 can be turned on when an input is activated by a Fire brigade tx output 16 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Push buttons on the Fire Brigade Panel FBP Push button Operation function Alarms queued black Used when LEDs Alarms queued L2 are lit to scroll browse through the queued alarms zones Function see chapter Fire alarm page 35 under LEDs Alarms queued Silence Alarm devices red Used to silence the sounders i e outputs for alarm devices 4 Reset green Has to be pressed for gt 0 5 sec Used to reset the fire alarm s Used to reset co incidence alarm Ps Evacuate green 1 Used to activate the sounders i e outputs for alarm devices In Belgian British Standard and British Standard Marine Application P2 Silence buzzer yellow Used to silence the buzzer in the c i e P1 P2 P3 P P5 conventions has P3 to be activated before P4 can be used 10 Multiple reset Default All fire alarms in the system will be reset simultaneously Single reset The fire alarm displayed in the LCD first row to the left will be reset When more than one fire alarm i
143. ting sawing amp drilling These kind of jobs cause smoke Carpet welding Welding of plastic carpets causes a smoke that can be almost invisible but it still influences the smoke detectors sensors Cooking fumes toasting amp candles It is not only normal smoke that influences smoke detectors sensors It is all kinds of combustion products caused by cooking frying grilling toasting etc Warning Be careful when there are smoke detectors sensors near such activity Special environments In certain premises a special environment can exist which can influence smoke detectors sensors and cause alarm It can be ions from plastics flour dust oil haze aerosols strong perfumes strong ventilation insecticides disinfecting sprays etc If many odd and unnecessary alarms occur the environment must be examined and perhaps other detector types have to be chosen Steam hot air Smoke and heat detectors are influenced by steam and hot air e g from an oven dry blower heater etc 149 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Exhausts Exhausts from cars trucks lift trucks lawn mowers etc influences smoke detectors sensors If windows and doors are open exhausts can slip in that way Lack of maintenance Smoke detectors sensors are influenced by their environment and become dirty In an analog s
144. tinguishing system Press A to accept If there are no outputs to re enable menu B6 will be shown again L a list in which you can scroll Regarding the ASI 3377 amp ASB 3378 units Output O high priority 1 medium priority 2 low priority If it s the correct output to re enable press A to accept If not scroll or write the wanted output and press A to accept Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x If more re enablements shall be done continue like above If not press Return to menu B6 Scroll or press Return to menu H2 Scroll or press Return to log off 89 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 7 Re enable non reset zone address H2 B7 NOTE This menu is no longer valid See chapter Single encapsulated reset page 44 Menu H2 B5 shall be used instead Text in display Comments Access to chapter see page 77 i Scroll or press Return t menu H2 Scroll or press Return to log off 90 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 24 8 Disable Re enable all control exting and ventilation outputs H2 B8 Outputs programmed as type 0 control gener
145. trol unit and the installation shall be tested on a regular basis If one twelfth of the alarm points are tested each month the whole installation will be tested after one year In test mode only the alarm points are tested i e no outputs no sounders will be activated during the test Alarm devices can be tested via menu H8 S7 If a real fire alarm is activated for example by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc See also chapter Alphanumeric display LCD in the control unit page 20 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in Win512 There will be an automatic ending of the test mode one hour after the latest tested alarm point zone See also chapter Perform ZONE TEST test mode H7 page 123 Access According to chapter Access see page 77 A The buzzer in the C U S a sounds and all dots in the display are shown All LED s light up incl LED s in units connected via I O Matrix board 4582 When printer is available it will print out Z A ZO I st in TEST MODE NOTE In DBI Danish l CEPT convention only one zone Write zone numbers i Press A to start the test e g 001 002 003 t mode 004 78 Panasonic Electric Works Fire amp
