INSTALLATION MANUAL - Zeta Alarm Systems
Contents
1. SWITCHES SWITCHES SWITCHES ADDRESS ADDRESS ADDRESS 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 0 N O T U S E D 43 OFF OFF ON OFF ON OFF ON 86 ON OFF OFF ON OFF ON OFF 1 OFF ON ON ON ON ON ON 44 ON ON OFF OFF ON OFF 87 OFF OFF OFF ON OFF ON OFF 2 ON OFF ON ON ON ON ON 45 OFF ON OFF OFF OFF ON 88 ON ON ON OFF OFF OFF 3 OFF OFF ON ON ON ON ON 46 ON OFF OFF OFF ON OFF ON 89 OFF ON ON OFF OFF ON OFF 4 ON ON OF ON ON ON ON 47 OFF OFF OFF OFF ON OFF ON 90 ON OFF ON OFF OFF ON OFF 5 OFF ON OFF ON ON ON ON 48 ON ON ON ON OFF OFF 91 OFF OFF ON OFF OFF ON OFF 6 ON OFF OFF ON ON ON ON 49 OFF ON ON ON OFF OFF ON 92 ON ON OFF OFF OFF ON OFF 7 OFF OFF OFF ON ON ON ON 50 ON OFF ON ON OFF OFF ON 93 OFF ON OFF OFF OFF ON OFF 8 ON ON ON OFF ON ON ON 51 OFF OFF ON ON OFF OFF ON 94 ON OFF OFF OFF OFF ON OFF 9 OFF ON ON OFF ON ON ON 52 ON ON OFF ON OFF OFF 95 OFF OFF OFF OFF OFF ON OFF 10 ON OFF ON OFF ON ON ON 53 OFF ON OFF ON OFF OFF ON 96 ON ON ON ON ON OFF OFF 11 OFF OFF ON OF
2. 46 20 SIANDBY BATTERY REQUIREIVIENTS Aa 49 20 PANEL GcDEVICE CURRENT RATINGS ii PIER DI InME 49 20 2 STANDBY BATTERY CALCULATION ii ia vote scGouaouatcdue wi S ton SEE UR QU RU Sean OS Uode Rl beoe ien eiu mp 49 Doc No GLT MAN 134 PAGE 2 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 SAFETY INFORMATION amp USE OF THIS MANUAL WARNING Read this section completely before commencing installation 1 1 INSTALLATION INFORMATION THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED This equipment must be installed and maintained by a qualified and technically experienced person This C I E must be wired to a fused spur rated at 3A It must NOT be connected via a removable plug or be connected through an RCD device Prior to commencing installation of the control panel ensure that adequate precautions are taken to prevent damage to the sensitive electronic components on the display board and the control board due to electrostatic discharge You should discharge any static electricity you may have accumulated by touching a convenient earthed object such as an unpainted copper radiator pipe You should repeat the process at regular intervals during the installation process especially if you are required to walk over carpets The panel must be located in a clean dry positi
3. Multiple Point Alarm Multiple Zone Alarm NB Multiple Point Alarm 2 points in alarm in the panel causes fire condition NB Multiple Zone Alarm 2 zones in alarm before panel enters fire condition Addr 001 125 General Alarm MCP Alarm Detector Alarm Multiple Point Alarm NB Multiple Point Alarm 2 alarms in a zone before panel enters fire condition General Alarm Point Alarm OUTPUT SELECTION POINT ZONE LOOP PANEL Loop 1 4 Range 001 20 Range 1 4 Delay 000 999 Addr 001 126 Delay 000 999 Delay 000 999 Outputs ON Outputs OFF Sounders ON Sounders OFF Relays ON Relays OFF PCB Sounder One ON PCB Sounder One OFF PCB Sounder Two ON PCB Sounder Two OFF Delay 000 999 Outputs ON Outputs OFF Sounders ON Sounders OFF Relays ON Relays OFF Outputs ON Outputs OFF Sounders ON Sounders OFF Relays ON Relays OFF RMT EVENT Y N RMT EVENT Y N RMT EVENT Y N RMT EVENT Y N ACTIONS MODIFY For each ACTION Cause amp Effect previously selected you can Change Input Selection i e Point Zone Loop Panel etc Change Output Selection i e Point Zone Loop Panel etc Erase one or more previous action Exit to New Modify Doc No GLT MAN 134 Issue 1 33 Author GW NJ Date 14 1 2013 PAGE 45 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 am
4. OFF OFF OFF ON OFF ON ON 66 ON OFF ON ON ON ON OFF 109 OFF ON OFF OFF ON OFF OFF 24 ON ON ON OFF OFF ON ON 67 OFF OFF ON ON ON ON OFF 110 ON OFF OFF OFF ON OFF OFF 25 OFF ON ON OFF OFF ON ON 68 ON ON OFF ON ON ON OFF 111 OFF OFF OFF OFF OFF OFF 26 ON OFF ON OFF OFF ON ON 69 OFF ON OFF ON ON ON OFF 112 ON ON ON ON OFF OFF OFF 27 OFF OFF ON OFF OFF ON ON 70 ON OFF OFF ON ON ON OFF 113 OFF ON ON ON OFF OFF OFF 28 ON ON OFF OFF OFF ON ON 71 OFF OFF OFF ON ON ON OFF 114 ON OFF ON ON OFF OFF OFF 29 OFF ON OFF OFF OFF ON ON 72 ON ON ON OFF ON ON OFF 115 OFF OFF ON ON OFF OFF OFF 30 ON OFF OFF OFF OFF ON ON 73 OFF ON ON OFF ON ON OFF 116 ON ON OFF ON OFF OFF OFF 31 OFF OFF OFF OFF OFF ON ON 74 ON OFF ON OFF ON ON OFF 117 OFF ON OFF ON OFF OFF OFF 32 ON ON ON ON ON OFF ON 75 OFF OFF ON OFF ON ON OFF 118 ON OFF OFF ON OFF OFF OFF 33 OFF ON ON ON ON OFF ON 76 ON ON OFF OFF ON ON OFF 119 OFF OFF OFF ON OFF OFF OFF 34 ON OFF ON ON ON OFF ON 77 OFF ON OFF OFF ON ON OFF 120 ON ON
5. 19 2 1 Power Supply Controller PCB Doc No GLT MAN 134 Issue 1 33 Author GW NJ Date 14 1 2013 PAGE 46 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 Q 22 d Description Doc No GLT MAN 134 PAGE 47 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 19 2 2 CIE Termination PCB Fuses 1 amp 3 are used for the non approved Motherboard charger option Doc No GLT MAN 134 PAGE 48 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL 20 STANDBY BATTERY REQUIREMENTS 20 1 PANEL amp DEVICE CURRENT RATINGS Software Versions PANEL 1 52 amp LOOP CARD 2 0 The Following Table shows the Quiescent Fault amp alarm currents of the main parts of a Premier QUATRO Fire Alarm System PRODUCT MAX MAX DEVICE CODE Q FLT ALM PER PER MA MA MA LOOP SYSTEM Premier Quatro 1 Loop Analogue Addressable Fire Alarm QT 1 37 500 140 140 190 N A 32 Panel Premier Quatro 2 Loop Analogue Addressable Fire Alarm QT 2 37 501 190 190 240 N A 32 Panel Premier Quatro 3 Loop Analogue Addressable Fire Alarm QT 3 37 502 240 240 300 N A 32 Panel Premier Quatro 4 Loop Analogue Addressable Fire Alarm QT 4
6. Points person View event log Turn off delay Configure loops Assign zones Assign Text to each point Installer Modify Alarm Operation Programming K hON amp I 2a Engineer ENNEA ON Se Installer PASSW OTG Configure network if fitted System Diagnostics LED blink loop Autocheck Change passwords Configure RS232 Output if fitted Connect wiring during Install heck during Maint 3b nsta er pen Enone Lock attery check during Maintenance Engineer Reset System fault Update Cause amp Effect programming via USB Authorised Open Enclosure Lock amp PC 4 i Configure Panel protocol Service Engineer Programming Software Care should be taken to ensure that the access method for each level is only available to suitably qualified personnel 1 6 USING THIS MANUAL This manual explains in a step by step manner the procedure for the installation of the Premier Quatro Fire Alarm Control Panel This Installation Manual must not be left accessible to the User 1 7 FIRE ALARM SYSTEMS CODE OF PRACTICE This manual is not designed to teach Fire Alarm System design It is assumed that the System has been designed by a competent person and that the installer has an understanding of Fire Alarm System components and their use We strongly recommend consultation with a suitably qualified competent person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with ou
7. 37 503 300 300 360 N A 32 Panel Zeta Addressable Manual Call Point ZT CP2 AD 1 N A 2 9 125 500 Zeta Addressable Weatherproof Manual Call Point ZT CP2 AD WP 1 N A 2 9 125 500 Zeta Input Unit ZIU 0 9 2 8 2 9 125 500 Zeta Input Output Unit ZIOU 0 9 2 8 10 6 16 64 Zeta Input Output Unit mains switching ZIOU 230 0 9 2 8 19 10 40 Zeta Sounder Control Module ZSCC 0 9 2 8 10 6 16 64 Zeta Sounder Control Module 4 circuits ZSCCA 0 8 1 09 0 8 16 64 Zone Monitor Unit 1 1 08 1 09 1 09 10 40 Zone Monitor Unit 4 zones ZTZM A 1 08 1 09 1 09 10 40 Zeta Loop Powered Door Magnet interface ZTA DH 1 0 3 0 16 6 12 48 Fyreye Extra Addressable Optical Smoke Detector FEAOE2000 0 48 N A 2 3 125 500 Fyreye Extra Addressable Heat Detector FEAHE2000 0 44 N A 2 4 125 500 Fyreye Extra High Temperature Heat Detector FEAHHE2000 0 44 N A 2 4 125 500 Fyreye Extra Addressable Opto Heat Detector FEAOH2000 0 52 N A 2 3 125 500 Zeta Addressable Common Sounder Base ZTA CSB 0 4 N A 4 64 256 Zeta Addressable Common Sounder Flasher Base ZTA CSFIB 0 7 N A 5 5 48 192 Zeta Addressable Maxitone Sounder ZAMT 0 6 N A 12 32 128 Zeta Addressable Maxitone Sounder Flasher ZAMTF 0 6 N A 15 24 96 Zeta Addressable Securetone 2 Sounder ZAS2 R 0 5 N A 4 64 256 Zeta Addressable Securetone 2 Sounder Flasher ZAS2 RFI 0 9 N A 5 5 48 192 Zeta Addressable Remote LED Indicator ZTA LE2 1 5 N A 10 32 128 Zeta Addressable 3 wire Remote LED ZTA LE3 0 N A 10 32 128 Fyreye Addressable Beam Detector
8. ON OFF OFF OFF OFF 35 OFF OFF ON ON ON OFF ON 78 ON OFF OFF OFF ON ON OFF 121 OFF ON OFF OFF OFF OFF 36 ON ON OFF ON ON OFF ON 79 OFF OFF OFF OFF ON OFF 122 ON OFF ON OFF OFF OFF OFF 37 OFF ON OFF ON ON OFF ON 80 ON ON ON ON OFF ON OFF 123 OFF OFF ON OFF OFF OFF OFF 38 ON OFF OFF ON ON OFF ON 81 OFF ON ON ON OFF ON OFF 124 ON ON OFF OFF OFF OFF OFF 39 OFF OFF OFF ON ON OFF ON 82 ON OFF ON ON OFF ON OFF 125 OFF ON OFF OFF OFF OFF OFF 40 ON ON ON OFF ON OFF ON 83 OFF OFF ON ON OFF ON OFF 126 N O T U S E D 41 OF ON ON OFF ON OFF ON 84 ON ON OFF ON OFF ON OFF 127 N O T U S E D 42 ON OFF ON OFF ON OF ON 85 OFF ON OFF ON OFF ON OFF Doc No GLT MAN 134 PAGE 18 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 8 SOUNDERS AND OUTPUTS The Sounders in Sections 8 1 to 8 5 can be directly or indirectly connected to one of the 4 loops on Premier Quatro 8 1 ADDRESSABLE STAND ALONE SOUNDERS This type of sounder takes one of the 125 addresses available on each loop The address is selected via DIP switches 1 to 7 It can be activated individually or in groups related to its zone number
9. detectors AMAXIMUM OF 125 DEVICES CAN BE CONNECTED TO EACH LOOP WITH ADDRESSES 1 TO 125 WHICH CAN OCCUR IN ANY ORDER Address 126 has a special use It is not the address of any physical device but is used for common base sounders see Section 8 Short circuit isolators should be used to prevent losing the whole loop in the event of a single short circuit fault They should be fitted to each zone boundary such that any short circuit will only affect the devices in 1 zone Doc No GLT MAN 134 PAGE 13 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 Pre Commissioning Cable Checks ve in to ve out less than 24 ohms ve in to ve out less than 24 ohms may need to temporarily disable isolators to measure ve to ve greater than 500k ohm ve to Earth greater than 1M ohm ve to Earth greater than 1M ohm ve to ve less than 50 mV pickup on AC DC scales 7 1 SPECIFIC DEVICE WIRING INSTRUCTIONS Fyreye Common Base Fyreye Addressable Detector Relay Base FE CB 80 050 FEA RB 80 080 LOOP IN LOOP OUT LOOP IN LOOP OUT LOOP IN LOOP OUT Fyreye Loop Isolator Base Note that on the Fyreye Loop Isolator Base the loop wiring connects FE IB 80 090 to the terminal block on the PCB and NOT to the Base Spring Screws The terminals are marked amp in and amp out The second ve cont
10. loop number or panel number as determined by the cause and effect programmed An example of this type of sounder is the Zeta Maxitone Addressable Sounder 8 2 ADDRESSED SOUNDER BASE This consists of an addressable sounder in the base of an addressable detector The sounder and detector are set to different addresses i e two devices are located at the same position on a loop but occupy two addresses The correct operation of the dual addressed detector sounder combination requires that DIP switch 8 of the sounder must be ON A Securetone 2 Sounder can be used as an addressed sounder base or with the detector removed as a stand alone addressable sounder 8 3 ASSOCIATED SOUNDER BASE There are 2 types of associated sounder base a This is the same combination of base sounder and detector as in 8 2 above but this time DIP switch 8 is switched OFF and the address of the sounder in the base must be set to be the same as that of the detector In this case the sounder is hidden from the panel as it does not have its own address and the sounder will remain silent until the panel is told of its presence To tell the panel that a detector has an associated sounder follow the commands that configure a detector s remote indicator see Section 11 10 The sounder will now operate when the START SOUNDERS button is pressed or when the corresponding detector s address is part of a cause amp effect output b There is another kind of base so
