Home
User Guide - Invertek Drives
Contents
1. INVERTEK DRIVES www invertek co uk OPTIDRIVE HVAC CASCADE EXPANSION MODULE User Guide DECLARATION All rights reserved No part of this User Guide may be reproduced or transmitted in any form or by any means electrical or mechanical including photocopying recording or by any information storage or retrieval system without permission in writing from the publisher Copyright Invertek Drives Ltd 2010 The manufacturer accepts no liability for any consequences resulting from inappropriate negligent or incorrect installation The contents of this User Guide are believed to be correct at the time of printing In the interests of a commitment to a policy of continuous improvement the manufacturer reserves the right to change the specification of the product or its performance or the contents of the User Guide without notice SAFETY This option is specifically designed to be used with the Optidrive HVAC variable speed drive product and is intended for professional incorporation into complete equipment or systems If installed incorrectly it may present a safety hazard The Optidrive HVAC uses high voltages and currents carries a high level of stored electrical energy and is used to control mechanical plant that may cause injury Close attention is required to system design and electrical installation to avoid hazards in either normal operation or in the event of equipment malfunction System design installation commissi
2. e Option Module in its box until required It should be stored in a clean and dry environment Temperature range 40 C to 60 C e Install the Option Module into the Optidrive by inserting the module into the option module port of the Optidrive as shown in the mechanical installation section Do not use undue force in inserting the option module into the port WARNING e Optidrives and the Option Modules should be installed only by qualified electrical persons and in accordance with local and national regulations and codes of practice e Electric shock hazard Disconnect and ISOLATE the Optidrive before attempting any work on it High voltages are present at the terminals and within the drive for up to 10 minutes after disconnection of the electrical supply e Where the electrical supply to the drive is through a plug and socket connector do not disconnect until 10 minutes have elapsed after turning off the supply STANDARDS CONFORMITY An Optidrive fitted with this Option complies with the following standards e CE marked for Low Voltage Directive IEC 664 1 Insulation Coordination within Low Voltage Systems UL 840 Insulation Coordination for electrical equipment EN50081 2 EMC Generic Emissions Standard Industrial Level EN50082 2 EMC Generic Immunity Standard Industrial Level Enclosure ingress protection EN60529 IP00 NEMA 250 Flammability rating according to UL 94 SPECIFICATIONS OPT 2 CASCD IN Optidrive HVAC ODV 2 Optid
3. on is enabled P8 14 1 the relays will assume DOL operation as detailed in the Optidrive HVAC cascade operation section of this manual Default Operation DOL Cascade disabled P8 14 0 Relay 3 Drive Healthy Indication close on Healthy Relay 4 Drive Fault Indication close on fault Relay 5 Drive Running Indication close on enable OPTIDRIVE HVAC PLC LOGIC OPERATION Relays on the HVAC Cascade Expansion module can be assigned functionality within the internal PLC logic programmed via the OptiTools Studio software In order to allow PLC configuration parameter P9 41 must be set to 1 user defined PLC When P9 41 is set to 1 all default operation and cascade operation is automatically disabled and all extended relay function must be programmed through the PLC function See the OptiTools Studio software for further information HVAC CASCADE RELAY CONFIGURATION SUMMARY 0 O Default Operation 1 0 Cascade Operation CONNECTION OF THE CASCADE MODULE TO AN OPTIDRIVE P2 The HVAC Cascade Expansion module can be used with a Optidrive P2 model drive ODP 2 For Optidrive P2 operation the default or PLC defined functionality is available but there is no option to implement Cascade control The table below shows relay configuration summary when the module is connected to an Optidrive P2 P9 41 Function Selected Default Operation PLC logic defined operation Default operation is identical to the Optidri