146. undancy in distributed systems Fire alarm menu X1 X7 The special fire alarm menus X1 X7 can only be used if at least one fire alarm is activated If this fire alarm menu is disabled via Win512 it is a violation to the EN54 2 standard Press Access no access code and the user definable text message will be replaced as follows ZONE 123 EAST 789 No 003 Display alarms ACCEPT X1 A Y A gt and Return are used like in the normal menu tree see chapter Access page 77 The original presentation the user definable text message will be automatically displayed again 20 seconds after the latest time any of the push buttons A Vv AN gt and Return was used Scroll N to the wanted menu and press A Display alarms X1 ZONE 123 LAST 789 No 003 Display alarms ACCEPT X1 First row Explanations in chapter Fire alarm page 35 Second row All fire alarms also several alarm points in one zone will be displayed in zone address order i e up to 15360 alarms Press A E g ZONE 123 LAST 789 No 003 Point 123 45 00001 of 00005 Point Zone address for alarm no 00001 my ZONE 123 LAST 789 No 003 Point 234 00002 of 00005 Point Zone no for alarm no 00002 and so on 37 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 14 2 1 2 14 2 1 3 14
147. unicating in A direction alternatively B direction in menu A3 When you log out or if you are automatically logged out after 60 min the communication will start in the A direction Access According to chapter Access code for service H5 see page 110 Scroll to menu A3 Direction for communication on COM BS4 loop ACCEPT A3 Press A or 1 and A to accept O COMB SA ACCEPT Select type of loop 0 Lock COM loop Controll unit Write loop number board ACCEPT number and control unit number Press A to Lock direction on BS4 loop accept Board 0 Control unit 00 ACCEPT Mightbe the B direction is shown instead COM loop is currently communicating in A direction Press A to change See NOTE above DAA 8 direction Press Return When you select a BS4 loop the text in this menu will still be to finish the locking and Return COM loop Direction for communication on COM BS4 loop ACCEPT A3 return to menu A3 Scroll or press Return to H5 Scroll or press Return to log off 89 An Autronica interface board 1584 is required in the control unit 113 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 5 Show information about Site Specific Data H5 A4 Information regarding the current site specific data SSD is shown New SSD can be downloaded via a PC
148. uration TLON Manager is used for programming of network data addresses etc 85 Connected to the D connector J1 on the main board 1556 8 Connected to the modular connector J2 on the main board 1556 109 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 1 Access code for service H5 Access code to level 4 is required If login to level 2 was made with code for level 4 no code is required here Access According to chapter Access page 77 Scroll to menu H5 code is needed Enter code for level 4 The digits are replaced 4 digits in the display The access code was not correct Try again The access code was correct This is menu H5 A1 Press A to accept scroll or press return to menu H5 If login was made with code for level 4 no 110 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 2 Calibration of supervised outputs H5 A1 Supervised monitored outputs The voltage outputs SO S3 in each control unit The voltage outputs VOO VO1 in the COM loop output unit 3364 The voltage outputs 0 3 in the COM loop output units 2262 amp 2263 When all alarm devices sounders etc have been connected including required end of line devices and when the SSD download is ready a calibration has t
149. ustralian conventions S W version gt 2 2 3 shown as DD MM If the key cabinet is closed again the status information Serviced is added This key cabinet fault message is to be acknowledged the same way as a normal fault see chapter Fault acknowledge page 63 When the key cabinet fault is acknowledged the LED General fault L7 will be turned OFF if the key cabinet is closed and if there are no other faults in the system Quiet alarm reset Quiet alarms are non latching i e they will be automatically reset when the alarm point zone is no longer above alarm level Outputs activated by quiet alarm will be de activated In some cases after a programmable delay time Alarm Acknowledgement Facility AAF reset NOTE The AAF function is used in conjunction with an AAF Control which is available on the Australian market only The indication in the control unit display during the Acknowledgement Period 10 60 sec and the Investigation Period 0 3 min respectively will automatically disappear when e the AA process ends because no detector in the AAF zone is over the fire alarm level e the AA process ends up in a fire alarm which has higher priority Regarding Fire alarm reset see above 45 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 16 Fault In order not to generate any faults unnecessarily all faults a