11. 20 CHARACTERS 22 CHARACTERS ZONE LABEL N A N A 18 CHARACTERS PREALARM PROGRAMMABLE LEVEL PRESET 45 N A PROGRAMMABLE INCLUDING DETECTOR SENSITIVITY DAY NIGHT SENSITIVITY PRESET 55 PRESET 55 ZONE ALLOCATION PROGRAMMABLE SET BY DEVICE ADDRESS PROGRAMMABLE PROGRAMMING FULL PROGRAMMABILITY FULL PROGRAMMABILITY ALARM ONLY EVENT LOG YES 200 EVENTS YES 2048 EVENTS YES 4096 EVENTS Doc No GLT MAN 134 Issue 1 33 Author GW NJ Date 14 1 2013 PAGE 7 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 3 DESIGNING THE SYSTEM The first consideration when designing the fire alarm system is the type or category of fire protection that is required for the building In the UK this is fully explained in the British Standard BS 5839 1 2002 A2 2008 This contains guidance on how many smoke detectors heat detectors call points sounders etc should be fitted for the type of coverage that is required Next decide on the number of loops of addressable devices that need to be installed Quatro can be fitted with 1 to 4 loops The maximum loop capacity is 125 devices also called points or addresses If the building requires more than 4 x 125 devices then the control panels can be networked The network capacity is 64 panels including repeater panels if required All fire alarm systems must be subdivided into zones which represent the geographical areas of the building Quatro all
12. 5 50m ZT 50RA 5 7 9 20 80 Fyreye Addressable Beam Detector 50 100m ZT 100RA 5 7 9 20 80 Conventional Sounders Via 2 Sounder Circuits 450mA per Conv Circuit Zeta Conventional Maxitone Sounder ZMT 8 0 N A 15 N A 60 Zeta Conventional Miditone Sounder ZMD 8 0 N A 15 N A 60 Zeta Conventional Securetone Sounder ZST 8 0 N A 15 N A 60 Zeta Conventional Megatone Sounder ZIDC 0 N A 200 N A 4 Zeta Conventional Flasher ZFL2RR 0 N A 90 N A 10 Zeta Conventional Sounder Flasher ZLT 8RR 0 N A 110 N A 8 Zeta Conventional 6 Bells ZTB6B 24 0 N A 25 N A 36 Zeta Conventional 8 Bells ZTB8B 0 N A 35 N A 25 Conventional Detectors via a Zone Monitor Fyreye Conventional Optical Detector FEO2000 0 06 N A 25 N A N A Fyreye Conventional Heat Detector A1R FEHR2000 0 04 N A 25 N A N A Fyreye Conventional Heat Detector CS FEFH2000 0 04 N A 25 N A N A GSM COMMUNICATOR GSM COM 200 500 500 N A 1 20 2 STANDBY BATTERY CALCULATION In order to calculate the standby battery size required the following formula can be used Battery Size Standby time in Amp Hours 1 25 x Tam X larm Tsay X lap loz Where Taim Maximum time in hours required for the alarm hour is most common time Doc No GLT MAN 134 PAGE 49 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 lALM Total Alarm Current in amps laum 9ND Alarm Current of Sounders in amps Tspy Standby time in hours for
13. OF LOOP DEVICES AND ASSOCIATED EQUIPMENT DEVICE TYPE PRODUCT CODE DEVICE Fyreye Extra Addressable Detectors FEAOE2000 Fyreye Extra Addressable Optical Smoke Detector FEAOH2000 Fyreye Extra Addressable Combined Smoke amp Heat Detector FEAHE2000 Fyreye Extra Addressable Rate of Rise Heat Detector FEAHHE2000 Fyreye Extra Addressable High Temperature Fixed Heat Detector Fyreye Detector Bases FE CB Fyreye Common Base FEA RB Fyreye Addressable Relay Base FE IB Fyreye Addressable Loop Isolator Base FEA SB Fyreye Addressable Sounder Base FEA ISB Fyreye Addressable Isolator Sounder Base Zeta Detector Bases ZTA CSB Zeta Common Sounder Base ZTA CSFIB Zeta Common Combined Sounder amp Flasher Base Beam Detectors ZT 50RA Fyreye Addressable Reflective Beam Smoke Detector 50m ZT 100RA Fyreye Addressable Reflective Beam Smoke Detector 100m Zeta Call Points ZT CP2 AD Zeta Addressable Manual Call Point ZT CP2 AD WP Zeta Addressable Weatherproof Manual Call Point Sounders ZAMT R amp W Zeta Addressable Maxitone Sounder Red amp White ZAMTF R Zeta Addressable Maxitone Combined Sounder amp Flasher Red ZAS2 R amp W Zeta Addressable Securetone 2 Sounder ZAS2 RFI WFI Zeta Addressable Securetone 2 Combined Sounder amp Flasher ZASF RI Zeta Addressable Securetone 2 Flasher Electrical amp Mechanical I
14. Remove any debris from the enclosure Take care not to damage the FACP during installation 5 3 ADDRESSABLE LOOPS amp DEVICE BASES These are covered in more detail in Section 7 At this stage it is important to remember devices e g detectors call points sounders etc should not be fitted to device bases yet if a high voltage Megger type tester is to be used to check for continuity of the loop wiring Doc No GLT MAN 134 PAGE 10 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 6 CONNECTING MAINS amp BATTERY POWER 6 1 CONNECTING THE MAINS POWER Figure 3 Power Supply PCB layout and Mains connection details The panel should be connected to mains supply by a 3A rated spur to the fuse box with 1mm2 to 2 5mm2 3 core cable Nothing else should be connected to this supply The cable should be fire resistant NB It is recommended that the mains cable should pass twice through the ferrite supplied with the panel to improve the panel s immunity to electromagnetic interference The ferrite should be positioned between the mains entry port and the power supply cage The AC Live L Earth E and Neutral N connections are marked on the power supply cage top right of Figure 3 It is essential that the mains Earth cable is connected to the PSU s Earth terminal The incoming mains cable should be kept separate from the loop cables to help mini
15. Software Versions PANEL 1 52 amp LOOP CARD 2 0 Modify Action Number 5 Total Actions 10 Input Panel General Alarm Output Zone Range 1 to 3 with Outputs ON The means that the Output includes a RMT Event The current action i e 0005 can be erased by selecting the Erase command In this case actions 0006 to 0010 will then be automatically re numbered as actions 0005 to 0009 See also the Menu Command Structure in Section 18 Doc No GLT MAN 134 PAGE 40 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 18 MENU COMMAND STRUCTURE This section summarises the complete command structure of the Quatro panel Various functions can be accessed at different levels within the panel the UNRESTRICTED level the CONTROLS ACTIVE level the USER level and the INSTALLER level At the UNRESTRICTED level where the black controls key is switched OFF the basic status of the panel is indicated by its LEDs and alphanumeric display LCD An overview of any fires fault disablement and test condition can all observed at this level An audible warning is also given when a new event occurs With one exception all the keys i e front door buttons are inactive at this level The exception occurs when a delay to the fire alarm outputs Sounders etc has been selected by the installation engineer In this case when a fire alarm is indicated END DE
16. Take great care when lifting and transporting batteries DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the battery Electrolyte is a highly corrosive substance and presents significant danger to yourself and to anything else it touches In case of accidental skin or eye contact flush the affected area with plenty of clean fresh water and seek immediate medical attention Valve Regulated Lead Acid VRLA batteries are low maintenance requiring no electrolyte top up or measurement of specific gravity 1 4 PRODUCT DISPOSAL AT THE END OF ITS WORKING LIFE Like all electronic equipment at the end of its working life this unit should not be disposed of in a refuse bin It should be taken to a local reprocessing site as per the guidelines of the WEEE directive for correct disposal 1 5 EXPLANATION OF ACCESS LEVELS The Premier Quatro System has the following access levels ACCESS LEVEL ACCESSED BY ACCESS METHOD FUNCTIONS ACCESSED View Panel li Defaul 1 General public efault state Override delay if used Doc No GLT MAN 134 PAGE 3 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 Start stop sounders 2a Keyswitch to Silence buzzer person Reset panel Enable disable sections of system Responsible 20 Keyswitch amp user password View Zones
17. circuits a fire relay and a fault relay C NC amp NO All loop devices and panel outputs are fully configurable The cause and effect rules can be set up via the panel or a PC connected to the panel the latter is described in the Software manual Cause amp Effect rules also known as Actions can operate on 4 different levels i e panel loop zone and point For example Quatro can be programmed so that a fire in any zone can activate the sounders in one or more zones Another example is where a fire detected by a point at a specific address connected to one of the 4 loops can result in an output i e sounder or relay being activated in another address on any of the loops Rules that apply specifically to certain types of point devices such as a manual call point or detector can also be programmed Instructions on how to configure the panel are given in Sections 11 and 17 The menu command structure is displayed in Section 18 Doc No GLT MAN 134 PAGE 6 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 2 3 ADVANTAGES OF AN ADDRESSABLE FIRE ALARM SYSTEM The table below lists the main advantages of addressable systems and how our panels use them FEATURE PREMIER AL PREMIER AD PREMIER QUATRO UNIQUE ALARM IDENTIFICATION PANEL LOOP amp ADDRESS LOOP amp ADDRESS PANEL LOOP amp ADDRESS DEVICE LABEL 20 CHARACTERS
18. controls They can only be operated when the key on the front of the panel has been turned clockwise from OFF to CONTROLS ENABLED The CONTROLS ACTIVE LED indicates that the controls have been enabled START STOP SOUNDERS This control can be used by authorised personnel to stop or silence the sounders whilst the panel is in the fire alarm condition This control will alternately stop and start the sounders i e silence and sound the alarms Doc No GLT MAN 134 PAGE 31 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 SILENCE BUZZER This control silences the panel s internal buzzer which is always activated when a fire or a fault has been detected RESET After a fire or false alarm has been fully investigated and dealt with operating this control resets the fire alarm condition The same control is used to reset from a fault condition It is good practice to stop the sounders before resetting the panel However pressing the RESET control whilst the sounders are still active will silence the sounders as well as resetting the fire alarm condition OTHER CONTROLS In addition to the 3 mandatory controls the keypad also provides 12 alphanumeric including ENTER and CANCEL 6 navigational 4 V lt 4 gt v X and 4 menu functions F1 F2 F3 F4 keys Each menu function key corresponds to the function or command label in square brackets which is displ
19. output circuits and a 24V DC auxiliary output each capable of supplying 450mA each fitted with 0 5A fuses The LCD display is 40 x 4 characters It has a set of voltage free fire relay contacts rated at 1A SELV It has a set of voltage free fault relay contacts rated at 1A SELV This relay is normally energised to allow a fault output in the case of total power failure It has the ability to disable any point zone sounder or output It has a one man test mode which resets the zone in test after a few seconds It will operate in ambient temperatures of 5 to 40 C It will operate in a relative humidity of up to 95 non condensing It will withstand vibrations between 5 amp 150 Hz Premier Quatro should be maintained as described in the User Manual Maintenance Guide amp Log Book FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN 54 PART 2 The Premier Quatro fire alarm control panel provides the following mandatory and optional functions as prescribed by the European standard EN 54 Part 2 a Mandatory Functions The mandatory functions and corresponding indications provided by this panel are gt gt gt gt fire alarm fault warning disabled quiescent when the CIE is powered by a power supply conforming to EN 54 4 and no other functional condition is indicated b Optional Functions The options with requirements provided by this panel are A gt gt gt gt output to fire alarm d