4. oning and maintenance must be carried out only by personnel who have the necessary training and experience They must read carefully this safety information and the instructions in this Guide and follow all information regarding transport storage installation and use of the Option module including the specified environmental limitations Please read the SAFETY NOTICE carefully and all Warning and Caution boxes elsewhere WARRANTY All Invertek Drives Ltd IDL products carry a 2 year warranty valid from the date of manufacture Complete Warranty Terms and Conditions are available upon request from your IDL Authorized Distributor PartNo 82 OPT 2 CASCD IN Version 1 01 January 2010 gam A O am SGS SAFETY NOTICES WARNING is given where there is a hazard that could lead to injury or death of personnel CAUTION is given where there is a hazard that could lead to damage to equipment It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC legislation of the country of use Within the European Union equipment into which this product is incorporated must comply with 89 336 EEC Electromagnetic Compatibility WARNING Within the European Union all machinery in which this product is used must comply with the Directive 89 392 EEC Safety of Machinery In particular the equipment should comply with EN60204 1 CAUTION e Store the Optidriv
5. rive P2 ODP 2 limited functionality 250V AC 30V DC 6A 250V AC 5A 30V DC 10 C 50 C IP20 UL94V 0 Q Model Number Compatibility Max Relay switching voltage Max Relay switching current Environnemental Conformity 1 Option Module inserted into Optidrive Option Module Port 2 DO NOT use undue force in inserting the option module into the options port 3 Ensure the option module is fitted securely before powering on the Optidrive 4 Remove terminal block header from option module prior to tightening connections Replace when wiring is completed Tighten to Torque setting provided in Specifications Option Module Slot Option Module OPTION MODULE CONTROL TERMINALS Pin Function _ _ _ 1 Relay3Common 2 Relay3Contact_ __ 3 Relay4Common 4 Relay4Contact_ 5 RelayS5Common 6 Relay5Contact_ _ OPTIDRIVE HVAC CASCADE EXPANSION MODULE LED STATUS INDICATION The cascade module has a Status LED LED A Green e LED A Constant Green Indication Modular is OK e LED A Flashing Green Indication No Communication with drive e LED A LED Off Indication No power to module LED B is not used LED A Green OPTIDRIVE HVAC DEFAULT OPERATION The additional relays will assume default configuration whilst the DOL cascade function is disabled Default none cascade functions are listed in the table below Once the DOL cascade functi
6. the configuration is as shown below and a maximum of 3 DOL pumps are permitted Mains Input Supply Cascade Relay Module lt eee eee eee Sensor E Feedback To Drive PID _ avebsauavvdbucstnucndececouwew Master Pump DOL Pump 1 DOL Pump 2 DOL Pump 3 Pump Output Channel For this configuration only parameters P8 14 and P8 15 need be set and the relays in the cascade module are assigned automatically starting with the lowest numbered relay When cascade mode is enabled P8 14 1 the relays contained on the cascade option module are dedicated to the cascade function and can only be used for other functions if P9 41 is set to 1 and relay functions are defined through the PLC logic using the OptiTools Studio software
7. ve HVAC default operation OPTIDRIVE HVAC CASCADE OPERATION The Optidrive HVAC DOL Cascade control uses a maximum of three relays from the cascade option module and the 2 user relay from the standard drive terminals giving the potential for 4 separate pumps under DOL control The cascade option module is required if the system requires more than 1 DOL pump or when the 2 user relay on the drive is required for another function The basic configuration for the drive and DOL pumps is shown below Mains Input Supply Cascade Relay Module iai imaat 00999 lal Isasa iak isian ist Istat x EE Cx ia Relay 2 Output Sensor Relay 3 Output To Drive I Relay 4 Output Relay 5 Output ee ee ee ee ee ee ee ee _ wseeekbee ee eee ee eee eee eee eseeees Master Pump DOL Pump 1 DOL Pump 2 DOL Pump 3 DOL Pump 4 Pump Output Channel In this configuration the 2 drive relay is used to control the first DOL pump with the cascade module controlling the remaining DOL pumps In this configuration P2 18 must be set to 8 to configure the 2 drive relay for DOL pump control P8 14 must be set to enable the DOL cascade function and P8 15 must be set with the number of pumps that make up the cascade system from 1 to 4 The relays in the cascade module are assigned automatically starting with the lowest numbered relay If the 2 relay is not assigned to DOL control then
Download Pdf Manuals
Related Search
Related Contents
Melissa 643-044 User's Manual Samsung LTN1785W User Manual Samsung PS-42S5S User's Manual ESPECIFICACIONES TÉCNICAS ISP1122 USB Hub Demonstration Board User`s Manual Revision 1.01 Samsung Galaxy Tab 4 (7.0) Užívateľská príručka Samsung 941MW Kasutusjuhend User Manual. Xbrand XB-1001-xx User's Manual Copyright © All rights reserved.