150. value Pollings changed 117 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x 27 9 Select unit on COM loop to use for trigging H5 A8 This function is used by service engineer and by R amp D for troubleshooting On the pin respectively you will get a pulse to trig an oscilloscope etc COM loop Main board 1556 JP2 upper pin Each unit not giving a correct answer Main board 1556 JP2 lower pin A specific unit is being polled BS4 loop Autronica interface board 1584 in the c i e BY3 left pin A specific unit is being polled Autronica interface board 1584 BY3 right pin 0O V BS4 board Autronica interface board 1584 Access According to chapter Access code for service H5 see page 110 A Select type of loop Press ACCI A to accept Loc q Write control unit number a board number 0 3 loop number and address Press ge A i i A to accept Select type of loop Press A to accept or press Return to menu A8 Scroll or press Return to H5 Scroll or press Return to log off 118 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 27 10 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Activate address setting mode for DU H5 A9 This function can be used by commissioning service engineer to activate the address sett
151. vated for example by an alarm point not in test mode the normal fire alarm functions will be activated i e fire alarm presentation outputs sounders activated routing equipment fire brigade tx activated etc See also chapter Alphanumeric display LCD in the control unit page 20 NOTE If the control unit door is left open the output s for routing equipment fire brigade tx might be disabled if set so in Win512 There will be an automatic ending of the test mode one hour after the latest tested alarm point Access According to chapter Access see page 77 Scroll to menu H7 Perform ZONE TEST ACCEPT H7 A Zone to be set in TEST MODE NOTE In DBI Danish PERE O ORo N D Start tost ACCEPT convention only one zone Write zone numbers Zone to be set in TEST MODE Press A to start the test e g 001 002 003 001 002 003 004 Start test ACCEPT mode 004 A Zones are set in test mode LED Test mode L9 wait will light up Zone in TEST MODE Perform the tests 001 002 003 004 End test ACCEPT 123 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x The zone s will stay in test mode until the test mode is ended but after 60 minutes or if you press Return two times you will be logged out from menu H7 Perform the test as quickly as possible since the output s for routing equipment fire brigade tx are disabl
152. w algorithm will not be in use until after the restart In case of an automatic log off and one or more algorithms are changed the affected control unit s will restart Sensor values and setting alarm algorithm for the Analog multi detector 3316 The procedure is similar to the procedure for 3304 and 3308 respectively When using gt the smoke detector information will be shown before the heat detector information The algorithms can only be changed one at a time i e if both algorithms are to be changed start with the smoke detector algorithm and continue with the heat detector algorithm as follows If a smoke detector algorithm shall be changed do as for 3304 If a heat detector algorithm shall be changed use gt to pass the smoke detector windows Then do as for 3308 105 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev 26 6 A Operating Instructions Fire alarm system EBL512 V2 5 x Sensors activating SERVICE signal H4 U6 Service signal is indicated by LED Service L12 The sensor week average value is below or over the service level respectively for one or more sensors Regarding the service signal levels see Planning Instructions chapter Service signal Menu H4 U6 is a list of the sensor s activating service signal NOTE Service signal is only information that the sensors have to be cleaned replaced soon The service signal has to be acknowledged
153. x 8 relays expansion board Fault on no communication to 1581 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1582 FBP interface board x CU xx External Fire Brigade Panel interface board Fault on no communication to 1582 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 FAULT 1583 Extinguishing system CU xx Fault in the extinguishing system equipment connected to the 1583 German Fire Brigade Panel interface board in control unit No xx FAULT 1583 GFBP interface board CU xx German Fire Brigade Panel interface board e Fault on no communication to 1583 board in control unit No xx Check address setting and connections on the board Check programming Win512 e Check the fuses F1 and F2 on the 1583 board 47 Panasonic Electric Works Fire amp Security Technology Europe AB MEW01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x FAULT 1584 Autronica board x CU xx Autronica interface board Fault on no communication to 1584 board No x in control unit No xx Check address setting and connections on the board Check programming Win512 PAULE T ISe board Se CU Tox External Fire Brigade Panel DU interface board Fault on no communication to 1587 board No x in control unit No xx Check address setting and connections on the