20. the system after mains failure normally 24 48 or 72 hr lap Quiescent current in amps of control panel in fault condition because of mains failure IAP Alarm current in amps of control panel IQL Quiescent current in amps of all loop devices Typical Example A system comprises of a 1 Loop Quatro panel with 80 Fyreye Extra Addressable Optical Smoke Detectors 15 Zeta Addressable Manual Call Points 20 Zeta Addressable Securetone 2 Sounders and the required standby is 24 hours It will need to operate in alarm for 2 hour Calculate the battery size required Tam 0 5 Hr laum snp 20 x 0 004 0 08A Tsgy 24 Hr lap 0 20A lap 0 19A la 80 x 0 00044 15 x 0 001 20 x 0 0005 0 0602A lam latm sno lap lar 0 08 0 19 0 0602 0 3302 Therefore using the equation Battery Size Standby time in Amp Hours 1 25 x Tam X lam Tsay X lap Battery Size Standby time in Amp Hours 1 25 x 0 5 x 0 33 24 x 0 20 0 06 Battery Size Standby time in Amp Hours 1 25 x 0 5 x 0 33 24 x 0 26 Battery Size Standby time in Amp Hours 1 25 x 0 165 6 24 Battery Size Standby time in Amp Hours 1 25 x 6 405 Battery Size Standby time in Amp Hours 8 01 Amp Hours For a system like this 2 x 12V sealed lead acid batteries must be used each with a capacity greater than 8 01 Ah For example 12Ah Doc No GLT MAN 134 PAGE 50 Issue 1 33 Author GW NJ Date 14 1 2013 PREMI
21. then there two probable causes Two or more devices may have the same address setting This is referred to as a DOUBLE ADDRESS FAULT If this occurs all devices with the same address will answer at the same time The panel will not be able to understand the answer it receives To find devices with the same address Press any key followed by the Level 2 password default 2222 Select Points then Toggling LED Enter the address which has been set for 2 or more devices This will cause the indicating LEDs for all devices with this address to flash Old Call Points Sounders and some I O units will not be indicated as they have no panel controlled LED to light up An alternative method to find double addresses is to AUTOSEARCH the loop and then select REPORTS This gives a TYPE LOOP REPORT i e the total number of each device type found on the loop which was auto searched Next by selecting ADDRESSES button F3 the device type is displayed at each address from 1 to 125 in groups of 10 Where there is no device present at an address a blank replaces the device type A double address is indicated by DOU There may be some reversed connections to devices they are polarity sensitive The positive core of the loop should be connected to the L2 terminals of the Fyreye detector base and the negative core to the L1 terminals in the base Other devices will have their polarity marked accordingly in their bases 15 3 ZONE FAULTS There are several reaso
22. 2 0 5 MOUNTING THE FIRE ALARM CONTROL PANEL The Premier Quatro comes with many cable entry holes If another entry hole is required it is strongly recommended that the panel door is removed to avoid accidental damage Also the back plate which holds the loop cards and power supply should be removed and stored in a safe place This would also help while fixing the back box to the wall 5 1 PLANNING CABLE ENTRY Fig 2 below shows the location of the cable entries to facilitate planning of wiring to be brought to the panel The grommets can be easily removed by a push from inside the control panel box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230V AC Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting the Mains Power in Section 6 1 5 2 FIXING THE BACK BOX TO THE WALL 485 0 125 0 425 5 4775 Figure 2 Plan view inside the enclosure without PCBs Side view for surface installation Dimensions mm Fix the enclosure to the wall using the three mounting holes provided 2 circular holes near the bottom of the rear face and one keyhole near the top of the rear face Check the build and condition of the wall to decide a suitable screw fixing The mounting holes are designed for No 8 roundhead or countersunk woodscrews or similar
23. AXIMUM LOOP CURRENT IN ALARM 500 mA 400 mA 300 mA 200 mA 1mm CSA cable 500 m 625m 830m 1250m 1 5mm CSA cable 750m 930m 1250 m 1870 m 2 5mm CSA cable 1000 m 1250 m 1660 m 2500 m EG A system with a maximum load of 300mA using 1 5mm cable can have a maximum loop run of 1250 m end to end 7 4 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS amp INTERFACE UNITS The device Address is set with a dip switch on the rear of the device HH NE E E IUE S A The Address setting is binary with the ON position being binary 0 and the OFF position being binary 1 Switch 8 is not used for setting the Quatrodress but sometimes has a device specific function check instructions that came with the device If you are not familiar with binary check the table on page 14 or use the following rule Switch 7 off Add 64 Switch 6 off Add 32 Switch 5 off Add 16 Switch 4 off Add 8 Switch 3 off Add 4 Switch 2 off Add 2 Switch 1 off Add 1 The example shown would be switches 6 4 amp 1 32 8 1 Address 41 Doc No GLT MAN 134 Issue 1 33 Author GW NJ Date 14 1 2013 PAGE 17 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 7 5 DIP SWITCH ADDRESS SETTINGS FULL TABLE
24. Base No extra cabling Individually started Tends to be more expensive Maximum 64 per loop Quiescent current relatively high Uses device address Associated with own address No extra cabling Individually started 4 8 second start amp stop time Uses device address Needs detector present to operate Does not operate during sounder test mode Associated at detector address No extra cabling Doesn t occupy own address Individually started Not monitored Common Sounder Base No extra cabling Doesn t occupy device address Quick start Not monitored Always configured as common sounders Addressable Sounder Circuit Controller Wide range of devices Devices tend to be cheaper Can Add many sounder circuits to system Sounder circuit can be assigned to zone Needs Extra Cabling Needs External PSU Quiescent current high Uses device Address Doc No GLT MAN 134 Issue 1 33 Author GW NJ Date 14 1 2013 PAGE 20 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 8 8 FIRE RELAY VOLTAGE FREE CHANGEOVER CONTACTS m LOOP CARD 1 Figure 6 Connections for fire relay fault relay conventional sounders and auxiliary DC outputs The fire relay R ALARM changes over in any fire condition and can be used for driving local fire fighting equipment such as sprinkler systems magnetic door holders air conditioni
25. CB CONVENTIONAL SOUNDER CIRCUITS The terminations PCB has 2 conventional sounder circuit outputs with a maximum capacity of 450 mA each Please note that conventional sounders should be wired as shown in the diagram below The descriptions of sounders in this section also apply to flashers and combined sounder flashers Doc No GLT MAN 134 PAGE 19 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL ND Note If non polarised alarm devices e g some types of old mechanical bell or a relay are used then a diode will have to be placed in line with the device to enable fault monitoring They may also need a back EMF protection diode Symptoms Chattering sounder relays that don t turn off SND CONNEC IOR HOCK p SND 8 7 ADVANTAGES AND DISADVANTAGES OF DIFFERENT SOUNDER TYPES Software Versions PANEL 1 52 amp LOOP CARD 2 0 4k7 End of Line Resistor I oF ii Ak7 End of Line Resistor Ss SOUNDER TYPE ADVANTAGE DISADVANTAGE Conventional Wide range of devices Devices tend to be cheaper Immediate start stop No quiescent current Needs extra cabling Always configured as common sounders Stand Alone Addressable or Addressed Sounder
26. EN 50200 including the 120 minute survival time of BS 8434 2 Note that all cables should be at least 1mm2 cross section On the Premier Quatro Panel the general recommendation would be to use standard fire resistant cable such as GLT Exports Fire Defence Cable Firetuff FP200 or an equivalent These cables are screened and will provide good EMC shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this fact For non BS5839 installations other cable types may be suitable Depending on the environment the cables may need mechanical protection such as a conduit 4 3 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire resisting 3 core cable Between 1 mm and 2 5mm fed from an isolating double pole switch fused spur fused at 3A IT SHOULD NOT BE CONNECTED THROUGH AN RCD This should be secure from unauthorised operation and be marked FIRE ALARM DO NOT SWITCH OFF The supply must be exclusive to the Fire Panel MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS PROVIDED For information on how to connect Mains to the Panel s Power Supply PCB see Section 6 Also refer to rating information on the mains cover inside the FACP Doc No GLT MAN 134 PAGE 9 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD
27. ER QUATRO INSTALLATION MANUAL Doc No GLT MAN 134 Zeta Alarm Systems by GLT Exports Ltd 72 78 Morfa Road Swansea SA1 2EN 12 0359 CPD 0139 EN54 2 1997 A1 2002 A2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings Premier Quatro QT 1 QT 2 QT 3 QT 4 Provided options Output to fire alarm devices Delays to outputs Fault signals from points Disablement of addressable points Test condition Other Technical Data See Doc Premier Quatro Product file held by the manufacturer Issue 1 33 Author GW NJ Date 14 1 2013 Software Versions PANEL 1 52 amp LOOP CARD 2 0 PAGE 51
28. F ON ON ON 54 ON OFF OFF ON OFF OFF ON 97 OFF ON ON ON ON OFF OFF 12 ON ON OFF OFF ON ON ON 55 OFF OFF OFF ON OFF OFF ON 98 ON OFF ON ON ON OFF OFF 13 OFF ON OFF OFF ON ON ON 56 ON ON ON OFF OFF OFF ON 99 OFF OFF ON ON ON OFF OFF 14 ON OFF OFF OFF ON ON 57 OFF ON ON OFF OFF OFF ON 100 ON ON OFF ON ON OFF OFF 15 OFF OFF OFF OFF ON ON ON 58 ON OFF ON OFF OFF OFF ON 101 OFF ON OFF ON ON OFF OFF 16 ON ON ON ON OFF ON ON 59 OFF OFF ON OFF OFF OFF ON 102 ON OFF OFF ON ON OFF OFF 17 OFF ON ON ON OFF ON ON 60 ON ON OFF OFF OFF OFF 103 OFF OFF OFF ON ON OFF OFF 18 ON OFF ON ON OFF ON ON 61 OFF ON OFF OFF OFF OFF ON 104 ON ON ON OFF ON OFF OFF 19 OFF OFF ON ON OFF ON ON 62 ON OFF OFF OFF OFF OFF 105 OFF ON ON OFF ON OFF OFF 20 ON ON OFF ON OFF ON ON 63 OFF OFF OFF OFF OFF OFF ON 106 ON OFF ON OFF ON OFF OFF 21 OFF ON OFF ON OFF ON ON 64 ON ON ON ON ON ON OFF 107 OFF OFF ON OFF ON OFF OFF 22 ON OFF OFF ON OFF ON ON 65 OFF ON ON ON ON ON OFF 108 ON ON OFF OFF ON OFF OFF 23
29. General and then Installation Name You are now able to enter the site reference name of the panel plus name and telephone number of the installation or maintenance company The site reference name is displayed on the top line of the SYSTEM NORMAL screen on the left hand side The name and phone number of the maintenance company will be alternately displayed with any fault condition of the panel 11 5 CONFIGURING THE LOOPS Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default is 2222 The display changes to the view indicated in the yellow box to the right Select Loop by pressing ENTER or V or B and then Autosearch and choose Loop No 1 and Accept by pressing the F1 key The panel searches the chosen loop After the search has reached 100 the panel displays the number of valid points i e devices Doc No GLT MAN 134 PAGE 26 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 found and the number of double addresses i e points with the same address and the number of addresses that have been modified since the last search Check that the number of VALID devices is the same as the number of devices actually installed on the loop If the panel reports an open or short circuit for a loop select Autocheck This checks the numbe
30. LAY is displayed above key F4 Pressing F4 causes the outputs to be activated immediately At the CONTROLS ACTIVE level the following controls are active START STOP SOUNDERS SILENCE BUZZER RESET the Band Keys to scroll faults and fires the F keys to display faults during a fire alarm and scroll between information on the main screen during disablements and test conditions and the numeric keys to change a password At the USER level the user can also access the information shown below in Section 18 1 by entering his her unique level 1 password Doc No GLT MAN 134 PAGE 41 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 18 1 USER LEVEL LEVEL 1 Default Password 1111 PRIMARY SELECTION SECONDARY SELECTION COMMENT Zones Show Displays zone details Show Enabled Zones Indicates enabled zones Show Disabled Zones Indicates disabled zones Show Test Zones Displays zones in test mode Enable Enables zones in range x to y Disable Disables zones in range x to y Test Zones in range x to y are changed to test mode amp enables disables sounders in zones in test mode Point Show Shows loop address zone type mode analogue value text for each point Show Disabled Points Indicates disabled points Enable Enables points in range x to y Disable Di
31. MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 12 FIRE ALARM 12 1 INDICATIONS A fire is indicated on the Quatro panel by the COMMON FIRE red LED The zonal location of the fire is indicated by one of the zonal indication red LEDs Zonal indication is limited to the first 20 zones of the installation Fires in all zones will be indicated on the LCD An example of the 4 line fire display is shown below Line 1 indicates the first zone in fire In the example the first alarm was in Zone 3 Zone 3 is the Second Floor The 2nd line indicates the most recent zone in fire The format is the same as line 1 The most recent fire occurred in Zone 5 which is the Fourth Floor Line 3 shows the total number of zones in fire and the total number of points devices in fire All the points that are in the fire condition can be displayed in turn by using the lt or keys to scroll through the fires This information is displayed on lines 3 and 4 For example In this example line 3 indicates the 2nd point of the 10 points in fire Point 2 was triggered at the time 08 10 Point 2 is in Zone 17 the Stair Well Point 2 is an Optical detector connected to Panel 2 and Loop 4 Its address is 124 Note that if the device in alarm is connected to one of the loops of the panel which is indicating the fire the panel number is not displayed in line 4 i e Optical 4 124 ROOM 101 12 2 OUTPUTS AND DELAYS Following the indication o
32. ND DATE idv ae EE AA HA 26 LDA CREATING AN INSTALLATION NAE ipie neue enu qi idees edocet br 26 iMm CONFIGURING THE POO PS NET a one ea 26 SEN ILE Se rere ne ne ear eee ere ere rer ce rer cr 27 IT 7sADDRESS EABELS AND ZONE 2 Tro VIEVVIING DEVICE STATUS EA 28 19 LOCATE OR VERIEN Ab S den m 28 LAG TOAREMO TE OUTPUT er tend pues ped 25 TT dT pASSWORDS wai E a EZA 28 11 12 PROTOCOL SELECTION ET 29 TAS IWIISCEELANEOU AI 29 SEZ IIS ALARM zeny UM 31 TA INS e uM e M ME CHE 31 Doc GLT MAN 134 PAGE 1 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 12 2 OUTPUTS AND eine ied ms 31 IZ CIE E 31 ISIS DISAB 33 13d ZONE DISABLEIVMIEIN T 5 5 33 13 2 DEVICE DISABEBIVIENJTG E 33 13 3 SOUNDERDISABLE MEN kii AAA 34 AA n waa 34 TEAM DN 35 TAI WW EP USE MEST IM AA tucson tone
33. NG IHIETEIREXAEABIECODNTROE PANEL eos pelea EIE use SES 10 S I PEANNING CABEESEN TR Vs scare tsb e e oro opm dis duet im o er aa Kaa kausha Ead deas IM LER 10 Sz FIXING THE BAC BOX TO THE WA dace Sitat o je Rin into E E eios x ie c tutu su KA noui i da ese ER td 10 9 ADDRESSABLE LOOPS amp DEVICE BASES 1 gre rit oy leid dtt is 10 6 CONNECTING MAINS Se BATTERY POWER nv pep 11 6 1 CONNECTING THE MAINS POWER ts aE 11 6 2 CONNECTING THE BATTERIES beta det 12 V ADDRESSABELEEOOPAVIRINO AAA AA 13 Z P DEVICE WIRING INSTRUCTIONS Bo exea es elit Eee 14 7 2 LIST OF LOOP DEVICES ANDASSOCIATED ECUIPIVIEIN 14 7 3 MAXIMUM LOOP LENGTH RECOMIVIENDATIO NS ii tee rM NEVER PERRO NEA EUN boo 17 7 4 SETTING THE DEVICE ADDRESS DETECTORS CALL POINTS SOUNDERS amp INTERFACE UNITS eene 17 S SOW NDERS AND OUTPUTS PT ean eats 19 S ADDRESSABLE STAND ALONE SOUNDERS cirrata nn sss exccauig career vac ecient asc cess nua ep E 19 SZ ADDRESSED SOUNDER BASE cinarikan aaae ie webu sagan sou 19 O CIATED SOUNDER BASE opsirni iee n AA KA 19 S4 COMIVION
34. NUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 DOUBLE ADDRES xxx MODIFIED TYPE xxx Reports Optical xxx Heat xxx Opt Heat xxx MCP xxx Zone xxx Sounder xxx Input O xxx lonisat xxx ERROR xxx Addresses Address Map Autocheck Checks from start of loop S amp then end of loop R Displays no of devices seen from each end of loop LED Flash Setup Device LEDs flash every 2s selected per loop Protocol Setup Selects Standard or Mark 2 device protocol Zones Zone edit Edits zone text label amp adds points to zone xxx in loop y AutoAssign points Assigns points to zones automatically 25 devices per zone Add point Adds points to zone xxx in loop y Point Edit Point Displays type mode analog value amp text for each point amp allows text to be edited Platform sounder Operates Remote LED Output or Associated Sounder Base Toggling LED Activates LED selected point Common sounder Configures common sounders ON or OFF for each loop Actions New See Section 18 3 Modify Event Log Faults Event No Date Time Event Panel No Loop No Addr Zone if applicable Text if applicable Alarms Event No Date Time Event Panel No Loop No Addr Zone if applicable Text if applicable Test Event No Date Time Event Panel No Loop No Addr Zone if applicable Text if applicable All Event No Date Time Event Panel No Loop No Addr Zone i
35. No GLT MAN 134 PAGE 27 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 11 8 VIEWING DEVICE STATUS To view the status of any loop device point Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 1 password 1111 is the default Next select Point from the menu followed by Show The information displayed is Loop address zone point type mode analogue value amp text label NB the same parameters are displayed as in Section 11 7 Address Labels and Zones However Level 1 password control does not allow the zone number and address label to be changed For detectors V is usually about 25 for clean air and 55 during alarm Non analogue devices such as call points and I O Units have a normal value of 16 and an alarm value of 64 They will return a value of less than 8 to report a fault condition The text labels displayed for each addressable point are Sounder Input Output lonisation Zone Optical Opt Heat Heat and MCP Each of these is known as the TYPE of a point or device NB Sounder can be a standard loop sounder or a sounder circuit controller for connecting conventional sounders to the loop Zone is an abbreviation for Zone Monitor Unit for interfacing conventional detectors or call points to the loop Opt Heat is a combined optical and heat detector H
36. O INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 disrupt the network It also reports the number of nodes found as well as the Network address of the first and last device on the line Isolated There are no other nodes on the network This would be the situation if the network card is used for the printer output for example Note a STAR topology is not allowed Gateway Network Card The gateway network card also has a screen to configure its TCP IP settings It is accessed by pressing F2 on the Node Setup screen It has options for setting the gateway cards TCP IP address the default gateway address and the subnet mask These should be set up to allow the host PC to communicate with the panel Consult the building network administrator for suitable settings Doc No GLT MAN 134 PAGE 24 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 PAN WARNING LIVE PARTS INSIDE MENU NAVIGATION gt INDICATIONS FAULT SYSTEM SUPPLY FAULT FAULT TEST COM FAULT START STOP SILENCE SOUNDERS SOUNDERS BUZZER CONTROLS Premle 4 LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL EN 54 2 amp EN 54 4 OFF ACCESS ON 10 4 REPEATER PANEL The Repeater Panel is used to remotely indicate the status of the CIE to which it is connected The general fire and fault LED indicatio
37. PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 Premier 7 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL INSTALLATION MANUAL R ALARM SYSTEMS Doc No GLT MAN 134 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 TABLE OF CONTENTS SAFETY INFORMATION TES MANUAL NQI ENDE ree 3 1 INSTAEBATION UNE RWA EOIN iii HAA i cu xp ud ei puta Sud 3 1 2 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL 5 io etie seno porno tho ne pk o Eae no Ene Pre ama Ka ERE Vah 3 13 BATTERY INFORIVIAT ION since is kwania quer Ue RO Ama Ug akawa mU ce sa os A IAA NUN su visa d AA res UA Kahawa 3 14 PRODUCT DISPOSAL AT THE END OF ITS WORKING EIFE deba rs toa Ere leta Cet ebbe eol noeh pun ete cop eran In Ee ne nex en rte Reb tos 3 LS EXPLANATION OP ACCESS LEVEES irirna e se t A Od E 3 1 5 USING EFIS WIANU AD sese ae ERE DIESE on Ia EM Ru QUEM TM Pp DAI p DE and 4 L FIREXAEARIVL SYSTEMS CODE OF PRACTICE as seo deba etd ue tuae t done asp optat duct e RUE Ree 4 LS EQUIPIVIEBULAWARRBAIN TY esa st t uet I ou tI QUEM o Uem deu oe dou eae 4 Zi PREMIER QUALRONOVERVEBUU M MM I EE 5 1 ABOU
38. SOUNDER BASE IA 19 6 ADDRESSABLE SOUNDER CIRCUIT CONTROLLER ate bue ote eo R6 19 8 6 PCB CONVENTIONAL SOU UR Aa 19 8 7 ADVANTAGES AND DISADVANTAGES OF DIFFERENT SOUNDER TYPES petite ten npe rao eate eS 20 8 6 FIRE RELAY VOLTAGE FREE CHANGEOVER CONTACTS i525 ea na 21 8 9 FAULT RELAY VOLTAGE FREE CHANGEOVER CONTACTS 5 1 eeu enter ah Recte ende ru eatur a e ob anaanzia aanzie 21 DIO AURILIARY DC OUTPUT rrari e pen eeu patte iia eu d aou Et E 21 9 PIELDUDEVICE HER MINA enm AA 22 TOL cue RU eu M una AE ENEA 23 LOST RING NE PW Umm 23 10 2 BUS NETWORK etree ees tee peer etree aes ee een er ee t mU EMI RU M M cf 23 LOS CONFIGURING THENETWORR 23 TO ZEE REPEATERGJANBLE ss eset MUR D DERE peut I Ine otn teme niodo b I Pu Hoe PUO Nobb UP Roe D a Sd 25 AAA 26 EIDPOWERING UP IHE PANEL erp on eet rot dut IA nd opt dei on S vente 26 TL2 POWER SUPPLY ec t 26 LIO SETTING TIME A
39. T THE PREMIER QUATRO FIREALARM PANE E 5 FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN 54 PART 2 5 er pret opens REVUE RN ERES ERRSR wa 5 2 2 PANEL DESCRIPTION amp DESIGN CONGEPJ REN TIC DER NR 6 2 3 ADVANTAGES OF AN ADDRESSABLE FIRE ALARM SYSTEM ierat det etait rbd tt rero ted eth tn ex ees Hone n Ene ote n erae rei es 7 S DESIGNING THE SY SIEM anes DAD DA ae 4 FIRST FIX FIRE ALARM CONTROL PANEL CABLE amp 5 9 A EPEOCATING IHEFIREAEARMECONTROEPANE Ls Aaaa 9 4 2 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS Kon rhe 9 4 3 MAINS WIRING RECOMMENDATIONS 9 SOMOURBNTI
40. VICE BASES 4 1 LOCATING THE FIRE ALARM CONTROL PANEL The control panel should be installed in accordance with the following recommendations A The panel should be close to the main entrance of the building so that it can be viewed by any fire fighting personnel entering the building It should be fitted to a sturdy wall that will not flex unnecessarily It should be mounted at eye level in order for it to be viewed without need of a ladder It should be installed in a dry weatherproof place preferably NOT in direct sunlight gt gt gt gt It should be easily accessible so that the responsible person can perform their regular fire alarm checks 4 2 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS All wiring must be installed to meet BS5839 Pt1 2002 A2 2008 and BS 7671 2008 IEE Wiring Regulations standards Other National standards of fire alarm system installation should be adhered to where applicable Screened cables should be used throughout the installation to help shield the Panel from outside interference and ensure EMC compatibility The two categories of cable according to BS5839 Pt1 2002 A2 2008 Clause 26 Fire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation and Servicing are Standard fire resisting cable to PH30 classification of EN 50200 including the 30 minute survival time of Annex E Enhanced fire resisting cable to PH120 classification of