154. xxxx Follow the instructions for 3304 3308 3309 and 3316 respectively 101 Panasonic Electric Works Fire amp Security Technology Europe AB MEWO01002 Rev Operating Instructions Fire alarm system EBL512 V2 5 x Show sensor values and setting alarm algorithm for the Analog photo electric detector 3304 Access According to chapter Access see page 77 Scroll to menu H4 Present system status on display and printer ACCEPT H4 A Disablement Printout 1l yes U1 Scroll to menu US Sensor values To make a printout press Printout l yes 1 else press A to accept Enter technical number 000000 Write the sensor s techn number and or press A to accept A Sensor 000001 This is a list in which Momentary XX X m Weekly XX X m you can scroll or use gt to see the next information window for the selected sensor Press Return to Enter technical number gt Sensor 000001 Min XX X m NOTE Perf Factor X XX m Max XX X m XX X m XX X obscuration per meter Perf Factor see below this table gt Sensor 000001 N 15 short name see Current algorithm NAIS separate table page 99 Press Return to Enter technical number or press Access to change the algorithm Access Access code _ If login was made with code for level 3 no code is needed Enter code for level 3 4 Access code The digits are replaced digits in the display Change algorithm 000
155. y reset see chapter Alarm reset page 43 Fire alarm The system can handle up to 15360 fire alarms Up to 512 fire alarms will be shown in the c i e display No more fire alarms will be shown until one or more of the 512 alarms are reset See also chapter Alphanumeric display LCD in the control unit page 20 Regarding POINT 999 nn nn 00 29 99 see NOTE at the end of this chapter According to the EN54 2 standard in case of a fire alarm the following will happen e The buzzer in the control unit sounds 0 4 sec each 0 4 sec 0 4 0 4 sec e LEDs Fire L1 are blinking 0 4 0 4 sec e Output for routing equipment Fire brigade tx and outputs type 4 routing equipment are activated e Outputs for fire alarm are activated e Inthe c i e display and ext FBP display the fire alarms are presented as follows Only one alarm point activated in a zone is presented as zone address POINT or LAST Two or more alarm points activated in a zone is presented as zone only ZONE or LAST One alarm point Via Win512 can Point alarm presentation be selected which is a violation to the EN54 2 standard Outputs programmed for General fire alarm and outputs programmed for the activated fire alarm s 3 Plus Alert Annunciation and Ext Presentation units In the old ext FBPs 2425 2426 and 2428 only the ten first fire alarms will be displayed 35 Panasonic Electric Works Fire amp
156. ystem like EBL512 a Service signal is given when it is time to clean or exchange the smoke detectors sensors The alternative is to exchange detectors at even intervals to be on the safe side Change in activities or wrong choice of detector If the activities in the premises are altered the detector choice might also need altering Due to special environments see above an in appropriate detector type might have been chosen from the beginning and thus cause unnecessary alarms Miscellaneous Choosing another type of detector can solve certain problems Bear also in mind that the coverage area can be different for different types of detectors It is however not always the best action to change detector type Here is a list of other actions programmed via Win512 which can be used e Another alarm algorithm can be used e Alarm delay for smoke detectors sensors can be used e Two zone or two unit dependent co incidence fire alarm activation can be used e Inan installation with addressable detectors sensors e g EBL512 the affected detectors can be individually disabled or whole zones when the work is in progress Bear in mind that the smoke spreads and consideration must be taken to adjacent detectors zones Disablements can be done automatically via a time channel built in or external or via menu H2 B1 B3 Automatic re enabling can be used e If there is an alarm organisation for the personnel on site