41. act can be used during commissioning to check the loop integrity Connect the in to the spare out Repeat for all isolators Measure ve line resistance with a DVM Return the in cable to its original terminal block when tests completed LOOP IN LOOP OUT Zeta Addressable Common Sounder Base Zeta Manual Call Point Resettable ZTA CSB 42 510 ZT CP3 AD 43 621 Loop In ve Loop In ve LOOP OUT LOOP IN LOOP OUT Doc No GLT MAN 134 PAGE 14 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 Zeta Input Unit Zeta Input Output Unit ZIU 48 100 ZIOU 48 105 LOOP OUT LOOP OUT LOOP OUT LOOP OUT COMPATIBLE WITH ZETA ADDRESGABLE FIRE ALARM SYSTEM Zeta Sounder Controller Circuit Zeta Zone Monitoring Unit ZSCC 48 110 ZTZM A LOOP OUT LOOP OUT LOOP OUT LOOP OUT HE LL COMPATIBLE WITH 1ETA ADORERS IELE COMPATIBLE WITH FIRE ALARM BYETEM ZETA ADDREBBABLE PANELE FIRE ALARM SYSTEM PARE Sab WE BIL XpOrta con MADE IN THE UK Securetone 2 Addressable Sounder ZAS2 R 42 520 NB Flying leads not shown are for connection to detector base when used as base sounder Loop In ve Loop In ve Doc No GLT MAN 134 PAGE 15 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 7 2 LIST
42. anges from SYSTEM NORMAL to ZONES IN TEST as shown In the example line 2 indicates that a total of 2 zones have been disabled and the 1st of these is shown on line 3 Zone 3 003 has the text label THIRD FLOOR The zone no and text label for each disabled zone can be displayed by pressing the control buttons F1 and F2 which correspond to the previous disabled zone and 1 the next disabled zone NOTE that if more than one of the disablement or test conditions described in sections 13 and 14 then the condition displayed on the main screen is dependent on the following order of priority A DISABLED ZONES highest priority A DISABLED POINTS A DISABLED PCB SOUNDER ZONES IN TEST lowest priority The control button F4 labelled NEXT can be used to scroll between these conditions Doc No GLT MAN 134 PAGE 35 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 15 FAULTS All faults are indicated by a flashing yellow LED Faults can be divided into 2 types Faults and Device Faults Device Faults are any fault associated with a particular address on the loop Faults are everything else e g sounder circuits power supply etc 15 1 COMMON FAULT LED This is a general indicator which flashes whenever any type of fault is present 15 2 LOOP CONTENTS FAULT FINDING If the loop contents are different to what was expected
43. ated at the brass earthing strip MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS PROVIDED Doc No GLT MAN 134 PAGE 22 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 10 NETWORKING Up to 64 control panels CIEs and or repeater panels can be connected together i e networked The maximum distance between nodes is 1 km To set up a network of panels each panel must be fitted with a network card The RS485 terminals on the network card are used to connect one or two other panels using the same type of fire resistant cable with which the fire devices are connected to each panel So each panel has one input connector and one output connector The network can be configured with a ring or bus topology 10 1 RING NETWORK In a ring network each control panel is connected to 2 other control panels to form a ring This has the same topology as the loops of addressable devices connected to each CIE This has the advantage that no panels are lost if there is a single break in the network 10 2 BUS NETWORK This is the same as a ring network but wired panel to panel without a return connection from last panel to first panel It could also be referred to as a radial or sour network At the final panel in the network only the input connector is used 10 3 CONFIGURING THE NETWORK There are 2 types of network card available for the Premier Quatr
44. ayed on the bottom line of the LCD immediately above the function key Doc No GLT MAN 134 PAGE 32 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 13 DISABLEMENT To aid commissioning and assist routine maintenance checks various functions of the Quatro fire alarm system can be disabled as described below 13 1 ZONE DISABLEMENT When a zone is disabled the panel will not respond to any fault or fire signals it receives from DETECTORS from that zone This might be used if the system requires routine maintenance and the user needs the rest of the system to continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones Any number of zones can be disabled but it is good practice to only disable one zone at a time A zone can be disabled as follows Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the Level 1 password default 1111 Select Zones then Disable Enter the zone s or range of zones to be disabled Finally select Accept and then Exit When zones have been disabled the General Disablement LED will be lit and also the zonal disablement LEDs in one or both of the columns labelled FAULT DISABLE TEST The zonal disablement LEDs only apply to zones 1 to 20 When one or more zones have b
45. by Powersonic 12V 17 Ah Other makes and sizes of battery may be suitable Calculate the standby requirements to determine the most suitable size of battery Doc No GLT MAN 134 PAGE 12 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 7 ADDRESSABLE LOOP WIRING The Premier Quatro can be fitted with between 1 and 4 addressable loop cards One addressable loop can be connected to each loop card Addressable detectors addressable call points addressable loop powered sounders and several other interface units can be fitted to these loops A MAXIMUM OF 125 ADDRESSES CAN BE CONNECTED TO EACH LOOP We recommend that the first and last devices on a loop have isolator bases fitted Also the last device on each zone should have an isolator fitted This is to prevent a short circuit fault in one zone affecting another zone The screen cable at each end of the loop not shown below must be connected to the loop card s earth terminal S Smoke Detector T Loop Isolator Base H Heat Detector Call Point sj Loop Card Terminals BGU S 7 ND S S R R Figure 5 Example of addressable loop wiring top amp connections to loop cards bottom S S E R R E S S E R R E S S E R R E S S E R R E 2 LOOP CARDS 3 o o A maximum of 64 sounders are permitted on each loop which can be either stand alone sounders or sounders in the bases of
46. ckets on the 3rd line of the display Selecting F3 allows one or more points i e devices to be added to the loop The LCD also indicates the current mode of each zone enabled or disabled 11 7 ADDRESS LABELS AND ZONES Premier Quatro is an addressable panel i e it will indicate the address or location of a fire that has been detected The address number of each point or device on each loop has already been selected according to its DIP switch setting The installation engineer must now assign a label or location for each device e g ROOM 107 A maximum of 20 characters can be used for each label At the same time each point can be allocated to a zone To access the menu for selecting Address Labels Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the Password 2222 Select Points followed by Edit Point For each point the following data can be entered Loop Number Address Number Zone Number amp the Text Label e g ROOM 107 The LCD also indicates the MODE of a point i e ENABLED or DISABLED the analogue value V that the device is sending to the panel and the type Pressing the F keys below and decreases or increases the address number When a fire is detected the address label of the device which has been triggered can be displayed by using the keys Band scroll through the list of fires detected and stored by the panel Doc
47. d Default 2222 Only one level 2 password is permitted by the panel at any time It is essential that the level 2 password is kept secret from the panel users and of course the general public This 4 digit password which the installation engineer can select and edit is required to set up the site configuration of a panel The Level 2 password can be changed as follows Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default is 2222 Press the Wkey until General is highlighted Select General and then Password You are now able to enter the password for the 1st authorised user The LEVEL must be set to 2 see top right corner The current Level 2 password must be entered before it can be changed to a new password 11 12 PROTOCOL SELECTION The Premier Quatro panel is capable of running a number of different protocols Original Zeta protocol Standard which has A 125 addresses per loop 8 basic device types Panel Coded Protocol PC 7 1 which has A 125 addresses per loop A 8 basic device types NOTE A standard device will work with a panel configured as Standard or Panel coded A panel coded device will not run ona standard panel Fyreye protocol The new protocol has A 250 addresses per loop A 256 device types Sounder synchronisation A Plus room for future expansion Note that no more tha
48. dicated by a flashing LED on the OUTPUT DISABLEMENTS FAULTS section of the panel 15 8 OUT OF SERVICE FAULTS If the system is in a condition in which it is unable to detect a fire or sound the alarm for example if a loop is being configured this is indicated to the User by flashing the Out of Service LED 16 EVENT LOGS In order to maintain useful system information the Premier Quatro uses 4 separate event logs All events except Tests are stored in the general log which has a capacity of 4096 events Alarm events and Fault events are also stored in the Alarm log and Fault log respectively The former log can hold up to 512 events and the latter up to 1024 events Using this method ensures that regardless of the most recent entries the last 512 alarms and 1024 faults will always be available Test events are stored in a separate 512 entry log Alarm Log 512 Doc No GLT MAN 134 PAGE 37 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 The screen will show the event number the total no of alarms the date the time the type of device that is in alarm the address of the device in alarm which zone that it is in and its location i e text label A maximum of 512 alarm events can be stored When the alarm log is full the next alarm over writes the first alarm event and so on Fault Log 1024 The screen will show the event number th
49. e total no of alarms the date the time the type of device that is in alarm the address of the device in alarm which zone that it is in and its location i e text label A maximum of 512 alarm events can be stored When the alarm log is full the next alarm over writes the first alarm event and so on All types of faults are stored in this category For a device fault the layout is almost identical to the Alarm log see example For a general fault line 2 is simply a description of the fault and there is no information on line 3 The size of the Fault log is 1024 Test Log 512 This category indicates events that occur to devices contained in zones which are in the test mode The LCD display is identical to that of the Alarm log 512 test events can be stored All Log 4096 This category stores all Alarm and Fault events but not Test events It has a capacity of 4096 Note The Event Logs also known as Reports can be accessed by the Level 1 password default 1111 or the Level 2 password default 2222 The only difference is that with the Level 2 password it is also possible to erase the entire contents of all 4 logs This should NOT be done during the normal use of the panel Doc No GLT MAN 134 PAGE 38 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 17 CAUSE AND EFFECT ACTIONS The Premier Quatro system has very comprehensive Cau
50. eat can either be a fixed temperature heat detector or a high temperature heat detector 11 9 LOCATE OR VERIFY A DEVICE It is possible to send commands to individual devices to turn on their alarm LED This can be a very useful function when one wants to locate a device or verify its address Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default 2222 Select Points followed by Toggling LED Select the loop and address of the point to be checked The and commands can be used to decrement or increment the address of the point being searched for If the device has a panel controlled alarm LED it will be turned on immediately its address is selected Scrolling to another device or exiting the menu will automatically turn the LED off 11 10 REMOTE OUTPUT The remote output on a detector is used to switch on a connected remote indicator LED It is also used to tell the panel that a detector has an associated sounder Also known as a Platform sounder Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default 2222 Select Point followed by Platform sounder Change RMT from No to Yes 11 11 PASSWORDS As described earlier in this section 2 passwords are required to view and set up the configuration on the Quatro panel These are requ
51. een disabled the main screen on the LCD display changes from SYSTEM NORMAL to DISABLED ZONES as shown In the example line 2 indicates that a total of 9 zones have been disabled and the 5th of these is shown on line 3 Zone 1 Z001 has the text label FIRST FLOOR The zone no and text label for each disabled zone can be displayed by pressing the control buttons F1 and F2 which correspond to the previous disabled zone and 1 the next disabled zone Alternatively up to 10 disabled zones without text labels can be displayed in one screen as follows Select any key followed by Level 1 password default 1111 and then Zones followed by Show Disabled Zone Zones are displayed in groups of 10 with the symbol X underneath a zone which has been disabled The next group of 10 zones can be displayed by pressing the symbol The symbol can be used to go back 10 zones To re enable a disabled zone repeat the same procedure used for disabling the zone selecting Enable instead of Disable 13 2 DEVICE DISABLEMENT Rather than disable an entire zone it is often useful to just disable one or more input devices or points detector call point or interface within a zone especially if they are malfunctioning and likely to cause a false alarm or repeatedly indicate a fault To disable a device point follow the same procedure as in Section 13 1 but selecting Point instead of Zone followed by Disable Once a device is disabled the pa
52. evices i e sounders delays to outputs fault signals from points disablement of addressable points test NB the terms device and point are used interchangeably throughout this manual Doc No GLT MAN 134 Issue 1 33 Author GW NJ Date 14 1 2013 PAGE 5 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 2 2 PANEL DESCRIPTION amp DESIGN CONCEPT Top Relays amp lerminations Conventional Sounders PCB F o Block 125 0 LCD Peo Display PCB Mounting Plate 5A PSE Tn Up to 4 oc Loop Cards Key Switch 2 x 17Ah Batteries Door AY USB Ribbon Front Right Connector Cables Figure 1 Plan view of Quatro panel showing internal view of populated enclosure on the right amp inside of hinged door on the left The Premier Quatro panel is an analogue addressable fire alarm control panel designed to EN54 parts 2 amp 4 It is available in 1 2 3 or 4 loop versions Premier Quatro 1 Loop Analogue Addressable Fire Alarm Panel QT 1 37 500 Premier Quatro 2 Loop Analogue Addressable Fire Alarm Panel QT 1 37 501 Premier Quatro 3 Loop Analogue Addressable Fire Alarm Panel QT 1 37 502 Premier Quatro 4 Loop Analogue Addressable Fire Alarm Panel QT 1 37 503 Each loop is capable of driving up to 125 devices All Zeta addressable devices are compatible with the panel In addition to the loop devices Premier Quatro has 2 conventional sounder
53. f a fire the panel will activate outputs i e sounders and or relays according to the cause and effect rules or ACTIONS that have been programmed see Section 17 In certain circumstances the activation of outputs may be delayed whilst the fire is being investigated a Sounder Delays If the operation of sounders has been delayed in one or more of the programmed ACTIONS then this will be indicated by the illumination of the DELAY ON LED in the SOUNDER STATUS section of LEDs When a fire has been indicated the DELAY ON LED remains lit until the longest sounder delay has expired During a fire alarm it is possible to override all the sounder delays at any access level by pressing button F4 which is labelled END DELAY as shown The END DELAY label is erased from the display when either the longest sounder delay has expired or the sounder delay has been overridden by pressing FA b Relay Output Delays Relay outputs can also be delayed via the cause and effect actions In this case no LED is lit to indicate a delay since this type of output is not mandatory NOTE It is possible to toggle delays on amp off via the user menu If the delay is not working as expected check in the user menu if the delays have been turned off If there are delays to sounders the sounder delay LED will be lit when the delays are enabled Delays to relays do not turn on this LED 12 3 CONTROLS The panel contains the following mandatory
54. f applicable Text if applicable Erase Erase Log Yes No General Installation Name Reference Maintenance Phone Language English Espagnol Passwords Level 1 Range xx to xx Password Level 2 Current Password New Password Power supply PSU Charger Motherboard Charger Doc No GLT MAN 134 Issue 1 33 Author GW NJ Check version Date 14 1 2013 Panel s w version amp s w versions of each loop PAGE 43 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 card SW Upgrade Enables an authorised engineer to upgrade the Quatro software using PC software Network Node Setup Address amp Node Type per Panel Also TCP IP settings for Gateway Network card Network Filter All Selective Listen Address of Repeater Panel Node search Finds amp configures all network nodes Printer Real Time Chose if Alarm and or Fault events are printed in real time Print Log Select a date to print events from that date to present day Date Time Date Date amp Time Setup Time Doc No GLT MAN 134 PAGE 44 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL 18 3 CAUSE amp EFFECT ACTIONS NEW See also Section 17 Software Versions PANEL 1 52 amp LOOP CARD 2 0 INPUT SELECTION POINT ZONE LOOP PANEL Loop 1 4 Zone 001 20 Loop 1 4 General Alarm
55. he device will be triggered again and the Alarm sounders will operate for a further 10 seconds Should an Alarm occur on a zone that is not programmed to test the Fire Alarm Panel will operate as normal 14 2 TO PROGRAMME ZONE IN TEST MODE Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the Level 1 password default1111 Select Zones then Test The LCD displays the following Enter the range of zones to be put in to test mode Change No to Yes if you require the Alarm sounders to operate as described in Section 14 1 If the Sounders are not enabled a zone of devices can be tested silently All of the events in 14 1 will occur apart from the sounders turning on and off again after 10 seconds Press Accept Note that this is the SELECT ZONES TO TEST screen It is possible to select more than one zone or range of zones to test So if ENABLE SOUNDER has been changed to Yes the panel registers that those zones will be tested with sounder activation then clears the screen ready for the next entry le the screen will revert to Zone 001 to 001 Enable sounders No when Accept is selected Finally select Exit to leave the Test Zone screen NOTE When Enable Sounders is selected for test mode the panel only operates the sounders in the zone that gives the alarm test When one or more zones are in test mode the main screen on the LCD display ch
56. ired to increase the security of a site configuration a Level 1 or User Passwords Default 1111 Authorised users are allowed to view the panel s configuration status and event logs see section 16 They can also disable section 13 and test section 14 the panel Each authorised user can be assigned his own 4 digit Level 1 password by the installation commissioning engineer The panel permits up to 31 unique level 1 passwords i e up to 31 people can have their own unique access to Level 1 data It is recommended that these passwords are assigned during the commissioning of the panel Changes to these passwords at a later date will require a further site visit by the installation engineer The Level 1 password can be changed as follows Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default is 2222 Press the Wkey until General is highlighted Select General and Doc No GLT MAN 134 PAGE 28 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 then Password You are now able to enter the password for the 1st authorised user The LEVEL must be set to 1 see top right corner In the example the 1st user has been assigned a Password of 4321 There can be up to 31 user numbers each with a unique Password b Level 2 or Installer Passwor
57. mise mains interference Once the mains is connected the panel door should be closed BEFORE turning on the mains power This will protect the installer from the chance of receiving an electric shock MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE PLASTIC GROMMETS PROVIDED It is advisable to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls Doc No GLT MAN 134 PAGE 11 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 6 2 CONNECTING THE BATTERIES SOUNDER DETECTION MAINS CIRCUIT LOOP IN EARTH BAR 2 X 12V VRLA BATTERIES 17 AH MAX Figure 4 Battery location and connection details To calculate the exact requirement use the equation in section 20 STANDBY BATTERY REQUIREMENTS The two batteries are wired in series The ve of one battery is connected to the red battery lead The of the other battery is connected to the black battery lead The ve of the first battery is connected to the ve of the second battery using the link wire supplied The battery leads will be factory fitted to either the 5A PSE or to the motherboard depending upon which version of the panel has been supplied Recommended Battery Types Small Lightly loaded systems Powersonic 12V 7 Ah Heavily loaded systems or systems requiring longer stand
58. n 512 detectors and or call points should be fitted to a single panel in order to comply with EN54 A Fyreye II panel can only run Fyreye II devices Due to the differences in the protocol a Fyreye Mk system can not be configured through the panel to run standard devices But it can be configured to do this via a PC Contact your distributor for further details 11 13 MISCELLANEOUS a LED Flash Setup By selecting this function for a specific loop a device s indicating LED will flash every few seconds b Printer Setup The network card for the Premier Quatro panel has a built in RS232 port This is intended to be linked to a serial printer such as the Epson LQ300 or the Maxatec 1014 The serial port can be configured to print selected events live as they happen or the user can go to the printer menu and choose to reprint events from a certain date The serial port outputs data in 19200 8 n 1 format The printer should be adjusted to this if it is not already its default setting Doc No GLT MAN 134 PAGE 29 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 To investigate how the entire menu command structure of the Quatro panel interlinks refer to Section 18 This illustrates the command structure in a menu tree flowchart of the control keys Doc No GLT MAN 134 PAGE 30 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION
59. ne 1 Multiple alarm means that at least 2 points devices in Zone 1 must be activated before the programmed Effects occur Select Output Category Zone Select Remote RMT Event amp Panel No this is used when the panel being configured e g 0001 is networked to 1 or more other panels e g 0002 causing the outputs of 0002 to operate according to the 0002 panel s configuration when there is a fire in the 0001 panel Select Range Zones 1 3 Select Delay 30 seconds Select Type of O P Switch on all Sounders NB other types of output are Switch off all sounders switch on all outputs switch off all outputs switch on all relays amp switch off all relays The 4 digit number in the top right of each display is the Action Number If more than one action is chosen then ACTION 0001 will be executed first then ACTION 0002 and then ACTION 0003 and so on However because the time taken to perform each action is very small it will appear to user that all actions occur simultaneously Be careful when configuring the panel that there are no unintentional conflicts between the ACTIONS If required it is possible to delay the execution of one or more of the ACTIONS This is done through the output parameter DELAY 000 to 600 seconds ACTIONS can be modified later by selecting Modify from the Actions menu For example Doc No GLT MAN 134 PAGE 39 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL
60. nel ignores any alarms or faults generated by the device If all devices in a zone are disabled the panel will indicate a zone disablement If subsequently one or more devices are re enabled then the zone disablement indication will be automatically cancelled When one or more points have been disabled the main screen on the LCD display changes from SYSTEM NORMAL to DISABLED POINTS as shown In the example line 2 indicates that a total of 5 points have been disabled and the 1st of these is shown on line 3 The 1st disabled device is an MCP which is located on loop 1 at address 97 with the text label ENTRANCE Each disabled point can be displayed by pressing the control buttons F1 and F2 which correspond to the previous disabled point and the next disabled zone Alternatively up to 10 disabled points without indicating device type or address can be displayed on one screen as follows Select any key followed by Level 1 password default 1111 and then Points followed by Show Disabled Points The menu structure is then the same as for zone disablement To re enable a disabled device repeat the same procedure used for disabling the device selecting Enable instead of Disable Doc No GLT MAN 134 PAGE 33 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 13 3 SOUNDER DISABLEMENT On the Quatro Panel all sounders are disabled toge
61. ng shut off auto diallers etc NB In the quiescent condition there is electrical continuity between C and NC In the fire condition there is continuity between C and NO 8 9 FAULT RELAY VOLTAGE FREE CHANGEOVER CONTACTS The fault relay R FAULT is energised in the quiescent condition When any type of fault occurs this is indicated by the fault relay to ensure fail safe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and open when there is a fault This should be taken into account when any device is connected to the fault relay 8 10 AUXILIARY DC OUTPUT This 24V DC output is provided to support low power requirements 450mA max A separate power supply will be required for higher current applications Doc No GLT MAN 134 PAGE 21 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 9 FIELD DEVICE TERMINATION Connect loop Earth Screens to NR Earth Bar m S S ER R Figure 7 Connecting cables to the Quatro panel All cables should enter the enclosure via the cable gland and the cable shields must be connected to the steel EMC cable grounding plate Figure 7 illustrates how the mains cable and an addressable loop cable are connected to the panel Loop cable screens and the mains earth must be connected as shown in Figure 7 All other screens must be termin
62. ns are repeated on the Repeater Panel An alphanumeric display provides further fire fault data The Repeater also has its own control buttons to reset the CIE start the sounders stop the sounders and silence its own internal buzzer For further information about the Repeater Panel and how to connect it and other Quatro CIEs onto the network refer to the Quatro Repeater Panel installation manual GLT MAN 143 Doc No GLT MAN 134 PAGE 25 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 11 INITIAL SET UP 11 1 POWERING UP THE PANEL After the system has been installed and the cabling checked and the Addresses of each device set via its DIP switch connect the 1st loop to loop card 1 the 2nd loop to loop card 2 and so on depending on the number of loops to be connected to the panel maximum of 4 loops Power up the system mains amp batteries After about 10 seconds it will display SYSTEM NORMAL and the date and time as shown and only the green Power LED will be lit After a few seconds the panel will report faults for all unconfigured devices and any other fault disablement test conditions Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light 11 2 POWER SUPPLY Quatro can operate with a power supply which is part of the panel s MOTHERBOARD PCB Alternatively it can operate with a CAGE ty
63. ns for the zone fault LED to light There is a cable break or short circuit to devices in that zone A device has been removed from that zone A device has been changed for one of a different type There is a Double Address in this zone see previous section A device in that zone is communicating a fault condition to the panel with its analogue value A value less than 8 is usually a fault condition This could be a zone monitor reporting a fault in its zone wiring for example 15 4 SUPPLY FAULTS LOSS OF BATTERY POWER OR LOW BATTERY VOLTAGE A Check battery fuse A Check that battery connections are secure A Check battery voltage should be around 26 27V A Check that the two batteries are connected in SERIES to give double the voltage of 1 battery on its own A Check the charger fuse Doc No GLT MAN 134 PAGE 36 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 LOSS OF MAINS POWER A Check mains fuse Check that main power is present A Check charger fuse LOSS OF BATTERY CHARGER A Check charger fuse HIGH INTERNAL RESISTANCE OF BATTERY Replace old batteries with new ones Other possible causes of supply faults are Wrong Charging Voltage The charging voltage should be 27 6V off load at 22 240C If it has been altered reset using potentiometer Overcharged Batteries Remove the batteries and measure the voltage If they are
64. nterfaces ZIU Zeta Input Unit ZIOU Zeta Input Output Unit ZIOU 230 Zeta Input Output Unit mains switching ZSCC Zeta Sounder Control Module ZSCCA Zeta Sounder Control Module 4 circuits ZTZM 1 Zone Monitor Unit ZTZMA Zone Monitor Unit 4 zones ZTA DH Zeta Loop Powered Door Magnet interface Conventional Fire Alarm Devices compatible with ZSCC amp ZSCC A ZMT 8 Zeta Conventional Maxitone Sounder ZMD 8 Zeta Conventional Miditone Sounder ZST 8 Zeta Conventional Securetone Sounder ZIDC 10R Zeta Conventional Megatone Sounder ZFL2RR Zeta Conventional Flasher ZLT 8RR Zeta Conventional Flasher Sounder ZTB6B 24 Zeta Conventional 6 Bells ZTB8B Zeta Conventional 8 Bells Doc No GLT MAN 134 PAGE 16 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL 7 3 MAXIMUM LOOP LENGTH RECOMMENDATIONS Software Versions PANEL 1 52 amp LOOP CARD 2 0 With an addressable system some care must be taken when calculating the appropriate cable gauge for the system The main limitation is that during an alarm condition maximum current draw the voltage at all detectors must be at least 17 Volts with at least 5V of superimposed data signal The exact calculation equations are beyond the scope of this manual because of the distributed loAd of the sounders on the loop but the following table gives a rough guide for maximum cable lengths at various current loads for 3 different cable gauges M
65. o Panel STANDARD NETWORK CARD GATEWAY NETWORK CARD gt 153953 exc 11 H nre a c I us uo ok R ORRA aea 34115304 i gt OS HUU Uzi meet 1111 E UBI aa iN 0000000000 ww SY OOOOOOO The Standard Network card provides an RS485 repeater connection and an RS252 Printer connection The Gateway Network Card has an RS485 repeater connection and a TCP IP Interface for connection to the Datalog Alarm Manager software From the Installer menu select Network There are 3 sub menus Node Setup From here you select whether this node is the controller or just a normal node You also assign a network address Node number There should always be just one controller on the network Network Filter This determines whether this node reports all network events or just those from a specific network address Node search This should be performed from the controller panel The panel configures the network and displays the results The 3 possible configurations are Ring All nodes are connected as a ring Recommended configuration As there are 2 paths to each node the system will tolerate a break in any of the network cables It also reports the number of nodes found Bus The nodes are daisy chained together with no return from the last node to the first Here a single cable break would Doc No GLT MAN 134 PAGE 23 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATR
66. on which is not subject to excessive shock or vibration and at least 2 metres away from pager systems or any other radio transmitting equipment The operating temperature range is 02C to 4096 maximum humidity is 95 HANDLING THE PCBS If the PCBs are to be removed to ease fitting the enclosure and cables care must be taken to avoid damage by static The best method is to wear an earth strap but touching any earth point e g building plumbing will help to discharge any static Always handle PCBs by their sides and avoid touching the legs of any components Keep the PCBs away from damp dirty areas e g in a small cardboard box 1 2 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL NOTE When the Premier M Plus panel is operating normally i e not being tended by service personnel the access door must be closed and locked After locking the key MUST be removed and ONLY held by the responsible person and or the service personnel It must under NO CIRCUMSTANCES be held by the user 1 3 BATTERY INFORMATION This C I E uses 2 x 12V Sealed Lead Acid SLA batteries with capacities between 7Ah and 17Ah CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE DISPOSE OF USED BATTERIES ACCORDING TO BATTERY MANUFACTURERS INSTRUCTIONS IMPORTANT NOTES ON BATTERIES DANGER Batteries are electrically live at all times NEVER short circuit the battery terminals WARNING Batteries are often heavy Each 17Ah battery weighs 6 1kg
67. ows any number of devices to be allocated to a zone However it is assumed that a zone will not contain more than 32 fire detectors and or manual call points since this would correspond to an unacceptably large search area Each panel may be configured to have between 1 and 20 zones Although a fire alarm system has to be subdivided into zones the cause and effect actions applicable to Quatro can be based on other groupings as well as zones The other groupings are panels loops and points Cause and effect is described in the Section 17 In order to gain the maximum benefits from Quatro it is worth considering the types of sounder that can be connected to the system before getting to the cause and effect configuration stage These sounders and their respective advantages disadvantages are explained in Section 8 Whenever possible give each device as descriptive a label as possible The better the description the easier it is to locate in the event of an alarm The panel allows 22 characters It may be necessary to use abbreviations to achieve the required label Keep the design of the system and any changes to it well documented This makes it easier to trace any configuration errors during installation amp commissioning Doc No GLT MAN 134 PAGE 8 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 4 FIRST FIX FIRE ALARM CONTROL PANEL CABLE amp DE
68. p LOOP CARD 2 0 19 PANEL SPECIFICATIONS 19 1 ENCLOSURE SPECIFICATIONS DESCRIPTION ENCLOSURE SIZE L x W x D mm 485 x 477 5 x 125 TOP CABLE ENTRIES BOTTOM CABLE ENTRIES 19 2 ELECTRICAL SPECIFICATIONS ELECTRICAL DESCRIPTION MAINS VOLTAGE BATTERY VOLTAGE POWER SUPPLY CIE DC INPUT VOLTAGE CHARGER VOLTAGE CONVENTIONAL SOUNDER OUTPUT x2 FAULT RELAY OUTPUT x1 CABLE TYPE ALPHA NUMERIC LCD DISPLAY LED INDICATIONS KEY ENTRY ENVIRONMENTAL DATA ENCLOSURE RATING OTHER PORTS VALUE 230 V AC 4 1096 1596 2 x 12V SLA 27 6V DC 20 C 7Ah 17Ah NON INTEGRAL SWITCH MODE DC OUTPUT Vmax 31V Vmin 19V max A 4 1A Ripple Noise lt 0 6V Vmax 31 5V Vmin 19V 27 6V max 450mA Quiescent voltage 5 to 9V DC Active voltage 18 to 28V DC End of Line Resistance 4k7 ohm 0 25W Normally Energised C NO NC Contact rating 30V DC 1A Vmax 32 VDC Vmin 26 V DC 00 mA 25 2 km 44 ohm OO nF 024 64 nodes 1 km Fire Proof 2core screen 1 5mm 40 x 4 characters Fire Fault Disable Test 12 alphanumeric 6 navigational 3 mandatory 4 menu functions F1 F2 F3 F4 Temperature 5 to 40 C Relative Humidity 95 Non Condensing IP 30 USB RS485 via plug in network card TCP IP via plug in network card Zones 1 20 Zones 1 20 EN 54 2 Optional Functions with Requirements 7 8 7 11 8 3 9 5 10 19 2 FUSE SPECIFICATIONS The Premier Quatro Panel has the following Fuses
69. pe PSU see Figure 7 which is fitted as standard next to the motherboard PCB To ensure that the correct fault monitoring is performed the installer must indicate whether the MOTHERBOARD PSU or the CAGE PSU is being used as follows 1 Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default is 2222 Select the option General Press ENTER Select the option Power Supply Toggle between Motherboard Charger and PSU Charger using the Aand Wsymbols until the correct mode is displayed a ph ee Press F1 Accept to accept the selection or F4 Cancel to retain the previous PSU mode 11 3 SETTING TIME AND DATE Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default is 2222 Press the Wkey until Date Time is highlighted Press the ENTER key The date and time can now be entered using the numeric keypad and the directional keys Press F1 Accept to accept a new date and time or F4 Cancel to leave the date time unchanged Press Cancel or Until the screen shows SYSTEM NORMAL or FAULT 11 4 CREATING AN INSTALLATION NAME Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default is 2222 Press the Wkey until General is highlighted Select
70. r instructions and the relevant National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 1 2002 A2 2008 Fire Detection and Alarm Systems for buildings Code of Practice for System Design Installation commissioning and maintenance available from the BSI or at your local reference library 1 8 EQUIPMENT WARRANTY If this equipment is not fitted and commissioned according to our guidelines and the relevant National Standards by an approved and competent person or organisation the warranty may become void Doc No GLT MAN 134 PAGE 4 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL 2 PREMIER QUATRO OVERVIEW 2 1 ABOUT THE PREMIER QUATRO FIRE ALARM PANEL Software Versions PANEL 1 52 amp LOOP CARD 2 0 A The Premier Quatro fire alarm control panel is a 4 loop 20 zone analogue addressable Fire Alarm Control Panel with 125 devices per loop It can support a 64 panel network control panels and repeater panels Sounders strobes relays and isolators can be combined at the same address as smoke detectors heat detectors or combined smoke heat detectors The PSE is a switch mode power supply with a total rated output current of 5A with a max output whilst charging of 4 1A Quatro supports all Zeta addressable devices The maximum loop length is 2km It has 2 conventional sounder
71. r of points found when the loop is checked from the start of the loop S and then checked from the end of the loop R The Start and Return values indicate the position of the loop fault from each end of the loop Loop 1 is now configured Press Accept and then repeat the operations above for the remainder of the loops fitted to the panel Press Accept then Cancel then the Key until the screen either shows SYSTEM NORMAL or FAULT The panel will now function as a basic system 11 6 ZONE LABELS The subdivision of a fire alarm system was explained in Section 3 the Premier Quatro panel being capable of assigning 20 zones When a fire is enunciated the zone number in which the fire is located is indicated on the alphanumeric display In addition to its numerical description a zone can be identified by a text label e g 3rd floor west ext If the installer associates a text label with each zone of a fire alarm system this will be displayed on the LCD when a fire is detected The maximum length of the zone text label is 18 characters To access the menu for selecting Zone Labels Turn the keyswitch clockwise to the Controls Enabled Position The controls Active LED will light Press any key followed by the level 2 password default is 2222 Select Zone edit and then the zone number by either using the alphanumeric keypad or the function keys F1 and F2 to increment or decrement the zone number Type in the text label between the bra
72. reading over 27 6 V then the batteries are overcharged Try to run the panel on batteries only for half an hour or so to try to discharge the batteries If this doesn t solve the problem replacement batteries will be required 15 5 EARTH FAULTS An EARTH fault indicates that something is shorting to earth usually through the cable screen Disconnect the earth screens one at a time to determine the problem line Note connecting other equipment e g an oscilloscope to the panel can give an earth fault The earth fault message will indicate if it is a Positive or Negative voltage shorting to earth DO NOT DISCONNECT THE MAINS EARTH CONNECTION THIS WILL CAUSE A PROBLEM WITH THE PANELS OPERATION 15 6 SYSTEM FAULT A system fault is an abnormal microprocessor running condition due to various unexpected phenomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and internal fault buzzer will be constantly active A system fault indication can be cleared by momentarily closing jumper link JP20 on the display card to the right of the coin battery If the fault does not clear please consult your distributor 15 7 SOUNDER FAULTS Faults on the two conventional sounder circuits connected to the Terminations PCB and addressable sounders connected to the loops are indicated on the LCD display Conventional sounder circuit faults are also in
73. s te toms bb Ruane vu nN abana 35 T4 2 TO PROGRAMME ZONE IN TEST MODE a M P qued pet hop ed RI 35 De NIE e M 36 ISCO MMEONA UE ED S atten eda eeu pa t oom etre pute Dua been ra ute aite a HAE 36 15 2 tOOP CONTENTS t ed e bas veas Cbr E buo ed blue Cor 36 D3 ZO FA UL 36 I5 dL oOUPPEPTEAUEESS d da 36 eee ee 3 15 5 S YS WEI EAU 3 15 7 SOUNDER FAULTS ata ee ae ae a eee ee 37 15 3 OUT OF SER VICE FAULTS ia menue KA eae eee en Oe 37 ads 3 T CAUSE AND EE RECT ACTIONS sums A 39 18 MENU COMMAND STRUCTURE EM 41 IS USER LEVEE LEVEE T AAA 42 18 DINSTALLER EEVELAEBVELE UA 42 1 NO NA WAA 46 ES TI ENCLOSURE SPECIFICATIONS aa aa r AA WA AA WAA NA UNA ANA ERNA 46 TI 2 ELECTRICAL S PE eoi eaten ea 46 T9 2 FUSE SPECIEICATIOTNS iii shee
74. sables points in range x to y Relays Enable All Enables all relays Disable All Disables all relays Enable by Zone Enables relays in zones x to y Disable by Zone Disables relays in zones x to y PCB outputs Enable Disable Alarm relay and or Fault relay on Terminations PCB Show Shows the number of Enabled amp Disabled Relays Sounders Enable All Enables all sounders Disable All Disables all sounders Show Shows the number of Sounders Event Log Faults Event No Date Time Event Panel No Loop No Addr Zone if applicable Text if applicable Alarms Event No Date Time Event Panel No Loop No Addr Zone if applicable Text if applicable Test Event No Date Time Event Panel No Loop No Addr Zone if applicable Text if applicable All Event No Date Time Event Panel No Loop No Addr Zone if applicable Text if applicable Delays Delay On Off Switches delay on off which has been selected at AL3 Test LED amp LCD All LEDs and LCD pixels active Buzzer activated The installation engineer has to access the information in Section 18 2 by entering the unique level 2 password 18 2 INSTALLER LEVEL LEVEL 2 Default Password 2222 PRIMARY SELECTION SECONDARY SELECTION TERTIARY SELECTION OR COMMENT Loop Autosearch Searches for all devices on specified loop amp displays VALID xxx Doc No GLT MAN 134 PAGE 42 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MA
75. se and Effect capabilities known in the panel menu as Actions The Default factory configuration is that any alarm will activate all outputs on the panel Like most addressable systems the panel allows comprehensive programming of the sounder outputs It is the responsibility of the commissioning engineer to verify that the programmed panel actions operate the sounders as required Any input or cause can generate any output or effect For example if the input is a fire in zone 1 e g an optical detector triggered by smoke the system can be programmed to generate output s e g operate one or more sounders or relay outputs in one or more zones The inputs and outputs can be selected from 4 categories Point Zone Loop amp Panel Example of Selecting a Cause amp Effect New Action The following example shows ACTION No 5 top right of LCD being selected A fire input in Zone 1 is programmed to have the effect of activating the sounders in Zones 1 2 and 3 In addition the activation of the sounders is delayed by 30 seconds after the fire has been detected Select Input Category Zone Select Range of Zones 001 Select Type of Input General Alarm NB General Alarm means detector alarm MCP alarm or multiple alarm By selecting More the operator can choose from one of these 3 For example if MCP alarm is chosen the Cause amp Effect will only apply to an MCP alarm in Zone 1 and will ignore detector alarms in Zo
76. ther through the User Menu This affects The conventional sounder circuits loop sounders and any Platform hidden sounders When the sounders have been disabled the Sounders Output Disablements LED will light up The LCD will show a list of all the sounders showing that they are disabled It also shows both of the conventional sounder circuits are disabled on the screen on the LCD 13 4 RELAY DISABLEMENT Relay outputs can also be disabled These can either be addressable output units on any of the loops or a PCB output relay ALARM or FAULT Doc No GLT MAN 134 PAGE 34 Issue 1 33 Author GW NJ Date 14 1 2013 PREMIER QUATRO INSTALLATION MANUAL Software Versions PANEL 1 52 amp LOOP CARD 2 0 TEST MODE 14 1 WHY USE TEST MODE To aid commissioning and assist routine maintenance check a non latching one man test facility is available When a detector manual call point or input unit is triggered on any zone in Test the Alarm sounders operate for approximately 10 seconds on and then switch off The triggered device is automatically reset The panel will enter the fire condition and indicate the address of the fire The panel automatically resets from the fire condition at the same time as the triggered device but the LCD indication remains until the panel is manually reset If the device is still in the fire condition e g MCP still activated or the analogue value of a detector still above the alarm threshold t
77. under which interfaces with a conventional detector This is called the Securetone Micro Addressable Sounder It contains DIP switches to set its address and a jumper connector which can be set to either the smoke detector position or the heat detector position depending on the type of conventional detector which is connected When the detector is triggered the panel indicates a fire at the address allocated to the sounder and displays the type of detector at this address As with 8 3 a the sounder will not operate unless the remote output is configured 8 4 COMMON SOUNDER BASE The common sounder base is connected to an addressable detector but does not take the detector s address Common sounders are allocated an address of 126 and are placed in Zone 1 So if the panel is configured to turn on Zone 1 outputs during an alarm all common sounders will be activated There is also a Loop Common Sounder option Instead of common sounders on all loops being activated as above it is possible to select individual loops for common sounder operation If switched off the common sounders on that loop will not sound during an alarm see also Section 18 2 8 5 ADDRESSABLE SOUNDER CIRCUIT CONTROLLER The Zeta addressable sounder circuit controllers ZSCC amp ZSCC 4 can be used to connect one or four conventional sounder circuits respectively to one address on the loop It needs external power to be supplied from a suitable 24 V power supply 8 6 P